AIR CONDITIONING SYSTEM

20
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced. 2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor. Cautions on product corrosion Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion. Read the user's manual carefully before using this product. The user's manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings. If you have any enquiries, please contact your local importer, distributor and/or retailer. COOLING ONLY [50Hz] AIR CONDITIONING SYSTEM DIDSI2009 • SERVICE AND SPARE PARTS : Jakarta Selatan, Telp. : 021-2782 5545 Cirebon, Telp. : 0231-880 2760 | Samarinda, Telp. : 0541-252 2889 | Banjarmasin, Tlp. : 0511-326 8168 • TRAINING CENTER : Sunter, Telp. : 021-650 5028 • BRANCH : Bekasi, Telp. :021-2945 0585 Tangerang, Telp. : 021-5314 1195 | Bandung, Telp. : 022-522 5150 | Semarang, Telp. : 024-7660 3221 Yogyakarta, Telp. : 0274-551 321 | Surabaya, Telp. : 031-503 1138 | Denpasar, Telp. : 0361-900 5514 Makassar, Telp. : 0411-805 2691 | Palembang, Telp. : 0711-573 2282 | Pekanbaru, Telp. : 0761-561 139 Medan, Telp. : 061-4200 8866 | Manado, Telp. : 0341-719 1199 Specifications, designs and other content appearing in this brochure are current as of August 2020 but subject to change without notice.

Transcript of AIR CONDITIONING SYSTEM

Page 1: AIR CONDITIONING SYSTEM

1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.

Cautions on product corrosion

Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.

Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.

Read the user's manual carefully before using this product. The user's manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.

If you have any enquiries, please contact your local importer, distributor and/or retailer.

COOLING ONLY [50Hz]AIR CONDITIONING SYSTEM

DIDSI2009

• SERVICE AND SPARE PARTS : Jakarta Selatan, Telp. : 021-2782 5545Cirebon, Telp. : 0231-880 2760 | Samarinda, Telp. : 0541-252 2889 | Banjarmasin, Tlp. : 0511-326 8168• TRAINING CENTER : Sunter, Telp. : 021-650 5028 • BRANCH : Bekasi, Telp. :021-2945 0585Tangerang, Telp. : 021-5314 1195 | Bandung, Telp. : 022-522 5150 | Semarang, Telp. : 024-7660 3221Yogyakarta, Telp. : 0274-551 321 | Surabaya, Telp. : 031-503 1138 | Denpasar, Telp. : 0361-900 5514Makassar, Telp. : 0411-805 2691 | Palembang, Telp. : 0711-573 2282 | Pekanbaru, Telp. : 0761-561 139Medan, Telp. : 061-4200 8866 | Manado, Telp. : 0341-719 1199

Specifications, designs and other content appearing in this brochure are current as of August 2020 but subject to change without notice.

Page 2: AIR CONDITIONING SYSTEM

21

Designed for use in cafe and restaurants, retail shops and small offices.

Daikin’s SkyAir series delivers superior comfort

and energy performance

for both occupants and building owners.

Page 3: AIR CONDITIONING SYSTEM

Cooling onlyCooling only

New Inverters launched

Previous non-inverter series R22 <cassette type>

New inverter RZFC-D series R32 <cassette type>

4.90 4.90

RZFC40DVM4Inverter

Non Inverter R18NUV1R35GV1 R30NUV1 / Y1R21NUV1 R26NUV1 / Y1 R36NUV1 / Y1 R42NUY1 R48NUY1

RZFC50DVM4

RZFC60DVM4

RZFC71DVM4 / Y14

RZFC85DVM4 / Y14

RZFC100DVM4 / Y14

RZFC125DY14

RZFC140DY14

CSPFValue

Comparison of cooling seasonal power consumptionbased on average CSPF values

Coo

ling

seas

onal

po

wer

con

sum

ptio

n

New inverter RZFC-D series(average)

Previous non-inverter series(average)

100

65

Note: Value 100 represents the amount of electricity used by a non-inverter model during a similar annual cooling period.

(cassette type)(cassette type)

4.674.10

4.674.29

2.63 2.79

4.67

2.77

5.13

2.69 2.79 2.732.71

6

5

4

3

2

1

0

CSPF values by capacity for cassette models

35%reduction!

What is CSPF?CSPF is the value for the annual total cooling load divided by the annual total power consumption at outdoor air conditions specified by ISO standard.

*CSPF (cooling seasonal performance factor) is a new international energy-efficiency criterion calculated by methods stipulated in ISO 16358-1.

3.10

Throughout the cooling season,Daikin’s new inverter models reduce energy consumptionCompared with previous non-inverter series, the new RZFC-D series uses about 35% less power consumption for quick and effective cooling that reduces electricity bills.

Energy Saving Tota

l cos

t =un

it pr

ice

+ c

ost o

f ele

ctric

ity

Time

InverterNon inverter

Roomtemperature

Time

Too hot

Set temperature

Smalltemperaturefluctuation

Too coldToo cold

Largetemperaturefluctuation

Comfortable

Non inverter

Non inverter

Inverter

Non inverter

Inverter control responds to load changes and causes minor temperature adjustments. Non-inverter control frequently turns ON and OFF in response to load fluctuations or load mismatch and causes large temperature swings.

Cap

acity

Load

0

Non inverter cooling capacity

Inverter cooling capacity

On/Off operation

Lower efficiency

Partial load area

Rated condition

Outdoor ambient temperature (°C)35

Cooling load

Continuous driving without stopping and starting is more fuel efficient.

Highway drivingInverterConstantly stopping and starting consumes energy and is less fuel efficient.

City drivingNon inverterStop, go, stop ...

Recovery point

Inverters save more energy over time

Inverter system consumes less electricity, and soon recovers the difference in initial cost. This results in lower total cost.

Inverter air conditioner can adjust its cooling capacity according to the cooling load. This results in less power consumption.

Inverters operate without repeated ON/OFF operation.

Why is inverter technology economical?Why is inverter technology economical?

Why is inverter technology more comfortable?Why is inverter technology more comfortable?

In response to fluctuating cooling load, Non inverter air conditioners repeatedly perform ON (full-power)/OFF (zero-power) operation. Inverter air conditioners, however, operate at optimal cooling capacity according to the cooling load. Since inverter air conditioners provide required minimum cooling capacity with minimum electrical power, total power consumption can be reduced during cooling period.

When temperature does not fluctuate much, the set temperature is maintained.

Inverter

Benefits of Inverter

43

Page 4: AIR CONDITIONING SYSTEM

Durability

100mm or

more

100mm or more 100mm or

more500mm or

more

Microchannel technology utilises superior heat transfer benefits of aluminium to create a more efficient air conditioner.With a new resistance corrosion aluminium alloy, the Daikin microchannel heat exchanger becomes highly durable.A salt spray test has been conducted to demonstrate the corrosion-resistant capability of our products in corrosive environments for a certain period of time.

After undergoing an intensive test, the Daikin microchannel heat exchanger is able to maintain its shape without corrosion, which strongly confirms its durability in a highly corrosive environment.

Microchannel heat exchanger

Outdoor unit installation is possible even with limited space

Test of durability- Testing organization - Testing standard- Result

MTEC ThailandASTM B117

Before testing After testing

Normalobservation

No evidence of corrosion was observed

Undertelescope

Coated circuit boards prevent problems caused by humidity and airborne dust.It also protects against salt contained in sea breezes.Both sides of the PCB in outdoor units are coated.

Coated printed circuit boards(outdoor unit)

In AM and PM peak electricity consumption periods, supply may fluctuate. Built-in low-voltage protection will automatically cut operations. When normal voltage is restored, operation will resume as before.

Automatic protection against low voltage

*FHFC40-85D requires optional adaptor to connect DIII-Net.

Possible to forced OFF and ON/OFF operation using external command

Indoor units (FCFC-D, FHFC100-140D, and FBFC-D) comply with D -Net standards

Design Flexibility

VRV

New indoor unit

Easy connection to DIII-NET and long piping length makes this solution suitable for projects including and SkyAir.

Adaptor notrequired

*Field setting with remote controller

Please see a video of the Micro Channel Heat Exchanger test in Pattaya.

QRspace

Interlock

Duct connection middle static pressure typeRound flow cassette type

Interlock

Lighting

65

Page 5: AIR CONDITIONING SYSTEM

Cooling only

Product Lineup

FCFC85DVM4

85 100 125 140

FCFC100DVM4 FCFC125DVM4 FCFC140DVM4

FHFC85DV14 FHFC100DV14 FHFC125DV14 FHFC140DV14

RZFC100DVM4 RZFC100DY14 RZFC125DY14 RZFC140DY14

1 phase, 220-240 / 220-230V,

50 / 60Hz

3 phase, 380-415V,

50Hz

1 phase, 220-240 / 220-230V,

50 / 60Hz

3 phase, 380-415V,

50Hz

3 phase, 380-415V,

50Hz

3 phase, 380-415V,

50Hz

RZFC85DVM4 RZFC85DY14

RZFC100DVM4 RZFC100DY14 RZFC125DY14 RZFC140DY14RZFC85DVM4 RZFC85DY14

RZFC100DVM4 RZFC100DY14 RZFC125DY14 RZFC140DY14RZFC85DVM4 RZFC85DY14

RZFC85DVM4 RZFC85DY14

RZFC85DVM4 RZFC85DY14

RZFC100DVM4 RZFC100DY14 RZFC125DY14 RZFC140DY14RZFC85DVM4 RZFC85DY14

FDBF85DV14

FDLF85DV14

FBFC85DVM4 FBFC100DVM4 FBFC125DVM4 FBFC140DVM4

40

RZFC40DVM4

FCFC40DVM4

CEILING MOUNTED CASSETTE TYPE

Round Flow

CEILING SUSPENDED TYPE

Outdoor unit

Indoor unit

FHFC40DV14

Outdoor unit

Indoor unit

OUTDOOR UNIT

Power supply1 phase,

220-240 / 220-230V, 50 / 60Hz

1 phase, 220-240 / 220-230V,

50 / 60Hz

1 phase, 220-240 / 220-230V,

50 / 60Hz

1 phase, 220-240 / 220-230V,

50 / 60Hz

3 phase, 380-415V,

50Hz

Outdoor unit

50

RZFC50DVM4

FCFC50DVM4

FHFC50DV14

60

RZFC60DVM4

FCFC60DVM4

FHFC60DV14

71

FCFC71DVM4

FHFC71DV14

RZFC71DVM4 RZFC71DY14

RZFC40DVM4 RZFC50DVM4 RZFC60DVM4 RZFC71DVM4 RZFC71DY14

RZFC40DVM4 RZFC50DVM4 RZFC60DVM4 RZFC71DVM4 RZFC71DY14

DUCT CONNECTION LOW STATIC PRESSURE WIDTH COMPACT TYPE

DUCT CONNECTION LOW STATIC PRESSURE HEIGHT COMPACT TYPE

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

Outdoor unit

Indoor unit

RZFC40DVM4 RZFC50DVM4 RZFC60DVM4 RZFC71DVM4 RZFC71DY14

Outdoor unit

Indoor unit

RZFC40DVM4 RZFC50DVM4 RZFC60DVM4 RZFC71DVM4 RZFC71DY14

Outdoor unit

Indoor unit

RZFC40DVM4 RZFC50DVM4 RZFC60DVM4 RZFC71DVM4 RZFC71DY14

FDBF40DV14 FDBF50DV14 FDBF60DV14 FDBF71DV14

FDLF40DV14 FDLF50DV14 FDLF60DV14 FDLF71DV14

FBFC40DVM4 FBFC50DVM4 FBFC60DVM4 FBFC71DVM4

87

NEW

NEW

NEW

Page 6: AIR CONDITIONING SYSTEM

Power supply

SPECIFICATION (1 Phase)

Model Name

Indoor unit

Outdoor unit

Outdoor unit

40 50 60 71 85 100

Cooling Capacity 1,2

Rated (Min. - Max.) kW

Btu/h

COP kW/kWCSPF Wh/Wh

Certified Operation range

°CWBCertified Operation range

Motor outputCompressor

Coil

Dimensions(HXWXD)

Colour

mmmm

dB(A)

kWRefrigerant charge (R32) kg

dB(A) 48 49 50 51 52mmkg

°CDBmmmmmmmmmm

Dimensions (HXWXD)Machine weight

Unit

Piping connections

Liquid (Flare)Gas (Flare)

Drain Indoor unitOutdoor unit

Decoration panel

UnitDecoration panel

Airflow rate(H / M / L)

m3/mincfm

Outdoorunit

Colour

Heat insulation

Max. interunit piping lengthMax. installation level difference

Type

Sound pressure level 3 Cooling

Sound pressure level 3 (H / M / L)

Indoor unit

Type

1 Phase, 220–240 / 220-230V, 50 / 60Hz

4.0(1.8-4.5)

5.0(2.3-5.6)

6.0(2.6-6.3)

7.1(3.2-8.0)

8.5(4.2-10.0)

