Advances in Heating & Cooling Technologies Ruben Willmarth Comm. Regional Mgr

Transcript of Advances in Heating & Cooling Technologies -...

Page 1: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

Advances in Heating & Cooling

Technologies

Ruben WillmarthComm. Regional Mgr

Page 2: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

• Mini-Splits• VRF Systems• Mini-Splits• VRF Systems

Ductless HVACDuctless HVAC

Page 3: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

What is a Mini-Split?What is a Mini-Split?

• Indoor Fan Coil• Indoor Fan Coil

Page 4: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

4

Wall-mounted Indoor UnitWall-mounted Indoor Unit

Page 5: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

What is a Mini-Split?What is a Mini-Split?

• Outdoor “Condenser” Unit• Outdoor “Condenser” Unit

Connected with Refrigerant TubingConnected with Refrigerant Tubing

Page 6: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

Japan90%

7.2M Systems

China86%

16.7M Systems

Europe81%

7.6M Systems

USA3%

0.2M Systems

Ductless is a small percent of the U.S. HVAC market, but current building and energy usage trends indicate a large growth opportunity

Source: BSRA report 2005-2007

Worldwide Usage-Ductless Technology

WindowUnitaryChillersMovebleDuctless

Page 7: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

7

Split-zoning AdvantagesSplit-zoning Advantages

• Easy Retrofit• No Duct Losses• Inverter-Driven

Variable Speed Compressor

• Enormous Potential Savings with Zoning

• Easy Retrofit• No Duct Losses• Inverter-Driven

Variable Speed Compressor

• Enormous Potential Savings with Zoning

Page 8: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

8

Inefficient!

INVERTER Compressor AdvantagesINVERTER Compressor Advantages

Set Temp.

60Hz

Compressor

0Hz

90º F

73º FToo cool!Too cool!

Too warm!Too warm!

Too cool!Too cool!

Too warm!Too warm!

ON

OFF OFF

ON

OFF

ON

Long duration!

High starting current creates energy loss

Uncomfortable!

75º F

77º F

Conventional ON/OFF control

Page 9: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

9

INVERTER Compressor AdvantagesINVERTER Compressor Advantages

Set Temp. 75º F

60Hz

Compressor

0Hz

150Hz

30Hz

Starting current at low level

Room temperature is steadyRoom temperature is steady

High rotation speed up to 100-120Hz generates accelerated performance!

Keep rotation speed at low levels after temperature is stabilized.

Adjust rotation speed precisely to keep steady room temperatureAdjust rotation speed precisely to keep steady room temperature

90º F

ON

Very efficient!

Comfortable!Very fast!

Smooth INVERTER control

Page 10: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

10

INVERTER Compressor AdvantagesINVERTER Compressor Advantages

• Quiet start• No light flicker• No locked rotor amps for very low in-rush• Very low starting amperage• No stress on windings or compressor

frame• Bearing lubrication increased during

ramp-up• Reduces noise and stress on piping with

gradual start• Greatly improved heating capacity

• Quiet start• No light flicker• No locked rotor amps for very low in-rush• Very low starting amperage• No stress on windings or compressor

frame• Bearing lubrication increased during

ramp-up• Reduces noise and stress on piping with

gradual start• Greatly improved heating capacity

DC Compressor

Compressor starts at minimum frequency

Page 11: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

11

INVERTER Compressor AdvantagesINVERTER Compressor Advantages

DC rotary compressor motor equipped with powerful magnets assists compressor rotationDC rotary compressor motor equipped with powerful magnets assists compressor rotation

Magnetic torque

Reluctance torque

DC Compressor motor

Neodymium magnets

Efficiency!

Page 12: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

12

INVERTER Compressor AdvantagesINVERTER Compressor Advantages

PAM (Pulse Amplitude Modulation) adjusts the form of the output current wave so that it becomes close to that of the supply voltage wave.

98% of input power supply is effectively utilized.

PAM (Pulse Amplitude Modulation) adjusts the form of the output current wave so that it becomes close to that of the supply voltage wave.

