Adaptive Wide-Area Damping Controller Using Transfer Function Model Derived from Measurements: Case Studies on Realistic Power Grid Models Presented by Lin Zhu NASPI WG Meeting San Diego, CA April 15-17, 2019 Team: Yilu Liu 1,2 , Lin Zhu 1 , Yi(Joy) Zhao 1 , Huangqing(Hans) Xiao 1 , Ibrahim Altarjami 1 , Evangelos Farantatos 3 , Mahendra Patel 3 , Atena Darvishi 4 , George Stefopoulos 4 , Giorgio Giannuzzi 5 , Roberto Zaottini 5 , Ahmed Al-Mubarak 6 , Muhammad Ali 6 1. The University of Tennessee, Knoxville; 2. Oak Ridge National Laboratory; 3. Electric Power Research Institute; 4. New York Power Authority; 5. Terna, Italy; 6. Saudi Electricity Company.

Transcript of Adaptive Wide-Area Damping Controller Using Transfer Function … · Adaptive Wide-Area Damping...

Page 1: Adaptive Wide-Area Damping Controller Using Transfer Function … · Adaptive Wide-Area Damping Controller Using Transfer Function Model Derived from Measurements: Case Studies on

Adaptive Wide-Area Damping Controller Using Transfer Function Model Derived from Measurements: Case Studies

on Realistic Power Grid ModelsPresented by Lin Zhu

NASPI WG MeetingSan Diego, CA

April 15-17, 2019

Team: Yilu Liu1,2, Lin Zhu1, Yi(Joy) Zhao1, Huangqing(Hans) Xiao1, Ibrahim Altarjami1, Evangelos Farantatos3, Mahendra Patel3, Atena Darvishi4, George Stefopoulos4, Giorgio Giannuzzi5, Roberto Zaottini5, Ahmed Al-Mubarak6, Muhammad Ali6

1. The University of Tennessee, Knoxville; 2. Oak Ridge National Laboratory; 3. Electric Power Research Institute; 4. New York Power Authority; 5. Terna, Italy; 6. Saudi Electricity Company.

Page 2: Adaptive Wide-Area Damping Controller Using Transfer Function … · Adaptive Wide-Area Damping Controller Using Transfer Function Model Derived from Measurements: Case Studies on

2

Outline

• Motivation• WADC Design Using Measurement-Driven Approach• Case Studies on Realistic Grid Models

• New York State Grid Model• Terna (TSO in Italy) Grid Model• SEC (Saudi) Grid Model

• Summary

Page 3: Adaptive Wide-Area Damping Controller Using Transfer Function … · Adaptive Wide-Area Damping Controller Using Transfer Function Model Derived from Measurements: Case Studies on

3

Motivation

• Decreasing and inadequate damping during cascading events.• Adaptive wide-area damping control is desirable.

Table and Figure Source: 1. J. F. Hauer and J. W. Burns, “Roadmap to monitor data collected

during the WSCC breakup of August 10, 1996,” in PNNL-19459, Pacific Northwest National Laboratory, Richland, WA, USA.

Time/Event Frequency Damping10:52:19 (brake insertion) 0.285Hz 8.4%14:52:37 (John Day-Marion) 0.264Hz 3.7% 15:42:03 (Keeler-Allston) 0.264Hz 3.5%15:47:40 (oscillation startup) 0.238 Hz -3.1% 15:48:50 (oscillation finish) 0.216 Hz -6.3%

North-South Mode on August 10, 1996

Page 4: Adaptive Wide-Area Damping Controller Using Transfer Function … · Adaptive Wide-Area Damping Controller Using Transfer Function Model Derived from Measurements: Case Studies on

4

Planning Model Based v.s. Meas.-Driven Approach

• Measurement-driven approach Build a simple, low order transfer function model to depict

system oscillatory behavior for damping controller designSystem Planning Model Measurement-driven Model

Model size Large (~70,000 bus for EI)High order

Simple Low order

Model accuracy Low (if not well validated) High (for damping controller design)

Model update rate Every year (typically) Every 5 minutesTrack operating condition variation Not easy Easy

Adaptive damping control Not easy Easy

Page 5: Adaptive Wide-Area Damping Controller Using Transfer Function … · Adaptive Wide-Area Damping Controller Using Transfer Function Model Derived from Measurements: Case Studies on

5

Adaptive Wide-Area Damping Controller Design

• Build measurement-driven model to capture current operating condition

• Adaptively adjust WADC parameters for the current operating condition

5

Gen.