10.0(5.0-11.2)

13,600(6,100-15,400)

1.26 1.57 1.89 2.38 2.85

38 / 34 / 2937 / 34 / 28 45 / 38 / 33

3.353.18 2.98

5.13 4.90 4.67

17,100(7,800-19,100)

20,500(8,900-21,500)

White

19 / 14 / 11671 / 494 / 388

37 / 32 / 28

19

23 / 18 / 13 34 / 27 / 20812 / 635 / 459 1,200 / 953 / 706

298X840X840

22 24

1.20 1.30 1.60

Fresh white

Ivory whiteMicro channel

Hermetically sealed swing type

256X840X84050X950X950

5.514 to 25

21 to 46

24,200(10,900-27,300)

29,000(14,300-34,100)

34,100(17,100-38,200)

FCFC40DVM4

RZFC40DVM4

FCFC50DVM4

RZFC50DVM4

FCFC60DVM4

RZFC60DVM4

FCFC71DVM4

RZFC71DVM4

FCFC85DVM4

RZFC85DVM4

FCFC100DVM4

RZFC100DVM4

Machine weight kg

kgUnitDecoration panel

0.7 (Charged for 10 m) 0.8 (Charged for 10 m)

595X845X300 695X930X350

1.0 (Charged for 15 m)

34 37 44

6.4 9.512.7 15.9

301530 (Equivalent length 40) 50 (Equivalent length 70)

VP20 (I.D. 20XO.D. 26)18.0 (Hole)

Both liquid and gas piping

Power consumption Cooling 1 kW

Sound pressure level 3 Cooling

WhiteFresh white

Ivory white

34 / 27 / 2023 / 18 / 13 36 / 29 / 211,200 / 953 / 706812 / 635 / 459 1,271 / 1,024 / 741

Micro channelHermetically sealed swing type

1.60 2.40

256X840X840 298X840X840

22 2450X950X950

5.514 to 25

21 to 46

SPECIFICATION (3 Phase)

Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).2Capacities are net, including a deduction for cooling for indoor fan motor heat.3The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.

125 1401008571

1.0 (Charged for 15 m) 1.35 (Charged for 15 m)

695X930X350 990X940X320

46 62

9.515.9

30

50 (Equivalent length 70)

VP20 (I.D. 20XO.D. 26)18.0 (Hole) 26.0 (Hole)

Both liquid and gas piping

Power supply

Model Name

Indoor unit

Outdoor unit

Outdoor unit

Cooling Capacity 1,2

Rated (Min. - Max.) kW

Btu/h

COP kW/kWCSPF Wh/Wh

Certified Operation range

°CWBCertified Operation range

Motor outputCompressor

Coil

Dimensions(HXWXD)

Colour

mmmm

dB(A)

kWRefrigerant charge (R32) kg

dB(A) 50 51 52 54 56mmkg

°CDBmmmmmmmmmm

Dimensions (HXWXD)Machine weight

Unit

Piping connections

Liquid (Flare)Gas (Flare)

Drain Indoor unitOutdoor unit

Decoration panel

UnitDecoration panel

Airflow rate(H / M / L)

m3/mincfm

Outdoorunit

Colour

Heat insulation

Max. interunit piping lengthMax. installation level difference

Type

Sound pressure level 3 (H / M/ L)

Indoor unit

Type

3 Phase, 380-415V, 50Hz

7.1(3.2-8.0)

24,200(10,900-27,300)

2.38 2.85 3.35 4.70 5.88

37 / 34 / 28 38 / 34 / 29 45 / 38 / 33 46 / 40 / 33

2.98 2.66 2.384.67 4.29 4.10

FCFC71DVM4

RZFC71DY14

8.5(4.2-10.0)

29,000(14,300-34,100)

FCFC85DVM4

RZFC85DY14

10.0(5.0-11.2)

34,100(17,100-38,200)

FCFC100DVM4

RZFC100DY14

12.5(5.7-14.0)

42,700(19,500-47,800)

FCFC125DVM4

RZFC125DY14

14.0(6.2-15.5)

47,800(21,200-52,900 )

FCFC140DVM4

RZFC140DY14

Machine weight kg

kgUnitDecoration panel

Power consumption Cooling 1 kW

CEILING MOUNTED CASSETTE TYPE Round Flow

FCFC40/50/60/71/85/100/125/140DVM4

Accessory required for indoor unit.

Option

BRC2E61

Simplified Remote Controller (Wired Remote Controller)

Note: Remote controller cable is not included and must be obtained locally.

NEW

A signal receiver must be added to the indoor unit.

Wireless remote controller is supplied in a set with a signal receiver.

Wireless remote controller

Signal receiver unit (Installed type)

BRC7F635FCooling only

Cassette air conditioner with 360° uniform airflow sets the standardCassette air conditioner with 360° uniform airflow sets the standard

BYCQ125EAF

KDBH551C160

KDBH552C160

KDB55J160F

KDDP55B160 (KDDP55C160-1, KDDP55B160-2) 4

KDDP55B160K (KDDP55C160-1, KDDP55B160K2) 4

KDDP55X160A

KDDFP55C160

KAF5511D160

KAF555D160

KAF550D160

KAF556D160KAF556D80

KAF557D160KAF557D80

KAF552D160KAF552D80

KAF553D160

KDJP55C160

KAF553D80

KDJP55C80

KDTP55K160AKDTP55K80A

FCFC40DVM4FCFC50DVM4FCFC60DVM4

FCFC71DVM4FCFC85DVM4

FCFC100DVM4FCFC125DVM4FCFC140DVM4

Name of option Remark

Kit name

Option List

Fresh whiteDecoration panel

Panel spacer

Filter chamber

Replacement long-life filter

Ultra long-life filter unit (Including filter chamber)

Replacement ultra long-life filter 5

Branch duct chamber

Insulation kit for high humidity 612

11

10

9

8

6

2

4

5

1

7

3

Sealing material of air discharge outlet

Fresh air intake kit

For usage of 3-, 4-way flow

For usage of 2-way flow

High-efficiency filter unit(Including filter chamber)

(Colorimetric method 65%)

(Colorimetric method 90%)

Replacement high-efficiency filter 5(Colorimetric method 65%)

(Colorimetric method 90%)

Direct installation type 3

Without T-duct jointChambertype 1,2

With T-duct joint

Standard panel

Note: 1When installing a fresh air intake kit (chamber type), two air outlet corners are closed.2It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit. Introducing higher quantities will increase the operating sound and may also influence temperature sensing.

3The volume of fresh air for direct installation type is approximately 1% of the indoor unit airflow. The chamber type is recommended when more fresh air is necessary.

4Please order using the names of both components instead of set name.5Filter chamber is required.6Please use in case temperature/humidity inside ceiling may get over 30˚C, 80% RH.

No.

109

Page 7: AIR CONDITIONING SYSTEM

40 50 60 71 85 100

Sound pressure level 3 Cooling

SPECIFICATION (1 Phase)

Power supply

Model Name

Indoor unit

Outdoor unit

Outdoor unit

Cooling Capacity 1,2

Rated (Min. - Max.) kW

Btu/h

COP kW/kWCSPF Wh/Wh

Certified Operation range

°CWBCertified Operation range

Motor outputCompressor

Coil

Dimensions (HXWXD)

Colour

mmdB(A)

kWRefrigerant charge (R32) kg

dB(A) 48 49 50 51 52mmkg

°CDBmmmmmmmmmm

Dimensions (HXWXD)Machine weight

Unit

Piping connections

Liquid (Flare)Gas (Flare)

Drain Indoor unitOutdoor unit

Unit

Airflow rate(H / M / L)

m3/mincfm

Outdoorunit

Colour

Heat insulation

Max. interunit piping lengthMax. installation level difference

Type

Sound pressure level 3 (H / M / L)

Indoor unit

Type

1 Phase, 220–240 / 220-230V, 50 / 60Hz

4.0(1.8-4.5)

5.0(2.3-5.6)

6.0(2.6-6.3)

7.1(3.2-8.0)

8.5(4.2-10.0)

10.0(5.0-11.2)

13,600(6,100-15,400)

1.33 1.67 2.00 2.50 2.99 3.523.00 2.84

4.51 4.30 4.09

17,100(7,800-19,100)

20,500(8,900-21,500)

White13 / --- / 10 17 / --- / 14 24 / --- / 20 30 / --- / 25 28 / 24 / 20

459 / --- / 353 600 / --- / 494 847 / --- / 706 1,059 / --- / 883 988 / 847 / 70638 / --- / 33 39 / --- / 35

195X1,160X680 195X1,400X680 195X1,590X680 235X1,590X69042 / --- / 37 44 / --- / 39 42 / 38 / 34

1.20 1.30 1.60

Ivory whiteMicro channel

Hermetically sealed swing type

195X960X68027 32 35 3825

24,200(10,900-27,300)

29,000(14,300-34,100)

34,100(17,100-38,200)

FHFC40DV14

RZFC40DVM4

FHFC50DV14

RZFC50DVM4

FHFC60DV14

RZFC60DVM4

FHFC71DV14

RZFC71DVM4

FHFC85DV14

RZFC85DVM4

FHFC100DV14

RZFC100DVM4

Machine weight kgUnit

0.7 (Charged for 10 m) 0.8 (Charged for 10 m)

595X845X300 695X930X350

1.0 (Charged for 15 m)

34 37 44

6.4 9.512.7 15.9

301530 (Equivalent length 40) 50 (Equivalent length 70)

VP20 (I.D. 20XO.D. 26)18.0 (Hole)

Both liquid and gas piping

Power consumption Cooling 1 kW

21 to 46

14 to 25

Sound pressure level 3 Cooling

SPECIFICATION (3 Phase)

Power supply

Model Name

Indoor unit

Outdoor unit

Outdoor unit

Cooling Capacity 1,2

Rated (Min. - Max.) kW

Btu/h

COP kW/kWCSPF Wh/Wh

Certified Operation range

°CWBCertified Operation range

Motor outputCompressor

Coil

Dimensions (HXWXD)

Colour

mmdB(A)

kWRefrigerant charge (R32) kg

dB(A)mmkg

°CDBmmmmmmmmmm

Dimensions (HXWXD)Machine weight

Unit

Piping connections

Liquid (Flare)Gas (Flare)

Drain Indoor unitOutdoor unit

Unit

Airflow rate(H / M / L)

m3/mincfm

Outdoorunit

Colour

Heat insulation

Max. interunit piping lengthMax. installation level difference

Type

Sound pressure level 3 (H / M / L)

Indoor unit

Type

2.50 2.99 3.52 4.88 6.072.84 2.56 2.314.09 3.82 3.71

34 / 29 / 2431 / 27 / 2328 / 24 / 2030 / --- / 2524 / --- / 201,200 / 1,024 / 8471,094 / 953 / 812988 / 847 / 7061,059 / --- / 883847/ --- / 706

46 / 42 / 3844 / 41 / 3742 / 38/ 3444 / --- / 3942 / --- / 37

50 51 52 54 56

White

195X1,400X6803532 38

195X1,590X680 235X1,590X690

1.60 2.40

Ivory whiteMicro channel

Hermetically sealed swing type

Machine weight kgUnit

1.0 (Charged for 15 m) 1.35 (Charged for 15 m)

46 62990X940X320695X930X350

9.515.9

3050 (Equivalent length 70)

VP20 (I.D. 20XO.D. 26)18.0 (Hole) 26.0 (Hole)

Both liquid and gas piping

Power consumption Cooling 1 kW

125 1401008571

3 Phase, 380-415V, 50Hz

7.1(3.2-8.0)

24,200(10,900-27,300)

FHFC71DV14

RZFC71DY14

8.5(4.2-10.0)

29,000(14,300-34,100)

FHFC85DV14

RZFC85DY14

10.0(5.0-11.2)

34,100(17,100-38,200)

FHFC100DV14

RZFC100DY14

12.5(5.7-14.0)

42,700(19,500-47,800)

FHFC125DV14

RZFC125DY14

14.0(6.2-15.5)

47,800(21,200-52,900 )

FHFC140DV14

RZFC140DY14

Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).2Capacities are net, including a deduction for cooling for indoor fan motor heat.3The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.

21 to 46

14 to 25

CEILING SUSPENDED TYPE

Comfortable airflow travels throughout the roomComfortable airflow travels throughout the room

OptionAccessory required for indoor unit.

Option

BRC2E61

Simplified Remote Controller (Wired Remote Controller)

Note: Remote controller cable is not included and must be obtained locally.

NEW

FHFC100/125/140DV14

FHFC40/50/60/71/85DV14

A signal receiver must be added to the indoor unit.

Wireless remote controller

Wireless remote controller is supplied in a set with a signal receiver.

Signal receiver unit (Installed type)

BRC7GA56Cooling onlyFHFC100-140D

Wireless remote controller is supplied in a set with a signal receiver.

Signal receiver unit (Installed type)

BRC7EA66Cooling onlyFHFC40-85D

Note: 1Wiring for wired remote controller should be obtained locally.2 This optional accessory requires DTA112BA51.3 The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.4 Installation box for adaptor PCB (KRP1CA93, KRP1D93A) is necessary.