98% of input power supply is effectively utilized.DC Compressor

Input current

Input voltage

Without PAM control

time

DC voltage

Input currentInput voltage

DC voltage

With PAM control

time

Page 13: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

13

Split-ductless AdvantagesSplit-ductless Advantages• Unmatched zone comfort• Extremely quiet• Flexible solutions• Efficient zoning• Easy to install

• Unmatched zone comfort• Extremely quiet• Flexible solutions• Efficient zoning• Easy to install

Page 14: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

14

A Heat Pump Like no OtherA Heat Pump Like no OtherHyper-Heating INVERTER

Hyper-heat INVERTER (H2iTM)Standard INVERTER Heat Pump systemTypical Unitary Equipment

-13 -4 0 5 10 17 25 30 35 40 47

120

100

80

60

40

20

0

100% @ 5o F

87% @ -4o F

80% @ -13o F

100% @ 5o F

87% @ -4o F

80% @ -13o F

Page 15: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

A Heat Pump Like No OtherA Heat Pump Like No Other

Lake Mills (Milwaukee), WI [Design 0°F] PK in Church

Page 16: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

A Heat Pump Like No OtherA Heat Pump Like No Other

Yes, it is +2°F Outside of the church

Page 17: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

A Heat Pump Like No OtherA Heat Pump Like No Other

Inside it is +70°F AND the Discharge temperature is +123°F

Page 18: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

Is a 12 EER Ducted = 12 EER Ductless??

Benefits of Ductless ApplicationBenefits of Ductless Application

*Many thanks to Ductesters for the use of these graphics

Page 19: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

Retrofit with 15% supply leakage:

12 EER Ducted x 0.85 = 10.2 EER

Benefits of Ductless ApplicationBenefits of Ductless Application

Page 20: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

20

True Zoning Benefits True Zoning Benefits

Residential Solutions Residential Solutions Commercial SolutionsCommercial Solutions

Page 21: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

Application of Multi-zone

2.5 Ton MXZ-3B30 (3,120W)18 mbh F.C.=1,270 Watts

9mbh+12mbh F.C.=1,940 Watts

12 EER Standard Ducted 2.5 ton2,500 Watts (Whole House)

True Zoning BenefitsTrue Zoning Benefits

Page 22: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

Variable Refrigerant

Flow Zoning

Systems

Page 23: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

History of VRFHistory of VRFVRF was introduced to the Japanese market in the early 1980s to provide a more efficient solution for heating and cooling buildings.

VRF was introduced to the Japanese market in the early 1980s to provide a more efficient solution for heating and cooling buildings.

Page 24: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

History of VRFHistory of VRF

VRF vs. Chiller in Japanese market

0

200

400

600

800

1,000

1985 1987 1989 1991 1993 1995 1997 1999 2001 2003 2005 2007

Tons

(Tho

usan

ds)

VRF Chiller

Page 25: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

Office Application-Standard ProcessOffice Application-Standard Process

Page 26: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

Fresno IRS BuildingFresno IRS Building

Page 27: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

What is VRF Technology?What is VRF Technology?

Variable

Refrigerant

Flow

Page 28: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

There are 3 ways to Move Thermal EnergyThere are 3 ways to Move Thermal Energy

•Air (low density, compressible)

•Water (high density, non-compressible)

•Refrigerant (phase change, compressible)

•Air (low density, compressible)

•Water (high density, non-compressible)

•Refrigerant (phase change, compressible)

Page 29: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

Air30” Diameter

Ductwork

Water2 1/2” Iron Pipe

2” Iron Pipe

Refrigerant R410A1 1/8” Copper Pipe

Space required to deliver 20 tons of cooling

Moving Thermal energy comparison

Page 30: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

VRF Heat Pump TechnologyVRF Heat Pump Technology

COOLING

HEATING

Page 31: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

VRF Heat Recovery TechnologyVRF Heat Recovery TechnologySimultaneous cooling and heatingSimultaneous cooling and heating

Page 32: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

Heating & Cooling with Traditional SystemsHeating & Cooling with Traditional Systems

Heat

CHILLER, COOLINGTOWER, &PUMPS

HeatBOILER& PUMPS

Typical Winter Loads

Page 33: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

Heating & Cooling WithVRF Heat Recovery

Typical Winter Loads

Heat

Page 34: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

Why is VRF More Efficient?Why is VRF More Efficient?

