AccuMind

Instruction manual

BA-AccuMind-en-L-1633.pdf

Page 2: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

AccuMind

SKI GmbH

August 18, 2016

Instruction manual

Designated use

Computer with touch screen for accurate calculation of flows with digital and analog output

using analog and digital inputs.

Page 3: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

Contents

1 General Hints 1

1.1 Icon Explanation . . . . . . . . . . . . . . . . . . . . . . 11.2 Note . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11.3 Qualified Personnel . . . . . . . . . . . . . . . . . . . . 11.4 Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2 Technical Specifications 3

2.1 overview . . . . . . . . . . . . . . . . . . . . . . . . . . . 32.2 galvanical isolation . . . . . . . . . . . . . . . . . . . . . 42.3 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . 52.4 AccuMind R© terminal assignment . . . . . . . . . . . . 62.5 Services and features . . . . . . . . . . . . . . . . . . . 72.6 cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

3 Installation 8

3.1 Electrical connection . . . . . . . . . . . . . . . . . . . . 83.1.1 Power Supply . . . . . . . . . . . . . . . . . . . . 8

3.2 Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . 83.2.1 PT100 RTD . . . . . . . . . . . . . . . . . . . . . 9

4 Operation 10

4.1 Selection of the shown Process Parameters . . . . . . 104.2 Password access . . . . . . . . . . . . . . . . . . . . . . 104.3 Tool symbol button . . . . . . . . . . . . . . . . . . . . 114.4 Bread crumb navigation . . . . . . . . . . . . . . . . . . 11

5 Menu structure 12

5.1 Access control . . . . . . . . . . . . . . . . . . . . . . . 125.2 User menu . . . . . . . . . . . . . . . . . . . . . . . . . 12

5.2.1 Media . . . . . . . . . . . . . . . . . . . . . . . . 135.2.2 Pipe Data . . . . . . . . . . . . . . . . . . . . . . 145.2.3 Design . . . . . . . . . . . . . . . . . . . . . . . . 155.2.4 Sensors . . . . . . . . . . . . . . . . . . . . . . . 165.2.5 Interfaces . . . . . . . . . . . . . . . . . . . . . . 175.2.6 Calibration . . . . . . . . . . . . . . . . . . . . . 185.2.7 Configuration . . . . . . . . . . . . . . . . . . . . 185.2.8 Access . . . . . . . . . . . . . . . . . . . . . . . . 185.2.9 lnformation . . . . . . . . . . . . . . . . . . . . . 19

6 Errors 20

Page 4: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

General Hints

1 General Hints

1.1 Icon Explanation

Attention: Warning of danger (attention: observe documentation!)ISO 3864, No. B.3.1Warning: Beware of dangerous electrical voltageISO3864, No. B.3.6

1.2 Note

For reasons of clarity this manual does not contain detailed informa-tion about all types of products and cannot take into account everyconceivable case of installation, operation or maintenance.Attention: If you require further information or should problemsoccur which are not sufficiently explained in the manual, you canconsult us directly to obtain the necessary information.CAUTIONThis equipment is a Limit Class A once. It can cause radio dis-turbance in residential. On this case costumer has to take careappropriate measure.This equipment should only be installed and operated afterqualified personnel have ensured that suitable power supply(see name plate) will be used and that during normal operationor in case of a defect in the system or in components no haz-ardous situation can occur. Therefore serious injuries and/orconsiderable material damage cannot be ruled out in the eventof improper handling of the device.The perfect and safe operation of this equipment is conditionalupon proper transport, proper storage, installation and assem-bly as well as on careful operation and commissioning.

May we also draw your attention to the fact that the contents of themanual are not part of a previous or existing agreement, approvalor legal relationship or an amendment thereof. All obligations of theS.K.I. GmbH result from the contract of purchase which also containsthe full and solely valid warranty agreement. These contractual war-ranty conditions are neither extended nor restricted by the contentsof the manual.1.3 Qualified Personnel

Attention: Qualified personnel includes persons familiar with theinstallation, assembly, commissioning and operation of the productand who have the appropriate qualifications for their activities suchas:• Training or instruction or authorization to operate and main-tain devices/systems according to the standard of safety tech-nology for electrical installations.

1

Page 5: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

• Training or instruction in the proper care and use of protectiveequipment in accordance with appropriate safety practices.• Training in first aid.

