A

B

C

C.1

Technical overview

Air circuit breakers 400A-4000A

Order codes

Wiring DiagramsDimensional drawings

C.2 Mpro 27 & 50 Connection SchemeC.6 Dimensional drawings

Page 2: Air circuit breakers 400A-4000A Technical overview A · A B C C.1 Technical overview Air circuit breakers 400A-4000A Order codes Wiring Diagrams Dimensional drawings C.2 Mpro 27 &

M-PACT

A

B

C

Wir

ing

diag

ram

sD

imen

sion

al d

raw

ings

C.2

Connection scheme

N-RC

A15 A14

N-RC- +

N

B 5 B 6

24V+ 24V-

+24-VDC

Electronic Trip Unit MPRO 27

Connection scheme

Relay O/P2

A 6 A 5

Relay O/P1

A 8 A 7

Electronic Trip Unit MPRO 50

N-RC

A15 A14

N-RC- +

N

Relay O/P3 Relay O/P4

A 2 A 1A 4 A 3 B 5 B 6

24V+ 24V-

+24-VDC

EL CT

B 3 B 4

Interposing CT

A12 A11 A10 A 9

1 2 3 4

Input 1 - 4

A13

C

A20 A19

RX- RX+

Communication

A16

SCR

A18 A17

TX- TX+

N

Breaker accessories

OFF ONOFF

C15

AAAAABBBAA

C

D

MLAL

M ST CC UVRUVTD

C13

C11

C9C7C5C3C1

B15

B13

(+VE)(-VE)

B11

C16

C14

C12

C10

LP6

LP5

LP7

C8C6C4C2

B16

B14

(-VE)

B12

B10

B8

LP4

B9B7

(+VE)

B1B2

Mpro 27 & 50 Connection Scheme

Wiring Diagrams

Page 3: Air circuit breakers 400A-4000A Technical overview A · A B C C.1 Technical overview Air circuit breakers 400A-4000A Order codes Wiring Diagrams Dimensional drawings C.2 Mpro 27 &

A

B

C

C.3

Dimensional drawingsHorizontal, rear access connectionFixed patternType A-3 pole- Frame size 1, In=400A to 1600A

Type A-4 pole- Frame size 1, In=400A to 1600A

100 to door

100

Centre line of operating panel

Centre line of operating panel

Centre line ofoperating panel

Centre line ofoperating panel

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Minimum space to earth metaland for arc chute removal

Minimum space to earth metaland for arc chute removal

Insulated metal or insulatedsheet ( customer supplied )

Insulated metal or insulatedsheet ( customer supplied )

Dim

ensional drawings

Page 4: Air circuit breakers 400A-4000A Technical overview A · A B C C.1 Technical overview Air circuit breakers 400A-4000A Order codes Wiring Diagrams Dimensional drawings C.2 Mpro 27 &

M-PACT

A

B

C

Wir

ing

diag

ram

sD

imen

sion

al d

raw

ings

C.4

Horizontal, rear access connectionFixed patternType D-3 pole- Frame size 1, In=400A to 1600A

100 to door

100 to door

Centre line of operating panel

Centre line of operating panel

Centre line ofoperating panel

Centre line ofoperating panel

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Minimum space to earth metaland for arc chute removal

Minimum space to earth metaland for arc chute removal

Insulated metal or insulatedsheet ( customer supplied )

Insulated metal or insulatedsheet ( customer supplied )

Type D-4 pole- Frame size 1, In=400A to 1600A

Page 5: Air circuit breakers 400A-4000A Technical overview A · A B C C.1 Technical overview Air circuit breakers 400A-4000A Order codes Wiring Diagrams Dimensional drawings C.2 Mpro 27 &

A

B

C

C.5

100 to door

100 to door

Horizontal, rear access connectionFixed patternType A, D-3 pole- Frame size 1, In=2000A to 2500A

Centre line of operating panel

Centre line of operating panel

Centre line ofoperating panel

Centre line ofoperating panel

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Minimum space to earth metaland for arc chute removal

Minimum space to earth metaland for arc chute removal

Insulated metal or insulatedsheet ( customer supplied )

Insulated metal or insulatedsheet ( customer supplied )

Type A, D-4 pole- Frame size 1, In=2000A to 2500A

Dim

ensional drawings

Page 6: Air circuit breakers 400A-4000A Technical overview A · A B C C.1 Technical overview Air circuit breakers 400A-4000A Order codes Wiring Diagrams Dimensional drawings C.2 Mpro 27 &

M-PACT

A

B

C

Wir

ing

diag

ram

sD

imen

sion

al d

raw

ings

C.6

Horizontal, rear access connectionFixed patternType A, D-3 pole- Frame size 2, In=3200A to 4000AType H-3 pole- Frame size 2, In=800A to 4000A

