Active Fire Fighting, 4&5
Transcript of Active Fire Fighting, 4&5
-
8/17/2019 Active Fire Fighting, 4&5
1/57
DOC. N.
2017 30 000 R SP SP 22400
IRAN – SOUTH PARS GAS FIELD
PHASES 4 & 5
PLANT :
ONSHORE FACILITIES
DOC. N.
RP 2017 999 1900 002
Page 1 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
Agi p
I r an GROUP
ACTIVE FIRE FIGHTING
6 IAFD C.H.PARK J.H.KIM H.M.CHANG 22-11-2004
5 IAFD(HAZOP,PTR incorporated) C.H.PARK J.H.KIM H.M.CHANG 26-07-2003
REV. DESCRIPTION BY CHKD APPR DATE
4 AFD CZ RB GV 21-06-2002
3 IFD CZ RB GV 24-05-2002
2 Re-Issue for EPC C. Zini R.Brusoni F.Comodi 18-07-2001
REV. DESCRIPTION BY CHKD APPR DATE
Snampr oget t i Job. 309400 Doc. n° 999-ZA-E-03098
-
8/17/2019 Active Fire Fighting, 4&5
2/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 2 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
TABULATION OF REVISED PAGES
PAGE Rev.4 Rev.5 PAGE Rev.4 Rev.5
1 X 30
2 X 31 X
3 X 32
4 X 33 X
5 34 X
6 35 X
7 36 X
8 37
9 X 38 X
10 X 39
11 X 40 X
12 X 41 X
13 X 42 X
14 X 43
15 44
16 45
17 X 46 X
18 X 47
19 48 X
20 49 X
21 50 X
22 51 X
23 52 X
24 53 X
25 X 54 X
26 55 X
27 56 X
28 57 X
29
-
8/17/2019 Active Fire Fighting, 4&5
3/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 3 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
CONTENTS
1. SCOPE ....................................................................................................................................... 4
2. APPLICABLE CODES AND REFERENCE DOCUMENTS ....................................................... 4
3. ACTIVE FIRE-FIGHTING PHILOSOPHY .................................................................................. 6
4. FIRE WATER DEMAND ............................................................................................................ 8
5. FIRE WATER STORAGE TANKS ............................................................................................. 9
6. FIRE WATER PUMPS ............................................................................................................. 10
7. FIRE WATER MAINS............................................................................................................... 11
8. FIXED WATER SYSTEMS....................................................................................................... 12
9. FIXED FIRE MONITORS ......................................................................................................... 15
10. FIRE HYDRANTS AND HOSE REELS ................................................................................... 16
11. ACTIVE FIRE-FIGHTING FOR HYDROCARBON LIQUID STORAGE .................................. 17
12. FOAM CONCENTRATE STORAGE ....................................................................................... 19
13. TOTAL FLOODING CO2 SYSTEMS ...................................................................................... 20
14. MOBILE AND PORTABLE EQUIPMENT ............................................................................... 21
15. TECHNICAL APPENDIXES .................................................................................................... 22
16. ATTACHMENTS ...................................................................................................................... 47
-
8/17/2019 Active Fire Fighting, 4&5
4/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 4 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
1. SCOPE
This Job Specification covers the fire protection design requirements for the gas treatment plant for
the “South Pars Development Project (Phases 4 and 5)”, in IRAN.
Design requirements for passive fire protection systems and fire & gas detection systems are
defined in separate documents.
2. APPLICABLE CODES AND REFERENCE DOCUMENTS
Fire-fighting engineering shall be generally based on the requirements of this specification.
In addition reference can be made to the below indicated standards for development of detailed
engineering of specific fire-fighting systems and equipment.
2.1 APPLICABLE CODES AND STANDARDS
NFPA 10 (1998 Ed) Portable Fire Extinguishers
NFPA 11 (1998 Ed) Low Expansion Foam and Combined Agent Systems
NFPA 11A (1999 Ed) Medium and High-Expansion Foam Systems
NFPA 11C (1995 Ed) Mobile Foam Apparatus
NFPA 12 (2000 Ed) Carbon Dioxide Extinguishing Systems
NFPA 13 (1996 Ed) Sprinkler Systems
NFPA 15 (1996 Ed) Water Spray Fixed Systems for Fire ProtectionNFPA 16 (1999 Ed) Foam-Water Sprinkler and Foam-Water Spray Systems
NFPA 20 (1999 Ed) Installation of Centrifugal Fire Pumps
NFPA 24 (1995 Ed) Private fire Service Mains and their Appurtenances.
-
8/17/2019 Active Fire Fighting, 4&5
5/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 5 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
2.2 REFERENCE DOCUMENTS
SPP-2017-130-T-101 ISBL Firewater storage tank
SPP-2017-130-T-102 OSBL Firewater storage tank
SPP-2017-130-P-101 A/B ISBL Firewater jockey pumps –Lower section
SPP-2017-130-P-102 A/B/C ISBL Firewater main pumps –Lower section
SPP-2017-130-P-103 A/B ISBL Firewater jockey pumps – Upper section
SPP-2017-130-P-104 A/B/C ISBL Firewater main pumps – Upper section
SPP-2017-130-P-105 A/B OSBL Firewater jockey pumps
SPP-2017-130-P-106 A/B/C OSBL Firewater main pumps
PID-2017-130-0030-0101 ISBL Fire water storage – Fire water pumping system – Lower section
PID-2017-130-0030-0102 ISBL Fire water pumping system – Upper section
PID-2017-130-0030-0103 OSBL Fire water storage & pumping system
-
8/17/2019 Active Fire Fighting, 4&5
6/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 6 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
3. ACTIVE FIRE-FIGHTING PHILOSOPHY
3.1 GENERAL PRINCIPLES
It shall be first understood that extinguishing a main jet fire is not credible. The single possible
strategy in case of such a fire is to shut-off the source of fuel and to promptly evacuate all
personnel.
The fire-fighting philosophy shall be focused on the capability of :
Extinguishing small hydrocarbons fires at their early stage of development. This shall be
achieved manually, through portable or wheeled fire extinguishers.
Extinguishing pool fires limited to the retention basins or the dikes below equipment or tanks.
This shall be achieved manually, through mobile or fixed foam systems of low expansion.
Extinguishing automatically fires in the machinery enclosures through CO2 total flooding.
Extinguishing manually electrical fires by means of either portable and mobile extinguishers, or
fixed CO2 extinguishing system depending on the enclosure characteristics.
Extinguishing cellulosic fires and limiting smoke development in buildings with high occupancy.
The use of water as a cooling agent shall be understood to be a mitigation measure only.
-
8/17/2019 Active Fire Fighting, 4&5
7/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 7 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
3.2 SPECIFIC PLANT REQUIREMENTS
3.2.1 Plant arrangement
The Plant layout looks for two separate areas : one including all process facilities ( ISBL ) , the
other including the condensate storage facilities ( OSBL ).
Because these two areas are some 3 Km apart from each other, two separate fire-fighting systems
shall be provided, each one serving the dedicated area only.
The ISBL area looks for a wide ground levels differences so that fire water shall be supplied by
two independent pumping system : one serving the upper level section, the other serving the lower
level section.
The OSBL area is assumed to be like a flat area, so fire water will be supplied by a dedicated fire
water supply system.
3.2.2 Water sources
The system shall provide for two independent sources of water for fire service.
Primary Water SourceDesalinated water shall be used as primary source and be permanently stored to allow for system
uninterrupted operation for the required time.
Desalinated water shall be supplied to ISBL and OSBL storage directly from Phase 4&5 Unit 126
desalination facilities at 350 m3/h rate approx.
This capacity shall serve for tank filling and continuous make-up service.
A dedicated pipeline shall be provided from ISBL Phase 4&5 Unit 126 desalination facilities area to
supply the OSBL area.
Alternative Water Source
Sea water shall be used as an alternative source and be supplied at the design capacity as
required by any of the fire water system.
At ISBL area, Sea Water shall be directly supplied by Phase 4&5 Unit 125 sea water pumps.
At OSBL area, Sea Water shall be supplied by any source as available through the entire South
Pars Field ; investigation and selection for the the most practical sea water source shall be
performed during detailed engineering stage as well as study for adequate modification and
interconnecting as necessary.
