EXHAUST, SUPPLY AND OUTDOOR AIR ELEMENTS. VALVES. 500 on FIRE SAFETY SYSTEMS AND SHUTTER ELEMENTS. 516 on In order to prevent the spread of fire to adjacent floors and rooms in multi- storey buildings, openings for ventilation ducts that cross fire sections are to be equipped with shut-off elements. Helios offers these for a wide range of installations and all required classifica- tions. The development of acces- sories optimally tailored to the corresponding fan ranges is part of Helios' corporate philosophy. SHUTTERS. GRILLES. WALL AND ROOF DUCTS. Helios backdraught shut- ters, weather protection and ventilation grilles and roof and wall ducts are popular due to their pleasant shapes, practical handling and robustness. Noise-damping volume elements and volumetric flow stabilisers are simply pushed into the duct and are efficient solutions for reducing the sound level and to adjust or stabilise the air flow volume. 488 on The current ventilation valves with their award- winning design, innovative exhaust air elements for demand-based functionality, preliminary filter elements, poppet valves for supply and exhaust air operation and incoming air elements for the controlled supply of outdoor air. The Helios range has ideal solutions for any type of room and use. Accessories to optimally satisfy all building requirements. 487 Accessories Mechanical accessories

Transcript of Accessories to optimally

Page 1: Accessories to optimally

EXHAUST, SUPPLYAND OUTDOOR AIRELEMENTS. VALVES.

500on

FIRE SAFETYSYSTEMS ANDSHUTTER ELEMENTS.

516on

In order to prevent thespread of fire to adjacentfloors and rooms in multi-storey buildings, openingsfor ventilation ducts thatcross fire sections are tobe equipped with shut-offelements.Helios offers these for awide range of installationsand all required classifica-tions.

The development of acces-sories optimally tailored tothe corresponding fanranges is part of Helios'corporate philosophy.

SHUTTERS. GRILLES.WALL AND ROOFDUCTS.

Helios backdraught shut-ters, weather protection andventilation grilles and roofand wall ducts are populardue to their pleasantshapes, practical handlingand robustness.

Noise-damping volumeelements and volumetricflow stabilisers are simplypushed into the duct andare efficient solutions forreducing the sound leveland to adjust or stabilisethe air flow volume.

488on

The current ventilationvalves with their award-winning design, innovativeexhaust air elements fordemand-based functionality,preliminary filter elements,poppet valves for supplyand exhaust air operationand incoming air elementsfor the controlled supply ofoutdoor air.The Helios range has idealsolutions for any type ofroom and use.

Accessories to optimallysatisfy all building requirements.

487

Acce

ssor

ies

Mechanical accessories

Page 2: Accessories to optimally

488

� Special characteristics� Made of non-corrosive, weather

proof, long life and ultra-violetstable polymers, colour lightgrey (VK 160 in white).

� Resists most harmful atmo-spheres.

� External building cladding staysclean longer as air flow chan-nelled straight through the shut-ter.

� Easy and quick installation.� Flat design.� Attractive appearance.

� Pressure lossWhen selecting a fan the pres-sure drop of all components ofthe system like ducting andshutters must be considered.The diagram shows the resis-tance subject to air velocity.

� Model ranges

� AutomaticAir stream operated louvres in acompact flat design to coverexhaust air openings in walls.

� Automatic operation; opens andcloses when the fan is switchedon and off.

� Fixed to wall by means of fourconcealed holes in corners.

� Supplied in individual boxesincluding mounting materials.

� Maximum air flow velocity= 8 m/s.

� Sizes 630 and 710 have anadditional centre mullion to in-crease overall stability and sizes800 and 900 have two mullionsresulting in several louvre pan-els.

Larger sizes are available on request, also see custom models. 1) For specification, design and dimensions of smaller shutters see following page.

Automatic Manually adjustable Electric control Fits fan Dimensions Type Ref. no. Type Ref. no. Type Ref. no. nominal size mm A mm B mm C mm D mm E mm

VK 160 1) 0892 — — 1) 1) 150/160 190 190 25 131 131

VK 200 0758 RVK 200 0766 EVK 200 0774 180/200 240 240 28 193 167

VK 250 0759 RVK 250 0767 EVK 250 0775 225/250 290 290 28 243 217

VK 315 0760 RVK 315 0768 EVK 315 0776 280/315 340 340 28 293 267

VK 355 0761 RVK 355 0769 EVK 355 0777 355 390 390 28 343 317

VK 400 0762 RVK 400 0770 EVK 400 0778 400 440 440 28 393 367

VK 450 0763 RVK 450 0771 EVK 450 0779 450 490 490 30 443 417

VK 500 0764 RVK 500 0772 EVK 500 0780 500 540 540 30 493 467

VK 630 0836 EVK 630 0781 560/630 686 690 40 520 630

VK 710 0838 EVK 710 0784 710 785 785 40 771 685

VK 800 0839 800 876 885 40 862 785

VK 900 0841 900 1026 985 40 1012 885

Pressure loss diagramDpPa

c m/s

EVK 200 – 710VK 200 – 900 RVK

� Manually adjustableTo cover intake and exhaust airopenings in external walls.Compact flat design. Suitablefor reversible axial fans (intakeand extract) as air flow in eitherdirection is possible.

� Rattle-free and tight insulated, asthe louvres are closed by springforce via mullions.

� Manual operation by means ofpull cord via guide roller.

� Supplied with pull cord protec-tion, guide roller, fixing hook andmounting materials.

� Frames, louvres with axis andadjusting parts made of UV re-sistant, impact resistant polymerin light grey.

� Up to nominal size 500 the lou-vre has one centre mullion. Forlarger sizes (see “custom sizes“)the models have an additionalcentre mullion to increase overallstability and result in several lou-vre panels. Each part has a sep-arate pull cord.

� Electrically adjustableExternal shutters to cover intakeand exhaust air openings.

� Automatic operation linked withfan controller. It can be wired sothat the fan start is delayed untilthe shutter is fully opened.

� Control of fan and shutter viaremote switch to be installed onsite. The limit switch in servomotor connects the fan circuitwhen the shutter is fully opened.Max. current 1 A (ind.). Withhigher currents or 3 phase fansan auxiliary relay is required(contactor, Ref. no. 99611).

� If the fan is operated by a speedcontroller the shutter must becontrolled via a relay installed onsite.

� Ready for installation with a lead(5 x 1,5 mm2, approx. 1,5 mlong). Connection according towiring diagram no. 39 and 73.

� Water proof motor housing, pro-tected to IP 55, made of poly-mer; includes maintenance freegear box motor 230 V~, 50 Hz.

� Made of light grey polymer, rattlefree operation and tight closing.

Bef

estig

ung

Befestigung

Bef

estig

ung

Befestigung

EVKVK, RVK

Dim. in mm – see table Dim. in mm – see table

� AccessoriesAdapter F allows installation ofthese shutters (up to nominaldiameter 710) on circular ducting.For selection and specificationsee page 496.

Shutters

Fixing

Fixi

ng Fixi

ng

Fixing

Page 3: Accessories to optimally

489

Acce

ssor

ies

� Custom sizesThe shutter ranges

– automatic (airstream operated)– manually adjustable– electrical control

are available in project specificcustom sizes.

� The dimensions can be variedwithin steps of 50 mm. Anyrectangular portrait, landscapeor square dimensions are avail-able. The shutters are manufac-tured to order and are non ex-changable or returnable.Therefore the dimensions mustbe defined accurately.

� For more stability, an additionalvertical centre mullion is fittedover 40 cm louvre length anda horizontal centre mullion over100 cm louvre length.Large shutters are supplied insegments for stability and trans-port reasons and have to be as-sembled on frames.

� The maximum air flow velocityfor standard models is 10 m/s.

� All parts (frames, shutters andtheir stocks) made of light grey,high quality, UV resistant poly-mer.

Break-proof polymer, alpine white.Wiring diagram no. 479Voltage/Frequency 230 V~, 50/60 Hz Power consumption approx. 6 W

* low-cost bulk pack

Dim. in mm Type A B H Weight kg

VK 30/15 381 395 235 1.0

VK 40/20 473 485 285 1.3

VK 50/25 574 585 335 2.0

VK 50/30 574 585 385 2.2

VK 60/30 674 685 385 2.4

VK 60/35 674 685 435 2.6

VK 70/40 774 785 485 3.1

VK 100/50 1162 1176 585 5.5

VK 80/50 864 876 585 4.4

Type Ref. no. Colour Spigot Ømm Qty

VK 100 0757 white 100 1

VK 100 B 0765 brown 100 1

VK 100 VE* 0885 white 100 24

VK 125 0857 white 125 1

EVK 100, 150 VK rectangular ductVK 100, 125, 160

Type Ref. no. Spigot Ø mm Weight kg

EVK 100 0453 100 0,26

EVK 150 0251 150 0,44

Type Ref. no. Duct nominal size cm

VK 30/15 0735 30 x 15

VK 40/20 0874 40 x 20

VK 50/25 0875 50 x 25

VK 50/30 0876 50 x 30

VK 60/30 0877 60 x 30

VK 60/35 0878 60 x 35

VK 70/40 0879 70 x 40

VK 100/50 0881 100 x 50

VK 80/50 0880 80 x 50

Dim. in mm Type A Ø B C D

VK 100 140 98 15 28

VK 160 190 145 25 35

VK 125 160 120-125 20 30

Dim. in mm Type � A B C Ø D

EVK 100 140 58 38,5 97

EVK 150 190 62 43 145

Custom sizes

� Small automatic shuttersmade of polymer for Ø 100,125 and 160 mmAirstream operated louvres tocover exhaust air openings.

� Suitable as extract outlet ofsmall fans, cooker hoods, tum-ble dryers and others.

� Made of UV-resistant and im-pact resistant polymer.

� Fixing via spigot or masonryplugs. Sealing foam strip includ-ed in contents.

� Model range

� Small electric shutterTo cover intake and exhaust airopenings in all types of rooms.

� Attractive design blends into anydecor. The view into the duct isobscured even when the shutteris open.

� Maximum air flow velocityapprox. 6 m/s.

� Noise free operation with a 60second opening delay.

� Control via on/off switch, wiredin parallel by preference.

� Model range

� Rectangular shutterIn landscape format, to coverexhaust air openings in externalwalls.

� Dimensions fit Helios rectangularfan range.

� Automatic operation.� All parts made of high quality,

light grey polymer.� Fixing via dowels.� Maximum air flow velocity

= 10 m/s.

� Model range

VK 160 0892 white 150/160 1

Dim in mm – see tableDim in mm – see tableDim in mm – see table

� NoteOperating temp. EVK 100,EVK 150: 0 to + 40 °C, for allother polymer backdraughtshutters: – 30 to + 60 °C.

Small and rectangular shuttersCustom sizes

Page 4: Accessories to optimally

490

RSK

� Backdraught shutters RSKAutomatic shutters for in-ductinstallation.

� Prevents back draughts (extractof warm air or intake of cold air)when the fan is switched off.

� Automatic operation at low andhigh pressure (rotatable mountingposition) through spring blades.At horizontal air flow the rotationaxis must be in vertical position.If installed vertically it only operateswith rising air flow. To cover furtherrequests and severe conditionsuse RVS or RVM.

Pressure loss RSKDpPa

c m/s

Type Ref. Dim. in mm Wgt.no. Ø D L S kg

RSKK 100* 5106 97 57 2,0 0,1

RSKK 125* 5107 121 57 2,0 0,1

RSK 150 5073 149 100 1,25 0,5

RSK 160 5669 159 100 1,25 0,5

RSK 180 5662 170 70 0,5 0,3

RSK 250 5673 248,5 140 1,25 1,2

RSK 200 5074 199 140 1,25 1,0

RSK 315 5674 312,5 140 1,25 1,5

RSK 355 5650 352 160 0,75 1,3

RSK 400 5651 397 160 0,75 1,4

* made of polymer (temp. max. +70 °C).Remaining models made of galvanised steel,flaps made of aluminium and springs made ofstainless steel.

Automatic

Type Ref. no.

RVS 225 2591

RVS 250 2592

RVS 280 2593

RVS 315 2594

RVS 355 2595

RVS 400 2596

RVS 450 2597

RVS 500 2598

RVS 560 2599

RVS 630 2600

RVS 710 2601

RVS 800 2602

RVS 900 2603

RVS 1000 2604

Automatic backdraught shutterwith spring releaseFor all horizontal ducting and verti-cal with the air flow upwards i.e.blades opening upwards. Bladesopen in air flow direction auto -maticly by the airflow (fan opera-tion).The spring mechanism is outsidethe air flow. Closing force, fanpower and installation position canbe adjusted. Blades and casingmade of galvanised steel, at dia.225 – 560 mm blades are made ofaluminium. Flanged on both ends.Fixing holes DIN 24155, Pt. 2.Ambient temperature –30 to +100 °C

RVS RVM

Motorised1) Dim. in mm Weight

Type Ref. no. Ø D i.L. A B C L Ø LK kg

RVM 225 2575 225 – 95 130 300 259 3,3

RVM 250 2576 250 – 95 130 300 286 3,7

RVM 280 2577 280 – 95 130 300 322 4,2

RVM 315 2578 315 – 95 130 300 356 4,6

RVM 355 2579 355 – 95 130 300 395 5,3

RVM 400 2580 400 – 95 130 330 438 7,5

RVM 450 2581 454 15 95 130 330 487 10,7

RVM 500 2582 504 40 95 130 330 541 12,0

RVM 560 2583 560 65 95 130 330 605 16,4

RVM 630 2609 630 115 150 225 400 674 21,0

RVM 710 2610 710 155 150 225 400 751 28,0

RVM 800 2614 800 200 150 225 420 837 37,8

RVM 900 2615 900 250 150 225 420 934 42,3

RVM 1000 * 2616 1000 300 150 225 420 1043 47,81) Typen RVM not suitable for exlosion proof areas. * RVM 1000 only for horizontal through flow.

Pressure loss RVSDpPa

c m/s

Pressure loss RVMDpPa

c m/s

Dim. in mm – see table

RVE

� Air tight in-duct backdraughtshutter RVEIn-duct mounted, ideal for retro-fit installation.

� Polymer ring with surroundingdouble lip seal and tight adja-cent rubber membrane, whichopens at low and high pressure.

� Supplied with two membranes forair flow velocity up to approx.3.5 m/s or 6 m/s.

� At horizontal air flow the rotationaxis must be in vertical position.

� Temperature range –20 to +90 °C.

Type Ref. Dim. in mm Wgt.no. Ø D1 Ø D2 L kg

RVE 80 2584 75 83 20 0,1

RVE 100 2587 95 103 20 0,1

RVE 125 2588 120 128 20 0,1

RVE 160 2589 155 163 20 0,2

RVE 200 2618 195 203 20 0,2

Dim. in mm – see table Dim. in mm – see table Dim. in mm – see table

Motorised backdraught shutter1)As RVS, but with built-on springrelease motor (outside the air flow),can be installed horizontally andvertically in any direction. Electricalcontrol wired in parallel with thefan; for installation supplied with a0.9 m long lead, closed when cur-rentless. Ambient temperature –30 to +60 °CProtection to IP 54Voltage/Frequency 230 V AC, 50/60 HzPower consumption– to Ø 560 14 W– from Ø 630 6,5 WOpening time of flaps, approx. 75 sec.Wiring diagram no. 380.1

Pressure loss RVEDpPa

c m/s

�Type/Membr. thickness (mm)

Dim. in mm

� RVE 80-125/1,5� RVE 160/1,5 RVE 200/2� RVE 80-200/0,5

Backdraught shutters

Page 5: Accessories to optimally

491

Acce

ssor

ies

� Rain repellent grille RAGTo cover intake and exhaust airopenings in facades, made ofpolymer.

� Attractive, corrosion and weath-er resistant finish in light greycolour prevents rain, snow andinsects from entering the sys-tem.

� Frame with louvres made ofUVresistant, impact resistantpolymer. Mesh guard made ofgalvanised steel and coated withpolymer. Mesh size 8 mm.

� Simple (also available as surfacemounted or integrated incladding) installation via dowels(mounting materials included).With adapter F (accessory) alsosuitable for circular ducting.

RAG

Pressure loss RAGDpPa

c m/s

� Weather proof grille WSGIn square or rectangular land-scape format; to cover intake orexhaust air openings in facades.

� Attractive finish protectingagainst rain, snow and verminfrom entering the ducting. Suit-able for square, rectangular andcircular ducts.

� Solid construction made of alu-minium extrusion profile, naturalcolour, anodised.

� Installation: Flush mounted orintegrated in cladding.

� Fixed louvres and mesh guardbehind made of galvanisedsteel. Mesh size: 16 mm.

� The rectangular modelsfit the Helios rectangular fanrange and therefore can befitted to rectangular ducting.

Type Ref. no. Fits to Dim. in mm Weightfan nom. size spigot in mm � b � B kg

WSG 200 0117 180/200 � 200 195 271 0,8

WSG 250 0118 225/250 � 250 245 321 1,0

WSG 315 0119 280/315 � 315 310 386 1,5

WSG 355 0120 355 � 355 350 426 2,0

WSG 400 0121 400 � 400 395 471 2,5

WSG 450 0122 450 � 450 445 521 3,0

WSG 630 0124 600/630 � 630 625 701 4,0

WSG 500 0123 500 � 500 495 571 3,5

WSG 710 0125 710 � 710 705 781 4,5

Type Ref. no. Fits to Dim. in mm Weightnominal size duct in mm b B h H kg

WSG 100/50 0116 1000 x 500 996 1070 496 570 5,0

WSG 80/50 0115 800 x 500 796 870 496 570 4,0

WSG 70/40 0114 700 x 400 696 770 396 470 2,9

WSG 60/35 0113 600 x 350 596 670 346 420 2,4

WSG 60/30 0112 600 x 300 596 670 296 370 2,2

WSG 50/30 0111 500 x 300 496 570 296 370 2,0

WSG 50/25 0110 500 x 250 496 570 246 320 1,9

WSG 40/20 0109 400 x 200 396 470 196 270 1,2

WSG 30/15 0108 300 x 150 296 370 146 220 0,9

Pressure loss WSGDpPa

c m/s

WSG

Type Ref. to fan nominal size Dimensions in mm Weightno. mm � B C D E kg

RAG 200 0750 180/200 240 28 193 167 0,35

RAG 250 0751 225/250 290 28 243 217 0,45

RAG 315 0752 280/315 340 28 293 267 0,60

RAG 355 0753 355 390 28 343 317 0,75

RAG 400 0754 400 440 28 393 367 1,00

RAG 450 0755 450 490 30 443 417 1,35

RAG 500 0756 500 540 30 493 467 1,60

Dim. in mm – see table

Dim. in mm – see table

Weather grillesMade of polymer and anodised aluminium

Fixing

Fixi

ng

Page 6: Accessories to optimally

492

LGR

� Grilles LGRRectangular with adjustablelouvres.

� To cover rectangular intake or ex-haust air openings especially forflat ducting.

� Centrally adjustable louvres al-low the adjustment of air flowvolume.

� Corrosion resistant design madeof galvanised steel in a whiteepoxy finish.