Kit name

Name of option Remark

Option List

No.

16

15

17

14

13

12

11

10

9

8

6

5

4

3

2

1

7

intelligent Touch Controller

Replacement long-life filter KAFJ501D56

BRC7EA66

--------

KAFJ501D112KAFJ501D80

KDU50N60VE KDU50N125VE

KHFP5M63 KHFP5M160

BRC2E61

BRP11B61

KRP4AA52

KJB311AA

KJB212AA

KAFJ501D160 KAF501B160

KDDQ50A140

KDU50R160

KHFP5N160

BRC7GA56

KRP1CA93 KRP1D93A

DTA112BA51 --------

BRCS01A-1 BRCS01A-4

DCS302CA61 2 DCS302CA61 3

DCS301BA61 2 DCS301BA61 3

DST301BA61 2 DST301BA61 3

DCS601C51 2 DCS601C51 3

Resin net

Wireless type

Wired type 1

L-type piping kit (for upward direction)

Remote controller

Central remote controller

Unified ON/OFF controller

Schedule timer

Adaptor for wiring

Wiring adaptor for electrical appendices 4

Installation box for adaptor PCB

Remote sensor (for indoor temperature)

Electrical box with earth terminal (3 blocks)

Electrical box with earth terminal (2 blocks)

Simplified remote controller

Drain pump kit

Fresh air intake kit

Interface adaptor for SkyAir series

Cooling only

FHFC100DV14FHFC125DV14FHFC140DV14

FHFC85DV14FHFC71DV14FHFC60DV14FHFC40DV14FHFC50DV14

1211

Page 8: AIR CONDITIONING SYSTEM

SPECIFICATION (1 Phase)

Model Name

Indoor unit

Outdoor unit

3.35 3.20 2.90 3.00 2.854.38 4.13 4.13 3.93 3.93

15 / 12 / 9.5 22.5 / 20 / 17.5530 / 424 / 335

37 / 33 / 25 39 / 35 / 33

794 / 706 / 618

245X700X800 245X1,000X80026

1.20 1.30 1.60

36

1.19 1.56 2.07

----------

----------

----------

1 Phase, 220-240V, 50Hz

2.37 2.98

40

FDBF40DV14

RZFC40DVM4

50

FDBF50DV14

RZFC50DVM4

60

FDBF60DV14

RZFC60DVM4

71

FDBF71DV14

RZFC71DVM4

85

FDBF85DV14

RZFC85DVM4

48 50 5149

34595X845X300 695X930X350

37 44

0.8 (Charged for 10 m) 1.0 (Charged for 15 m)0.7 (Charged for 10 m)

4.0(1.8-4.5)

5.0(2.3-5.6)

6.0(2.6-6.3)

7.1(3.2-8.0)

8.5(4.2-10.0)

13,600(6,100-15,400)

17,100(7,800-19,100)

20,500(8,900-21,500)

24,200(10,900-27,300)

29,000(14,300-34,100)

Ivory whiteMicro channel

Hermetically sealed swing type

21 to 46

14 to 25

Power supply Indoor unit

Cooling Capacity 1,2

Rated (Min. - Max.) kW

Btu/h

COP W/WCSPF Wh/Wh

Certified Operation range

Sound pressure level 4

Motor outputCompressor

Coil

Colour

dB(A)

kWRefrigerant charge (R32) kg

dB(A)mmkg

°CDBmmmmmmmmmm

Dimensions (HXWXD)Machine weight

Piping connections

Liquid (Flare)Gas (Flare)

Drain Indoor unitOutdoor unit

Fan m3/mincfmPa

Outdoorunit

Colour

Heat insulation

Max. interunit piping lengthMax. installation level difference

Type

Cooling

Sound pressure level 4 (H/M/L)

Indoor unit

Type

Outdoor unit

Power consumption Cooling 1

Airflow rate (H/M/L)

External static pressure 3

kW

°CWBCertified Operation range

Dimensions (HXWXD) mm

Machine weight kg

Air filter 5

Rated 15 (15-38)

6.4 9.512.7 15.9

Both liquid and gas piping

30 (Equivalent length 40) 50 (Equivalent length 70)15 30

VP25 (I.D. 25XO.D. 32)18.0 (Hole)

----------

----------

----------

3 Phase, 380-415V, 50Hz

3.00 2.853.93 3.93

50 51

2.37 2.98

Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)2Capacities are net, including a deduction for cooling for indoor fan motor heat.3External static pressure is changeable in 11 stages by remote controller.4The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.5Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity method) 50% or more.

SPECIFICATION (3 Phase)

Model Name

Indoor unit

Outdoor unit

71

FDBF71DV14

RZFC71DY14

85

FDBF85DV14

RZFC85DY14

2.401.0 (Charged for 15 m)

22.5 / 20 / 17.5794 / 706 / 618

245X1,000X800

39 / 35 / 33

36

7.1(3.2-8.0)

8.5(4.2-10.0)

24,200(10,900-27,300)

29,000(14,300-34,100)

14 to 25

695X930X35046

1.60

Ivory whiteMicro channel

Hermetically sealed swing type1.60

21 to 46

Power supply Indoor unit

Cooling Capacity 1,2

Rated (Min. - Max.) kW

Btu/h

COP W/WCSPF Wh/Wh

Certified Operation range

Sound pressure level 4

Motor outputCompressor

Coil

Colour

dB(A)

kWRefrigerant charge (R32) kg

dB(A)mmkg

°CDBmmmmmmmmmm

Dimensions (HXWXD)Machine weight

Piping connections

Liquid (Flare)Gas (Flare)

Drain Indoor unitOutdoor unit

Fan m3/mincfmPa

Outdoorunit

Colour

Heat insulation

Max. interunit piping lengthMax. installation level difference

Type

Cooling

Sound pressure level 4 (H/M/L)

Indoor unit

Type

Outdoor unit

Power consumption Cooling 1

Airflow rate (H/M/L)

External static pressure 3

kW

°CWBCertified Operation range

Dimensions (HXWXD) mm

Machine weight kg

Air filter 5

Rated 15 (15-38)

9.515.9

Both liquid and gas piping

50 (Equivalent length 70)30

VP25 (I.D. 25XO.D. 32)18.0 (Hole)

Perfect for narrow entranceways

DUCT CONNECTION LOW STATIC PRESSURE WIDTH COMPACT TYPE

Perfect for narrow entranceways

FDBF40/50/60/71/85DV14

NEW

Accessory required for indoor unit.

BRC2E61

Simplified Remote Controller (Wired Remote Controller)

Note: Remote controller cable is not included and must be obtained locally.

NEW

Option

Option List

FDBF40DV14FDBF50DV14FDBF60DV14

FDBF71DV14FDBF85DV14

Kit name

No. RemarkName of option

Remote controller

Wired type 1

BRC4C66

BRC2E61Simplified Remote Controller

Cooling

Note: 1Wiring for wired remote controller should be obtained locally.

2

1 Wireless type

BRCS01A-1Remote sensor (for indoor temperature)3

Mirror Pipe

Enables selection of right or left piping at installation site

For left side connection

For right side connection

Can select!

*New features for both FDBF and FDLF series.

BRC4C66

A signal receiver must be added to the indoor unit.

Cooling only

Wireless remote controller is supplied in a set with a signal receiver.

Wireless remote controller

Signal receiver unit (Separate type)

1413

Page 9: AIR CONDITIONING SYSTEM

----------1 Phase, 220-240V, 50Hz

3.35 3.20 2.90 3.00 2.854.33 4.13 4.13 3.93 3.93

1.19 1.56 2.07 2.37 2.98

SPECIFICATION (1 Phase)

Model Name

Indoor unit

Outdoor unit

40

FDLF40DV14

RZFC40DVM4

50

FDLF50DV14

RZFC50DVM4

60

FDLF60DV14

RZFC60DVM4

71

FDLF71DV14

RZFC71DVM4

85

FDLF85DV14

RZFC85DVM4

4.0(1.8-4.5)

5.0(2.3-5.6)

6.0(2.6-6.3)

7.1(3.2-8.0)

8.5(4.2-10.0)

13,600(6,100-15,400)

17,100(7,800-19,100)

20,500(8,900-21,500)

24,200(10,900-27,300)

29,000(14,300-34,100)

Power supply Indoor unit

Cooling Capacity 1,2

Rated (Min. - Max.) kW

Btu/h

COP W/WCSPF Wh/Wh

Certified Operation range

Sound pressure level 4

Motor outputCompressor

Coil

Colour

dB(A)

kWRefrigerant charge (R32) kg

dB(A)mmkg

°CDBmmmmmmmmmm

Dimensions (HXWXD)Machine weight

Piping connections

Liquid (Flare)Gas (Flare)

Drain Indoor unitOutdoor unit

Fan m3/mincfmPa

Outdoorunit

Colour

Heat insulation

Max. interunit piping lengthMax. installation level difference

Type

Cooling

Sound pressure level 4 (H/M/L)

Indoor unit

Type

Outdoor unit

Power consumption Cooling 1

Airflow rate (H/M/L)

External static pressure 3

kW

°CWBCertified Operation range

Dimensions (HXWXD) mm

Machine weight kg

Air filter

16 / 14 / 12 20 / 18 / 16.5565 / 494 / 424 706 / 635 / 582

200X900X620 200X1,100X620

37 / 33 / 30 40 / 37 / 34

28 31

----------

Removable / Washable / Mildew proof

Rated 15 (15-38)

1.20 1.30 1.60

48 50 5149

34595X845X300 695X930X350

37 44

0.8 (Charged for 10 m) 1.0 (Charged for 15 m)0.7 (Charged for 10 m)

Ivory whiteMicro channel

Hermetically sealed swing type

21 to 46

14 to 25

6.4 9.512.7 15.9

Both liquid and gas piping

30 (Equivalent length 40) 50 (Equivalent length 70)15 30

VP25 (I.D. 25XO.D. 32)18.0 (Hole)

----------

----------

3 Phase, 380-415V, 50Hz

3.00 2.853.93 3.93

50 51

2.37 2.98

Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)2Capacities are net, including a deduction for cooling for indoor fan motor heat.3External static pressure is changeable in 11 stages by remote controller.4The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.

SPECIFICATION (3 Phase)

Model Name

Indoor unit

Outdoor unit

71

FDLF71DV14

RZFC71DY14

85

FDLF85DV14

RZFC85DY14

Removable / Washable / Mildew proof

20 / 18 / 16.5706 / 635 / 582

200X1,100X620

40 / 37 / 34

31

7.1(3.2-8.0)

8.5(4.2-10.0)

24,200(10,900-27,300)

29,000(14,300-34,100)

Power supply Indoor unit

Cooling Capacity 1,2

Rated (Min. - Max.) kW

Btu/h

COP W/WCSPF Wh/Wh

Certified Operation range

Sound pressure level 4

Motor outputCompressor

Coil

Colour

dB(A)

kWRefrigerant charge (R32) kg

dB(A)mmkg

°CDBmmmmmmmmmm

Dimensions (HXWXD)Machine weight

Piping connections

Liquid (Flare)Gas (Flare)

Drain Indoor unitOutdoor unit

Fan m3/mincfmPa

Outdoorunit

Colour

Heat insulation

Max. interunit piping lengthMax. installation level difference

Type

Cooling

Sound pressure level 4 (H/M/L)

Indoor unit

Type

Outdoor unit

Power consumption Cooling 1

Airflow rate (H/M/L)

External static pressure 3

kW

°CWBCertified Operation range

Dimensions (HXWXD) mm

Machine weight kg

Air filter

Rated 15 (15-38)

2.401.0 (Charged for 15 m)

695X930X35046

1.60

Ivory whiteMicro channel

Hermetically sealed swing type1.60

21 to 46

14 to 25

9.515.9

Both liquid and gas piping

50 (Equivalent length 70)30

VP25 (I.D. 25XO.D. 32)18.0 (Hole)

Option ListKit name

No. RemarkName of option FDLF40DV14FDLF50DV14FDLF60DV14

FDLF71DV14FDLF85DV14

Remote controller

Wired type 1

BRC4C66

BRC2E61Simplified Remote Controller

Cooling

Note: 1Wiring for wired remote controller should be obtained locally.

2

1 Wireless type

BRCS01A-1Remote sensor (for indoor temperature)3

Enables high-ceiling design

DUCT CONNECTION LOW STATIC PRESSURE HEIGHT COMPACT TYPE

Enables high-ceiling design

FDLF40/50/60/71/85DV14

NEW

Accessory required for indoor unit.

BRC2E61

Simplified Remote Controller (Wired Remote Controller)

Note: Remote controller cable is not included and must be obtained locally.

NEW

Option

BRC4C66

A signal receiver must be added to the indoor unit.

Cooling only

Wireless remote controller is supplied in a set with a signal receiver.