-
8/17/2019 Active Fire Fighting, 4&5
8/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 8 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
4. FIRE WATER DEMAND
The quantity of water supplied to any Plant area/section shall be at least sufficient to provide fire
fighting and exposure protection of the equipment within a Fire Area as described in the
appendices .
Separate water demand calculations shall be performed for the following Plant areas:
ISBL upper section area
ISBL lower section area
OSBL area
Fire in two separate Fire Area at the same time shall not be considered.
The maximum fire water demand shall correspond to the most demanding Fire Area, plus extra
capacity for monitors and hoses streams.
Extra capacity shall be calculated in compliance with Technical Appendix, anyway considering the
following minimum figures :
120 m3/h for one mobile monitor plus 60 m3/h for fire hoses in process areas.
300 m3/h for mobile water/foam monitors in storage areas.
-
8/17/2019 Active Fire Fighting, 4&5
9/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 9 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
5. FIRE WATER STORAGE TANKS
Two fire water storage tanks shall be provided:
one serving the ISBL area fire water system , common to both upper and lower section
one serving the OSBL area fire water system.
Both the storage tanks shall be normally filled with desalinated water which is the primary fire water
source.
In case of an emergency or prolonged fire fighting operation, the tanks shall be replenished with
sea water which is the alternative fire water source.
Each of the tanks shall be sized to allow for not less than six hours operation at the rated design
capacity of the reference area / section.
At ISBL area the tank design capacity shall be calculated assuming the simultaneous operation of
both fire pumps sets ( Upper section and Lower section ) at the same time.
The plant shall not be repressurised after a fire, until the tank is refilled with desalinated water.
The tank shall be provided with a level indicator and the maximum filling level shall be fitted with an
overflow.
-
8/17/2019 Active Fire Fighting, 4&5
10/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 10 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
6. FIRE WATER PUMPS
Three fire pumps sets shall be provided to deliver water to the ring mains as follows :
One set serving the ISBL Upper section area
One set serving the ISBL Lower section area
One set serving the OSBL area
Each pumping set shall consist of three horizontal fire water pumps (one electrically and two diesel
driven; the electrically driven pump shall remain powered in case of total normal power failure)
corresponding to 3x50% of the Design Water Demand.
Each diesel engine shall include a fuel tank with a capacity of at least twelve hours running,
manually refilled by the main storage.
The fire water main shall be permanently pressurised by two electrically driven jockey pumps
having a capacity of 30 m3/h minimum.
The fire water network shall be pressurised at 7 barg at the highest point of the fire water network.
One pump shall run continuously with the second acting as spare.
The pumps shall be sized to provide the rated flow at a minimum pressure of 7 barg at the
hydraulically most remote user.
This requirement shall apply even if one supply branch of the fire water mains is blocked.
Fire water pumps and drivers shall fully comply with NFPA 20 Codes and be provided with proper
Listing /Approval.
Any fire water pump shall be provided with :
a manually operated isolation valve between the pump and the tie-in point with the main ring
a minimum flow and a non-return valve on the discharge side of the pump
testing facilities, designed to enable testing of the pump at 150% of the rated pump capacity
surge protection, if necessary.
The spare jockey pump and the three fire water pumps shall start automatically. The spare jockey
pump shall be started automatically in the case of shutdown of the first jockey pump. The three
water pumps shall be controlled by a low pressure signal from the fire water distribution network.
After a suitable delay, should for any reason the fire water ring main pressure be below its set
point, indicating the demand is not being satisfied, the logic shall initiate in sequence the starting of
fire pump n°1, pump n°2 and pump n°3.
Fire water pumps shall also be started automatically in the operation of automatic deluge system
via the activation of fusible plug (PSL)/ heat sensitive cable.
Pumps shall also be manually started from the pump local control panel. The possibility of starting
the fire water pumps from the control room shall be envisaged. The only means for the operator to
shutdown the fire pumps shall be by pressing the local stop push button.
-
8/17/2019 Active Fire Fighting, 4&5
11/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 11 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
7. FIRE WATER MAINS
Three independent fire mains shall be provided to supply fire water to field equipment and
systems:
One main serving the ISBL Upper section area
One main serving the ISBL Lower section area
One main serving the OSBL area
The mains shall be arranged in the form of a ring around fire zones so that each ring and any area
within a fire zone can be supplied with water coming from two opposite directions.
A single fire water line supplying fire fighting systems is acceptable for warehouses and low-risk,
non-hydrocarbon process.
Fire water ring main shall be underground and the required depth shall be at least 0.8m below the
ground level.
Piping should run along side roads at some distance from hydrocarbon piping and 2m away from
the edge of the road or 1 m from the sidewalk if any.
The firewater main shall be equipped with isolation gate valves so that any section of the grid can
be taken out of service and the grid can still supply water through adjacent sections. Number of
valves shall be based on number of pipes at a main junction less one. Easy access to these valves
shall be provided. The valves shall be located in pits and position indicators shall be provided.
The pipe sizes in the fire water mains network shall be calculated to give the design flowrate at the
required pressure at the fire-fighting equipment even when one of the supply branches of the loop
is blocked. The maximum allowable velocity in the fire water mains shall be 3 m/s during normal
operation, and 4 m/s with one of the supply branches isolated when discharging the design
capacity as required in any Fire Zone.
The fire water system components (flanges, fittings, line pipe etc.) shall be capable of withstanding
the maximum pressure with the fire water pumps in operation with no take off flow, plus the static
head of the fully filled storage tank and the over pressure which could be developed due to surge
(hammer effect) at pump start-up or when the take-off flow is stopped. Dynamic study to
investigate the need for surge protection shall be performed during detailed engineering stage.
Underground piping material shall be GRP type and shall be chosen according to : Piping Material
Classes Specification RP 2017 999 1300 001. When glass reinforced piping is used underground,
detail design of the GRP network, including its installation shall be carried by the pipe supplier. The
fire water mains shall be provided with full bore valved flushing connections so that all sections and
dead ends can be properly cleaned out.
-
8/17/2019 Active Fire Fighting, 4&5
12/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 12 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
8. FIXED WATER SYSTEMS
a) Deluge Systems
Fixed water deluge systems are installed to provide cooling or fire intensity control.
Deluge systems shall be installed for the protection of the following equipment :
All vessels, columns and exchangers holding a hydrocarbon liquid volume of more
than 5 m3.
Water rate shall be 10.2 lit/min/m² of developed surface.
Columns should be deluged on whole vertical length ; however consideration shall be
made during detailed design to limit water application to 12 m maximum height from
any possible hydrocarbon accumulation level, this in compliance NFPA 15
recommendation.
Pumps handling products close to or above their auto-ignition temperature.
Pumps handling C4 and lighter products.
The foundation/skid of the pumps including an outskirt of at least 1.5 m shall be
covered by water spray. The water rate shall be 20.4 lit/min/m² of the floor area.
Compressors handling C4 and lighter products which are not installed in enclosures.
The compressor floor area including an outskirt of at least 1.5 m around the
foundation, shall be covered by water spray.
The system shall cover the compressor casing, associated piping and valving, the
gearbox, the lube-oil console and other auxiliary equipment.
The water rate shall be 20.4 lit/min/m² of the floor area..
Slug catcher.
Deluge shall be limited to equipment extremities and 5 m beyond.
Water rate shall be 10.2 lit/min/m².
The pig receiver, if hydrocarbon liquid inventory is more than 5 m3.
The water flow rate shall be 10.2 lit/min/m².
As propane refrigerant storage supply is not a continuous service, deluge on transfer
pumps is not required. Protection shall be by monitors.
Flow rates for the spray systems shall be based on the mentioned water rates, which are in
compliance with NFPA 15 Codes and already include a wastage factor , over-spray flow up
to 15% rate can be added on the presence only of extreme conditions affecting proper
water application like very strong wind effect, etc..
The piping downstream the deluge valves is normally dry. Provisions shall be made to
drain the piping after operation.
-
8/17/2019 Active Fire Fighting, 4&5
13/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 13 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
The Material for fire water deluge piping shall be Cu-Ni which is in accordance with
Piping Material Classes Specification N° RP 2017 999 1300 001; alternatively
galvanised CS can be considered, as a minimum for dry pipes downstream the delugevalve.
Deluge valves shall be either located at a minimum distance of 15m from the protected
area or, if not possible, behind a fire wall.