Vref

Pref

……

Vref

FACTS PMU_1

Measurement-driven Model

WADC

PMU_i

PMU_n

Power System

HVDC

Bus_1

Bus_2

Bus_n

Bus_FACTS

Bus_Gen

VWADC

Adaptive Wide-area Damping Controller

Page 6: Adaptive Wide-Area Damping Controller Using Transfer Function … · Adaptive Wide-Area Damping Controller Using Transfer Function Model Derived from Measurements: Case Studies on

6

2 4 6 8 10 12 14-5

-4

-3

-2

-1

0

1

2

3

4

y1

10 -5

data_mean1 (y1)

model_oe: 84.98%

Simulated Response Comparison

Time (seconds)

Am

plitu

de

Measurement-driven Model Identification and Validation

• Model Identification: Using ring-down or probing measurements.• Model validation: Check fitness index; Compare damping ratios,

oscillation frequencies, residue magnitude, and residue angle.

Order Fitness Index(%)

Oscillation frequency(Hz)

Damping ratio(%)

Residue Mag.

Residue angle (deg.)

4 77.33 0.2652 16.09 0.0009 117.87

5 84.98 0.2781 19.62 0.0013 139.15

6 76.25 0.2566 23.70 0.0014 101.95

7 85.36 0.2765 17.52 0.0011 136.63

8 75.76 0.2956 8.88 0.0007 159.70

9 85.31 0.2801 18.84 0.0013 142.52

Model Identification Results

Fitness = 84.98%

Page 7: Adaptive Wide-Area Damping Controller Using Transfer Function … · Adaptive Wide-Area Damping Controller Using Transfer Function Model Derived from Measurements: Case Studies on

7

NYPA Case Study (1/3)

• 2019 NYISO planning models (Spring, Summer and Winter)

• Modal analysis: Identified coherent groups and dominant modes

• Feedback signal/Actuator: Bus frequency/STATCOM in Area E.

• Demonstrating adaptive performance of WADC Cascading events Seasonal operating condition

variations Area map of New York State grid (Source: NYISO)

Mode #1

Mode #2

WADCBus frequency in Area E

STATCOM

Page 8: Adaptive Wide-Area Damping Controller Using Transfer Function … · Adaptive Wide-Area Damping Controller Using Transfer Function Model Derived from Measurements: Case Studies on

8

NYPA Case Study (2/3)

• Cascading events Create operating conditions via multi-line trip disturbances. Using ring-down data to build the model

Control effect: Adaptive v.s. Non-adaptive

No WADCNon-Adaptive WADCAdaptive WADC

Page 9: Adaptive Wide-Area Damping Controller Using Transfer Function … · Adaptive Wide-Area Damping Controller Using Transfer Function Model Derived from Measurements: Case Studies on

9

NYPA Case Study (3/3)

• Seasonal operating condition variations• Adaptive WADC: WADC tuned based on each case separately• Non-adaptive WADC: WADC tuned based on winter case

Case WADC Damping Ratio Improvement of Mode #1

Damping Ratio Improvement of Mode #2

WinterNon-Adaptive +7.85% +4.47%

Adaptive +7.85% +4.47%

SummerNon-adaptive +5.38% +6.82%Adaptive +7.00% +7.23%

SpringNon-adaptive +5.65 % +1.63%Adaptive +7.33% +6.25%

Page 10: Adaptive Wide-Area Damping Controller Using Transfer Function … · Adaptive Wide-Area Damping Controller Using Transfer Function Model Derived from Measurements: Case Studies on

10

Terna Case Study (1/3)

• Model provided by Terna• Modal analysis: Italy-France

mode in Terna model• Observation signal selection:

PMU1 South Italy PMU2 North Italy (France

area is optimal)• Actuators: Two synchronous

condensers in South Italy Mode #1 7.03%@0.281Hz

Z8

Z7

Z1

Z4

Mode #211.11%@0.318Hz

Mode #311.75%@0.417HzZ13

Page 11: Adaptive Wide-Area Damping Controller Using Transfer Function … · Adaptive Wide-Area Damping Controller Using Transfer Function Model Derived from Measurements: Case Studies on