Wireless remote controller

Signal receiver unit (Separate type)

Easier and faster cleaning

Need to be removedby orderly

The integrated fan motorcan be removed andreinstalled in one time

Current New

Easy access to Control boxfrom bottom side

Need space area inside for maintenance Control box

All wiring and maintenance can be done from bottom side

Current New

*New features for both FDBF and FDLF series.Easy Maintenance

1615

Page 10: AIR CONDITIONING SYSTEM

SPECIFICATION (1 Phase)

Power supply

Model Name

Indoor unit

Outdoor unit

Indoor unit

Cooling Capacity 1,2

Rated (Min. - Max.) kW

Btu/h

4.0(1.8-4.5)

13,600(6,100-15,400)

5.0(2.3-5.6)

17,000(7,800-19,100)

6.0(2.6-6.3)

20,500(8,900-21,500)

7.1(3.2-8.0)

24,200(10,900-27,300)

8.5(4.2-10.0)

29,000(14,300-34,100)

10.0(5.0-11.2)

34,100(17,100-38,200)

COP W/W 3.35 3.20 2.90 3.00 3.10 3.15CSPF Wh/Wh

Certified Operation range

Sound pressure level 4

Motor outputCompressor

Coil

Colour

dB(A)

kWRefrigerant charge (R32) kg

dB(A)mmkg

°CDBmmmmmmmmmm

Dimensions (HXWXD)Machine weight

Piping connections

Liquid (Flare)Gas (Flare)

Drain Indoor unitOutdoor unit

Fan m3/mincfmPa

Outdoorunit

Colour

Heat insulation

Max. interunit piping lengthMax. installation level difference

Type

Cooling

Sound pressure level 4 (H/M/L)

Indoor unit

Type

Outdoor unit----------

----------

----------

1 Phase, 220–240 / 220-230V, 50 / 60Hz

----------3 Phase, 380-415V, 50Hz

40

FBFC40DVM4

RZFC40DVM4

50

FBFC50DVM4

RZFC50DVM4

60

FBFC60DVM4

RZFC60DVM4

71

FBFC71DVM4

RZFC71DVM4

85

FBFC85DVM4

RZFC85DVM4

100

FBFC100DVM4

RZFC100DVM4

Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)2Capacities are net, including a deduction for cooling for indoor fan motor heat.3External static pressure is changeable in 11 stages by remote controller.4The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.5Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity method) 50% or more.

Power consumption Cooling 1

Airflow rate (H/M/L)

External static pressure 3

kW 1.19

48 50 51 5249

1.56 2.07 2.37

1.30

2.74 3.17

4.38 4.18 4.18 3.983.98 3.98

547 / 424 / 318 883 / 706 / 582 1,271 / 1,077 / 883Rated 40 (40-140) Rated 50 (50-150)

15.5 / 12 / 9 25 / 20 / 16.5 36 / 30.5 / 25

°CWBCertified Operation range

Dimensions (HXWXD) mm

Machine weight kg

Air filter 5

Power supply Indoor unit

Cooling Capacity 1,2

Rated (Min. - Max.) kW

Btu/h

COP W/WCSPF Wh/Wh

Certified Operation range

Sound pressure level 4

Motor outputCompressor

Coil

Colour

dB(A)

kWRefrigerant charge (R32) kg

dB(A)mmkg

°CDBmmmmmmmmmm

Dimensions (HXWXD)Machine weight

Piping connections

Liquid (Flare)Gas (Flare)

Drain Indoor unitOutdoor unit

Fan m3/mincfmPa

Outdoorunit

Colour

Heat insulation

Max. interunit piping lengthMax. installation level difference

Type

Cooling

Sound pressure level 4 (H/M/L)

Indoor unit

Type

Outdoor unit

Power consumption Cooling 1

Airflow rate (H/M/L)

External static pressure 3

kW

°CWBCertified Operation range

Dimensions (HXWXD) mm

Machine weight kg

Air filter 5

SPECIFICATION (3 Phase)

Model Name

Indoor unit

Outdoor unit

71

FBFC71DVM4

RZFC71DY14

85

FBFC85DVM4

RZFC85DY14

100

FBFC100DVM4

RZFC100DY14

125

FBFC125DVM4

RZFC125DY14

140

FBFC140DVM4

RZFC140DY14

Rated 30 (30-130)

34

2.37 2.74 3.17 5.21

2.40

6.22

50 51 52 54 5650

3.00 3.10 3.15 2.40 2.25

39 / 37 / 34 40 / 37.5 / 3537 / 35 / 30

245X1,000X800 245X1,400X800245X700X800

595X845X300 695X930X350

36 4626

1.60

37 44

1.200.8 (Charged for 10 m) 1.0 (Charged for 15 m)0.7 (Charged for 10 m)

Ivory whiteMicro channel

Hermetically sealed swing type

6.412.7

9.515.9

Both liquid and gas piping

30 (Equivalent length 40) 50 (Equivalent length 70)15 30

VP25 (I.D. 25XO.D. 32)18.0 (Hole)

14 to 25

21 to 46

7.1(3.2-8.0)

8.5(4.2-10.0)

10.0(5.0-11.2)

12.5(5.7-14.0)

14.0(6.2-15.5)

24,200(10,900-27,300)

29,000(14,300-34,100)

34,100(17,100-38,200)

42,700(19,500-47,800)

47,800(21,200-52,900)

----------

----------

3.983.98 3.98 3.71 3.60

883 / 706 / 582 1,271 / 1,077 / 883Rated 40 (40-140) Rated 50 (50-150)

25 / 20 / 16.5 36 / 30.5 / 25

39 / 37 / 34 40 / 37.5 / 35

245X1,000X800 245X1,400X800

695X930X350 990X940X32046 62

36 46

1.601.0 (Charged for 15 m) 1.35 (Charged for 15 m)

Ivory whiteMicro channel

Hermetically sealed swing type

9.515.9

Both liquid and gas piping

50 (Equivalent length 70)30

VP25 (I.D. 25XO.D. 32)18.0 (Hole) 26.0 (Hole)

14 to 25

21 to 46

Note: 1If installing high efficiency filter and long-life filter to the unit, filter chamber is required.2Wiring for wired remote controller should be obtained locally. 3Mounting plate is necessary for each adaptor marked .

Option List

FBFC40DVM4FBFC50DVM4FBFC60DVM4

FBFC71DVM4FBFC85DVM4

FBFC100DVM4FBFC125DVM4FBFC140DVM4

High-efficiency filter 1

Filter chamber(for rear suction)1

Long-life filter 1

Air discharge adaptor

Adaptor for wiring 3

Wiring adaptor for electrical appendices(2) 3

Central remote controller 6

Unified ON/OFF controller 6

Schedule timer 6

intelligent Touch Controller 6

Service panel

Remote controller

65%

90%

Fresh white

Brown

Wired type 2

Kit name

KAF632C56 KAF632C80 KAF632C160

KAF633C56 KAF633C80 KAF633C160

KDDFP63B56 KDDFP63B80 KDDFP63B160

KDAP25A56A KDAP25A71A KDAP25A140A

KAF631C56 KAF631C80 KAF631C160

KTBJ25K56W KTBJ25K80W KTBJ25K160W

KTBJ25K56F KTBJ25K80F KTBJ25K160F

KTBJ25K56T KTBJ25K80T KTBJ25K160T

KDBD63A160

BRC4C66

BRC2E61

KRP4A98

BRCS01A-4

DCS302CA61

DCS301BA61

DST301BA61

DCS601C51

Shield plate for side plate

Simplified Remote Controller

Cooling

4Up to 2 adaptors can be fixed for each mounting plate.5Only one mounting plate can be installed for each indoor unit.6The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.

BRP11B62

KRP4AA51

14

13

16

15

Drain pump kit BDU24AMD217

11

5

4

3

10

8

2

1

6

7

No. RemarkName of option

Remote sensor (for indoor temperature)9

Mounting plate for adaptor PCB.3,4,512

White

Wireless type

Middle static type allows greater flexibility

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

Middle static type allows greater flexibility

FBFC40/50/60/71/85/ 100/125/140DVM4

NEW

Accessory required for indoor unit.

BRC2E61

Simplified Remote Controller (Wired Remote Controller)

Note: Remote controller cable is not included and must be obtained locally.

NEW

Option

BRC4C66

A signal receiver must be added to the indoor unit.

Cooling only

Wireless remote controller is supplied in a set with a signal receiver.

Wireless remote controller

Signal receiver unit (Separate type)

1817

Page 11: AIR CONDITIONING SYSTEM

4

3

2

1

Temperaturesetting (+/-)

BRC7F635FBRC7EA66BRC7GA56

BRC4C66

Cooling only

REMOTE CONTROLLER

All initial settings can be set from the remote controller. After interior construction is complete, ceiling mounted cassette type can be remotely set without having to use a stepladder to access for manual setting.Setting contents: High ceiling use, air direction, filter type, address for centralised control (group control address is set automatically).

Enables temperature sensing closer to target area for improved comfort. (When using a remote control from another room, temperature-sensor of the indoor unit air inlet must be selected.)

Remote controller is equipped with error code display function. This facilitates service in the unlikely event of a malfunction.

SkyAir shares common control with Heat Reclaim Ventilator and the other Daikin air-conditioning units, thus simplifying interlocking operations.

Easily adaptable to large-scale, high-function, centralised remote control systems.Installing and connecting control wiring between SkyAir and other Daikin air-conditioning equipment is easy.

LCD panel shows operating status in letters, numbers, and motion.Airflow / swing display

Preset temperature / operation mode display

Programming time display

Self-diagnosis function

Displays auto-swing operating status and setting position of air discharge angle.

Displays preset room temperature and operating status (fan, dry, cool).

Operation start and stop time can be set for individual timers up to 72 hours. The LCD also shows when it is time to clean the filter, when changeover is under centralised control, and ventilation/cleaning.

Monitors operating status within the system covering 40 items, and displays a message to indicate as soon as a malfunction occurs.

Optional accessory

BRC2E61NEW

Airflow rate (Fan speed)

Airflow direction

ON/OFF button

Operation mode selectionSimple operation

Using only six buttons, users have direct access to basic functions.This enables them to easily set comfort to their preference.

Intuitive designBy using pictograms, the user-friendly interface enables:

CompactMeasuring only 85 x 85 mm, the new remote controller is extremely compact and complements any interior design.

Overseas guests at hotels to understand functions without having to know a foreign language.

Children and elderly users at home to operate without having to read difficult and hard-to-see commands.

120 mm 120 mm

120 mm 85 mm

85 mm

70 mm

35mm

35mm

Conventional remote controller

Conventional simplifiedremote controllerBRC2E61

Reduced size

Signal receiver unit(Installed type)

BRC7F635F The wireless remote controller is supplied in a set with a signal receiver.Signal receiver unit of installed type is contained inside decoration panel or indoor unit.Shape of signal receiver unit differs according to the indoor unit.

Wired remote controller has built-in temperature-sensor

Facilitates maintenance and repair

CEILING MOUNTED CASSETTE TYPE

DUCT CONNECTION LOW STATIC PRESSURE WIDTH COMPACT TYPEDUCT CONNECTION LOW STATIC PRESSURE HEIGHT COMPACT TYPEDUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

CEILING SUSPENDED TYPE40-85100-140

Wireless remote controller for each indoor unit type

BRC7GA56

Signal receiver unit(Installed type)

Signal receiver unit(Installed type)

BRC7EA66 BRC4C66

Signal receiver unit (Separate type)

Simplified Remote Controller (wired)

Wireless remote controller

OUTDOOR UNIT

Compact Outdoor Unit

Through use of a V-cut propeller fan that imitates the efficiency of the swan, a migratory bird, airflow becomes smooth and loss is reduced.

V-cut Propeller Fan

Technology for energy efficiency

3

2

1

4

Imitating the performance of the swan

(RZFC40-100DVM4/Y14)

RZFC40DVM4RZFC50DVM4RZFC60DVM4RZFC71DVM4

RZFC85DVM4RZFC100DVM4

RZFC71DY14RZFC85DY14RZFC100DY14

RZFC125DY14RZFC140DY14

*Although pumping-down operation allows most of the refrigerant to be recovered in a short period of time, some refrigerant will remain inside the indoor unit and refrigerant piping.Using a refrigerant recovery machine, recover remaining refrigerant from the stop valve service port until the pressure falls to 0.09 MPa. (gauge pressure:-0.011MPa) or less.

(Refrigerant recovery function)Facilitates pump down

*Pump-down function is available for pre-charged refrigerant amount.

Refrigerant cooling helps protect the printed circuit board and maintains high cooling capacity even during high outdoor temperatures.

(RZFC71-140DY14)

Conventional tube and fin coil Micro channel coil

High efficiency by micro channel heat exchangerHigh efficiency by micro channel heat exchanger

Daikin’s unique refrigerant cooling system exhibits high cooling capacity even during high outdoor temperatures.

Refrigerant coolingRefrigerant cooling

Utilizing flat, multi-hole heat exchanger tubes increases the heat exchange area and realizes energy savings.