1.4 Warnings

exceeding or falling below the permissible operating temperatureIt must be ensured through appropriate measures, that the permis-sible operating temperature is not exceeded or undershot.Damage: Measuring elements may not enjoy improper mechanicalloads such as occur for example during a fall. There must be nounacceptable higher forces acting on the device.Improper installation of the measuring elements: It must be en-sured by appropriate measures that the individual sensing elementsare properly installed.Corrosion: It must be ensured that themeasuring elements are usedand used for its intended use.Electricity: Warning of electrical voltages. Before making any con-nections in the wiring, the system must be switched off.Other hazards It is important to ensure that the manufacturer’s useregulations are always respected.

2

Page 6: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

Technical Specifications

2 Technical Specifications

2.1 overview

calculation methodMeasured Media:Water, steam IAPWS-97Natural gases AGA-8 (DC92) G1/G2(ISO20765-1, ISO12213-3)SGERG-88 (ISO 12213-2)AGA-NX19 korr. and mod. methodsTechnical gases Ideal gas, real gas correction acc. toRedlich-Kwong-Soave, Peng-Robinsonet.al.Heat transfer fluids Multiple fluids, property values calcu-lated by polynomial approximationOther media Assumption of constant propertiesCompatible sensors and signal types:Primary flow elements ISO 5167, AGA-3Ultrasonic devices AGA-10Volumetric sensors AGA-7Massflow meters AGA-11Resist. Thermometers Pt100Pipes and Ducts:Thermal expansion Calculated according to AGA-3, VDI-2040,ISO 5167power supplyAC power supply 100V - 250V∼ ±10%; 50 - 60Hz ±5%DC power supply (optional) 20 V - 32V= ± 10%Inputsanalog Inputs: 4internal load (main diff.pressure-sensor port) 265Ω, because of FSK-Modem*)

internal load (other ports) 25Ω

resolution 224 stepstransmitter supply 24V (2.5Watt for each channel)percentage error 0,1% or 0,05% of the exchange valuecurrent protection auto re-settable fuseRTD connections: 2connection 2, 3 or 4 wire configurationmeasuring range -200 to +550Cresolution 224 stepsmax. deviation typ. ± 0,005Kfeed current 200µA (4 / 2wire) or 400µA (3wire)counter-/frequencyinput: 2voltage threshold at ≈ 3V; max. 24Vfunction max. 10 kHz; EN1434 Kl. IB, IC, ID, IE*) To communicate with the field instrument, a digital signal is modulatedonto this analogue signal with the FSK procedure (Frequency Shift Keying)which is part of the HART R© standard.

3

Page 7: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

outputsanalog outputs: 2 current loopsrange 0 or 4 - 20mAresolution 216 stepspercentage error 0,15% or 0,10% of full scale valuemax. external load 500ΩOutput ripple <10mV at 500Ω for f<50 kHzswitches 3Out.1 (traditional relais) 250V∼ / 220V=; 6 AOut.2 (normaly open) 48V∼ / 60V=; 0,1 AOut.3 (normaly closed) 48V∼ / 60V=; 0,1 AInterfacesfieldbusses 3Modbus Slave RS485 or RS422 (galv. isolated)Modbus RTUModbus Master RS485 (with remote feeding)Modbus RTUMeter Bus (option) M-Bus (two wire interface)2nd ModBus Slave (option) RS485, RS232 (galv. isol.)2nd ModBus Slave (option) TCP/IP (galv. isol.)Profibus (option) RS485 (galv. isol.)Profinet (option) TCP/IP (galv. isol.)Additional features other field busses available on requestIT-Interfaces 2SD-Card Memory & UpdatesEthernet Webinterface with measuring resultsAttention: Please ensure before powering the device that the supply voltagematches the values mentioned on the nameplate. Furthermore connect externaldevices to the correct terminals in a proper manner (see section 2.4).

2.2 galvanical isolation

powersupp

lyPT100RTD

analogin

analogout

1analogout

2mech.Rel.