� Includes mounting frame whichallows universal installation.When installing in thin walledducts it must be fixed with 4screws.

Type Ref. Fits nominalno. duct openings in mm

LGR 250/150 0927 228 x 128

LGR 450/150 0928 428 x 128

LGR 350/230 0929 328 x 208

LGR 450/230 0930 428 x 208

Type Free cross Dim. in mm Wgt.section cm2 B b kg

LGR 250/150 160 250 150 0,6

LGR 450/150 320 450 150 1,0

LGR 350/230 430 350 230 1,2

LGR 450/230 575 450 230 1,5

QVK

� Grilles QVKSquare, with adjustable louvres.

� To cover intake or exhaust airopenings with a square crosssection.

� Centrally adjustable louvres al-low the adjustment of air flowvolume.

� Corrosion resistant design madeof galvanised steel in a whiteepoxy finish.

� Includes mounting frame. There-by suitable for flush mountedwall installation and withoutframe suitable for fixing viascrews.

Type Ref. Fits up to fan sizeno. nominal size mm

QVK 200 0791 200

QVK 250 0792 250

QVK 315 0793 315

QVK 355 0794 355

QVK 400 0795 400

Type Free cross Dim. in mm Weightsection cm2 B kg

QVK 200 320 � 250 0,8

QVK 250 490 � 300 1,0

QVK 315 680 � 350 1,3

QVK 355 920 � 400 1,8

QVK 400 1190 � 450 3,2

54

G 200 0255 white 200

G 250 0256 white 250/280

Type Ref. no. Colour Fits tofan size mm

G 315 0798 white 315

G 355 0799 white 355

G 400 0800 white 400

G 500 0801 light grey 450/500

G 200 – 500

� Grilles G fixedTo cover vents on walls and ceil-ings.

� Made of high quality, UV-resis-tant and impact resistant poly-mer.

� Compact flat design. Simple fix-ing via mounting materials whichare included.

� Some models obscure view intoducting when installed.

Type Dim. in mm Wgt.� A B C D Ø kg

G 200 287 210 210 39 5,2 0,7

G 250 337 240 240 39 5,2 0,9

G 315 340 300 300 22 5,2 0,4

G 355 390 350 350 22 5,2 0,4

G 400 440 400 400 22 5,2 0,6

G 500 540 490 465 30 5,2 1,8

G 200 and 250

G 315 – 500

G 100, 160

Dim. in mm – see table

� Grilles G fixedTo cover and insert in circularvent openings.

� Made of high quality and impactresistant polymer. Corrosion re-sistant and therefore suitable forindoor and outdoor applications.

� Simple installation using rearconnecting sockets with conicalshape. Foam strip for air tightconnection is included. Fixed in-stallation is ensured via four cor-ner holes. Egg grille inserts caneasily be removed for cleaningeven when fixed.

Type Dim, in mm Wgt.� b � B C S Ø D kg

G 100 90 140 28 15 100 0,8

G 160 130 190 40 24 150 0,3

Type Ref. Nom. size Colour Qtyno. in mm

G 100 0796 90/100 white 1

G 100 B 0782 90/100 brown 1

G 100 VE* 0828 90/100 white 12

G 160 0893 150/160 white 1

� Model range

� Model range

� Model range � Model range

Dim. in mm – see tableDim. in mm – see tableDim. in mm – see table

Dim. in mm – see table

* low cost quantity pack

GrillesAdjustable and fixed

Page 7: Accessories to optimally

493

Acce

ssor

ies

� Model range � Model range

LGK 80 135 105 14 80

LGM 100 155 127 16 95

LGM 125 195 150 25 120

LGM 160 252 190 25 155

� Grilles LGWith pitched louvres to covercircular vent openings of Ø 80,100, 125 and 160 mm.

� High quality and attractivelydesigned cover.

� Pitched louvres obscure theview into ducting when installed.

� Made of corrosion resistant diecasting aluminium, powdercoated. Colour: White.LGK 80 made of high qualityand impact resistant polymer,Colour: White.

� Simple installation in ductingusing rear spigots fixing springsand sealing tape.

Type Dim. in mmA B C D

Type Ref. Weight no. in grams

LGK 80* 0259 120

LGM 100 0254 300

LGM 125 0258 450

LGM 160 0261 750

� Door grilles LTGFixed air transfer grilles for in-stallation into door leaves.

� Attractive and unobtrusive de-sign, made of high quality andimpact resistant polymer in lightgrey or brown.

� With wide surroundings andpitched louvres to obscure view.Only 3 mm visible thickness.

� Two telescopic parts.Installation: One element of thegrille to be pushed in from eitherside of the door. Pulled togetherand tightened by the fixingscrews.

Type Ref. Colourno.

LTGW 0246 white

LTGB 0247 brown

LG LTG

Dim. in mm Door leaf depth min. 30 mm

Pressure loss LGDpPa

V· m3/h

Pressure loss LTGDpPa

V· m3/h––– Supply ––– Extract

� LGK 80� LGM 100� LGM 125� LGM 160

� �� �

Dim. in mm – see table

* made of polymer

GrillesFixed

Page 8: Accessories to optimally

494

DN Roof outlet* Roof pantile*, Roof pantile for Connector

mm lead flat roof, alu.

Mains Type Ref. no. Type Ref. no. Type Ref. no. Type Ref. no.

100 DH 100 R 2014 UDP 100 R 2020 FDP 100 2024 STV 100 2026

DH 100 S 2015 UDP 100 S 2021

125 DH 125 R 2016 UDP 125 R 2020 FDP 125 2013 STV 125 2027

DH 125 S 2017 UDP 125 S 2021

160 DH 160 S 2019 UDP 160 S 2023 FDP 160 2025 STV 160 2028* R = Brick-red, S = Black

� Model range: Outlet, pantile, connector to be ordered separately.

Type FDH Ref. no. 1477Flat roof outletFor connection of vent openings, upto 160 mm diameter, via the roof.Made of weather resistant polymerwith a wide frame for fixing. Coldand heat resistant up to + 200 °C.Cowl can be removed by insertionof a supplied ladder strip or insula-tion material (on site) to prevent theoccurrence of condensation.

Pressure loss DHDpPa

c m/s

Roof appliances

DN mm Dimensions in mm

Mains A Ø B C D Ø E F

100 120 170 320 785 100 225

125 140 210 335 825 125 255

160 180 265 365 1113 160 345

� Dimensions: Roof outlet DH with roof pantile UDP or FDP

Roof outlet DH with roof pantiles FDP, UDP and connector STVFDH

Roof outlet DH The ideal solution for ventilationsystem, without static pressuredrop. Made of weather resistantpolypro pylene, removable exhaustoutlet with protection against driv-ing rain. Connection with ductingby means of the connector STV(accessory), which obstructs theescape of condensation at thejuncture. For the Installation of theroof outlet, the following roof pan-tiles should be used:– Roof pantile UDP, fits almost to

every brick model, in black orbrick-red. For roofs with inclina-tions of 25 – 45°.

Pressure loss FDH

V· m3/h

DpfaPa

r = kg/m3

Dim. in mm Dim. in mm – see tableDim. in mm – see table

DH + FDPDH + UDP

25-45°

– Flat roof pantile FDP made ofaluminium for flat roofs.

Roof outlet DHwith duct

Flat roof pantile FDP

Pitched roofpantile UDP

Connector STV

Roof appliances

Page 9: Accessories to optimally

495

Acce

ssor

ies

Roof and wall appliances SDH

Telescopic wall sleeveFor wall applications of supply andextract air ducting. Two telescopicpolymer sleeves can be adapted tosuit the wall thickness with airstream operated outdoor shutter orgrille. Internal spigot suitable forconnection of ducting.TMK 125/150 with stepped spigotin Ø 125, 150 and 160 mm.TMK 100 for duct Ø 100 mm.

Type TMK 100 TMK 125 / 150

Ref. no. 0844 0845

Dim. A mm 140 � 190 �

B max. 500 500

Ø D 100 125/150/160

� Model range and dimensions

TMK

Universal roof appliancesFor air inlet/outlet or for connectionto ducting of Ø 125 – 400 mm.Cowl brick-red or slate grey asoptional.A large leaded sheet allows adap-tation to all tile profiles on pitchedroofs. Also suitable for flat roofs.Carrier plate for fixing. All remain-ing parts made of galvanisedsteel.

DDF

Type1) Ref. Type2) Ref Dimensions in mm Weightno. no. A B C Ø D F G kg

DDF 125 1964 DDF 125 G 1848 124 200 328 125 500 400 4

DDF 160 1965 DDF 160 G 1849 135 248 396 160 500 400 4

DDF 200 1966 DDF 200 G 1850 185 333 495 200 600 600 8

DDF 250 1967 DDF 250 G 1851 185 333 495 250 600 600 8

DDF 315 1968 DDF 315 G 1852 197 420 666 315 600 600 9

DDF 355 1969 DDF 355 G 1853 350 550 900 355 900 750 17

DDF 400 1970 DDF 400 G 1854 350 550 900 400 900 750 171) Outlet brick-red painted (RAL 8012) 2) Outlet slate grey painted (RAL 7024)

� Model range and dimensions DDF

V· m3/h

Dim. in mm – see table Dim. in mm – see table Dim. in mm – see table

Pressure loss DDF at extract air

DpPa

Type SDH Ref. no. 1476Pitched roof outletUniversal design, suitable for mosttile profiles. The large leaded sheetallows adaptation to different tileprofiles. Cowl and mounting platemade of galvanised steel.Flexible polymer tube with steppedspigot for connection of all ductdiameters from 70 – 115 mm.Duct fixing via supplied hoseclamp.

Roof and wall appliances

Page 10: Accessories to optimally

496

� Flexible ducting for universaluse in the most industrial,commercial and domesticapplications such as generalventilation and air-conditioningtechnology, outlets of cookerhoods and tumble dryers etc.

Reducersmade of galvanised steel or poly-mer.*

Type AS 100 Ref. no. 5224Connection spigot square flange plate (102 x 102 mm)with circular spigots (50 mm long),made of polymer.To connect ducting (DN 100 mm)on flat surfaces.

Hose clamps A steel band with a snap on ten-sion lock. Supplied in quantities of10 pieces.

RVB 355 5991 355 RVB 400 5992 400

RVB 315 5999 315 RVB 250 5998 250 RVB 200 5997 200 RVB 160 5987 160 RVB 125 5995 125 RVB 100 5994 100RVB 80 5993 80Type Ref. no. Nominal Ø mm

Duct connectormade of galvanised steel.

TS 160 5805 160 TS 125 5720 125TS 100 1479 100Type Ref. no. Nominal Ø mm

T-piecesmade of galvanised steel.

SCH 200 5724 165 – 215 SCH 125/160 5723 115 – 165

SCH 315/355 5727 265 – 375 SCH 250 5725 215 – 265

SCH 400 5728 375 – 425

SCH 80/100 5722 80 – 115Type Ref. no. Nominal Ø mm

RZ 125/100* 5222 125 100 RZ 160/125 5729 160 125 RZ 160/150* 7684 160 150 RZ 200/160 5710 200 160

RZ 100/80* 5223 100 80

Type Ref. Nominal Ø reducedno. mm Ø mm

Type Ref. no. Nominal Ø mm Inner Ø mm Weight for 10 m Contents per unit

ALF 80 5711 80 80 1.2 10 m

ALF 100 5712 100 102 1.4 10 m

ALF 125 5713 125 127 1.9 10 m

ALF 160 5757 160 160 2.5 10 m

ALF 200 5715 200 203 4.8 10 m

ALF 250 5716 250 254 5.3 10 m

ALF 315 5717 315 315 9.3 10 m

ALF 400 5759 400 406 11.2 10 m

ALF 355 5758 355 356 9.7 10 m

� Special characteristics� Avoids storage, transportation

and capacity issues.� A carton of approx. 60 cm

length incorporates 10 mducting.

� Optimal in handling and finish.� Smallest possible bending

radius.� Super elastic, can be bent

repeatedly with no fatigue ofmaterial or leakage.

� Self extinguishing in the eventof fire.

� Specification� Two layers of polyester foil,

aluminium coated.� Incorporated spring steel spiral

for rigidity.� No toxic fumes in event of fire.� Temperature range from – 20 to

+ 100 °C.� Maximum pressure: 2500 Pa� Maximum allowed air flow

speed: 20 m/s.

� Adaption plate F tosquare shutters for circularducting / fans.

� Use: By using this adaptor, theshutter ranges VK, RVK, EVKand RAG can be mounted di-rectly to circular ducting or fanspigots (HQ / HW).

� Installation: The four holes in thecorners match the fixing pointsof the shutters. The circularspigot fits over the fan’s casingand is fixed with screws.

� Material: Made of galvanisedsteel.

F 200 0804 20 240 55 210

F 250 0805 25 290 55 259

F 315 0807 30 340 55 324

F 355 0808 35 390 55 364

F 400 0809 40 440 55 409

F 450 0810 45 490 55 460

F 500 0811 50 540 55 510

F 560/630 0257 63 685 55 570

F 6301) 0813 63 685 55 640

F 6302) 0826 63 685 55 630

F 7101) 0824 71 785 55 717

F 7103) 0825 71 785 55 710

Type Ref. Shutter Dim. in mmno. size cm � A B ØD. i. L.

1) For Type HQ 2) For Type HW3) For Type AVD DK

� Model range

TS RVB

Helioflex ALF ASAdaption plate F

RZ SCH

� A

Ø D i.L.

B

Duct componentsVentilation ducts and accessories

Page 11: Accessories to optimally

SVE 80 8309 80 50 32 0* 9.0 5.0 11.5 14.5 18.0 20.0 24.0

1 4.5 3.5 7.5 11.5 10.5 17.5 21.0

3 4.5 2.5 5.0 8.0 9.5 13.0 15.5

497

Acce

ssor

ies

Type Ref. no. for DN (mm) Thick. in mm Weight in g Holes 125 250 500 1000 2000 4000 8000

14 1.0 1.0 2.0 7.0 8.0 10.0 13.0

SVE 125 Number of holesPa

Pa

Pa

SVE 200 Number of holes

SVE 160 Number of holes

SVE

Pa

SVE 250 Number of holesPa

SVE 315 Number of holes

Pa

8 3.0 2.0 3.0 8.0 12.0 13.0 15.0

SVE 315 8315 315 75 690 0* 5.0 3.0 6.0 12.0 15.0 16.0 18.0

5 2.5 1.5 3.5 6.0 6.0 12.0 16.5

8 1.5 1.5 2.5 6.0 5.0 11.0 17.5

SVE 160 8312 160 50 140 1 7.0 4.0 9.5 12.5 16.0 17.5 22.0

5 3.0 1.5 2.5 9.5 8.5 14.0 14.5

8 2.0 1.0 1.5 7.0 7.0 13.0 13.5

SVE 250 8314 250 75 480 0* 4.0 3.0 7.0 13.0 18.0 18.0 17.0

5 2.0 2.0 5.0 9.0 13.0 15.0 15.0

10 2.0 1.0 3.0 7.0 11.0 14.0 13.0

3 3.5 2.5 5.5 8.5 8.5 14.5 19.5

5 2.0 2.5 3.0 8.5 8.0 13.5 19.0

SVE 200 8313 200 50 190 2 6.5 2.5 5.5 13.0 14.0 18.0 15.5

SVE 125 8311 125 50 70 2 6.0 5.0 5.0 12.0 12.5 19.0 21.0

Ordering data Insulation standard De dB bei Hz

SVE 100 8310 100 50 60 1 7.0 4.0 9.5 12.5 16.0 17.5 22.0

3 3.5 2.5 5.5 8.5 8.5 14.5 19.0

5 2.5 1.5 3.5 6.0 6.5 12.0 16.5

The innovative SVE elementshave low cost solutions for:– Air flow volume adjustmentand optimised distribution inducting system of centralisedventilation units.

– Sound level reduction throughabsorption of air flow and fannoises.

In order to increase the sound level reduction, several elementscan be mounted in series, oneafter the other. Two elementsvirtually doubling the insertionloss.

� Performance figures andinsulation standardsThe diagrams give an overviewabout air flow volumes andpressure levels according to thenumber of holes. The red linesand dB(A) values show the noiselevels of elements (LWA).The sound power levels for therelated frequency (noise level ofSVE elements) are available assum levels in the installationmanuals and operating instruc-tions. The values on the tablegive the insulation standard Defor the corresponding frequency.

� Material� Fire retardant foam material with

protection against mould.� Meets the requirements of the

emission category M1.� No harmful toxic fumes in event

of fire.� Complies with fire class B.

� Advantages� Cost effective solution for

prevention of noise transferin ventilation ducting systems.

� Simple installation throughinsertion into the ducting.

� Simple adjustment thanks topre-punched holes.

� Minimises the system costs byusing low cost ducting.

� Can be used with all types ofdampers,grilles and valves.

� Can be easily cleaned with avacuum cleaner.

� DeliveryEach element is delivered ina separate poly-bag.

� InstallationSVE to be inserted into theducting and a valve grille orexhaust element can be usedas wall termination. By removingthe elliptical plugs, the air flowcan be adjusted to the desiredvolume in accordance with thediagrams above.

* Minimum air flow volume ensured by lateral recesses

SVE 100 Number of holes

m3/hm3/hm3/h

m3/hm3/hm3/h

Noise level Noise level Noise level

EigengeräuschNoise levelNoise level Noise level

* *

SVE 80 Number of holes

m3/h

Pa *

Noise level

Sound insulation element SVEfor customised adjustment of air flow volumes

Page 12: Accessories to optimally

m3/h

VKH 250 250 245 127 500-700

498

VKH

Inner casing with adjustment unit

Adjustment unit

Stabiliser

Outer casing

rubber seal ring

Model range Dim. in mm Air flow range Type Ø nom. duct Ø D L m³/hVKH 80 80 76 55 15-50VKH 100 100 96 70 15-100VKH 125 125 120 86 100-180VKH 150-160 150-160 146 91 180-300VKH 200 200 190 91 300-500

� At the minimum static pressurelevel the butterfly valve opensthe cross section completely.

� The guiding cylinder is responsi-ble for an equal movement offlaps and controls therefore therelation between pressure andair flow volume.

� Installation� Simple insertion in vertical or

horizontal ducts, matchingnominal duct diameter.

� The direction shown for the airflow must be considered.

� Perfect fitting and tightness isensured due to textile sealingstrip.

� Easy change of air flow volumefor each diameter of VKH.Thereby the other system inletsand outlets are not affected.

� Automatic adjustment to giveconstant air flow volume overa wide pressure range.

� Quick installation.

� Made of flame retardant poly-mer, class B1 DIN 4102-1.

� Function� With an increasing pressure lev-

el the air flow velocity increases.The pressure against the butter-fly valve decreases the openingcross section and keeps the airflow volume constant.

Automatically achieving con-stant air flow volume the VKH isan easy and low cost solutionthat ensures a constant air flowvolume desired for a wide rangeof pressures.

� OperationSimply insert the automaticvolume stabiliser in the duct orduct components, either supplyor extract. The VKH gives thepreset air volume over a diffe-rential pressure range of approx.50 – 200 Pa.

