aire haier

48
SERVICE MANUAL Air Conditioners CAUTION READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE . MODEL: HSU-09C13 THIS MANUAL IS USED BY QUALIFIED APPLIANCE TECHNICIANS ONLY. HAIER DOES NOT ASSUME ANY RESPONSIBILITY FOR PROPERTY DAMAGE OR PERSONAL INJURY FOR IMPROPER SERVICE PROCEDURES DONE BY ONE UNQUALIFIED PERSON. Air Conditioner Edition:2006/01/09 REVISION 0 MODEL: HSU-12C13 MODEL: HSU-22C13 MODEL: HSU-18C13

Transcript of aire haier

Page 1: aire haier

SERVICE MANUAL

Air Conditioners

CAUTION

READ THIS MANUAL CAREFULLY TO

DIAGNOSE TROUBLE CORRECTLY

BEFORE OFFERING SERVICE .

MODEL: HSU-09C13

THIS MANUAL IS USED BY

QUALIFIED APPLIANCE

TECHNICIANS ONLY. HAIER

DOES NOT ASSUME ANY

RESPONSIBILITY FOR PROPERTY

DAMAGE OR PERSONAL INJURY

FOR IMPROPER SERVICE

PROCEDURES DONE BY ONE

UNQUALIFIED PERSON.

Air Conditioner Edition:2006/01/09

REVISION 0

MODEL: HSU-12C13

MODEL: HSU-22C13

MODEL: HSU-18C13

Page 2: aire haier

IMPORTANT INFORMATION

Features

Comfortable: wide-angle airflow

Wide variety of functions

quiet operation

Main Specification

Cooling Capacity 2600W

Rated Power/Current(cooling) 960W/4.5A

EER: 2.71

Air Conditioner Edition:2006/01/09

Air Volume(Indoor/outdoor):420m3/h

Power: 1PH 220V~ 60 Hz

Model:HSU-09C13

Air Volume(Indoor/outdoor):540m3/h

Power: 1PH 220V~ 60 Hz

Model:HSU-12C13

Rated Power/Current(cooling):1250W/5.8A

EER:2.80

Cooling Capacity:3500W

Air Volume(Indoor/outdoor):700m3/h

Power: 1PH 220V~ 60 Hz

Model:HSU-18C13

Rated Power/Current(cooling):1700W/7.9A

EER:2.94

Cooling Capacity:5000W

Air Volume(Indoor/outdoor):700m3/h

Power: 1PH 220V~ 60 Hz

Model:HSU-22C13

Rated Power/Current(cooling):2200W/10.4A

EER:2.73

Cooling Capacity:6000W

HSU-09/12C13

HSU-22C13

HSU-18C13

Page 3: aire haier

Air Conditioner Edition:2006/01/09

Safety Information

General Information

This Service Manual describes the operation,disassembly,troubleshooting,and repair of Haier Room Air

Conditioners,etc. It is intended for use by authorized servicers who troubleshoot and repair these units.

NOTE:It is assumed that users of this manual are familiar with the use of tools and equipment used to

troubleshoot and repair electrical,mechanical,and refrigeration systems;and understand the terminology

used to describe and discuss them.

Haier urges you read and follow all safety precautions and warnings contained in this manual. Failure

to comply with safety information may result in severe personal injury or death.

Related Publications

This is a base service manual,covering a range of similar models.It is intended to be used in

conjunction with the Parts Manual and Technical Sheet covering specific model being serviced.

General Precautions and Warnings

WARNING

To avoid risk of personal injury or death due to electrical shock,disconnect electrical power to unit

before attempting to service the unit.

WARNING

To avoid risk of personal injury or death due to electrical shock,DO NOT,under any circumstances,alter

the grounding plug .Air conditioner must be grounded at all times.Do not remove warning tag from power

cord.If a two-prong (non-grounding) wall receptacle is encountered,contact a qualified electrician and

have the receptacle replaced with a properly grounder wall receptacle in accordance with the National

Electrical Code.

WARNING

To avoid risk of personal injury or death due to electrical shock,grounding wires and wires colored like

grounding wires are NOT to be used as current carrying conductors.The standard accepted color coding

for ground wires is green or green with a yellow stripe.Electrical components such as the compressor

and fan motor are grounded through an individual wire attached to the electrical component and to

another part of the air conditioner.Grounding wires should not to be removed from individual components

while servicing,unless the component is to be removed and replaced.It is extremely important to replace

all removed grounding wires before completing service.

WARNING

To avoid risk of heat exposure,which may cause death or severe illness,air conditioner must be

monitored when malfunctions or shuts down.

Page 4: aire haier

Air Conditioner Edition: 2006/01/09

CONTENTS

1.SPECIFICATION...............................................................................1

2.

3.

OPERATION.....................................................................................6

4.

ELECTRICAL CONTROL................................................................21

5.

TROUBLE SHOOTING...................................................................29

6.