Flow of refrigerant Flow of refrigerant

Flat, multi-hole aluminium heat exchanger tubes

Conventional heat exchanger

The diameter of the refrigerant channel(holes where refrigerant flows) is approx.1 mm.

The diameter of the refrigerant channel (holes where refrigerant flows) is approx. 7 mm

Approx. 1 mm

Approx. 7 mm

Reduced wind resistance

Micro channel heat exchanger

The flattening of the heat exchanger tubes improves the flow of air and increases heat exchange efficiency.

Energy savings is realised, eliminating the friction and the leakage of refrigerant gas.

Swing bushing Refrigerant gas

Piston by incorporated blade and roller.

Swing compressor High efficiency during partial load operation.

Fan

V-cut propeller fan

A pump-down switch is provided to make it easier to collect refrigerant if the unit is to be moved or layout modified.

Low gas pressure detection functionEffective gas monitoring reduces the labor required for operation, maintenance, and repairs.

Easy Installation and Maintenance

2019

Page 12: AIR CONDITIONING SYSTEM

REMOTE CONTROLLER Optional accessory

LCD REMOTE CONTROLLER

Central remote controller

Easily adaptable to large-scale, high-function, centralised remote control system.

Centralised control, with setting as simple as it is with a standardremote controller, of up to 64 groups (1,024 indoor units) is possible.

DCS302CA61 (Option)

With its high functionality, the full colour “all-in-one” graphic controller facilitates management of SkyAir System in a variety of ways.

DCS601C51 (Option)Unified on/off controller

Centralised control of on/off by group or all at once for up to 256 indoor units.

DCS301BA61 (Option)

Schedule timer

Unified control of weekly schedule for up to 1,024 indoor units.

DST301BA61 (Option)

Schedule timer sets on/off time in 1 minute units to be executed twice a day for a week at a time.

System variation to control multiple indoor units

(Command from outside)

Control by 1remote controller

Control pattern Wired remote controller Wireless remote controller

Control by 2remote controllers

Group control

Control by external command

Centralised remotecontrol

Interlock controlwith Heat Reclaim

Ventilator

(Basic system)

Link by remote controller group control.

Zone link control by centralised control.

For control from 2 locations such as in room and control room, exits, etc.

For simultaneous control of up to 16 indoor units.

Centralised control of up to 64 indoor groups from remote locationup to 1 km away.

Control by 1 wireless remote controller and 1 wired remotecontroller (See note 2)

Signal receiver unit installed on indoor unit

Signal receiver unit installed on indoor unit

Heat Reclaim Ventilator for indoor units within a zone is operated by interlocking.Can also be operated independently by remote controller.

Central remote controller (option)

Heat ReclaimVentilator

Can be operated simultaneously or independently by remote controller (set by ventilation mode)

Heat ReclaimVentilator

Central remote controller (option)

Non-polar, double-core (max. wiring length 500 m)

Connects 2 wired remote controllers (See note 1)

Automatic address setting function Automatic address setting function

Signal receiver unit installed on 1 indoor unit

Optional wiring adaptor for electrical appendices is necessary

Central remote controller (option)

Interface adapter for SkyAir series (option) is required (See note 3)

Interface adapter for SkyAir series (option) is required (See note 3)

Can be operated simultaneously by remote controller

Heat ReclaimVentilator

Heat Reclaim Ventilator for indoor units within a zone is operated by interlocking.

Central remote controller (option)

Heat ReclaimVentilator

Operation and monitoring is carried out using the contact signal from the operation control box in the monitoring room. Optional wiring adaptor for

electrical appendices is necessary

Interface adaptor for SkyAir series

DTA112BA51 (Option)Necessary for interface adaptor for SkyAir series with the central remote control units shown at above.

Enables centralised control via connection to a high-speed, DIII-NET communication system, adopted for the Daikin   system.

(Command from outside)

The interface adaptor for SkyAir series is required for Ceiling suspended type 40-85 class.

Note: 1BRC2E61 can connect to BRC2E61 only. 2When a wireless remote controller is used, it is not possible to use 2 wireless remote controllers. Combination of BRC2E61 (main) and wireless remote controller (sub) is available. 3FHFC40-85D requires interface adaptor for SkyAir series.

*Except for FDBF and FDLF

Whatever your space, give it the comfort it deserves

*Except for FDBF and FDLF

*Except for FDBF and FDLF

2221

Page 13: AIR CONDITIONING SYSTEM

ON / OFF timer

Auto swing

Swing pattern selection

DC fan motor

Switchable fan speed

Auto airflow rate

Two selectable temperature-sensors

High ceiling application

FUNCTIONS

Cooling only

Functionsoverview

2

3

4

5

6

7

8

1

Drain pump mechanism

Pre-charged for up to 10 / 15 m *1

Long-life filter

Filter sign

Low gas pressure detection *1

Emergency operation

Self-diagnosis function

13

14

15

16

17

18

12

High-efficiency filter

Ultra long-life filter

Fresh air intake kit

28

29

27

Auto-restart

Control by 2 remote controllers

Group control by 1 remote controller

External signal forced OFF and ON/OFF operation

External command control *2

Central remote control

Interlock control with Heat Reclaim Ventilator

DIII-NET communication standard

20

21

22

23

24

25

26

19

Anti-bacterial air filter

Mould-proof air filter10

Silver ion anti-bacterial drain pan11

9

2

3

4

5

6

7

8

1

13

14

15

16

17

18

12

28

29

27

20

21

22

23

24

25

26

19

10

11

9

Indoor unit

Outdoor unit

Remotecontroller

BRC2E61

-------

-------

BRC7F635F

Wired

Wireless

Note:*1: For outdoor units. *2: Wiring adaptor for electrical appendices (and installation box) is necessary. *3: Option is requied. *4: For outdoor unit RZFC-DY14 only. *5: It is not possible to use 2 wireless remote controllers. Combination of BRC2E61 (main) and wireless remote controller (sub) is available.

3 step 3 step 2 step 2 step 3 step

3.5m / 4.2m 3.5m 4.3 m

3 step

-------

BRC7EA66

BRC2E61

-------

*3

*4*4 *4

*3

*5

*3

*3

*5 *5

FHFC100-140DV14

RZFC100DVM4RZFC100-140DY14

-------

BRC7GA56

BRC2E61

-------

CEILING SUSPENDED TYPECEILING MOUNTED

CASSETTE TYPE( Round Flow )

FHFC40-85DV14

RZFC40-85DVM4RZFC71/85DY14

FCFC40-140DVM4

RZFC40-100DVM4RZFC71-140DY14

3 step 3 step3 step 3 step 3 step 3 step

*3

*3

*3

*4

*5*5 *5

*4 *4

FBFC40-140DVM4

RZFC40-100DVM4RZFC71-140DY14

-------

BRC4C66

BRC2E61

-------

-------

BRC4C66

BRC2E61

-------

-------

BRC4C66

BRC2E61

-------

DUCT CONNECTION LOW STATIC PRESSURE WIDTH COMPACT TYPE

DUCT CONNECTION LOW STATIC PRESSURE HEIGHT COMPACT TYPE

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

FDLF40-85DV14

RZFC40-85DVM4RZFC71/85DY14

FDBF40-85DV14

RZFC40-85DVM4RZFC71/85DY14

Cleanliness

Comfort

Work & Servicing

Control

Options

2423

Page 14: AIR CONDITIONING SYSTEM

Product Lineup

OUTDOOR UNIT

WALL MOUNTED TYPE

Outdoor unit

Indoor unit

FCQ60KAVE4FCQ50CKAVE4

25 60

CEILING MOUNTED CASSETTE TYPE

Round Flow

Series

CEILING SUSPENDED TYPE

Outdoor unit

Indoor unit

FLOOR STANDING TYPE

Outdoor unit

Indoor unit

DUCT CONNECTIONMIDDLE STATIC PRESSURE TYPE

Outdoor unit

Indoor unit

COMPACT MULTI FLOW CEILING MOUNTED CASSETTE TYPE

Outdoor unit

Indoor unit

Outdoor unit

Indoor unit

RZR50MVM4RZR50MVM4

FFQ25BV1B4

RKS25AVMG4

FHQ50DAVM4

RZR50MVM4

FHQ60DAVM4

RZR60MVM4

FHQ71DAVM4

RZR71MVM4

RZR50MVM4 RZR60MVM4 RZR71MVM4

RZR50MVM4 RZR60MVM4 RZR71MVM4

FHQ100DAVM4

RZR100MYM4

FAQ100CVEA4

RZR100MYM4

FHQ125DAVM4 FHQ140DAVM4

OUTDOOR UNIT

Outdoor unit

FCQ71KAVE4

RZR50MVM4

FCQ100KAVE4

RZR50MYM4

FCQ125KAVE4

RZR125MYM4 RZR125LUY14 RZR140MYM4 RZR140LUY14

RZR125MYM4 RZR125LUY14 RZR140MYM4 RZR140LUY14

RZR50MVM4 RZR60MVM4 RZR71MVM4 RZR100MYM4 RZR125MYM4 RZR125LUY14 RZR140MYM4 RZR140LUY14

FBQ125EVE4FBQ125EVE4FBQ71EVE4FBQ60EVE4FBQ50EVE4 FBQ140EVE4RZR125MYM4RZR100MYM4

RZR100MYM4

RZR125LUY14 RZR140MYM4 RZR140LUY14

FVQ125CVEB4FVQ100CVEB4FVQ71CVEB4FVQ60CVEB4FVQ50CVEB4 FVQ140CVEB4RZR125MYM4 RZR125LUY14 RZR140MYM4 RZR140LUY14

FCQ140KAVE4

FFQ35BV1B4

RKS35AVMG4

FFQ50BV1B4

RKS50AVMG4

FFQ60BV1B4

RKS60AVMG4

71 100 125 14035

Outdoor unit

50

RKS25AVMG4 RKS35AVMG4 RKS50AVMG4 RKS60AVMG4

2625

Page 15: AIR CONDITIONING SYSTEM

SPECIFICATION (3 Phase)

Cooling capacity1,2

Rated (Min. - Max.) kW

Btu/h

ModelName

Indoor unit

Outdoor unit

Outdoor unitPower supply 1 Phase, 220–240 V, 50 Hz

kWPower consumption Cooling1

°CWBCertified Operation range

Dimensions(HXWXD) mm

mmdB(A)

Unit

Decoration panelMachine weight kg

kgUnitDecoration panel

Airflow rate (H/M/L) m3/mincfm

Sound pressure level 3 (H/M/L)

Indoorunit

256X840X840 298X840X840 256X840X840298X840X84050X950X950

5.5

14 to 25

44/39/34 44/40/36 44/39/34 44/40/36

33/28/22.5 21/17.5/13.5 33/28/22.5 21/17.5/13.51,165/988/794 741/618/477 1,165/988/794 741/618/477

35/31.5/28 35/31.5/28

24 21 24 21

W/WCOP

125

FCQ125KAVE4

RZR125LVVM4

12.5 (5.7-14.0)

140

FCQ140KAVE4

RZR140LVVM4

14.0 (6.2-15.4)

3.68 4.913.40 2.85

125

FCQ60KAVE4x2

RZR125LUY14

12.5 (5.7-14.0)

140

FCQ71KAVE4x2

RZR140LUY14

14.0 (6.2-15.4)

3.68 4.913.40 2.85

125

FCQ60KAVE4x2

RZR125LVVM4

12.5 (5.7-14.0)

140

FCQ71KAVE4x2

RZR140LVVM4

14.0 (6.2-15.4)

3.68 4.913.40 2.85

3 Phase, 380–415 V, 50 Hz

125

FCQ125KAVE4

RZR125LUY14

12.5 (5.7-14.0)

140

FCQ140KAVE4

RZR140LUY14

14.0 (6.2-15.4)

42,700(19,500-47,800)

47,800(21,200-52,600)

42,700(19,500-47,800)

47,800(21,200-52,600)

42,700(19,500-47,800)

47,800(21,200-52,600)

42,700(19,500-47,800)

47,800(21,200-52,600)

3.68 4.913.40 2.85

Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).2Capacities are net, including a deduction for cooling for indoor fan motor heat.3The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.

dB(A)

°CDBCertified Operation range

Sound pressurelevel3

Motor outputCompressor

Coil

kWRefrigerant charge (R-410A) kg

dB(A)

Dimensions (HXWXD) mmMachine weight kg

Piping connections

mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit

Outdoor unit

Outdoorunit

mmMax. interunit piping length m

mMax. installation level difference

Type

Cooling

Ø9.5Ø15.9

50

1,170X900X32097

3050 (Equivalent length 70)

Hermetically sealed scroll typeType Cross fin coil

Ø26.0 (Hole)VP25 (I.DØ25XO.DØ32)

21 to 46

Night quiet mode

3.15 (Charged for 30 m)2.4 3.1

45 46

2.4 3.1

45 46

2.4 3.1

45 46

3.7 (Charged for 30 m)2.4 3.1

45 46

intelligent Touch Controller4

Note: 1Refer to page 20 for the details. 2Required for installing high-efficiency filter unit and ultra long-life filter unit. 3Wiring for wired remote controller to be procured locally.4The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary. 5Installation box for adaptor PCB (KRP1H98) is necessary.

