Voltas is the pioneer and a leading provider of integrated end-to-end solutions in the field of electro-mechanical and refrigeration. We are committed to provide customers with technology that suits their needs. We have introduced a wide variety of air-cooled and water-cooled scroll chillers with R22 and R407C refrigerant options.

With ISO:9001 certified factories, Voltas possesses total capability in the manufacture of scroll chil le rs . These chillers are available in a wide range of capacities from 12 TR to 111 TR. They are easy to ins ta l l and commission, and can handle various cooling requirements, aided by multiple compressor configurations.

Voltas scroll chillers are an ideal choice for various air-conditioning applications, including office spaces, banks, hotels, hospitals, shopping malls, multiplexes, commercial complexes and process cooling.

MODEL NOMENCLATURE:

AC WC D S D M N 2044

AIR-COOLED

WATER-COOLED

DX CHILLER

SCROLLCOMPRESSOR

NOM. CAPACITY

048 = 48 TR

NO. OF COMPRESSORS PER CIRCUIT(FOR TANDEM MODEL)

NO. OF REF. CIRCUITS (FOR TANDEM MODEL)

N - STANDARD PANELA - ADVANCED BMS

MICROPROCESSOR-BASEDCONTROL PANEL

C - COPELAND COMPRESSOR D - DANFOSS COMPRESSOR - R22DP - DANFOSS COMPRESSOR - R407C

X 2

KEY FEATURES INCLUDE:1) Scroll Compressor with R22 and R407C Refrigerant Options

2) Energy Efficiency

3) Modular Design

4) Application Flexibility

5) Low Noise and Compact Design

6) Easy-to-use Microprocessor Panel and Controls

Page 3: Air-cooled & Water-cooled Scroll · PDF file · 2013-03-14air-cooled and water-cooled scroll chillers ... dx chiller scroll compressor nom. capacity 048 = 48 tr no. of compressors

ACDS077DPMN2X2

ACDS096DPMN2X2

77 96

4 4

100/75/50/25 100/75/50/25

DX DX

1 1

205 256

5" nps 5" nps

2 3

4 6

2625 3710

2236 2236

2590 2615

2562 2872

ACDS011DPMN1X1UNIT MODEL

*Nominal Capacity - TR

ACDS022DPMN2X1

ACDS034DPMN3X1

ACDS045DPMN2X2

CACDS066DPMN3X2

11 22 34 45 66

Compressor Qty.

Unit Capacity ReductionSteps in %

1 2 3 4 6

100/50 100/50 100/66.7/33.3 100/75/50/25100/83.3/66.7/50/33.3/

16.7

Evaporator Type

Evaporator Qty.

Evap. Water Flow Rate GPM (US)

Evap. Water NozzleSize**

DX DX DX DX DX

1 1 1 1 1

29 59 90 120 176

2-1/2" nps 3" nps 3" nps 4" nps 5" nps

Condenser Module Qty. 1 1 1 2 2

2 2 2 4 4

LENGTH (MM)

WIDTH (MM)

HEIGHT (MM)

Shipping Wt. Kg.

2500 2535 2535 2850 2625

650 1270 1270 2235 2236

1400 2310 2410 2590 2690

631 1033 1349 1961 2633

Note 1: * Capacity rated for evap. inlet water temp. 12 C leaving water temp. 7 C and at design ambient of 35 C Evap. water side fouling factor of 0.000018 m2 C/W. Power and control supply voltage ranges are 360-440 V and 210-240 V

respectively, and frequency 50Hz.

Note 2: ** Sizing of water piping to be done at site, based on operating tonnage and available pump head.

Note 3: For higher ambient applications, please contact us.

AIR-COOLED SCROLL CHILLERS R407C

TECHNICAL DATA

COMPRESSOR

EVAPORATOR

CONDENSER

No. of Fans

CHILLER PACKAGE PHYSICAL DATA

Page 4: Air-cooled & Water-cooled Scroll · PDF file · 2013-03-14air-cooled and water-cooled scroll chillers ... dx chiller scroll compressor nom. capacity 048 = 48 tr no. of compressors

OBEROI HOTEL, DELHIIISC, BANGALOREIISC, BANGALOREIISC, BANGALOREBHUSHAN STEEL LTD., KOLKATA

MICROPROCESSOR-BASED LCD CONTROLLER:

Three Modes of Operation:• Auto Mode: Auto start-and-stop, programmable for the entire year. Hence there is no need for any operator interface.

