100A-5000AExample One-line DiagramsAdditional applications available. Contact 507-333-3990
507.333.3990 TRYSTAR.COM2917 Industrial Drive, Faribault, MN 55021
Docking Stations
SBDS-6 SBDS-7
GDS-7
To Load
PermanentGenerator 1
TemporaryGenerator
Generator Docking Station DualPurpose Pass Through with Hardwire
and Double Kirk Key Acces
Load BankConnection
K
K
Access to Male Cam Locksand Hardwire Lugs Prevented
Until Permanent GeneratorCircuit Breakers are Opened
and Kirk Key is Removed
PermanentGenerator 2
K
K
Male Cam Lock
Female Cam Lock
Hardwire Lug
Load Center
Circuit Breaker
K Kirk Key Interlock SystemTerminal Block
Auto Start Terminals
Phase Rotation Monitor
Class CC Fuse Holder
Manual Transfer Switch
Connection Point
Single Breaker Docking Station, DualPurpose Pass Through with Hardwire
and Kirk Key Interlock AlternateBreaker Location
2/17/2016
Male Cam Lock
Female Cam Lock
Hardwire Lug
Load Center
Circuit Breaker
K Kirk Key Interlock SystemTerminal Block
Auto Start Terminals
Phase Rotation Monitor
Class CC Fuse Holder
Manual Transfer Switch
Connection Point
To LoadPermanentGenerator
TemporaryGenerator
Load BankConnection
Access to Cam LockPanelmounts Prevented UntilCircuit Breaker is Opened and
Kirk Key is Removed
K
K
Compression Lugs forPermanent Bus Connection
Compression Lugs forPermanent Bus Connection
Male Cam Lok PanelmountsColor Coded to System Voltage
Female Cam Lok PanelmountsColor Coded to System Voltage
Kirk Key InterlockedCircuit Breaker
To Load/ATS
PermanentGenerator
GeneratorSource
Single Breaker Docking StationDual Purpose Pass Through with
Kirk Keyed Breaker
4/30/2014
Load BankConnection
K
K
Male Cam Lock
Female Cam Lock
Hardwire Lug
Load Center
Circuit Breaker
K Kirk Key Interlock SystemTerminal Block
Auto Start Terminals
Phase Rotation Monitor
Class CC Fuse Holder
Manual Transfer Switch
Connection Point
To Load/ATS
PermanentGenerator
TemporaryGenerator
Dual Purpose Docking Station PassThrough with Kirk Key Access
Load BankConnection
K
Access to Cam LockPanelmounts Prevented UntilPermanent Generator CircuitBreaker is Opened and Kirk
Key is Removed
K
Male Cam Lock
Female Cam Lock
Hardwire Lug
Load Center
Circuit Breaker
K Kirk Key Interlock SystemTerminal Block
Auto Start Terminals
Phase Rotation Monitor
Class CC Fuse Holder
Manual Transfer Switch
Connection Point
DUAL PURPOSE DOCKING STATION
GDS-6
Example One-line DiagramsAdditional applications available. Contact 507-333-3990
100A-5000A
507.333.3990 TRYSTAR.COM2917 Industrial Drive, Faribault, MN 55021
Docking Stations
DBDS-6
PermanentGenerator
TemporaryGenerator
Dual Breaker Docking Station DualPurpose Pass Through with Hardwire
and Kirk Keyed Breaker
5/20/2014
Load BankConnection
K
KTo Load/
ATS
Male Cam Lock
Female Cam Lock
Hardwire Lug
Load Center
Circuit Breaker
K Kirk Key Interlock SystemTerminal Block
Auto Start Terminals
Phase Rotation Monitor
Class CC Fuse Holder
Manual Transfer Switch
Connection Point
Shunt Trip available onthis breaker to trip whenemergency side of ATS
calls for power.
PermanentGenerator
TemporaryGenerator
Dual Breaker Docking Station DualPurpose Pass Through with
Hardwire and Kirk Key Interlock
Load BankConnection
K
To Load/ATS
K
Male Cam Lock
Female Cam Lock
Hardwire Lug
Load Center
Circuit Breaker
K Kirk Key Interlock SystemTerminal Block
Auto Start Terminals
Phase Rotation Monitor
Class CC Fuse Holder
Manual Transfer Switch
Connection Point
Shunt Trip Available onLoad Bank Circuit Breaker,
so Breaker Trips whenATS Demands Power from
Permanent Generator
PermanentGenerator
TemporaryGenerator
Dual Breaker Docking Station DualPurpose Pass Through with Hardwire
and Kirk Key Interlocked Breakers
5/15/2014
Load BankConnection
K
KTo Load/
ATS
Male Cam Lock
Female Cam Lock
Hardwire Lug
Load Center
Circuit Breaker
K Kirk Key Interlock SystemTerminal Block
Auto Start Terminals
Phase Rotation Monitor
Class CC Fuse Holder
Manual Transfer Switch
Connection Point
DBDS-5
DUAL PURPOSE DOCKING STATION
DBDS-4
TMTS-5 up to 1200A
Permanent Generator
Temporary Generator
Trystar Manual Transfer Switch Dual Purpose Pass Through
Load BankConnection
Male Cam Lock
Female Cam Lock
Hardwire Lug
Load Center
Circuit Breaker
Kirk Key Interlock System Terminal Block
Auto Start Terminals
Phase Rotation Monitor
Class CC Fuse Holder
Manual Transfer Switch
Connection Point
K
Silver Plated Busbar Strip Heater
To Load/ ATS
TMTS-6 up to 1200A
Permanent Generator
Temporary Generator
Load BankConnection
Mal e Cam Lock
Fem ale Cam Lock
Hardwi re Lug
Load Center
Circui t Breaker
K irk Key Interlock System Termi nal B lock
Auto S tart Termi nals
Phase Rotati on Moni tor
Class CC Fuse Holder
Manual Transfer Swi tch
Connect ion Point
K
Silver Pl ated Busbar S trip Heater
To Load/ ATS
Trystar Manual Transfer SwitchDual Purpose Pass Through with Main Breaker