Option ListKit name

KDJP55B160KDJP55B80

KAFP556B80KAFP557B80KAFP552B80KAFP553B80

KAFP556B160KAFP557B160KAFP552B160KAFP553B160

FCQ71KAVE4 FCQ100KAVE4FCQ50KAVE4 FCQ60KAVE4 FCQ125KAVE4 FCQ140KAVE4Name of option Remark

Chamber type

Decoration panel

Fresh air intake kit1

Central remote controller4

Unified ON/OFF controller4

Schedule timer4

Adaptor for wiring5

Without T-duct jointWith T-duct joint

Direct installation type

Sealing material of air discharge outletPanel spacer

Wiring adaptor for electrical appendices(2)5

Installation box for adaptor PCB

High-efficiency filter unit (including filter chamber)

(Colorimetric method 65%)(Colorimetric method 90%)

Replacement high-efficiency filter

(Colorimetric method 65%)(Colorimetric method 90%)

Remote controller Wireless type Cooling only

Wired type3 Wired type3

Branch duct chamber

Remote sensor (for indoor temperature)

DCS601C51

DCS302CA61DCS301BA61DST301BA61

KRP1C63

KDBH55K160FKDBP55H160FA

KDDP55B160KDDP55B160KKDDP55X160

KRP4AA53

BRC7F635F

BYCP125K-W1

KRP1H98KRCS01-4B

BRC1E62BRC1C61

KDDFP55B160Filter chamber

Navigation Remote Controller

KDTP55K160Chamber connection kit2

Insulation kit for high humidityKKSJ55KA160

KDTP55K80

KAFP551K160KAFP55B160

KAFP55H160H

Replacement long-life filterUltra long-life filter unit (including filter chamber)Replacement ultra long-life filter

FCQ50/6071/100/125/140KA

CEILING MOUNTED CASSETTE TYPE Round Flow

Cassette air conditioner with 360° uniform airflow sets the standardCassette air conditioner with 360° uniform airflow sets the standard

Accessory required for indoor unit.

BRC1C61

Wired LCD Remote Controller

Note: Remote controller cable is not included and must be obtained locally.

A signal receiver must be added to the indoor unit. Wireless LCD remote controller

Signal receiver unit (Installed type)

Wireless remote controller is suppliedin a set with a signal receiver.

BRC7F635FBRC1E63

Navigation Remote Controller(Wired Remote Controller)

Note: Remote controller cable is not included and must be obtained locally.

SPECIFICATION (1 Phase)

Cooling capacity1,2

Rated (Min. - Max.) kW

Btu/h

ModelName

Indoor unit

Outdoor unit

Power supply

71

FCQ71KAVE4

RZR71MVM4

7.1 (3.2-8.0)

100

FCQ100KAVE4

RZR100MVM4

10.0 (5.0-11.2)

125

FCQ125KAVE4

RZR125MVM4

1 Phase, 220–240 V, 50 Hz 3 Phase, 380–415 V, 50 Hz12.5

(5.7-14.0)

140

FCQ140KAVE4

RZR140MVM4

14.0 (6.2-15.4)

kWPower consumption Cooling1

100

FCQ100KAVE4

RZR100MYM4

10.0 (5.0-11.2)

125

FCQ125KAVE4

RZR125MYM4

12.5 (5.7-14.0)

140

FCQ140KAVE4

RZR140MYM4

14.0 (6.2-15.4)

1.99 2.78 4.31 5.62 2.78 4.31 5.62

50

FCQ50KAVE4

RZR50MVM4

5.0 (2.3-5.6)

60

FCQ60KAVE4

RZR60MVM4

°CWBCertified Operation range

Dimensions(HXWXD) mm

mmdB(A)

Unit

Decoration panelMachine weight kg

kgUnitDecoration panel

Airflow rate (H/M/L) m3/mincfm

Sound pressure level 3 (H/M/L)

Indoorunit

43/37.5/32

32/26/20

44/39/34

24

298X840X84050X950X950

5.5

33/28/22.51,130/918/706 1,165/988/794

44/40/36

14 to 25

43/37.5/32

32/26/20

44/39/34

33/28/22.51,130/918/706 1,165/988/794

44/40/3635/31.5/28

21

256X840X840

21/17.5/13.5741/618/477

6.0 (2.6-6.3)

24,200(10,900-27,300)

34,100(17,100-38,200)

42,700(19,500-47,800)

47,800(21,200-52,600)

34,100(17,100-38,200)

42,700(19,500-47,800)

47,800(21,200-52,600)

17,100 (7,900-19,100)

20,500(8,900-21,500)

1.24 1.58W/WCOP 3.57 3.60 2.90 2.49 3.60 2.90 2.494.03 3.80

dB(A)

°CDBCertified Operation range

Sound pressurelevel3

Motor outputCompressor

Coil

kWRefrigerant charge (R-410A) kg

dB(A)

Dimensions (HXWXD) mmMachine weight kg

Piping connections

mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit

Outdoor unit

Outdoorunit

mmMax. interunit piping length m

mMax. installation level difference

Type

Cooling

Hermetically sealed swing typeType Cross fin coil Micro channel

1.76

49

990X940X32065

2.031.9(Charged for 30 m)

Ø9.5Ø15.9

52 54 52 54

3050 (Equivalent length 70)

Ø26.0 (Hole)VP25 (I.DØ25XO.DØ32)

21 to 4673

1.92

49Night quiet mode

1.12

48

595X845X30043

1.351.6(Charged for 30 m)

4544

Outdoor unit

36O° AIRFLOW

GENTLE AIR MOVEMENT WITH ROUND FLOW

SILVER ION ANTI-BACTERIAL DRAIN PAN

ANTI-MOULD & ANTI-BACTERIAL TREATMENTFILTER

SUITABLE FOR HIGH CEILINGS

QUICK & EASY TO INSTALL

FEATURES

27 28

Page 16: AIR CONDITIONING SYSTEM

COMPACT MULTI FLOW CEILING MOUNTED CASSETTE TYPE25 35

1 Phase, 220–240 V, 50 Hz2.5

(1.2-3.0)3.4

(1.2-3.7)

0.73 1.103.42 3.09

4.7 (1.7-5.6)

5.8 (1.7-6.0)

8,500(4,100-10,250)

11,600(4,100-12,600)

16,000(5,800-19,100)

19,800(5,800-20,500)

1.62 2.072.90 2.80

FFQ25BV1B4

RKS25AVMG4

FFQ35BV1B4

RKS35AVMG4

50 60

FFQ50BV1B4

RKS50AVMG4

FFQ60BV1B4

RKS60AVMG4

kWPower consumption

ModelName

Indoor unit

Outdoor unit

cfm

286X575X57555X700X700

2.717.5

29.5/24.5 32/25

14 to 23°CWBCertified operation range

Indoorunit

Dimensions(HXWXD) mm

mmSound pressure level2 (H/L) dB(A)

UnitDecoration panel

Machine weightkgkgUnit

Decoration panel

Airflow rate (H/L) 9/6.5 10/6.5317/229 353/229

36/27 41/32

12/8 15/10423/282 529/353

m3/min

Power supply

Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).2The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.

VP20 (I.DØ20XO.DØ26)

10 to 46

46 47 49550X765X285

34735X825X300

47

1.00.6

Ø6.4o/ 9.5 o/ 12.7

2015

3020

Hermetically sealed swing type

Ø18.0 (Hole)

(Charged for 10 m)1.51.1

(Charged for 10 m)

Sound pressure level2

°CDBCertified operation range

Motor outputCompressor

kWRefrigerant charge (R-410A)

dB(A)Dimensions (HXWXD) mmMachine weight kg

Piping connections

mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit

Outdoor unit

kg

Outdoorunit

mmMax. interunit piping length m

mMax. installation level difference

TypeCross fin coilCoil Type

kW

Btu/h

Cooling capacity1

Rated (Min. - Max.)

Cooling1

W/WCOP

Outdoor unit

BRC7E531W

Kit nameName of option Remark

intelligent Touch Controller3

FFQ25BV1B4 FFQ35BV1B4 FFQ50BV1B4 FFQ60BV1B4Decoration panel

Fresh air intake kit

Central remote controller3

Unified ON/OFF controller3

Schedule timer3

Adaptor for wiring2

Direct installation type

Wiring adaptor for electrical appendices2

Sealing material of air discharge outletPanel spacer

Interface adaptor for SkyAir series

Installation box for adaptor PCB

Replacement long-life filter

Remote sensor (for indoor temperature)

DCS302CA61DCS301BA61

DCS601C51DST301BA61

KRP1BA57KRP4AA53KRCS01-1B

BYFQ60B3W1

BRC1C61

KDBH44BA60KDBQ44BA60A

KDDQ44XA60

DTA112BA51

KRP1BA101

KAFQ441BA60

Note: 1Wiring for wired remote controller to be procured locally.2Installation box for adaptor PCB (KRP1BA101) is necessary. 3This optional accessory requires DTA112BA51.

Option List

Remote controller Wireless type Cooling only

BRC1E62Navigation Remote Controller Wired type1

Wired type1

FFQ25/35/50/60B

COMPACT MULTI FLOW CEILING MOUNTED CASSETTE TYPE

Quiet decor-blending form and easyinstallation in new or old buildingQuiet decor-blending form and easyinstallation in new or old building

Accessory required for indoor unit.

BRC1C61

Wired LCD Remote Controller

Note: Remote controller cable is not included and must be obtained locally.

A signal receiver must be added to the indoor unit.

Wireless LCD remote controller

Signal receiver unit (Installed type)

Wireless remote controller is suppliedin a set with a signal receiver.

BRC7E531W

SIZED TO FIT INSIDE 600mm WIDE CEILING GRIDS

MULTI-FLOW SYSTEM

QUIET, SMALL-DIAMETER FAN

AIR DIRECTION CAN BE SELECTEDACCORDING TO INSTALLATION

CONSISTENT COMFORT THROUGHOUT

TWO SELECTABLE TEMPERATURE-SENSORS

FEATURES

BRC1E63

Navigation Remote Controller(Wired Remote Controller)

Note: Remote controller cable is not included and must be obtained locally.

3029

Page 17: AIR CONDITIONING SYSTEM

intelligent Touch Controller2

Kit nameName of option

FHQ50DAVM4 FHQ60DAVM4

DCS302CA61DCS301BA61DST301BA61

KAFP501A56

Remark

Replacement long-life filter

L-type piping kit (for upward direction)Remote controller

Resin net

Wireless type

Central remote controllerUnified ON/OFF controllerSchedule timer

Wiring adaptor for electrical appendicesWiring adaptor for electrical appendices3

Installation box for adaptor PCB

Option List

Note: 1Wiring for wired remote controller to be procured locally.2The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.3Installation box for adaptor PCB(KRP1D93A) is necessary.

Cooling only

FHQ71DAVM4 FHQ100DAVM4 FHQ125DAVM4 FHQ140DAVM4

KRP1BA54DCS601C51

KRP4AA52

KAFP501A80 KAFP501A160

KJB311AAKJB212AA

Remote sensor (for indoor temperature)Electrical box with earth terminal (3 blocks)Electrical box with earth terminal (2 blocks)

BRC1C61BRC1E62Navigation Remote Controller Wired type1

Wired type1

Drain pump kitFresh air intake kit

KDU50P140VEKDDQ50A140

BRC7GA56

KRP1D93AAdaptor box mounting plate KKSAP50A56

KHFP5N160

KRCS01-4B----------

SPECIFICATION (3 Phase)

kW

Btu/h

kWPower consumption

ModelName

Indoor unit

Outdoor unit

Outdoor unitPower supplyCooling capacity1,2

Rated (Min. - Max.)

140

FHQ140DAVM4

RZR140LUY14

13.3(6.2-15.4)

125

FHQ125DAVM4

RZR125LUY14

12.5(5.7-14.0)

W/WCOP 2.843.12

1 Phase, 220–240 V, 50 Hz 3 Phase, 380–415 V, 50 Hz

140

FHQ140DAVM4

RZR140LVVM4

13.3(6.2-15.4)

2.52

125

FHQ125DAVM4

RZR125LVVM4

12.5(5.7-14.0)

2.83 2.522.83 2.522.83 2.522.832.843.12

140

FHQ71DAVM4x2

RZR140LUY14

13.3(6.2-15.4)

Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).2Capacities are net, including a deduction for cooling for indoor fan motor heat.3The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.