INSTALLATION...............................................................................31

CIRCUIT AND WIRING DIAGRAM................................................40

Page 5: aire haier

Air Conditioner Edition:2006/01/09

SPECIFICATION

1

Page 6: aire haier

Model HSU-09C13 Brand Mark -----

Cooling Capacity 2600 W Frequency Range

Rated Power/Current 960 W/4.5 A Power 1PH 220V~ 60 Hz

Max Power/Current 1250W/6.4A Cooling

EER 2.71 Model×Sectional Area

--------

Heating Capacity: -----------

Power Cord

Refer. No. --------

Rated Power/Current: -----------Compressor

manufacturer/Type

Max Power/Current: --------------

Heating

COP ------

Compressor

Oil charge

Power/Current of

Electric Heating----- Type/Net Charge R22 570g

Operating temp. range 18OC-43OC

Additional Charge for

exhausting air. 50 g

H 1150 r/min

Refrigerant

Charge if over Standrad

Pipe Lenth 16g/m

M 1100 r/min Lenth×Internal/External

Diametre

Indoor

Velocity

L 920 r/min

Capilary

Refer No. 0010707509

H 950 r/min Indoor 1.35 mm H ---- r/min

Height of rising

radiator slice Outdoor 1.50 mm

H ---- r/min Net 7.2kg

Outdoor

Velocity Indoor Weight

Gross 10.2kg

Net 24kg

Indoor 420 m3/hOutdoor Weight

Gross 28kg

Air

Volume

(High) Outdoor ----- m3/h Indoor Dimension(L×W×H) 795x182x265 mm

Capacitor of Fan Motor …… Indoor Packaging Dimension(L×W×H) 863x277x339 mm

Class of electric Shock Protection Outdoor Dimension (L×W×H) 745x315x428 mm

Class of Water Proof IP 24 Outdoor Packaging dimension(L×W×H) 843x359 x515 mm

Moisture Removal 1.2×10-3m3/h liquid /Gas pipe Diametre 6.35/9.52 mm

Model: YL-H03 or YL-M05 standard Lenth 5 mRemote

Controller Refer. No. -----

Refrigerant

Pipe Max Lenth 7 m

Remote Controller Bracket ----- Lenth/Diametre of Drain Hose 1.0 m

Appearance ----- Max. pressure at warm side 2.65 MPa

Climate Type T1 Max.pressure at cool side ---

Installation Bracket Type ----- Plug Type(spec.) ---

Area available for clooling/heating 12-18 m2 Ammeter spec. ---

Dry/Wet ball(indoor) 32 / 23 Dry/Wet ball(indoor) 20 /--Max.running

temperature(cooling): Dry/Wet ball(outdoor) 43 / 26

Max.running

temperature(heating): Dry/Wet ball(outdoor) 2 / 1

Air Conditioner Edition:2006/01/09

Rechi/44R212AE-FJS

270CC

2.7x1.2x680

2

Page 7: aire haier

Model HSU-12C13 Brand Mark -----

Cooling Capacity 3500 W Frequency Range

Rated Power/Current 1250 W/5.8 A Power 1PH 220V~ 60 Hz

Max Power/Current: 1650W/8.5A Cooling

EER 2.80 Model×Sectional Area

--------

Heating Capacity: -----------

Power Cord

Refer. No. --------

Rated Power/Current: -----------Compressor

manufacturer/Type

Max Power/Current: --------------

Heating

COP ------

Compressor

Oil charge

Power/Current of

Electric Heating----- Type/Net Charge R22 850g

Operating temp. range 18OC-43OC

Additional Charge for

exhausting air. 50 g

H 1290 r/min

Refrigerant

Charge if over Standrad

Pipe Lenth 16g/m

M 1100 r/min Lenth×Internal/External

Diametre

Indoor

Velocity

L 1000 r/min

Capilary

Refer No. 0010707503

H 950 r/min Indoor 1.35 mm H ---- r/min

Height of rising

radiator slice Outdoor 1.45 mm

H ---- r/min Net 7.6kg

Outdoor

Velocity Indoor Weight

Gross 10.6kg

Net 26kg

Indoor 540 m3/hOutdoor Weight

Gross 30kg

Air

Volume

(High) Outdoor ----- m3/h Indoor Dimension(L×W×H) 795x182x265 mm

Capacitor of Fan Motor …… Indoor Packaging Dimension(L×W×H) 863x277x339 mm

Class of electric Shock Protection Outdoor Dimension (L×W×H) 745x315x428 mm

Class of Water Proof IP 24 Outdoor Packaging dimension(L×W×H) 843x359 x515 mm

Moisture Removal 1.5×10-3m3/h liquid /Gas pipe Diametre 6.35/12.7 mm

Model: YL-H03 or YL-M05 standard Lenth 5 mRemote

Controller Refer. No. -----

Refrigerant

Pipe Max Lenth 10 m

Remote Controller Bracket ----- Lenth/Diametre of Drain Hose 1.0 m

Appearance ----- Max. pressure at warm side 2.65 MPa

Climate Type T1 Max.pressure at cool side ---

Installation Bracket Type ----- Plug Type(spec.) ---

Area available for clooling/heating 15-24 m2 Ammeter spec. ---

Dry/Wet ball(indoor) 32 / 23 Dry/Wet ball(indoor) 20 /--Max.running

temperature(cooling): Dry/Wet ball(outdoor) 43 / 26

Max.running

temperature(heating): Dry/Wet ball(outdoor) 2 / 1

Air Conditioner Edition:2006/01/09

Rechi/44R292AG-JESC

270CC

2.7x1.4x650

3

Page 8: aire haier

Model HSU-18C13 Brand Mark -----

Cooling Capacity 5000 W Frequency Range

Rated Power/Current 1700 W/7.9 A Power 1PH 220V~ 60 Hz

Max Power/Current: 2300W/11.8A Cooling

EER 2.94 Model×Sectional Area

--------

Heating Capacity: -----------

Power Cord

Refer. No. --------

Rated Power/Current: -----------Compressor

manufacturer/Type

Max Power/Current: --------------

Heating

COP ------

Compressor

Oil charge

Power/Current of

Electric Heating----- Type/Net Charge R22 910g

Operating temp. range 18OC-43OC

Additional Charge for

exhausting air. 50 g

H 1350 r/min

Refrigerant

Charge if over Standrad

Pipe Lenth 16g/m

M 1260 r/min Lenth×Internal/External

Diametre

Indoor

Velocity

L: 1150 r/min

Capilary

Refer No. 0010707496

H 760 r/min Indoor 1.30 mm H ---- r/min

Height of rising

radiator slice Outdoor 1.40 mm

H ---- r/min Net 11kg

Outdoor

Velocity Indoor Weight

Gross 14kg

Net 24kg

Indoor 700 m3/hOutdoor Weight

Gross 28kg

Air

Volume

(High) Outdoor ----- m3/h Indoor Dimension(L×W×H) 938x182x265 mm

Capacitor of Fan Motor …… Indoor Packaging Dimension(L×W×H) 1005x277x339 mm

Class of electric Shock Protection Outdoor Dimension (L×W×H) 833x286x540 mm

Class of Water Proof IP 24 Outdoor Packaging dimension(L×W×H) 932x342 x619 mm

Moisture Removal 2.0×10-3m3/h liquid /Gas pipe Diametre 6.35/12.7 mm

Model: YL-H03 or YL-M05 standard Lenth 5 mRemote

Controller Refer. No. -----

Refrigerant

Pipe Max Lenth 10 m

Remote Controller Bracket ----- Lenth/Diametre of Drain Hose 1.0 m

Appearance ----- Max. pressure at warm side 2.65 MPa

Climate Type T1 Max.pressure at cool side ---

Installation Bracket Type ----- Plug Type(spec.) ---

Area available for clooling/heating 22-34 m2 Ammeter spec. ---

Dry/Wet ball(indoor) 32 / 23 Dry/Wet ball(indoor) 20 /--Max.running

temperature(cooling): Dry/Wet ball(outdoor) 43 / 26

Max.running

temperature(heating): Dry/Wet ball(outdoor) 2 / 1

Air Conditioner Edition:2006/01/09

Rechi/48R442AL-51SF

410CC

3.0x1.8x650

4

Page 9: aire haier

Model HSU-22C13 Brand Mark -----

Cooling Capacity 6000 W Frequency Range

Rated Power/Current 2200 W/10.4 A Power 1PH 220V~ 60 Hz

Max Power/Current 2800W/13.4A Cooling

EER 2.73 Model×Sectional Area

--------

Heating Capacity: -----------

Power Cord

Refer. No. --------

Rated Power/Current: -----------Compressor

manufacturer/Type

Max Power/Current: --------------

Heating

COP ------

Compressor

Oil charge

Power/Current of

Electric Heating----- Type/Net Charge R22 1850g

Operating temp. range 18OC-43OC

Additional Charge for

exhausting air. 80 g

H 1350 r/min

Refrigerant

Charge if over Standrad

Pipe Lenth 20g/m

M 1260 r/min Lenth×Internal/External

Diametre

Indoor

Velocity

L 1150 r/min

Capilary

Refer No. 0010707707

H 760 r/min Indoor 1.35 mm H ---- r/min

Height of rising

radiator slice Outdoor 1.40 mm

H ---- r/min Net 11kg

Outdoor

Velocity Indoor Weight

Gross 14kg

Net 47kg

Indoor 700 m3/hOutdoor Weight

Gross 51kg

Air

Volume

(High) Outdoor ----- m3/h Indoor Dimension(L×W×H) 938x182x265 mm

Capacitor of Fan Motor …… Indoor Packaging Dimension(L×W×H) 1005x277x339 mm

Class of electric Shock Protection Outdoor Dimension (L×W×H) 810x288x680 mm

Class of Water Proof IP 24 Outdoor Packaging dimension(L×W×H) 946x425 x755 mm

Moisture Removal 2.4×10-3m3/h liquid /Gas pipe Diametre 9.52/15.88 mm

Model: YL-H03 or YL-M05 standard Lenth 5 mRemote

Controller Refer. No. -----

Refrigerant

Pipe Max Lenth 15 m

Remote Controller Bracket ----- Lenth/Diametre of Drain Hose 1.0 m

Appearance ----- Max. pressure at warm side 2.65 MPa

Climate Type T1 Max.pressure at cool side ---

Installation Bracket Type ----- Plug Type(spec.) ---

Area available for clooling/heating 28-46 m2 Ammeter spec. ---

Dry/Wet ball(indoor) 32 / 23 Dry/Wet ball(indoor) 20 /--Max.running

temperature(cooling): Dry/Wet ball(outdoor) 43 / 26

Max.running

temperature(heating): Dry/Wet ball(outdoor) 2 / 1

Air Conditioner Edition:2006/01/09

Hitachi/SHY73MC4-U

600CC

3.0x1.8x750

5

Page 10: aire haier

Air Conditioner Edition:2006/01/09

OPERRATION

6

Page 11: aire haier

Air Conditioner Edition:2006/01/09

Before disposing an old air conditioner that

goes out of use, please make sure it's

inoperative and safe. Unplug the air conditioner

in order to avoid the risk of child entrapment.

It must be noticed that air conditioner system

contains refrigerants, which require speciali-

zed waste disposal. The valuable materials

contained in an air conditioner can be recycled.

Contact your local waste disposal center for

proper disposal of an old air conditioner and

contact your local authority or your dealer if

you have any question. Please ensure that

the pipework of your air conditioner does not

get damagedprior to being picked up by the

relevant waste disposal center, and contribute

to environmental awareness by insisting on an

appropriate, anti-pollution method of disposal.