• Auto Mode facilitates auto restart on power restoration after load shedding or grid supply failure.

• Semi-auto Mode: Manual, single button start-and-stop, since further sequence is programmed.

• Manual (Test) Mode: Facilitates testing under supervision.

Equalization of Compressor Runtime

• The Microprocessor Controller ensures equal running of compressors in multiple compressor units. This ensures longer life of compressors.

All chillers are equipped with microprocessor controls that provide the following benefits:

Page 5: Air-cooled & Water-cooled Scroll · PDF file · 2013-03-14air-cooled and water-cooled scroll chillers ... dx chiller scroll compressor nom. capacity 048 = 48 tr no. of compressors

Controls and Interlocks

• The chilled water pump is interlocked with compressors.• The safety controls are preset at factory while operating controls are field adjustable, depending on actual operating requirements.

Optional Features

• Communication port RS485 for remote connectivity, status and fault indication.• Advanced BMS with ASCII or RTU MODBUS protocol can be linked to Integrated Building Management System (IBMS).• Limited hardware BMS for remote control operation.• Dual-mode chillers for thermal storage system.

Safety and Protection• Microcomputer Motor Protection Device (uMPD) and Microcomputer Voltage Protection Device (uVPD) protect chillers from phase unbalance, phase loss, treversal, overload,under / over voltage and supply failure.

• Programmed safety features available using sensitive and accurate temperature which protects the system from: • Freezing • Low Pressure • Anti-recycle • Low Chilled Water Temperature • High Pressure • Inlet and Outlet Temperature for Chiller • Sensor Error • Low Water Flow in Condenser, Chiller

User-friendly Operation

• Interface with keypad and 32 character LCD display.• Gives visual annunciation for safety trips.

Self-diagnosis Function• Digital display of all vital parameters such as: • Outlet temperature for Chillers • Current • Voltage • Compressor run hours

• Diagnose mode for easy trouble shooting shows alarm history for the last 5 trips with date, time and cause of failure.

EMAMI, KOLKATAHONDA R&D, DELHIHONDA R&D, DELHIHONDA R&D, DELHITATA POWER, MUMBAI

Page 6: Air-cooled & Water-cooled Scroll · PDF file · 2013-03-14air-cooled and water-cooled scroll chillers ... dx chiller scroll compressor nom. capacity 048 = 48 tr no. of compressors

R22

R407C

R407C

R410A

R410A

R22

EIGHT POWERFUL FEATURES:

Voltas chil lers are available in a wide range of models, with R407C and R22 r e f r i ge ran t s .

Higher Energy Efficiency - Tandem Compressor ModelsScroll chillers from 48 TR to 111 TR use compressors operating in tandem. This improves the operat ing efficiency during part load periods, since the entire condenser area is utilized for heat reject ion, even though only one compressor may be in operation.

Capacity Modulation Multiple compressors are used in most of the models, with independent refrigerant circuits. The microprocessor cont ro l le r ensures that only the required number of compressors operate during part load conditions, thereby saving power.

Operating ReliabilityThe compressor is a no-contact scroll design with the motor, cooled by the suction gas. Higher capacity scroll chi l lers use tandem compressors with suction gas distribution restrictor, which allows balanced operat ion o f compressor. The chillers are charged and tested in the factory prior to dispatch, thus enhancing operating reliability.

Energy EfficiencyA range of sophisticated components such as highly energy-efficient, imported compressor, superior design of water-cooled condenser and chiller, internally grooved, cross-hatched copper tube coil with matched circuitry, and a microprocessor controller, results in low power consumption.

Quiet OperationThe chillers use ultra-quiet, high efficiency scroll compressors. The condenser fans are designed for low noise levels.

Easy to InstallThe chillers are pre-wired, fully charged and run-tested at the factory, saving installation and start-up time.

Voltas Countrywide After-Sales ServiceA nationwide service network backs every unit. After the initial warranty period, Voltas offers annual service schemes. More than 90% of the customers have opted for these schemes. You cannot get better insurance.