11

Terna Case Study (2/3)

• Realistic oscillation event in Dec. 2017 PMU measurements provided by Terna Two consecutive generator trip events Growing oscillation: ~0.292Hz

Gen. #1 trip

Gen. #2 trip

PMU:Frequency: 0.293HzDamping ratio: -1.062%

PSS/E:Frequency: 0.293HzDamping ratio: -0.410%

Page 12: Adaptive Wide-Area Damping Controller Using Transfer Function … · Adaptive Wide-Area Damping Controller Using Transfer Function Model Derived from Measurements: Case Studies on

12

Terna Case Study (3/3)

• Two WADCs are designed using ring-down measurements• The growing oscillations can be damped by WADCs

Bus Frequency Difference between South and North Italy

Tie-line active Power

Page 13: Adaptive Wide-Area Damping Controller Using Transfer Function … · Adaptive Wide-Area Damping Controller Using Transfer Function Model Derived from Measurements: Case Studies on

13

SEC Case Study (1/2)

• Target mode: est/south v.s. central/east• Observation signal:

Bus frequency between west and central

• Actuators: SVCs Generator governors in west/south Generator exciters in west/south

• Improve damping ratio and transient stability simultaneously Three incidents since 2015 that resulted in

tripping tie-line between west and central –system separation

Page 14: Adaptive Wide-Area Damping Controller Using Transfer Function … · Adaptive Wide-Area Damping Controller Using Transfer Function Model Derived from Measurements: Case Studies on

14

• Improve damping ratio and transient stability simultaneously Temporary fault on tieline between West and Central Large generation trip in west: ~2 GW

0 5 10 15 20

t(s)

-1200

-1000

-800

-600

-400

-200

0

200

Rot

or A

ngle

(deg

.)

withWADC

East-Plant

Central-Plant

West-Plant1

West-Plant2

South-Plant

North-Plant

0 5 10 15 20

t(s)

-15000

-10000

-5000

0

Rot

or A

ngle

(deg

.)

noWADC

East-Plant

Central-Plant

West-Plant1

West-Plant2

South-Plant

North-Plant

SEC Case Study (2/2)

Damping Control Effect (Actuators: Exciters)

Rotor Angle (No WADC) Rotor Angle (with WADCs)

System Separates

WADC prevents system separation

Page 15: Adaptive Wide-Area Damping Controller Using Transfer Function … · Adaptive Wide-Area Damping Controller Using Transfer Function Model Derived from Measurements: Case Studies on

15

Summary

• A measurement-driven approach to design WADC, does not rely on full system dynamic model.• Model Identification using ring-down or probing measurements. • Model validation in time-domain and frequency domain

• Adaptive WADC to accommodate variations in operating conditions, providing better control effect.

• Validated in three realistic large power grid models: NYPA, Terna and SEC.

• Next steps• RTDS/OPAL-RT hardware-in-the-loop test

Page 16: Adaptive Wide-Area Damping Controller Using Transfer Function … · Adaptive Wide-Area Damping Controller Using Transfer Function Model Derived from Measurements: Case Studies on

16

Acknowledgements

• This work was supported primarily by Electric Power ResearchInstitute(EPRI), New York Power Authority (NYPA), Terna (Italian TSO) andSaudi Electricity Company (SEC).

• This work made use of Engineering Research Center Shared Facilitiessupported by the Engineering Research Center Program of the NationalScience Foundation and DOE under NSF Award Number EEC-1041877 andthe CURENT Industry Partnership Program.

Page 17: Adaptive Wide-Area Damping Controller Using Transfer Function … · Adaptive Wide-Area Damping Controller Using Transfer Function Model Derived from Measurements: Case Studies on

17

Backup: Case Study on Two-area Four-machine System

Page 18: Adaptive Wide-Area Damping Controller Using Transfer Function … · Adaptive Wide-Area Damping Controller Using Transfer Function Model Derived from Measurements: Case Studies on

18

Backup: Adaptive Wide-Area Damping Controller Structure

• Lead-lag structure is employed• Adjust T1, T2 , Ka and ω based on the identified model

WADC Based on Lead-lag Structure