ACCOYA ® and the Trimarque Device are registered trademarks owned by Titan Wood Limited, Trading as “Accsys Technologies”, a wholly owned subsidiary of Accsys Technologies PLC. The trademarks ACCOYA ® and the Trimarque Device may not be used or reproduced without written permission from Accsys Technologies. ACCOYA ® wood should always be installed and used in accordance with the written instructions and guidelines of Accsys Technologies and/or its agents (available upon request). Accsys Technologies accepts no liability for any defect, damage or loss that may occur where such written instructions and guidelines are not adhered to. No liability is accepted in relation to any coating, fastener or other product of a third party applied to ACCOYA ® wood. Please refer to [accoya.com/downloads] for further information and full terms and conditions. ACCSYS T E C H N O L O G I E S ACCOYA ® CLADDING ON A TIMBER FRAME Accoya is suitable for standard cladding types, and in general the installer should follow the same recom- mendations for fitting as with traditional wood cladding, requiring no special detailing or tools, and performs best when installed properly on a suitable frame. Accoya wood can be cut, profiled and routered to specified designs without encountering restrictions or issues associated with the instability of traditional wood cladding while maintaining its durability. FASTENERS SUB-FRAME Like all cladding materials, Accoya cladding performs best when installed properly on a suitable frame and in a ventilated façade system - characterised by continu- ous ventilation behind the cladding boards, through ventilation in- and outlets situated at the top and bottom of the façade. This ensures rain water and condensa- tion behind the cladding to be removed and for the insulation to retain its effectiveness. The sub-frame the cladding is fastened to should have a maximum spacing of 600 mm on center and should consist of vertical timber battens of at least 38 x 19 mm when fully supported by a substrate. Horizontal battens and counter battens should be at least 50 x 25 mm. Support battens used with Accoya sould be of a durabi- lity class 1 or 2. In case of a discouloration risk of the cladding boards because of leaching of extractives from the timber sub- frame, apply a barrier between the sub-frame battens and the boards. Timber support battens should not be used above 18 m building height. To ensure a durable and lasting fixation, the boards should be fixed with at least 50 mm clearance to the end of the board (pre-drill holes to 1 mm less than the screw shank diameter or 80% of the nail diameter). The minimum distance to the top and bottom edge of the boards is 15 mm. The recommended point side penetration of nails into the sub-frame is at least 6xd for ring shank or 12xd for smooth nails. If the nail head is larger than twice the shank diameter, assumedly pull-through will not occur, as the pull-through resistance exceeds the withdrawal resistance. Accoya can be face fixed onto the timber sub-frame with ring shank (or other improved) nails or screws (raised or round head). As Accoya is slightly acidic, like most durable woods, it is recommended to use stain- less steel grade 1.4301 (general applications) or grade 1.4401 (for coastal or industrial sites). Stapling is not recommended, nor to drive the nail or screw heads into the wood. T-nails should not be used for external cladding as they offer little resistance to axial withdrawal. Lost head nails should also be avoi- ded as they offer little resistance to pull-through. In case of vertical cladding, best prac- tice is a double sub-frame where hori- zontal support battens are fastened on vertical counter battens. The horizontal battens should be chamfered at the top side, shedding water into the cavity. 4 12mm 68mm 2 x d d Point side penetration ≥ 6xd (ring shank) / 12xd (smooth) If only horizontal support battens are used, additional measures need to be taken to ensure sufficient ventila- tion (500 mm 2 per m horizontal length), e.g. by making cut-outs in the battens or interrupting the battens at re- gular intervals, staggered relative to each other. In this case it is preferable if the horizontal battens are cham- fered on the top edge to shed any water outwards . Water penetration at the end grain of vertical battens should be avoided by applying a suitable sealer. Accoya ® is the world’s leading high technology wood. It is produced from sustainably sourced, fast growing softwood using a non-toxic modi- fication process, resulting in a durable, stable and beautiful material with excellent performance characteristics and providing for a minimum 50 year above ground life. The lowest batten should slant inward at the bottom, creating a drip lip at the in- tersection with the counter battens. UK Accoya Cladding V11.15 these guidelines have been written for pro-fessionals wishing to use Accoya to create beautiful, reliable and highly du-rable end products. Should you require further information, please contact Accsys through www.accoya.com. UK CAVITY COATINGS Coatings are applied to Accoya for largely aesthetic reasons. Please refer to the general guidance given in the brochures provided through accoya.com and the applicable advice from coating manufacturers. The drawing shows the rough principles but are not meant to contain actual products. The system used must be designed to the specific project requirements, in accordance with all applicable building standards and regulations. The strength of the total system - spacing, number and type of fasteners required for the occurring wind load - must always be checked by a licensed engineer. To the best of the knowledge and belief of Accsys Technologies PLC the information contained in this document is in accordance with common building practice and is provided on the basis that Accsys Technologies and/or any of its affiliates, officers, employees or advisers are not liable for any loss or damage whatsoever in respect of the accuracy or completeness of such information or the result of having acted upon it. Innovation in wood

Transcript of ACCOYA CLADDING UK ON A TIMBER FRAMElathams-accoyacladding.co.uk/wp-content/uploads/... · a...

Page 1: ACCOYA CLADDING UK ON A TIMBER FRAMElathams-accoyacladding.co.uk/wp-content/uploads/... · a ventilated façade system ... because of leaching of extractives from the timber sub-

ACCOYA® and the Trimarque Device are registered trademarks owned by Titan Wood Limited, Trading as “Accsys Technologies”, a

wholly owned subsidiary of Accsys Technologies PLC. The trademarks ACCOYA® and the Trimarque Device may not be used or

reproduced without written permission from Accsys Technologies. ACCOYA® wood should always be installed and used in accordance

with the written instructions and guidelines of Accsys Technologies and/or its agents (available upon request). Accsys Technologies accepts no liability for any defect, damage or loss that may occur where such written instructions and guidelines are not adhered to. No liability is accepted in relation to any coating, fastener or other product of a third party applied to ACCOYA

® wood. Please refer to

[accoya.com/downloads] for further information and full terms and conditions.

ACCSYST E C H N O L O G I E S

ACCOYA® CLADDING

ON A TIMBER FRAME

Accoya is suitable for standard cladding types, and in general the installer should follow the same recom-mendations for fitting as with traditional wood cladding, requiring no special detailing or tools, and performs best when installed properly on a suitable frame.

Accoya wood can be cut, profiled and routered to specified designs without encountering restrictions or issues associated with the instability of traditional wood cladding while maintaining its durability.

FASTENERSSUB-FRAME

Like all cladding materials, Accoya cladding performs best when installed properly on a suitable frame and in a ventilated façade system - characterised by continu-ous ventilation behind the cladding boards, through ventilation in- and outlets situated at the top and bottom of the façade. This ensures rain water and condensa-tion behind the cladding to be removed and for the insulation to retain its effectiveness.

The sub-frame the cladding is fastened to should have a maximum spacing of 600 mm on center and should consist of vertical timber battens of at least 38 x 19 mm when fully supported by a substrate. Horizontal battens and counter battens should be at least 50 x 25 mm. Support battens used with Accoya sould be of a durabi-lity class 1 or 2.

In case of a discouloration risk of the cladding boards because of leaching of extractives from the timber sub-frame, apply a barrier between the sub-frame battens and the boards. Timber support battens should not be used above 18 m building height.