Each deluge system shall be fed from two separate headers. One connection will have
an automatic deluge valve and the other will have a manual (easily accessible) shut off
valve.
Isolation of automatic deluge systems shall be possible by means of manual block
valves, locked open in normal service.
The deluge valve shall be a specific quick opening automatic valve energised by the firewater pressure. Remote manual opening of each automatic deluge valve shall be
possible from the Central Control Room. Local manual release shall also be possible.
Deluge valves shall also be open in case of ESD1F.
The deluge valve shall preferably be of the “straight through” design to avoid possible
obstruction while operating. The maximum diameter for deluge valve shall be 8” (200
mm) and the maximum pressure drop at nominal flow shall be less than 0.7 barg.
Deluge valves shall be of a type approved by an international organisation for deluge
system.
Deluge system water demand shall not exceed the maximum allowed per NFPA 15.Valve reset must always be accomplished locally and manually. Means shall be provided
to enable the testing of deluge valve without discharging firewater through the pipework
and nozzles.
Deluge valves and associated piping should be sized so that water velocity does not
generally exceed 3 m/s in any part of the deluge branch.
However, higher velocities up to 5-6 m/sec are allowed to meet pressure drop
requirement between the deluge valve and the hydraulically most remote nozzle.
Restriction orifice should be avoided in compliance with NFPA 15; if deemed necessary
, the number shall be kept to minimum and should be located at maintainable locations,
preferably downstream of, close to deluge valves. Other location will require Company's
approval.
Spray nozzles shall be selected with due consideration of their upstream working
pressure.
Spray nozzles shall be of the medium velocity type. The normal working pressure in the
piping upstream of the nozzles should be around 3.5 barg and shall never be less than
-
8/17/2019 Active Fire Fighting, 4&5
14/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 14 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
2.5 barg. Spray nozzles shall have a 5 mm minimum diameter to minimise plugging.
Spray nozzles shall be made of stainless steel.
A study shall be conducted during detailed design stage to investigate corrosionproblems due coupling of SS nozzles to Cu-Ni piping.
Hydraulic calculations shall be performed for each deluge system according to NFPA 15
assuming Hazen & Williams formula C factor = 150 for both Cu-Ni or SS pipes.
b) Water curtains
From a first assessment, water curtains are not requested.
In case of insufficient distance between two units, water curtains could be installed to limit
the effect of thermal radiation from a fire.
c) Sprinklers
Sprinkler system could be installed in non-technical building where fires are expected to
involve cellulosic material.
However, smoke detection coupled with manual fire fighting means (hose reels, fire
extinguishers etc..) shall be preferred.
-
8/17/2019 Active Fire Fighting, 4&5
15/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 15 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
9. FIXED FIRE MONITORS
Monitors can be ground level or elevated, local or remote controlled.
Monitors shall be provided around receiving, process and flare KO drums facilities. A minimum
distance of 15m and a maximum of 30m from the protected equipment shall be provided.
Special precautions shall be taken to ensure that monitors are adequately protected from possible
road traffic accidents.
Two monitors shall be installed for each protected item of equipment to allow at least the use of
one in any fire scenario and wind configuration.
Monitors coverage shall be assumed the ground projected 30 m radius regardless of any
interference or shadow equipment.
Each monitor shall have a capacity of 120 m3/h approximately at a working pressure of 7 barg
immediately upstream of the monitor.
Each monitor shall have sufficient movement in the horizontal and vertical planes in order to permit
coverage of any point protected by that monitor. There shall be means for locking the monitor in
position. The minimum movement capabilities shall be :
rotation angle : 360° stop to stop
elevation angles : 80° upwards, 45° downwards.
Each monitor should be capable of discharging under jet and spray conditions. The distance
reached shall be 40 to 45 m horizontal at straight water stream or 30 m for the center of water
spray pattern.
Monitors shall be of such design that the hydraulic forces (including pressure surge when opening
the monitor valve) are balanced. Each monitor shall have a block valve and, shall be provided with
adequate drainage facilities due to corrosive action of fire water.
Water/foam monitors shall be provided in the MEG regeneration unit, near the chemical storage
tanks and for the spillage pit in the slug catcher area.
A double-gun type (one for water and one for foam) should be provided. The range of reach of
foam monitors shall be around 30 m.
Monitors will be supplied with foam by direct foam concentrate suction from local drums as well as
by external sources ( fire trucks ). For this purpose monitors foam gun will be provided with an
inline inductor allowing for foam concentrate suction. No fixed foam facilities shall be provided.
-
8/17/2019 Active Fire Fighting, 4&5
16/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 16 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
10. FIRE HYDRANTS AND HOSE REELS
a) Hydrants
Fire hydrants shall be 6” (150mm) type with a single hydrant valve. One 4” (100 mm) and two
2½ ” (65mm) outlets with chained caps are required, and shall be provided with adequate
drainage facilities due to corrosive action of fire water.
Hydrants will be made of carbon steel pipe internally lined.
Hydrants shall be arranged to provide coverage of the target area from two different directions.
Hydrant spacing shall not exceed 60 m for process facilities and 80 m for storage facilities.
Hydrants shall be located along access ways and roadways, around process and storage
facilities, at least 15 m away from the equipment to be protected. Possible damage by road
traffic shall be minimised and, if necessary, hydrants should be protected by guard systems.
b) Hose Reels
Hose reels shall be provided in the following buildings :
Administration buildings
Control building
Workshop/warehouse
Firefighting station
Hose reels are fitted onto the permanently pressurised part of the firewater network.
Hose reels comprise the four following components :
a globe valve size 1”
a reel with axial water supply connected to the globe valve,
a semi rigid hose 30 m long, 1”
an adjustable jet with orifice 8 mm
Part of the hose reel from the inlet globe valve to the jet orifice shall be provided with adequate
drainage facilities due to corrosive action of fire water.
The pressure requirements at the hydraulically most remote reel is 2.5 barg minimum and the
pressure shall never exceed 12 barg. If necessary, a pressure control valve can be installed.
At 2.5 barg water pressure, the flowrate requirement is 55 lit/min. The distance reached shall
be between 15 and 20 m under this pressure condition.
Hose reels shall be located so that any single spot where a fire may exist shall be reachable
by at least two hose reels. Hose reels shall be located away from the potential sources of
hazard, preferably close to accesses e.g. stair landings, doors, etc.
-
8/17/2019 Active Fire Fighting, 4&5
17/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 17 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
11. ACTIVE FIRE-FIGHTING FOR HYDROCARBON LIQUID STORAGE
11.1 ACTIVE FIRE-FIGHTING FOR FLOATING ROOF TANKS
The Active Fire-Fighting for floating roof tanks consists of the sequenced use of the following
means:
An automatic extinguishing system, (to be provided by tank vendor) which shall discharge foam
into the rimseal of the floating roof tank on fire (application rate:12 lit/min/m2 of rimseal for a
duration of 30 to 40 sec).
Foam generators and pourers, which shall discharge foam into the rimseal of the floating roof
tank on fire (application rate: 7.5 lit/min/m2 of rimseal) ; system to be supplied with foam
solution by fire trucks.
Water spray systems for cooling the shell of the tank on fire and adjacent tank(s) included in
the Fire Area (application rate: 15 lit/min/m of the whole shell circumference).
Mobile water/foam monitor(s).
All the above systems, except the automatic extinguishing system on tank rim seal, require human
local operation.
For bund area, small surface bund area around loading / unloading line can be extinguished by
mobile means. Fixed foam protection system for full surface bund fire are not envisaged since
there is no credibility in extinguishing the fire due to very large area of bund. In case of large pool
fire in bund, the tank in bund on fire could be lost and the adjacent tank(s) will be protected by the
distance from the bund on fire and by the cooling system to be applied on their skirt.
11.2 ACTIVE FIRE-FIGHTING FOR FIXED ROOF TANK
The Active Fire-Fighting for fixed roof tank consists of the sequenced use of the following means
depending on fire scenario:
a. Tank on fire
A foam system discharging directly into the tank under the surface of hydrocarbon liquid
application rate: 2.5 lit/min/m2) ; system to be supplied with foam solution by fire trucks
Water spray systems for cooling the shell of the tank on fire and adjacent tank(s) included in
the Fire Area (application rate: 15 lit/min/m of the whole outer shell circumference).
Mobile water/foam monitor(s).
