Advanced Generator Protection and Monitoring Using...
Transcript of Advanced Generator Protection and Monitoring Using...
Copyright © Snowy Hydro Limited and SEL 2017
Advanced Generator Protection and Monitoring Using
Transducer Measurements
Terry Foxcroft, Snowy Hydro Limited, Australia
and
Normann Fischer, Dale Finney, Satish Samineni, and Yu XiaSchweitzer Engineering Laboratories, Inc., USA
Protection Enhancements
Measurements Applications
Rotor and Exciter
Stator Winding
Generator Controls
LCI Starting
Bearings
Subsynchronous Resonance
Field Current and Voltage
DC Ground Current
Shaft Current
Shaft Angle
Typical Relay Data Acquisition System
VAC/IAC
VDC/IDC Antialiasing Filtering
Protection
Antialiasing FilteringADC
ADC
• Frequency-specific• Reject dc and the
harmonics• Suppresses inter
harmonics
Full-Cycle Cosine Filter
0 50 100 150 200 250 3000
0.2
0.4
0.6
0.8
1
Frequency (Hz)G
ain
(dB
)
• Includes all frequencies• Ideal for thermal
protection elements
RMS Filter Under- and Overestimates Magnitude
0 20 40 60 80 100 1200
0.5
1.0
Frequency (Hz)
Gai
n (d
B)
1.5
• Field quantity measurements• DC ground fault protection• Stator-field differential protection• Generator control monitoring • Subsynchronous resonance• Generator shaft currents
Applications
• Shaft current causes arcing
• Arcing removes metal from bearing face
• Guide bearing was also damaged
Damage to Thrust Bearing
• Monitoring shaft voltage is not effective
• Monitoring shaft current is best
• Requires shaft CTs
Detection of Shaft Currents
100Pe
rcen
tage
50
0
75
25
3.11Frequency (Hz)
15.53 40.37 65.2227.95 52.80
No Shaft Current Frequency Spectrum
Shaft Current Frequency Spectrum(2 A Primary)
100Pe
rcen
tage
50
0
75
25
50.0Frequency (Hz)
250.0 450.0 650.0 850.0 1050.0
• Additional generator measurements such as field voltage and current complement traditional protection
• Additional generator measurements increase the level of observability of the generator
• This allows generators to be operated more efficiently and economically
Conclusions