Disposal of the old air conditioner All these valuable materials may be taken to

a waste collecting center and used again after

adequate recycling.

Consult your local authorities for the name

and address of the waste materials collecting

centers and waste paper disposal services

nearest to your house.

Disposal of the packaging of yournew air conditioner

Safety Instructions and Warnings

Caution

All the packaging materials employed in the

package of your new air conditioner may be

disposed without any danger to the

environment.

The cardboard box may be broken or cut into

smaller pieces and given to a waste paper

disposal service. The wrapping bag made of

polyethylene and the polyethylene foam padscontain no fluorochloric hydrocarbon.

Before starting the air conditioner, read the

information given in the User's Guide caref-

ully. The User's Guide contains very impor-

tant observations relating to the assembly,

operation and maintenance of the air

conditioner.

The manufacturer does not accept respon-

sibility for any damages that may arise due

to non-observation of the following

instruction.

Damaged air conditioners are not to be

put into operation. In case of doubt, consult

your supplier.

Use of the air conditioner is to be carried

out in strict compliance with the relative

instructions set forth in the User's Guide.

Installation shall be done by professional

people, don't install unit by yourself.

7

Page 12: aire haier

Air Conditioner

For the purpose of the safety,the air con-

ditioner must be properly grounded in acco-

rdance with specifications.

Always remember to unplug the air

conditioner before openning inlet grill. Never

unplug your air conditioner by pulling on

the power cord. Always grip plug firmly and

pull straight out from the outlet.

All electrical repairs must be carried out

by qualified electricians. Inadequate repairs

may result in a major source of danger for

the user of the air conditioner.

Do not damage any parts of the air

conditioner that carry refrigerant by piercing

or perforating the air conditioner's tubes

with sharp or pointed items, crushing or

twisting any tubes, or scraping the coatings

off the surfaces. If the refrigerant spurts

out and gets into eyes, it may result in

serious eye injuries.

Caution

Do not obstruct or cover the ventilation

grille of the air conditoner.Do not put fingers

or any other things into the inlet/outlet and

swing louver.

Do not allow children to play with the air

conditioner.In no case should children be

allowed to sit on the outdoor unit.

The refrigerating circuit is leak-proof.

Remark per EMC Directive 89/336/EEC.

To prevent flicker impression during the

start of the compressor(Technical Process)

and the adversely influence caused by

the 2nd harmonies of compressor following

installation conditions do apply:

1.The power connection for air conditioner

has to be done at the main power

distribution.This distribution has to be of a

Iow impedance. Normally the required

impedance is reached at a 32A fusing point.

2.No other equipment has to be connected:

to this power line.

3.For the details installation acceptance

please refer to your contract with the power

supplier, if restrictions do apply for products:

like washing machines,air conditioners or

electrical ovens.

4.For the details of the power of air,

conditioner, please refer to the rating plate

of the product.

5.For any question contact your local dealer.

Specifications

Edition:2006/01/09

8

Page 13: aire haier

Air Conditioner Edition:2006/01/09

1.Applicable ambient temperature range:

The machine is adaptive in following situation

Caution

3. If the fuse on PC board is broken please change it with the type of T. 3.15A/250V.

4. The distance between the indoor unit and the floor should be more than 2m.

5. The wiring method should be in line with the local wiring standard.

6. After installation, the power plug should be easily reached.

7. The waste battery should be disposed properly.

8. The appliance is not intended to use by young children or infirm persons without supervision.

9.Young children should be supervised ensure that they do not play with the appliance.

10.The appliance must be installed on strong enough supporter.

11 .The wiring diagram is attached inside the machine.

2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent

or a similar qualified person. The type of connecting wire is H05RN-F or H07RN-F

Cooling

Heating

Indoor

Outdoor

Indoor

Outdoor

Maximum: D.B / W.BMinimum: D.B / W.BMaximum: D.BMinimum: D.B

Maximum: D.BMinimum: D.BMaximum: D.B / W.BMinimum: D.B / W.B

32oC/23oC18oC/14oC43oC/26oC18oC

27oC15oC24oC/18oC-7oC/-8oC

9

Page 14: aire haier

Air Conditioner Edition:2006/01/09

HSU-09C13HSU-12C13

HSU-18C13

Parts and Functions

Remote signal receiver

Operation mode indicatorTimer mode indicatorPower indicatorVertical flap

Air filter

Inlet grille

Emergency switch(manual)

Test running switch(manual)

Use remote controller toadjust up and down air flow.(Don't adjust it manually.)

Lights up when unit starts. Lights up when Timer operationis selected.

Lights up during compressorrunning.

A beeping sound is generated when

received.a signal from remote controller is

Used when remote controller is lost ordefective. Unit will run temporarily.

Used only for test running in cooling

Don't use it in normal operation.when room temp. is below 16oC.

HSU-22C13HSU-24C13

Indoor Unit

Outdoor Unit

CONNECTING PIPING AND ELECTRICAL WIRING

DRAIN HOSE

OUTLET

INLET

Actual inlet grille may vary from the one shown in the manual according to the product purchased.

10

Page 15: aire haier

Air Conditioner Edition:2006/01/09

Parts and Functions

FAN

DRYHEAT

COOLAUTO

AUTO LO MED HI

Operation1. Mode display

2. SWING display3. FAN SPEED display4. SLEEP display5. LOCK display6. SIGNAL SENDING7. TIMER OFFdisplay8. TIMER ON display9. CLOCK display10. TEMP display11. POWER ON/OFF

Used for unit start and stop.12. MODE

Used to select AUTO run, COOL,DRY, HEAT and FAN operation

13. FANUsed to select fan speed LO, MED, HI, AUTO

14. HOURUsed to set clock and timer setting.

15. SWINGUsed to set auto fan direction.

16. SLEEPUsed to select sleep mode.

17. LOCKUsed to lock buttons and LCDdisplay.

18. TEMP.Used to select your desired temp.

19. SETUsed to confirm timer and clock settings.

20. TIMERUsed to select TIMER ON, TIMER OFF,TIMER ON-OFF

21. CLOCKUsed to set correct time

22. RESET

normal condition.Used to reset the controller back toClock set

When unit is started for the first time and after replacing batteries in remote controller,clock should be adjusted as follows:Press CLOCK button, "AM" or "PM" flashes.Press or to set correct time. Each press will increase or decrease 1min. If thebutton is kept depressed, time will change quickly.After time setting is confirmed, press SET, "AM "and "PM" stop flashing, while clockstarts working.

HintsAfter replacing with new batteries, remote controller will conduct self-check, displayingall information on LCD. Then, it will become normal.

ON/OFF TEMP

MODE SET

FAN TIMER

SWING CLOCK

SLEEP

LOCK RESET

NOTE: Cooling only unit do not have displays and functions related with heating

4

1

23

11

12

13

14

15

16

17

18

20

5

6789

10

19

21

22

Buttons and display of the remote controller.

11

Page 16: aire haier

Air Conditioner Edition:2006/01/09

*********7#

**,******,*

***********

********,******,6**********

****************

*********7#

**,******,*

***********

********,******,6**********

****************

*********7#

**,******,*

***********

********,*

*****,6****

******

********

********

Remote controller's operation

When in use, put the signal transmission head directly to thereceiver hole on the indoor unit.

The distance between the signal transmission head and thereceiver hole should be within 7m without any obstacle as well.

Don't throw the controller, prevent it from being damaged.

When electronic-started type fluorescent lamp or change-overtype fluorescent lamp or wireless telephone is installed in the

room, the receiver is apt to be disturbed in receiving the signalsso the distance to the indoor unit should be shorter.

Loading of the battery

Load the batteries as illustrated. 2 R-03 batteries, resetting key (cylinder)

Remove the battery cover:

Slightly press " " and push down the cover.

Load the battery:

Be sure that the loading is in line with the" + "/"-"pole request as illustrated.

Put on the cover againConfirmation indicator:In disorderation, reload the batteries or load the new batteries after 6mins.

Note:Use two new same-typed batteries when loading.If the remote controller can't run normally or doesn't work at all,use a sharp pointed item to press the reset key.

