Addendum #1 – USU CCA Academic Advising Center Renovation Project SPARANO + MOONEY ARCHITECTURE ADDENDUM #1 PROJECT: USU CCA Academic Advising Center Renovation Project Project #: CP001046 ARCHITECT: Sparano + Mooney Architecture DATE: April 6, 2020 PAGES: (5) Total Pages Notice to all Plan Holders: The following modifications, additions, deletions, clarifications and/or information are hereby made part of the Contract Documents and shall be fully binding. Addendum must be acknowledged as part of the Bid Form. Item #1: Electrical Questions and Light Fixture Substitution Request See attached electrical narrative regarding electrical questions and lighting substitution requests, including (2) drawing sheets: ED101 and EP101. Item #2: Mechanical Substitution Request See attached mechanical narrative regarding a mechanical duct silencer substitution request.

Transcript of ADDENDUM # 1 1 CCA Academic...2007/04/20  · D7 REMOVE EXISTING 6" CANS AND REPLACE WITH A NEW...

Page 1: ADDENDUM # 1 1 CCA Academic...2007/04/20  · D7 REMOVE EXISTING 6" CANS AND REPLACE WITH A NEW RETROFIT LED LIGHT FIXTURE. UTILIZE EXISTING CIRCUIT FOR NEW LIGHT FIXTURE. D8 AT THE

Addendum #1 – USU CCA Academic Advising Center Renovation Project

SPARANO + MOONEY ARCHITECTURE

ADDENDUM #1

PROJECT: USU CCA Academic Advising Center Renovation Project

Project #: CP001046

ARCHITECT: Sparano + Mooney Architecture DATE: April 6, 2020

PAGES: (5) Total Pages

Notice to all Plan Holders: The following modifications, additions, deletions, clarifications and/or information are hereby made part of the Contract Documents and shall be fully binding. Addendum must be acknowledged as part of the Bid Form. Item #1: Electrical Questions and Light Fixture Substitution Request See attached electrical narrative regarding electrical questions and lighting substitution requests, including (2) drawing sheets: ED101 and EP101. Item #2: Mechanical Substitution Request See attached mechanical narrative regarding a mechanical duct silencer substitution request.

Page 2: ADDENDUM # 1 1 CCA Academic...2007/04/20  · D7 REMOVE EXISTING 6" CANS AND REPLACE WITH A NEW RETROFIT LED LIGHT FIXTURE. UTILIZE EXISTING CIRCUIT FOR NEW LIGHT FIXTURE. D8 AT THE

USU CCA ACADEMIC ADVISING CENTER

ELECTRICAL ADDENDUM NO. 1

Sheet #: ED101

1. REFERENCE NOTE D4, SMALL GUTTER OR J-BOX CAN BE INSTALLED TO SPLICE EXISTING BRANCH CIRCUITS AND EXTEND THEM TO NEW PANEL.

Sheet #: EP101

1. KEY PLAN ADDED. ROOM 135 FIELD VERIFY.

APPROVED MANUFACTURERS

The following additional manufacturers are approved to bid. Approval of the

equipment from catalog information indicates that the brand name and general

characteristics are acceptable to the Engineer. Any conflict arising from use

of the substituted equipment shall be the responsibility of the Supplier who

shall bear all costs required to make the equipment comply with the intent of

plans and specifications.

LIGHT FIXTURES Type MFG

T-1 BIRCHWOOD LIGHTING

ALW

AXIS

NULITE

T-2 LITHINIA

HALO

EX-1 LITHONIA

EVENLITE

Page 3: ADDENDUM # 1 1 CCA Academic...2007/04/20  · D7 REMOVE EXISTING 6" CANS AND REPLACE WITH A NEW RETROFIT LED LIGHT FIXTURE. UTILIZE EXISTING CIRCUIT FOR NEW LIGHT FIXTURE. D8 AT THE

F

S

S

S

SPECIAL NOTE:

CONTRACTOR MUST VISIT THE SITE PRIOR TO BID AND INCLUDE ALL THE COST ASSOCIATED WITH EXISTING CONDITIONS IN BID. ANY CLARIFICATION NEEDED MUST BE BROUGHT UP PRIOR TO BID.

+42"

B

B-3

B-1

4444

+42" +42"+42"+42"+42"+42"+42"+6"+42"+42"+42"

11 13 1312,14

7 7 9 9 15,17

30A.