To ensure a durable and lasting fixation, the boards should be fixed with at least 50 mm clearance to the end of the board (pre-drill holes to 1 mm less than the screw shank diameter or 80% of the nail diameter). The minimum distance to the top and bottom edge of the boards is 15 mm.

The recommended point side penetration of nails into the sub-frame is at least 6xd for ring shank or 12xd for smooth nails. If the nail head is larger than twice the shank diameter, assumedly pull-through will not occur, as the pull-through resistance exceeds the withdrawal resistance.

Accoya can be face fixed onto the timber sub-frame with ring shank (or other improved) nails or screws (raised or round head). As Accoya is slightly acidic, like most durable woods, it is recommended to use stain-less steel grade 1.4301 (general applications) or grade 1.4401 (for coastal or industrial sites).

Stapling is not recommended, nor to drive the nail or screw heads into the wood. T-nails should not be used for external cladding as they offer little resistance to axial withdrawal. Lost head nails should also be avoi-ded as they offer little resistance to pull-through.

In case of vertical cladding, best prac-tice is a double sub-frame where hori-zontal support battens are fastened on vertical counter battens. The horizontal battens should be chamfered at the top side, shedding water into the cavity.

4

12

mm

68mm

≥ 2

x d

d

Point side penetration ≥ 6xd

(ring shank) / 12xd (smooth)

If only horizontal support battens are used, additional measures need to be taken to ensure sufficient ventila-tion (500 mm

2 per m horizontal length), e.g. by making

cut-outs in the battens or interrupting the battens at re-gular intervals, staggered relative to each other. In this case it is preferable if the horizontal battens are cham-fered on the top edge to shed any water outwards. Water penetration at the end grain of vertical battens should be avoided by applying a suitable sealer.

Accoya® is the world’s leading high technology

wood. It is produced from sustainably sourced, fast growing softwood using a non-toxic modi-fication process, resulting in a durable, stable and beautiful material with excellent performance characteristics and providing for a minimum 50 year above ground life.

The lowest batten should slant inward at the bottom, creating a drip lip at the in-tersection with the counter battens.

UK Accoya Cladding V11.15 − these guidelines have been written for pro-fessionals wishing to use Accoya to create beautiful, reliable and highly du-rable end products. Should you require further information, please contact Accsys through www.accoya.com.

UK

CA

VIT

Y

COATINGS

Coatings are applied to Accoya for largely aesthetic reasons. Please refer to the general guidance given in the brochures provided through accoya.com and the applicable advice from coating manufacturers.

The drawing shows the rough principles but are not meant to contain actual products. The system used must be designed to the specific project requirements, in accordance with all applicable building standards and

regulations. The strength of the total system - spacing, number and type of fasteners required for the occurring wind load - must always be checked by a licensed engineer. To the best of the knowledge and belief of

Accsys Technologies PLC the information contained in this document is in accordance with common building practice and is provided on the basis that Accsys Technologies and/or any of its affiliates, officers,

employees or advisers are not liable for any loss or damage whatsoever in respect of the accuracy or completeness of such information or the result of having acted upon it.

Innovation in wood

Page 2: ACCOYA CLADDING UK ON A TIMBER FRAMElathams-accoyacladding.co.uk/wp-content/uploads/... · a ventilated façade system ... because of leaching of extractives from the timber sub-

ACCOYA® and the Trimarque Device are registered trademarks owned by Titan Wood Limited, Trading as “Accsys Technologies”, a

wholly owned subsidiary of Accsys Technologies PLC. The trademarks ACCOYA® and the Trimarque Device may not be used or

reproduced without written permission from Accsys Technologies. ACCOYA® wood should always be installed and used in accordance

with the written instructions and guidelines of Accsys Technologies and/or its agents (available upon request). Accsys Technologies accepts no liability for any defect, damage or loss that may occur where such written instructions and guidelines are not adhered to. No liability is accepted in relation to any coating, fastener or other product of a third party applied to ACCOYA

® wood. Please refer to

[accoya.com/downloads] for further information and full terms and conditions.

Title

Section Date

Version

08.09.2015

1.0 / HWIScale

Detail

1:2

vert + hor

James Latham profiles

Accoya cladding

ACCSYST E C H N O L O G I E S

14

5m

m

145mm

15m

m

15mm

James Latham LT AC 01

tongue and groove profile

for horizontal cladding

James Latham LT AC 02

tongue and groove profile

for vertical cladding

14

5 / 1

95

mm

15 mm

145 / 195 mm

15

mm

Because of the improved stability of the Accoya wood, the gap needed between the height of the boards is very limited, and can be as little as 1 mm. This permits spacing to be built into the profile rather than use of a spacer on site.

The speed of installing Accoya® cladding boards can be

increased significantly by the crusher bead milled into the James Latham tongue and groove profile.

This bead will insure the necessary spacing when installing the boards without additional measures. If and when the boards move relative to each other, this small triangle of material will be easily pressed together, ‘releasing’ the necessary distance.

When meeting other construction elements and/or between the length of two boards, a free space of 5 - 10 mm should be allowed for.

When this free space is left open, a vermin mesh might

be required at certain joint widths. Please check local

building codes to verify requirements.

The drawing shows the rough principles but are not meant to contain actual products. The system used must be designed to the specific project requirements, in accordance with all applicable building standards and

regulations. The strength of the total system - spacing, number and type of fasteners required for the occurring wind load - must always be checked by a licensed engineer. To the best of the knowledge and belief of

Accsys Technologies PLC the information contained in this document is in accordance with common building practice and is provided on the basis that Accsys Technologies and/or any of its affiliates, officers,

employees or advisers are not liable for any loss or damage whatsoever in respect of the accuracy or completeness of such information or the result of having acted upon it.

Innovation in wood

Page 3: ACCOYA CLADDING UK ON A TIMBER FRAMElathams-accoyacladding.co.uk/wp-content/uploads/... · a ventilated façade system ... because of leaching of extractives from the timber sub-

The drawing shows the rough principles but are not meant to contain actual products. The system used must be designed to the specific project requirements, in accordance with all applicable building standards and

regulations. The strength of the total system - spacing, number and type of fasteners required for the occurring wind load - must always be checked by a licensed engineer. To the best of the knowledge and belief of

Accsys Technologies PLC the information contained in this document is in accordance with common building practice and is provided on the basis that Accsys Technologies and/or any of its affiliates, officers,

employees or advisers are not liable for any loss or damage whatsoever in respect of the accuracy or completeness of such information or the result of having acted upon it.

ACCOYA® and the Trimarque Device are registered trademarks owned by Titan Wood Limited, Trading as “Accsys Technologies”, a

wholly owned subsidiary of Accsys Technologies PLC. The trademarks ACCOYA® and the Trimarque Device may not be used or

reproduced without written permission from Accsys Technologies. ACCOYA® wood should always be installed and used in accordance

with the written instructions and guidelines of Accsys Technologies and/or its agents (available upon request). Accsys Technologies accepts no liability for any defect, damage or loss that may occur where such written instructions and guidelines are not adhered to. No liability is accepted in relation to any coating, fastener or other product of a third party applied to ACCOYA

® wood. Please refer to

[accoya.com/downloads] for further information and full terms and conditions.

Title

Section Date

Version

17.11.2015

2.0 / HWIScale

Detail

1:2

vertical

Base

Horizontal cladding – LT AC 01

ACCSYST E C H N O L O G I E S

8

7mm

4111

4

10

11

9

2

Room lining (such as plaster board).

