AirAirAirAir cooledcooledcooledcooled heatheatheatheat pumppumppumppump chillerchillerchillerchiller(with internal Hydraulic module)
2
ProductProductProductProduct OOOOvervievervievervieverviewwwwssss
This Air cooled heat pump chiller can be installed with fan coil units. One Chiller can match withmany indoor fan coil units. Compare to the spilt duct air conditioner, it has more advantages. Itbelongs to mini central air conditioning system and no need of special plant room. The indoor fancoil unit can be concealed installed (or semi-concealed).with high-end interior decoration, you canenjoy the elegant atmosphere as in high-class hotel, it is suitable for the dance halls, restaurants,bar, offices, high class clubs and all kinds of apartments.
Model Explanation
MSRA 4.0 H P CRefrigerant,C refers to R407c,R refers to R410A,The default one is R22
P:Internal Hydraulic module,default means
without Internal Hydraulic module
H:heat pump,C:cooling only,default is cooling
Only plus electrical heater.
4.0:Unit cooling capacity
MSRA:Mini air cooled heat pump chiller
3
Product Features� Easy to install;
The outdoor unit can be installed on the roof, wall or outdoor ground;
There is a connecting water pipe between the indoor unit and outdoor unit, easy to install and
flexible;
The indoor unit can be installed according to the environment decoration needs and personal
preferences, with various forms;
� Safety and environmental friendly, with low-cost
There is water pipe system in indoor unit, the initial installation cost is low and no extra cost for
the high cost refrigerant supplement.
The refrigerant is well sealed in the outdoor unit; the impact on the environment is much less than
the direct evaporation system;
� Flexible design, easy to control
There is no limitation on the height and length of the water pipe system.( but must within the
range of pump head), various types of fan coil unit can be chosen to meet the users’ requirement
and matching the decoration and personal taste. The supplied controller with operation display
screen---HART, using the vivid image and English interface, user can control the host unit and
monitor the parameter setting and operation status, easy to use and intuitive;
� With hydraulic module, easy for users
The specifically user-friendly designed of the unit with a hydraulic module system installed inside
the unit; users only need to connect the power, water pipe and the supplied accessories to use
the unit, greatly saves the installation space and time, and avoid the failures that may occur
during installation.
� Safe, reliable, easy connections
Single power connection and provides interlock connector to the pump, provide high / low alarm,
low water alarm, power recovery restart functions.
4
Product Components� Condensing coil
High purity seamless internal thread copper tube mechanically bonded together with the
aluminum fin in order to perform the best heat transfer effect.
The hydrophilic aluminum fin can effectively reduce the thickness condensing water film during
cooling operation, and reduce the thermal resistance, improving the coil heat transfer efficiency.
� Evaporator
We adopt the high efficient, compact, and corrosion-resistant MTB brazed plate heat exchanger,
the plate of which is made of AISI316 stainless steel plates, welded together in a vacuum
furnace. The plate heat exchanger manufacturing process can absolutely meet the cooling
system requirements of clean, dry and no leakage. The herringbone plates stacked in opposite
directions combine into plate heat exchanger, and the internal passage stable the water flow
which not only improve the heat transfer efficiency, and delayed the formation of dirt.
� Compressor
Use High-performance hermetic scroll compressor, with sophisticated manufacturing technology,
reliable performance, low noise, and high energy consumption.
� Hydraulic module
Save money, save time, save your energy: with innovative built in water system design, includes
the pumps, water filters, expansion tank, flow switch, pressure gauge, safety valve, exhaust
valve and all necessary hydraulic components, dramatically saving system initial investment,
design and installation. Just a wrench for coupling pipes, a screwdriver for coupling power,
non-professionals can complete professional installation quickly.
� Body structure
The frame and panel adopt panel insert mounting structure, the panel using electrostatic spray,
strong and generous, totally integrated with the control environment.
� Cooling Accessories
Use DANFOSS, SAGINOMIYA, ALCO and other well-known European and American brands
–control the cooling system self-control components, the quality is stability.
Refrigeration systems include high &low pressure switch, expansion valve, filter drier, solenoid
valve, vapor-liquid separator and other accessories.