All the above systems require human local operation.
For bund area, small surface bund area around loading / unloading area can be extinguished by
-
8/17/2019 Active Fire Fighting, 4&5
18/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 18 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
mobile means. Fixed protection system for full surface bund fire is not foreseen. All the above
mentioned manually operated water systems shall be fed by the fire water network from two
opposite sides, through manual shut-off valves. These shut-off valves shall be located either at aminimum distance of 30 m from the protected equipment, or if this is not possible, behind a fire
wall.
11.3 ACTIVE FIRE FIGHTING FOR LPG STORAGE TANK
The active fire fighting shall be hydrants around the storage area. A fixed water spray system shall
be required for vital appurtenances on the tank roof and pumping platform if the thermal radiation
calculation leads to more than 8 kW/m2 for this equipment. For appurtenances located on the tank
roof, fireproofing could be used as an alternate.
The pressure relief valves discharging to air shall be provided with dry powder extinguishing
system in accordance with NFPA 17.
-
8/17/2019 Active Fire Fighting, 4&5
19/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 19 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
12. FOAM CONCENTRATE STORAGE
12.1 CONCENTRATE FOR HYDROCARBON LIQUID STORAGE PROTECTION
The foam concentrate storage capacity shall allow supply of foam for 20 min for the scenario “Tank
on Fire”.
Film Forming Fluoro Protein (FFFP) foam concentrate of low expansion type shall be used.
The foam concentrate will be stored in 200 litres drums wich shall be brought by mobile means
when necessary. Mobile facilities shall be provided with facilities for foam concentrate
proportioning and supply to foam systems.
12.2 CONCENTRATE FOR FIXED WATER /FOAM MONITORS
Foam concentrate for fixed water/foam monitors shall be stored in 200 litres drums which shall be
brought by mobile means when necessary.
For fixed water/foam monitors located in the MEG regeneration unit and near chemical storage
tanks, foam concentrate of alcohol resistant type shall be used.
For fixed water/foam monitors located near the slug catcher unit spillage pit, foam concentrate of
FFFP low expansion type shall be used.
-
8/17/2019 Active Fire Fighting, 4&5
20/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 20 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
13. TOTAL FLOODING CO2 SYSTEMS
Fixed C02 system with manual activation shall be provided to protect the false floors of instrument
rooms and central control room. These systems shall not be used before HVAC system has been
shutdown and damper closed in these rooms.
Each system shall have bottles fixed in a rack on the outside wall of the ITR/Control Room.
Bottles will be protected from direct sunlight by an overhead canopy.
Bottles will be designed for the maximum in shade temperature either by having a suitable rating at
full pressure or by derating the pressure in the bottles so that it meets the bottle design pressure at
the design maximum air temperature.
Total flooding C02 systems linked to the fire detection system shall be installed for gas
turbines, combustion engines, compressor enclosures and emergency generator room. These
systems shall be provided by the machine supplier who shall also determine whether
successive C02 releases are necessary or not (taking into account the cool-down response of
machinery) and the time delay between releases.
It shall be possible to manually initiate the CO2 discharge from machine local control panel.
Discharge, fault and inhibition of total flooding CO2 systems shall initiate a common audible
alarm and a visual alarm on the operator control desk in the Central Control Room.
The protection system shall be provided by the machine supplier.
-
8/17/2019 Active Fire Fighting, 4&5
21/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 21 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
14. MOBILE AND PORTABLE EQUIPMENT
a) Hose boxes
Hose boxes shall be installed adjacent to hydrants and shall contain fire fighting accessories
(fire hoses, water branch pipe, foam branch pipe with foam pick-up tube assembly, containers
of foam compound). As a general rule, one hose box shall be installed for every two hydrants.
b) Portable and wheeled extinguishers
12 kg portable and 50 kg wheeled dry powder extinguishers suitable for types B and C fires,
shall be provided throughout the plant in the areas to be protected in order to have for the
portable extinguishers a maximum travel distance of 15m for process units and 30m for the
other areas and for the wheeled extinguishers between 30m and 50m.
For compressors handling flammable gas, at least one extinguisher shall be provided at
each floor level.
Extinguishers shall be equipped with protection from the radiant heat of the sun.
In buildings where hydrocarbons could be present, 12 kg dry powder extinguishers shall be
provided.
6 Kg water extinguishers for type A fire shall be provided in buildings such as offices,
stores, etc.
6 Kg CO2 extinguishers shall be installed in areas or buildings where electrical fires are
expected such as control room, switchgear room, instrument room.
Extinguishers shall be placed at each exit of such rooms.
c) Trailer mounted water/foam cannons
Trailer mounted water/foam cannons (also called ‘mobile water/foam monitors’) shall be
provided. They shall be suitable for towing behind a fire fighting vehicle or a utility vehicle.
d) Fire-fighting vehicles
The following vehicles shall be provided on plant premises :
water/foam and dry powder multi-service vehicle
a general purpose support vehicle for fire brigade personnel
The characteristics of the water/foam and dry powder vehicle shall be :
water, tank capacity : 2 m3
foam tank capacity : 4 m3
foam solution system : 6000 lit/min - 10 bar
dry powder tank capacity : 1 000 kg
This vehicle shall be equipped with a water/foam monitor
The vehicles shall be located in the fire station.
-
8/17/2019 Active Fire Fighting, 4&5
22/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 22 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
15. TECHNICAL APPENDIXES
Scope of the Technical Appendixes is to provide additional information to the general requirements
previously described.
-
8/17/2019 Active Fire Fighting, 4&5
23/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 23 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
15.1 DEFINITIONS
15.1.1 Fire Area
Fire Area is an hypothetical area used to for the purpose of sizing the fire water system, whose
boundaries are assumed as spread limits of fire and heat radiation; by this way no fire/ heat
spread from one Fire Area to another is considered .
Fire Area in process areas shall be logically defined depending on location of equipment and
buildings provided that the minimum distance between equipment/vessels in one Area and
equipment/vessels in another Area shall be not less than 15 m.
Fire Area extension in tankage area shall be defined including all tanks/equipment totally or
partially included within “one diameter” distance from the shell of the tank on fire or “two diameters”
downwind whichever requiring the largest water demand; being “one diameter” and “two
diameters” distance referred to the diameter of the tank on fire.
15.1.2 Area Water Demand
The Area Water Demand is the fire water capacity required to achieve fire protection in any single
Fire Area in compliance with procedure described in Appendix 15.2
15.1.3 Design Water Demand
The Design Water Demand is the largest Area Water Demand among all figures calculated
through each Plant area.
15.1.4 Fire Water User Pressure
The Fire Water User Pressure is the minimum residual pressure to be available at any user when
the reference Area Water Demand is discharged.
-
8/17/2019 Active Fire Fighting, 4&5
24/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 24 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
15.1.5 Fire Water Design Pressure
The Fire water Design pressure is the maximum pressure which can be found through the plant at
any working condition.
The fire water design pressure shall not exceed 16 barg in any case.
15.1.6 Reference Fire Scenario
The reference Fire Scenario is the summary of all fire protection actions which are expected to be
performed to control a selected fire risk.
-
8/17/2019 Active Fire Fighting, 4&5
25/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 25 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
15.2 FIRE WATER DEMAND CALCULATION
15.2.1 Area Water Demand calculation
Area Water Demand shall be calculated per each one Fire Area; these areas are evaluated
through the entire Plant area on the basis of criteria indicated in Appendix 15.1.1
Area Water Demand shall be calculated on the basis of a reference Fire Scenario representing the
fire situation requiring the largest water demand in the Area under discussion.
Reference Fire Scenarios shall be selected on the basis of Appendixes 15.3.1 through 15.3.11
depending on the actual fire risk in the subject Area.
15.2.2 Design Water Demand
Design Fire Water demand is to be assumed as the largest figure among all Area Water Demand
as resulting from investigation investigated through all Fire Area.
Such figure is to be used to design the fire water supply systems, including storage, pumping and
distribution facilities.
Separate Design Water Demand shall be calculated for any one Plant area as follow : ISBL Upper section area
ISBL Lower section area
OSBL area
-
8/17/2019 Active Fire Fighting, 4&5
26/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 26 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
15.3 REFERENCE FIRE SCENARIOS
Here below are listed the reference fire scenarios to be considered for Area Water Demand
calculation.