� Advantages� Measuring and balancing on

building site omitted; thereby thesystem can be commissionedfaster.

� Secure and simple design.� Ensuring a constant air flow

volume, even at low counterpressure.

Ø 80 Ø 100 Ø 125 Ø 150-160 Ø 200 Ø 250 Selection chart

15-50 80/15-50 100/15-50 125/15-50

50-100 100/50-100 125/50-100 150-160/50-100

100-180 125/100-180 150-160/100-180 200/100-180

180-300 150-160/180-300 200/180-300 250/180-300

300-500 200/300-500 250/300-500

500-700 250/500-700

Air flow volume stabiliser VKHfor in-line installation

Fixing screw

L

D

Dim in mm – see table

Assembly

Flow rateadjustment scale

1 x D

3 x D

Installation supply:Discharge = 3 x D

Installation extract:Discharge = 1 x D

Page 13: Accessories to optimally

499

Acce

ssor

ies

Ref. Type Air flowno. volume* Sound Lw in dB(A) at

m³/h 50 Pa 100 Pa 150 Pa 250 Pa0001 VKH 80/15-50 15-50 25 29 32 35

VKH 100

VKH 125

Pressure difference in Pa

Air flow volume m

3 /h

Pressure difference in Pa

Air flow volume m

3 /h

Pressure difference in Pa

Air flow volume m

3 /h

Pressure difference in Pa

Air flow volume m

3 /h

Pressure difference in Pa

Air flow volume m

3 /h

VKH 200

VKH 80

VKH 150-160

* Tolerance range (50-250 Pa) for nominal air flow volume +/- 10%.

Air flow volume stabiliser VKHModel range – technical data

Pressure difference in Pa

Air flow volume m

3 /h

VKH 250

50 m³/h45 m³/h

30 m³/h25 m³/h

15 m³/h

100 m³/h

75 m³/h

50 m³/h

30 m³/h15 m³/h

180 m³/h

150 m³/h

100 m³/h

60 m³/h

15 m³/h

300 m³/h

240 m³/h

180 m³/h

120 m³/h

50 m³/h

500 m³/h

400 m³/h

300 m³/h

240 m³/h

100 m³/h

700 m³/h

550 m³/h450 m³/h

300 m³/h

180 m³/h

Ø 80 mm nominal duct diameter

Ref. Type Air flowno. volume* Sound Lw in dB(A) at

m³/h 50 Pa 100 Pa 150 Pa 250 Pa0002 VKH 100/15-50 15-50 25 29 32 350003 VKH 100/50-100 50-100 32 37 39 42

* Tolerance range (50-250 Pa) for nominal air flow volume +/- 10%.

Ø 100 mm nominal duct diameter

Ref. Type Air flowno. volume* Sound Lw in dB(A) at

m³/h 50 Pa 100 Pa 150 Pa 250 Pa0004 VKH 125/15-50 15-50 25 29 32 350005 VKH 125/50-100 50-100 32 37 39 420006 VKH 125/100-180 100-180 30 37 39 42

* Tolerance range (50-250 Pa) for nominal air flow volume +/- 10%.

Ø 125 mm nominal duct diameter

Ref. Type Air flowno. volume* Sound Lw in dB(A) at

m³/h 50 Pa 100 Pa 150 Pa 250 Pa0007 VKH 150-160/50-100 50-100 32 37 39 420008 VKH 150-160/100-180 100-180 30 37 39 420009 VKH 150-160/180-300 180-300 34 40 42 44

* Tolerance range (50-250 Pa) for nominal air flow volume +/- 10%.

Ø 150-160 mm nominal duct diameter

Ref. Type Air flowno. volume* Sound Lw in dB(A) at

m³/h 50 Pa 100 Pa 150 Pa 250 Pa0010 VKH 200/100-180 100-180 30 37 39 420011 VKH 200/180-300 180-300 34 40 42 440012 VKH 200/300-500 300-500 35 40 44 47

* Tolerance range (50-250 Pa) for nominal air flow volume +/- 10%.

Ø 200 mm nominal duct diameter

Ref. Type Air flowno. volume* Sound Lw in dB(A) at

m³/h 50 Pa 100 Pa 150 Pa 250 Pa0013 VKH 250/180-300 180-300 30 37 39 420014 VKH 250/300-500 300-500 35 40 44 470015 VKH 250/500-700 500-700 36 40 46 49

* Tolerance range (50-250 Pa) for nominal air flow volume +/- 10%.

Ø 250 mm nominal duct diameter

Page 14: Accessories to optimally

FILTER ELEMENTSATTENUATORS

504

Preliminary filter elementsprevent the build-up of fatand dust on extract air ele-ments and poppet valves,as well as in the ductingsystem.

Slide-in cross-talk soundattenuators reduce the noisefrom the ducting system andtelephony from one residen-tial unit to another.

VENTILATION ANDPOPPET VALVES

506on

The ventilation valves (DLV),the design of which has wonseveral awards, fit in beauti-fully and inconspicuously inany home atmosphere.

Conventional poppet valvesfor exhaust air and supplyair operation are ideally suit-ed for various industrial andcommercial applications.

OUTSIDE AIR FLOWSUPPLY ELEMENTS

512on

Outside air elements are themost efficient way of ensur-ing the scheduled supply ofair in compliance with thestandards. The number,size and placement of theelements are to be definedsuch that the required vol-ume can be dosed and canflow in without causing adraught. According to DIN1946-6, it should be takeninto account when sizingthe extract air elements thatan indoor pressure is notmore than around 8 Pabelow the outside pressure.

EXTRACT AIR ELEMENTS

501on

Alongside the fan, extractair elements form the basisfor demand-optimised func-tion in central ventilationsystems. By equippingthem with varying air flowvolumes or time, motionand moisture control fulfil,the innovative extract airelements (AE) from Heliosare ideal for fulfilling require-ments in this area.

The ideal solution for all types of room and use.

Exhaust air, supply air, outside air elementsand poppet valves

500

Page 15: Accessories to optimally

AE B 15/30* 2055 (without constant air flow control)

Acoustic data for extract air elements of series AEThe following sound levels are relevant for the extract air elements:– Sound power level for permanent air flow (Lw in dB (A))– Sound insulation between ducting system and ventilated room

(Dn,e in dB (A)).

This sound data is specified in the respective type table. They weremeasured according to the standard EN 13141.The sound insulation value can be increased by using attenuator “AESD”or “AESE” (accessories), which is to be positioned and simply insertedbehind the extract air element.Cross talk attenuators are available for further noise reduction (p. 505).

Differential pressure in Pa

AE 75

AE 45

AE 30

Air flow volume performance curve AE

Air

flow

vol

ume

m3 /

h

AE

Ordering data Sound power level Sound insulationLw in dB (A) Dn,e in dB (A)

100 Pa 130 Pa 160 Pa without withType Ref. no. AESD AESD

AE 30* 2030 30 33 36 60 641)

AE 45* 2031 33 34 37 56 631)

AE 75* 2033 35 36 39 57 641)

1) Equipped with attenuator AESD (accessories) * Air flow volume in m3/h

� OperationExtract air elements with self ad-justing constant air flow volumecontrollers are the ideal compo-nents for extraction in kitchens,bathrooms and toilets for centralventilation systems in houses.

� Advantages� Constant air flow volume be-

tween 40 and 160 Pa.� No need for adjustment or

balancing of the system.� Attractive design.� High quality construction in an

aerodynamic shape with lowsound levels.

� The cover and optimised heightof the inlet nozzle offer an air-tight seal against the wall.

� Easy cleaning without a risk ofair flow volume change.

� DesignExtract air element with mount-ing ring, ready to install, made ofwhite polymer to be inserted inducts with a nominal diameter of125 mm. A rubber seal on themounting ring to avoid leakage.As a result, the discolouration ofdecor is minimised.

� FunctionEnsures constant air flow volumeunder different pressure condi-tions between 40 and 160 Pa.

� DeliverySupplied as one element incl.mounting ring in separate polybag.

� Accessories� Attenuator AESD to be inserted

behind the element(Ref. no. 2059)

� Adapter filter element VFE 70(Ref. no. 2552).

Dim. in mm

� InstallationSuitable for wall and ceiling in-stallation. The mounting ring, tobe fixed via screws on duct orwall openings and the extract airelement to be inserted.For an equal inlet and outlet airflow a straight duct of at least300 mm is required.

SelectionExtract air elements only optimally perform the required function when theyare coordinated with the task. Use the chart below to select the correctextract element where the selection depends on volume and application.There is a choice of element designs, with constant air flow volume withand without on demand ventilation, with timer, motion or humidity con-trolled operation.

Type Ref. no. Type Ref. no. Type Ref. no.

* Air flow volume in m³/h

Bathroom WC Kitchen

AE 45* 2031 AE 30* 2030 AE 75* 2033

AE GB 20/75* 2036 AE GB 15/30* 2035 AE GB 45/120* 2038

AE GBE 30/60* 2047 AE GBE 15/30* 2044 AE GBE 45/120* 2048

Humidity controlled with variable, limited air flow volume, page 503

AE Hygro GBE 5/40/75* 2053 AE Hygro GBE 10/45/120* 2054

Constant air flow volume controller, self-adjusting

Two air flow volumes (std. and demand-based ventilation), constant air flow control, self-adjusting

Two air flow volumes with electrical timer (without constant air flow volume control)

Humidity controlled with electrically controlled on demand ventilation, page 503

AE Hygro 10/45* 2049

140

120

100

80

60

40

20

040 60 80 100 120 140 160

Two air flow volumes with electrical timer and motion sensor, page 503

501

Extract airelement AE

Noise reductionelement SVE

Fire protectiondamper ELS-D

Cold smoke shutterKAK

Acce

ssor

ies

AE FV 125 9478 AE FV 125 9478

With filter and air flow volume adjustment

Extract air elements AESelection chart, constant air flow volume elements

Page 16: Accessories to optimally

502

AE GBE

Air flow performance curve AE GBE Nom. air flow volume (m3/h)

� OperationExtract air elements for two airflow volumes (basic and boost)with self adjusting constant airflow volume controller are theideal components for extractionin kitchens, bathrooms and toi-lets for central ventilation sys-tems in houses.

� Advantages� Two air flow volumes for stan-

dard and demand-based venti-lation.

� Constant air flow volume be-tween 40 and 160 Pa.

� No need for adjustment orbalancing of the system.

� Attractive design.� High quality construction in an

aerodynamic shape with lowsound levels.

� The cover and optimised heightof the inlet nozzle offer an air-tight seal against the wall.

� Easy cleaning without a risk ofair flow volume change.

� Function AE GBThe self adjusting air flow vol-ume limiter keeps the adjustednominal air flow volume (be-tween 40 and 160 Pa) constant(see performance curve).Two control steps allow for stan-dad and demand-based ventila-tion.On/off switching of high air flowvolumes manually via pull cord.

� Design (AE GB, AE GBE)Extract air element with mount-ing ring, ready to install, made ofwhite polymer to be inserted inducts with nominal diameter of125 mm. The rubber seal on themounting ring avoids leakage ofair. As a result, dis-colouration ofthe decor is minimised.

� Accessories� Attenuator:

AE GB: AESD, Ref. no. 2059AE GBE: AESE, Ref. no. 2058

� Adapter filter elementAE GBE: VFE 90, Ref. no. 2553obstructs grease and dust de-posits on extract air elementsand in ducting.

� DeliverySupplied as one element incl.mounting ring in separate Poly-bag.

� OperationExtract air device with electrictimer for two air flow volumes(standard and demand-basedventilation).Ideal components for extractionin kitchens, bathrooms and toi-lets for central ventilation sys-tems in houses.

� Advantages� Two air flow volumes for stan-

dard and demand-based venti-lation e.g. via on-site switch.

� No need for adjustment orbalancing of the system.

� Attractive design.� High quality construction in an

aerodynamic shape with lowsound levels.

� The cover and optimised heightof the inlet nozzle offer an air-tight seal against the wall.

� Easy cleaning without a risk ofair flow volume change.

� Function AE GBEThe basic air flow is increased tothe higher level of air flow via aswitch on-site (by others). After30 minutes – regardless of theposition of the switch on-site –it automatically returns to “stan-dard ventilation”.230 V, AC 0.5 / 3 W, IP X1

Differential pressure in Pa Differential pressure in Pa

Air

flow

vol

ume

m3 /

h

Air

flow

vol

ume

m3 /

h

Air flow performance curve AE GB

� Installation (AE GB, AE GBE)AE GB for wall, AE GBE alsosuitable for ceiling installation.The mounting ring, to be fixedvia screws on duct or wall open-ings and the extract air elementto be inserted. For an equal inletand outlet air flow a straightduct of at least 300 mm is re-quired.

Dim. in mm Dim. in mm

Ordering data Sound power level2) Sound insulationLw in dB (A) Dn,e in dB (A)

100 Pa 130 Pa 160 Pa without withType Ref. no. AESD AESD

AE GB 15/30* 2035 27 31 34 60 641)

AE GB 20/75* 2036 27 30 33 57 641)

AE GB 45/120* 2038 33 34 37 56 631)

1) Equipped with attenuator AESD (accessories) 2) Values are valid for standard ventilation * Air flow volume in m3/h

Ordering data Sound power level2) Sound insulationLw in dB (A) Dn,e in dB (A)

100 Pa 130 Pa 160 Pa without withType Ref. no. AESD AESD

AE GBE 15/30* 2044 30 33 36 60 641)

AE GBE 30/60* 2047 27 30 33 57 641)

AE GBE 45/120* 2048 29 32 35 57 621)

1) Equipped with attenuator AESE (accessories) 2) Values are valid for standard ventilation

AE GB

Nom. air flow volume (m3/h)140

120

100

80

60

40

20

0

200

150

100

50

040 60 80 100 120 140 160 40 60 80 100 120 140 160

120

75

45

30

15

120

6045

30

15

� Upon requestType AE FV 125 Extract airelement filter and air flow volumeadjustment, Ref. no. 9478

Extract air elementswith two air flow volumes AE GB and AE GBE

Page 17: Accessories to optimally

� Delivery and installationSee description Type AE GB.

� Accessories� Attenuator AESE to be

inserted behind the element(Ref. no. 2058).

� Design, delivery andinstallationSee description Type AE GB.

� Accessories� Attenuator AESE to be

inserted behind the element(Ref. no. 2058).

� Adapter filter element VFE 90for installation in front of theelement (Ref. no. 2553).

� OperationExtract air device with motionsensor and timer for two airflows (standard and demand-based ventilation).Ideal for extraction in kitchens,bathrooms and toilets for centralventilation systems in houses.

� Advantages� Two air flow volumes for stan-

dard and demand-based venti-lation via integrated motion sen-sor.

� No need for adjustment orbalancing of the system.

� Attractive design.� High quality construction in an

aerodynamic shape with lowsound levels.

� The cover and optimised heightof the inlet nozzle offer an air-tight seal against the wall.

� Easy cleaning without a risk ofair flow volume change.

� DesignExtract air element with mount-ing ring, ready to install, made ofwhite polymer to be inserted inducts with nominal diameter of125 mm. The rubber seal on themounting ring avoids air leakage.As a result, discolouration of thedecor is minimised.

� Function AE BThe basic air flow is to be in-creased to on demand air flowvia an integrated motion sensor.After 30 minutes it automaticallyreturns to “standard ventilation”.Electrical supply through threebatteries (on site, model LR 03,1.5 V, operational life span ap-prox. 18 months).).

503

Acce

ssor

ies

AE B – with motion sensor AE Hygro – humidity controlled

Ordering data Sound power level2) Sound insulationLw in dB (A) Dn,e in dB (A)

Type Ref. no. 100 Pa 130 Pa 160 Pa without withAESE AESE

AE B 15/30* 2055 20 25 28 60 641)

1) Equipped with attenuator AESE (accessories) 2) Values are valid for standard ventilation

Dim. in mm

Ordering data Sound power level2) Sound insulationLw in dB (A) Dn,e in dB (A)

Type Ref. no. 100 Pa 130 Pa 160 Pa without withAESE AESE

AE Hygro 10/45* 2049 29 32 35 57 611)

AE Hygro GBE 5/40/753)* 2053 28 31 34 56 641)

AE Hygro GBE 10/45/1203)* 2054 29 32 35 56 621)

1) Equipped with attenuator AESE (accessories) 2) Values for standard ventilation3) For the performance curve of on demand ventilation see AE GBE left page * Air flow vol. in m3/h

Operation range AE Hygro

Relative humidity in %

� OperationThe humidity controlled extractair elements allow a variable airflow volume depending on therelative humidity. They are suit-able for the operation control ofextract air volumes in bathroomand kitchen for ventilation sys-tems in houses.

� Advantages� Automatically controlled air flow

volume depending on the rela-tive humidity between minimumand maximum limits.

� No need for adjustment orbalancing of the system.

� Attractive design.� High quality construction in an

aerodynamic shape with lowsound levels.

� The cover and optimised heightof the inlet nozzle offer an air-tight seal against the wall.

� Easy cleaning without a risk ofair flow volume change.

� Function AE HygroThe air flow volume is automati-cally controlled depending onthe relative humidity betweenminimum and maximum limits.Achieving the defined trickle airflow at ∆p of 80 Pa dependingon the relative humidity.No need for electric connection.

� Additional functionAE Hygro GBEThe basic air flow is increased tothe higher level of air flow via aswitch on-site (by others). After30 minutes – regardless of theposition of the switch on-site –it automatically returns to “stan-dard ventilation”.230 V, AC 0.5 / 3 W, IP X1

A

ir flo

w v

olum

e m

3 /h

Air flow performance curve AE B Nom. air flow volume (m3/h)

40 60 80 100 120

30

15

1600

10

20

30

40

50

60

140Differential pressure in Pa

Dim. in mm

10/45 m3/h

5/40 m3/h

Air

flow

vol

ume

m3 /

h

Extract air dev AE B with motion sensorAE Hygro with humidity control

Page 18: Accessories to optimally

504

� AbluVent ABV 100Can be used in central ventila-tion systems in accordance withDIN 18017-3 with variable airflow volumes. Demand-regulat-ed ventilation, e.g. for bath-rooms and toilets without win-dows. All elements in the sys-tem must have the same de-sign. Made of high quality poly-mer, colour: White.

� FunctionAbluVent is operated via a lightswitch. The louvres open whenthe room is in use. Standardventilation is provided when theroom is not in use, a low air flowis extracted when the louvresare closed.

� Advantages� Energy saving.� Low cost.� Quick installation.� Always an optimum solution.� Delayed closure of approx. 5

minutes.� Stepless adjustment of air flow

volume.� Noiseless operation.� Changeable filter to keep duct

system clean.

� Air flow volumeThe opening pitch of the louvrescan be set stepless between15 – 80 degrees (covered, insidefacia panel).

Dim. in mm

ABV 100

V· m3/h

50 321G *

G*= Std. ventilation, 0-5 = Slide positions

The diagram above shows theair flow in relation to the settingand negative pressure.

