Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

78
Advanced Calculations Drill 1 for the 2011 NEC © Ted “Smitty” Smith 2012

Transcript of Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Page 1: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Advanced Calculations Drill 1 for the 2011 NEC

© Ted “Smitty” Smith 2012

Page 2: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• What is the minimum sized service required for a machine shop if the shop is equipped with the following:

• 50 feet of multioutlet assembly expected to be used simultaneously• 50 duplex receptacles at 125V• The following motors

– Single phase, 208V, ¼ hp, 2.9 A varying duty motor, 15 mins– Single phase, 208V, 1 ½ hp, 9.2 A intermittent duty motor, 5 mins– Three phase, 208V, 5 hp, 14.9 A 15 minute, short time duty motor, 15 mins– (3) single phase, 120V, ½ hp, 120V, 11.1 A, intermittent duty motors, 30 mins

• A 208V three phase, 41.6 A rated roof mounted HVAC system• The machine shop is 15000 square feet with 3000 square feet classified

office and 12,000 square feet classified warehouse.

• The service will be 208V, three phase.

Page 3: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• 175 ampere service

• Lighting= 10500 + 3000= 13500 va• Recepts= 9000+ 9000= 18000 -10000=8000 x.5 =4000 • 10000+ 4000= 14000 va• Motors = 6441.3 va• 723.84 va 1626.5 va 1198.8 va 1198.8 va 1198.8 vaRoof Mounted HVAC 41.6 x 1.732 x 208= 14986.6 vaTotal = 54874.64 / 208 /1.732= 152.32 amperes

Page 4: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Motor Calc

• What is the minimum sized THHN wire that can be used to feed the following motor:

• Three Phase, squirrel cage, 30 HP, 480 Volts, 33.6 amperes FLC, 1.15 marked service factor and Design K.

Page 5: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• 6 AWG THHN• Based on the 60 degree column of 310.16

based on 110.14(C)

Page 6: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Welding Calculation

• What is the minimum sized THHN copper conductor that can be used to feed six arc welders with the following ratings:

• 1. 50 A at 30 Duty Cycle• 2. 60 A at 40 duty cycle• 3. 100 at 10 duty cycle• 4. 100 A at 10 duty cycle• 5. 75 A at 50 duty cycle• 6. 44.6 A at 60 duty cycle

Page 7: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• 250 KCMIL• Determined by 6301.11 (A )and (B)• Table 310.16 Column 60 degrees C based on

110.14(C)

Page 8: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Load Calc

• How many 15 ampere lighting circuits will be required for a single family dwelling that is 2650 square feet to meet the minimum requirements of the National Electric Code?

Page 9: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• 5

• 2650 x 3= 7950/120=66.25 amperes/ 15= 4.41• Total of 5 circuits

Page 10: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Load Calcs

• What is the demand on the main service entrance of a multifamily dwelling for 15 electric clothes dryers that are rated at 4.4 kW at 240 volts?

Page 11: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• 32250 VA

• 5000 x 15= 75000• 75000 x .43= 32250 VA

Page 12: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Load Calcs

• What is the demand on the main service entrance of a multifamily dwelling for the lighting and receptacle loads for 20 apartments if each apartment is 1300 square feet?

Page 13: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• 55950 VA

• 3 x 1300 x 20= 78000• 4500 x 20= 90000• 78000 + 90000= 168000- 3000= 165000• 165000- 117000= 48000 117000 x .35= 40950• 48000 x .25= 12000• 12000 + 40950 + 3000= 55950 VA

Page 14: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Motor Calc

• What is the maximum sized instantaneous trip breaker that can be used to protect the following motor for short circuit protection:

• 50 HP, 208V, three phase, squirrel cage motor, 116.8 amperes FLC, marked service factor of 1.15?

Page 15: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• 1200 Amperes• Based on T430.52 and 240.6 for standard sized

fuses and circuit breakers.

Page 16: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• What is the calculated load on the branch circuit of a three phase, 480V, 50 HP squirrel cage motor that operates a ore rolling chute? The motor has a nameplate rating of 61.6 amperes. The motor is rated to operate on intermittent duty and is rated for 60 minute operation.