15.3.1 Liquid hydrocarbons small pool fire
Such kind of fire, originated by small oil leaks, are expected to occur everywhere through the plant
area; they will be manually extinguished at their early stage of development by means of portable
or wheeled fire extinguishers.
Water application is not generally required.
15.3.2 Liquid hydrocarbons large pool fires in process areas
Such kind of fire, originated by large oil release in process unit area; because the extinguishment
of such fires is very difficult, the fire-fighting action will meet fire intensity control as well as
exposure protection by spray water application via fixed facilities.
Additionally foam can be manually applied as possible by mobile facilities.
Water demand shall be calculated as follows:
Demand from the deluge systems protecting the equipment on fire
Demand for all the adjacent deluge systems and included in the same Fire Zone Demand for additional streams ( water or foam service ) at not less than 180 m3/h capacity.
15.3.3 Liquid hydrocarbons large pool fires in diked areas
Such kind of fire, originated by large oil release is mainly expected to occur in the tankage area
only partially involving the retention pond area; it is not considered a “Credible Fire “ the full surface
bund fire.
Fire will be controlled / extinguished by means of manual foam application by mobile facilities.
Water demand shall calculated as follows:
Demand for master streams ( water / foam service ) -not less than 300 m3/h capacity.
-
8/17/2019 Active Fire Fighting, 4&5
27/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 27 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
15.3.4 Liquid hydrocarbons fires in floating roof storage tanks
Such kind of fire, is expected to involve the roof rim seal area only.
Fire will be controlled / extinguished by automatic foam application by fixed facilities .
Additionally spray water can be applied for exposures protection.
Water demand shall be calculated as follows:
Demand for foam solution application to the rim seal of the tank on fire
Demand for exposure protection of the shell of the tank on fire
Demand for exposure protection of the shell of the tanks adjacent to the tank on fire ( totally or
partially included within a distance equal to the diameter of the tank on fire measured shell to
shell ). Coverage shall be limited to the exposed half shell only if applicable.
Demand for additional streams ( water or foam service ) - not less than 300 m3/h capacity.
15.3.5 Liquid hydrocarbons fires in cone roof storage tanks
Such kind of fire, is expected to involve the entire fuel surface inside the tank wall.
Fire will be controlled / extinguished by automatic foam application by mobile facilities .
Additionally spray water can be applied for exposures protection.
Water demand shall be calculated as follows: Demand for foam solution application to the full fuel surface of the tank on fire
Demand for exposure protection of the shell of the tank on fire
Demand for exposure protection of the shell of the tanks adjacent to the tank on fire ( totally or
partially included within a distance equal to the diameter of the tank on fire measured shell to
shell ). Coverage shall be limited to the exposed half shell only if applicable.
Demand for additional streams ( water or foam service ) - not less than 300 m3/h capacity.
15.3.6 Liquefied hydrocarbons jet fires in process units
Such kind of fire is expected to have reduced magnitude so involving few equipment through the
process unit; it is not considered a “ Credible Fire “ a large jet fire.
Extinguishment of such fire must not be achieved unless the fuel source is shut-off ; exposure
protection will be achieved by spray water application via both automatic and manual facilities.
Water demand shall be calculated as follows:
Demand for additional streams ( water service ) - not less than 180 m3/h capacity.
-
8/17/2019 Active Fire Fighting, 4&5
28/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 28 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
15.3.7 Liquefied hydrocarbons jet fires at storage tanks
Such kind of fire is expected to occur at inlet/outlet appurtenances only on the tank roof and
pumping platform ; it is not considered a “ Credible Fire “ a fire involving the entire tank content.
Extinguishment of such fire must not be achieved unless the fuel source is shut-off ; exposure
protection will be achieved by spray water application via automatic and manual facilities.
Water demand shall be calculated as follows:
Demand for deluge system protecting the equipment on fire.
Demand for all the adjacent deluge systems and included in the 8 KW/m2 radiation range.
Demand for additional streams ( water or foam service ) - not less than 300 m3/h capacity.
15.3.8 Liquid / gas hydrocarbons fires in enclosures
Such kind of fire is expected to occur inside the enclosure of rotating machinery ( gas turbines,
combustion engines, compressors enclosure, emergency generators).
Extinguishment of such fire will be achieved by automatic total flooding of the subject enclosure via
proper extinguishing gas.
Water application is not generally required.
15.3.9 Electrical fires in unmanned enclosures
Such kind of fire is expected to occur in the cable basement only below floating floors; it is not
considered unmanned an enclosure in which people can enter for manual fire fighting.
Extinguishment of such fire will be achieved by manually operated total flooding of the subject
enclosure via proper extinguishing gas.
Water application is not generally required.
15.3.10 Electrical fires in manned enclosures
Such kind of fire is expected to occur in enclosures holding larger quantity of electrical facilities (
Control Room, Electrical Substation etc. ); they will be manually extinguished at their early stage
of development by means of portable or wheeled fire extinguishers.
Water application is not generally required.
15.3.11 Class A and B fires in technical buildings
Class A and B fires in technical buildings are expected to occur in high occupancy technical
building. ( Offices, Warehouses, etc) ; they will be manually extinguished at their early stage of
development by means of portable or wheeled fire extinguishers.
-
8/17/2019 Active Fire Fighting, 4&5
29/57
-
8/17/2019 Active Fire Fighting, 4&5
30/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 30 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
15.4 FIRE WATER S YSTEM DESIGN
The Onshore facilities Phases 4 & 5 are located in two separate sites : One site housing all
process facilities ( ISBL ) , the other housing the condensate storage facilities ( OSBL ).
The two sites are separated and each is far from the other, so the design of fire water supply
system shall require different approaches as follows.
-
8/17/2019 Active Fire Fighting, 4&5
31/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 31 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
15.4.1 ISBL Area
The plant layout looks for some 48 m level difference between the fire water pumping station and
the highest plant area, this last being expected to require a very high water demand.
Due to this reason it appears not acceptable to provide one only pumping system serving all the
plant areas at the same time; because of the wide level range it would originate very high pressure
at lower areas, this last being an unacceptable condition from both technical and safety point of
view .
Considering the above and the need for having the Fire Water pumping station located in a safe
place ( far from major risks ), the selected approach is to provide two separate fire water systems,
each one serving plant sections at a elevation level range hydraulically acceptable.
Any system shall consist of three main fire pumps as well as two jockey pumps supplying a
distribution network located all around the reference plant areas.
Because of the differences in pressure design, any system shall operate as a stand alone system
without interface to the other system.
The two pumping sets shall take suction from a common storage tank provided with suitable
facilities for independent handling and isolation of any set.
The proposed arrangement looks for the following Units grouping :
Plant upper section : units at elevation between 70 and 90 m
Plant lower section : units at elevation between 38 and 56 m
In general the Fire Water Supply System shall be designed on the following general principles :
One only fire occurrence at any time; being the fire source located everywhere through the
reference plant area.
Simultaneous running of both Upper and Lower section fire pump sets at the same time for six
hours minimum time.
Normal power failure in case of fire
Emergency power availability in case of fire
Full independence from Firefighting facilities external to the Phase 4 & 5 Plant
Based on final estimation the ISBL Design Fire Water Demand is set as follows :
Plant upper section : 1010 m3/h
Plant lower section : 1237 m3/h
-
8/17/2019 Active Fire Fighting, 4&5
32/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 32 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
E L . 8
8 m
U 130 F I R E W A T E R N E T W O R K – L O W E R S E C T I O N
F I R E W A T E R N E T W O R K – U P P E
R S E C T I O N
E L . 4 0 m
E L . 5 6 m
E L . 6 8 m
E L . 8 2 m
FIRE WATER NETWORK ARRANGEMENT
U 116/1
U 107/1
U 114/2
U 115/2
U 143
U 147
U 148
U 100/1
U 100/2
U 116 /1U 107 /1
U 114/2U 105/2
E L . 8 2 m
E L . 9
0 m
E L . 7 0 m
E L . 5 6 m
E L . 3 8 m
U 130
U 143
-
8/17/2019 Active Fire Fighting, 4&5
33/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 33 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
Fire Water Storage
There shall be one only storage tank (130 - T - 101 ) common to both upper and lower sections.