3

5

5

5

+60"

6

D2

D2

D2

D2

D2 D2 D2

D2

D2

D2

D2

D2

D2D2D2D2

D2

WIFI

WIFI

D6

D2

PANEL "A" PANEL "B"

D4

D4

D8

D2

D8

D2D9

D2

D3D10

D9

D1

D2

D1D1D1D1 D1

D1D1D1D1

D1D1D1D1

D7

D7

D7

D1

D2

D2

939 S. West Temple SLC, UT 84101Phone : 801.521.8007Email : [email protected] Project # 5574

ELECTRICAL CONSULTING ENGINEERS

SEFORP

DE

SN

EC

IL R

EE

NI

GN

E

LANOIS

O FU T

A

H

ETA

T

S

AKBAR

MATINKHAH

#172577

SHEET NO.

SP

AR

AN

O +

MO

ON

EY

(S

MA

) R

ES

ER

VE

S IT

S C

OM

MO

N L

AW

CO

PY

RIG

HT

AN

D O

TH

ER

PR

OP

ER

TY

RIG

HT

S IN

TH

ES

E D

OC

UM

EN

TS

. T

HE

SE

DO

CU

ME

NT

S A

RE

NO

T T

O B

E R

EP

RO

DU

CE

D,

CH

AN

GE

D O

R C

OP

IED

IN

AN

Y F

OR

M O

R M

AN

NE

R W

HA

TS

OE

VE

R W

ITH

OU

T F

IRS

T O

BT

AIN

ING

TH

E E

XP

RE

SS

WR

ITT

EN

PE

RM

ISS

ION

OF

SM

A;

NO

R A

RE

TH

ES

E D

OC

UM

EN

TS

TO

BE

AS

SIG

NE

D T

O A

NY

TH

IRD

PA

RT

Y W

ITH

OU

T O

BT

AIN

ING

SA

ID W

RIT

TE

N P

ER

MIS

SIO

N &

CO

NS

EN

T.

SCALE

JOB NO.

DATE

KEY PLAN

IF THIS SHEET IS LESS THAN24"X36" IT IS A REDUCED PRINT,SCALE REDUCED ACCORDINGLY

SEAL SEAL

CONSULTANT

ISSUE

As indicated

DEMOLITION FLOOR PLAN

AND CEILING PLAN

ED101

CCA ACADEMIC ADVISING

CENTER RENOVATION

PROJECT

19-14

16 MAR 2020

4030 OLD MAIN HILL

LOGAN, UT 84322

BID SET

REFERENCE NOTES:

D1 REMOVE ALL EXISTING LIGHT FIXTURES, IN REMODEL AREA, ASSOCIATEDCONDUIT, CONDUCTORS, J-BOXES, ETC. ALL THE WAY BACK TO PANELBOARD.

D2 REMOVE EXISTING DEVICES, WIREMOLD, LIGHT SWITCHES, ASSOCIATEDCONDUIT, CONDUCTORS, BOXES, ETC. ALL THE WAY BACK TO PANELBOARD.

D3 EXISTING FIRE ALARM DEVICES ARE TO REMAIN. PROTECT DURINGCONSTRUCTION.

D4 REMOVE EXISTING PANELBOARD ASSOCIATED CONDUIT, CONDUCTORS,J-BOXES, ETC. EXTEND EXISTING BRANCH CIRCUITS TO NEW PANEL INWEEKENDS OR EVENINGS AS DIRECTED BY USU ELECTRICAL SHOP.TEMPORARY PROVIDE POWER TO PANEL "A" FROM PANEL "B" TO ALLOWFEEDER FOR PANEL "A" BE EXTENDED TO NEW PANEL. SMALL GUTTER ORJ-BOX CAN BE INSTALLED TO SPLICE EXISTING BRANCH CIRCUITS ANDEXTEND THEM TO NEW PANEL.

D6 RELOCATE EXISTING WIFI ANTENNA TO NEW LOCATION SHOWN. EXTENDEXISTING CONDUIT AND CONDUCTORS TO NEW LOCATION FOR A COMPLETEINSTALLATION. COORDINATE WITH USU IT GROUP FOR EXACT LOCATION.

D7 REMOVE EXISTING 6" CANS AND REPLACE WITH A NEW RETROFIT LED LIGHTFIXTURE. UTILIZE EXISTING CIRCUIT FOR NEW LIGHT FIXTURE.