Switch(2x)

digitalin(2x)

Modbu

sSlave

.PowerSupply - >5kV >5kV >5kV >5kV >5kV >5kV >5kV >5kVPT100RTD >5kV - >1kV >1kV >1kV >5kV >1kV >1kV >1kVanalog in >5kV >1kV - >1kV >1kV >5kV >1kV >1kV >1kVanalogout 1 >5kV >1kV >1kV - >1kV >5kV >1kV >1kV >1kVanalogout 2 >5kV >1kV >1kV >1kV - >5kV >1kV >1kV >1kVmech.Rel. >5kV >5kV >5kV >5kV >5kV - >5kV >5kV >5kVSwitch(2x) >5kV >1kV >1kV >1kV >1kV >5kV - >1kV >1kVdigital in(2x) >5kV >1kV >1kV >1kV >1kV >5kV >1kV - >1kVModbusSlave >5kV >1kV >1kV >1kV >1kV >5kV >1kV >1kV -ModbusMaster >5kV >1kV - >1kV >1kV >5kV >1kV >1kV >1kV

4

Page 8: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

2.3 Dimensions

housingMaterial: PVC (front) and metal (electronic enclo-sure)panel mount housing Dimensions in mmelectronic enclosure 135 w x 65 h x 118 ddisplay module size 144 w x 83 h x 14 dpanel cut-out 137 w x 70 hProtection (electronic) IP31Protection (display ) IP54

144 mm

83 mm

135 mm

65 mm

Figure 1: housing

5

Page 9: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

2.4 AccuMindR©terminal assignment

12

34

56

11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26

27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42

Figure 2: AccuMind R© rearMain terminal striprow A row B

1stelectronic switch 2

ndelectronic switch11 1st output + 27 2nd output +12 1st output - 28 2st output -

1stswitching input 2

ndswitching input13 1st input + 29 2nd input +14 1st input - 30 2nd input -

1stanalog out 2

ndanalog out15 1st output - 31 2nd output -16 1st output + 32 2nd output +

1stRTD 2

ndRTD17 1- 1st wire 33 2- 1st wire18 1- 2nd wire 34 2- 2nd wire19 1+ 3rd wire 35 2+ 3rd wire20 1+ 4st wire (option*) 36 2+ 4th wire (option*)

1stanalog input 2

ndanalog input21 GND (for aktive transm.) 37 GND (for aktive transm.)22 signal input 38 signal input

1st

dp-transmitter (lowrange when using split-range mode)optional 2nd

dp-transmitter(high range when using split-range mode) or optional2ndT-transmitter23 +24V (f. passive transm.) 39 +24V (f. passive transm.)

3rdanalog input 4

thanalog input24 GND (for aktive transm.) 40 GND (for aktive transm.)25 signal input 41 signal input

p-transmitter 1stT-transmitter26 +24V (f. passive transm.) 42 +24V (f. passive transm.)

*) When wiring the RTD in three-wire mode, this port remains empty. Thishas to be set in the menu system.power supply terminal RJ45 plastic socket1 AC Supp. (L) 1 B; connect to Y for RS4852 AC Supp. (PE) 2 A; connect to X for RS4853 AC Supp. (N) 3 Y4 Relais N.C. 4 5 Vcc (auxiliary power)5 Relais COM (6A / 240V) 6 X6 Relais N.O. 7 8 GNDA DC power supply (24V) is available on request.

Additional connectors• field businterface: module slot• RJ11-socket: ext. display• Network socket: Ethernet RJ45 (equipped with LEDs)

6

Page 10: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

• Memory: SD-Card2.5 Services and features

display & user interface (separable) displaytechnology 4,3′′ WQVGA color TFT displayoperation capacitive touch operationFunction Display the results and the process stateon color graphic display with interactivemenu systemfunktionInputs Analog and digital inputs for determiningthe required physical input variablesPeripheral power Electrical supply of connected sensorsSignal Processing Investigations of the flow signal and de-termination of the media propertiesCalculated Media Size Density, dynamic viscosity, energy con-tentCalculation of the mass flow and the heatand the amount of energy transportedProcess real-time linearization of differentialpressure transducers ISO5167 andAGA3 at each operating pointcalculations IAPWS-IF97, ISO5167, ISO6976,GOST30319, ISO20765-1, AGA8-DC92Detailed Method (equals ISO 12213-2),AGA8 Gross Method, AGANX19 mod.,AGANX19 corr., SGERG88 (equals ISO12213-3), ASTM54, Material properties ofvarious thermal oils, material propertiesvaried pipeline materialsSD-card Software updates and data loggingSoftwareupdate Anytime via service interfacecommunicationInterfaces Output of the corresponding values viabus interfacesFSK modem Highly accurate measurements by digi-tal access to a variety of field devices viabuilt-in modem (standard). This leadsto very precise results even without splitrange setupsAutomatic zero point calibration of dif-ferential pressure transmitters possible(when using the relevant automatic valveAccuFlo-zero (available on request))MOD-Bus serial field bus for communication with amaster using the industry standard field-bus MODBUSM-Bus (Option) As an alternative to MOD Bus, the devicecan be equipped with an M-Bus module.The M-Bus (meter-bus) is a fieldbus forthe consumption data acquisitionAnybus (Option) Almost unlimited variety of other, avail-able fieldbus interfacesNetzwerk Ethernet-interface (standard)Inter-/Intranet integrated WebserverRemote access and service possibility