� Technical data – connectionThe unit is operated by a stan-dard on/off switch, ideally com-bined with a light switch. Supplyvoltage: ~220/240 V, 3 W. Dou-ble insulated, interference-free,protected to IP 44.Casing: polymer, alpine white.The thermal metal shutter workswith a short delay opening(approx. 30 sec.) and closingof (approx. 5 min.).

Type ABV 100 Ref. no. 0452

� AccessoriesType ELF/ABV Ref. no. 6906Spare filter mats.Contents = 5 pcs.

� Adapter filter element VFESimple and cost effective solu-tion for filtering greasy, contami-nated room air. To be installed infront of extract air elements orpoppet valves.

� OperationFilter element to cover air ventsand prevent dirt deposits frompoppet valves, extract air ele-ments and connected ducting.Ideal for use in the kitchen witha central ventilation system inline with DIN 18017.

� Advantages� Prevents grease and dust de-

posits from extract air elementsor poppet valves and connectedducting.

� Filter replacement in a few easysteps.

� The permanent filter can becleaned in a dishwasher.

� Discreet design in pleasantwhite.

� Simple installation via fourscrews.

� Hinders possible contaminationareas.

� Less maintenance cost of duct-ing through longer cleaning peri-ods

� CasingRobust casing made of gal-vanised sheet steel, white, pow-der coated polymer. The fasciapanel is pivotable at 90° andprevents the view into the filterand contamination area.

� FilterDimensionally stable aluminiumfilter fabric with 324 cm2 freefilter area and aluminium frame.

VFE

� InstallationSuitable for wall and ceiling in-stallation. Simply fixed with fourscrews. Elongated slot-fixingholes ensure easy positioning.To be fixed directly over the in-stalled extract air element (max.outer Ø 175 mm). Fascia panelis hinged at 90°; for easy filterremoval and a space betweenthe upper edge of the casingand the ceiling (see drawing) isnecessary.

� DeliveryEach element including installa-tion accessories is packed sep-arately.

� Delivery range

Type VFE 70 Ref. no. 2552Suitable for extract air elementswith max. 70 mm installation depthsuch as AE, MTVA, KTVA, BTV,BTK.

Type VFE 90 Ref. no. 2553Suitable for extract air elementswith max. 90 mm installation depthsuch as e.g. AE GBE, AE Hygro.

� AccessoriesType ELF/VFE Ref. no. 2554Spare air filter, suitable for thetypes VFE 70 and VFE 90.Contents = 2 pcs.

V· m3/h

DpPa

DpPa

VFE Pressure loss clean conditionABV Air flow volume adjustment

AbluVent ABVAdapter filter element VFE

Dim. in mm VFE 70, *VFE 90

Page 19: Accessories to optimally

505

Acce

ssor

ies

ETS

Installation example crosstalk attenuator ETS (sliced)

Attenuator ETS, installation with valveWithout cross talk attenuator, only with valve

ETS 125

ETS 100

Surprisingly simple and costeffective solution to reducenoise transmission in centralventilation systems. Easy installation direct intoducting behind the air valve.

� Advantages� Optimum solution for the pre-

vention of noise transmission inventilation ducting.

� Excellent attenuation figures(see diagram).

� Simple installation by insertinginto duct behind the air valve.

� Virtually no additional resistanceto the system, as the resistancevalue is below the setting valueof the valve.

� Minimising system costs byusing cost effective ducting.

� Can be used with any brand ofvalves.

Sectional view Horizontal system

� Delivery range

Type ETS 100 Ref. no. 4521Nominal duct Ø 100 mm

Type ETS 125 Ref. no. 4522Nominal duct Ø 125 mm

Cross talkattenuator ETS Poppet valve

Sectional view Vertical system

Cross talkattenuatorETS Poppet

valve� Attenuation figureThe attenuation figure can bedoubled if you have two facingrooms where both have an ETSattenuator in the ducting.

� MaterialFlexible polyurethane foam withimproved reaction in case of fire,complies with DIN 4102, classB1, UL-94-HF 1, MVSS 302among others.

Cross talk attenuator ETS

Poppetvalve

Cross talkattenuator

Verticalshaft

Page 20: Accessories to optimally

506

A

B D

C

Dim. in mm see table

DLVZ

� OperationFor supply air operation in allrooms without special fire pro-tection requirements.Ideal for wall installation closeto the ceiling with the air flowdirected into the room.

� Advantages� Elegant, square casing made

from high-quality polymer.� Air cone evenly streams to the

centre of the room.� Includes mechanically adjustable

volume controller for adjustingthe ventilation system.Accessible by removing thecasing, with location markers(stages 0 – 9, see diagram).

� Casing can be removed withouttools for the simple cleaning ofthe air-exposed valve parts.

� Sealing ring on spigot for pre-cise positioning and sealingin the ducting, prevents dis-colouration of the wall.

� Fixing holes in casing base forsecure fixation.

� DesignCasing design made from white,impact-resistant polymer.

� DeliveryValves individually packaged inpolybag, including setting con-trol (mountable if necessary) aswell as installation and operatinginstructions.

� Installation� Mount volume controller if nec-

essary. Pre-set air volume ac-cording to diagram.

� Position casing base in ventila-tion duct and fix to the wall.

Type DLVZ 100

Ø C 100

D 20

Weight in g 150

A 135

B 135

Ref. no. 3040

Ordering data

Dimensions in mm

55

10

10

30

30

60

5070

100

V m³/h

Pa Blendstufen 0-9

DLVZ 100 Supply air w/o filter

V· (m3/h)

Stagew/o adjust.panel

Panel stages 0-9 9 8 7 6 54321

0

Design ventilation valve DLVZfor supply air

� When adjusting the entire sys-tem, adjust any air volume set-tings.

� Upper part of casing attachablewithout tools.

� Performance dataThe diagrams provide anoverview of the air volumes andpressure losses for different vol-ume controller settings, as wellas the flow velocity of the out-flowing air at 30 m³/h in relationto the valve distance.

Distance [mm]

Air

flow

vel

ocity

[m/s

]

DLVZ 100

Page 21: Accessories to optimally

507

Acce

ssor

ies

10 1001

10

100

20 40

Pa

V m³/h

10 10040201

10

100

V m³/h

Pa

10 100

10

100

1

Pa

V m³/h20 50

10 1001

10

100Pa

V m³/h20 50

� DesignCasing design made from white,impact-resistant polymer.Elegant square appearance withclosed front panel.

� DeliveryValves individually packaged inpolybag, including G2 filter, in-stallation and operating instruc-tions.

� Installation� Place G2 filter in the filter holder.� Pre-set air volume according to

diagram.� Position casing base in ventila-

tion duct and fix to the ceiling.

B

A

D

C

DLV 100 Extract air w/o filter

Pa

Pa

Pa

Pa

DLV 100 Supply air w/o filter

Dim. in mm see table

DLV 125 Extract air w/o filter

DLV

Type DLV 100 DLV 125

Ø C 100 125

D 10-30 15-30

Weight in g 150 210

A 135 176.5

B 135 176.5

Ref. no. 3039 3049

Ordering data

Dimensions in mm

� OperationFor supply and extract air oper-ation in all rooms without specialfire protection requirements.Ideal for ceiling installation.

� Advantages� Elegant, square casing made

from high-quality polymer withcovered air intake and dischargearea.

� Precise air volume adjustmentby turning the elegant front pan-el in 90° stages, with locationmarkers for adjusting the ventila-tion system.

� Integrated filter exchangeablewithout tools and without risk ofchanging the setting.

� Selected air volume setting canbe locked.

� Minimum air volume also en-sured for fully closed air volumesetting. Full closure only by nurirreversibly removing the mini-mum air volume stop.

� Front panel can be removedwithout tools, with adjustmentmechanism and filter holder forthe simple cleaning of the air-exposed valve parts.

� Sealing ring on spigot for pre-cise positioning and sealing inthe ducting.

� Fixing holes in casing base forsecure fixation to the ceiling.

� Accessories

Replacement air filter class G2Contents: 5 pcs.

Type ELF-DLV 100 No. 3042

Type ELF-DLV 125 No. 3058

DLV 125 Supply air w/o filter

V· (m3/h)

V· (m3/h)

V· (m3/h)

V· (m3/h)

54321

5 4 3

21

5 4321

5 4321

Design ventilation valve DLVfor supply and extract air

� When adjusting the entire sys-tem, adjust any air volume set-tings.

� Front panel with adjustmentmechanism and filter holder canbe attached without tools.

� Performance dataThe diagrams provide anoverview of the air volumes andpressure losses for different frontpanel settings, as well as theflow velocity of the outflowing airat 30 m³/h (DLV 100) or 60 m³/h(DLV 125) in relation to the valvedistance.

Distance [mm]

Air

flow

vel

ocity

[m/s

]

DLV 100 – DLV 125

DLV 100

DLV 125

Page 22: Accessories to optimally

508

for DN (mm) 75/80 100 125 150/160 200

Ø A 73 – 85 95 – 105 120 – 130 150 – 165 195 – 205

Type MTVA 75/80 MTVA 100 MTVA 125 MTVA 160 MTVA 200

Ref. no. 8868 8869 8870 8871 8872

Ø B 108 135 160 195 230

C 15 15 15 15 18

D 58 59 60 58 63

Weight in g 150 190 255 340 450

Type EBR 75/80 EBR 100 EBR 125 EBR 160 EBR 200

Ref. no. 0952 0953 0954 0955 0956

Ordering data

MTVA 75/80

Pa

Pa

Pa

Pa

Pa

MTVA 125

MTVA 100

Air flow volume settingDistance A = in mm

Dim. in mm see table

MTVA 160

MTVA 200

MTVA

� OperationFor air extract in any room espe-cially where ventilation systemcomponents of non flammablematerials are required.Suitable for low and high airflow speed.Low noise characteristic.

� Advantages� Technically advanced design,

aerodynamically shaped for lowsound levels.

� Large cover with optimisedheight of the inlet ring avoidsmarking of decor.

� Quick mounting in ceiling andwall without tools.

� Plaster and difference compen-sation for unevenness, differ-ences in diameter or ductingthat has been too deeply plas-tered.

� Spring mounting clamp offers adirect insertion in ducts or wallsup to approx. 20 mm size with-out an additional mounting ring.

� DesignMetal construction protectedagainst corrosion by a highquality epoxy paint in white.The foam strip fitted around thevalve provides an air tight con-nection avoiding air leakage anddis-colouration around the valve.

� DeliveryEach valve is separately sup-plied in polybag.

� AccessoriesFor installation in ducting, wallsor thin panels, a mounting ringmay be required (see table).

� InstallationSet valve to required air flowvolume according to the dia-gram. The distance ‘A’ is givenin mm from the 0 point. Thensimply press valve into wall orducting.

� Performance dataThese diagrams show the rela-tionship between air flow vol-umes, resistances and soundlevels at various adjustments ofthe distance “A“ in mm.

Mounting ring

Dim. in mm

Metal valve MTVAfor extract air

Page 23: Accessories to optimally

509

Acce

ssor

ies

D 35 35 35 35 35

� OperationFor air extraction with highand low air flow speeds orresistances.For all rooms without specialfire protection requirements.

� Advantages� Installation without tools in

seconds.� High noise attenuation through

built-in attenuator in fan.� High quality anti static polymers

suitable for temperatures up to+100 °C.

� Using a mounting ring avoidsdis-colouration of surroundingdecor.

� Plaster and difference compen-sation for unevenness, differ-ences in diameter or ductingthat has been too deeply plas-tered.

� Spring fit connector allows directinstallation in ducting or wallwith a minimum thickness ofapprox. 20 mm without anadditional mounting ring.

� DesignAerodynamically shaped madefrom impact resistant white poly-mers. Adjustable air flow viarotating valve plate (volumethroughput see diagram).

� DeliveryEach valve is individuallysupplied in polybag.

� AccessoriesFor installation in ducting, wallsor thin panels, a mounting ringmay be required (see table).

� InstallationSet valve to required air flowvolume according to the diagramthrough core revolutions thensimply press valve into wall orducting.

� Performance dataThese diagrams show the rela-tionship between air flow vol-umes, resistances and soundlevels at various core openings.

Ø A 73 – 85 95 – 105 120 – 130 150 – 165 195 – 210

Type KTVA 75/80 KTVA 100 KTVA 125 KTVA 160 KTVA 200

Ref. no. 0940 0941 0942 0943 0944

Ø B 45 70 95 125 172

Ø C 120 145 160 195 240

Weight in g 90 115 150 200 340

Type EBR 75/80 EBR 100 EBR 125 EBR 160 EBR 200

Ref. no. 0952 0953 0954 0955 0956

for DN (mm) 75/80 100 125 150/160 200

Ordering data

KTVA 75/80 Core revolutionsPa

Pa

Pa

Pa

Pa

KTVA 125 Core revolutions

KTVA 100 Core revolutions

Dim. in mm see table

KTVA 160 Core revolutions

KTVA 200 Core revolutions

KTVA

m3/h

m3/h

m3/h

m3/h

m3/h

Dim. in mm

Mounting ring

Plastic valves KTVAsound-insulated, for extract air

Page 24: Accessories to optimally

510

� OperationFor air supply to any room espe-cially where ventilation systemcomponents of non flammablematerials are required.Suitable for low and high air flowspeed.Low noise characteristic.

� Advantages� High-quality metal design, aero-

dynamically shaped for lowsound levels.

� Large cover with optimisedheight of the inlet ring avoidsmarking of decor.

� Quick mounting in ceiling andwall without tools.

� Plaster and difference compen-sation for unevenness, differ-ences in diameter or ductingthat has been too deeply plas-tered.

� Spring mounting clamp offers adirect insertion in ducts or wallsup to approx. 20 mm size with-out an additional mounting ring.

� DesignMetal construction protectedagainst corrosion by a highquality epoxy paint in white.The foam strip fitted arround thevalve provides an air tight con-nection and avoids air leakageand dis-colouration around thevalve.

� DeliveryEach valve is separately suppliedin a polybag.

� AccessoriesFor installation in ducting, wallsor thin panels a mounting ringmay be required (see table).

� InstallationSet valve to required air flow vol-ume according to the diagram.The distance ‘A’ is given in mmfrom the 0 point. Then simplypress valve into wall or ducting.For an even air flow a straightduct of approximately 300 mmis required.

MTVZ

Dim. in mm see table

Ordering data

Type MTVZ 75/80 MTVZ 100 MTVZ 125 MTVZ 160 MTVZ 200

Ref. no. 9603 9604 9605 9606 9607

Dim. in mm

Ø A 73 – 85 95 – 105 120 – 130 150 – 165 195 – 210

Ø B 108 135 160 195 230

C 26 – 46 26 – 46 26 – 46 26 – 56 26 – 56

D 68 70 70 68 73

Weight approx. g 190 240 300 390 480

Mounting ring

Type EBR 75/80 EBR 100 EBR 125 EBR 160 EBR 200

Ref. no. 0952 0953 0954 0955 0956

for DN (mm) 75/80 100 125 160 200

MTVZ 75/80Pa

MTVZ 100Pa

MTVZ 125Pa

MTVZ 160Pa

MTVZ 200Pa

Air flow volume settingDistance A = in mm

� Performance dataThese diagrams show the rela-tionship between air flow vol-umes, resistances and soundlevels at various adjustments ofthe distance “A“ in mm.

Distance A = mm

Distance A = mm

Distance A = mm

Distance A = mm

Distance A = mm

Metal valve MTVZfor supply air

Page 25: Accessories to optimally

511

Acce

ssor

ies

� OperationFor air extraction with highand low air flow speeds orresistances.In all rooms without specialfire protection requirements.

� Advantages� Installation without tools in

seconds.� Elegant valve plate covering the

opening for stepless adjustment.Made from high-quality whitepolymer, suitable for tempera-tures up to +100 °C.

� Using a mounting ring avoidsdis-colouration of surroundingdecor.

� Plaster and difference compen-sation for unevenness, differ-ences in diameter or ductingthat has been too deeply plas-tered.

� Spring mounting clamp offers adirect insertion in ducts or wallsup to approx. 20 mm size with-out an additional mounting ring.

� DesignMade from impact resistant whitepolymers and aerodynamicallyshaped.Adjustable air flow via rotatingvalve plate (volume throughputsee diagram).

� DeliveryEvery valve is suppliedseparately in polybag.

� AccessoriesFor installation in ducting, wallsor thin panels a mounting ringmay be required (see table).

� InstallationSet valve to required air flowvolume through correspondingnumber of core revolutionsaccording to the diagram.Then simply press valve intowall or ducting.For an even air flow a straightduct of approximately 300 mmis required.The air flow can be directed ina defined direction through thetargeted placement of the pro-vided sealing element, e.g. to-ward centre of room.

� Performance dataThese diagrams show the rela-tionship between air flow vol-umes, resistances and soundlevels at various core openings.

KTVZ

Dim. in mm see table

Ordering data

Type KTVZ 80 KTVZ 100 KTVZ 125 KTVZ 160 KTVZ 200

Ref. no. 2762 2736 2737 2738 2739

Dim. in mm

Ø A 70 – 80 95 – 105 120 – 130 145 – 160 195 – 210

Ø B 80 138 170 195 235

Ø C 119 148 180 205 245

D 19,5 17 21 23 22

E 52 47 47 51 56

Weight approx. g 90 100 260 370 600

Mounting ring

Type EBR 75/80 EBR 100 EBR 125 EBR 160 EBR 200

Ref. no. 0952 0953 0954 0955 0956

for DN (mm) 75/80 100 125 150/160 200

V· (m3/h)

KTVZ 80 Core revolutionsPa

20 50 90

150

100

50

30

25

30

35

4 5 6 7

89

V· (m3/h)

KTVZ 100 Core revolutionsPa

V· (m3/h)

KTVZ 125 Core revolutionsPa

V· (m3/h)

KTVZ 160 Core revolutionsPa

V· (m3/h)

KTVZ 200 Core revolutionsPa

Fig.: Type KTVZ 100 – 200

Plastic valve KTVZfor intake air

Page 26: Accessories to optimally

512

� Special features – OperationInnovative thermostatic supplyair valve for automatic tempera-ture controlled replacement air.Efficiently combines energy sav-ings and permanent ventilation.Permanent control of supply airflow volume with adjustable corefor any type of room.Suitable for natural (thermal) andmechanical ventilation as supplyair element.

� Advantages� Fully automatic, demand-regu-

lated air flow control.� Maintenance free, no running

cost.� Individual air flow volume adjust-

ment by rotating the valve plate.� Good sound insulation due to

the attenuator built into the valveplate.

� Attractive, functional design.� Wide intake ring reduces wall

discolouration.� Quick and easy installation.

� DesignThe Helios supply air thermostatvalves are made of impact resis-tant, white polymer.Aerodynamically shaped and anattractive design. Insulated coat-ing on inner side of the valveplate to prevent condensation.

Ø A = Duct nominal size 80 100 160

Type ZTV 80 ZTV 100 ZTV 160

Ref. no. 0078 0073 0074

Ø B 77 95 156

Ø C 147 147 207

D 77 77 77

Weight approx. g 230 240 370

E 49 49 50

Dim. in mm

Ordering data

Pa

Pa Pa

ZTV 80

ZTV 100 ZTV 160

Summer operation

Winter operation

ZTV

Dim. in mm see table

Automatic change of core opening depending on outsidetemperature. – – – Totally closed without spacer ring.