D8 AT THE END OF PROJECT REMOVE PANEL "A" & "B". REMOVE FEEDERCONDUIT AND CONDUCTORS FOR PANEL "B" ALL THE WAY BACK TODISTRIBUTION PANEL "PDA" IN ROOM 135A. EXTEND EXISTING FEEDERCONDUIT AND CONDUCTORS TO NEW PANELBOARD "A". UPDATE PANELIDENTIFICATION CARD FOR PANEL "PDA" TO SHOW THE CHARGERS.

D9 RELOCATE EXISTING HORN/STROBE TO NEW LOCATION SHOWN ON POWERSHEET. EXTEND CONDUIT AND CONDUCTORS TO NEW LOCATION SHOWN. DONOT SPLICE CABLES BETWEEN DEVICES. MAINTAIN CIRCUIT INTEGRITY TODEVICES WHICH ARE TO REMAIN.

D10 REMOVE EXISTING FIRE ALARM PULL STATION AND REMOVE ASSOCIATEDCONDUIT AND CONDUCTORS. MAINTAIN CLASS "A" LOOP TO EXISTINGDEVICES.

1/4" = 1'-0"1

DEMOLITON FLOOR PLAN-ELECTRICAL1/4" = 1'-0"

2DEMOLITION CEILING PLAN-LIGHTING

REVISION SCHEDULE

NO DATE DESCRIPTION

1 4.6.2020 ADD#1

N N

1

Page 4: ADDENDUM # 1 1 CCA Academic...2007/04/20  · D7 REMOVE EXISTING 6" CANS AND REPLACE WITH A NEW RETROFIT LED LIGHT FIXTURE. UTILIZE EXISTING CIRCUIT FOR NEW LIGHT FIXTURE. D8 AT THE

J

UP

E D

4

E

3

4

P3

P3

P2

P3

+42"

+42"

22

2

2

2

2

OFFICE

102

OFFICE

103

OFFICE

104

MECH.

106

BREAK RM

109

PROD. SERV.

OFFICE

107

DIRECTORS

OFFICE

105STUDENT

WAITING AREA

101B

RECEPTION

101A

CORRIDOR

100K

NEW PANEL "A"

WIFI

+42"

A- 8

A- 6

A- 5

A- 10

A- 3

A- 7 A- 2

P4

P5

P5 P5 P5P5

P5

P5

P5P5

P5

P52

A- 4

P5

A- 9

+42"

P7

P8

P1

P6

1/2" C.

P7

SPECIAL NOTE:

1. SECURITY WORK TO INSTALL ALL DEVICES (CARD READER, DOOR STRIKE, MOTION SENSOR, DOOR CONTACT, ETC.) IS TO BE DONE BY STONE SECURITY (CONTACT CRAIG EPPERSON 877-888-0129). GC IS TO INCLUDE IN HIS BID THE COST FOR STONE SECURITY WORK (MATERIAL AND INSTALLATION).

OUR AREA ROOM 135 FILED VERIFY

939 S. West Temple SLC, UT 84101Phone : 801.521.8007Email : [email protected] Project # 5574

ELECTRICAL CONSULTING ENGINEERS

SEFORP

DE

SN

EC

IL R

EE

NI

GN

E

LANOIS

O FU T

A

H

ETA

T

S

AKBAR

MATINKHAH

#172577

SHEET NO.

SP

AR

AN

O +

MO

ON

EY

(S

MA

) R

ES

ER

VE

S IT

S C

OM

MO

N L

AW

CO

PY

RIG

HT

AN

D O

TH

ER

PR

OP

ER

TY

RIG

HT

S IN

TH

ES

E D

OC

UM

EN

TS

. T

HE

SE

DO

CU

ME

NT

S A

RE

NO

T T

O B

E R

EP

RO

DU

CE

D,

CH

AN

GE

D O

R C

OP

IED

IN

AN

Y F

OR

M O

R M

AN

NE

R W

HA

TS

OE

VE

R W

ITH

OU

T F

IRS

T O

BT

AIN

ING

TH

E E

XP

RE

SS

WR

ITT

EN

PE

RM

ISS

ION

OF

SM

A;

NO

R A

RE

TH

ES

E D

OC

UM

EN

TS

TO

BE

AS

SIG

NE

D T

O A

NY

TH

IRD

PA

RT

Y W

ITH

OU

T O

BT

AIN

ING

SA

ID W

RIT

TE

N P

ER

MIS

SIO

N &

CO

NS

EN

T.

SCALE

JOB NO.