2.6 cleaning

The AccuMind R© may only be cleaned with a dry cloth.

7

Page 11: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

Installation

3 Installation

By default the the AccuMind is mounted on a switch panel in a cut-out according to above mentioned dimensions. The Flow Computeris held by the mounting clips in the cut-out. Please make sure thatthe seals are pressed tightly against the front panel.3.1 Electrical connection

3.1.1 Power SupplyPower between 100V to 250V AC or 20V to 32V DC has to be con-nected to the small terminal strip according to figure 3.Please refer to the type code which power supply (AC or DC) has tobe used.

123456

LPEN

(a) AC device: Connection to 100V -250V AC.

123456

-+

(b) DC device: Connection to 20V -32V DC.Figure 3: Power Supply Connection for AccuMind R© .

In case of a power failure the meter readings and parameterizationare being saved to avoid loss of data. The AccuMind is equipped witha real time clock which is being powered by an internal battery. Thisbattery can be replaced in the factory.3.2 Transmitter

Passive transmitters: Powered from AccuMind R©Passive transmitters are being powered by the AccuMind. The con-nection is shown in Figure 3.2. Digital signal transfer according toHART R© is possible with this connection sheme on the 1st dp-channel.The 0-20mA Range is not usefull with this connection sheme. Pleaseuse the 4-20mA range.

Aktive transmitters with external power supplyAktive transmitters are being powered by the AccuMind or by exter-nal power supply. The connection is shown in Figure 3.2 for externalpower supply. If the AccuMind R© should power the transmitter anadditional wire has to be used for the +24V connection (not shownin figure). Digital signal transfer according to HART R© is possible withthis connection sheme on the 1st dp-channel.

8

Page 12: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26

27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42

Q

I=

P

I=

T

I= -+ +

+--

Figure 4: using passive transmitters

This connection sheme supports 0-20mA and 4-20mA configura-tion, too.

11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26

27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42

Q

I=

P

I=

T

I= -+ +

+--

+ + +---

Figure 5: using aktive transmitters with external power supply

3.2.1 PT100 RTDPT100 RTD’s are connected according to chapter 2.4.

9

Page 13: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

Operation

4 Operation

The AccuMind R© is operated via the touch screen display. The Ac-cuMind offers five different screen modes which can be switchedbetween with the arrow buttons in the bottom line (see Figure 4).Different screen modes are available with one up to six fields to dis-play measurement readings and calculation results.

Figure 6: Basic display with process parameters. The display can bechanged with the arrow buttons. Touching a field will open a menuto select different process parameters and may trigger a passwordrequest! (→ 4.2))4.1 Selection of the shown Process Parameters

To switch between displayed process parameter the correspondingfield on the display has to be touched. The AccuMind will then askfor a passwor(→ 4.2).The available process parameters are depending on the entered pass-word and the corresponding access level.A variation of process parameters are selectable. Depending on thenumber of parameters the selection has to be divided into severaldisplays with nine parameters each. To switch between displaysplease use the arrow buttons.Once a parameter has been selected the appropriate measurementunit has to be selected. If the variable has been selected before theaccording unit is stored and can be changed later through the menu(configuration→ units→ selection of units (5.2.7)). Finally the num-ber of decimal digits can be selected. If the Enter button is pressedor 0 is entered the process parameter will be shown as a whole num-ber.

4.2 Password access

The AccuMind R© is protected against unauthorized accress througha hierarchic password system. Profound changes in the system canonly be executed by authorized personnel. Simple changes (e.g.change of displayed process parameter) can be executed by the stan-dard user.