The tank shall be fitted with proper nozzles to allow independent operation of the two Fire Pumpssets. The Storage Tank is set at 15000 m3 minimum capacity, allowing for 6 hour operation at 1010
m3/h ( upper section ) plus 1237 m3/h ( lower section ) fire water demand.
15.4.1.1 Lower section fire water system
Fire Water Pumps set
Fire Water shall be supplied to the network lower section by the following pump set:
130 P 101 A/B Electric motor driven jockey pumps130 P 102 A Electric motor driven main fire pump – rated for 50% of design water demand
130 P 102 B/C Diesel engine driven main fire pump– rated for 50% of design water demand
At present the system is set for the following :
Design Water demand : 1400 m3/h. Design water Demand shall not be less than 1000 m3/h.
Fire water pumps capacity : 700 m3/h ( rated capacity as per NFPA 20 definition )
Fire water pumps discharge pressure : 11.9 barg
Actual fire water pumps capacity and pressure shall be calculated during the detailed engineering
stage in compliance with requirements of paragraph 15.2 and taking into consideration thefollowing pressure needs :
Min. User pressure not less than 7 barg at the hydraulically most remote user when
discharging the required Area Demand. Such condition shall be
checked assuming the fire water storage tank as empty.
Max. User Pressure not more than 12 barg at the hydraulically nearest user when
discharging the required Area Demand. Such condition shall be
checked assuming the fire water storage tank is fulfilled.
Design pressure not exceeding 16 barg, to be inline with standard execution of fire
protection equipment
In addition , a study shall be conducted during detailed engineering stage to investigate for :
Reducing the Min. & Max. User pressures for a better operating range
The needs for a pressure control system to limit operating conditions to the required values.
Fire Water Distribution Network
-
8/17/2019 Active Fire Fighting, 4&5
34/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 34 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
The Fire water Distribution network shall be designed on the basis of following general principles :
Twin supply header – from pumps to the network – each rated for 100% Design water demandcapacity.
Fire Water Network single impairment option - no flow through any one of the network
branches at a time.
Fire Pumps single impairment option - one of the pumps out of service
GRP Piping for both headers and distribution rings
A detailed Hydraulic Study Report shall be developed to demonstrate that the entire fire water
system met the required design data for three cases at least :
The Design Case ( pressure drop calculation at Design Water Demand delivery condition )
The Minimum Case ( pressure drop calculation at Minimum Water Demand delivery condition )
The Worst case ( pressure drop calculation at largest water demand among all hydraulically
most remote from pumps )
Each case shall include calculation for both full network and single impairment network options;
Calculations shall be performed fully in compliance with NFPA 15 procedures assuming Hazen &
Williams formula C Factor = 135 for GRP piping.
Computer modelling shall include all facilities of the Fire water System (storage tank, pumps,network, users ) and shall extent up to the following types of users:
Fire monitors
Deluge systems
Foam systems
Other streams shall be assumed to be delivered from nodes located around the subject Fire Zone.
-
8/17/2019 Active Fire Fighting, 4&5
35/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 35 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
15.4.1.2 Upper section fire water system
Fire Water shall be supplied to the network lower section by the following pump set:130 P 103 A/B Electric motor driven jockey pumps
130 P 104 A Electric motor driven main fire pump – rated for 50% of design water demand
130 P 104 B/C Diesel engine driven main fire pump– rated for 50% of design water demand
At present the system is set for the following :
Design Water demand : 1100 m3/h. Design water Demand shall not be less than 1000 m3/h.
Fire water pumps capacity : 550 m3/h ( rated capacity as per NFPA definition )
Fire water pumps discharge pressure : 14.9 barg
Actual fire water pumps capacity and pressure shall be calculated during the detailed engineeringstage in compliance with requirements of paragraph 15.2 and taking into consideration the
following pressure needs :
Min. User pressure not less than 7 barg at the hydraulically most remote user when
discharging the required Area Demand. Such condition shall be
checked assuming the fire water storage tank as empty.
Max. User Pressure not more than 12 barg at the hydraulically nearest user when
discharging the required Area Demand. Such condition shall be
checked assuming the fire water storage tank as fulfilled. Design pressure not exceeding 16 barg, to be inline with standard execution of fire
protection equipment
In addition , a study shall be conducted during detailed engineering stage to investigate for :
Reducing the Min. & Max. User pressures for a better operating range
The needs for a pressure control system to limit operating conditions to the required values.
Fire Water Distribution Network
The Fire water Distribution network shall be designed on the basis of following general principles :
Twin supply header – from pumps to the network – each rated for 100% Design water demand
capacity.
Fire Water Network single impairment option - no flow through any one of the network
branches at a time.
-
8/17/2019 Active Fire Fighting, 4&5
36/57
-
8/17/2019 Active Fire Fighting, 4&5
37/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 37 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
15.4.2 OSBL Area
The area, including the condensate storage facilities, is some 3 Km far from the ISBL area and it is
assumed to be a flat area without any level difference between the fire water pumps and the
hydraulically most remote user.
Because of the distance from the ISBL facilities a dedicated fire water supply system is to be
provided serving the OSBL area only.
The system will consist of a fire water storage from which take suction a main fire pumps set as
well as jockey pumps set to supply a distribution network.
In general the Fire Water Supply System shall be designed on the following general principles :
One only fire occurrence at any time; being the fire source located everywhere through the
entire OSBL plant area.
Normal power failure in case of fire
Emergency power availability in case of fire
Full independence from Fire-fighting facilities other than those provided for Phases 4 & 5 Plant
15.4.2.1 Fire water storage
There shall be one only storage tank (130 - T - 102 ) for the OSBL fire water system.
The tank will be supplied with desalinated water by a dedicated line from ISBL facilities and be
fitted with proper nozzles to allow pumps operation .
The Storage Tank is set at 6000 m3 minimum capacity, allowing for 6 hour operation at 1000 m3/h
design water demand.
Because this is a tentative figure only, it is the scope of EPC Contractor to calculate the actual
storage capacity depending on design water demand which shall be calculated in compliance with
requirements of paragraph 15.2.
-
8/17/2019 Active Fire Fighting, 4&5
38/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 38 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
15.4.2.2 Fire water pumps set
Fire Water shall be supplied to the network lower section by the following pump set:
130 P 105 A/B Electric motor driven jockey pumps
130 P 106 A Electric motor driven main fire pump – rated for 50% of design water demand
130 P 106 B/C Diesel engine driven main fire pump– rated for 50% of design water demand
At present the system is set for the following :
Design Water demand : 1000 m3/h.
Fire water pumps capacity : 500 m3/h ( rated capacity as defined by NFPA 20 )
Fire water pumps discharge pressure : 11.0 barg
Actual fire water pumps capacity and pressure shall be calculated during the detailed engineering
stage in compliance with requirements of paragraph 15.2 and taking into consideration the
following pressure needs :
Min. User pressure not less than 7 barg at the hydraulically most remote user when
discharging the required Zone Demand. Such condition shall be
checked assuming the fire water storage tank as empty.
Max. User Pressure not more than 12 barg at the hydraulically nearest user when
discharging the required Zone Demand. Such condition shall be
checked assuming the fire water storage tank as fulfilled.
Design pressure not exceeding 16 barg, to be inline with standard execution of fire
protection equipment
Based on the above, a study shall be conducted during detailed engineering stage to investigate
for :
Reducing the Min. & Max. User pressures for a better operating range
The needs for a pressure control system to limit operating conditions to the required values.
15.4.2.3 Fire water distribution network
The Fire water Distribution network shall be designed on the basis of following general principles :
Twin supply header – from pumps to the network – each rated for 100% Design water demand
capacity.
-
8/17/2019 Active Fire Fighting, 4&5
39/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 39 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
Fire Water Network single impairment option - no flow through any one of the network
branches at a time.
Fire Pumps single impairment option - one of the pumps out of service GRP Piping for both headers and distribution rings
A detailed Hydraulic Study Report shall be developed to demonstrate that the entire fire water
system met the required design data for three cases at least :
The Design Case ( pressure drop calculation at Design Water Demand delivery condition )
The Minimum Case ( pressure drop calculation at Minimum Water Demand delivery condition )
The Worst case ( pressure drop calculation at largest water demand among all hydraulically
most remote from pumps )
Each case shall include calculation for both full network and single impairment network options;
Calculations shall be performed fully in compliance with NFPA 15 procedures assuming Hazen &
Williams formula C Factor = 135 for GRP piping.