Wall structure (wooden structural frame filled

with a suitable insulation material of sufficient

thickness to achieve required values).

Water repellent breather membrane - UV

resistant in case of open joints.

Structural sheathing board.

Service void (optional, may also be filled with

insulation material).

14

15

co

ntin

uo

us

ve

ntila

tio

n

129

10

3 Air barrier / vapour control layer.

5

5 Wooden structural frame.

8 Wall and floor structure, details to be de-

signed in line with strength and insulation

requirements.

3

5 –

10

mm

Ring shank or other improved nails:

· grade 1.4301 (general applications) or

grade 1.4401 (coastal or industrial sites)

· Holes pre-drilled:

- 1 mm less than nail Ø

- to 80% of screw shank Ø

Vertical timber battens of at least 38 x 19 mm

of durability class 1 or 2.

It is recommended to position the cladding above the splash

zone, between ground level and a height of 200 to 250 mm.

This will avoid rain water splashing onto the boards, which can

cause staining and reduce the service life of coatings. Applying

a gravel section below the cladding is recommended.

13

13 Preformed corrosion resistant metal flashing.

12

12 Vermin mesh of corrosion resistant metal,

hole width ≤ 4 mm. Void area in line with ven-

tilation requirements.

6

6 Soleplate.

7 DPC.

7

Innovation in wood

4

12

mm

68mm

≥ 2

x d

d

Point side penetration ≥ 6xd

(ring shank) / 12xd (smooth)

14

15

Accoya® LT AC 01 horizontal cladding board,

available from James Latham in 15x145 and

15x195 mm.

35

mm

>1

5 m

m

Page 4: ACCOYA CLADDING UK ON A TIMBER FRAMElathams-accoyacladding.co.uk/wp-content/uploads/... · a ventilated façade system ... because of leaching of extractives from the timber sub-

ACCOYA® and the Trimarque Device are registered trademarks owned by Titan Wood Limited, Trading as “Accsys Technologies”, a

wholly owned subsidiary of Accsys Technologies PLC. The trademarks ACCOYA® and the Trimarque Device may not be used or

reproduced without written permission from Accsys Technologies. ACCOYA® wood should always be installed and used in accordance

with the written instructions and guidelines of Accsys Technologies and/or its agents (available upon request). Accsys Technologies accepts no liability for any defect, damage or loss that may occur where such written instructions and guidelines are not adhered to. No liability is accepted in relation to any coating, fastener or other product of a third party applied to ACCOYA

® wood. Please refer to

[accoya.com/downloads] for further information and full terms and conditions.

ACCSYST E C H N O L O G I E S

4 125

3

913

14

6

75m

m≥2

5m

m / ≤

15

x b

oa

rd th

ickn

.

10

9m

m

Horizontal timber battens of at least 50 x

25 mm, of durability class 1 or 2.

co

ntin

uo

us

ve

ntila

tio

n

11

1

4

2

Room lining (such as plaster board).

Wall structure (wooden structural frame filled

with a suitable insulation material of sufficient

thickness to achieve required values).

Service void (optional, may also be filled with

insulation material).

3 Air barrier / vapour control layer.

6

5

Water repellent breather membrane - UV

resistant in case of open joints.

Structural sheathing board.

7

10

11

9

14

8

13

12

7

Ring shank or improved nails:

· grade 1.4301 (general appli-

cations) or grade 1.4401

(coastal or industrial sites)

· Holes pre-drilled:

- 1 mm less than nail Ø

- to 80% of screw shank Ø

Vermin mesh of corrosion resistant metal,

hole width ≤ 4 mm. Void area in line with

ventilation requirements.

Brick base or cladding.

500 micron polyethylene flashing.

Vertical timber counter battens of dura-

bility class 1 or 2.

Code 4 lead flashing.

5 – 10 mm

Title

Section Date

Version

17.11.2015

2.0 / HWIScale

Detail

1:2

vertical

Brick cladding junction

Vertical cladding – LT AC 02

8

12

4

12

mm

68mm

≥ 2

x d

d

Point side penetration ≥ 6xd

(ring shank) / 12xd (smooth)

The drawing shows the rough principles but are not meant to contain actual products. The system used must be designed to the specific project requirements, in accordance with all applicable building standards and

regulations. The strength of the total system - spacing, number and type of fasteners required for the occurring wind load - must always be checked by a licensed engineer. To the best of the knowledge and belief of

Accsys Technologies PLC the information contained in this document is in accordance with common building practice and is provided on the basis that Accsys Technologies and/or any of its affiliates, officers,

employees or advisers are not liable for any loss or damage whatsoever in respect of the accuracy or completeness of such information or the result of having acted upon it.

Accoya® LT AC 02 vertical

cladding board, available from

James Latham in 15x145 mm

and 15x195 mm.

Innovation in wood

Page 5: ACCOYA CLADDING UK ON A TIMBER FRAMElathams-accoyacladding.co.uk/wp-content/uploads/... · a ventilated façade system ... because of leaching of extractives from the timber sub-

ACCOYA® and the Trimarque Device are registered trademarks owned by Titan Wood Limited, Trading as “Accsys Technologies”, a

wholly owned subsidiary of Accsys Technologies PLC. The trademarks ACCOYA® and the Trimarque Device may not be used or

reproduced without written permission from Accsys Technologies. ACCOYA® wood should always be installed and used in accordance

with the written instructions and guidelines of Accsys Technologies and/or its agents (available upon request). Accsys Technologies accepts no liability for any defect, damage or loss that may occur where such written instructions and guidelines are not adhered to. No liability is accepted in relation to any coating, fastener or other product of a third party applied to ACCOYA

® wood. Please refer to

[accoya.com/downloads] for further information and full terms and conditions.

ACCSYST E C H N O L O G I E S

47

8

9

12

3

5

6

Joints co

ntin

uo

us

ve

ntila

tio

n

8

9

The crusher bead milled into the LT AC 01 Accoya®

cladding board insures sufficient mutual distance

between the boards, with an increased installing

speed. When meeting other construction elements

and/or between the length of two boards, a free

space of 5 - 10 mm should be allowed for.

1

4

2

Room lining (such as plaster board).

Wall structure (wooden structural frame filled with a

suitable insulation material of sufficient thickness to

achieve required values).

Service void (optional, may also be filled with

insulation material).

3 Air barrier / vapour control layer.

6

5

Water repellent breather membrane - UV resistant in

case of open joints.

Structural sheathing board.

Vertical timber battens of at least 38 x 19 mm of

durability class 1 or 2.

7

Ring shank or other improved nails:

· grade 1.4301 (general applications) or grade

1.4401 (coastal or industrial sites)

· Holes pre-drilled:

- 1 mm less than nail Ø

- to 80% of screw shank Ø

Title

Section Date

Version

17.11.2015

2.0 / HWIScale

Detail

1:2

vertical

Horizontal joint

Horizontal cladding – LT AC 01

4

12

mm

68mm

≥ 2

x d

d

Point side penetration ≥ 6xd

(ring shank) / 12xd (smooth)

The drawing shows the rough principles but are not meant to contain actual products. The system used must be designed to the specific project requirements, in accordance with all applicable building standards and

regulations. The strength of the total system - spacing, number and type of fasteners required for the occurring wind load - must always be checked by a licensed engineer. To the best of the knowledge and belief of

Accsys Technologies PLC the information contained in this document is in accordance with common building practice and is provided on the basis that Accsys Technologies and/or any of its affiliates, officers,

employees or advisers are not liable for any loss or damage whatsoever in respect of the accuracy or completeness of such information or the result of having acted upon it.

