  • SINGLE LINE DIAGRAM (SLD) Or, ONE LINE DIAGRAM

    Page1of3

    The singleline diagram is the blueprint forelectrical system analysis. It is the first step inpreparingacriticalresponseplan,allowingyouto become thoroughly familiar with theelectricaldistributionsystem layoutanddesigninyourfacility.

    Whyitsrequired?

    Whetheryouhaveaneworexistingfacility,thesingleline diagram is the vital roadmap for allfuture testing, service and maintenanceactivities.Assuch,thesinglelinediagramislikeabalancesheet foryour facilityandprovidesasnapshotofyourfacilityatamomentintime.Itneeds to change as your facility changes toensure that your systems are adequatelyprotected.

    To make all the changes documented in acommonfile,makingtheelectricalsystemeasilyunderstandable for any technical personinside/outsideofthefactory.

    An uptodate singleline diagram is vital for avarietyofserviceactivitiesincluding:

    o Shortcircuitcalculationso Coordinationstudieso Loadflowstudieso Safetyevaluationstudieso Allotherengineeringstudieso Electricalsafetyprocedureso Efficientmaintenance

    Whatshouldbeinasinglelinediagram(SLD)?

    A typical package of single line diagram shallinclude:

    Incominglinesshowingvoltageandsize

    Incomingmainfuses,cutouts,switches,andmain/tiebreakers

    Power transformers (rating, windingconnectionandgroundingmeans)

    Feeder breakers and fused switches ratingandtype.

    Relays(function,useandtype)

    Currentand/orpotentialtransformerswithsize,typeandratio

    Controltransformersrating.

    All main cable and wire runs with theirassociatedisolatingswitches

    Allsubstations, including integralrelaysandmainpanelswith total loadofeach feederandeachsubstation

    Critical equipment voltage and size (UPS,battery, generator, power distribution,transfer switch, computer room airconditioning)

    A summary load schedule for the LTswitchgearpanel.

    A loadscheduleforeachdistributionpanelsandswitchboard.

    Ratinganddimensionofbusbar.

    Alloutgoingcableswithcablesizeandtypewith rating and type of their associatedisolatingswitches(e.g.circuitbreaker).

    Length and voltage drop of all outgoingcables.

    RatingofPFI ,changeover,ATS,generatorswith associated protection and isolatingswitch

    Allearthingcablerating(size,typeetc.)

    Allconnectedloadwiththeirindividualloadcapacity.

    Allspareswitches(outgoingcircuitbreaker)shallbementioned.

    Earthing system must be included withdimension of earthing pit, boring, earthelectrodesize,earthleadandECCcablesizeandtype.

    Here isgivenanexampleofa typical LTpanelone linediagramor Single linediagram (try tofollowitasbestaspossible).

    ACCO

    RD

  • PROJECT NAME:

    DRAWING TITLE:

    Revisions

    Date No Descriptions

    Scale: Date:

    LOAD SCHEDULE & SINGLE LINE DIAGRAM OF SMDB-S (SECOND FLOOR)

    MEP CONSULTANT:

    Note:

    R=49.330 KWY=49.340 KWB=49.330 KWTL=148.000 KWDL=103.600 KW (70%)

    PROJECT NAME:

    DRAWING TITLE:

    Revisions

    Date No Descriptions

    Scale: Date:

    SINGLE LINE DIAGRAM OF SMDB-FOF FIRST FLOOR

    MEP CONSULTANT:

    Note:

    R=49.340 KWY=49.330 KWB=49.330 KWTL=148.000 KWDL=103.600 KW (70%)

    PROJECT NAME:

    DRAWING TITLE:

    Revisions

    Date No Descriptions

    Scale: Date:

    SINGLE LINE DIAGRAM OF SMDB-T OFTHIRD FLOOR

    MEP CONSULTANT:

    Note:

    R=19.720 KWY=19.720 KWB=19.720 KWTL=59.160 KWDL=41.412 KW (70%)

    PROJECT NAME:

    DRAWING TITLE:

    Revisions

    Date No Descriptions

    Scale: Date:

    LOAD SCHEDULE & SINGLE LINE DIAGRAMOF SMDB-Fr. (FOURTH FLOOR)

    MEP CONSULTANT:

    Note:

    R=49.330 KWY=49.330 KWB=49.340 KWTL=148.000 KWDL=103.600 KW (70%)

    PROJECT NAME:

    DRAWING TITLE:

    Revisions

    Date No Descriptions

    Scale: Date:

    LOAD SCHEDULE & SINGLE LINE DIAGRAMOF SMDB-Ff. (FIFTH FLOOR)

    MEP CONSULTANT:

    Note:

    R=49.340 KWY=49.330 KWB=49.330 KWTL=148.000 KWDL=103.600 KW (70%)

    M

    2x1c,120.0 mm2 Cu.