Hint:Remove the batteries in case unit won't be in usage for a long period.If there are any display after taking-out just need to press reset key.

Power failure resume(please set and apply as necessary)If sudden power failure occurs, the unit will resume original operation when power is

supplied again.

Note: When sudden power failure happens during unit operation in power failure resume mode, if

the air conditioner is not desired for use in a long period, please shut off the power supply

in case that the unit automatically resume operation when power is re-supplied, or press

ON/OFFto turn off the unit when power resumes.

Operation

12

Page 17: aire haier

Air Conditioner Edition:2006/01/09

(4) Unit stop

(1) Unit start

Auto run, Fan operation Enjoy yourself by just a gentle press.

mode changes as follows:

Press ON/OFF button, unit starts.Previous operation status appears on display.(Not Timer setting)Power indicator on indoor unit lights up.

(2) Select operation modePress MODE button. For each press, operation

AUTO COOL DRY HEAT FAN

Unit will run in selected mode.

Stop display at " " AUTO or " "FAN.

(3) FANPress FAN button. For each press, fan speed changesas follows:

AUTO LO MED HI

Unit will run at selected fan speed.

Note:AUTO is not available in FAN mode.Press ON/OFF button.Only time remains on LCD.All indicators on indoor unit go out.Vertical flap closed automatically.

HintsRemote controller can memorize settings in each operation mode. To run it next time justselect the operation mode and it will start with the previous setting.No reelecting is needed.(TIMER ON/OFF needs reelecting)

Cautions: Note:On cooling only unit, heating mode is not available, The above information is theAfter replacing batteries, press ON/OFF, and display explanation of the displayedbecomes as follows: information therefore variesOperation mode: AUTO, Temp. No with those displayed in actualTimer mode: No, Fan speed :AUTO operation.

ON/OFF TEMP

SET

TIMER

CLOCKSWING

SLEEP

LOCK RESET

FAN

MODE

Operation

1

2

3

4

13

Page 18: aire haier

Air Conditioner Edition:2006/01/09

Press MODE button. For each press, operation

Recommendations:

OperationCOOL,HEAT and DRY operation

Use COOL in summer. Use HEAT in winter

Use DRY in spring, autumn and in damp climate.

(1) Unit start

mode changes as follows:

Press ON/OFF button, unit starts.Previous operation status appears on display. (Not Timer setting)Power indicator on indoor unit lights up.

(2) Select operation mode

AUTO COOL DRY HEAT FAN

Unit will run in operation mode displayed on LCD.Stop display at your desired mode.

(3) Select temp. settingPress TEMR button.

Every time the button is pressed, temp. setting increases 1oCEvery time the button is pressed, temp. setting decreases 1oC

Unit will start running to reach the temp. setting on LCD.

Press FAN button. For each press, fan speed changes

(4) Fan speed selection

as follows:

AUTO LO MED HI

just press ON/OFF button and unit will run in previous status.

Unit runs at the speed displayed on LCD.

In DRY mode, when room temp. becomes 2oC higher than

temp. setting, unit will run intermittently at LO speed

regardless of FAN setting.

HintsOn cooling only unit, heating mode is not available.Remote controller can memorize each operation status. When starting it next time,

COOL operation starts when roomtemp. is higher than temp. setting.

Ultra-low air flow

Temp. setting+2oC

Temp. setting

On reaching temp. setting, unitwill run in mild DRY mode.

ON/OFF TEMP

SET

TIMER

CLOCKSWING

SLEEP

LOCK RESET

FAN

MODE1

2

3

4

3

5

6

14

Page 19: aire haier

Air Conditioner Edition:2006/01/09

Operation(5) Air flow direction adjustment

After operation mode is selected, vertical flap will open automatically according to the mode.Referring to the Fig.

COOLHEAT

COOL

About 10o

About 10o

About 45o

About 60o

better set a temp. difference of 3-5oC between indoor and outdoor temp. in COOL mode.

HintsAs cold air flows downward in COOL mode, adjusting air flow horizontally will be much more

helpful for a better air circulation.

As warm air flows upward in HEAT mode, adjusting air flow downward will be much more

helpful for a better air circulation.

Be careful not to catch a cold when cold air blows downward.

It is harmful to your health in summer to go frequently in and out of places where temp.

difference is above 7oC. Temp. difference of 3-5oC will remove your fatigue.

More than this, unit's load can be reduced and power consumption cut down as well. So, you'd

(6) Unit stopPress ON/OFF button.Only time remains on LCD.All indicators on indoor unit go out.Vertical flap closes automatically.

Cautions:Unit won't restart until 3 minutes haveelapsed, due to system protection.HEAT mode is not available oncooling only unit.

It is advisable not to keep vertical flap at

downward position for a long time in COOL

or DRY mode, otherwise, condensate

water might occur.

Cautions: Cautions:When humidity is high, condensate water

might occur at air outlet if all horizontal

louvers are adjusted to left or right.

Move the horizontal blade by a knob on air

conditioner to adjust left and right direction

referring to Fig.

Left and right air flow adjustment(manual)Press SWING button, vertical flap will move within

the range shown in the Fig. Press SWING button

stop it at a fixed position.

Up and down (Use remote controller)

15

Page 20: aire haier

Air Conditioner Edition:2006/01/09

ON/OFF TEMP

SET

TIMER

CLOCKSWING

SLEEP

LOCK RESET

FAN

MODE

OperationTIMER Operation

You can let unit start or stop automatically at following times: Before you wake up in themorning, or get back from outside or after you fall asleep at night.

Set Clock correctly before starting Timer operation

TIMER ON/OFF

Power indicator on indoor unit lights up.

(1)After unit start, select your desired operation mode.Operation mode will be displayed on LCD.

(2)TIMER mode selectionPress TIMER button to change TIMER mode.Every time the button is pressed, display changes as follows:

ON OFF ON OFF

TIMER ON TIMER OFF TIMER ON-OFF

blank

Select your desired TIMER mode (TIMER ON or TIMER

OFF) ON or OFF will flash.

(3)Timer settingPress HOUR / button.

Every time the button is pressed, time increases 10 min.If button is kept depressed, time will change quickly.

Every time the button is pressed, time decreases 10 min.If button is kept depressed, time will change quickly. Timewill be shown on LCD. It can be adjusted within 24 hours.

Timer mode indicator on indoor unit lights up.

(4)Confirming your setting After setting correct time, press SET button to confirm, "ON"or "OFF" stops flashingTime displayed: Unit starts or stops at x hour x min. (TIMERON or TIMER OFF).

To cancel TIMER modeJust press TIMER button several times until TIMER mode disappears.

HintsAfter replacing batteries or a power failure happens, Time setting should be reset.Remote controller possesses memory function, when use TIMER mode next time, justpress SET button after mode selecting if timer setting is the same as previous one.

1

23

43

16

Page 21: aire haier

Air Conditioner Edition:2006/01/09

TIMER ON-OFF

ON/OFF TEMP

SET

TIMER

CLOCKSWING

SLEEP

LOCK RESET

FAN

MODE

OperationTIMER ON-OFF

To cancel TIMER mode

Power indicator on indoor unit lights up.

(1)After unit start, select your desired operation modeOperation mode will be displayed on LCD.

ON OFF ON OFFTIMER ON TIMER OFF TIMER ON-OFF

blank

Every time the button is pressed, display changes as follows:

(2) Press TIMER button to change TIMER mode.

Select TIMER ON-OFF. "ON" will flash.

(3)Time setting for TIMER ON

If button is kept depressed, time will change quickly.Every time the button is pressed, time decreases 10 min.

If button is kept depressed, time will change quickly.

Every time the button is pressed, time increases 10 min.

It can be adjusted within 24 hours.Time will be shown on LCD.

AM refers to morning and PM to afternoon

Press HOUR button.

(4) Time confirming for TIMER ONAfter time setting, press TIMER button to confirm."ON" stops blinking, While "OFF" starts blinking.Time displayed: Unit starts at x hour x min.

(5)Time setting for TIMER OFFFollow the same procedures in "Time setting for TIMER ON".

(6) Time confirming for TIMER OFFAfter time setting, press SET button to confirm, "OFF" stops flashing

Time displayed: Unit stops at X hour X min.