Page 17: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• 55.4 amperes

• 430.22(E)

Page 18: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• What is the minimum sized THHN conductor needed to feed a short time duty rated motor that is single phase, 208V, 5 HP, 26.9 amperes, and is rated to operate 5 minutes? The motor is rated at 75 degrees C.

Page 19: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• 10 AWG

• 29.59 amperes

Page 20: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Conductor Ampacity

• A 1/0 AWG THHN conductor installed in an ambient temperature of 103 degrees F. will have an ampacity of _________.

Copyright 2005 Ted "Smitty" Smith

Page 21: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Conductor Ampacity

• 154.70 Amperes

Page 22: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Conductor Ampacity

What is the ampacity of a 250 kCMIL aluminum THW conductor installed in an ambient temperature of 44 degrees Celsius?

Copyright 2005 Ted "Smitty" Smith

Page 23: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Conductor Amapacity

• 168.100 amperes

Page 24: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Box Fill

• What is the volume allowance required for the following junction box which has a total of nine 12 AWG THHN conductors entering the junction box, one of which is an equipment grounding conductor. The box will contain one duplex receptacle, has no internal clamps, and no luminairie studs or hickeys.

Page 25: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Box Fill

• 24.75

Page 26: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Conductor Ampacity

• A load of 23 amperes is being fed by a circuit consisting of 10 AWG THHN copper conductors. The conductors are installed in a conduit that is installed on a rooftop in the direct sunlight. The conduit is installed 12” above the roof from the bottom of the conduit. The average ambient temperature for the area in which the conduit is installed is 87 degrees F. The conduit contains a total of three current carrying conductors. Is this an acceptable installation?

Copyright 2005 Ted "Smitty" Smith

Page 27: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Conductor Ampacity• Yes, it is rated to carry 32.8 amperes.

Page 28: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Raceway Fill

• Three 10 AWG THHN, four 6 AWG THW and five 8 AWG TW conductors are installed in a one and one half inch electrical metallic tubing conduit that is 280 feet in length. Is this an acceptable installation?

Copyright 2005 Ted "Smitty" Smith

Page 29: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Raceway Fill

• Yes, the wires make up a volume of .5722 and at 40% fill an EMT 1 1/2” conduit is .814.

Copyright 2005 Ted "Smitty" Smith

Page 30: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Conductor Ampacity

• What is the ampacity of 2 AWG TW aluminum conductor installed in a conduit that is installed in a boiler room with an ambient temperature of 103 degrees F and the conductor is installed in a conduit with a total of 17 current carrying conductors?

Page 31: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Conductor Amapacity

• 30.75 Amperes

Page 32: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Box Fill

• A 4 x 1 ½ square metal box is installed with two duplex receptacles. The box has a total of three 12 AWG MC cables entering the box, each MC cable is a 12/2 with ground. The box contains no internal cable clamps, and no luminairie studs or hickeys. Is this an acceptable installation?

Page 33: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Box Fill

• No, the conductors and devices require a volume allowance of 24.75 and Table 314.16(A) lists a 4 x 1 ½” metal box as having a volume of 21.0

Page 34: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• What is the minimum sized service, minimum sized aluminum grounded conductor and minimum sized copper grounding electrode conductor required for a machine shop if the shop is equipped with the following:

• 100 feet of multioutlet assembly not expected to be used simultaneously• 75 duplex receptacles at 125V• The following motors

– Single phase, 208V, ½ hp, 1.9 A varying duty motor, 5 mins– Single phase, 208V, 5 hp, 28.7A intermittent duty motor, 30 mins– Single phase, 208V, 10 hp, 48.6 A 5 minute, short time duty motor, 15 mins– (6) single phase, 120V, 1 hp, 120V, 14.8 A, intermittent duty motors, 30 mins

• A 208V three phase, 58.7 A rated roof mounted HVAC system• The machine shop is 36000 square feet with 5000 square feet classified office and

29000 square feet classified warehouse.

• The service will be 208V, three phase. The service entrance conductors will be THHN aluminum. All circuits are specified to be rated at 75 degrees C.