Number of units with mechanical demand-based ventilation

II > 50, < 80 m2 3 4 2

Hotel room � 25 m2 2 – 1Apartment � 25 m2 2 (3) ** – 1

III > 80 m2 4 5 3

House up to 120 m2 4 5 3

* according to DIN 1946, T.6 tab. 10 ** if a kitchenette is also to be extracted

Flat I � 50 m2 2 3 – 4 2

Apartment size m2 Number of ZLA / ZLE FansExtract air (8 Pa)* Supply air (4 Pa)* Number/Unit

� InstallationZTV valves can be easily in-stalled in existing supply airopenings. They are fixed toducting by push fit (with rubbergasket) or by three concealedfixing holes in the frame suppliedwith fixing screws.

� FunctionThe thermostat operates auto-matically within a temperaturerange of –6 °C to +20 °C.Within this range air flow vol-umes between 0 and 30 m3/hare achieved conforming to DINguidelines. See performancediagrams on the right. In itsstandard setting the valve closescompletely at outside air tem-perature of approx. –4 °C.A minimum supply air rate isallowed by the 4 mm wide dis-tance clip. The initial setting ofthe valve can be changed man-ually by rotating the centre core.One full rotation equals to a vari-ance of 4 mm gap (see bluemarked areas in diagram).

� Number of unitsThe number of supply air ele-ments necessary is to be de-fined according to DIN 1946,T.6 depending on the apartmentsize and wind force (see charton the right).

Thermostat supply valve ZTV

Opening in mm

Outsidetemp. °C

Opening in mmOpening in mm

Page 27: Accessories to optimally

513

Accessories

Duct nominal size (mm) 80 100 160

Wall penetration Ø mm 96 115 175

Ordering data

Type ZLA 80 ZLA 100 ZLA 160

Ref. no. 0214 0215 0216

Volume max. with filter m3/h 25 35 100

Ø A mm 147 147 207

B mm 49 49 50

C mm 260–500 260–500 260–500

D mm 107 140 190

E mm 3 15 24

Weight approx. kg 0,7 0,8 1,6

Sound insulation value Dn,e 30 to 35 dB (depending on installation or wall thickness; corresponds to double glazing acc. to VDI 2719 protection class 2 or 3).

� FunctionThe thermostat operates auto-matically within a temperaturerange of –6 °C to +20 °C.Within this range air flow vol-umes between 0 and 30 m3/hare achieved conforming to DINguidelines. See performance dia-grams on the right. In its standardsetting the valve closes complete-ly at outside air temperature ofapprox. –4 °C. A minimum sup-ply air rate is allowed by the 4mm wide distance clip.The initial setting of the valve canbe changed manually by rotatingthe centre core. One full rotationequals to a variance of 4 mm gap(see blue marked areas in dia-gram).

� InstallationSuitable for wall or ceiling open-ings. Telescopic duct should beinserted from outside and thecover grille should be screwedon. Duct to be cleaned and thevalve to be inserted from inside.

� Special features – OperationUniversally adaptable tempera-ture controlled supply air unit.The energy saving, thermostaticsupply valve provides a continu-ous air exchange at highest effi-ciency.The supply air volume is con-trolled depending on the outsideair temperature, without anyelectrical connection. The supplyair is evenly distributed, filtered(class G 3) and attenuated.

� Advantages� Fully automatic, on demand airflow control.

� Maintenance free, no runningcost.

� Individual air flow volume adjust-ment by rotating the centralcore.

� Telescopic wall duct, made ofpolymer for wall thicknessesbetween 200 to 500 mm.

� High sound insulation via thebuilt-in attenuator.

� Easily removable filter.� No electrical supply required.� Quick and easy installation.

� Performance dataThe air flow volume dependingon pressure difference is determined by the opening gap of thevalve plate. The performancevalues can be seen from thediagrams above.

� Accessories

Spare filters class G 3Contents: 10 pcs.

Type ELFZ 80 Ref. no. 0339

Type ELFZ 100 Ref. no. 0340

Type ELFZ 160 Ref. no. 0341

Flow rate diagram

Flow rate diagram

Flow rate diagram

Wide inlet ring which preventswall discolouration

Automaticthermostatic valve

Insulation to avoidcondensation

Filter cartridgeeasy to change

Sound insulation toreduce the noisecoming from outside

External grille withremovable louvres

Telescopic wall duct200 – 500 mm

ZLA

Dim. in mm see table

ZLA 80

ZLA 100

ZLA 160

Automatic change of core opening dependingon outside temperature. – – – Totally closed without spacer ring.

� NoteThe number of supply air unitsis to be defined according toDIN 1946, T.6 (see chart on the left page).

Supply air device ZLAautomatic temperature controlled

with filter

without filter

with filter

without filter

with filter

without filter

Outsidetemp.°C

Volume

Page 28: Accessories to optimally

514

� Performance dataThe air flow volume dependingon pressure difference is deter-mined by the opening gap of thevalve plate. The performancefigures are shown in the diagramabove. Sound insulation rate:Dn,e: 30 – 35 dB (depending oninstallation and wall thickness;comparable with double glazingclass 2 or 3).

� Number of unitsThe number of required supplyair elements is to be definedaccording to DIN 1946, T.6independant to the apartmentsize and wind force (see thefollowing chart).

Type ZLE 100 Ref. no. 0079

� Special features – OperationManually operated supply airelement for any kind of room.The air flow volume can beadjusted through a four stepratchet mechanism using a pullcord. The supply air is evenlydistributed, filtered (class G 3)and attenuated.

� Advantages� Permanent intake air reduces

draughts.� Adjustable air volume controlled

by adjusting the valve plate.� Simple control via pull cord.� No electrical supply required.� Wide intake ring reduces wall

discolouration.� Telescopic wall duct, made of

polymer for wall thicknessesbetween 255 to 400 mm.

� Good sound insulation with thebuilt-in attenuator.

� Easily removable filter.� Quick and easy installation.

� InstallationSimple installation in wall open-ings. Insert the telescopic ductfrom outside, adjust to thicknessof wall and render.Push in rain repellent grille fromoutside, snap lock fixing or canbe screwed with masonaryplugs. Insert valve from inside.If placed near radiators the sup-ply air is preheated during thecooler periods. Ensure that valveis accessible for filter change.

Duct nominal size 100Wall penetration Ø 110 mm

� Accessories

Spare filter class G 3Type ELF/ZLE 100 Ref. no. 0338Contents = 10 pcs.

ZLE

� DesignZLE comes as a complete unitincluding:

� ValveAttractive, unobtrusive designmade of high quality white poly-mer. Incorporating a pull cord forthree core positions. Insulatedcoat on inner valve to preventcondensation.

� Telescopic wall ductTwo liners, made of impactresistant polymer.

� AttenuatorTo reduce air sound levels fromoutside.

� Air filterFor clean and dust free airsupply (class G 3), replaceable.

� Outside wall grilleFixed, rain repellent, made ofUV-stable polymer in white.

� Filter changeEasy, without any tool kit. Canbe maintained by removing thevalve.

Number of units with mechanical demand-based ventilation

II > 50, < 80 m2 3 4 2

Hotel room � 25 m2 2 – 1Apartment � 25 m2 2 (3) ** – 1

III > 80 m2 4 5 3

House up to 120 m2 4 5 3

* according to DIN 1946, T.6 tab. 10 ** if a kitchenette is also to be extracted

Flat I � 50 m2 2 3 – 4 2

Apartment size m2 Number of ZLA / ZLE FansExtract air (8 Pa)* Supply air (4 Pa)* Number/Unit

Supply air element ZLE

with filter

without filter

Page 29: Accessories to optimally

515

Accessories

ALEF ALEFSwith air flow volume control and limits similar to ALEF, extra attenuation

Application sample ALEFIn windows with aluminium frames

insideoutside

Air flow volume elements ALEFwith air flow volume control /limitation, to install in windowframes / casements.

� OperationThe window element flow is di-rectly related to the differentialpressure and supplies the out-side air to living rooms and bed-rooms. Simple installation, is al-so suitable for retro-fitting.

� DesignReady-to-install unit, containsinner facade with an auto maticair flow volume delimiter, installa-tion plate and cover strip.All parts are made of high quali-ty, white polymer.The models ALEFS have anacoustic element for an in-creased sound insulation.

� FunctionDue to the negative pressure ofextract air in the kitchen, bath-room and toilet, the element al-lows a certain amount of air flowvolume to enter in the living /bed rooms from outside (seediagram).

ALEF

Dim. in mm

� InstallationIn wooden, polymer and metalwindow frames. Openings bymeans of milling groups or holesin the upper frame. Simplyscrew the cover strip to the in-stallation plate and clip the innerfacade on.

Air flow vol. m³/h 30 45 30 45

Type ALEF 30 ALEF 45 ALEFS 30 ALEFS 45

Sound insulation Dn,e in dB (A) 39 37 41 39

Weight approx. g 190 190 210 210

Ref. no. 2100 2101 2102 2103

Ordering data Air flow volume elements to install in window frames

ALEF ALEF HygroFlow rate diagram

Flow rate diagram

Dp Pa

V.

m3/hALEF 45

ALEF 30

Dim. in mm

ALEF Hygro – humidity controlled

Humidity controlled air flowvolume elements ALEF Hygrowith air flow volume control /limitation to install in windowframes / casements.

� OperationWindow elements that allow acontrolled air flow volume, de-pendent on the humidity level inthe room, to enter in the living /bed rooms.Ideal in combination with humid-ity controlled extract fans. Sim-ple installation, is also suitablefor retro-fitting.

� DesignReady-to-install unit, containsinner facade with an auto maticair flow volume delimiter, installa-tion plate and cover strip.All parts are made of high quali-ty, white polymer.The models ALEFS Hygro havean acoustic element for an in-creased sound insulation.

� FunctionDue to the negative pressure ofextract air in the kitchen, bath-room and toilet, the element al-lows a certain amount of air flowvolume, which depends on thehumidity level in the room, toenter in the living / bed roomsfrom outside (see diagram).

� InstallationIn wooden, polymer and metalwindow frames. Openings bymeans of milling groups or holesin the upper frame. Simplyscrew the cover strip to the in-stallation plate and clip the innerfacade on.

ALEF Hygro – with humidity controlled ALEFS Hygroair flow volume control and limits similar to ALEF with extra attenuation

Air flow vol. m³/h 6/45 6/45

Type ALEF 6/45 Hygro ALEFS 6/45 Hygro

Sound insulation Dn,e in dB (A) 37 39

Weight approx. g 200 220

Ref. no. 2056 2057

Ordering data Air flow volume elements to install in window frames

Dimension opening andfixing in mm

V.

m3/h

Humidity level in %

ALEF ALEFSincreased sound insulation

ALEF Hygro ALEFS Hygroincreased sound insulation

Air flow volume element ALEF

Page 30: Accessories to optimally

516

Fire safety systems and shutter elements

Seal it up if there is a fire.

The aim of preventive firesafety in multi-storey buildingsis to prevent the spread of fireto adjacent floors and rooms.The construction ordinancestherefore divide apartmentunits or rooms into so-calledunits of usable area (fire sec-tion), the ceilings and walls ofwhich have to fulfil specificrequirements in terms of theirfire resistance duration.

As supply lines such as ventila-tion ducts cross fire sections,their openings are to be fittedwith shutter elements with therequired classifications.

Page 31: Accessories to optimally

Fire safety systems and shutter elements

517

Acce

ssor

ies

FIRE PROTECTIONDAMPERS,COLD SMOKEDAMPERS

FIRE PROTECTIONVENTILATION TILES

FIRE SAFETYSHUTTER ELEMENTS

FIRE SAFETYPOPPET VALVES

524

Fire safety ventilation tiles(BLS) enable the static ven-tilation of trapped personsto prevent the spread ofsmoke and fire to roomsand chambers to be pro-tected, such as installationshafts, cable channels andthe like.

518 520

Fire safety shutter elements(BAE/BAK) prevent thetransmission of fire andsmoke through ventilationducts or vents into otherfire sections.

Shutter elements with airflow volume throttling(BTV/BTK) to prevent thetransfer of fire and smokethrough ventilation ductsor vents.

Fire protection dampers(ELS-D) for ventilation ductsaccording to DIN 18017. Withtheir installation the use of fur-ther classified fire protectionelements on air intakes / ex-tracts is unnecessary. Idealfor installation shafts withmixed assignments (includingthose flammable ducting).

Cold smoke dampers (KAK)prevent the ingress of coldsmoke into other fire sec-tions. For room-side ductinsertion, positioning behindpoppet valves or extract airelements.

522

Page 32: Accessories to optimally

� DesignCylindrical duct sleeve withbutterfly shutter and integratedthermal coupling.

� DeliveryIndividually shrink-wrapped.

� Installation and setting� The installation and operatinginstructions contain the exactguideline relating to operationand installation.

� The specifications of the respec-tive approval must be observed.

� AccessoriesLimit switchTo control BAEand report itsoperating statusto the central building managementsystem. For mounting on all DN,simple snap-in mounting.Type BA-S Ref. no. 2585Switch as change-over IP 67max. load 5 – 250 V / 6 A (2 A ind.)Connect. cable 50 cm long / 3 x 0.34 mm²Wiring diagram no. 830

518

� Installation examples� Duct installationThe element is to be installedthrough simple insertion (e.g.in spiral ducting) and to befixed together with the duct inthe wall.Suitable for installation in bothdirections, independent from airflow direction.

� Wall installationVia mounting sleeve EH (acces-sory) in walls of brick, thermoliteblock or plaster panel, shaft par-tition walls in F 90 and F 30 orsystem tested walls with morethan 40 mm thickness.Suitable for installation in bothdirections, independent from airflow direction.

� Ceiling installation– Can be installed in non-fire-resistant suspended ceilings.

– Can be installed in fire-resistantceilings as a damper unless afree cross-section is required.

� OperationShutter to prevent fire andsmoke transmission. Suitable forinstallation in ventilation shaftsand ducting with required fireresistance class K 90-18017.Suitable for insertion into spiralducting or for wall installationwith mounting sleeve EH (acces-sories) and non-fire-resistantsuspended ceilings and fire-

resistant ceilings as a damper.

� FunctionWhen the ambient temperatureof +72 °C is exceeded, the inte-grated thermal coupling releasesthe spring loaded semicircleblades. Two safety bows inter-lock the shutter blades.

� Official approvalThe suitability of this shutter hasbeen tested for use in ventilationsystems to DIN 18017 and ap-proved with the German Institutefor Building Technology no.Z-41.3-696.

� Special features� Maintenance free.� Cleaning and inspectiontogether with the respective fan.

� Insertion in spiral ducting with-out additional wall mountingframe.

� Can be installed outside theshaft wall.

� For air flow in both directions,suitable for extract and supplyair systems.

� Lower flow resistance even withhigh air flow volumes.

� Can be connected to fumeextractors or cooker hoods.

� Low sound levels.� Can also be used for commer-cial applications e.g. internaltoilets, kitchenettes, etc.

BAE Approval Z-41.3-696maintenance-free

Pressure loss and acousticsPa

V· (m3/h)

Ordering data

Accessories:

Type Ref. no. Dim. in mm Weight Mount. Ref. no. Dim. in mmØ A B approx.kg sleeve Ø C Ø D E F

BAE 80 2624 78 60 0,17

BAE 100 2625 98 60 0,23 EH 100 2639 100 98 110 140

BAE 125 2626 123 60 0,30 EH 125 2640 125 123 110 140

BAE 160 2627 158 60 0,40 EH 160 2641 160 158 110 140

BAE 200 2628 198 60 0,55 EH 200 2642 200 198 110 140

Dim. in mm see table

BAE EH

Wall installation with mounting sleeve orspiral duct and plug-in supply / extract airelement.

Ceiling installation with mounting sleeveand plug-in supply / extract air element.Connection to mains through spiral ducting.

Duct installation

Spiral ducting

In-duct fire damper K 90-18017BAE

Page 33: Accessories to optimally

Acce

ssor

ies

519

� Installation examples� Duct installation in wallor ceilingThe element is fixed by insertinginto the spiral ducting or themounting sleeve EH (acces-sories) and then mounted to-gether to the wall, ceiling orshaft wall. Installation is inde-pendent from air flow direction.Completed with connection toducting on both ends of themounting sleeve.

� Wall installationVia mounting sleeve EH (acces-sory) in walls of brick, thermoliteblock or plaster panel, shaft par-tition walls in F 90 and F 30 orsystem tested walls with morethan 40 mm thickness.Suitable for installation in bothdirections, independent from airflow direction

� Overflow openingThe technical approvalZ-19.18-2180 regulates the useas a shutter for overflow open-ings.Suitable for installation in tubesleeves from spiral ducting ormounting sleeve EH (acces-sories).

In accordance with the EuropeanConstruction Products Regulation,fire dampers required an EC certifi-cate of conformity and declarationof performance since 01.07.2013.Helios BAK meet these Europeanrequirements.

� OperationShutter to prevent fire andsmoke transmission. Suitable forinstallation in ventilation shafts orwalls which serve as fire sectionwith required fire resistanceclass EI 90 S or K 90-4102.Suitable for wall and ceilinginstallation or as overflow open-ing. Suitable for insertion intospiral ducting. In case of one-sided duct connection, mount-ing sleeve EH (accessories)recommended.

� FunctionWhen the ambient temperatureof +72 °C is exceeded, the inte-grated thermal coupling releasesthe spring loaded semicircleblades. Two safety bows inter-lock the shutter blades.

� Official approval� With EC certificate of conformityand performance declarationaccording to European Con-struction Products Regulation305/2011.

� Test according to EN 1366-2.� Classified according toEN 13501-3: EI 90 (ve, ho, i1 o)S – (300 Pa).

� Corresponds to European Prod-uct Standard DIN EN 15650.

� General Technical Approval fromGerman Institute for BuildingTechnology with no. Z-19.18-2180 and Z-41.3-695.

� Special features� Insertion in spiral ducting inspace-enclosing component.

� For air flow in both directions,suitable for extract and supplyair systems.

� Lower flow resistance even withhigh air flow volumes.

� Simple fixing through mountingsleeve (accessory).

� DesignCylindrical duct sleeve withbutterfly shutter and integratedthermal coupling.

� DeliveryIndividually shrink-wrapped.

� Installation and setting� The installation and operatinginstructions contain the exactguideline relating to operationand installation.

� The specifications of the respec-tive approval must be observed.