100 to door

100 to door

Centre line of operating panel

Centre line of operating panel

Centre line ofoperating panel

Centre line ofoperating panel

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Minimum space to earth metaland for arc chute removal

Minimum space to earth metaland for arc chute removal

Insulated metal or insulatedsheet ( customer supplied )

Insulated metal or insulatedsheet ( customer supplied )

Type A, D-4 pole- Frame size 2, In=3200A to 4000AType H-4 pole- Frame size 2, In=800A to 4000A

Page 7: Air circuit breakers 400A-4000A Technical overview A · A B C C.1 Technical overview Air circuit breakers 400A-4000A Order codes Wiring Diagrams Dimensional drawings C.2 Mpro 27 &

A

B

C

C.7

Rear access connectionWithdrawable patternType A-3 pole- Frame size 1, In=400A to 1600A

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Centre line of operating panel

Centre line of operating panel

35 Test50 Disconnected

275 Fully withdrawn

Connected

Ventilation

Minimum clearanceto cassette side

Centre line of operating panel

Centre line of operating panel

35 Test50 Disconnected

275 Fully withdrawn

Connected

Ventilation

Minimum clearanceto cassette side

to door

to door

Type A-4 pole- Frame size 1, In=400A to 1600A

Dim

ensional drawings

Page 8: Air circuit breakers 400A-4000A Technical overview A · A B C C.1 Technical overview Air circuit breakers 400A-4000A Order codes Wiring Diagrams Dimensional drawings C.2 Mpro 27 &

M-PACT

A

B

C

Wir

ing

diag

ram

sD

imen

sion

al d

raw

ings

C.8

Rear access connectionWithdrawable patternType A-3 pole- Frame size 1, In=2000A & 2500AType D-3 pole- Frame size 1, In=400A to 2500A

Type A-4 pole- Frame size 1, In=2000A & 2500AType D-4 pole- Frame size 1, In=400A to 2500A

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Centre line of operating panel

Centre line of operating panel

35 Test

50 Disconnected

275 Fully withdrawn

Connected

Ventilation

Minimum clearanceto cassette side

Centre line of operating panel

Centre line of operating panel

35 Test

50 Disconnected275 Fully withdrawn

Connected

Ventilation

Minimum clearanceto cassette side

to door

to door

Page 9: Air circuit breakers 400A-4000A Technical overview A · A B C C.1 Technical overview Air circuit breakers 400A-4000A Order codes Wiring Diagrams Dimensional drawings C.2 Mpro 27 &

A

B

C

C.9

Rear access connectionWithdrawable patternType A, D-3 pole- Frame size 2, In=3200AType H-3 pole- Frame size 2, In=800A to 3200A

Type A, D-4 pole- Frame size 2, In=3200AType H-4 pole- Frame size 2, In=800A to 3200A

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

to door

to door

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

50 Disconnected35 Test

275 Fully withdrawn

50 Disconnected35 Test

275 Fully withdrawn

Connected

Connected

Vent

ilatio

n

Ventilation

Minimum clearance to cassette side

Minimum clearance to cassette side

Dim

ensional drawings

Page 10: Air circuit breakers 400A-4000A Technical overview A · A B C C.1 Technical overview Air circuit breakers 400A-4000A Order codes Wiring Diagrams Dimensional drawings C.2 Mpro 27 &

M-PACT

A

B

C

Wir

ing

diag

ram

sD

imen

sion

al d

raw

ings

C.10

Rear access connectionWithdrawable pattern

Type A, D,H - 3 pole - Frame size 2, ln=4000A

Type A, D,H - 4 pole - Frame size 2, ln=4000A

Must not be removedor fitted horizontally

Must not be removedor fitted horizontally

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel 50 Disconnected

35 Test

275 Fully withdrawn

50 Disconnected35 Test

275 Fully withdrawn

Connected

Connected

to d

oor

to d

oor Ventilation

Vent

ilatio

n

Minimum clearance to cassette side

Minimum clearance to cassette side

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Page 11: Air circuit breakers 400A-4000A Technical overview A · A B C C.1 Technical overview Air circuit breakers 400A-4000A Order codes Wiring Diagrams Dimensional drawings C.2 Mpro 27 &

A

B

C

C.11

Front access connectionFixed pattern

Type A, D - 3 pole - Frame size 1, ln = 400A to 1600A

Type A, D - 4 pole - Frame size 1, ln = 400A to 1600A

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Insulated metalor insulated sheet(customer supplied)

Insulated metalor insulated sheet(customer supplied)