Accoya® LT AC 01 horizontal cladding board, availa-

ble from James Latham in 15x145 and 15x195 mm.

Innovation in wood

Page 6: ACCOYA CLADDING UK ON A TIMBER FRAMElathams-accoyacladding.co.uk/wp-content/uploads/... · a ventilated façade system ... because of leaching of extractives from the timber sub-

ACCOYA® and the Trimarque Device are registered trademarks owned by Titan Wood Limited, Trading as “Accsys Technologies”, a

wholly owned subsidiary of Accsys Technologies PLC. The trademarks ACCOYA® and the Trimarque Device may not be used or

reproduced without written permission from Accsys Technologies. ACCOYA® wood should always be installed and used in accordance

with the written instructions and guidelines of Accsys Technologies and/or its agents (available upon request). Accsys Technologies accepts no liability for any defect, damage or loss that may occur where such written instructions and guidelines are not adhered to. No liability is accepted in relation to any coating, fastener or other product of a third party applied to ACCOYA

® wood. Please refer to

[accoya.com/downloads] for further information and full terms and conditions.

ACCSYST E C H N O L O G I E S

7

108

7

8

4

9

1

2

3

5

6

10

9

1

4

2

Room lining (such as plaster board).

Wall structure (wooden structural frame filled with a

suitable insulation material of sufficient thickness to

achieve required values).

Service void (optional, may also be filled with

insulation material).

3 Air barrier / vapour control layer.

6

5

Water repellent breather membrane - UV resistant in

case of open joints.

Structural sheathing board.

Horizontal timber battens of at least 50 x 25 mm, of

durability class 1 or 2.

Vertical timber counter battens of durability class 1 or 2.

Joints

Ring shank or other improved nails:

· grade 1.4301 (general applications) or grade

1.4401 (coastal or industrial sites)

· Holes pre-drilled:

- 1 mm less than nail Ø

- to 80% of screw shank Ø

Title

Section Date

Version

17.11.2015

2.0 / HWIScale

Detail

1:2

horizontal

Vertical joint

Vertical cladding – LT AC 02

4

12m

m

68mm

≥ 2

x d

d

Point side penetration ≥ 6xd

(ring shank) / 12xd (smooth)

The drawing shows the rough principles but are not meant to contain actual products. The system used must be designed to the specific project requirements, in accordance with all applicable building standards and

regulations. The strength of the total system - spacing, number and type of fasteners required for the occurring wind load - must always be checked by a licensed engineer. To the best of the knowledge and belief of

Accsys Technologies PLC the information contained in this document is in accordance with common building practice and is provided on the basis that Accsys Technologies and/or any of its affiliates, officers,

employees or advisers are not liable for any loss or damage whatsoever in respect of the accuracy or completeness of such information or the result of having acted upon it.

The crusher bead milled into the LT AC 02 Accoya®

cladding board insures sufficient mutual distance

between the boards, with an increased installing

speed. When meeting other construction elements

and/or between the length of two boards, a free

space of 5 - 10 mm should be allowed for.Accoya

® LT AC 02 vertical cladding board, available

from James Latham in 15x145 mm and 15x195 mm.

Innovation in wood

Page 7: ACCOYA CLADDING UK ON A TIMBER FRAMElathams-accoyacladding.co.uk/wp-content/uploads/... · a ventilated façade system ... because of leaching of extractives from the timber sub-

ACCOYA® and the Trimarque Device are registered trademarks owned by Titan Wood Limited, Trading as “Accsys Technologies”, a

wholly owned subsidiary of Accsys Technologies PLC. The trademarks ACCOYA® and the Trimarque Device may not be used or

reproduced without written permission from Accsys Technologies. ACCOYA® wood should always be installed and used in accordance

with the written instructions and guidelines of Accsys Technologies and/or its agents (available upon request). Accsys Technologies accepts no liability for any defect, damage or loss that may occur where such written instructions and guidelines are not adhered to. No liability is accepted in relation to any coating, fastener or other product of a third party applied to ACCOYA

® wood. Please refer to

[accoya.com/downloads] for further information and full terms and conditions.

ACCSYST E C H N O L O G I E S

co

ntin

uo

us

ve

ntila

tio

n

5m

m5 –

10

mm

4

8

2

5

6

1

11

10

9

1

4

2

Room lining (such as plaster board).

Wall structure (wooden structural frame filled

with a suitable insulation material of sufficient

thickness to achieve required values).

Service void (optional, may also be filled with

insulation material).

3 Air barrier / vapour control layer.

6

5

Water repellent breather membrane - UV

resistant in case of open joints.

Structural sheathing board.

10

11

Vertical timber battens of at least 38 x 19 mm

of durability class 1 or 2.

8

Ring shank or other improved nails:

· grade 1.4301 (general applications) or

grade 1.4401 (coastal or industrial sites)

· Holes pre-drilled:

- 1 mm less than nail Ø

- to 80% of screw shank Ø

9 Vermin mesh of corrosion resistant metal,

hole width ≤ 4 mm. Void area in line with ven-

tilation requirements.

7

7 Framing.

3

Title

Section Date

Version

17.11.2015

2.0 / HWIScale

Detail

1:2

vertical

Sash window sill

Horizontal cladding – LT AC 01

4

12m

m

68mm

≥ 2

x d

d

Point side penetration ≥ 6xd

(ring shank) / 12xd (smooth)

The drawing shows the rough principles but are not meant to contain actual products. The system used must be designed to the specific project requirements, in accordance with all applicable building standards and

regulations. The strength of the total system - spacing, number and type of fasteners required for the occurring wind load - must always be checked by a licensed engineer. To the best of the knowledge and belief of

Accsys Technologies PLC the information contained in this document is in accordance with common building practice and is provided on the basis that Accsys Technologies and/or any of its affiliates, officers,

employees or advisers are not liable for any loss or damage whatsoever in respect of the accuracy or completeness of such information or the result of having acted upon it.

Accoya® LT AC 01 horizontal cladding board,

available from James Latham in 15x145 and

15x195 mm.

Innovation in wood

Page 8: ACCOYA CLADDING UK ON A TIMBER FRAMElathams-accoyacladding.co.uk/wp-content/uploads/... · a ventilated façade system ... because of leaching of extractives from the timber sub-

ACCOYA® and the Trimarque Device are registered trademarks owned by Titan Wood Limited, Trading as “Accsys Technologies”, a

wholly owned subsidiary of Accsys Technologies PLC. The trademarks ACCOYA® and the Trimarque Device may not be used or

reproduced without written permission from Accsys Technologies. ACCOYA® wood should always be installed and used in accordance

with the written instructions and guidelines of Accsys Technologies and/or its agents (available upon request). Accsys Technologies accepts no liability for any defect, damage or loss that may occur where such written instructions and guidelines are not adhered to. No liability is accepted in relation to any coating, fastener or other product of a third party applied to ACCOYA

® wood. Please refer to

[accoya.com/downloads] for further information and full terms and conditions.

ACCSYST E C H N O L O G I E S

48 25

6

1

12

11

5m

m5

– 1

0 m

m

co

ntin

uo

us

ve

ntila

tio

n

3

35

mm

>1

5 m

m

10

9

1

4

2

Room lining (such as plaster board).