� AccessoriesLimit switchTo control BAKand report itsoperating statusto the central building manage-ment system. For mounting on allDN, simple snap-in mounting.Type BA-S Ref. no. 2585Switch as change-over IP 67max. load 5 – 250 V / 6 A (2 A ind.)Connect. cable 50 cm long / 3 x 0.34 mm²Wiring diagram no. 830

Pressure loss and acousticsPa

V· (m3/h)

Ordering data

Accessories:

Type Ref. no. Dim. in mm Weight Mount. Ref. no. Dim. in mmØ A B approx.kg sleeve Ø C Ø D E F

BAK 100 2620 98 60 0,24 EH 100 2639 100 98 110 140

BAK 125 2621 123 60 0,32 EH 125 2640 125 123 110 140

BAK 160 2622 158 60 0,46 EH 160 2641 160 158 110 140

BAK 200 2623 198 60 0,64 EH 200 2642 200 198 110 140

Dim. in mm see table

BAK EH

Wall installation in brick, thermolite blockor plaster panel.

Ceiling installation in brick, thermolite blockor plaster panel.

Duct installationSpiral ducting

BAK Approval Z-19.18-2180EC certificate of conformity

BC1-606-0464-15650.69-2517

In-duct fire damper EI 90 S or K 90-4102BAK

Page 34: Accessories to optimally

520

� OperationShutter to prevent fire andsmoke transmission. Suitable forinstallation in ventilation shaftsand ducting with required fireresistance class K 90-18017.Suitable for insertion into spiralducting or for wall and ceilinginstallation by means of mount-ing ring (included in the delivery).

� FunctionWhen the ambient temperatureof +72 °C is exceeded, the ther-mal coupling trips. The built-inpressure spring closes the valveautomatically.

� Official approvalThe suitability of this shutter hasbeen tested for use in ventilationsystems to DIN 18017 and ap-proved with the German Institutefor Building Technology no.Z-41.3-694.

� Special features� Maintenance-free.� Cleaning and inspection togeth-er with the respective fan.

� Officially tested fire protectionvalve with low air noise at highpressure drop.

� Installation in spiral ducting,shaft walls or non-fire-resistantceilings.

� High attenuation value.� Attractive, functional shape.� Simple adjustment that cannotbe changed by unauthorisedperson reduces the amount ofwork.

� Can be easily removed only byauthorised person for mainte-nance and cleaning purposes.

� Wide operation range.� Can also be used for commer-cial applications e.g. internaltoilets, kitchenettes, etc.

� DesignSheet steel construction withwhite powder-coating.Aerodynamically designed withcenter core and bell mouth ring.

� DeliveryOne valve in a polybag incl.mounting ring made of gal-vanised sheet steel.

� Installation and setting� The installation and operatinginstructions contain the exactguideline relating to operationand installation.

� Fitted with one hand using thebayonet plug of the mountingring (included in the delivery).

� The specifications of the respec-tive approval must be observed.

� Air flow volume settings accord-ing to the adjacent diagrams.

� Setting stays fixed and cannotbe changed by an unauthorisedperson without dismantling thevalve.

BTV Approval Z-41.3-694maintenance-free

BTV 200 Core revolutionsPa

V· (m3/h)

BTV 125 Core revolutionsPa

V· (m3/h)

BTV 160 Core revolutionsPa

V· (m3/h)

BTV 100 Core revolutionsPa

V· (m3/h)

Ordering data

Mounting ring included in the delivery

Type Ref. no. Dim. in mm WeightØ A Ø B C D E approx. kg

BTV 100 2634 135 99 17 67 91 0,38

BTV 125 2635 161 124 18 68 103 0,48

BTV 160 2636 191 160 18 68 107 0,64

BTV 200 2637 242 199 17 67 124 0,77

Dim. in mm see table

BTV Installation in walls and non-fire-resistantceilings with mounting ring (included in thedelivery).

Fire protection valve K 90-18017BTV

Page 35: Accessories to optimally

Acce

ssor

ies

521

In accordance with the EuropeanConstruction Products Regulation,fire dampers required an EC certifi-cate of conformity and declarationof performance since 01.07.2013.Helios BTK meet these Europeanrequirements.

� OperationShutter to prevent fire andsmoke transmission. Suitable forinstallation in ventilation shafts orwalls which serve as fire sectionwith required fire resistanceclass EI 90 S or K 90-4102.Suitable for wall and ceiling in-stallation or as overflow opening.Suitable for insertion into spiralducting. In case of one-sidedduct connection, mountingsleeve EH (accessories) recom-mended.

� FunctionWhen the ambient temperatureof +72 °C is exceeded, the ther-mal coupling trips. The built-inpressure spring closes the valveautomatically.

� Official approval� With EC certificate of conformityand performance declarationaccording to European Con-struction Products Regulation305/2011.

� Test according to EN 1366-2.� Classified according toEN 13501-3: EI 90 (ve, ho, i1 o)S – (300 Pa).

� Corresponds to European Prod-uct Standard DIN EN 15650.

� General Technical Approval fromGerman Institute for BuildingTechnology with no. Z-19.18-2180 and Z-41.3-695.

� Special features� Insertion in spiral ducting inspace-enclosing component.

� Officially tested fire protectionvalve with low air noise with highpressure drop.

� High attenuation value.� Attractive, functional shape.� Simple adjustment that cannotbe changed by unauthorisedperson reduces the amount ofwork.

� Can be easily removed only byauthorised person for mainte-nance and cleaning purposes.

� Wide operation range.

� DesignPolymer valve body, optimumaerodynamical design withcentre core and bell mouth ring.Cylindrical duct sleeve withbutterfly shutter and integratedthermal coupling.

� DeliveryIndividually shrink-wrapped.

� Installation and setting� The installation and operatinginstructions contain the exactguideline relating to operationand installation.

� The specifications of the respec-tive approval must be observed.

� Installation examples� Duct installation in wallor ceilingThe element is fixed by insertinginto the spiral ducting or themounting sleeve EH (acces-sories) and then mounted to-gether to the wall, ceiling orshaft wall. Installation is inde-pendent from air flow direction.Completed with connection toducting on both ends of themounting sleeve.

� Overflow openingThe technical approval Z-19.18-2180 regulates the use as ashutter for overflow openings.Suitable for installation in tubesleeves from spiral ducting ormounting sleeve EH (acces-sories).

� AccessoriesLimit switchTo control BTKand report itsoperating statusto the central building manage-ment system. For mounting on allDN, simple snap-in mounting.Type BA-S Ref. no. 2585Switch as change-over IP 67max. load 5 – 250 V / 6 A (2 A ind.)Connect. cable 50 cm long / 3 x 0.34 mm²Wiring diagram no. 830

BTK

BTK 125 Core revolutionsPa

V· (m3/h)

BTK 100 Core revolutionsPa

V· (m3/h)

BTK 160 Core revolutionsPa

V· (m3/h)

BTK 200 Core revolutionsPa

V· (m3/h)

Ordering data

Accessories:

Type Ref. no. Dim. in mm Weight Mount. Ref. Dim. in mmØ A Ø B C D E kg sleeve no. Ø F G H Ø I

BTK 100 2633 150 98 19 129 20 0,45 EH 100 2639 100 110 140 98

BTK 125 2630 165 123 19 129 33 0,60 EH 125 2640 125 110 140 123

BTK 160 2631 220 158 19 129 51 0,85 EH 160 2641 160 110 140 158

BTK 200 2632 245 198 19 129 71 1,20 EH 200 2642 200 110 140 198

Dim. in mm see table

BTK EH

Fire protection valve EI 90 S or K 90-4102BTK

Approval Z-19.18-2180EC certificate of conformity

BC1-606-0464-15650.69-2517

Page 36: Accessories to optimally

522

According to building regulationsventilation ducts that cross morethan two storeys vertically must beprotected against fire and smoke.These conditions have beenfulfilled so far through installing theventilation duct in a fire proof shaft.This has some disadvantages suchas high investment cost, need oflarge space and longer buildingtime, especially the constructionof two shafts (separation of themixed installation shaft from theventilation shaft).

� The use of ELS-D firedampers results in variousbenefits such as:

� Ventilation ducting can beplaced in mixed instal lationshaft with simple, 12,5 mm thickplasterboard cladding.

� ELS-D are completely mainte-nance free. Additional fire resis-tant elements that might needmaintenance are not necessary.

� Allows the in-duct ventilationunits to be connected via Aluflexducting without fire protectionsheathing and fire protectiondamper.

� In central ventilation systems,the poppet valves or air flowcontrolling extract air elementscan be replaced with units madeof polymer. In order to avoidcold smoke cold smokedampers (KAK) to be used.

� The extraction of air fromkitchens is admissible.

� The constructional and function-al advantages of prewall installa-tions or registers can be uncon-ditionally implemented.

� Approximate reduction of thespace required to the DN ofthe main ducting through axialrotation during installation(width like narrow side forwardor diagonal).

� The full cross section of the ven-tilation duct remains, that meansno additional pressure drop.Cleaning and maintenanceworks are not hindered.

General Technical Approvalfrom DIBt with no. Z-41.3-368.Fire resistance class:K 90-18017 (three-storey test).

� SpecificationCasing made of galvanisedsheet steel with integratedspigot on top and bottom.The top spigot can also beused as ceiling lead through.

� Two stage function� The shutter closes first at ap-prox. 90 °C and prevents thetransmission of high tempera-tures to other storeys.

� At approx. 180 °C the integrat-ed fire rated foam seals the ven-tilation ducting completely abovethe shutter.

� InstallationELS-D can be easily installedsingle handed vertically againstthe bottom part of the floor slabor in installation registers. Thefire damper is to be fixed withtwo mounting fish plates, thatare held in grating and floorfinish.The ceiling leadthrough isalready integrated in ELS-D.Thanks to the standard connec-tion nozzles the main ductingcan be simply imposed and in-serted to the other side like afitting.

� AccessoriesCold smokedamperPrevents anyreverse flow ofcold smoke in central ventilationsystems and much else in otherventilation zones while the fan isnot working. (Not required in indi-vidual ventilation systems.)Type KAK 100 Ref. no. 4097DN 100 mmType KAK 125 Ref. no. 4098DN 125 mm

ELS-D

Dim. in mm

Approval Z-41.3-368maintenance-free

Legend 1 Fire damper ELS-D2 Ceiling grouting3 Installation shaft cladding e.g. 12,5 mm plasterboard panels

4 Main ducting (spiral duct)5 Connection ducting (Aluflex)6 Insulation against condensation7 ELS individual ventilation unitssurface of flush mounting withoutfire protection requirements

8 Central fan, e.g. DV EC (see page 65 on)

9 Cold smoke damper KAK10 Extract air element AE or poppet

valve (KTVA or MTVA)

System with in-duct fans

System with central fan

1 2

3

7

4

5

6

1 26

8

3

10

4

5

9

� NoteFurther sizes and product details for use of the cold smoke damper KAK.

see page 523

Ordering data

Type Ref. Dim. in mm Weight no. A B C Ø d Ø D E F H approx. kg

ELS-D 100 0270 183 123 385 99 102 50 250 85 2,5

ELD-D 125 0185 208 148 394 124 127 50 250 94 3,4

ELS-D 140 0186 233 163 403 139 142 50 250 103 4,0

ELS-D 160 0187 258 183 413 159 162 50 250 113 5,0

ELS-D 180 0188 283 203 424 179 182 50 250 124 6,0

ELS-D 200 0271 308 223 434 199 202 50 250 134 7,2

Fire protection damper ELS-DFor single and central ventilation systems K 90-18017

Page 37: Accessories to optimally

Acce

ssor

ies

523

The following is stipulated in theModel Building Regulation andvarious Regional ConstructionOrdinances:The spreading of fire and smokemust be prevented !The automatic Helios coldsmoke damper with magneticlock meets this requirement.They seal the supply or extractair system as required in fireregulations.

� ApplicationAccording to DIN 18017-3 thecentral extract ventilation sys-tems in multi-storey dwellingshave common mains and a cen-tral fan that is specified above orbelow the ceiling.The affiliated rooms (e.g. kitchen,bathroom, toilet) in the respec-tive storey ventilation zone) areventilated through the extract airducting. The mains cross multi-ple ventilation zones they mustbe led into a fire-resistant (F90classified) shaft. The extract airvents in each ventilation zonemust be equipped with firedampers or fire safety valves.These costly and space occupy-ing solutions can be replacedwith certified fire dampers whichare integrated or moulded onthe route of mains in the ceilingarea. Thereby the mains can beintegrated in the installationshaft.

Regional building regulations aswell as general technical ap-provals for shut-off elementsand fire dampers ensure that anexhaust air flow on the verticallyattached shut-off device in themains must always be securedto outside through the mains.The requirement becomes rele-vant, if the central fan breaksdown, in case of fire and the

smoke reaches to the mains inthe room due to excess pres-sure and also enters areas

(other ventilation zones) whichare not affected by fire due toupcoming air pressure throughopenings (poppet valves).

The Helios cold smokedampers KAK with magneticlock prevent cold smoke fromentering other ventilationzones. They must be posi-tioned in all supply / extractair vents behind the poppetvalves or extract air elements(also in combination withBAE/BAK).

� Design� Ready to install element forinsertion in ducting and fittings.

� Frames with surrounding U-lipseal ring made of EPDM gasketto seal the ventilation duct.

� Shutter frames on both sidesmade of polymer with metal in-sert encompass the siliconmembrane.Therefore the shutter sits quietlyin the air stream.

� A permanent magnet whichseals the shutter at low pressurelevels is located on a thread axisIn the inner cylinder frame.

� Closing and opening pressurecan be adjusted to the installa-tion circumstances.

� The very low installation depthand the asymmetric shape ofthe shutter frames, which ensurea big opening angle, are particu-larly beneficial.

� Installation and setting� While inserting KAK into ducting,the air flow direction must beconsidered.

� For vertical installation withhorizontal air flow, the horizontalpositioning of rotation axis mustbe considered.

� Positioning must be directly be-hind the poppet valve or behindthe air inlet /outlet.

KAK

Pressure loss diagramPa

V· (m3/h)

Ordering data

Type Ref. no. Dim. in mm Ø D A B

KAK 80 4096 79 12 63

KAK 100 4097 95 20 60

KAK 125 4098 120 20 83

KAK 160 4099 155 20 110

KAK 200 4100 196 20 150 Dim. in mm see table

KAK

System with central fan

1 26

7

3

9

4

5

8

Legend 1 Fure damper ELS-D

2 Ceiling grouting

3 Installation shaft cladding e.g. 12.5 mm plasterboard panels

4 Main ducting (spiral duct)

5 Connection ducting (Aluflex)

6 Insulation against condensation

7 Central fan, e.g. type DV EC (see page 65 on)

8 Cold smoke damper KAK

9 Extract air element AE or poppet valve (KTVA or MTVA)

� KAK 80� KAK 100� KAK 125� KAK 160� KAK 200

�����

Cold smoke damper KAK

Page 38: Accessories to optimally

524

Fire protection ventilation tileBLS

Fire protection ventilation tiles allow intake and extract ventila-tion in rooms and compartmentsprotected against fire and smoketransmission, such as installa-tion shafts and cable ducts.They enable a constant, static airchange, which prevents the heatbuild-up in the closed compart-ments.Furthermore, the tiles serve asair vent openings in the walls ofnecessary corridors (emergencyroutes), as long as the openingsare located on the lower part ofthe wall.

� Special featuresFire resistance class F 30 toF 120 conforms to DIN 4102part 2 (see the box on the right).

� BLS consists of intumescentpainted building material withDIBt approval.Furthermore, the regulations forthe use and installation of BLSshould be taken from thegeneral technical approvalno. Z-19.18-2065.

� Maintenance and inspection-free, no moving parts.

� Simple installation.� Resistant against humidity, mostoils, benzine and weak acids.

� During the installation processthe classification of buildingcomponents is not affected. Theventilation tiles are finished withorganic intumescent material,that foams up under the effectof heat. Openings, slots andjoints close and thereby preventfire and smoke transmission.

� Each brick is delivered with twoventilation grilles made of gal-vanised sheet steel.These should be attached oncethe tile is in position on one sideor both sides as mechanicalprotection and optical claddingdepending on the area of appli-cation, i.e. screwed to the con-struction (wall).

� Rectangular fire protection venti-lation tiles must be installed hori-zontally.

� In case of weaker walls, on-sitereinforcement with fibre silicateframes in area of BLS.

Installation in brick walls andconcrete walls F 30 – F 120

Installation in classifiedpartition wall and cableduct F 30 – F 120

Installation in classifiedpartition wall and cableduct F 30 and F 90

Product range, dimensions in mm

Ventilation tile Ins. opening Wt. Free cross- Cover grille

Ref. no. Type Ø D max. i.L. kg section cm² W H

2712 BLS 100 100 75 Ø 103 0.21 37 200 200

2715 BLS 125 125 75 Ø 128 0.50 56 200 200

2767 BLS 150 150 75 Ø 153 0.60 85 200 200

2718 BLS 160 160 75 Ø 163 0.67 102 255 255

2721 BLS 200 200 75 Ø 204 1.12 158 255 255

W H D W H

2766 BLS 100/100 93 93 75 103 x 103 0.38 35 200 200

2724 BLS 150/150 150 150 75 153 x 153 0.80 115 255 255

2727 BLS 200/100 186 93 75 203 x 103 0.75 69 305 155

2730 BLS 200/150 200 150 75 203 x 153 1.15 153 305 200

2733 BLS 300/150 300 150 75 303 x 153 1.56 230 405 205

Fire resistant Ventilation tile Thick. class installation in mm

F 30 Brick and concrete walls. 75Light partition and shaft walls,classified cable ducts.

F 90 / F 120* Brick-built and concrete walls. 75

Light partition wall, classified 75shaft walls and cable ducts.

Legend

� Brick wall

� Ventilation tile

� Ventilation grille, both sides

� Fibre silicate panels

Approval Z-19.18-2065BLS

� Air flow volumes – Differential pressure

V· (m3/h)

BLS / round

Pa

BLS / rectangular

Pa

V· (m3/h)

��

Dim. in mm

Dim. in mm

Dim. in mm

* Cover grilles on both sides

Page 39: Accessories to optimally

525

Measure. Control. Regulate.

Comfortably controlled and energy-saving.

MEASURE CONTROL REGULATE

The extensive MSR rangefrom Helios provides theideal solution for any appli-cation and simultaneouslymeets all requirements inrelation to energy savingand noise reduction.

Controlling ventilation andair conditioning systemsin accordance withchanging requirementsand conditions is a mustfor comfortable, energyefficient ventilation.

Changes in room occu-pancy, deteriorations inthe quality of air at differenttimes, fluctuating tempera-tures, day and night set-tings, etc. call for corre-sponding adjustments.Helios offers regulation,control and switch devicesfor all functions, which aretailored to the fans.

Complete system solutionsbring the maximum possiblesecurity for the user and fullguarantee by Helios.Furthermore, a lot of timecan be saved during plan-ning, installation and opera-tion if the control and regu-lation devices are perfectlyadapted to the fans andtheir functions.Problems are solved beforethey emerge.

Mea

sure

Cont

rol ·

Reg

ulat

e

Page 40: Accessories to optimally

526

Control. Regulate. Optimise.