Minimum space to earth metaland for arc chute removal

Minimum space to earth metaland for arc chute removal

100 to door

100 to door

Minimum clearance to breaker side

Minimum clearance to breaker side

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Dim

ensional drawings

Page 12: Air circuit breakers 400A-4000A Technical overview A · A B C C.1 Technical overview Air circuit breakers 400A-4000A Order codes Wiring Diagrams Dimensional drawings C.2 Mpro 27 &

M-PACT

A

B

C

Wir

ing

diag

ram

sD

imen

sion

al d

raw

ings

C.12

Front access connectionFixed pattern

Type A, D - 3 pole - Frame size 1, ln = 2000A to 2500A

Type A, D - 4 pole - Frame size 1, ln = 2000A to 2500A

Insulated metalor insulated sheet(customer supplied)

Minimum space to earth metaland for arc chute removal

100 to door

Insulated metalor insulated sheet(customer supplied)

Minimum space to earth metaland for arc chute removal

100 to door

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Minimum clearance to breaker side

Minimum clearance to breaker side

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Page 13: Air circuit breakers 400A-4000A Technical overview A · A B C C.1 Technical overview Air circuit breakers 400A-4000A Order codes Wiring Diagrams Dimensional drawings C.2 Mpro 27 &

A

B

C

C.13

Front access connectionFixed pattern

Type A, D - 3 pole - Frame size 2, ln = 3200A to 4000AType H - 3 pole - Frame size 2, ln = 800A to 4000A

Type A, D - 4 pole - Frame size 2, ln = 3200A to 4000AType H - 4 pole - Frame size 2, ln = 800A to 4000A

Insulated metalor insulated sheet(customer supplied)

Minimum space to earth metaland for arc chute removal

100 to door

Insulated metalor insulated sheet(customer supplied)

Minimum space to earth metaland for arc chute removal

100 to door

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Minimum clearance to breaker side

Minimum clearance to breaker side

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Front access connection

Page 14: Air circuit breakers 400A-4000A Technical overview A · A B C C.1 Technical overview Air circuit breakers 400A-4000A Order codes Wiring Diagrams Dimensional drawings C.2 Mpro 27 &

M-PACT

A

B

C

Wir

ing

diag

ram

sD

imen

sion

al d

raw

ings

C.14

Center line ofoperating panel

Center line ofoperating panel

Minimum clearance to cassette side

Connected

Connected

Disconnected

Disconnected

Test

Test

to d

oor

to d

oor

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Front access connectionWithdrawable pattern

Type A, D - 3 pole - Frame size 1, ln = 400A to 1600A

Type A, D - 4 pole - Frame size 1, ln = 400A to 1600A

Page 15: Air circuit breakers 400A-4000A Technical overview A · A B C C.1 Technical overview Air circuit breakers 400A-4000A Order codes Wiring Diagrams Dimensional drawings C.2 Mpro 27 &

A

B

C

C.15

Front access connectionWithdrawable pattern

Type A, D - 3 pole - Frame size 1, ln = 2000A to 2500A

Type A, D - 4 pole - Frame size 1, ln = 2000A to 2500A

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Minimum clearance to cassette side

Minimum clearance to cassette side

Connected

Connected

Disconnected

Disconnected

Test

Test

to d

oor

to d

oor

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Front access connection

Page 16: Air circuit breakers 400A-4000A Technical overview A · A B C C.1 Technical overview Air circuit breakers 400A-4000A Order codes Wiring Diagrams Dimensional drawings C.2 Mpro 27 &

M-PACT

A

B

C

Wir

ing

diag

ram

sD

imen

sion

al d

raw

ings

C.16

Front access connectionFixed pattern

Type A, D - 3 pole - Frame size 2, ln = 3200A to 4000AType H - 3 pole - Frame size 2, ln = 800A to 4000A

Type A, D - 4 pole - Frame size 2, ln = 3200A to 4000AType H - 4 pole - Frame size 2, ln = 800A to 4000A

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Minimum clearance to cassette side

Minimum clearance to cassette side

Connected

Connected

DisconnectedTest

DisconnectedTest

to d

oor

to d

oor

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Page 17: Air circuit breakers 400A-4000A Technical overview A · A B C C.1 Technical overview Air circuit breakers 400A-4000A Order codes Wiring Diagrams Dimensional drawings C.2 Mpro 27 &

A

B

C

C.17

Adaptor connections

Rear Adapter Vertical ConnectionType A - Frame 1 - ln = 400A to 1600A (max)

Rear Adapter Horizontal ConnectionType A - Frame 1 - ln = 400A to 1600A (max)

Type D - Frame 1 - ln = 400A to 2500A (max)

Rear Adapter Vertical / Horizontal Connection

Type A,D,H - Frame 2 - ln = 800A to3200A (max)

