ACS - Power Source - HBS Electronic · 0 - 2000 Hz distortion < 0,2% ... ACS - Power Source The...
Transcript of ACS - Power Source - HBS Electronic · 0 - 2000 Hz distortion < 0,2% ... ACS - Power Source The...
HBS Electronic GmbH
ACS - Power SourceACS - Power SourceACS - Power Source
Thanks to the well designed li-near power booster the ACS canfeed the connected load constant-ly and with high reliability. For thisthe operator will face a wide ope-ration spectrum in the areas ofcommercial nets, supply nets,and aircraft board supply begin-ning from the first laboratory testsup to the mass production.
The digital DDS signal generationof the ACS Power Source provi-des a very clean and pure sinewave AC voltage with a distortionless than 0.2%.
The AC, DC, AC+DC mode ex-pands the operation possibilitiesin many areas.
Input and measure values aredisplayed on a vacuum fluores-cence display of high intensity.The operation can be simplymade via push buttons and tur-ning knobs.
Using the integrated RS232 Inter-face and the available optional In-terfaces all ACS Power PowerSource settings and measure-ments can be completely control-led with an PC.
With the option ‘sequence’ theoperator can simulate fast transi-ents, voltage drops, voltage rises,etc.
The complete power line simulation
commercial TestingAvionics TestingAC / DC Mode1 and 3-Phase operationlinear PowerboosterPower from 400 - 6000 VA
Voltage range Standard0 - 300 V AC0 - 425 V DCVoltage range HV (Option)0 - 500 V AC0 - 700 V DCVoltage range XHV (Option)0 - 700 V AC0 - 1000 V DC
Frequency range Standard0 - 500 HzFrequency range F1 (Option)0 - 1000 HzFrequency range F2 (Option)0 - 2000 Hz
distortion < 0,2%
MeasurementsVoltage(V), Current(A), Peakcurrent(A),effective Power(W), apparent Power(VA),Powerfaktor, Crestfaktor
Voltage and Current constant-Mode
programmable start up phaseangle
20 programmable Device-States
20 programmable sequences(Option)
RS232 Interfacewith galvanic isolation StandardInterface (Option)with galvanic isolationIEEE488, USB, LAN
external Oscillator Input (Option)with galvanic isolation
3-Phase-Mode (Option)
built in Output-Relais
protection for power- voltage-,current and temperature overload
HBS Electronic2
ACS - Power SourceACS - Power SourceACS - Power Source
programmable sequences (Option)
With the ACS-Power Source you can generate automatic test-command-sets (Sequences). Youcan store 20 Sequences with 50 commands for call back later. The function can be used to ge-nerate voltage dropouts etc. The minimum time-step of on Sequence is 10 ms. To generate andtransfer sequences you can use the PC-program tool(ACS-Control) or remote commands.
generate a linear voltage ramp with the Option‘Sequence’.
generate a voltage dropout on Phase 1 for10ms duration with the Option „Sequence“ ona 3-phase system.
the succession of an sequence for 10ms/100VAC, 10ms/130VAC, 20ms/100VAC on 400 Hzrepeating 2 times.
HBS Electronic 3
ACS - Power SourceACS - Power SourceACS - Power Source
The software tool ACS-Control uses an Soft-Controlpanel for remote control the ACS-Power Source over PC.
available functions:setting values / parametersdisplay measurementsgenerate, transfer, load, save and compu-ting sequences.generate, transfer, load, save and compu-ting easy to use test-command-sets
For the generation of sequences the SoftwareACS-Control gives you an easy to use Sequen-ce-Table.
available functions:generate, load, save sequences to hard disk.transfer sequences to the ACS-Power-Sour-ceload, save and computing sequences in theuser ACS-Power Source RAM.Start and Stop sequences
The Software ACS-Control gives you also anfunction for generation of simple testcom-mand-sets to make settings and measure-ments for testing equipment.