Just press TIMER button several times until TIMER mode disappears.

1

2

3

45

6

17

Page 22: aire haier

Air Conditioner Edition:2006/01/09

Emergency Operation:

Pi...Pi Pi

Emergency operation and test operation

Operation

Carry out this operation only when the remote controller is defective or lost.When the emergency operation switch is pressed, a" Pi "sound starts once, whichmeans the start of this operation.In this operation, it is not possible to change thesettings of temperature and air flow speed, it isalso impossible to do an operation by the timer.Follow the requirements below.

Roomtemperature

Designatedtemperature

Timermode

Air flowspeed

Operation mode

More than 23oC

Less than 23oC 23oC

26oC CONTINUOUS

CONTINUOUS

AUTO

AUTO

COOL

HEAT

Pi

Heating when the room temperature at the start of operation is below 23oC

If an air conditioner is a model for both cooling and heating.Cooling when the room temperature at the start of operation is above 23oC.

temperature is less 16oC, do not use it in the normal

Test operation:Use this switch in the test operation when the room

operation.

operation starts with the air flow speed setting "Hi".

Continue to press the test operation switch for morethan 5 seconds. After you hear the "Pi" sound twice,release your finger from the switch, the cooling

Removal of the restriction of emergency or test operation:Press once more the emergency operation switch, or manipulate through the remotecontroller, a "Pi" sound causes the restriction of emergency or test operation to beremoved.When the remote controller is manipulated for the removal, then the selected operationby the remote controller.

18

Page 23: aire haier

Air Conditioner Edition:2006/01/09

ON/OFF TEMP

SET

TIMER

CLOCKSWING

SLEEP

LOCK RESET

FAN

MODE

Comfortable SLEEP

Operation

In COOL mode

sleep in selected mode.

Before going to bed at night, you can simply pressthe SLEEP button and unit will bring you a sound

One hour after SLEEP mode starts, temp. will

become 1oC higher than temp. setting. After

running for another 1 hour, temp. rises by 1oC

further. Unit will run for 6 hours then stops

automatically. Temp. is higher than temp.

setting so that room temp. won't be too low

for your sleep.(As shown in Fig.l)

In HEAT mode

(As shown in Fig .2)

One hour after SLEEP mode starts, temp. willbecome 2oC lower than temp. setting. Afterrunning for another 1 hour, temp. decreasesby 2oC further. Unit will run for 3 hours at thistemp. then increases another 1oC and stopsautomatically 3 hours later. Temp. is lowerthan temp. setting so that room temp. won'tbe too high for your sleep.

Power Failure Resume Function

with the indicator lighting up.

If the unit is started for the first time, thecompressor will not start running unless 3minutes have elapsed. When the powerresumes after power failure, the unit will runautomatically, the power indicator lights up, and3 minutes later the compressor starts running

Note:In AUTO mode, unit will run in SLEEP

function according to operation mode.

In FAN mode, comfortable sleep is not

available.

SLEEP operation starts SLEEP operation stops

Approx. 6 hrs

1 hr

1 hr

Rises 1oC

Rises 1oC

Temp. setting Unit stop

Temp. setting Unit stop

decreases 2oC

decreases 2oC

Approx. 3 hrs

1 hr

1 hr

Rises 1oC3 hrs

SLEEP mode starts SLEEP mode stops

Fig.1

Fig.2

19

Page 24: aire haier

Air Conditioner Edition:2006/01/09

MaintenanceDifferent models have different appearance

Cleaning of unit casing

Cleaning of remote controller

Cleaning of air filter

Cut off power supplybefore cleaning unit casing with soft cloth.In case of heavy stain, clean it with neutral detergent.squeeze water in the cloth, wipe off the detergent on unitcasing completely.

Don't use water to wash unit casing, please use dry cloth.Don't use glass cleaner or cloth soaked with chemicals.

1.Open inlet grille by pulling it upward.Air Filter

2.Remove air filterPush up the filter's center tabslightly until it is caesura ofthe stopper. Remove it bypulling down.

3.Clean the filterUse a vacuumcleaner to removedust,or wash thefilter with water.After washing,dry the filtercompletely in the shade.

5.Close the inlet grille.

4.Attach the filterAttach filter behind the stopper so thatthe "Front" indication is facing to the front. Make surethat it is completely behind the stopper, otherwiseproblems might occur.

20

Page 25: aire haier

Air Conditioner Edition:2006/01/09

ELECTRICAL CONTROLL

21

Page 26: aire haier

Air Conditioner

Introduction to electrical control function Including brief introduction to air conditioners of series models and electric control

function.

(1) Automatic running (applicable to fan-coil model)

When the running mode is turned to automation after starting the system, the system

will first determine the running mode according to the current room temperature and then

will run according to the determined mode. Tr in the following selection conditions

means room temperature, Ts means setting temperature, Tp means temperature of indoor

coil pipe

a. Tr≥23℃ running refrigerating mode Ts=26℃

b. Tr<23℃ running fan only mode

(2) Indoor temperature control

(3) Dehumidification running

The compressor, outdoor fan and indoor fan will run as per the following working

pattern so as to realize the refrigerating running of dehumidification:

① Tr> Ts+2℃, compressor, outdoor fan run continuously, indoor fan runs as per

setting wind speed (State 1);

② Ts+2℃≥Tr≥Ts, compressor, outdoor fan run intermittently with 10 minutes

ON, 6 minutes OFF. (Compressor and outdoor fan are synchronous) indoor fan

runs in fixed lower wind speed, and will cease at the stand-by time of 3 minutes

(State 2)

③ Tr <Ts, compressor, outdoor fan ceases, indoor fan runs in lower wind speed.

(State 3)

State1

State2

State3

Ts-1 Ts Ts+2 Ts+3

Compressor OFF

Compressor OFF

Setting

temperature

Refrigerating

+1-1

Compressor ON

Edition:2006/01/09

22

Page 27: aire haier

Air Conditioner

(4) Freezing prevention function

Under refrigerating and dehumidifying state, the air conditioner will control the

outdoor fan as per the temperature Tp of the indoor coil pipe according to the

following conditions:

Zone of return deference

Compressor,outdoor fan OFF after 5 minutes Fan,compressor ON

0 7 Tp(℃.)

(5) 3 minutes stand-by time

When the compressor ceases due to the sensor OFF, unit On or OFF or fault, it

will maintain pause for 3 minutes.

(6) Compensatory function of power failure

If the unit is suddenly off during running due to power failure, or closed for

maintenance or troubleshooting, it will restart to run after the power resumes with

the original condition before the unit is off

Note: 1. Function setting: Pressing the SLEEP button on the remote control unit

for 10 times until hearing 4 sounds from the buzzer on the panel.

2. Memory content: Running mode, setting wind speed, setting

temperature, sleep state, flap state.

3. Cancellation of function: Pressing the SLEEP button on the remote

control unit for 10 times until hearing 2 sounds from the buzzer on the

panel.

(7) Trial run function

When the air conditioner is in OFF state, press the emergency switch for 5

seconds till hearing 2 sounds of click from the buzzer, then the air conditioner will

turn to the trial run state. The unit will run in the refrigerating mode and the

indoor fan will run in high wind speed mode.

(8) Emergency running mode

When the air conditioner is in stand-by state, press the emergency switch till

hearing a sound from the buzzer, then the air conditioner will turn to the

emergency run state. The rules of emergency run are as follows:

a. Tr≥23℃, running refrigerating mode, Ts = 26℃;

b. Tr<23℃, running fan only mode,.

Edition:2006/01/09

23

Page 28: aire haier

Air Conditioner

(9) Sleeping function

After setting the sleeping function, the refrigerating mode and dehumidification

mode will run as per the following rules:

6hours

T(℃)

1 hour

Ts+2

Ts+1 1 hours

Ts Sleep OFF t(hour)

As shown in the above diagram, after running for 1 hour under refrigerating mode

and dehumidification mode, the setting temperature will increase 1℃; after

another 1 hour, it will increase 1℃ again, and after 6 hours, it will cease.