Computer modelling shall include all facilities of the Fire water System ( storage tank, pumps,
network, users ) and shall extent up to the following types of users:
Fire monitors
Deluge systems
Foam systemsOther streams shall be assumed delivered from nodes located around the subject Fire Zone.
-
8/17/2019 Active Fire Fighting, 4&5
40/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 40 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
15.5 DESIGN OF DELUGE WATER SPRAY SYSTEM
The following are included within the scope of “Deluge Water Spray” :
Manual systems for water application to the shell of oil storage tanks
Auto/manual system for water application to vital appurtenances on LPG storage tanks
Auto/manual systems for water application to process equipment
15.5.1 Water Spray System for Oil storage tanks
The Fire Water System shall be designed on the following general criteria :
Any system can be divided in two sections, whenever applicable, in order to minimise water
demand for exposure protection.
Any system/section shall be fed by a riser/ header line supply line connected to one only
branch of the fire water network.
Any system/section shall be operated manually only by means of a dedicated block valve
located outside the bound at not less than 30 m far from tank shell.
Minimum water rate application as indicated in section 11.
Spray nozzles shall be flat jet type, Listed or Approved by recognized international Institute;
they shall be arranged in a single row, equally spaced, on top of the tank shell; spacing shall
allow for discharge jet pattern overlapping.
15.5.2 Water spray systems for LPG storage tanks
The Fire Water System shall be designed on the following general criteria :
Any system can be divided in sections, whenever allowed by radiation range , in order to
minimise water demand for exposure protection.
Vital appurtenances shall include at least : inlet/outlet nozzles, safety valves, product piping,
steel structures and parts of the roof involved in the heat radiation range.
Any system/section shall be fed by a riser/ header line supply line connected to one only
branch of the fire water network.
Any system/section shall be operated manually only by means of a dedicated block valve
located outside the bound at not less than 30 m far from tank shell.
Minimum water rate application as indicated in section 11.
Spray nozzles shall be full cone Protectospray D3 type or equivalent , Listed or Approved by
recognized international Institute; they shall be arranged in over the protected equipment to
guarantee complete coverage of exposures.
-
8/17/2019 Active Fire Fighting, 4&5
41/57
-
8/17/2019 Active Fire Fighting, 4&5
42/57
-
8/17/2019 Active Fire Fighting, 4&5
43/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 43 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
15.6 FIRE TRUCKS
Fire-fighting vehicles shall be designed for industrial purposes and shall be in accordance with
local authority regulations.
15.6.1 Multi-service Fire Truck (Water/Foam/Dry Chemical)
Chassis
The Truck chassis shall be Mercedes model ; standard commercial type, commonly available and
serviceable in the country of destination.
The Fire Truck shall be open construction type to assist visual inspection, maintenance and repair;
all fire-fighting equipment and facilities shall be properly located for easy access and operation.
The angle of approach and departure shall meet NFPA 1901 requirements and be 15° or more.
The chassis shall also include the following facilities :
an adequate cooling system of sufficient capacity to prevent overheating during stationary use
in tropical areas in conjunction with prolonged fire-fighting under full operational conditions of
both water and foam pumps.
A Power Take-Off transmission for the water booster pump, which shall be electrically or
pneumatically engaged from both the cabin and the rear Operating Panel.
The PTO engagement shall be on stopped truck only.
An Exhaust pipe with approved spark arrestor
An automatic over-speed protection to shut down the engine in the event of intake of
flammable gases.
A driver cab having seats for three persons and shall be equipped with air conditioning and
mobile radio.
Lighting and siren facilities including at least: one long range search light, twin reversing lights
at the rear, floodlights, revolving beacons, fog lamps and a two tone siren.
An upper platform for operation of the monitors
Water / Foam System
The water / foam system shall allow for the following operation :
Water/foam discharge with direct supply from hydrants ( by-passing the water pump )
Water/foam discharge with supply from the water pumps ( direct suction from pit or from
hydrants)
-
8/17/2019 Active Fire Fighting, 4&5
44/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 44 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
Foam Concentrate proportioning and injection in each individual discharge connection.
Foam concentrate delivery under pressure
Water / foam delivery by one manually operate monitor Water / foam delivery by two hose reels ( one at each side )
Water / foam delivery by 8 valved hose connections ( four at each side )
Water / Foam system main characteristics shall be as follow :
The water pump shall be of the centrifugal type, rated for 6000 lit/min capacity at 10 bar g
minimum discharge pressure; the pump shall be driven by PTO and shall be able to take direct
suction from pits
The Foam concentrate pumps shall be a positive displacement type, driven by other powersource than PTO; the pump shall be rated to provide adequate supply for 6000 lit discharge
capacity at variable concentration up to 6%.
The foam concentrate tank shall be non metallic type and shall have 4000 lit capacity
The water tank shall be non metallic type and shall have 2000 lit capacity
All piping shall be AISI 316 minimum and be designed for 16 bar g pressure (as minimum )
The water / foam monitor shall be a twin gun type, arranged on top of the truck, manually
operable at the monitor itself.
The monitor shall be rated for 2000 lit/min at 10 barg supply pressure and be fitted with
adjustable foam baffle The side hose reel shall have 25 m of 1” rubber hose and be fitted with interchangeable
nozzles for water or foam service.
Dry Chemical System
The Dry Chemical Extinguishing system shall allow for the following :
Dry powder discharge by two hose reel ( one per side )
Dry powder discharge by manually operated monitor
The Dry Chemical system characteristics shall be as follow :
The storage vessel shall be designed for 16 barg design pressure ( minimum )
Nitrogen bottle number and capacity shall be sufficient to empty the storage tank and to flush
all piping and to guarantee that, during operation the pressure shall not be less than 14 barg.
The cylinders contents shall have a reserve of 30% to deal with possible small leakages.
-
8/17/2019 Active Fire Fighting, 4&5
45/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 45 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
The hose reels shall be fitted with 30 m 1” rubber hose and trigger nozzle capable to discharge
2.5 Kg/sec dry chemical powder allowing for 15 m minimum jet throw.
Dry powder monitor shall be manually operated type, arranged on top of the truck. The monitorshall be rated for 20 Kg/sec minimum discharge capacity with a throw between 30 and 50 m.
Ancillary equipment
The fire truck shall be equipped with the ancillary equipment below listed; equipment shall be
stored in suitable enclosures of same truck.