available functions:generate, load, save and computing test-command-sets.measurement comparing for upper and lo-wer-limitsreport test-stepsload, save and print test-reports
Application software (Option)
HBS Electronic4
ACS - Power SourceACS - Power SourceACS - Power Source
SpecificationsTyp ACS-0400-PS ACS-0800-PS ACS-1600-PS
Power Output (VA) 400 / 500** extended for 1 minute
800 / 1000** extended for 1 minute
1600 / 2000** extended for 1 minute
Voltage-RangeStandard
0-300VAC0-425VDC
0-300VAC0-425VDC
0-300VAC0-425VDC
Voltage-Range(Option HV)
0-500VAC0-700VDC
0-500VAC0-700VDC
0-500VAC0-700VDC
Voltage-Range(Option XHV)
0-700VAC0-1000VDC
0-700VAC0-1000VDC
0-700VAC0-1000VDC
Maximum Current r.m.s.(Option HV)(Option XHV)
3A1,8A1,5A
6A3,6A3A
12A7,2A6A
Maximum Current DC(Option HV)(Option XHV)
3A1,8A1,5A
6A3,6A3A
12A7,2A6A
Max. period. peak Current(Option HV)(Option XHV)
8A4,8A4A
20A12A10A
40A24A20A
Creast Factor 2,6 3,3 3,3
Line Regulation 0,1% 0,1% 0,1%
Load Regulationon Nominalpower
0,1% 0,1% 0,1%
Distortionon Nominalpower
0,2% 0,2% 0,2%
Programming AccuracyAC-Voltage
0,1%(10-400Hz)
0,1%(10-400Hz)
0,1%(10-400Hz)
Programming AccuracyDC-Voltage
0,1% 0,1% 0,1%
Programming AccuracyConstantcurrent r.m.s.
0,2%(40-400Hz)
0,2%(40-400Hz)
0,2%(40-400Hz)
Programming AccuracyFrequency
0,1HzOption 0,01Hz
0,1HzOption 0,01Hz
0,1HzOption 0,01Hz
Programming AccuracySwitch On Phase
0,1 degree 0,1 degree 0,1 degree
Frequency StandardFrequency (Option F1)Frequency (Option F2)
500Hz1 kHz2 kHz
500Hz1 kHz2 kHz
500Hz1 kHz2 kHz
External Oscillator InputFrequency StandardFrequency (Option F1)Frequency (Option F2)
20VssDC-500 HzDC-1 kHzDC-2 kHz
20VssDC-500 HzDC-1 kHzDC-2 kHz
20VssDC-500 HzDC-1 kHzDC-2 kHz
Measurement Voltage r.m.s. 0,2%(40-400Hz)
0,2%(40-400Hz)
0,2%(40-400Hz)
Measurement Current r.m.s. 0,2%(40-400Hz)
0,2%(40-400Hz)
0,2%(40-400Hz)
Measurement Current peak 0,8% 0,8% 0,8%
Measurement Real Power 0,2%(40-400Hz)
0,2%(40-400Hz)
0,2%(40-400Hz)
externalOscillator input (Option T)with optical isolation
Option Option Option
Interfacewith optical isolationIEEE488,USB,LAN
Option
RS232 Standard
Option
RS232 Standard
Option
RS232 Standard
chassis 19“ 19“ 3HE, weight 17Kgdeepness 590mm
19“ 3HE, weight 19Kgdeepness 590mm
19“ 6HE, weight 32Kgdeepness 590mm
HBS Electronic 5
ACS - Power SourceACS - Power SourceACS - Power Source
SpecificationsTyp ACS-2200-PS ACS-3000-PS ACS-4600-PS ACS-6000-PS
Power Output (VA) 2200 / 2750** extended for 1 minute
3000 / 3750** extended for 1 minute
4600 / 5750** extended for 1 minute
6000 / 6000** extended for 1 minute
Voltage-RangeStandard
0-300VAC0-425VDC
0-300VAC0-425VDC
0-300VAC0-425VDC
0-300VAC0-425VDC
Voltage-Range(Option HV)
0-500VAC0-700VDC
0-500VAC0-700VDC
0-500VAC0-700VDC
0-500VAC0-700VDC
Voltage-Range(Option XHV)
0-700VAC0-1000VDC
0-700VAC0-1000VDC
0-700VAC0-1000VDC
0-700VAC0-1000VDC
Maximum Current r.m.s.(Option HV)(Option XHV)
16A9,6A8A
20A12A10A
30A18A15A
40A24A20A
Maximum Current DC(Option HV)(Option XHV)
16A9,6A8A
20A12A10A
30A18A15A
40A24A20A
Max. period. peak Current(Option HV)(Option XHV)
60A36A30A
80A48A40A
100A60A50A
120A72A60A
Creast Factor 3,75 4 4 3
Line Regulation 0,1% 0,1% 0,1% 0,1%
Load Regulationon Nominalpower
0,1% 0,1% 0,1% 0,1%
Distortionon Nominalpower
0,2% 0,2% 0,2% 0,2%
Programming AccuracyAC-Voltage
0,1%(10-400Hz)
0,1%(10-400Hz)
0,1%(10-400Hz)
0,1%(10-400Hz)
Programming AccuracyDC-Voltage
0,1% 0,1% 0,1% 0,1%
Programming AccuracyConstantcurrent r.m.s.