Page 35: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• 300A ampere service, 500 kcmil AL SE conductors, 500 kcmil AL grounded conductor, 2 AWG copper grounding electrode conductor

• Lighting= 17500+7250= 24750 va• Recepts= 17100 VA- 10000= 7100*.5=3550• 10000+ 3550= 13550 va

– Motors = Single phase, 208V, ½ hp, 1.9 A varying duty motor, 5 mins 434.72 va

– Single phase, 208V, 5 hp, 28.7A intermittent duty motor, 30 mins 5074.16 va

– Single phase, 208V, 10 hp, 48.6 A 5 minute, short time duty motor, 15 mins 12130.56 va

– (6) single phase, 120V, 1 hp, 120V, 14.8 A, intermittent duty motors, 30 mins 16623.36 va

• Roof Mounted HVAC 58.7 x 1.732 x 208= 21147.03• Total = 93709.83 / 208 /1.732= 260.12 amperes= 300A service• 300A at 75C Aluminum = 500 kcmil Service Entrance Conductors• Neutral Loads Lighting= 24750 + Recep= 13550 + 120V motors= 16623.36• Total Neutral Load= 54923.36va /120V= 457.69 A. 220.24 Requires the neutral to be no larger than the ungrounded

conductors so this would require 500 KCMIL grounded conductor• T250.66 Requires a 2 AWG copper grounding electrode conductor if the service entrance conductors are 500 kcmil aluminum. •

Page 36: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Raceway Fill

• Is it allowable to add three 10 AWG THHN conductors to an existing conduit that is 150 feet in length and currently has eight 6 AWG THWN conductors and one 12 AWG THHN conductor installed? The conduit is a 1 ¼” inch electrical metallic tubing.

Page 37: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Raceway Fill

• No. The total area used by the conductors once the three 10 AWG conductors are added will be .4822 inches and a 1 ¼” EMT at 31% fill has an allowance of only .464 inches.

Page 38: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Conductor Ampacity

• A 39.6 ampere load is fed with a 6 AWG THW conductor that is installed in a conduit with a total of 7 current carrying conductors. The conduit is installed in a room that has an ambient temperature 38 degrees Celsius. Is this an acceptable installation?

Page 39: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Conductor Ampacity

• Yes it is acceptable. The conductor is rated at 40.04 amperes.

Page 40: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Stop This is the end of the

presentation.

You can now review the slides and answers without the timer.

Click the slide to advance to the next slide

Page 41: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• What is the minimum sized service required for a machine shop if the shop is equipped with the following:

• 50 feet of multioutlet assembly expected to be used simultaneously• 50 duplex receptacles at 125V• The following motors

– Single phase, 208V, ¼ hp, 2.9 A varying duty motor, 15 mins– Single phase, 208V, 1 ½ hp, 9.2 A intermittent duty motor, 5 mins– Three phase, 208V, 5 hp, 14.9 A 15 minute, short time duty motor, 15 mins– (3) single phase, 120V, ½ hp, 120V, 11.1 A, intermittent duty motors, 30 mins

• A 208V three phase, 41.6 A rated roof mounted HVAC system• The machine shop is 15000 square feet with 3000 square feet classified

office and 12,000 square feet classified warehouse.

• The service will be 208V, three phase.

Page 42: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• 175 ampere service

• Lighting= 10500 + 3000= 13500 va• Recepts= 9000+ 9000= 18000 -10000=8000 x.5 =4000 • 10000+ 4000= 14000 va• Motors = 6441.3 va• 723.84 va 1626.5 va 1198.8 va 1198.8 va 1198.8 vaRoof Mounted HVAC 41.6 x 1.732 x 208= 14986.6 vaTotal = 54874.64 / 208 /1.732= 152.32 amperes

Page 43: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Motor Calc

• What is the minimum sized THHN wire that can be used to feed the following motor:

• Three Phase, squirrel cage, 30 HP, 480 Volts, 33.6 amperes FLC, 1.15 marked service factor and Design K.

Page 44: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• 6 AWG THHN• Based on the 60 degree column of 310.16

based on 110.14(C)

Page 45: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Welding Calculation

• What is the minimum sized THHN copper conductor that can be used to feed six arc welders with the following ratings:

• 1. 50 A at 30 Duty Cycle• 2. 60 A at 40 duty cycle• 3. 100 at 10 duty cycle• 4. 100 A at 10 duty cycle• 5. 75 A at 50 duty cycle• 6. 44.6 A at 60 duty cycle

Page 46: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• 250 KCMIL• Determined by 6301.11 (A )and (B)• Table 310.16 Column 60 degrees C based on

110.14(C)

Page 47: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Load Calc

• How many 15 ampere lighting circuits will be required for a single family dwelling that is 2650 square feet to meet the minimum requirements of the National Electric Code?