3000 BTUH

6000 BTUH

3000 BTUH3000 BTUH

Simultaneous Load:Cooling: 27000 BTUH

3000 BTUH

Heating: 21000 BTUH

Electrical

Room

JanitorCloset

Break Room

Lobby/Waiting Room

ConferenceRoom

Office #1 Office #2

Cubicle Area

Open WorkRoom

6000 BTUH

12000 BTUH6000 BTUH

3000 BTUH

PURY-P723000 BTUH

Bathroom

Bathroom

Sample Building in Part Load: OA Temp 50oF

Increased Efficiency OpportunityIncreased Efficiency Opportunity

Page 35: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

Why is VRF More Efficient? Why is VRF More Efficient?

Cooling Power Input PURY-P72

0.00

1.00

2.00

3.00

4.00

5.00

6.00

7.00

0 12000 24000 36000 48000 60000 72000 84000

System Load BTUH

Pow

er In

put K

W

72,000 BTUH6.48 KW

27,000 BTUH2.38 KW

Page 36: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

Why is VRF More Efficient?Why is VRF More Efficient?

Outdoor Temperature Power Input Correction(For a 68 Indoor WB Temperature)

1.5000

1.6000

1.7000

1.8000

1.9000

2.0000

2.1000

2.2000

2.3000

2.4000

0 10 20 30 40 50 60 70 80 90 100

OA Temperature FDB

Powe

r Inp

ut K

W

2.38 KW at 95oF

1.87 KW at 50oF

Page 37: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

School Energy Modeling ResultsSchool Energy Modeling ResultsSchool--Percentage Energy Cost Savings V/S Comparable Systems

0% 4% 7% 11% 14% 18% 21% 25% 28% 32%

Atlanta

Miami

Boston

NYC

Chicago

Dallas

LA

Seattle

Loca

tion

Energy Savings

CM v/s VAVCM v/s 4 PipeCM v/s WSHP

Page 38: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

Office Building Energy Modeling Results

Percentage Energy Savings V/S Comparable Systems

0% 4% 7% 11% 14% 18% 21% 25%

Atlanta

Miami

Boston

NYC

Chicago

Dallas

LA

Seattle

Loca

tion

Energy Savings

CM v/s 4 PipeCM v/s VAVCM v/s WSHP

Page 39: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

Italian Bank StudyItalian Bank Study

• Side-by-Side comparison of 14 branch retrofit– 7 Buildings with VRF– 7 with 4-pipe system (boiler, chiller)

• Equipment cost was higher for VRF• Installed cost was less for VRF

– 2 Copper pipes cost more, labor was less – 4 ABS pipes cost less, labor higher

• Side-by-Side comparison of 14 branch retrofit– 7 Buildings with VRF– 7 with 4-pipe system (boiler, chiller)

• Equipment cost was higher for VRF• Installed cost was less for VRF

– 2 Copper pipes cost more, labor was less – 4 ABS pipes cost less, labor higher

Page 40: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

Italian Bank StudyItalian Bank Study

Maintenance cost 40% lower for VRF

Operating cost lower for VRFEnergy cost was 28% to 48% lessAverage was 35% less

Maintenance cost 40% lower for VRF

Operating cost lower for VRFEnergy cost was 28% to 48% lessAverage was 35% less

Page 41: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

of a building’s energy usage is fromits HVAC system.

Source: http://www1.eere.energy.gov/buildings/commercial/hvac.html

40-60%40-60%

Page 42: Advances in Heating & Cooling Technologies - …cabec.org/wp-content/uploads/2011/10/Advances_heating_cooling... · 800 1,000 1985 1987 1989 1991 ... CM v/s VAV CM v/s 4 Pipe CM v/s

Sacramento Drill TowerSacramento Drill Tower

• Retrofit of Sac City offices inside 1st floor of water tower

• Old system was 30 Ton air-cooled chiller & natural draft boiler

• Replaced with 2x16 ton Heat Recovery VRF systems & all ducted fan coils

• ERV for ventilation air

Total Building Energy cost savings in 2009 vs. 2007= 27%

• Retrofit of Sac City offices inside 1st floor of water tower

• Old system was 30 Ton air-cooled chiller & natural draft boiler

• Replaced with 2x16 ton Heat Recovery VRF systems & all ducted fan coils

• ERV for ventilation air

Total Building Energy cost savings in 2009 vs. 2007= 27%