10

Page 14: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

The password menu is shown in figure 4.2. When a valid password isbeing entered and confirmed through touching the ’ENTER’ button asub-menu will open which is associated to the user rights connectedto the entered password. ’DEL’ will delete wrong input and ’CANCEL’will leave the password menu.

Figure 7: Password input menu.The following passwords are being stored in factory default:Level Factory Default User Setting1. Operating staff 56982. User 89563. Service 89144. Parameterization 64575. Lab 89726. OEM7. SKI intern8. SKI Development9. MasterThese passwords can be changed through themenu via→ Access→Change PWD. For amore detailed explanation please refer to section5.2.8).

4.3 Tool symbol button

Touching the tool symbol buttonwill open amenuwhich allows chang-ing all settings. This menu is password protected. All settings aredescribed in the next menu point under → 5. For the simple flowmeasurement operation this button is not required.4.4 Bread crumb navigation

The bread crumb navigation allows simple and fast solving of prob-lems. If a problem occurs which can be solved through a differentsetting in the menu system amessage is shown in the top row of thedisplay. Touching this message will redirect the user to the appropri-ate sub menu and allows to change the user the setting.The company symbol in the upper right corner serves as an ’EXIT ’button for fast navigation and will change the display to the last usedbasic operational display.

11

Page 15: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

Menu structure

5 Menu structure

The tool symbol icon opens the menu and may trigger a passwordrequest.5.1 Access control

The system is divided into separate access layers which can be ac-cess through different passwort (see section→ 4.2).5.2 User menu

The main menu includes the following points:Media → 5.2.1Setting of the fluid media.This menu point requires the Parameterization -password (→ 4.2).Pipe → 5.2.2Setting of the pipe properties.This menu point requires the Parameterization -Password (→ 4.2).

Design → 5.2.3Setting of design parameters, constants and individual coefficientsof the process.This menu point requires the Parameterization -Password (→ 4.2).

Sensors → 5.2.4Setting of the sensors: Paramterization of analog and digital inputsfor the measurement of process paramters.This menu point requires the Parameterization -Password (→ 4.2).

Interfaces → 5.2.5Setting of the analog and digital interfaces to high level control sys-tems and to sensors connected via field bus.This menu point requires the Parameterization -Password (→ 4.2).

Calibration → 5.2.6Calibration settings for all analog and digital in- and outputs of theAccuMind. This menu point requires the Lab -Password (→ 4.2).

Configuration → 5.2.7This menu points allows to save all settings and to change settingsfor use and display of the AccuMind. This menu point requires theParameterization -Password(→ 4.2).

12

Page 16: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

Access → 5.2.8Enables access through different password levels and the change ofpasswords.This menu point requires Operating staff Password (→ 4.2).

Information → 5.2.9Shows hardware and software version of the AccuMind and the se-rial number. Shows an overview of all unlocked functions.This menu point requires the User Password (→ 4.2).Every time the user enters a physical quantity initially a query inwhich physical unit the user will want to enter its value is done. TheAccuMind R© calculates internally with SI - units and transferred allthe values automatically in this system. This can lead to smal devia-tions if displaying the entered value again.

5.2.1 MediaSteam Calculation of transferred heat or flow of steam.The following kinds of steam are selectable:• Superheated steam: Entering the percentage wet superheatedsteam content is required.• Saturated steam (p): Calculation of saturated steam1 proper-ties based on absolute pressure signal.• Saturated steam (T): Calculation of saturated steam propertiesbased on temperature2 signal

Water Calculation of transferred heat or flow of water.Oil Calculation of transferred heat of oil as heat transfer medium.The following oils are selectable:• Shell Thermia B• Therminol 66

Gas This menu point is only accessible if the available device in-cludes option ’technical gases’Calculation of volume flow or energy of a gas. The following gasesare selectable:• Air• Nitrogen• Flue Gas• Bio Gas• Custom Gas

Air and nitrogen are factory preset technical gases. Other technicalgases can be configured through the menu ’Custom Gas’.• Relative humidity φ

1 Requieres absolute pressure sensor. Calculation with fixed value of absolute pres-sure is only recommended for testing purposes→ 5.2.42 Requieres temperature sensor. Calculation with fixed value of temperature is onlyrecommended for testing purposes→ 5.2.4