Page 48: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• 5

• 2650 x 3= 7950/120=66.25 amperes/ 15= 4.41• Total of 5 circuits

Page 49: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Load Calcs

• What is the demand on the main service entrance of a multifamily dwelling for 15 electric clothes dryers that are rated at 4.4 kW at 240 volts?

Page 50: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• 32250 VA

• 5000 x 15= 75000• 75000 x .43= 32250 VA

Page 51: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Load Calcs

• What is the demand on the main service entrance of a multifamily dwelling for the lighting and receptacle loads for 20 apartments if each apartment is 1300 square feet?

Page 52: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• 55950 VA

• 3 x 1300 x 20= 78000• 4500 x 20= 90000• 78000 + 90000= 168000- 3000= 165000• 165000- 117000= 48000 117000 x .35= 40950• 48000 x .25= 12000• 12000 + 40950 + 3000= 55950 VA

Page 53: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Motor Calc

• What is the maximum sized instantaneous trip breaker that can be used to protect the following motor for short circuit protection:

• 50 HP, 208V, three phase, squirrel cage motor, 116.8 amperes FLC, marked service factor of 1.15?

Page 54: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• 1200 Amperes• Based on T430.52 and 240.6 for standard sized

fuses and circuit breakers.

Page 55: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• What is the calculated load on the branch circuit of a three phase, 480V, 50 HP squirrel cage motor that operates a ore rolling chute? The motor has a nameplate rating of 61.6 amperes. The motor is rated to operate on intermittent duty and is rated for 60 minute operation.

Page 56: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• 55.4 amperes

• 430.22(E)

Page 57: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• What is the minimum sized THHN conductor needed to feed a short time duty rated motor that is single phase, 208V, 5 HP, 26.9 amperes, and is rated to operate 5 minutes? The motor is rated at 75 degrees C.

Page 58: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• 10 AWG

• 29.59 amperes

Page 59: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Conductor Ampacity

• A 1/0 AWG THHN conductor installed in an ambient temperature of 103 degrees F. will have an ampacity of _________.

Copyright 2005 Ted "Smitty" Smith

Page 60: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Conductor Ampacity

• 154.70 Amperes

Page 61: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Conductor Ampacity

What is the ampacity of a 250 kCMIL aluminum THW conductor installed in an ambient temperature of 44 degrees Celsius?

Copyright 2005 Ted "Smitty" Smith

Page 62: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Conductor Amapacity

• 168.100 amperes

Page 63: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Box Fill

• What is the volume allowance required for the following junction box which has a total of nine 12 AWG THHN conductors entering the junction box, one of which is an equipment grounding conductor. The box will contain one duplex receptacle, has no internal clamps, and no luminairie studs or hickeys.

Page 64: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Box Fill

• 24.75

Page 65: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Conductor Ampacity

• A load of 23 amperes is being fed by a circuit consisting of 10 AWG THHN copper conductors. The conductors are installed in a conduit that is installed on a rooftop in the direct sunlight. The conduit is installed 12” above the roof from the bottom of the conduit. The average ambient temperature for the area in which the conduit is installed is 87 degrees F. The conduit contains a total of three current carrying conductors. Is this an acceptable installation?

Copyright 2005 Ted "Smitty" Smith

Page 66: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Conductor Ampacity• Yes, it is rated to carry 32.8 amperes.

Page 67: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Raceway Fill

• Three 10 AWG THHN, four 6 AWG THW and five 8 AWG TW conductors are installed in a one and one half inch electrical metallic tubing conduit that is 280 feet in length. Is this an acceptable installation?

Copyright 2005 Ted "Smitty" Smith

Page 68: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Raceway Fill

• Yes, the wires make up a volume of .5722 and at 40% fill an EMT 1 1/2” conduit is .814.