5
Product Performance Data Sheet
Model
ItemMSRA4.0HPR MSRA5.0HPR MSRA7.5HPR MSRA12.5HP
Cooling
Nominal capacity kW 12.7 17.1 26 43
Input power kW 3.96 5.34 8.13 13.4
Running current A 13 17.5 26.7 44
Heating
Nominal capacity kW 14.9 19.8 27.3 43.5
Input power kW 4.65 6.18 8.5 13.6
Running current A 15.3 20.3 27.9 44.6
Power 220V~3PH~60Hz
Noise dB(A) 59 59 62 62
CompressorType High efficient scroll compressor
Qty 1 1 2 2
RefrigerationType R410
Charge qty kg 3.5 4.8 2*3.5 2*5.0
Throttling External balanced thermal expansion valve
Waterside heat
exchanger( for
user)
Type BPHE
Nominal water flow
ratem
3/h 2.2 2.95 4.47 7.4
Waterside pressure
dropkPa 40 40 43 45
Fan
Type low noise axial fan
Qty 2 2 2 2
Input power kW 0.06*2 0.06*2 0.2*2 0.55*2
Internal Hydraulic module(optional)water pump, filter, expansion water tank, flow valve,pressure
gauge,water drain valve
Water pumplift m 12 13 15 15
Input power kW 0.55 0.55 1.3 1.3
Closed
expansion tankWater volume l 5 8 9 10
Water pipe
connection
Inlet connector inch 1" 1" 1-1/4" 1-1/4"
Outlet connector inch 1" 1" 1-1/4" 1-1/4"
Water drain valve inch 1/2" 1/2" 1/2" 1/2"
Dimension
Width mm 1600 1600 1558 1500
Depth mm 485 485 882 1091
Height mm 1450 1450 1046 1181
Unit weight
With Hydraulic module kg 210 235 300 550
Without Hydraulic
modulekg 190 215 260 490
Note:
1. Cooling condition: water inlet &outlet temp.7℃&12℃,ambient 35°C.
2. Heating condition: water inlet &outlet temp.45℃&40℃,ambient 7°C.
3. The unit power includes the compressor, the fan and electrical control system.(exclude the water pump).
6
Installation and use instruction
Typical hydrographic chart without hydraulic module
Note:
1. Mini chiller without hydraulic module
2. Fan coil unit
3. Circulating water pump
5. Expansion water tank
6. Pressure gauge
7. Manual stop valve
8. Filter
9. Pressure connector
10. Thermometer
11. Water flow switch
12. Vent hole
13. Water drain valve
14. Water supplement valve
15. Flexible connector
16. Safety
7
Typical hydrographic chart with hydraulic module
Typical hydrographic chart with hydraulic module
Note:
1. Mini chiller without hydraulic module
2. Fan coil unit
4. Pressure gauge
5. Manual stop valve
6. Pressure connector
7. Thermometer
10. Water drain valve
11. Water supplement valve
12. Flexible connector
15. Safety
8
Typical water pipe connection
Unit with Internal Hydraulic module
1-11. Unit and the components of the internal hydraulic module
1. Clamp type water filter
2. Closed expansion water tank
3. Safety valve
4. Water pump (single or double)
5. Pressure test point and the vent valve (together with valve 7)
6. Pressure gauge (if not use, close valve 5, separate with the water cycle.)
7. System vent valve
8. Water flow switch
9. Water flow rate adjustment valve
10. Plate heat exchanger
11. Plate heat exchanger anti freeze electrical heater
12-24 other system hydraulic components
12. Vent valve
13. Thermometer bulb
14. Soft connector
9
15. Stop valve
16. System drain plug (offered by factory)
17. Pressure gauge (built in the unit)
18.Anit-freeze bypass damper ( if the valve will close at 15 ℃℃℃℃ degree in winter, so thevalve must be installed)
19. Water supplement valve
20. Plate heat exchanger water outlet
21. Plate heat exchanger water inlet
22. Unit water inlet
23. Unit water outlet
24. Clamp type connection pipe section for user (supplied by factory, with standard threadfor users to connect to or weld to water pipe onsite)
10
Dimension:MSRA4.0HPR- MSRA5.0HPR
MSRA7.5HPR
11
MSRA12.5HP
12
Design &Unit Selection1. According to the user's building type, orientation, function, size, structure and
so on conditions to calculate the cooling and heating load, then determine thechiller’s type and numbers for using.