13

Page 17: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

• N2

• O2

• CO2

After input of every component the total sum of all parts is shown.The individual flue gas composition can be stored after successfulconfiguration with a total of 100%. The relative humidity φ is not be-ing considered for calculation of the volume flow and can be selectedfreely.Bio gas can be configured from the following components:• Relative humidity φ• N2

• NH3

• O2

• CO2

• CH4

After input of every component the total sum of all parts is shown.The individual bio gas composition can be stored after successfulconfiguration with a total of 100%. The relative humidity φ is not be-ing considered for calculation of the volume flow and can be selectedfreely.Custom Gas can be configured from the following components: Rel-ative Humidity φ, air,N2, NO2, H2S, NH3, H2, O2, SO2, CO2, CO, HCL, C3H6, CH4, C2H2, C2H4,C2H6, C3H8, C4H8, ISO C4H10, nC4H10, Ar, HeUnder the point Options a gas calculation algorithm (’Peng Robin-son’, ’Redlich Kwong’ or ’Redlich Kwong Soave’) can be selected ascalculation method instead of ’ideal gas calculation’.Natural Gas This menu point is only accessible if the available de-vice includes option ’natural gases - NG’SGERG-88 Natural Gas If ’Selection’ → ’Custom Gas’ was selectedthe following gas components are available for selection: CO2, H2,d und Hs. Alternatively the test gases 1 to 6 according to SGERG-88are available.NX-19 Natural Gas If ’Selection’ → ’Custom Gas’ was selected thefollowing gas components are available for selection: CO2, H2, d undHs. Alternatively the test gases 1 to 6 according to NX-19 are avail-able.AGA-8 Natural GasWhen selecting ’AGA-8’ either ’detailed’ or ’gross’calculation method can be selected. Further information can befound under https://www.aga.org/.

5.2.2 Pipe DataThe pipe data menu includes the following fields:Shape Round or square shape of pipe.

14

Page 18: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

Material The following pipe materials are available:• Carbon Steel• Stainless Steel• Hastelloy C

Other pipe materials can be entered according to the standard viathe submenu ’Standard material’.Pipe material information according to standard ’VDI2040’ or ’AGA 3’:• VDI 2040

– Steel group I, II, III, IV, V or VI– Bronze– Copper– Red brass– Brass– Nickel– Hastelloy C

• AGA 3– Carbon Steel– Stainless Steel– Monel

’Not considered’ will delete the entered material and perform theflow without consideration of material.5.2.3 Design

This menu allows to adapt the AccuMinds’ calculation methods tothe special requirements of the particular flow measurement. Cali-bration results can be stored here.The design menu offers the following parameters:Measurement factor When entering a globalmeasurement factor6= 1 the entire flow measurement results will be multiplied by thisfactor.Linearization The linearization affects the results of the flowmea-surement as well. X−Y -value pairs can be entered here and a linearinterpolation will be performed betweenX values. ’Reset’will deleteall value pairs. X-Values are entered as Reynold’s numbers. Y valuesare measurement factors corresponding to each Reynold’s numberand are treated as ’local’measurement factors. The global Measure-ment factors and factors from linearization are both multiplied withthe flow calculation results.Low flow cut-off Entering a low flow cut-of value will set all valuesbelow this treshold to zero. The low flow cut-off value has to beentered as a differential pressure.

15

Page 19: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

5.2.4 SensorsThe AccuMind allows connecting sensors via the 4-20mA connec-tion. Alternatively each sensor can be simulated by entering a fixedvalue for the physical dimension. Flow and temperature sensors of-fer additional possibilities shown in the following table:Durchfluss Druck TemperaturFixed Value Fixed Value Fixed ValueCurrent loop Current loop Current loopSplitrange with RTD connection2nd dp-transmitterDigital value viaHART SignalPulse InputFrequency Counter

SourceFixed value When entering a fixed value this value can be choseninstead of the actual sensor data.Analog input Paramterization of the analog current inputs:• Start Value: Input the lower range value (4mA (standard) or0mA) . The upper value is always 20mA.• Characteristic (only for dp-measurement): Selection if the con-nected differential pressure transmitter is being set to linearor square-root operation mode• Split range: (only for dp-measurement) Allows connection ofa second differential pressure transmitter. The first differen-tial pressure transmitter at input 1 should be calibrated for asmaller measurement band. Switch over will be performed at95% flow of the first transmitter with a hysteresis.• Physical Unit: Selection of physical units of min and max val-ues.• min: Physical value for 4 mA or 0 mA• max: Physical value for 20 mA.