0,2%(40-400Hz)
0,2%(40-400Hz)
0,2%(40-400Hz)
0,2%(40-400Hz)
Programming AccuracyFrequency
0,1HzOption 0,01Hz
0,1HzOption 0,01Hz
0,1HzOption 0,01Hz
0,1HzOption 0,01Hz
Programming AccuracySwitch On Phase
0,1 degree 0,1 degree 0,1 degree 0,1 degree
Frequency StandardFrequency (Option F1)Frequency (Option F2)
500Hz1 kHz2 kHz
500Hz1 kHz2 kHz
500Hz1 kHz2 kHz
500Hz1 kHz2 kHz
External Oscillator InputFrequency StandardFrequency (Option F1)Frequency (Option F2)
20VssDC-500 HzDC-1 kHzDC-2 kHz
20VssDC-500 HzDC-1 kHzDC-2 kHz
20VssDC-500 HzDC-1 kHzDC-2 kHz
20VssDC-500 HzDC-1 kHzDC-2 kHz
Measurement Voltage r.m.s. 0,2%(40-400Hz)
0,2%(40-400Hz)
0,2%(40-400Hz)´
0,2%(40-400Hz)
Measurement Current r.m.s. 0,2%(40-400Hz)
0,2%(40-400Hz)
0,2%(40-400Hz)
0,2%(40-400Hz)
Measurement Current peak 0,8% 0,8% 0,8% 0,8%
Measurement Real Power 0,2%(40-400Hz)
0,2%(40-400Hz)
0,2%(40-400Hz)
0,2%(40-400Hz)
externalOscillator Input (Option T)with optical isolation
Option Option Option Option
Interfacewith optical isolationIEEE488, USB, LAN
Option
RS232 Standard
Option
RS232 Standard
Option
RS232 Standard
Option
RS232 Standard
chassis 19“ 19“ 6HE, weight 34Kgdeepness 590mm
19“ 6HE, weight 38Kgdeepness 590mm
19“ 12HE, weight 64Kgdeepness 590mm
19“ 12HE, weight 64Kgdeepness 590mm
HBS Electronic6
ACS - Power SourceACS - Power SourceACS - Power Source
AF-
0314
-03.
20
Order Information
TypesACS-0400-PS Power 400 / 500* VAACS-0800-PS Power 800 / 1000* VAACS-1600-PS Power 1600 / 2000* VAACS-2200-PS Power 2200 / 2750* VAACS-3000-PS Power 3000 / 3750* VAACS-4600-PS Power 4600 / 5750* VAACS-6000-PS Power 6000 / 6000* VA
* extended for 1 minute
OptionsHV extended voltage range 1
0 - 500 V AC / 0 - 700 V DCXHV extended voltage range 2
0 - 700 V AC / 0 - 1000 V DCF1 extended frequency range 1
0 - 1000 HzF2 extended frequency range 2
0 - 2000 HzIEEE488 IEEE488 InterfaceUSB USB InterfaceLAN LAN and USB InterfaceSEQ programmable SequencesT external Oscillator Input
with galvanic isolation3P 3 Phase-Mode
HBS Electronic GmbHHBS Electronic GmbHHBS Electronic GmbHMannheimer Straße 89-91Mannheimer Straße 89-91Mannheimer Straße 89-91
68782 Bruehl68782 Bruehl68782 BruehlTel. 06202 / 97 87 46-0Fax 06202 / 97 87 46-6
email [email protected]
Copyright © HBS Electronic GmbH. All rights reserved. changes without notice.