Manual control of airflow volume

Overrun timer

Air quality –automatic system

Air flow velocity

Room temperaturedependant

Temperaturedifference dependant

Humidity dependantcontrol

Temperature,pressure, speedPressure dependantcontrol

Motor protectionagainst overload

Operation switch

Timer

� Manual speed controller– Without motor protection

– 10 V, 24 V DC – Potentiometer for EC fans PU /PA, SU /SA 541– 230 V~ – Electronic, flush / surface mounted ES, BSX 531– 230 V~ – Transformer, surface mounted TSW, TSSW 532– 400 V 3~ – Transformer, surface mounted TSD, TSSD 533– 230 V~ – Transformer, electronic, surface mounted ETW 535

– With built-in motor full protection for connection to thermal contacts– 230 V~ / 400 V 3~ – Transformer, surface mounted MWS / RDS 532 f.– 400 V 3~ – Electronic, surface mounted ESD 535– 400 V 3~ – Frequency inverter FU 536 f.

� Operation switch for fans with 2 speeds– Pole switch for Dahlander windings, flush / surface mounted PDA / PDU 529– Pole switch for separated windings, flush / surface mounted PGWA / PGWU 529

� Overrun switch Thermal electric, electronic, mechanic ZT, ZNE, ZNI,with adjustable and fixed times ZV 527

� Air quality sensor with on / off function dependingon room air quality ACL 543

� Air flow monitor for monitoring the minimum air flowvelocity in ducts and pipes SWE, SWT 543

� Ventilation thermostat – one step with on / off function TME 1 542– four step, mechanical TME 4 534– stepless, electronic EST 534

� Temperature controllers with integrated power unit, surface mounted– 230 V~ – electronic EUR 6 C 538– 230 V~ / 400 V 3~ – transformer KTRW / KTRD 534

� Differential temperature controller electronic,, stepless, with power unit– 230 V~ for surface mounting EDTW 543

� Humidistat with on / off function, surface mounted HY 3 542

� Fans for sanitary areas with integrated humidity control M1/.. F, ELS-VF 22,53

� Universal controller with power unit 230 V~ EUR 6 C 538with 0-10 V DC output, for EC fans EUR EC 539with power unit 400 V~ FU 536 f.

� Differential pressure controllers, surface mounted, with digital display– 0-10 V DC – electronic EDR 540

� Differential pressure switch for monitoring the air filters,system pressure and fan operation DDS 542

� Motor full protection switch to connect the thermal contacts for MD, MWmonitoring the windings temperature M 2, M 3, M 4 530

� Motor protection tripping unit for PTC – temperature sensor in windings MSA 530

� Reverse switch to change air flow directionof axial fans WS 528

� Isolation switch to disconnect all phases for service works RS, RHS 528 f.

� Pole / reverse switch as before, but for 2 speed axial fansPWGW, PWDA 529

� Weekly autotimer for automatic operation controlWSUP, WSUP-S 527

°C

°C

I 0

Task Helios controller solution Page

D Por°Corm/s

Pa

Page 41: Accessories to optimally

527

Type ZT Ref. no. 1277Thermal electric overrun timerwith adjustable run on time,depending on duty cycle.Optional delayed start via differentwiring options.In parallel wiring with light switchthe fan can be temporarilyswitched off via a series switch.

Variable run on time, depending onduty cycle.Min. approx. 2 min.; max. approx. 12 min.Optional delayed start (approx. 45 sec.)Voltage 230 V, 1~, 50/60 HzCurrent 4 A (ind.)Protection class IP 20 Dimensions mm W 32 x H 40 x D 14Installation flush mount box behind switchWiring diagram no. SS-174– when two rooms/switches are to be controlled SS-174.3

Type ZNE Ref. no. 0342Electronic overrun timer withstepless adjustable run on timesOperation via on / off switch,e.g. in combination with lightswitch.Compact design allows easyinstallation.

Stepless adjustablerun on time 0–21 min.Optional delayed start 45 sec.Voltage 230 V, 1~, 50/60 HzCurrent min. 0.05 A max. 0.8 A (ind.)Protection class IP 40Dimensions mm W 17 x H 37 x D 13Installation flush mount box behind switchWiring diagram no. SS-477.1– when two rooms/switches are to be controlled SS-174.3

Type ZNI Ref. no. 0343Electronic interval switch withadjustable interval and run ontimesStarts operation automatically atadjustable time intervals, if nomanual switching has taken place.If switched manually, e.g. lightswitch, the preset overrun timeapplies.

Adjustable interval time 0, 4, 8, 12, 24 hr.Run on time if manually switched,stepless adjustable 0–21 min.Optional delayed start 45 sec.Voltage 230 V, 1~, 50/60 HzCurrent min. 0.05 A max. 0.8 A (ind.)Protection class IP 40Dimensions mm W 17 x H 37 x D 13Installation flush mount box behind switchWiring diagram no. SS-477.1 – when two rooms/switches are to be controlled SS-174.3

Type ZV Ref. no. 1279Electronic overrun timer withstepless adjustable run on timesand operation switch with run ontime/continuous operation options.Parallel wiring to a light switch andfan is possible via an on / offswitch or push button.

Stepless adjustable run on time4 – 15 min.

Voltage 230 V, 1~, 50/60 HzCurrent 2,1 A (ind.)Protection class IP 20Dimensions mm W 18 x H 93 x D 67Installation terminal box,

35 mm sectional railWiring diagram no. SS-236.1

Type WSUP Ref. no. 9990Weekly autotimerDigital autotimer with LCD displayto automatically control any unit inaccordance with the technical da-ta. Suitable for switching the leastelectronic current from 1 mA /20 mV through a standard, gildedµ-contact. Installation in dry envi-ronment.

Voltage 230 V, 1~, 50 HzCurrent 1 mA / 20 mV DCSwitching contact potential-free changeover 250 V, 1~, 8 A cosj » 1, µ-contactProtection class IP 20 / IIDimensions mm W 85 x H 85 x D 52Installation surf. casing, flush boxTemperature range -10° C to +35° CMemory space (switching time) 42Wiring diagram no. SS-862

� Overrun timer for mountingin terminal box

� Weekly autotimerSurface mounted or in flushmounted box

Control cabinet installation

� Flush mounted overrun timerfor installation in gang boxesbehind a switch

Specially designed overrun timerfor bathroom and toilet. The com-pact design allows installation be-hind a switch within a single gangbox. Operation via on / off switchor ideally to be combined with alight switch in rooms without awindow. Can be individually adjust-ed through different timer varia-tions.

Interference immunity and emissionZT is designed with a thermal electric circuit,is immune against tolerable peak voltages andinterference-free. The interference immunityand emission of ZNE/ZNI comply with thelatest EN guidelines. ZV is tested as follows:Interference emission to DIN EN 55014 / VDE0875-14-1; DIN EN 50370 / VDE 0875-1;DIN EN 61000-3-3 / VDE 0838-3.

Type WSUP-S Ref. no. 9577Weekly autotimer for controlcabinet installationDigital autotimer with LCD displayto automatically control any unit inaccordance with the technical da-ta. Suitable for switching low-volt-age or low currents through astandard, gilded µ-contact.Installation in dry environment orwith occasional condensation.

Voltage 230 V, 1~, 50-60 HzCurrent 1 mA / 20 mV DCSwitching contact potential-free changeover

250 V, 1~, 16 A cosj » 12 A cosj » 0.6, µ-contact

Protection class IP 20 / IIDimensions mm W 36 x H 90 x D 69Installation DIN rail mounting

control cabinetTemperature range -30° C to +55° CMemory space (switching time) 56Wiring diagram no. SS-1038

Overrun timer

Mea

sure

Cont

rol ·

Reg

ulat

e

Page 42: Accessories to optimally

528

Reversing switch

For surface and flush mounting

Reversing, speed andon / off switch

Installation in FM switch box

Three speed and operatingswitch with 0 position

Installation in FM switch box

Speed, operation andreversing switch

For surface and flush mounting

Isolation switch– 3 pole with auxiliary contact for direct starting

Isolation switch– 6 pole with auxiliary contact for Dahlander windings or Y/D starting

Type WS Ref. no. 1271To change air flow direction of1 ph. and 3 ph. axial high perform-ance fans. Installation: Surface orflush mounted (switch box is in-cluded as standard). With screwfixing (M 3, 60 mm). Similar toproduct pages the units are speci-fied in the model chart.

Type DSEL 2 Ref. no. 13061. Speed changeover switchand on / off switch of fans withtwo speed steps such as ELS-V60/35, -VN 100/60.2. Reverse switch for changingthe air flow direction of reversiblefans (for supply and extract air)and on / off switch.Similar to product pages the unitsare specified in the model chart.

Convenient flush mounted speedswitch for fans with three speedsteps. Cannot be parallel wiredwith the light switchVoltage 230 V, 1~, 50/60 HzWeight approx. 0.1 kgType DSEL 3 Ref. no. 1611Can be used with the fan modelsELS-V 100/60/35 and ZEB 380. Type DSZ Ref. no. 1598Can be used with the centralextract air box ZEB EC.

Type FR 22/30 Ref. no. 0998Suitable for fan models GX 225or 300.For surface and flush mountedinstallation in dry rooms.Three sliding switches with follow-ing functions: Two pole operationswitch on/off with operating dis-play, high or low speed andreverse switch (supply/extract air).

Type RS 3+1 7.5 Ref. no. 6387Plastic casing for flush mounting.Locking options in position“0 OFF” and “I ON”.

Type RS 6+1 7.5 Ref. no. 6388Current 20 A, AC-23 B, 7.5 kWDimensions mm W 90.5 x H 90.5 x D 139Weight approx. 0.4 kg

Type RS 6+1 11 Ref. no. 6389Current 25 A, AC-23 B, 11 kWDimensions mm B 115 x H 115 x T 163Weight approx. 0.6 kg

Current AC 3 / 5.5 kW / 12 A (ind.) Voltage 230 V, 1~, 50/60 Hz

400 V, 3~, 50/60 HzProtection class IP 54

(when flush mounted IP 30)Wiring diagram no. SS-752Weight approx. 0.4 kgDimensions mm W 91 x H 121 x D 109– when flush mounted W 72 x H 72 x D 35 Casing polymer, light grey

Two switch rockers with symbolsfor speed change or reverse oper-ation delivered as standard. Colourpure white.Current 3 A (ind.) Voltage 230 V, 1~, 50/60 HzProtection class IP 30Installation in standard FM boxWiring diagram no. – two speed SS-827

– reverse operation SS-828Dimensions mm W 80 x H 80 x D 15Weight approx. 0.1 kg

Type DSEL 3Current 3 A (ind.)Protection class IP 30Installation in standard FM boxWiring diagram no. see fan modelDimensions mm W 80 x H 80 x D 23Type DSZCurrent AC 3 / 2,2 kW, AC 15 / 6 A Protection class IP 20Installation in FM box with 55 mm depthWiring diagram no. SS-735Dimensions mm W 80 x H 80 x D 23

Current approx. 0.8 A (ind.) Voltage 230 V, 1~, 50/60 HzProtection class IP 20Dimensions mm W 210 x H 85 x D 55Weight approx. 1.2 kgWiring diagram no. SS-497Casing polymer, white

Technical data Voltage 400 V, 3~, 50/60 HzOperating current 20 ACurrent AC-23 B, 7.5 kWProtection class IP 65Protection category IIActuation Rotary actuatorTemperature range -25 to +60 °CDimensions mm W 90.5 x H 90.5 x D 102Weight approx. 0.3 kgWiring diagram no. SS-1088Casing UV and weather-resistant

Technical data Voltage 400 V, 3~, 50/60 HzProtection class IP 65Protection category IIActuation Rotary actuatorLocking options “0 OFF” and “I ON”Temperature range -25 to +60 °CWiring diagram no. SS-1088Casing UV and weather-resistant

for surface mounting

Reversing, speed and operation switchesIsolation switches

Page 43: Accessories to optimally

529 Mea

sure

Cont

rol ·

Reg

ulat

e

Type RHS 3+1 Ref. no. 1594Position “0” is lockable via pad-lock. Conforms to DIN EN 60204T.1 / VDE 0113-1. Polymer casingfor surface mounting.3-pole isolator with additionalterminals, for single speed andspeed controlled fans.

Type RHS 6+2 Ref. no. 1595Position “0” is lockable via pad-lock. Conforms to DIN EN 60204T.1 / VDE 0113-1. Polymer casingfor surface mounting.6-pole isolator with 2 additionalterminals, for all pole changingfans.

Surface mounted operation switchfor pole changing fans.

1) For motors without thermal contacts: SS-732.

Pole switch PGWU /PDUFlush mounted operation switchfor pole changing fans.

1) For motors with thermal contacts; withoutthermal contacts: Connection to wiringdiagram no. SS-732.

Type PWGW Ref. no. 1281For separate windings

Type PWDA Ref. no. 1282For Dahlander windings

To switch speed and air flowdirection of individual polechanging fans.Grey polymer casing.

Type DS 2 Ref. no. 1351On / off and speed reversingswitch for two speed three phaseY/D-fans. Grey polymer casing forsurface mounting.

Type DS 2/2 Ref. no. 1267On / off and speed reversing switchfor two speed 1 ph. fans, RR andSlimVent SVR, SVS.

PDA 25 5060 AC 3/11 kW 25 A 7331)

Isolation /main switch– 3-pole with auxiliary contact

Isolation /main switch– 6-pole with 2 auxiliary contacts

Pole switches– for separate windings PGWA– for Dahlander windings PDA

For surface mounting

Pole switches– for separate windings PGWA– for Dahlander windings PDU

For flush mounting

Reverse and pole switch– for separate windings PWGW– for Dahlander windings PWDA

For surface mounting

Speed reversing switches DS 2

– for two speed three phaseY/D fans

– for two speed alternatingcurrent fans (SlimVent, RR)

Technical dataVoltage 400 V, 3~, 50 HzCurrent– Main contact AC 3 / 5.5 kW 12 A ind.– Aux. contact AC 3 / 2,2 kW 4 A ind.Protection to IP 54Dimensions mm W 101 x H 126 x D 104Weight approx. 0.35 kgWiring diagram no. SS-505.2

Technical dataVoltage 400 V, 3~, 50/60 HzCurrent AC 3 / 5.5 kW Protection to IP 65Dimensions mm W 82 x H 82 x D 125Weight approx. 0.3 kgWiring diagram no. SS-505.3

Technical data for all typesVoltage 400 V, 3~, 50/60 HzProtection to IP 65

Technical data for both typesVoltage 400 V, 3~, 50/60 HzProtection to IP 30Dim. mm Installation depth 87

Excess length 40Cover plate 80 x 80

Delivery incl. flush mounting boxWeight approx. 0.2 kg

Technical data for both typesVoltage 400 V, 3~, 50/60 HzCurrent AC 3 / 7.5 kW Protection to IP 55Dimensions mm W 96 x H 105 x D 147Weight approx. 0.5 kgWiring diagram no. for PWGW SS-13Wiring diagram no. for PWDA SS-11

Technical data for both typesVoltage 400 V, 3~, 50/60 HzCurrent AC 3 / 5.5 kW / 12 A Dimensions mm W 82 x H 82 x D 130Weight approx. 0.4 kgProtection to, Type DS 2 IP 65Wiring diagram no. for Type DS 2 SS-87

Protection to, Type DS 2/2 IP 54Wiring diagr. no. for Type DS 2/2 SS-939

Type Ref. no. Current SS no.

PGWA 12 5083 AC 3/5.5 kW 12 A 345

PGWA 25 5061 AC 3/11 kW 25 A 345

PDA 12 5081 AC 3/5.5 kW 12 A 7331)

For separate windings

For Dahlander windings

Type Dim. mm Weight B H T kg

P 12 82 82 130 0.4

P 25 92 92 140 0.5

Type Ref. no. Current SS No

PGWU 12 5084 AC 3/5.5 kW 12 A 345

PDU 12 5082 AC 3/5.5 kW 12 A 7331)

For separate windings

For Dahlander windings

Isolator / main switchesPole and reversing switches

Page 44: Accessories to optimally

530

For 1 ph. fanswith thermal contact leads wiredto the terminal block

Motor full protection switch MWin polymer casing for surfacemounting or installation in fuseboard (clamping assembly forsupport rail).

For 3 ph. fans with thermalcontacts

Motor full protection switch MOperation and full protection unitin polymer casing for surfacemounting or installation in fuseboard (clamping assembly forsupport rail).

For pole changing 3 ph. fanswith separate windingsand thermal contacts

Motor full protection switch M 2Switching and full protection unitin light grey polymer casing withcontrol lamp for surface mounting.

For pole changing 3 ph. fanswith Dahlander windings andthermal contactsMotor full protection switch M 3Design and functions as M 2.For two speed 3 ph. fans withY/D switching and thermalcontactsMotor full protection switch M 4Design and function as M 3.

For 3 ph. fans with built-inpositive temperature coefficientthermistors (PTC temperaturesensors) for thermal motorprotection. Specified for use inspeed controlled, explosionproof fans.

Motor full protection switch MSATripping unit with manual reset for1 to 6, PTC thermistors wired inseries.

Type MW Ref. no. 1579On/off operation via push-buttonswitch. Manual reset functioninterference.Volt free auxiliary contact for con-nection of failure indication alarm. 230 V, 1~, 50/60 Hz, applicable from 80 V Nominal current 0.4 to 10 AProtection to IP 55 Weight approx. 0.5 kgDimensions mm W 80 x H 140 x D 95Wiring diagram no. SS-517

Type MD Ref. no. 5849On/off operation via push-buttonswitch. Manual reset functioninterference.Volt free auxiliary contact for con-nection of failure indication alarm.400 V, 3~, 50/60 Hz, applicable from 80 VNominal current 0.1 to 25 AProtection to IP 55 Weight approx. 0.5 kgDimensions mm W 80 x H 140 x D 95Wiring diagram no. SS-518

Type M 2 Ref. no. 1292If the thermal contact opens themotor disconnects from the supply.Restarting after interference via“0“ position on the switch.

Voltage 400 V, 50/60 HzPower AC 3 / 5.5 kWNominal current approx. 12 AProtection to IP 55 Weight approx. 1.0 kgDimensions mm W 170 x H 135 x D 115Wiring diagram no. SS-142

Type M 3 Ref. no. 1293As M 2, but suitable for pole chang-ing 3 ph. fans with Dahlander wind-ings and built-in thermal contacts.Dimensions mm W 170 x H 135 x D 135Wiring diagram no. SS-143

Type M 4 Ref. no. 1571As M 3, but suitable for two speed3 ph. fans with Y/∆ switching andbuilt-in thermal contacts.Wiring diagram no. SS-144

Type MSA Ref. no. 1289For thermal protection of electricmotors (even explosion-proofelectric motors) according toDirective 2014/34/EU (ATEX)with integrated PTC temperaturesensors according to DIN 44081and DIN 44082.

Voltage 230 V ± 15 %, 50/60 Hz 3 phase operation via contactorCurrent at 230 V 3 A AC 15Connection options 1 to 6 PTC ther- mistors in seriesTested by Physikalisch-TechnischeBundesanstalt, according toDIN EN 60079-14 / VDE 0165-1,DIN EN 60079-0 / VDE 0170-1,DIN EN 60079-17 / VDE 0165-10-1.Protection to IP 20Weight approx. 0.2 kgDimensions mm W 35 x H 90 x D 58Wiring diagram no. SS-325.1

� Motor protectionRegulations and standardsThe harmonised Europeanstandards and national installa-tion directives require thermaloverload protection for electricmotors. This can be achieved invarious ways and depends onthe motor specification.

