  • Power Transducers

    AC&M

    TYPE MODEL INPUT OUTPUT AUX POWER TDV A. 0~150VAC

    B. 0~300VAC C. 0~600VAC

    AC Voltage TDV3 TDA

    AC Current TDA3

    A. 0~1A AC B. 0~5A AC C. 0~10A AC

    Watt TDW

    Var TDQ

    A. 1 2W B. 3 3W C. 3 4W D. Other

    A. 0~10mA DC B. 0~20mA DC C. 4~20mA DC D. 0~5V DC E. 1~5V DC F. 0~10V DC Y. Other

    Watt/Var TDWQ Power Factor TDPF Watthour TDWH

    A. 110V B. 220V Y. Other

    A. 110/220V AC B. 24V DC C. 110V DC D. 125V DC E. Self Power

    A. 1A B. 5A Varhour TDQH

    Watt/Watthour TDWWH

    A. 1Pulse/1WH B.10Pulse/1WH

    A. 50Hz B. 60Hz Var/Varhour TDQQH

    Same as V, A, W, Var, PF

    30~600V AC 50 or 60 Hz Frequency TDF

  • Specifications Input Burden : 0.1VA/60Hz at 150V AC; Self-Power Mode 2VA at

    150V AC. Input Range : Normal Voltage 110V, Effective Range 85~150V.

    Normal Voltage 220V, Effective Range 160~300V. Normal Current 5A, Effective Range 0~7.5A. Normal Current 1A, Effective Range 0~1.5A.

    Input Over : Normal AC 110V, Voltage Over 500V Continuous. Self-Power Mode 150V AC Maximum. Normal AC 5A. Current Over 15A Continuous; 50A 10 Sec/Hour; 400A 0.5 Sec/Hour.

    Output Load : DC Current Mode : 10VDC Maximum, DC Voltage Mode : 10mA Maximum.

    Output of WH or VarH

    : Open Collect Type, Effective Range 5~30V DC, 5~100mA.

    Output Protection : Without Damage for Output Open or Short Circuit. : 2.6KV AC / Min between Input/Output/Power/Case. Dielectric Strength

    Impulse : 4KV 1.2x50 uS. ANSI C37.90a/1983. DIN IEC 255 4.

    120db, 50/60 Hz. Common Mode Rejection

    :

    Stability 0.2%/Year. : Calibration : SPAN and ZERO 10%. Response Time 400mS, 0 ~ 99%. : Ripple 0.5%rms Max. : Magnetic Effect : DIN - IEE688 0.05% Change 10" Center 100A

    Turn. 100ppm /C From 0~60C Temperature

    Coefficientt :

    Operation Condition

    : 10C ~ + 65C 20 ~ 95% RH Non- Condensed.

    Storage Condition : -40C ~ + 75C 20 ~ 95% RH Non- Condensed. Power Supply : Dual Power 110/220V AC or DC 20%, 50/60Hz. Aux. Power Effect 0.01% / V : Housing material : ABS Plastic, Self-Extinguishing to UL Subject 94

    Class V-O. : DIN Rail or Wall Mounting. Mounting