SCROLL CHILLERS

AIR-COOLED CHILLERS

WATER-COOLED CHILLERS

13 TR 26 TR 39 TR 52 TR 78 TR 111 TR

13 TR 26 TR 39 TR 52 TR 77 TR

Will be available shortly

11 TR 22 TR 34 TR 45 TR 66 TR 77 TR 96 TR

12 TR 24 TR 36 TR 48 TR 72 TR 83 TR 100 TR

Will be available shortly

Page 7: Air-cooled & Water-cooled Scroll · PDF file · 2013-03-14air-cooled and water-cooled scroll chillers ... dx chiller scroll compressor nom. capacity 048 = 48 tr no. of compressors

AIR-COOLED SCROLL CHILLERS R22

ACDS012DMNUNIT MODEL

*Nominal Capacity - TR 12 24 36 48 72 83 100

COMPRESSOR

EVAPORATOR

CONDENSER

Compressor Qty.

Unit Capacity ReductionSteps in %

1 2 3 4 6 4 4

100/50 100/50 100/66.7/33.3 100/75/50/25100/83.3/66.7/50/33.3/

16.7100/75/50/25 100/75/50/25

Evaporator Type

Evaporator Qty.

Evap. Water Flow Rate GPM (US)

Evap. Water NozzleSize**

DX DX DX DX DX DX DX

1 1 1 1 1 1 1

32 64 96 128 192 221 266

2-1/2" nps 3" nps 3" nps 4" nps 5" nps 5" nps 6" nps

Condenser Module Qty.

No. of Fans

1 1 1 2 2 2 3

2 2 2 4 4 4 6

UNIT DIMENSION & WEIGHTS

LENGTH (MM)

WIDTH (MM)

HEIGHT (MM)

Shipping Wt. Kg.

2500 2535 2535 2850 2625 2625 3900

650 1270 1270 2235 2236 2236 2236

1400 2310 2310 2690 2690 2690 2590

631 1034 1300 1961 2634 2515 2868

ACDS024DMN

ACDS036DMN

ACDS048DMN2X2

CACDS072DMN3X2

ACDS083DMN2X2

ACDS100DMN2X2

Note 1: * Capacity rated for evap. inlet water temp. 12 C leaving water temp. 7 C and at design ambient of 35 C Evap. water side fouling factor of 0.000018 m2 C/W. Power and control supply voltage ranges are 360-440 V and 210-240 V

respectively, and frequency 50Hz.

Note 2: ** Sizing of water piping to be done at site, based on operating tonnage and available pump head.

Note 3: For higher ambient applications, please contact us.

Page 8: Air-cooled & Water-cooled Scroll · PDF file · 2013-03-14air-cooled and water-cooled scroll chillers ... dx chiller scroll compressor nom. capacity 048 = 48 tr no. of compressors

UNIT MODEL

*Nominal Capacity - TR

WATER-COOLED SCROLL CHILLERS R22

COMPRESSOR

Compressor Qty.

Unit Capacity ReductionSteps in %

Evaporator Type

Evaporator Qty / Unit

Evap. Water Flow Rate GPM (US)

Evap. Water NozzleSize**

Condenser Qty / Unit

Condenser Water FlowRate GPM (US)

UNIT DIMENSION & WEIGHTS

WCDS013DMN

WCDS026DMN

WCDS039DMN

WCDS052DMN2X2

WCDS078DMN3X2

WCDS111DMN2X2

13 26 39 52 78 111

Cond. Water Nozzle Size**

LENGTH (MM)

WIDTH (MM)

HEIGHT (MM)

Shipping Wt. Kg.

1 1/4" nps 1 1/4" nps 1 1/4" nps 2-1/2" nps

2000 2000 2500 2500 2500 3000

1300 1400

2100 19001700

950950

15351450

850850

1050

540 824 2345 267015451150

1 2 3 4

100 100/50 100/66.7/33.3 100/75/50/25

DX DX DX

1 1 1

35 69 104

2-1/2" nps 3" nps 3" nps

1 2 3 2

43 85 128 171

EVAPORATOR

DX DX

1 1

207 295

5" nps 6" nps

100/83.3/66.7/50/33.3/16.7

100/83.3/66.7/50/33.3/16.8

CONDENSER

DX

6 4

1

138

4" nps

2-1/2" nps 6" nps

3 1

256 365

Note 1: * Capacity rated for evap. inlet water temp. 12 C, leaving water temp. 7 C,Evap. water s ide fouling factor

of 0.000018 m2 C/W and condenser water side fouling factor of 0.000044 m2 C/W. Power and control supply voltage ranges are

360-440 V and 210-240 V respectively and frequency 50Hz.

Note 2: ** Sizing of water piping to be done at site, based on operating tonnage and available pump head.