4 water suction hoses ( 4 or 5 inch size )
1 suction strainer 4 suction pressure hoses 2.1/2” size
30 fire hoses 2.1/2” size x 25 m
4 water pistol grip rated for 400 lit/min
4 air foam making branch-pipe rated for 400 lit/min
2 collecting breechings 2.1/2” size
4 dividing breechings
6 fire extinguishers – dry chemical type 12 Kg charge – internal cartridge operated
2 fire extinguishers – CO2 – 6 Kg charge
2 hand portable water / foam monitors
Extinguishing agent
The truck shall include the first charge of extinguishing agent as below indicated :
4000 lit foam concentrate – synthetic type – suitable for low & medium expansion – rated for
3% proportioning
1000 Kg dry chemical powder – potassium bicarbonate based – compatible for use with foam
-
8/17/2019 Active Fire Fighting, 4&5
46/57
-
8/17/2019 Active Fire Fighting, 4&5
47/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 47 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
16. ATTACHMENTS
16.1 FIRE WATER DEMAND SUMMARY
16.2 FIRE WATER SYSTEM SUMMARY
16.3 SPRAY DELUGE SUMMARY
16.4 FIRE PROTECTION EQUIPMENT SUMMARY
-
8/17/2019 Active Fire Fighting, 4&5
48/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 48 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
16.1 FIRE WATER DEMAND CALCULATION SUMMARY
16.1.1 SUMMARY FOR ISBL – (LOWER SECTION)Fire Zone Zone Water Demand Remarks
Label Description m3/h
01 UNIT 100-1 1188
02 UNIT 100-2 1188
07 UNIT 102-1 / 2 / 3 / 4 / 5 / 6 180
08 UNIT 100-1 / 103-1 946
09 UNIT 100-2 / 103-2 946
15 UNIT 110 576
18 UNIT 113-1 / 114-1 / 115-1 935
19 UNIT 113-2 / 114-2 / 115-2 935
20 UNIT 120 / 121 / 123 / 124 / 130 / 131 180
21 UNIT 140 / 142 180
22 UNIT 140 / 141 / 142 794
23 UNIT 143 467
DESIGN WATER DEMAND 1188
16.1.2 SUMMARY FOR ISBL – (UPPER SECTION)
Fire Zone Zone Water Demand Remarks
Label Description m3/h
03 UNIT 101-1 / 104-1 / 105-1 662
04 UNIT 101-2 / 104-2 / 105-2 662
05 UNIT 101-3 / 104-3 / 105-3 662
06 UNIT 101-4 / 104-4 / 105-4 66210 UNIT 106-1 / 2 / 3 / 4 / 5 / 6 293
11 UNIT 107-1 / 116-1 1005
12 UNIT 107-2 / 116-2 1005
13 UNIT 108-1 / 108-2 180
14 UNIT 108-1 / 108-2 / 144 180
16 UNIT 111-1 / 111-2 / 111-3 477
17 UNIT 111-4 / 111-5 / 111-6 477
25 UNIT 131 / 145 / 146 300
27 UNIT 147 / 148 868
DESIGN WATER DEMAND 1005
16.1.3 SUMMARY FOR OSBL
Fire Zone Zone Water Demand Remarks
Label Description m3/h
24 UNIT 143 616
DESIGN WATER DEMAND 616
NOTE) 1. For the detail fire water demand evaluation, refer to “FIRE WATER DEMAND
CALCULATION NOTE (Doc.N. NC 2017 999 1900 002)”
-
8/17/2019 Active Fire Fighting, 4&5
49/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 49 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
16.2 FIRE WATER SYSTEM MAIN FACILITIES
FIRE WATER SYSTEM FACILITIES Design Capacity Design Pressure
Label Description m3/h - m3 bar g
130-T-101 Fire Water Storage Tank (ISBL) 13,940 m3
130-T-102 Fire Water Storage Tank (OSBL) 5,900 m3
130-P-101 A/B Electric Motor Driven Fire Water Pumps (ISBL-Lower Section) 30 m3 /h 10 bar g
130-P-102 A Electric Motor Driven Fire Water Pump (ISBL-Lower Section) 800 m3 /h 10 bar g
130-P-102 B/C Diesel Engine Driven Fire Water Pumps (ISBL-Lower Section) 800 m3 /h 10 bar g
130-P-103 A/B Electric Motor Driven Fire Water Pumps (ISBL-Upper Section) 30 m3 /h 13 bar g
130-P-104 A Electric Motor Driven Fire Water Pump (ISBL-Upper Section) 800 m3 /h 13 bar g
130-P-104 B/C Diesel Engine Driven Fire Water Pumps (ISBL-Upper Section) 800 m3 /h 13 bar g
130-P-105 A/B Electric Motor Driven Fire Water Pumps (OSBL) 30 m3 /h 9.5 bar g
130-P-106 A Electric Motor Driven Fire Water Pump (OSBL) 500 m3 /h 9.7 bar g
130-P-106 B/C Diesel Engine Driven Fire Water Pumps (OSBL) 500 m3 /h 9.7 bar g
130-PCV-0006 Min. Flow Control Valve - main fire pump (ISBL-Lower Section)
130-PCV-0007 Min. Flow Control Valve – jockey fire pump (ISBL-Lower Section)
130-PCV-0026 Min. Flow Control Valve - main fire pump (ISBL-Upper Section)
130-PCV-0027 Min. Flow Control Valve – jockey fire pump (ISBL-Upper Section)
130-PCV-0046 Min. Flow Control Valve - main fire pump (OSBL)
130-PCV-0047 Min. Flow Control Valve – jockey fire pump (OSBL)
130-PSV-0101 Safety Valves - design pressure control (130-P-102C)
130-PSV-0102 Safety Valves - design pressure control (130-P-102B)
130-PSV-0103 Safety Valves - design pressure control (130-P-104C)
130-PSV-0104 Safety Valves - design pressure control (130-P-104B)
130-PSV-0105 Safety Valves - design pressure control (130-P-106C)
130-PSV-0106 Safety Valves - design pressure control (130-P-106B)
-
8/17/2019 Active Fire Fighting, 4&5
50/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 50 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
16.3 EQUIPMENT COVERED BY WATER SPRAY DELUGE
SYSTEM GROUPING RISK EQUIPMENT REMARKS
Deluge Valve No. Label DescriptionDV-0101~0107 100-X-101 SLUG CATCHER
DV-0201~0207 100-X-201 SLUG CATCHER
DV-0208 100-L-102/202 RAW GAS SCRAPER TRAP
DV-0301 105-C-102 DEETHANIZER
105-D-102 DEETHANIZER REFLUX DRUM
105-E-104 DEETHANIZER REBOILER
105-E-105 DEETHANIZER CONDENSER
105-P-102 A/B DEETHANIZER REFLUX PUMPS
DV-0302 105-C-101 DEMETHANIZER
105-D-101 FEED FLASH K.O. DRUM
105-K-101 TREATED GAS COMPRESSOR
105-P-101 A/B DEETHANIZER TRANSFER PUMPS
DV-0303 104-K-101 A/B DRIERS REGENERATION COMPRESSORS
DV-0304 104-D-101 DRIERS INLET SEPARATORS
104-E-102 WET GAS CHILLER
DV-0305 101-C-101 AMINE ABSORBER
101-D-101 FEED-GAS K.O.DRUM
101-D-102 TREATED GAS K.O. DRUM
101-F-101 FEED GAS FILTER-COALESCER
DV-0401 105-C-202 DEETHANIZER
105-D-202 DEETHANIZER REFLUX DRUM
105-E-204 DEETHANIZER REBOILER
105-E-205 DEETHANIZER CONDENSER
105-P-202 A/B DEETHANIZER REFLUX PUMPS
DV-0402 105-C-201 DEMETHANIZER
105-D-201 FEED FLASH K.O. DRUM
105-K-201 TREATED GAS COMPRESSOR
105-P-201 A/B DEETHANIZER TRANSFER PUMPS
DV-0403 104-K-201 A/B DRIERS REGENERATION COMPRESSORS
DV-0404 104-D-201 DRIERS INLET SEPARATORS
104-E-202 WET GAS CHILLER
DV-0405 101-C-201 AMINE ABSORBER
101-D-201 FEED-GAS K.O.DRUM
101-D-202 TREATED GAS K.O. DRUM
101-F-201 FEED GAS FILTER-COALESCER
DV-0501 105-C-302 DEETHANIZER
105-D-302 DEETHANIZER REFLUX DRUM
105-E-304 DEETHANIZER REBOILER
105-E-305 DEETHANIZER CONDENSER
105-P-302 A/B DEETHANIZER REFLUX PUMPS
-
8/17/2019 Active Fire Fighting, 4&5
51/57
-
8/17/2019 Active Fire Fighting, 4&5
52/57
-
8/17/2019 Active Fire Fighting, 4&5
53/57
IRAN – South Pars Gas Field – Phases 4 & 5
Doc. N. RP 2017 999 1900 002 Rev. 6
Page 53 of 57
This document is the property of N.I.O.C.. Any unauthorised attempt to reproduce it, in any form, is strictly prohibited.
(Continued)
SYSTEM GROUPING RISK EQUIPMENT REMARKS
Deluge Valve No. Label DescriptionDV-1202 107-C-202 DEBUTANIZER
107-D-202 DEBUTANIZER REFLUX DRUM
107-E-202 DEBUTANIZER REBOILER
107-P-202 A/B DEBUTANIZER REFLUX PUMPS
107-P-203 A/B BUTANE FEED PUMPS
107-P-205 A/B CONDENSATE CIRCULATION PUMPS
DV-1203 116-K-201 A/B ETHANE REGENERATION GAS COMPRESSOR
DV-1204 116-D-212 TREATED GAS K.O. DRUM
116-E-212 REBOILER
DV-1501 110-D-103 DEGASSING DRUM
110-E-101 A/B CONDENSATE PREFLASH HEATER
110-E-102 CONDENSATE SECOND HEATER
110-E-103 CONDENSATE FINAL HEATER
110-P-101 STABILIZED CONDENSATE PUMP
DV-1502 110-D-101 PREFLASH DRUM
110-D-102 FLASH DRUM
DV-1601 111-K-101 REFRIGER