(10). Abnormality diagnosing

For the abnormal phenomenon occurred, please conduct trouble analysis and troubleshooting

according to the following table:

Edition:2006/01/09

24

Page 29: aire haier

Air Conditioner Edition:2006/01/09

Error Codes and Description Error Codes and Description

Code indication

Power timer operateDescription

ReferencePage

Room temperature sensor failure

Heat-exchange sensor failure

Indoor EEPROM error

Indoor Malfunction

repeate the cycle.

Indoor fan motor malfunction

explaination on flash off

Trouble Shooting

1. Indoor Malfunction

Thermistor or Related Abnormality (indoor unit)

the temperatures detected by the thermistors are used to determine hermistorerrors

when the thermistor input is more than 4.92V or less than 0.08V duringcompressor

operation.

The values vary slightly in some modelsFaulty connector connectionFaulty thermistorFaulty PCB

Troubleshooting Be sure to turn off power switch before connect or disconnectconnector, or parts damage may be occurred.

: Room temperature sensor failure CN6 : Heat-exchange sensor failure CN6

25

Page 30: aire haier

Air Conditioner Edition:2006/01/09

2. Fan Motor or Related Abnormality

The rotation speed detected by the Hall IC during fan motor operation is usedto determine

abnormal fan motor operation

when the detected rotation feedback singal don’t receiced in 2 minutes

Operation halt due to breaking of wire inside the fan motor . Operation halt due to breaking of the fan motor lead wiresDedection error due to faulty indoor unit PCB

Yes

NO

YES

whether terminal CN6 on

indoor PCB contact wellt?Pull out the terminals on the indoor mainboard

and reinsert them

Pull the sensor out of the mainboard

1) Measure the value of resistance Between its two

jumpers

2) Measure the temperature at the room temperature

sensing head.

Check the value of the

sensor to see whether the

sensor is damaged or not?

NOSensor is broken,replace it with new sensor

The indoor PCB is broken, replace with new indoor PCB

26

Page 31: aire haier

Air Conditioner Edition:2006/01/09

repeate the cycle. : Indoor fan motor malfunction

Yes

Yes

YES

NO

whether terminal CN8

and CN9 on indoor PCB

well inserted or not?

Pull out and reinsert the terminals

Electrify the machine again and turn it on in the cooling

operation, Measure voltage between the positions 1 ( red

wire) and 5( black wire) of Terminal CN9 on the indoor PCB

NO the indoor pcb is damaged and need replacethe voltage is about

90-200vac

check whether motor

can run when

turn on the unit

the indoor motor is damaged and need

replace

NO

When motor is running Measure

whether there is voltage

pulse(0-5VDC) between the

positions 2 (middle wire) and

3( black wire) of Terminal CN9

the indoor motor is damaged and need

replace

the indoor pcb is damaged and need replace

NO

27

Page 32: aire haier

Air Conditioner Edition:2006/01/09

3. The EEPROM Abnormality (indoor unit)

the Data detected by the EEPROM are used to determine MCU

when the Data of EEPROM is error or the EEPROM is damaged

Faulty EEPROM dataFaulty EEPROM Faulty PCB

Troubleshooting Be sure to turn off power switch before connect or disconnectconnector, or parts damage may be occurred.

Resolvent : Replace the PCB of indoor unit : Indoor EEPROM error: Replace the PCB of indoor unit

28

Page 33: aire haier

Air Conditioner Edition:2006/01/09

TROUBLE SHOOTING

29

Page 34: aire haier

Air Conditioner Edition:2006/01/09

Is the air filter dirty? Normally it should becleaned every 15 days.Are there any obstacles before inlet and outlet?Is temperature set correctly?Are there some doors or windows left open?Is there any direct sunlight through thewindow during the cooling operation?(Usecurtain)Are there too much heat sources or too manypeople in the room during cooling operation?

Cause or check pointsPhenomenon

The system does not restartimmediately.

Noise is heard:

Smells are generated.

Mist or steam are blown out.

Does not work at all.Multiplecheck

NormalPerformanceinspection

Poor cooling

Before asking for service, check the following first.

When unit is stopped, it won't restartimmediately until 3 minutes have elapsedto protect the system.When the electric plug is pulled out andreinserted, the protection circuit will workfor 3 minutes to protect the air conditioner.

During unit operation or at stop, a swishingor gurgling noise may be heard. At first 2-3minutes after unit start, this noise is morenoticeable. (This noise is generated byrefrigerant flowing in the system.)During unit operation, a cracking noise maybe heard. This noise is generated by thecasing expanding or shrinking because oftemperature changes.Should there be a big noise from air flow inunit operation, air filter may be too dirty.

This is because the system circulates smellsfrom the interior air such as the smell offurniture, cigarettes.

During COOL or DRY operation, indoor unitmay blow out mist. This is due to the suddencooling of indoor air.

Is power plug inserted?Is there a power failure?Is fuse blown out?

Trouble shooting

30

Page 35: aire haier

Air Conditioner Edition:2006/01/09

INSTALLATION

31

Page 36: aire haier

Air Conditioner Edition:2006/01/09

No.0010557707

Installation Manual of Room Air ConditionerRead this manual before installation

1.Driver2.Hacksaw3.Hole core drill4.Spanner(17,19 and 26mm)

5.Torque wrench(17mm,22mm,26mm)6.Pipe cutter7.Flaring tool8.Knife

9.Nipper 12.Reamer10.Gas leakage detector or soap-and-water solution11.Measuring tape

Explain sufficiently the operating means to the useraccording to this manual.

A

B

C

D

E

F

G

Optional parts for piping

Mark Parts name

Non-adhesive tape

Adhesive tape

Saddle(L.S) with screws

Connecting electric cablefor indoor and outdoor

Drain hose

Heating insulating material

Piping hole cover

Arrangement of piping directions

Rear left

Rearright

Left

BelowRight

The marks from to in the figure are the parts numbers.

The distance between the indoor unit and the floor should bemore than 2m.

A G

Attention must be paid tothe rising up of drain hose

mor

e th

an 5

cm

more than 10cm

more than 10cm

A

C

No. Accessory parts

Remote controller

R-03 dry battery

Mounting plate

Drain hose

Steel nail, cement

ScrewPlastic cap

Drain-elbow

Cover

Cushion

11

2

3

4

5

6

7

8

9

10

2

1

1

6

4

1

1

4

1

Number ofarticles

Accessory parts

4X50

4X25

Pipe supporting plate

more than 10cm

more than 60cm more than 15cm

more than 10cm

D

E

Drawing for the installation of indoor and outdoor units

Necessary Tools for Installation

32

Page 37: aire haier

Air Conditioner Edition:2006/01/09

Fixing of outdoor unit

Indoor Unit Selection of Installation Place

Power Source

Selection of pipe

Outdoor Unit

Fix the unit to concrete or block with bolts( 10mm) and nuts firmly and horizontally.

When fitting the unit to wall surface, roof or rooftop, fix a supporter surely with nailsor wires in consideration of earthquake and strong wind.

If vibration may affect the house, fix the unit by attaching a vibration-proof mat.

Place, robust not causing vibration, where the body can be supportedsufficiently.Place, not affected by heat or steam generated in the vicinity, whereinlet and outlet of the unit are not disturbed.Place, possible to drain easily, where piping can be connected with theoutdoor unit.Place, where cold air can be spread in a room entirely.Place, nearby a power receptacle, with enough space around. (Referto drawings).Place where the distance of more than lm from televisions, radios,wireless apparatuses and fluorescent lamps can be left.In the case of fixing the remote controller on a wall, place where theindoor unit can receive signals when the fluorescent lamps in the roomare lightened.

Place, which is less affected by rain or direct sunlight and issufficiently ventilated.Place, possible to bear the unit, where vibration and noise arenot increased.Place, where discharged wind and noise do not cause anuisance to the neighbors.Place, where a distance marked is available as illustratedin the above figure.

Before inserting power plug into receptacle, check the voltage without fail. The power source is the same as the corresponding name plate.

Install an exclusive branch circuit of the power.

A receptacle shall be set up in a distance where the power cable can be reached. Do not extend the cable by cutting it.

To this unit, both liquid and gas pipes shall be insulated

as they become Iow temperature in operation.

Use optional parts for piping set or pipes covered with

equivalent insulation material.

