ADT490 Panel Theory. 2 System Power Supply Grounding ‣ Circuit separates positive / negative from...
-
Upload
milton-oliver -
Category
Documents
-
view
214 -
download
0
Transcript of ADT490 Panel Theory. 2 System Power Supply Grounding ‣ Circuit separates positive / negative from...
ADT490Panel Theory
2
System Power Supply Grounding
‣Circuit separates positive / negative from Ground
‣Ground fault - resistance to ground ≤ 10 kΩ‣System power supply
‣Line - black‣Neutral - white (return)‣Ground - green
‣Exterior components bonded to Ground
3
Power Supply
‣ Output 27 to 30 Vdc
3
4
Power Supply Fault Analysis
‣ Power on - how do we know?‣ Disconnect or breaker station - looking for?
4
5
Power Supply Checklist
5
6
Power Supply Checklist 2
6
7
Battery Charger Concepts
‣ 2 x 12 V or 4 x 6 V batteries‣ To charge requires 27.4 to 28 V‣ must be recharged to 70% within 12 hours (ULC)‣ 5 to 35 mA - float Charge‣ Fast Charge - larger‣ Battery Condition Monitor‣ Ammeter in Series to check the Charge rate (A)‣ Can check power supply with DC & AC Voltage
Measurements
7
8
Battery Charger Concepts
8
9
Electrical Supervision
‣ small current though an EOL Resistor‣ no current though an EOL Capacitor‣ Power resistors
‣ approximately 200 Ω‣ 1 volt each‣ about 2 W
9
10
Electrical Supervision
10
11
Detection - Open Circuit
11
12
EOL Resistor Function
‣ Limits current through wiring‣ Regulates the voltage in the circuit
12
13
EOL Capacitor Function
‣ Siemens System 3 or MXL‣ EOL Capacitor‣ Blocks DC‣ Smooths ripple voltage
13
14
Detection Circuit with EOL Capacitor
14
15
EOL Capacitor Waveform
15
16
EOL Capacitor Waveform
16
17
Locating Faults
‣ Voltage on open EOL Capacitor circuit is 20.5V (System 3) & 21.5V (MXL)
‣ Voltage before the break‣ 0 V after the break
17
18
EOL Relays
‣ Mostly used on security systems or‣ 4 wire devices
18
19
EOL Relays
19
20
Wiring Architectures
‣ Class B‣ Class A‣ Split Class B‣ Tee-Tapped
20
21
Class B Wiring - Placement or Location Supervised (87%)
21
22
Class A Wiring - Placement or Location Supervised (8%)
22
23
Class A Wiring - Greater Reliability
23
24
Class B Wiring with Tee-Taps
‣ Tap is unsupervised‣ Reason each device is checked for open - S537‣ Some vendor use twice EOL size for main run and
single tap
24
25
Class B Wiring with Tee-Taps
25
26
Addressable Loop - no EOL
‣ A fault cannot disable more than 1 Zone
26
27
Signal Circuit Supervision
‣ Terminal may indicate polarity in alarm - not always‣ 24 VDC can be as low as a few volts‣ Shorts causes a circuit Trouble
27
28
Signal Circuit Alarm Operation
‣ Device could be reverses - rings supervision not alarm‣ Don’t exceed 85% of Current - Why?
28
29
Class A Signal Circuits
‣ Class A good for opens‣ Not good for shorts - Why?
29
30
Speaker Circuits - Supervision
30
31
Speaker Circuits - Alarm
31
32
Speaker Circuits - Alarm
‣ 25 Vrms 20 and 40 mA for speaker + 5 mA for EOL‣ 70.7 Vrms 7.1 and 14.1 mA for speaker + 7.1 mA for
EOL (equivalent to 1/2 W Speaker)
32
33
Split Speaker Circuits
33
34
Split Speaker Circuits
34
35
Telephone Circuits
35
36
Improperly Connected Signals
36
37
endofPresentation