Page 9: Air-cooled & Water-cooled Scroll · PDF file · 2013-03-14air-cooled and water-cooled scroll chillers ... dx chiller scroll compressor nom. capacity 048 = 48 tr no. of compressors

Note 1: * Capacity rated for evap. inlet water temp. 12 C, leaving water temp. 7 C,Evap. water s ide fouling factor

of 0.000018 m2 C/W and condenser water side fouling factor of 0.000044 m2 C/W. Power and control supply voltage ranges are

360-440 V and 210-240 V respectively, and frequency 50Hz.

Note 2: ** Sizing of water piping to be done at site, based on operating tonnage and available pump head.

*Nominal Capacity - TR

Compressor Qty.

Unit Capacity ReductionSteps in %

Evaporator Type

Evaporator Qty.

Evap. Water Flow Rate GPM (US)

Evap. Water NozzleSize**

Condenser Qty / Unit

Condenser Water FlowRate GPM (US)

ACWCDS013DPMN1X1

ACWCDS039DPMN3X1

ACWCDS052DPMN2X2

ACWCDS077DPMN3X2

13 26 39 52 77

Cond. Water Nozzle Size**

LENGTH (MM)

WIDTH (MM)

HEIGHT (MM)

Shipping Wt. Kg.

1 1/4" nps 1 1/4" nps 1 1/4" nps 2" nps 2" nps

2350 2400 2500 2500 2500

1350

21501800

10001100

13001450

850850

1050

552 846 240415881196

1 2 3 4 6

100 100/50 100/66.7/33.3 100/75/50/25100/83.3/66.7/50/

33.3/16.7

DX DX DX DX DX

1 1 1 1 1

35 69 104 138 205

2-1/2" nps 3" nps 3" nps 4" nps 5" nps

1 2 3 2 3

43 86 128 171 253

UNIT MODEL ACWCDS026DPMN2X1

COMPRESSOR

EVAPORATOR

CONDENSER

CHILLER PACKAGE PHYSICAL DATA

WATER-COOLED SCROLL CHILLERS R407C

Page 10: Air-cooled & Water-cooled Scroll · PDF file · 2013-03-14air-cooled and water-cooled scroll chillers ... dx chiller scroll compressor nom. capacity 048 = 48 tr no. of compressors

NORTH ZONE: DELHI (011) 66505550 / 66505657 / 66505680 / 66505683 / 66505684 CHANDIGARH (0172) 6610124 / 6610135 JAIPUR (0141) 6451756 / 6541011 LUCKNOW (0522) 237869 / 6546629 EAST ZONE: KOLKATA (033) 66266280 66266264 / 66266268 BHUBANESHWAR (0674) 6574044 JAMSHEDPUR (0657) 2427642 PATNA (0612) 2500786 WEST ZONE: MUMBAI (022) 66656754 / 66656756 / 66656757 / 66656760 GOA 09860976942 NAGPUR (0712) 6 4 6 4 6 9 2 PUNE (020) 66046607 / 66046447 AURANGABAD (020) 66046607 AHMEDABAD (079) 66301107 / 6 6 3 0 1 1 0 2INDORE (0731) 2498616 SOUTH ZONE: HYDERABAD (040) 66743007 / 66743033 VIJAYAWADA (0866) 2431507 CHENNAI (044) 66760349 / 66760357 BANGALORE (080) 67132637 / 67132639 KOCHI (0484) 6605553

VOLTAS LIMITEDEM&R Business Group Sales Headquarters Voltas House 'B', 3rd Floor, T.B. Kadam Marg, Chinchpokli, Mumbai - 400 033Tel: +91 22 66656666 / 66656552 Fax: +91 22 66656930 Email: [email protected] | www.voltas.com

ENERGY EFFICIENTWATER-COOLED SCREW CHILLER

AIR-COOLED RECIPROCATINGCHILLER

WATER-COOLED RECIPROCATINGCHILLER

PRODUCT RANGE

VARIABLE REFRIGERANT FLOW (VRF)SYSTEM

COGENERATION VAM

IAQ & ENERGY REDUCTIONSYSTEM

COILOTRON (UV FOR AHU COILS)

AIR-HANDLING UNIT

ENERGY EFFICIENTAIR-COOLED SCREW CHILLER

DOUBLE EFFECT VAM

GERMITRON (DUCT MOUNTED UV)

KITCHEN EA DEODOURISATION SYSTEMSTP EA ODOUR / H2S REMOVAL SYSTEM

PACKAGED & DUCTABLE SPLIT UNIT