    R=273.465 KWY=273.220 KWB=272.445 KWTL=819.130 KW

    R=55.296 KWY=55.060 KWB=54.275 KWTL=164.630 KW

    PROJECT NAME:

    DRAWING TITLE:

    Revisions

    Date No Descriptions

    Scale: Date:

    LOAD SCHEDULE & SINGLE LINE DIAGRAMOF LT PANEL

    MEP CONSULTANT:

    Note:

    R=98.670 KWY=98.670 KWB=98.660 KWTL=296.000 KW

    R=98.670 KWY=98.660 KWB=98.670 KWTL=296.000 KW

    PROJECT NAME:

    DRAWING TITLE:

    Revisions

    Date No Descriptions

    Scale: Date:

    ELECTRICAL LOAD SCHEDULE & SINGLELINE DIAGRAM OF DB-R (ROOF FLOOR)

    MEP CONSULTANT:

    Note:

    BYR

    PHASE LOAD IN KW

    POINTPER

    WATT

    POINTSNO. OFPOINT REFERANCESIZE

    NUTRALPHASE

    RATMCB

    REF.CKT

    B3

    Y3

    R3

    B2Y2

    R2

    B1Y1

    R1

    TOTAL CONNECTED LOAD 8.015 KW

    DS13--DS18

    0.510DS7--DS12

    DS19--DS24

    10A SP

    DB REF. : DB-R | FED FROM : RYB9/MDB-1 | LOCATION : CANTEEN (ROOF FLOOR)

    REF.MCCB

    20A

    TP M

    CB M

    AIN

    2.460TOTAL PHASE LOAD 3.260 2.295

    (rm)SIZE

    EARTH

    (re)LOCATION

    2X2.5 1X2.5 DS1--DS6 CANTEEN 6 0.51085Amp

    0.510

    6

    6

    85

    85

    TOTAL DIVERSIFIED LOAD (70%) 5.610 KW

    06WAY (TP) 20A TP MCB MAIN | CABLE SIZE : 1X4c,6.0mm2 NYY/PVC+1X1c,6.0mm2 PVC S/C ECC

    CANTEEN

    TOILETS

    10A SP

    10A SP

    10A SP

    10A SP

    10A SP

    10A SP

    10A SP

    10A SP

    B4

    Y4

    R4

    STAIR LOBBY

    10A SP

    10A SP

    10A SP

    2X2.5 1X2.5

    2X2.5 1X2.5

    2X2.5 1X2.5

    2X2.5 1X2.5

    2X2.5 1X2.5

    2X2.5 1X2.5

    2X2.5 1X2.5

    2X2.5 1X1.5

    DS25--DS30

    DS31--DS36

    DS37--DS42

    DS43--DS48

    L1--L6+EXF1--EXF2

    L12--L19+F1--F3

    L20--L27+F4--F6

    L7--L11

    6 85

    6

    6

    85

    85

    6 85

    6

    6+2

    85

    25/100

    8+3 40/70

    8+3

    5

    40/70

    25

    0.510

    0.510

    0.510

    0.510

    0.510

    0.350

    0.530

    0.530

    0.125

    B5

    Y5

    R5

    CANTEEN

    20A SP

    20A SP

    20A SP

    2X4.0 1X4.0

    2X4.0 1X4.0

    2X4.0 1X4.0

    S1--S2 (RADIAL)

    S3--S4 (RADIAL)

    S5--S8 (RADIAL)

    2 200

    2

    4

    200

    200

    0.400

    0.400

    0.800

    B6

    Y6R6 SPARE

    S9--S12 (RADIAL)

    SPARE

    M.PRAYER ROOM

    F.PRAYER ROOM

    2X2.5 1X2.5

    2X2.5 1X2.5

    2X2.5 1X2.5

    CANTEEN

    CANTEEN

    CANTEEN

    CANTEEN

    CANTEEN

    CANTEEN

    F.PRAYER ROOM

    M.PRAYER ROOM

    20A SP 2X4.0 1X4.0

    20A SP - -

    10A SP - -

    - -

    4-

    200-

    0.800

    -

    -

    TP MCB

    20A

    DB-R6WAY

    TL=8.015 KWB=2.295 KWY=3.260 KW

    FED FROM RYB9/MDB-1

    6WAY, 20A TPN+E COPPER BUS BAR

    R=2.460 KW

    10A

    MCB

    SP

    10A

    MCB

    SP

    10A

    MCB

    SP

    10A

    MCB

    SP

    10A

    MCB

    SP

    10A

    MCB

    SP

    10A

    MCB

    SP

    10A

    MCB

    SP

    10A

    MCB

    SP

    10A

    MCB

    SP

    10A

    MCB

    SP

    10A

    MCB

    SP

    DS

    1--DS

    6

    DS

    7--DS

    12

    DS

    13--D18

    DS

    19--DS

    24

    DS

    25--DS

    30

    DS

    31--DS

    36

    DS

    37--DS

    42

    DS

    43--DS

    48

    L1--L6+EX

    F1--EX

    F2

    L7--L11

    L20--L27+F4--F6

    L12--L19+F1--F3

    DL=5.610 KW (70%)

    +1X1c,6.0mm2 PVC S/C ECC

    1X4c,6.0mm2 NYY/PVC

    20A

    MCB

    SP

    20A

    MCB

    SP

    20A

    MCB

    SP

    S5--S

    8 (RA

    DIA

    L)

    S3--S

    4 (RA

    DIA

    L)

    S1--S

    2 (RA

    DIA

    L)

    SP

    AR

    E

    S9--S

    12 (RA

    DIA

    L)

    SP

    AR

    E

    20A

    MCB

    SP

    20A

    MCB

    SP

    10A

    MCB

    SP

    1x1c ECC 240 mm

    2

    BYA/NYY (or

    10-12 mm dia bare copper wire

    1x4c 240 mm2 BYA/NYY1x1c ECC 240 mm

    2

    BYA/NYY (or

    10-12 mm dia bare copper wire

    1x1c ECC 240 mm

    2

    BYA/NYY (or

    10-12 mm dia bare copper wire

    600 A (adjustable)MCCB

    ACCO

    RD

    SHAHIN AZADStamp

    SHAHIN AZADTypewriterSAMPLE ELECTRICAL SINGLE LINE DIAGRAM (SLD