2. According to user’s building’s layout, function, decoration, noise, fresh air flowrate and such conditions to select the model and the number of the AHU,confirm the AHU installation way and air distribution form.
3. The total sum up of the cooling (heating) capacity of the AHUs should be1.3~1.5 times bigger than the nominal cooling capacity on the chiller’snameplate.
4. Based on user’s building’s pattern and structure(plane function layout,floorheight, beams, columns and plates and etc), reasonably configure the supplyand return water piping system, try to reduce the water system resistance asmuch as possible and ensure the water force balance in each branch waterpiping work. The reversed supply and return water piping system isrecommended to use, and try to add the dia. Of the pipe to increase the watercapacity of the whole system.
5. Auto vent valves should be installed in the highest point of user’s side supplyand return water piping system and the partial rise up point.Water escape valveshould be installed in the lowest point. The stop valves should be installed in thewater inlet and outlet of the chiller. A filter should be installed in the front part of theinlet pipe.
6. The condensate water of user side should be drained out as close as possible,and try to reduce the condensate point.
Installation1. When handling, must take care on safety, and try to keep the unit be vertical,
when inclination needed, the angle of inclination should be less than 15 degree.2. The chiller must be installed in place with sufficient water source and good water
quality, no impurities are allowed to block on the chiller water source anddrainage.
3. The chiller can be installed in the outside of the building (anti-freeze actionsshould be taken in winter), or can be installed in the plant room, but there shouldbe enough space between the wall or other things so that can operate and serviceeasily.
4. Try to avoid installing in the place such as bedroom, study or living rooms whichwill affect the living environment to avoid the normal operation noise enter into theroom.
5. The Fan coil unit (AHUs) should be ceiling mounted on the solid and stablefoundation (e.g. floor). The installation must be leveling and no impurities areallowed in the water tray. The access panel should be left under the fan coil unitfor easy maintenance and service.
13
6. The supply and return water pipe should be straight and ensure the quality ofwelding and connection. The insulation should meet the water temperaturerequirement; anti-condensation protection should be carried out on thecondensate water pipe.
7. pressure withstand test should be carried out on the water system pipe afterinstallation finished, to ensure the leakproofness of the pipe; Flush the pipe ,ensure there is no welding slag, hemp, or sand left.
8. Anti-freeze actions should be made on the outdoor water pipe system and theaccessories.
NOTESIn order to keep the chiller always under good working status, and operate with highefficient, regular inspection and maintenance should be carried out.
1. Power supply checkIf the power supply in your area is not stable, pls check the power supplyregularly. Generally, the deviation of the power supply should not exceed 10%, ifexceed 10%, start the unit is not allowed. Or a voltage stabilizer should beinstalled before unit power. The selection of the voltage stabilizer better consultprofessional person. Casually installed a voltage stabilizer is strictly forbidden,the inaccurate installation will cause people injure or assets damage.
2. Filter checkOnly when the water under suitable flow rate, temperature, the unit can reliableand high efficient operates. If there is an indication of the water flow switch actions,besides check the water pump and the water valves, the filter also need to becheck to see whether there is any blockage. If so, clean the filter and reinstall it.Generally speaking, in the initial operation period, the clean cycle for the filter isshort, suggested to be 3-7 days. When the system is operated in long time, if thewater system still work stable, the water filter no need to clean in long time.
3. Water treatment equipment checkAfter long time operation, if the heat exchanger efficient of the heat exchanger isdecreased, besides check the water flow rate and temperature, whether there isdirty accumulation in the heat exchanger also need to be checked. If the watertreatment equipment loses the function of dirty clean or the efficient is decreased,it need to be clean or replaced.
4. after long time stop, check before start upThe following items should be checkeda). thoroughly check and clean the whole unitb). clean the filter, the water treatment equipment, the water pipe system thepump and valve in water systemc). check the power and the circuit.
14
5. daily energy saving suggestiona) in summer, the room temperature should not set too low, and in winter, not too
high;b) When unit running, pls close the door and winter and curtain to avoid direct
sunshine.c) Clean the water system regularly.d) Well protect the insulation material for the unit and water system, to avoid
unnecessary heating or cooling loss due to the insulation peel off or broken.6. If the main power switch had been cut off for long time, so 6 hours preheating for
the compressor is needed before start up.