Floor fixing dimensionsof the outdoor unit(Unit:mm)

Floor fixing dimensionsof the outdoor unit(Unit:mm)

HSU-09C13HSU-12C13

HSU-22C13

Gas pipe( )

09

6.35mm(1/4")

Gas pipe( ) 9.52mm(3/8")

12,18

6.35mm(1/4")

12.7mm(1/2")

22,24

9.52mm(3/8")

15.88mm(5/8")

HSU-24C13

Floor fixing dimensionsof the outdoor unit(Unit:mm)

HSU-18C13

113.5 583 113.5

319.

5

140 140415

280

140 500 140

256

33

Page 38: aire haier

Air Conditioner Edition:2006/01/09

Indoor unit

1.Fitting of the Mounting Plate and Positioning of the wall Hole

2.Making a Hole on the Wall and Fitting the Piping Hole Cover

When the mounting plate is first fixed

When the mounting plate is fixed side bar and lintel

1.Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be fixed against the wall, then temporarily fasten the plate with one steel nail.2. Make sure once more the proper level of the plate, by hanging a thread with a weight from the central top of the plate, then fasten securely the plate with the attachment steel nail.3. Find the wall hole location A using a measuring tape

Refer to the previous article, " When the mounting plate is first fixed ", for theposition of wall hole.

Fix to side bar and lintel a mounting bar, Which is separately sold, and then fasten

the plate to the fixed mounting bar.

Make a hole of 60 mm in diameter,

slightly descending to outside the wall.

Install piping hole cover and seal it

off with putty after installation

(Section of wall hole) Piping hole pipe

Outdoor side

Thicknessof wall

Indoor side

Wall hole

60mm

3.Installation of the Indoor Unit

Drawing of pipe

[ Rear piping ]Draw pipes and the drain hose, then fasten them with the adhesive tape

[ Left Left-rear piping ]In case of left side piping, cut away, with a nipper, the lid for left piping.In case of left-rear piping, bend the pipes according to the piping direction to the mark of hole for left-rearpiping which is marked on heat insulation materials.

G

Indoor unit

A=145mm

B= 60mm

30m

m

34

Page 39: aire haier

Air Conditioner Edition:2006/01/09

Indoor unit

4.Connecting the indoor/outdoor Electric Cable

Fixing the indoor unit body

Removing the wiring cover

[Other direction piping]

Indoor/outdoor electric cable and drain hose must be bound with refrigerant piping by protecting tape.

Cut away, with a nipper, the lid for piping according to the piping direction and then bend the pipe accordingto the position of wall hole. When bending, be careful not to crash pipes.Connect beforehand the indoor/outdoor electric cable, and then pull out the connected to the heat insulationof connecting part specially.

Hang surely the unit body onto the upper notches of themounting plate. Move the body from side to side to verifyits secure fixing.In order to fix the body onto the mounting plate,hold upthe body aslant from the underside and then put it downperpendicularly.

Remove terminal cover at right bottom corner of indoor unit, thentake off wiring cover by removing its screws.

When connecting the cable after installing the indoor unit1. Insert from outside the room cable into left side of the wall hole, in which the pipe has already existed.2. Pull out the cable on the front side, and connect the cable making a loop.

1. Insert the drain hose into the dent of heat insulation materials of indoor unit.2. Insert the indoor/outdoor electric cable from backside of indoor unit, and pull it out on the front side, then connect them.3. Coat the flaring seal face with refrigerant oil and connect pipes. Cover the connection part with heat insulation materials closely, and make sure fixing with adhesive tape

Heat insulationmaterial

Drain hose

Piping

Indoor/outdoorelectric cable

Lid for right piping

Lid for under pipingLid for left piping

Fix with adhesive tape

35

Page 40: aire haier

Air Conditioner Edition:2006/01/09

Indoor unit

1. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar

qualified person. The type of connecting wire is H05RN-F or H07RN-F.

2. If the fuse on PC board is broken please change it with the type of T. 3.15A/250V.

3. The wiring method should be in line with the local wiring standard.

4. After installation, the power plug should be easily reached.

When connecting the cable before installing the indoor unit

Insert the cable from the back side of the unit, then pull it out on the front side.

Loosen the screws and insert the cable ends fully into terminal block, then tighten the screws.

Pull the cable slightly to make sure the cables have been properly inserted and tightened.

After the cable connection, never fail to fasten the connected cable with the wiring cover.

Note: When connecting the cable, confirm the terminal number of indoor and outdoor units carefully. If wiring

is not correct, proper operation can not be carried out and will cause defect.

3G1.5mm23G2.0mm2

3G2.5mm2

Power cable: 3G1.5mm2 Power cable: 3G2.5mm2

Power cable: 3G2.5mm2

HSU-22C13

Indoor unit

Outdoor unit

YEL/GRN

BLK WHT YEL/GRN

BLK

4

WHT

HSU-24C13

1(L)2(N

)

LN

POW

ER P

LUG{

LNG

HSU-18C13

Indoor unit

Outdoor unit

YEL/GRN

BLK WHT YEL/GRN

WHT

BLK4

1(L)2(N

)

LN

POW

ER P

LUG{

LNG

HSU-09C13HSU-12C13

Indoor unit Outdoor unit

YEL/GRN

BLKWHT

4

YEL/GRN

WHT

BLK

1(L)2(N

)

36

Page 41: aire haier

Air Conditioner Edition:2006/01/09

Outdoor unit

1.Installation of Outdoor Unit

3.Connection

4.Attaching Drain-Elbow

2.Connection of pipes

Install according to

To bend a pipe, give the roundness as large as possible not to crush the pipeConnecting the pipe of gas side first makes working easier.The max vertical distance between the indoor unit and the outdoor unit is 5 m.

Use the same method on indoor unit. Loosen the screws on terminal block and insert the plugs fully intoterminal block, then tighten the screws.

If wiring is not correct, proper operation can not be carried out and controller may be damaged.

If the drain-elbow is used, please attach it as figure. (Note: Only for heat pump unit.)

Forced fastening without careful centeringmay damage the threads and cause aleakage of gas.

Pipe Diameter ( )

Liquid side 6.35mm(1/4")

Gas side 9.52mm(3/8")

Fastening torque

Drawing for the installation of indoor and outdoor units

Insert the cable according to terminal number in the same manner as the indoor unit.

Fix the cable with a clamp.

18N.m

40N.m

Half union Flare nut

SpannerTorque wrench

Gas side 12.7mm(1/2") 50N.m

Outdoor unit

Gas side 15.88mm(5/8") 60N.m

Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.

37

Page 42: aire haier

Air Conditioner Edition:2006/01/09

Outdoor unit5.Purging Method:

3-way valve2-way valve6.35mm(1/4") 12.7mm(1/2")

HSU-18C13

HSU-12C13HSU-09C13

HSU-22C13HSU-24C13

3-way valve

2-way valve6.35mm(1/4")

9.52mm(3/8")12.7mm(1/2")

9.52mm(3/8")

15.88mm(5/8")

Push the air out of the indoor unitand piping as followes:

(1) Remove the valve cap on 2-way valve in outdoor unit.

(2) Loosen by 1/2 turn the flare nut of gas pipe, which is conneted to 3-way valve.

(3) Loosen 2-way valve by 90o using hexagon wrench, and after approx. 10 sec tighten it up. Gas comes out through flare nut on wide pipe. If no gas is discharged, tighten flare nut with specified torque.

(4) Open 2-way and 3-way valves using specified torque.

(5) Tighten the caps on the valves with specified torque.

Valve rod

Valve cap

7-9

20-25

Tighten torque N.m

When connecting pipe exceeds 5 meters, 16g refrigerant shall be addedper exceeding meter. Charge according to the following list.

Piping length

Additional amount

5m 7m 10m

No need 32g

During this procedure, 50g or 80g(only for 22k and 24k unit) refrigerant will be discharged in piping.

(This must be strictly controlled within 90o and 10 sec.)

Brand new outdoor unit is charged 50g or 80g(only for 22k and 24k unit) more refrigerant than regulated weight.Only for first installation, this extra 50g or 80g(only for 22k and 24k unit) can be used to purge air in pipes.

Note: When extending piping, air inside piping shall be removed by using external refrigerant gas, charge according to the following list.