Copyright 2005 Ted "Smitty" Smith

Page 69: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Conductor Ampacity

• What is the ampacity of 2 AWG TW aluminum conductor installed in a conduit that is installed in a boiler room with an ambient temperature of 103 degrees F and the conductor is installed in a conduit with a total of 17 current carrying conductors?

Page 70: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Conductor Amapacity

• 30.75 Amperes

Page 71: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Box Fill

• A 4 x 1 ½ square metal box is installed with two duplex receptacles. The box has a total of three 12 AWG MC cables entering the box, each MC cable is a 12/2 with ground. The box contains no internal cable clamps, and no luminairie studs or hickeys. Is this an acceptable installation?

Page 72: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Box Fill

• No, the conductors and devices require a volume allowance of 24.75 and Table 314.16(A) lists a 4 x 1 ½” metal box as having a volume of 21.0

Page 73: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• What is the minimum sized service, minimum sized aluminum grounded conductor and minimum sized copper grounding electrode conductor required for a machine shop if the shop is equipped with the following:

• 100 feet of multioutlet assembly not expected to be used simultaneously• 75 duplex receptacles at 125V• The following motors

– Single phase, 208V, ½ hp, 1.9 A varying duty motor, 5 mins– Single phase, 208V, 5 hp, 28.7A intermittent duty motor, 30 mins– Single phase, 208V, 10 hp, 48.6 A 5 minute, short time duty motor, 15 mins– (6) single phase, 120V, 1 hp, 120V, 14.8 A, intermittent duty motors, 30 mins

• A 208V three phase, 58.7 A rated roof mounted HVAC system• The machine shop is 36000 square feet with 5000 square feet classified office and

29000 square feet classified warehouse.

• The service will be 208V, three phase. The service entrance conductors will be THHN aluminum. All circuits are specified to be rated at 75 degrees C.

Page 74: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

• 300A ampere service, 500 kcmil AL SE conductors, 500 kcmil AL grounded conductor, 2 AWG copper grounding electrode conductor

• Lighting= 17500+7250= 24750 va• Recepts= 17100 VA- 10000= 7100*.5=3550• 10000+ 3550= 13550 va

– Motors = Single phase, 208V, ½ hp, 1.9 A varying duty motor, 5 mins 434.72 va

– Single phase, 208V, 5 hp, 28.7A intermittent duty motor, 30 mins 5074.16 va

– Single phase, 208V, 10 hp, 48.6 A 5 minute, short time duty motor, 15 mins 12130.56 va

– (6) single phase, 120V, 1 hp, 120V, 14.8 A, intermittent duty motors, 30 mins 16623.36 va

• Roof Mounted HVAC 58.7 x 1.732 x 208= 21147.03• Total = 93709.83 / 208 /1.732= 260.12 amperes= 300A service• 300A at 75C Aluminum = 500 kcmil Service Entrance Conductors• Neutral Loads Lighting= 24750 + Recep= 13550 + 120V motors= 16623.36• Total Neutral Load= 54923.36va /120V= 457.69 A. 220.24 Requires the neutral to be no larger than the ungrounded

conductors so this would require 500 KCMIL grounded conductor• T250.66 Requires a 2 AWG copper grounding electrode conductor if the service entrance conductors are 500 kcmil aluminum. •

Page 75: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Raceway Fill

• Is it allowable to add three 10 AWG THHN conductors to an existing conduit that is 150 feet in length and currently has eight 6 AWG THWN conductors and one 12 AWG THHN conductor installed? The conduit is a 1 ¼” inch electrical metallic tubing.

Page 76: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Raceway Fill

• No. The total area used by the conductors once the three 10 AWG conductors are added will be .4822 inches and a 1 ¼” EMT at 31% fill has an allowance of only .464 inches.

Page 77: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Conductor Ampacity

• A 39.6 ampere load is fed with a 6 AWG THW conductor that is installed in a conduit with a total of 7 current carrying conductors. The conduit is installed in a room that has an ambient temperature 38 degrees Celsius. Is this an acceptable installation?

Page 78: Advanced Calculations Drill 1 for the 2011 NEC © Ted Smitty Smith 2012.

Conductor Ampacity

• Yes it is acceptable. The conductor is rated at 40.04 amperes.