VP20 (I.DØ20XO.DØ26)

30

Ø9.5Ø15.9

Ø26.0 (Hole)

°CDBCertified operation range

Motor output

CoolingNight quiet mode

CompressorCoil

kWRefrigerant charge (R-410A) kg

dB(A)dB(A)

Sound pressure level3

Dimensions (HXWXD) mm

Machine weight kg

Piping connections

mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit

Outdoor unit

Outdoorunit

mmMax. interunit piping length m

mMax. installation level difference

Type Hermetically sealed scroll typeType Cross fin coil

2.9

45 4645 46

21 to 46

1,170X900X32097

50

2.6

3.7(Charged for 30 m)

3.12.4

3.15 (Charged for 30 m)

50 (Equivalent length 70)

2.9

45 4645 46

2.4 3.12.4 3.1 2.4 3.12.4 3.1

125

FHQ60DAVM4x2

RZR125LUY14

12.5(5.7-14.0)

2.843.12

140

FHQ71DAVM4x2

RZR140LVVM4

13.3(6.2-15.4)

125

FHQ60DAVM4x2

RZR125LVVM4

12.5(5.7-14.0)

2.843.124.684.004.684.00 4.684.004.684.00

°CWBCertified operation range

Dimensions (HXWXD) mmdB(A)

Machine weight kg

Airflow rate (H/M/L) m3/min

Sound pressure level3 (H/M/L)

Indoorunit cfm

14 to 25

31/27/231,094/953/812 1,200/1,024/847

44/41/37 46/42/38 44/41/37 46/42/381,094/953/812 1,200/1,024/847

34/29/24 31/27/23 34/29/24

235X1590X69038

235X1590X69038

20.5/17/1415/12/10724/600/494530/424/353

38/36/3437/35/32235X1,270X690235X960X690

3225

20.5/17/1415/12/10724/600/494530/424/353

38/36/3437/35/32235X1,270X690235X960X690

3225

Cooling1

45,000(21,200-52,600)

42,700(19,500-47,800)

45,000(21,200-52,600)

42,700(19,500-47,800)

45,000(21,200-52,600)

42,700(19,500-47,800)

45,000(21,200-52,600)

42,700(19,500-47,800)

FHQ50/60/71/100/125/140DA

CEILING SUSPENDED TYPE

Comfortable airflow travels throughout the roomComfortable airflow travels throughout the room

100

FHQ100DAVM4

RZR100MVM4

10.0 (5.0-11.2)

3.03

60

FHQ60DAVM4

RZR60MVM4

6.0 (2.6-6.3)

1.58

SPECIFICATION (1 Phase)

3 Phase, 380–415 V, 50 Hz

kW

Btu/h

kWPower consumption

ModelName

Indoor unit

Outdoor unit

Power supplyCooling capacity1,2

Rated (Min. - Max.)

125100

FHQ100DAVM4 FHQ125DAVM4

RZR100MYM4 RZR125MYM4

140

FHQ140DAVM4

RZR140MYM4

10.0 (5.0-11.2)

12.5 (5.7-14.0)

50

FHQ50DAVM4

RZR50MVM4

5.0(2.3-5.6)

1.24 3.03 4.42

125

FHQ125DAVM4

RZR125MVM4

12.5 (5.7-14.0)

4.42

1 Phase, 220–240 V, 50 Hz

71

FHQ71DAVM4

RZR71MVM4

2.373.303.80W/WCOP 4.03 3.30 2.83

VP20 (I.DØ20XO.DØ26)

Hermetically sealed swing type

30

Ø9.5Ø15.9

990X940X32065

49

Ø26.0 (Hole)

2.031.9(Charged for 30 m)

595X845X30043

48

1.351.6 (Charged for 30 m)

°CDBCertified operation range

Motor output

CoolingNight quiet mode

CompressorCoil

kWRefrigerant charge (R-410A) kg

dB(A)dB(A)

Sound pressure level3

Dimensions (HXWXD) mmMachine weight kg

Piping connections

mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit

Outdoor unit

Outdoorunit

mmMax. interunit piping length m

mMax. installation level difference

TypeCross fin coil Micro channelType

73

49 52

1.92

4544

1.12

21 to 46

50 (Equivalent length 70)

1.76

5452 54

14.0(6.2-15.4)

5.552.522.833.00

7.1 (3.2-8.0)

20,500(8,900-21,500)

17,100(7,900-19,100)

24,200(10,900-27,300)

Cooling1

Outdoor unit

140

FHQ140DAVM4

RZR140MVM4

42/38/34235X1,590X690235X1,270X690

3832

28/24/2020.5/17/14988/847/706

38/36/34724/600/494

37/35/32235X960X690

25

15/12/10530/424/353

°CWBCertified operation range

Dimensions (HXWXD) mmdB(A)

Machine weight kg

Airflow rate (H/M/L) m3/min

Sound pressure level3 (H/M/L)

Indoorunit cfm

42/38/3446/42/38 44/41/37

28/24/20 31/27/23988/847/706 1,094/953/812

14 to 25

44/41/37

31/27/231,094/953/812

46/42/38

34/29/241,200/1,024/847

34/29/241,200/1,024/847

14.0(6.2-15.4)

34,100(17,100-38,200)

34,100(17,100-38,200)

42,700(19,500-47,800)

42,700(19,500-47,800)

47,800(21,200-52,600)

47,800(21,200-52,600)

5.552.52

Accessory required for indoor unit.

BRC1C61

Wired LCD Remote Controller

Note: Remote controller cable is not included and must be obtained locally.

A signal receiver must be added to the indoor unit. Wireless LCD remote controller

BRC7GA56

Wireless remote controller is supplied in a set with a signal receiver.

Signal receiver unit (Installed type)

BRC1E63

Navigation Remote Controller(Wired Remote Controller)

Note: Remote controller cable is not included and must be obtained locally.

SOPHISCATED DESIGN

FLEXIBLE INSTALLATION

AUTO SWING & LOUVERS

NON FLOCKING FLAP

SUITABLE FOR HIGH CEILINGS

QUIET OPERATION

FEATURES

3231

Page 18: AIR CONDITIONING SYSTEM

Cooling capacity1,2

Rated (Min. - Max.) kW

Btu/h

kWPower consumption

ModelName

Indoor unit

Power supply

Cooling1

SPECIFICATION (1 Phase, 3 Phase)100

FAQ100CVEA4

RZR100MVM4

100

FAQ100CVEA4

RZR100MYM4

10.0(5.0-11.2)

34,100(17,100-38,200)

°CWBCertified Operation range

Dimensions (HXWXD) mmdB(A)

Machine weight kg

Airflow rate (H/M/L)

Sound pressure level3 (H/M/L)

Indoorunit

m3/min

49/45/41

17340X1,200X240

26/23/19

14 to 25

cfm 918/812/671

3.37

W/WCOP 2.97

1 Phase, 220–240 V, 50 Hz 3 Phase, 380–415 V, 50 Hz

Outdoor unit

Outdoor unit

°CDBCertified Operation range

Sound pressure level 3

Motor outputCompressor

Coil

kWRefrigerant charge (R-410A) kg

dB(A)

Dimensions (HXWXD) mm

Machine weight kg

Piping connections

mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit

Outdoor unit

Outdoorunit

mmMax. interunit piping length m

mMax. installation level difference

Type

Cooling

Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).2Capacities are net, including a deduction for cooling for indoor fan motor heat.3The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.

Ø9.5

49dB(A)Night quiet mode 45

30

Ø15.9

Hermetically sealed swing typeType Micro channel

Ø26.0 (Hole)

1.9 (Charged for 30 m)

21 to 46

50 (Equivalent length 70m)

990X940X32065 73

2.03 1.92

VP13 (O.DØ18 X I.DØ13)

BRC1C61

intelligent Touch Controller2

Note: 1Wiring for wired remote controller to be procured locally.2The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.3Installation box for adaptor PCB (KRP4AA93) is necessary.

Option ListName of option Remark

Central remote controller2

Remote controller

Unified ON/OFF controller2

Schedule timer2

Wiring adaptor for electrical appendices3

Electrical box with earth terminal (3 blocks)Electrical box with earth terminal (2 blocks)

Kit nameFAQ100CVEA4

DCS302CA61DCS301BA61DST301BA61DCS601C51KRP4AA51

KJB311AAKJB212AA

Drain-up kit

Installation box for adaptor PCB

Noise filter ( For electromagnetic interface use only)

Remote sensor (for Indoor temperature) KRCS01-4B

K-KDU572EVE

KRP4AA93

KEK26-1A

BRC7EB519Wireless type

BRC1E62Navigation Remote Controller Wired type1

Wired type1

Cooling only

WALL MOUNTED TYPE

Compact designand easy installationCompact designand easy installation

FAQ100C

Accessory required for indoor unit.

BRC1E63

Navigation Remote Controller(Wired Remote Controller)

Note: Remote controller cable is not included and must be obtained locally.

BRC1C61

Wired LCD Remote Controller

Note: Remote controller cable is not included and must be obtained locally.

A signal receiver must be added to the indoor unit.

Wireless LCD remote controller

BRC7EB519

Wireless remote controller is supplied in a set with a signal receiver.

Signal receiver unit (Installed type)

COMPACT & SOPHISCATED DESIGN

6-DIRECTION REFRIGERANT PIPING FLEXIBILITY

AUTO SWING & WIDE-ANGEL LOUVERS

INTERLOCK CONTROL

COMFORT EVEN ON THE FAR SIDE OF THE ROOM

EASY CLEANING

FEATURES

3433

Page 19: AIR CONDITIONING SYSTEM

Power supply 1 Phase, 220–240 V, 50 Hz1 Phase, 220–240 V, 50 Hz

SPECIFICATION (1 Phase)

ModelName

Indoor unit

Outdoor unit

Indoor unitOutdoor unit

kW

Btu/h

°CDB

°CWB

Cooling

Certified Operation range

Certified Operation range

Motor outputCompressorCoil

Indoorunit

Dimensions (HXWXD)Air filter5

Colour

mm

dB(A)

kWRefrigerant charge (R-410A)Sound pressure level4

Sound pressure level4 (H/M/L)

dB(A)

Dimensions (HXWXD) mmMachine weight kg

Piping connections

mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit

Machine weight kg

kg

Airflow rate (H/M/L)Fan

Outdoorunit

Colour

Heat insulation

Max. interunit piping length mmMax. installation level difference

Type

----------

Both liquid and gas piping

mmOutdoor unit

Ivory white

kWCooling1Power consumption

Pa

cfm

Night quiet mode dB(A)

External static pressure3

Cooling capacity1,2

Rated (Min. - Max.)

30

21 to 46

14 to 25

m3/min

50

FBQ50EVE4

RZR50MVM4

5.0 (2.3-5.6)

50 (Equivalent length 70)

VP25 (I.DØ25XO.DØ32)

Ø9.5Ø15.9

Ø26.0 (Hole)

1.12

1.39

60

FBQ60EVE4

RZR60MVM4

6.0(2.6-6.3)

245X1,000X800----------

37

595X845X30043

Hermetically sealed swing typeType Micro channelCross fin coil

1.351.6 (Charged for 30 m)

635/530/44118/15/12.5

1.69

35/33/31

48

71

FBQ71EVE4

RZR71MVM4

7.1 (3.2-8.0)

1.76

2.22

140

FBQ140EVE4

RZR140MVM4

14.0(6.2-15.4)

5.85

4544

Rated 50 (50-150)

100

FBQ100EVE4

RZR100MVM4

990X940X320

10.0 (5.0-11.2)

65

2.031.9(Charged for 30 m)

1,130/953/79432/27/22.5

812/688/56523/19.5/16

2.82

38/35.5/3338/35/33

49 52 54 52 54

125

FBQ125EVE4

RZR125MVM4

12.5 (5.7-14.0)

245X1,400X80047

1,271/1,077/88336/30.5/25

4.58

40/37.5/35

100

FBQ100EVE4

RZR100MYM4

10.0 (5.0-11.2)

1,130/953/794

73

1.92

32/27/22.5

2.82

38/35.5/33

49

3 Phase, 380–415 V, 50 Hz

125

FBQ125EVE4

RZR125MYM4

12.5 (5.7-14.0)

1,271/1,077/88336/30.5/25

4.58

40/37.5/35

140

FBQ140EVE4

RZR140MYM4

14.0(6.2-15.4)

17,100(7,900-19,100)

20,500(8,900-21,500)

24,200(10,900-27,300)

47,800(21,200-52,600)

34,100(17,100-38,200)

42,700(19,500-47,800)

34,100(17,100-38,200)

42,700(19,500-47,800)

47,800(21,200-52,600)

5.85W/WCOP 3.60 3.56 3.20 2.393.55 2.73 3.55 2.73 2.39

Wh/WhCSPF 5.40 5.20 5.04 4.384.73 4.61 4.73 4.61 4.38

SPECIFICATION (3 Phase)

Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)2Capacities are net, including a deduction for cooling for indoor fan motor heat.3External static pressure is changeable in 11 stages by remote controller.4The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.5Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency(gravity method) 50% or more.