80g

38

Page 43: aire haier

Air Conditioner Edition:2006/01/09

It becomes highmidway.

The end is immersedin water.

It waves. The gap with the groundis too small

Less than 5cm

There is the bad smellfrom a ditch

1.Power Source Installation

2.Cutting and Flaring Work of Piping

3.On Drainage

Check for Installation and Test Run

Check Items for Test Run

The power source must be exclusively used for air conditioner. (Over I0A)In the case of installing an air conditioner in a moist place, please install anearth leakage breaker.For installation in other places, use a circuit breaker as far as possible.

Pipe cutting is carried out with a pipe cutter and burs must be removed.After inserting the flare nut, flaring work is carried out.

Please install the drain hose so as to be downward slope without fail.Please don't do the drainage as shown below.

Please pour water in the drain pan of the indoor unit, and confirm that drainage iscarried out surely to outdoor.In case that the attached drain hose is in a room, please apply heat insulationto it without fail.

Please kindly explain to our customers how to operate through the instruction manual.

Gas leak from pipe connecting?Heat insulation of pipe connecting?Are the connecting wirings ofindoor and outdoor firmly insertedto the terminal block?Is the connecting wiring of indoorand outdoor firmly fixed?

Is drainage securely carried out?Is the earth line securelyconnected?Is the indoor unit securely fixed?Is power source voltage abidedby the code?Is there any noise?

Put check mark in boxes

Is the lamp normally lighting?Are cooling and heating (whenin heat pump) performed normally?Is the operation of room temperatureregulator normal?

Liquid side

Pipe diameter( ) Size A(mm)6.35mm(1/4")

9.52mm(3/8")

0.8~1.5

1.0~1.8Gas side

Gas side 12.7mm(1/2") 1.2~2.0

Correct Incorrect

Lean Damage of flare Crack Partial Too outside

Flare tooling die

A

39

Page 44: aire haier

Air Conditioner Edition:2006/01/09

CIRCUIT AND WIRING DIAGRAM

40

Page 45: aire haier

Air Conditioner

HSU-09/12/18/22C13 CIRCUIT DIAGRAM

Edition:2006/01/09

1 2 3 4

A

B

C

D

4321

D

C

B

A

P04/INT241

P05/INT252

P06/INT263

P07/INT274

P605

P616

RES7

X08

X19

VSS10

P37/BUZ/PPG11

P36/INT1212

P35/INT1113

P34/TO/INT1014

P33/EC15

C16 P32/UI/SI 17P31/UO/SO 18P30/UCK/SCK 19P50/PWM 20P70 21P71 22P72 23P40/AN0 24P41/AN1 25P42/AN2 26P43/AN3 27P00/INT20/AN4 28P01/INT21/AN5 29P02/INT22/AN6 30P03/INT23/AN7 31VCC 32

IC1

C7

0.1UF

16

15

3 14

4 13

5 12

O6

O7

I2

I3

I5

I6 11

O2

O4

O5

I1

I4

I7

O1

O3

7

6

10

COM 9GND8

1

2

IC3

R18 10KR19 10KR20 10K

R10

3.3K

R11

3.3KR12

3.3K

+5V

R2110K

R133.3K

+5V

+5V

123

CN8

B3B-EH

R22

51K

R31K

C9

0.01uf-50V

C11

1nF

C12

0.01UF

12345

CN5

S5B-PH

+12V

+12V

R14 4.7K

R4 2K

R5

10KCN15

TJC8-02

C3 0.01UF

+5V

C4 0.01UF

+5V

SW1TSVC-1

R62K

R7

10K

A01

A12

A23

VSS4 SDA 5SCL 6TEST 7VCC 8IC2

AT24C02B

+5VC18

0.1UF

R24560

R8 10KR9

10K

+5V

R15

4.7K

R33

2K

R34

220

BUZZ

+12V

R28 560R29 560R26 560

R30 1K

+5V

R16

4.7K

C190.1UF

C13

0.1UF

+5V

R31 1K

R35

3.3K±1%

C5

0.01UF

C15

0.01UF

R32 1K

R23

20K ±1%

1234

CN6

S4B-XH

+5VC16

0.1UF

R17

4.7KR37

10K

+12V

R36

1K

E2

4.7uF/16V

E34.7uF/16V

R40

1K

RSRCK

RCKSER

COM3COM2

R25 560

R27 560

1

CON71

CON8

GND+5V

ABCD

CT50HZPGO

WFSTFLZYJHEAT

R101 1KR102 1K

R103 1K

SW2SW3

+5V

N12SC2412

N22SC2412

N3

2SC2412

P22SB1182

XT1 8M

12345678

CN7(1)

B8B-PH

C231nF

E8100uF/16V

RED

BLACK

CT50HZ

WF

FLZST

YJHEAT

PGO

1234567

CN7(2)B7B-PH

GND

+5V

R41 3.3K+5V

123456

CN7

B6B-PH-K

C170.1UF

R210K

+5V

R39

2KE1

4.7UF/16V

D13RLS4148

R494.7K

R534.7K

R544.7K

1 2 3 4

A

B

C

D

4321

D

C

B

A

CT

A057R

R52390

VRVR-101T-F

R51

1K

E6100UF/16V

R501K

D10

RLS4148

+5V

FUSE1

T3.15A-250VAC RV1

S14K350

C200.1UF-250VAC

D9

1N4007 C21

0.1UF

E5

470UF/16V

E4

1000UF/25V(35V)

Vin1

GN

D2

Vout 3IC4 1.5A-7805

C22

0.1UF

R4310K

R444.7K

C240.1UF

R42

10K

+5V

R454.7K

+5V

R464.7K

R474.7K

R48680

IC5 1A-600V-TLP3526+12V

K1G4A-1A(-E)

K2 835L-1AB-C

K3

OJE-SS H -112L D M

K5

OJE-SS H -112L D M

+12V+5V+12V

K4

OJE-SS H -112L D M

D11

RLS4148

D12

RLS4148

L L1

L

L1

1

EH2

1

C1

123

CN2

B3P5-VH

N

123

CN9

B3P5-VH

L1C263uF-450VAC

N

FUSE2

T10A-250VAC

1

C2

1

EH1

CT50HZPGO

WFSTFLZYJHEAT

L1 171UH-800MA-1KHZ

12

CN1

123

CN3AMP-171825-3

A1 K 2D4

1N4007D3

1N4007

D21N4007

D1 1N4007

N

R C

RC1 0.01uf-120

A 1K2D5

RLS4148D6

RLS4148D7

RLS4148D8

RLS4148

P3

2SA1037AK

N4

2SC2412

N52SC2412

BLUE

white

black

white

CT50HZ

WF

FLZST

YJHEAT

PGO

D14RLS4148

D15RLS4148

D16RLS4148

41

Page 46: aire haier

WIRING DIAGRAM FOR INDOOR UNITS

WIRING DIAGRAM FOR OUDOOR UNITS

Air Conditioner

HSU-09/12C13

sR

c

HSU-09/12C13

Edition:2006/01/09

42

Page 47: aire haier

Air Conditioner

WIRING DIAGRAM FOR INDOOR UNITS

WIRING DIAGRAM FOR OUDOOR UNITS

HSU-22C13

WIRING DIAGRAM 0010555054

3.The 1 is optional part

1.See above for wiring of heat pump type.2.There are no dotted lines on cool only type.(marked with @),Wire is connected from BR(marked with @@) on terminal block to W.

NOTE:

GREENG:

BL: BLUEWHITEW:YELLOWY:

BROWNBR:REDR:BLACKB:

BR

BR

CAPACITOR

CAPACITOR

R

R

W

W

W

W

W

1(L) 2(N) 3 4B

B

B

B

B

@@

@

@ @

Y/G

Y/G

TO INDOOR UNIT

TO INDOOR UNIT

fresh airDevice for

1

M

CSCOMPR

MOTOR

FAN

FOUR-WAYVALVE

HSU-18/22C13

HSU-18C13

Edition:2006/01/09

43

Page 48: aire haier

Air Conditioner Edition:2006/01/09

Sincere Forever

Haier GroupHaier Industrial Park, No.1, Haier Road

266101, Qingdao, China

http://www.haier.com

44