Wall structure (wooden structural frame filled

with a suitable insulation material of sufficient

thickness to achieve required values).

Service void (optional, may also be filled with

insulation material).

3 Air barrier / vapour control layer.

6

5

Water repellent breather membrane - UV

resistant in case of open joints.

Structural sheathing board.

7 Framing.

7

11

12

Vertical timber battens of at least 38 x 19 mm

of durability class 1 or 2.

8

Ring shank or other improved nails:

· grade 1.4301 (general applications) or

grade 1.4401 (coastal or industrial sites)

· Holes pre-drilled:

- 1 mm less than nail Ø

- to 80% of screw shank Ø

9 Vermin mesh of corrosion resistant metal,

hole width ≤ 4 mm. Void area in line with ven-

tilation requirements.

10 Preformed corrosion resistant metal flashing.

Title

Section Date

Version

17.11.2015

2.0 / HWIScale

Detail

1:2

vertical

Sash window head

Horizontal cladding – LT AC 01

4

12m

m

68mm

≥ 2

x d

d

Point side penetration ≥ 6xd

(ring shank) / 12xd (smooth)

The drawing shows the rough principles but are not meant to contain actual products. The system used must be designed to the specific project requirements, in accordance with all applicable building standards and

regulations. The strength of the total system - spacing, number and type of fasteners required for the occurring wind load - must always be checked by a licensed engineer. To the best of the knowledge and belief of

Accsys Technologies PLC the information contained in this document is in accordance with common building practice and is provided on the basis that Accsys Technologies and/or any of its affiliates, officers,

employees or advisers are not liable for any loss or damage whatsoever in respect of the accuracy or completeness of such information or the result of having acted upon it.

Accoya® LT AC 01 horizontal cladding board,

available from James Latham in 15x145 and

15x195 mm.

Innovation in wood

Page 9: ACCOYA CLADDING UK ON A TIMBER FRAMElathams-accoyacladding.co.uk/wp-content/uploads/... · a ventilated façade system ... because of leaching of extractives from the timber sub-

ACCOYA® and the Trimarque Device are registered trademarks owned by Titan Wood Limited, Trading as “Accsys Technologies”, a

wholly owned subsidiary of Accsys Technologies PLC. The trademarks ACCOYA® and the Trimarque Device may not be used or

reproduced without written permission from Accsys Technologies. ACCOYA® wood should always be installed and used in accordance

with the written instructions and guidelines of Accsys Technologies and/or its agents (available upon request). Accsys Technologies accepts no liability for any defect, damage or loss that may occur where such written instructions and guidelines are not adhered to. No liability is accepted in relation to any coating, fastener or other product of a third party applied to ACCOYA

® wood. Please refer to

[accoya.com/downloads] for further information and full terms and conditions.

ACCSYST E C H N O L O G I E S

4

8

9

10

2

5

6

1

3

50mm≥ 50 mm 5

5-10 mm

7

7

8

10

9

1

4

2

Room lining (such as plaster board).

Wall structure (wooden structural frame filled with a

suitable insulation material of sufficient thickness to

achieve required values).

Service void (optional, may also be filled with

insulation material).

3 Air barrier / vapour control layer.

6

5

Water repellent breather membrane - UV resistant in

case of open joints.

Structural sheathing board.

Framing.

Joints

Ring shank or other improved nails:

· grade 1.4301 (general applications) or grade

1.4401 (coastal or industrial sites)

· Holes pre-drilled:

- 1 mm less than nail Ø

- to 80% of screw shank Ø

Vertical timber battens of at least 38 x 19 mm of

durability class 1 or 2.

Title

Section Date

Version

17.11.2015

2.0 / HWIScale

Detail

1:2

horizontal

Sash window jamb

Horizontal cladding – LT AC 01

Innovation in wood

4

12m

m

68mm

≥ 2

x d

d

Point side penetration ≥ 6xd

(ring shank) / 12xd (smooth)

The drawing shows the rough principles but are not meant to contain actual products. The system used must be designed to the specific project requirements, in accordance with all applicable building standards and

regulations. The strength of the total system - spacing, number and type of fasteners required for the occurring wind load - must always be checked by a licensed engineer. To the best of the knowledge and belief of

Accsys Technologies PLC the information contained in this document is in accordance with common building practice and is provided on the basis that Accsys Technologies and/or any of its affiliates, officers,

employees or advisers are not liable for any loss or damage whatsoever in respect of the accuracy or completeness of such information or the result of having acted upon it.

Accoya® LT AC 01 horizontal cladding board, availa-

ble from James Latham in 15x145 and 15x195 mm.

The crusher bead milled into the LT AC 01 Accoya®

cladding board insures sufficient mutual distance

between the boards, with an increased installing

speed. When meeting other construction elements

and/or between the length of two boards, a free

space of 5 - 10 mm should be allowed for.

Page 10: ACCOYA CLADDING UK ON A TIMBER FRAMElathams-accoyacladding.co.uk/wp-content/uploads/... · a ventilated façade system ... because of leaching of extractives from the timber sub-

ACCOYA® and the Trimarque Device are registered trademarks owned by Titan Wood Limited, Trading as “Accsys Technologies”, a

wholly owned subsidiary of Accsys Technologies PLC. The trademarks ACCOYA® and the Trimarque Device may not be used or

reproduced without written permission from Accsys Technologies. ACCOYA® wood should always be installed and used in accordance

with the written instructions and guidelines of Accsys Technologies and/or its agents (available upon request). Accsys Technologies accepts no liability for any defect, damage or loss that may occur where such written instructions and guidelines are not adhered to. No liability is accepted in relation to any coating, fastener or other product of a third party applied to ACCOYA

® wood. Please refer to

[accoya.com/downloads] for further information and full terms and conditions.

ACCSYST E C H N O L O G I E S

4

8

9

10

2

5

6

1

3

5 5-10 mm

7

7

8

11

9

1

4

2

Room lining (such as plaster board).

Wall structure (wooden structural frame filled with a

suitable insulation material of sufficient thickness to

achieve required values).

Service void (optional, may also be filled with

insulation material).

3 Air barrier / vapour control layer.

6

5

Water repellent breather membrane - UV resistant in

case of open joints.

Structural sheathing board.

Framing.

Joints

Ring shank or other improved nails:

· grade 1.4301 (general applications) or grade

1.4401 (coastal or industrial sites)

· Holes pre-drilled:

- 1 mm less than nail Ø

- to 80% of screw shank Ø

Title

Section Date

Version

17.11.2015

2.0 / HWIScale

Detail

1:2

horizontal

Sash window jamb

Vertical cladding – LT AC 02

4

12

mm

68mm

≥ 2

x d

d

Point side penetration ≥ 6xd

(ring shank) / 12xd (smooth)

The drawing shows the rough principles but are not meant to contain actual products. The system used must be designed to the specific project requirements, in accordance with all applicable building standards and

regulations. The strength of the total system - spacing, number and type of fasteners required for the occurring wind load - must always be checked by a licensed engineer. To the best of the knowledge and belief of

Accsys Technologies PLC the information contained in this document is in accordance with common building practice and is provided on the basis that Accsys Technologies and/or any of its affiliates, officers,

employees or advisers are not liable for any loss or damage whatsoever in respect of the accuracy or completeness of such information or the result of having acted upon it.