Front access connection

Page 18: Air circuit breakers 400A-4000A Technical overview A · A B C C.1 Technical overview Air circuit breakers 400A-4000A Order codes Wiring Diagrams Dimensional drawings C.2 Mpro 27 &

M-PACT

A

B

C

Wir

ing

diag

ram

sD

imen

sion

al d

raw

ings

C.18

Type A - Frame 1 - ln = 400A to 2500A (max)Type D - Frame 1 - ln = 400A to 2500A (max)

Type A,D - Frame 2 - ln = 3200A to 4000A (max)Type H - Frame 2 - ln = 800A to 4000A (max)

Type A,D,H - Frame 2 - ln = 4000A

Copper connections - Rear access (withdrawable)

IP54 Door (Withdrawable unit only - Frame 1&2 only)

Copper connections - Front access (Fixed and/or withdrawable)

Page 19: Air circuit breakers 400A-4000A Technical overview A · A B C C.1 Technical overview Air circuit breakers 400A-4000A Order codes Wiring Diagrams Dimensional drawings C.2 Mpro 27 &

A

B

C

C.19

Type A,D - Frame 2 - ln = 3200A to 4000A (max)Type H - Frame 2 - ln = 800A to 4000A (max)

A. recommend installtion mounting cut

Cassette mounting details

Type A,D - Frame 1 - ln = 400A to 2500A (max)

Terminals

Terminals

Ventilation in base of cassette(leave unobstructed)

Ventilation in base of cassette(leave unobstructed)

Centre line ofoperating panel

Centre line ofoperating panel

3 pole

3 pole 4 pole

4 pole3 pole

4 pole

4 pole

4 pole

3 pole

3 pole

AA

A

A

A A

A

A

Adaptor connections

Page 20: Air circuit breakers 400A-4000A Technical overview A · A B C C.1 Technical overview Air circuit breakers 400A-4000A Order codes Wiring Diagrams Dimensional drawings C.2 Mpro 27 &

M-PACT

A

B

C

Wir

ing

diag

ram

sD

imen

sion

al d

raw

ings

C.20

Door cut-outs

Fixed pattern - Facia cut-out

Withdrawable pattern - Cubicle door/panel

Frame 1 = 42.5Frame 2 = 102.5

The cut-out dimensions shown above givean approximate nominal clearance of 30mm aroundACB fascia. These sizes are for guidanceand can be scaled if different apertureis required.

Escutcheon(LLA11PD055)

Escutcheon seal(LLA11RS001)

ACB facia16 off 3.0 6Self tapping screws

Frame 1 - Up to 2500A max.= 40Frame 2 - Up to 4000A max.= 100

Datum for 16 off 4 holes in door / panel - bottom left hand comer of cassette viewed from front.

Page 21: Air circuit breakers 400A-4000A Technical overview A · A B C C.1 Technical overview Air circuit breakers 400A-4000A Order codes Wiring Diagrams Dimensional drawings C.2 Mpro 27 &

A

B

C

C.21

2-Way cable interlocking

Fixed pattern - Front/rear access

Withdrawable pattern - Front/rear access

Min.clearancebelowcassette

Min.clearancebelowcassette

Min.bend radius 120

Min.bend radius 120 Min.bend radius 120

Min.bend radius 120

900

Max

ver

tical

bas

e to

bas

e90

0 M

ax v

ertic

al b

ase

to b

ase

Frame 1-3P = 322Frame 1-4P = 422Frame 2-3P = 410Frame 2-4P = 540

Frame 1-3P = 329Frame 1-4P = 429Frame 2-3P = 419Frame 2-4P = 549

Door cut-outs

Page 22: Air circuit breakers 400A-4000A Technical overview A · A B C C.1 Technical overview Air circuit breakers 400A-4000A Order codes Wiring Diagrams Dimensional drawings C.2 Mpro 27 &

GE Consumer & Industrial

Printing Code 119134

T : +82 2 6201 4300F : +82 2 6201 4343, 4344

T : +852 2100 6800

F : +886 2 2516 7356T : +61 2 8788 6911F : +61 2 8788 7224

BRI II Tower, 27th FloorJl. Jend Sudirman kav 44-46Jakarta. Indonesia 10210T : +62 21 573 0490F : +62 21 574 5241

Level 1, 8 Tangihua Street.Auckland. North Island.

Level 6, 1 Sentral, Jalan Travers, Kuala Lumpur 50470T : +603 2273 9788F : +603 2273 3481

240 Tanjong Pagar Road#06-00 GE TowerSingapore 088540T : +65 6326 3319F : +65 6326 3015

T : +63 2 895 7051 to 53F : +63 2 895 8332