DATE

KEY PLAN

IF THIS SHEET IS LESS THAN24"X36" IT IS A REDUCED PRINT,SCALE REDUCED ACCORDINGLY

SEAL SEAL

CONSULTANT

ISSUE

As indicated

FLOOR PLAN - ELECTRICAL

EP101

CCA ACADEMIC ADVISING

CENTER RENOVATION

PROJECT

19-14

16 MAR 2020

4030 OLD MAIN HILL

LOGAN, UT 84322

BID SET

1/4" = 1'-0"1

FLOOR PLAN - ELECTRICAL

REFERENCE NOTES:

P1 EXISTING FIRE ALARM DEVICE IS TO REMAIN. MAINTAIN CLASS "A"LOOP.

P2 INSTALL EXISTING HORN/STROBE IN NEW LOCATION SHOWN.EXTEND EXISTING CLASS "A" LOOP TO NEW LOCATION. DO NOTSPLICE CABLES BETWEEN DEVICES.

P3 FURNISH AND INSTALL NEW FIRE ALARM DEVICE IN THE NEWLOCATION SHOWN. EXTEND EXISTING CLASS "A" FIRE ALARM LOOPTO THESE DEVICES. IN AND OUT CABLES MUST RUN IN ASEPARATE CONDUIT. UPDATE BUILDING FIRE ALARM DRAWINGS TOSHOW NEW CHANGES. NEW DEVICES TO BE THE SAME BRAND ANDTYPE AS EXISTING.

P4 INSTALL EXISTING CEILING MOUNT WIFI PORTS IN NEW LOCATIONSHOWN. EXTEND EXISTING CONDUIT AND CABLES TO NEWLOCATION. COORDINATE WITH USU IT GROUP FOR EXACTLOCATION.

P5 FURNISH AND INSTALL A 4"X4"X2 1/8" J-BOX WITH SINGLE GANGMUD RING IN THE APPROXIMATE LOCATION SHOWN. RUN A 1"CONDUIT FROM EACH J-BOX TO THE CABLE TRAY IN CORRIDORCEILING SPACE NORTH OF DIRECTOR'S OFFICE 105. PROVIDEPLASTIC BUSHING AT THE END OF CONDUIT. PROVIDE PULLSTRING AND TAG TO SHOW ROOM NUMBER. VOICE/ DATA CABLESWILL BE INSTALLED BY USU.

P6 FURNISH AND INSTALL A 4"x4"x2-1/8" BOX WITH SINGLE GANG MUDRING IN APPROXIMATE LOCATION SHOWN FOR NEW CARDREADER. RUN A 1/2" CONDUIT FROM THIS BOX TO A J-BOXABOVETHE DOOR.

P7 FURNISH AND INSTALL A J-BOX ABOVE THE DOOR. RUN 1/2"CONDUIT TO DOOR STRIKE AND 3/4" CONDUIT TO EXISTINGCABLETRAY IN CORRIDOR NORTH OF STUDENT WAITING AREA101B. COORDINATE THIS WITH USU.

P8 TIE THE NEW MAGNETIC DOOR HOLDER TO EXISTING FIRE ALARMCONTROL PANEL FOR AUTOMATIC DOOR RELEASE. PROVIDEPOWER, RELAY, ETC. FOR A COMPLETE INSTALLATION.

REVISION SCHEDULE

NO DATE DESCRIPTION

1 4.6.2020 ADD#1

N

3/32" = 1'-0"2

key plan

1

Page 5: ADDENDUM # 1 1 CCA Academic...2007/04/20  · D7 REMOVE EXISTING 6" CANS AND REPLACE WITH A NEW RETROFIT LED LIGHT FIXTURE. UTILIZE EXISTING CIRCUIT FOR NEW LIGHT FIXTURE. D8 AT THE

ADDENDUM 1

DATE: April 6, 2020

PROJECT NO: 19519

PROJECT: USU FAC Academic Advising Center

The following revision, additions, deletions, and/or items of clarification shall hereby be included as an integral part of the Contract Documents for the above-listed project and shall be fully binding. All other requirements of the original plans and specification shall remain in effect in their respective order.

DIVISION – 23

PRIOR APPROVALS

The following manufacturers, trade names and products are allowed to bid on a name brand only basis with the provision that they completely satisfy all and every requirement of the drawings, specifications and all addenda shall conform to the design, quality and standards specified, established and required for the complete and satisfactory installation and performance of the building and all its respective parts.

Item Manufacturer Comments

Duct Silencer Nailor APPROVED