The crusher bead milled into the LT AC 02 Accoya®

cladding board insures sufficient mutual distance

between the boards, with an increased installing

speed. When meeting other construction elements

and/or between the length of two boards, a free

space of 5 - 10 mm should be allowed for.Accoya

® LT AC 02 vertical cladding board, available

from James Latham in 15x145 mm and 15x195 mm.

Innovation in wood

Horizontal timber battens of at least 50 x 25 mm, of

durability class 1 or 2.

Vertical timber counter battens of durability class 1 or 2.

10

11

Page 11: ACCOYA CLADDING UK ON A TIMBER FRAMElathams-accoyacladding.co.uk/wp-content/uploads/... · a ventilated façade system ... because of leaching of extractives from the timber sub-

ACCOYA® and the Trimarque Device are registered trademarks owned by Titan Wood Limited, Trading as “Accsys Technologies”, a

wholly owned subsidiary of Accsys Technologies PLC. The trademarks ACCOYA® and the Trimarque Device may not be used or

reproduced without written permission from Accsys Technologies. ACCOYA® wood should always be installed and used in accordance

with the written instructions and guidelines of Accsys Technologies and/or its agents (available upon request). Accsys Technologies accepts no liability for any defect, damage or loss that may occur where such written instructions and guidelines are not adhered to. No liability is accepted in relation to any coating, fastener or other product of a third party applied to ACCOYA

® wood. Please refer to

[accoya.com/downloads] for further information and full terms and conditions.

ACCSYST E C H N O L O G I E S

co

ntin

uo

us

ve

ntila

tio

n7m

m

4

8

2

5

6

111

10

9 7

3

5 –

10

mm

1

4

2

Room lining (such as plaster board).

Wall structure (wooden structural frame filled

with a suitable insulation material of sufficient

thickness to achieve required values).

Service void (optional, may also be filled with

insulation material).

3 Air barrier / vapour control layer.

6

5

Water repellent breather membrane - UV

resistant in case of open joints.

Structural sheathing board.

10

11

Vertical timber battens of at least 38 x 19 mm

of durability class 1 or 2.

8

Ring shank or other improved nails:

· grade 1.4301 (general applications) or

grade 1.4401 (coastal or industrial sites)

· Holes pre-drilled:

- 1 mm less than nail Ø

- to 80% of screw shank Ø

9 Vermin mesh of corrosion resistant metal,

hole width ≤ 4 mm. Void area in line with ven-

tilation requirements.

7 Framing.

Title

Section Date

Version

17.11.2015

2.0 / HWIScale

Detail

1:2

vertical

Window sill

Horizontal cladding – LT AC 01

4

12m

m

68mm

≥ 2

x d

d

Point side penetration ≥ 6xd

(ring shank) / 12xd (smooth)

The drawing shows the rough principles but are not meant to contain actual products. The system used must be designed to the specific project requirements, in accordance with all applicable building standards and

regulations. The strength of the total system - spacing, number and type of fasteners required for the occurring wind load - must always be checked by a licensed engineer. To the best of the knowledge and belief of

Accsys Technologies PLC the information contained in this document is in accordance with common building practice and is provided on the basis that Accsys Technologies and/or any of its affiliates, officers,

employees or advisers are not liable for any loss or damage whatsoever in respect of the accuracy or completeness of such information or the result of having acted upon it.

OFFICIALDISTRIBUTOR

lathams-accoya.co.uk

Innovation in wood

Accoya® LT AC 01 horizontal cladding board,

available from James Latham in 15x145 and

15x195 mm.

Page 12: ACCOYA CLADDING UK ON A TIMBER FRAMElathams-accoyacladding.co.uk/wp-content/uploads/... · a ventilated façade system ... because of leaching of extractives from the timber sub-

48 25

6

1

12

11

co

ntin

uo

us

ve

ntila

tio

n

3

9

7

ACCOYA® and the Trimarque Device are registered trademarks owned by Titan Wood Limited, Trading as “Accsys Technologies”, a

wholly owned subsidiary of Accsys Technologies PLC. The trademarks ACCOYA® and the Trimarque Device may not be used or

reproduced without written permission from Accsys Technologies. ACCOYA® wood should always be installed and used in accordance

with the written instructions and guidelines of Accsys Technologies and/or its agents (available upon request). Accsys Technologies accepts no liability for any defect, damage or loss that may occur where such written instructions and guidelines are not adhered to. No liability is accepted in relation to any coating, fastener or other product of a third party applied to ACCOYA

® wood. Please refer to

[accoya.com/downloads] for further information and full terms and conditions.

ACCSYST E C H N O L O G I E S

6m

m

5-10 mm

1

4

2

Room lining (such as plaster board).

Wall structure (wooden structural frame filled

with a suitable insulation material of sufficient

thickness to achieve required values).

Service void (optional, may also be filled with

insulation material).

3 Air barrier / vapour control layer.

6

5

Water repellent breather membrane - UV

resistant in case of open joints.

Structural sheathing board.

11

12

Vertical timber battens of at least 38 x 19 mm

of durability class 1 or 2.

8

Ring shank or other improved nails:

· grade 1.4301 (general applications) or

grade 1.4401 (coastal or industrial sites)

· Holes pre-drilled:

- 1 mm less than nail Ø

- to 80% of screw shank Ø

9 Vermin mesh of corrosion resistant metal,

max hole width 4 mm. Void area in line with

ventilation requirements.

7 Framing.

10

10 Preformed corrosion resistant metal flashing.

Title

Section Date

Version

17.11.2015

2.0 / HWIScale

Detail

1:2

vertical

Window head

Horizontal cladding – LT AC 01

4

12m

m

68mm

≥ 2

x d

d

Point side penetration ≥ 6xd

(ring shank) / 12xd (smooth)

The drawing shows the rough principles but are not meant to contain actual products. The system used must be designed to the specific project requirements, in accordance with all applicable building standards and

regulations. The strength of the total system - spacing, number and type of fasteners required for the occurring wind load - must always be checked by a licensed engineer. To the best of the knowledge and belief of

Accsys Technologies PLC the information contained in this document is in accordance with common building practice and is provided on the basis that Accsys Technologies and/or any of its affiliates, officers,

employees or advisers are not liable for any loss or damage whatsoever in respect of the accuracy or completeness of such information or the result of having acted upon it.

Innovation in wood

Accoya® LT AC 01 horizontal cladding board,

available from James Latham in 15x145 and

15x195 mm.

Page 13: ACCOYA CLADDING UK ON A TIMBER FRAMElathams-accoyacladding.co.uk/wp-content/uploads/... · a ventilated façade system ... because of leaching of extractives from the timber sub-

4

8

9

10

2

5

6

1

3

50mm≥ 50 mm 5

5-10 mm

7

ACCOYA® and the Trimarque Device are registered trademarks owned by Titan Wood Limited, Trading as “Accsys Technologies”, a

wholly owned subsidiary of Accsys Technologies PLC. The trademarks ACCOYA® and the Trimarque Device may not be used or

reproduced without written permission from Accsys Technologies. ACCOYA® wood should always be installed and used in accordance

with the written instructions and guidelines of Accsys Technologies and/or its agents (available upon request). Accsys Technologies accepts no liability for any defect, damage or loss that may occur where such written instructions and guidelines are not adhered to. No liability is accepted in relation to any coating, fastener or other product of a third party applied to ACCOYA

® wood. Please refer to

[accoya.com/downloads] for further information and full terms and conditions.