Power supply 1 Phase, 220–240 V, 50 Hz1 Phase, 220–240 V, 50 Hz 3 Phase, 380–415 V, 50 Hz

ModelName

Indoor unit

Outdoor unit

Indoor unitOutdoor unit

kW

Btu/h

°CDB

°CWB

Cooling

Certified Operation range

Certified Operation range

Motor outputCompressor

Coil

Indoorunit

Dimensions (HXWXD)Air filter5

Colour

mm

dB(A)

kWRefrigerant charge (R-410A)Sound pressure level4

Sound pressure level4 (H/M/L)

dB(A)

Dimensions (HXWXD) mmMachine weight kg

Piping connections

mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit

Machine weight kg

kg

Airflow rate (H/M/L)Fan

Outdoorunit

Colour

Heat insulation

Max. interunit piping length mmMax. installation level difference

Type

----------

Both liquid and gas piping

mmOutdoor unit

Ivory white

kWCooling1Power consumption

Pacfm

Night quiet mode dB(A)

External static pressure3

Cooling capacity1,2

Rated (Min. - Max.)

30

21 to 46

14 to 25

m3/min

50 (Equivalent length 70)

VP25 (I.DØ25XO.DØ32)

Ø9.5Ø15.9

Ø26.0 (Hole)

----------

Rated 50 (50-150)

1,170X900X32097

125

FBQ125EVE4

RZR125LUY14

12.5 (5.7-14.0)

1,271/1,077/88336/30.5/25 18/15/12.5 23/19.5/16

635/530/441 812/688/565 1,271/1,077/883 635/530/441 812/688/56536/30.5/25 18/15/12.5 23/19.5/16

40/37.5/35 35/33/31 38/35/33 40/37.5/35 35/33/31 38/35/33

3.73

245X1,000X800245X1,400X80047 37 47 37

140

FBQ140EVE4

RZR140LUY14

125

FBQ125EVE4

RZR125LVVM4

140

FBQ140EVE4

RZR140LVVM4

14.0(6.2-15.4)

4.71W/WCOP 3.35 2.97

12.5 (5.7-14.0)

3.73

14.0(6.2-15.4)

4.713.35 2.97

3.15 (Charged for 30 m)50

45

2.4 2.9

46

Hermetically sealed scroll typeType Cross fin coil

125

FBQ60EVE4x2

RZR125LUY14

12.5 (5.7-14.0)

3.73

140

FBQ71EVE4x2

RZR140LUY14

125

FBQ60EVE4x2

RZR125LVVM4

140

FBQ71EVE4x2

RZR140LVVM4

14.0(6.2-15.4)

4.713.35 2.97

12.5 (5.7-14.0)

3.73

14.0(6.2-15.4)

42,700(19,500-47,800)

47,800(21,200-52,600)

42,700(19,500-47,800)

47,800(21,200-52,600)

42,700(19,500-47,800)

47,800(21,200-52,600)

42,700(19,500-47,800)

47,800(21,200-52,600)

4.713.35 2.97

45

2.4 2.9

46

245X1,000X800245X1,400X800

3.7(Charged for 30 m)

45

2.92.4

46 45

2.4 2.9

46

DUCT CONNECTION MIDDLE and HIGH STATIC PRESSURE TYPE

FBQ50/60/71/100/125/140E

Thinner design allows greater installation flexibilityThinner design allows greater installation flexibility

Option List

Only one mounting plate can be installed for each indoor unit.Mounting plate is necessary for each adaptor marked .

FBQ50EVE4 FBQ60EVE4 FBQ71EVE4 FBQ100EVE4 FBQ125EVE4 FBQ140EVE4Name of option Remark

High-efficiency filter1

Filter chamber(for rear suction)1

Long-life filter1

Air discharge adaptor

Adaptor for wiring Wiring adaptor for electrical appendices(2)Remote sensorMounting plate for adaptor PCB.3,4,5

Central remote controller6

Unified ON/OFF controller6

Schedule timer6

intelligent Touch Controller6

Service panel

Remote controller

65%90%

WhiteFresh whiteBrown

Wired type2

Wired type2

Wireless type Cooling only

Kit name

KAFP632B80

Shield plate for side plate

Navigation Remote Controller

KAFP632B160KAFP633B80 KAFP633B160KDDFP63B80 KDDFP63B160KAFP631B80 KAFP631B160KTBJ25K80W KTBJ25K160WKTBJ25K80F KTBJ25K160FKTBJ25K80T KTBJ25K160TKDAP25A71A

KDBD63A160BRC4C66BRC1C61BRC1E62

KRCS01-4BKRP4A98

DCS302CA61DCS301BA61DST301BA61DCS601C51

KDAP25A140A

Note: 1If installing high efficiency filter and long-life filter to the unit, filter chamber is required.

3

4Up to 2 adaptors can be fixed for each mounting plate.2Wiring for wired remote controller to be procured locally. 5

6The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.

KRP1C64KRP4AA51

DESIGN & INSTALLATION FLEXIBILITY

ADJUSTABLE EXTERNAL STATIC PRESSURE

SILVER ION ANTI-BACTERIAL DRAIN PAN

INTERLOCK CONTROL

SWITCHABLE FAN SPEED

EASY MAINTENANCE

FEATURES

Accessory required for indoor unit.

BRC1C61

Wired LCD Remote Controller

Note: Remote controller cable is not included and must be obtained locally.

A signal receiver must be added to the indoor unit. Wireless LCD remote controller

BRC4C66Signal receiver unit

(Installed type)Wireless remote controller is suppliedin a set with a signal receiver.

BRC1E63

Navigation Remote Controller(Wired Remote Controller)

Note: Remote controller cable is not included and must be obtained locally.

3635

Page 20: AIR CONDITIONING SYSTEM

Note: Remote controller cable is not included and must be procured locally.

Wired LCD remote controller

BRC1C61

Accessory required for indoor unit.

BRC1E63 can be

incorporated into the

indoor unit.

(Wired Remote Controller)

Navigation Remote Controller

Note: Remote controller cable is not included and must be procured locally.

BRC1E63

FVQ50/60/71/100/125/140C

New airflow controlfor more comfortNew airflow controlfor more comfort

SPECIFICATION (1 Phase)

Power supply 1 Phase, 220–240 V, 50 Hz 3 Phase, 380–415 V, 50 Hz

ModelName

Indoor unit

Outdoor unit

Outdoor unit

kW

Btu/h

kWCooling1Power consumption

Cooling capacity1,2

Rated (Min. - Max.)

71

FVQ71CVEB4

RZR71MVM4

60

FVQ60CVE4

RZR60MVM4

50

FVQ50CVE4

RZR50MVM4

7.1 (3.2-8.0)

2.58

140

FVQ140CVEB4

RZR140MVM4

14.0(6.2-15.4)

5.89

100

FVQ100CVEB4

RZR100MVM4

10.0 (5.0-11.2)

3.28

125

FVQ125CVEB4

RZR125MVM4

140

FVQ140CVEB4

RZR140MYM4

100

FVQ100CVEB4

RZR100MYM4

125

FVQ125CVEB4

RZR125MYM4

12.5 (5.7-14.0)

4.62

°CWBCertified Operation range

Indoorunit

Dimensions (HXWXD) mmdB(A)Sound pressure level3 (H/M/L)

Machine weight kg

Airflow rate (H/M/L)Fancfm

14 to 25

m3/min

1,850X600X27039

635/565/49418/16/14

43/41/38988/883/777

28/25/22988/918/847

28/26/241,059/988/918

30/28/26

50/47/441,850X600X350

47

53/51/4851/48/46988/883/777

28/25/22988/918/847

28/26/241,059/988/918

30/28/26

50/47/44 53/51/4851/48/46

°CDB

Cooling

Certified Operation range

Motor outputCompressor

Coil

kWRefrigerant charge (R-410A)Sound pressure level3

dB(A)

Dimensions (HXWXD) mmMachine weight kg

Piping connections

mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit

kg

Outdoorunit

Max. interunit piping length mmMax. installation level difference

Type

mmOutdoor unit

Night quiet mode dB(A)

30

21 to 46

50 (Equivalent length 70)

VP20 (I.DØ20XO.DØ26)

Ø9.5Ø15.9

Ø26.0 (Hole)

595X845X30043

Hermetically sealed swing typeType Cross fin coil Micro channel

1.6 (Charged for 30 m)48

1.761.351.12 1.92

4544990X940X320

65

2.031.9 (Charged for 30 m)

49 52 54

73

49 52 54

W/WCOP 2.75

6.0 (2.6-6.3)

1.843.26

5.0 (2.3-5,6)

1.273.94 2.383.05 2.71

14.0(6.2-15.4)

5.89

10.0 (5.0-11.2)

3.28

12.5 (5.7-14.0)

24,200(10,900-27,300)

47,800(21,200-52,600)

34,100(17,100-38,200)

42,700(19,500-47,800)

20,500(8,900-21,500)

17,100(7,900-19,100)

47,800(21,200-52,600)

34,100(17,100-38,200)

42,700(19,500-47,800)

4.622.383.05 2.71

Power supply 1 Phase, 220–240 V, 50 Hz 3 Phase, 380–415 V, 50 Hz

ModelName

Indoor unit

Outdoor unit

Outdoor unit

kW

Btu/h

kWCooling1Power consumption

Cooling capacity1,2

Rated (Min. - Max.)

125

FVQ125CVEB4

RZR125LUY14

12.5 (5.7-14.0)

4.39

140

FVQ140CVEB4

RZR140LUY14

125

FVQ125CVEB4

RZR125LVVM4

140

FVQ140CVEB4

RZR140LVVM4

13.5(6.2-15.4)

5.40W/WCOP 2.85 2.50

12.5 (5.7-14.0)

4.39

13.5(6.2-15.4)

5.402.85

°CWBCertified Operation range

Indoorunit

Dimensions (HXWXD) mmdB(A)Sound pressure level3 (H/M/L)

Machine weight kg

Airflow rate (H/M/L)Fancfm

14 to 25

m3/min 28/26/24 30/28/26 18/16/14 28/26/24 30/28/26 18/16/14988/918/847 1,059/988/918 635/565/494

51/48/461,850X600X350 1,850X600X270

47 39 47 391,850X600X350 1,850X600X270

53/51/48 43/41/38 51/48/46 53/51/48 43/41/38988/918/847 1,059/988/918 635/565/494

2.50

125

FVQ60CVE4x2

RZR125LUY14

12.5 (5.7-14.0)

4.39

140

FVQ71CVEB4x2

RZR140LUY14

125

FVQ60CVE4x2

RZR125LVVM4

140

FVQ71CVEB4x2

RZR140LVVM4

13.5(6.2-15.4)

5.402.85 2.50

12.5 (5.7-14.0)

4.39

13.5(6.2-15.4)

42,700(19,500-47,800)

46,100(21,200-52,600)

42,700(19,500-47,800)

46,100(21,200-52,600)

42,700(19,500-47,800)

46,100(21,200-52,600)

42,700(19,500-47,800)

46,100(21,200-52,600)

5.402.85 2.50

Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal)2Capacities are net, including a deduction for cooling for indoor fan motor heat.3The operation sound is measured in anechoic chamber. If it is measured under the actual installation conditions, it is normally over the set value due to environmental noise and sound reflection.

°CDB

Cooling

Certified Operation range

Motor outputCompressor

Coil

kW

Refrigerant charge (R-410A)Sound pressure level3

dB(A)

Dimensions (HXWXD) mmMachine weight kg

Piping connections

mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit

kg

Outdoorunit

Max. interunit piping length mmMax. installation level difference

Type

mmOutdoor unit

Night quiet mode dB(A)

30

21 to 46

50 (Equivalent length 70)

VP20 (I.DØ20XO.DØ26)

Ø9.5Ø15.9

Ø26.0 (Hole)

1,170X900X320

5045

97

2.8 3.4

46

3.15 (Charged for 30 m)

45

2.4 3.1

46

Hermetically sealed scroll typeType Cross fin coil

3.7 (Charged for 30 m)

45

2.8 3.4

4645

2.4 3.1

46

SPECIFICATION (3 Phase)

Option ListKit name

Name of optionFVQ71CVEB4 FVQ100CVEB4FVQ50CVE4 FVQ60CVE4

DCS302CA61DCS301BA61DST301BA61

KAFJ95L160

Remark

Replacement long-life filterBRC1C61Remote controller

Navigation Remote ControllerCentral remote controller2

Unified ON/OFF controller2

Schedule timer2

intelligent Touch Controller2

Adaptor for wiring3

Wiring adaptor for electrical appendicesInstallation box for adaptor PCB

Note: 1Wiring for wired remote controller to be procured locally. 2The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary.3Installation box for adaptor PCB (KRP4AA95) is necessary.

FVQ125CVEB4 FVQ140CVEB4

KRP1BA57DCS601C51

KRP4AA52KRP4AA95

BRC1E62Wired type1

Wired type1

NEW COMFORTABLE AIRFLOW CONTROL

LONG-LIFE FILTER

SWITCHABLE FAN SPEED

SAFETY LOCK FUNCTION OF SUCTION GRILLE

QUIET OPERATION

QUICK & EASY TO INSTALL & MAINTENANCE

FEATURES

FLOOR STANDING TYPE

3837