FSK-Modem The signals of the connected transmitters are beingprocessed digitally. No physical values have to be selected.Pulse input For volume flow measurement the selection of a me-chanical impulse generator is possible. The value of Puls/V olumehave to be entered.

FlowSelection if the flow measurement is being performed with a ’pri-mary element’ or a ’volume flow measurement device’. Optionally adampening factor can be entered.Primary element Primary element according to the following stan-dards:• ISO 5167

– Orifice Plate with

16

Page 20: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

∗ Flange taps, D-D/2-taps or corner taps– Nozzle∗ ISA-1932-Nozzle, Long radius nozzle, venturi nozzle

– venturi∗ Cast unprocessed, processed castings, welded

– SDF-Sonde∗ SDF 10, 22, 32, 50, special sizes

• AGA-3A volume flow measurement device can be selected from a list.

PressureThe absolute pressure measurement or a fixed absolute pressurevalue can be selected. This value (actual measurement or fixed) isrequired to calculate density.

TemperatureUp to two temperature sensors can be connected to the AccuMind R©or a fixed temperature value can be selected. In addition to the 3- or4-wire connection the current loop can be used.

Gas Mixture RatioThe gasmixing ratio can be transferred via fixed ratios or via externalsensors. It is planned to achieve this through the Modbus interfaceand / or analog inputs.

5.2.5 InterfacesThe AccuMind R© can send the measurement and calculation valuesto a superior control system.

Analog output Two analog outputs are available and can be con-figured as follows:• Start value: Start of output signal at 4 or 20mA• Function: Selection of the process value to be used• Unit: Selection of physical unit for the min and max values• min value: Selection of value which shall be used for 0 or 4mAstart value• max value: Selection of value which shall be used for 20mAend value

17

Page 21: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

Switching Output Three switch outputs are available:• Relay: Can switch up to 6 Ampere at max. 230Volt.• Normally closed switch: This output is closed when not pow-ered and can be used as an alarm in case of error. The outputwill closed when the AccuMind is not powered.• normally open switch: This output is open when not poweredand can be used to indicate a valid measurement. The contactwill be open when the AccuMind is not powered.

Field Busses Several Field Bus Interfaces are available for externalcommunication and can be configured (e.g. baud rate).5.2.6 Calibration

Input Calibration of all analog input signalsOutput Calibration of all analog output signals.

5.2.7 ConfigurationPhysical Units

Reboot Restart of device with- or without saving of settings.Save

Time & Date Setting of real time clock and current date.Language Setting of operation language. Available: German andEnglish. Other languages can be loaded via update.TAGnumber Day number of themeasuring point is shown in headerrow if no problems are there to be displayed.Reset of totaliziers Resets the totalizer. Requires the ServicePassword→ 4.2.Restore factory settings Reset of all parameterst o factory set-tings. Calibration settings remain untouched.

5.2.8 AccessPassword Access Password access can be used to switch currentuser authorization.Log Out Log out of current user authorization log in to protect de-vice against unauthorized access. Log out will be performed auto-matically after a certain time of inactivitiy.Access counter Counter of successful log in attempts of users ofservice level or higher.Reset Access Counter Reset of access counter.

18

Page 22: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

Change PWD Changing the password of the selected sub-menu ac-cess level.5.2.9 lnformation

Version Current software versionSerial number Device serial number.

19

Page 23: AccuMind - SKI GmbH · AccuMind.ThismenupointrequirestheLab-Password(!4.2). Con1guration!5.2.7 ... Pipematerialinformationaccordingtostandard’VDI2040’or’AGA3’: VDI 2040

Errors

6 Errors

Display remains dark after switching on:• Please check the power supply voltage and compare to the re-quired voltage shown on the type plate.

The touch panel becomes unresponsive:• The touch panel has a noise cancelation mechanism. Pressthe button for a few seconds and move your finger across thebutton.• The touch panel is recalibrated from time to time. Please waita few seconds.• If this does not lead to a solution the device is defective.