ACCSYST E C H N O L O G I E S

7

8

10

9

1

4

2

Room lining (such as plaster board).

Wall structure (wooden structural frame filled with a

suitable insulation material of sufficient thickness to

achieve required values).

Service void (optional, may also be filled with

insulation material).

3 Air barrier / vapour control layer.

6

5

Water repellent breather membrane - UV resistant in

case of open joints.

Structural sheathing board.

Framing.

Joints

Ring shank or other improved nails:

· grade 1.4301 (general applications) or grade

1.4401 (coastal or industrial sites)

· Holes pre-drilled:

- 1 mm less than nail Ø

- to 80% of screw shank Ø

Vertical timber battens of at least 38 x 19 mm of

durability class 1 or 2.

Title

Section Date

Version

17.11.2015

2.0 / HWIScale

Detail

1:2

horizontal

Window jamb

Horizontal cladding – LT AC 01

4

12m

m

68mm

≥ 2

x d

d

Point side penetration ≥ 6xd

(ring shank) / 12xd (smooth)

The drawing shows the rough principles but are not meant to contain actual products. The system used must be designed to the specific project requirements, in accordance with all applicable building standards and

regulations. The strength of the total system - spacing, number and type of fasteners required for the occurring wind load - must always be checked by a licensed engineer. To the best of the knowledge and belief of

Accsys Technologies PLC the information contained in this document is in accordance with common building practice and is provided on the basis that Accsys Technologies and/or any of its affiliates, officers,

employees or advisers are not liable for any loss or damage whatsoever in respect of the accuracy or completeness of such information or the result of having acted upon it.

Innovation in wood

Accoya® LT AC 01 horizontal cladding board, availa-

ble from James Latham in 15x145 and 15x195 mm.

The crusher bead milled into the LT AC 01 Accoya®

cladding board insures sufficient mutual distance

between the boards, with an increased installing

speed. When meeting other construction elements

and/or between the length of two boards, a free

space of 5 - 10 mm should be allowed for.

Page 14: ACCOYA CLADDING UK ON A TIMBER FRAMElathams-accoyacladding.co.uk/wp-content/uploads/... · a ventilated façade system ... because of leaching of extractives from the timber sub-

4

2

5

6

1

3

55-10 mm

7

ACCOYA® and the Trimarque Device are registered trademarks owned by Titan Wood Limited, Trading as “Accsys Technologies”, a

wholly owned subsidiary of Accsys Technologies PLC. The trademarks ACCOYA® and the Trimarque Device may not be used or

reproduced without written permission from Accsys Technologies. ACCOYA® wood should always be installed and used in accordance

with the written instructions and guidelines of Accsys Technologies and/or its agents (available upon request). Accsys Technologies accepts no liability for any defect, damage or loss that may occur where such written instructions and guidelines are not adhered to. No liability is accepted in relation to any coating, fastener or other product of a third party applied to ACCOYA

® wood. Please refer to

[accoya.com/downloads] for further information and full terms and conditions.

ACCSYST E C H N O L O G I E S

7

11

1

4

2

Room lining (such as plaster board).

Wall structure (wooden structural frame filled with a

suitable insulation material of sufficient thickness to

achieve required values).

Service void (optional, may also be filled with

insulation material).

3 Air barrier / vapour control layer.

6

5

Water repellent breather membrane - UV resistant in

case of open joints.

Structural sheathing board.

Framing.Joints

Ring shank or other improved nails:

· grade 1.4301 (general applications) or grade

1.4401 (coastal or industrial sites)

· Holes pre-drilled:

- 1 mm less than nail Ø

- to 80% of screw shank Ø

Title

Section Date

Version

17.11.2015

2.0 / HWIScale

Detail

1:2

horizontal

Window jamb

Vertical cladding – LT AC 02

4

12m

m

68mm

≥ 2

x d

d

Point side penetration ≥ 6xd

(ring shank) / 12xd (smooth)

The drawing shows the rough principles but are not meant to contain actual products. The system used must be designed to the specific project requirements, in accordance with all applicable building standards and

regulations. The strength of the total system - spacing, number and type of fasteners required for the occurring wind load - must always be checked by a licensed engineer. To the best of the knowledge and belief of

Accsys Technologies PLC the information contained in this document is in accordance with common building practice and is provided on the basis that Accsys Technologies and/or any of its affiliates, officers,

employees or advisers are not liable for any loss or damage whatsoever in respect of the accuracy or completeness of such information or the result of having acted upon it.

Innovation in wood

8

9

The crusher bead milled into the LT AC 02 Accoya®

cladding board insures sufficient mutual distance

between the boards, with an increased installing

speed. When meeting other construction elements

and/or between the length of two boards, a free

space of 5 - 10 mm should be allowed for.Accoya

® LT AC 02 vertical cladding board, available

from James Latham in 15x145 mm and 15x195 mm.

Horizontal timber battens of at least 50 x 25 mm, of

durability class 1 or 2.

Vertical timber counter battens of durability class 1 or 2.

10

8

9

10

11

Page 15: ACCOYA CLADDING UK ON A TIMBER FRAMElathams-accoyacladding.co.uk/wp-content/uploads/... · a ventilated façade system ... because of leaching of extractives from the timber sub-

ACCOYA® and the Trimarque Device are registered trademarks owned by Titan Wood Limited, Trading as “Accsys Technologies”, a

wholly owned subsidiary of Accsys Technologies PLC. The trademarks ACCOYA® and the Trimarque Device may not be used or

reproduced without written permission from Accsys Technologies. ACCOYA® wood should always be installed and used in accordance

with the written instructions and guidelines of Accsys Technologies and/or its agents (available upon request). Accsys Technologies accepts no liability for any defect, damage or loss that may occur where such written instructions and guidelines are not adhered to. No liability is accepted in relation to any coating, fastener or other product of a third party applied to ACCOYA

® wood. Please refer to

[accoya.com/downloads] for further information and full terms and conditions.

ACCSYST E C H N O L O G I E S

4

11

co

ntin

uo

us

ve

ntila

tio

n

9

3

12

5

6

7

10

10

11

1

4

2

Room lining (such as plaster board).

Wall structure (wooden structural frame filled

with a suitable insulation material of sufficient

thickness to achieve required values).

Service void (optional, may also be filled with

insulation material).

3 Air barrier / vapour control layer.

6

5

Water repellent breather membrane - UV

resistant in case of open joints.

Structural sheathing board.

Vertical timber battens of at least 38 x 19 mm

of durability class 1 or 2.

7

Ring shank or other improved nails:

· grade 1.4301 (general applications) or

grade 1.4401 (coastal or industrial sites)

· Holes pre-drilled:

- 1 mm less than nail Ø

- to 80% of screw shank Ø

8

9

Roofing material to specification.

Roof trim (corrosion resistant), details to project

requirements; a minimum gap of 5 mm should

be kept between the surface of the panel and

the trim to ensure ventilation.

Title

Section Date

Version

17.11.2015

2.0 / HWIScale

Detail

1:2

vertical

Roof trim

Horizontal cladding – LT AC 01

4

12m

m

68mm

≥ 2

x d

d

Point side penetration ≥ 6xd

(ring shank) / 12xd (smooth)

The drawing shows the rough principles but are not meant to contain actual products. The system used must be designed to the specific project requirements, in accordance with all applicable building standards and

regulations. The strength of the total system - spacing, number and type of fasteners required for the occurring wind load - must always be checked by a licensed engineer. To the best of the knowledge and belief of

Accsys Technologies PLC the information contained in this document is in accordance with common building practice and is provided on the basis that Accsys Technologies and/or any of its affiliates, officers,

employees or advisers are not liable for any loss or damage whatsoever in respect of the accuracy or completeness of such information or the result of having acted upon it.

8

Innovation in wood

Accoya® LT AC 01 horizontal cladding board,

available from James Latham in 15x145 and

15x195 mm.

Page 16: ACCOYA CLADDING UK ON A TIMBER FRAMElathams-accoyacladding.co.uk/wp-content/uploads/... · a ventilated façade system ... because of leaching of extractives from the timber sub-

ACCOYA® and the Trimarque Device are registered trademarks owned by Titan Wood Limited, Trading as “Accsys Technologies”, a

wholly owned subsidiary of Accsys Technologies PLC. The trademarks ACCOYA® and the Trimarque Device may not be used or

reproduced without written permission from Accsys Technologies. ACCOYA® wood should always be installed and used in accordance

with the written instructions and guidelines of Accsys Technologies and/or its agents (available upon request). Accsys Technologies accepts no liability for any defect, damage or loss that may occur where such written instructions and guidelines are not adhered to. No liability is accepted in relation to any coating, fastener or other product of a third party applied to ACCOYA

® wood. Please refer to

[accoya.com/downloads] for further information and full terms and conditions.

ACCSYST E C H N O L O G I E S

4

co

ntin

uo

us

ve

ntila

tio

n

3

12

5

6

7

105-10 mm

8

10

9

1

4

2

Room lining (such as plaster board).

Wall structure (wooden structural frame filled

with a suitable insulation material of sufficient

thickness to achieve required values).

Service void (optional, may also be filled with

insulation material).

3 Air barrier / vapour control layer.

6

5

Water repellent breather membrane - UV

resistant in case of open joints.

Structural sheathing board.

Vertical timber battens of at least 38 x 19 mm

of durability class 1 or 2.

7

Accoya® frieze board

9

10 Ring shank or other improved nails:

· grade 1.4301 (general applications) or

grade 1.4401 (coastal or industrial sites)

· Holes pre-drilled:

- 1 mm less than nail Ø

- to 80% of screw shank Ø

8

Title

Section Date

Version

17.11.2015

2.0 / HWIScale

Detail

1:2

vertical

Overhang

Horizontal cladding – LT AC 01

4

12m

m

68mm

≥ 2

x d

d

Point side penetration ≥ 6xd

(ring shank) / 12xd (smooth)

The drawing shows the rough principles but are not meant to contain actual products. The system used must be designed to the specific project requirements, in accordance with all applicable building standards and

regulations. The strength of the total system - spacing, number and type of fasteners required for the occurring wind load - must always be checked by a licensed engineer. To the best of the knowledge and belief of

Accsys Technologies PLC the information contained in this document is in accordance with common building practice and is provided on the basis that Accsys Technologies and/or any of its affiliates, officers,

employees or advisers are not liable for any loss or damage whatsoever in respect of the accuracy or completeness of such information or the result of having acted upon it.

Innovation in wood

Accoya® LT AC 01 horizontal cladding board,

available from James Latham in 15x145 and

15x195 mm.

Page 17: ACCOYA CLADDING UK ON A TIMBER FRAMElathams-accoyacladding.co.uk/wp-content/uploads/... · a ventilated façade system ... because of leaching of extractives from the timber sub-

ACCOYA® and the Trimarque Device are registered trademarks owned by Titan Wood Limited, Trading as “Accsys Technologies”, a

wholly owned subsidiary of Accsys Technologies PLC. The trademarks ACCOYA® and the Trimarque Device may not be used or

reproduced without written permission from Accsys Technologies. ACCOYA® wood should always be installed and used in accordance

with the written instructions and guidelines of Accsys Technologies and/or its agents (available upon request). Accsys Technologies accepts no liability for any defect, damage or loss that may occur where such written instructions and guidelines are not adhered to. No liability is accepted in relation to any coating, fastener or other product of a third party applied to ACCOYA

® wood. Please refer to

[accoya.com/downloads] for further information and full terms and conditions.

ACCSYST E C H N O L O G I E S

7mm

5 – 10 mm5 – 10 mm

5mm5 – 10 mm

5mm

Title

Section Date

Version

26.08.2015

2.0 / HWIScale

Detail

1:2

horizontal

Interior corners

Horizontal cladding - UK

Innovation in wood

Joints

The drawing shows the rough principles but are not meant to contain actual products. The system used must be designed to the specific project requirements, in accordance with all applicable building standards and

regulations. The strength of the total system - spacing, number and type of fasteners required for the occurring wind load - must always be checked by a licensed engineer. To the best of the knowledge and belief of

Accsys Technologies PLC the information contained in this document is in accordance with common building practice and is provided on the basis that Accsys Technologies and/or any of its affiliates, officers,

employees or advisers are not liable for any loss or damage whatsoever in respect of the accuracy or completeness of such information or the result of having acted upon it.

The crusher bead milled into the LT AC 01/02

Accoya® cladding board insures sufficient mutual

distance between the boards, with an increased

installing speed. When meeting other construction

elements and/or between the length of two boards, a

free space of 5 - 10 mm should be allowed for.

Page 18: ACCOYA CLADDING UK ON A TIMBER FRAMElathams-accoyacladding.co.uk/wp-content/uploads/... · a ventilated façade system ... because of leaching of extractives from the timber sub-

ACCOYA® and the Trimarque Device are registered trademarks owned by Titan Wood Limited, Trading as “Accsys Technologies”, a

wholly owned subsidiary of Accsys Technologies PLC. The trademarks ACCOYA® and the Trimarque Device may not be used or

reproduced without written permission from Accsys Technologies. ACCOYA® wood should always be installed and used in accordance

with the written instructions and guidelines of Accsys Technologies and/or its agents (available upon request). Accsys Technologies accepts no liability for any defect, damage or loss that may occur where such written instructions and guidelines are not adhered to. No liability is accepted in relation to any coating, fastener or other product of a third party applied to ACCOYA

® wood. Please refer to

[accoya.com/downloads] for further information and full terms and conditions.

ACCSYST E C H N O L O G I E S

8m

m

7mm

5mm

5mm

7m

m

5m

m5

– 10

mm

5 – 10 mm

5 – 10 mm

5 –

10

mm

5 –

10

mm

Title

Section Date

Version

26.08.2015

2.0 / HWIScale

Detail

1:2

vertical

Exterior corners

Horizontal cladding - UK

Innovation in wood

Joints

The drawing shows the rough principles but are not meant to contain actual products. The system used must be designed to the specific project requirements, in accordance with all applicable building standards and

regulations. The strength of the total system - spacing, number and type of fasteners required for the occurring wind load - must always be checked by a licensed engineer. To the best of the knowledge and belief of

Accsys Technologies PLC the information contained in this document is in accordance with common building practice and is provided on the basis that Accsys Technologies and/or any of its affiliates, officers,

employees or advisers are not liable for any loss or damage whatsoever in respect of the accuracy or completeness of such information or the result of having acted upon it.

The crusher bead milled into the LT AC 01/02 Accoya® cladding board insures sufficient mutual distance between

the boards, with an increased installing speed. When meeting other construction elements and/or between the

length of two boards, a free space of 5 - 10 mm should be allowed for.