� Optimal protection is providedby thermal contacts (“TK” con-secutively), which monitor themotor winding temperature.These contacts protect alsothe speed controlled motors.

� For low motor powers, thethermal contacts are wired inseries with the motor windings,in other words, they are internal-ly wired. This ensures an auto-matic function (resetting aftercooling), without the operatorreacting necessarily on the inter-ference.

� For motors/ fans with higherperformances the leads of thethermal contacts or PTCthermistor-temperature sensorare wired to the terminal blockand must be connected to theadjacent motor full protection/tripping units. Only under thiscondition is the warranty claimvalid.

� Motors/ fans without thermalmonitoring elements in thewindings (e.g. IEC norm motors)must be secured on all poles bya suitable motor protectionswitch.

� Information PageTechnical information 15 onTransformer controllers withmotor full protection unit– for 1 ph. motors MWS 532– for 3 ph. motors RDS 533

Motor full protectionSwitches and tripping units

If the nominal response tempera-ture in PTC thermistors reaches aset limit the built-in relay discon-nects the motor. The fault is indi-cated by a light emitting diode.Restarting via pressing the “Reset”button or an external switch. Cas-ing made of polymer, suitable forfuse board installation on supportrail according to DIN EN 60715.

Page 45: Accessories to optimally

531 Mea

sure

Cont

rol ·

Reg

ulat

e

� Electronic speed controllerfor stepless speed controlof single phase fans

� Multiple, different fans can beoperated with a controller up tothe full load capacity. A reserveof 10% must be consideredwhen calculating.

� The minimum output voltagecan be adjusted to motor char-acteristics via potentiometer.Values must not fall below thelower limit for liquid motorstart-up!

� Overload protection from built-infine wire fuse.

� Additional connection of indica-tor lights or shutter possible viaunregulated output.

� Corresponds to EMC guidelines,DIN EN 50370, DIN EN 61000 /VDE 0838, DIN EN 55014,DIN EN 60669.

� Version ESU 1 and ESU 3A HELIOS innovation

� Both types are compatible withthe standard light switch pro-grammes of many manufac-

turers. Thus, the speed controller can

be integrated in the existingswitch programme on-site.Colour matching is also not aproblem. Frame, central insertand rotary knob are taken fromthe “dimmer programme“ of theswitch series and connected.

� Standard delivery includes: Controller insert, flush mounted

cover plate and rotary knobmade from white polymer.

� Operating display through cir-cumferential light ring on rotaryknob.

� Surface mounted models– Attractive, totally closed casing

of polymer.– ESA 1 and ESA 3 with

illuminated control knob.

� Important note� Only motors which are suitable

for speed control via electroniccontrol should be used.

� Electronic speed controllerswhich operate on the phasecontrol principle, can createhumming noises which canbe considered disturbing in thelower speed/voltage range.Silent transformer controllersshould be used for noise-criticalapplications.

For surface mounting230 V / 3 ph.

For surface mounting230 V / 1 ph.

For surface mounting,with reversing switch 230 V / 1 ph.Suitable for fan models:HVR 150/2 RE, REW 150and 200, range HV.H 200/4 and 250/4 andwindow fans GX.

For fuse board installation230 V / 1 ph.

Type ESU 1 Ref. no. 0236Max. load 1 AType ESU 3 Ref. no. 0237Max. load 2.5 A (T 40 E)White polymer casing. InstallationOperation display via illuminatedring.Minimum current 0.15 AProtection to (installed) IP 30Wiring diagram no. SS-556.1Dimensions mm W80 x H 80 x D 21 protr.

Type ESU 5 Ref. no. 1296Max. load 5 A (T 40 E)(for install. in lightweight walls 4 A)White polymer casing. The double-box required for flush mounting isincluded in the scope of delivery.Minimum current 0.2 AProtection to IP 20Wiring diagram no. SS-165Dimensions mm W 81 x H 152 x D 40

Type ESA 1 Ref. no. 0238Max. load 1 AType ESA 3 Ref. no. 0239Max. load 2.5 A (T 40 E)White polymer casing.Operation display via illuminatedring in control knob.Minimum current 0.15 AProtection to IP 40Wiring diagram no. SS-556.1Dimensions mm W 80 x H 80 x D 65

Type ESA 5 Ref. no. 1299Max. load 5 A (T 40 E)Light grey polymer casing, faciaplate anodied aluminium.Minimum current 0.2 A Protection to IP 44Wiring diagram no. SS-165Dimensions mm W 84 x H 170 x D 40

Type BSX Ref. no. 0240Max. load 1 A (T 40 E)Surface mounted speed controllerwith reversing switch for reversiblefans (intake/extract) in a whitepolymer casing. Only suitablefor fans, that are reversible viareversing switch.Minimum current 0.15 AProtection to IP 40Wiring diagram no. SS-480.2Dimensions mm W 80 x H 80 x D 65

Type ESE 2.5 Ref. no. 1302Max. load 2.5 A (T 40 E)For installation in fuse boards(35 mm standard buzzbar profileand for 68 mm built-in range).Minimum current 0.1 AProtection to IP 20Wiring diagram no. SS-376Dimensions mm W 50 x H 85 x D 60

(there from 10 mm protruding)

Electronic speed controllerfor 1 ph. fans, 230 V, 50/60 Hz

Page 46: Accessories to optimally

532

� Five step transformer speedcontroller for speed control-ling of 1 ph. alternatingcurrent fans

� Suitable for power control ofall speed controllable 1 ph.alternating current fans.

� Four secondary voltagesstepped in 80 / 100 / 130 / 170and 230 V (full mains voltage)allow to control 5 fan speeds.

� A number of different fans canbe connected to one controllerup to its nominal load.

� Advantages– Good cost effectiveness.– Reliable.– Low loss and low noise fan operation.– MWS-, TSW- (from the model

TSW 1.5) and STSSW modelswith full power output for con-nection with the signal lampor shutter.

� Design for surface mountingunits

– Robust ISO casing, light grey,made of impact resistantpolymer. Protection to IP 54.

– Built-in operating switch for fivespeed steps and on/off function.

– Operation display via controllamp.

– Fully impregnated transformersT 40 E.

– Conforms to DIN VDE 0550.– Max. permitted ambient

temperature +40 °C.– Delivered ready for installation,

simple connection to terminalblock.

� Design for built-intransformers

– Built-up terminal block for fivevoltage outputs.

– Attached fixing brackets forsimple fixture.

– Fully impregnated transformersT 40 E.

� AccessoriesSix step cam switch, modelSTSSW for switch boardinstallation, with front mountingplate.

For surface mountingMax. load 0.35 A1 ph. alternating current, 230 V

For surface mounting1 ph. alternating current, 230 V

For switchboard installation1 ph. alternating current, 230 V

With motor full protection facility1 ph. alternating current, 230 VFor surface mounting

Mini speed controller TSW 0.3Compact five step speed controllerwith on/off switch for surfacemounting in dry rooms. Polymercasing, white.

Type TSW 0.3 Ref. no. 3608max. load 0.35 AProtection to IP 20Dimensions mm W 160 x H 85 x D 60Wiring diagram no. SS-496.1

Transformer speed contr. TSWFor one or more alternatingcurrent fans.

Wiring diagram no. 1) SS-960 2) SS-437.1

Speed control transformerTSSWBuilt-in transformer with rail andterminals for 5 output voltages.

Wiring diagram no. SS-268

Five step operating switchSTSSW Accessory for controltransformer TSSW for 230 V, 1 ph.fans. For switchboard installationwith front fixing and front panel.Connections are deepened.

Type STSSW Ref. no. 0234Voltage AC 3, 230 Vmax. load 2,2 kWInstallation depth 70 mm, 46 mmWiring diagram no. SS-548

Transformer speed controllerMWS with motor full protectionfacility Five step speed controller withintegrated tripping unit for 230 V,1 ph. fans.To connect thermal contacts wiredto the terminal box. A number offans can be controlled up to thenominal load.If a thermal contact trips all fanswill be disconnected.Step switch and control lamp in-cluded. Restarting via “0” positionafter interference or power cut off.

Type Ref. I max. Dim. in mmno. A B H T

TSW 1.51) 1495 1.5 154 200 79

TSW 3.01) 1496 3.0 154 200 148

TSW 5.02) 1497 5.0 200 254 167

TSW 7.52) 1596 7.5 200 254 167

Connection according to wiring diagram no. SS-440.4

Type Ref. I max. Casing IP 54 Dimensions in mm Weightno. A made of W H D kg

MWS 1.5 1947 1.5 Polymer 200 254 98 3.0

MWS 3 1948 3.0 Polymer 200 254 98 4.0

MWS 5 1949 5.0 Polymer 200 254 167 5,3

MWS 7.5 1950 7.5 Polymer 236 316 188 10.0

Type Ref. I max. Dim. in mmno. A B H T

TSSW 1.5 6520 1.5 78 90 78

TSSW 3 6521 3.0 84 94 92

TSSW 5 6522 5.0 105 111 87

TSSW 10 6523 10.0 120 122 112

TSW 10 2) 1498 10.0 200 254 167

MWS 10 1946 10.0 Polymer 236 316 188 13.5

H

B

Transformer speed controllers with and without motor full protectionfor 1 ph. alternating current fans, 230 V, 50/60 Hz

Page 47: Accessories to optimally

533 Mea

sure

Cont

rol ·

Reg

ulat

e

� Five step transformer speedcontroller for speed control-ling of 3 ph. alternatingcurrent fans

� Suitable for speed control of allspeed controllable 3 ph. alter-nating current fans, for Y/∆reversible switching models inhigher steps.

� Four secondary voltagesstepped in 80 / (115)* / 140 /200 / 280 and 400 V (full mainsvoltage) allow to control 5 fanspeeds.* On TSD internally adjustablefor voltage controllable, explo-sion proof in-duct and roof fans.

� A number of different fans canbe connected to one controllerup to its nominal load.

� Advantages– Good cost effectiveness.– Reliable.– Low loss and low noise fan

operation.– RDS-, TSD- and STSSD

models with full power outputfor connection with the signallamp or shutter.

� Design for surface mountingunits

– Robust ISO casing, light grey,made of impact resistantpolymer. Protection to IP 54.Models from RDS 7 andTSD 5.5 made of steel, doublepainted, protection to IP 65.

– Built-in operating switch for fivespeed steps and on/off func-tion.

– Operation display via controllamp.

– Fully impregnated transformersT 40 E, protection class II.

– Conforms to DIN VDE 0550.– Max. permitted ambient

temperature +40 °C.– Delivered ready for installation,

simple connection to terminalblock.

� Design for built-intransformers

– Two transformers in V switchingensure the functions as describedabove.

– Built-up terminal block for fivevoltage outputs.

– Attached fixing brackets forsimple fixture.

– Fully impregnated transformersT 40 E.

– Contactors and external wiringto be supplied onsite.

� AccessoriesFive step switch STSSD forfuse board installation, withfront board.

For surface mounting3 ph. alternating current, 400 V

For switchboard installation3 ph. alternating current, 400 V

With motor full protection facility3 ph. alternating current, 400 VFor surface mounting

Speed control transformer TSDAs TSW, but for 3 phase fans.

Wiring diagram no. SS-436.2

Speed control transformer TSSDAs TSSW, but two transformerswithout casing, in V switching.

Wiring diagram no. SS-267.1

5 step operating switch STSSDSuitable for control of transformerTSSD for 400 V, 3 ph. fans. Forswitchboard installation with frontfixing and front panel. Connectionsare deepened.

Type STSSD Ref. no. 0235Voltage AC 3, 400 Vmax. load 5.5 kWInstallation depth 110 mm, 46 mmWiring diagram no. SS-549.1

Transformer speed controllerRDS with motor full protectionfacility Five step speed controller withintegrated thermal contact trippingunit for 400 V, 3 ph. alternatingcurrent fans.To connect thermal contacts wiredto the terminal box. A number offans can be controlled up to thenominal load.If a thermal contact trips all fanswill be disconnected.Step switch and control lamp in-cluded. Restarting via “0” positionafter interference or power cut off.

Type Ref. I max. Dim. in mmno. A W H D

TSD 0.8 1500 0.8 200 254 167

TSD 1.5 1501 1.5 200 254 167

TSD 3.0 1502 3.0 200 254 167

TSD 5.5 1503 5.5 300 300 150

TSD 7.0 1504 7.0 300 300 150

Type Ref. I max. Dim. in mmno. A W H D

TSSD 1 6516 1.0 84 95 80

TSSD 2 6517 2.0 96 104 92

TSSD 4 6518 4.0 105 112 98

TSSD 7 6519 7.0 120 122 134

Designed to comply with VDE 0550, fully impregnated transformers in V switching.Max. permitted ambient temperature +40 °C. Wiring diagram no. SS-139.

Type Ref. I max. Casing IP 54 Dimensions in mm Weightno. A made from W H D kg

RDS 1 1314 1.0 Polymer 236 316 128 6.0

RDS 2 1315 2.0 Polymer 236 316 128 9,7

RDS 4 1316 4.0 Polymer 236 316 128 10.5

RDS 7 1578 7.0 Steel 300 300 150 21.0

TSD 11.0 1513 11.0 300 400 200

TSSD 11 6515 11.0 150 146 158

RDS 11 1332 11.0 Steel 300 400 200 26.0

H

B

T

Transformer speed controllers with and without motor full protectionfor 3 ph. alternating current fans, 400 V, 50/60 Hz

Page 48: Accessories to optimally

534

Voltage 230 V~, 50/60 HzProtection class IP 54Max. ambient temperature +40 °CWiring diagram no. SS-674

Voltage 400 V, 3~, 50/60 HzProtection class IP 54Max. ambient temperature +40 °CWiring diagram no. SS-676.1

Electronic control thermostatESTwith various control variablesto control a climate transformercontroller KTR.

Control functions– Temperature dependent, five-

step fan control via KTR units.Limitation of control range pos-sible by selecting a minimumand maximum air rate (voltage).Minimum air rate can beswitched on and off.

– Ventilation damper control(analogue 0...10 V)

– Control of a frequency inverter(analogue 0...10 V)

– Heating thermostat– Temperature monitor (insufficient

and excessive temperatureswith outside air temperaturecompensation).

– Adjustments made via a dirt-resistant membrane keypad.

� Five-step climate transformercontroller KTRW and KTRD

� Trouble-free, low-loss trans-former controller for tempera-ture-dependent fan control in-cluding full motor protection.

� Recommended for noise criticalapplications.

� Control via an electronic thermo-stat type TME 4 or EST to be or-dered separately as accessory.

For single phase fans 1 ph., 230 V, 50/60 Hz

For three phase fans 3 ph., 400 V, 50/60 Hz

� Accessories for KTRWand KTRD

Four-step electronic thermostatFor temperature-dependent controlof a KTR transformer controller orfor on/off operation of up to foursingle phase fans.(Supply voltage 230 V required.

Climate transformer controllerKTRW 230 VFor automatic control of one orseveral 1 ph. fans in relation to theroom temperature.Five-step automatic operation,whereby each step can also beswitched manually. Integrated fullmotor protection by connectingthe thermal contacts on the motor.Suitable for stable ventilation.Light grey polymer casing.

Climate transformer controllerKTRD 400 VFor automatic control of five step3 ph. fans in relation to the roomtemperature. The built-in operatingswitch also allows manual control.Integrated full motor protection byconnecting the thermal contactson the motor.Robust casing made of steel, dualcoating in light grey.

Electronic four step thermostatwith a switching sequence of 1 Kfor adjusted setpoint. Enables fivestep temperature-controlled fanoperation in combination with theclimate controller KTR in relationto the pre-set setpoint and actualtemperatures.Robust casing made of impact-resistant, light grey polymer.Cable entry at the bottom of thecasing in PG 11.

Type TME 4 Ref. no. 1335Voltage 230 V~, 50/60 HzMax. continuous current (AC 3) 6 ATemperature range 0 to +50 °CSwitching precision +/- 0.8 K at 20 °CSwitching distance 1 KProtection category IIProtection class IP 54Dim. mm W 120 x H 80 x D 75Weight approx. 0.4 kgWiring diagram no. SS-702

Type EST Ref. no. 1355Voltage 230 V, 1~, 50/60 HzProtection class IP 54Transf. connection 230 V AC / max. 10 ATemperature range (adjustable) 0 – 40 °CControl range (adjustable) 2 – 12 KAlarm low temp. (adjustable) -20 – 0 K Alarm high temp. (adjustable) 0 – 25 K Heating (adjustable) -15 – +5 KOutside temp. compensation 0 – 20 KMin. air rate approx. 0 – 40 %Max. air rate approx. 60 – 100 %Disable minimum air speed -25 – 0 KDim. mm W 260 x H 215 x D 120Weight approx. 2.0 kgWiring diagram no. SS-357.3

– Stepless temperature specifica-tion for activation of heating.

– Stepless specification for alarmsignal for low and high tempera-tures.

– Min. and max. shutter opening.

Type Ref. no. I max. Dim. in mmA B H T

KTRW 3 1662 3 236 316 128

KTRWKTRD

TME 1

EST

or

or

Alarm

FanMWMD

� Displays– Displays for operation mode,

room temperature, outside tem-perature and adjusted setpointtemperature.

– Signal LED for soft-closing mech-anism.

– Alarm signal LED for insufficient,excessive temp., system error.

– Scaled LED display (0 –100 %)for fan speed and opening ofshutter.

� Temperature sensorAn outside and an inside tem-perature sensors are included asstandard. Casing protected to IP55, installation up to 100 m dis-tance from controller, connectionby means of NYM 3 x 1.5 mm2.

� Possible settings– Stepless specification of set-

point temp. and control range.– Min. / max. power (speed) limit.– Min. air flow vol. can be on/off.– Soft-closing mechanism on/off.

TME 4

Type Ref. no. I max. Dim. in mmA B H T

KTRD 3 1650 3 300 500 200

KTRD 5.5 1651 5.5 300 500 200

KTRD 10 1652 10 400 500 200

KTRD 15 1653 15 400 500 200

� CasingPolymer, light grey with transpar-ent hinged lid, for surface instal-lation.

Transformer control systemstemperature-controlled, five-step

Page 49: Accessories to optimally

No. mm

Weight Dimensions

H W D

Coolingelementwidth

mm mm mm

535 Mea

sure

Cont

rol ·

Reg

ulat

e

ETWESD

With these speed controllers,Helios offers a simple solutionby connecting the fans andcentral building managementsystems specified by the cus-tomer!

� Common features� Control via analogue 0 –10 V

on-site input signal, electroniccontrol system EUR 6 C orother controllers.

� A number of different fans canbe controlled by one controllerup to its maximum load.

� Several controllers can be con-trolled in parallel by a centralbuilding management systemthat allows the ventilation to bedistributed to several fans or fanunits and therefore in severalcircuits.

� Accessories for both seriesAn universal control unit with10 V output can be used if thefans are not controlled by acentral building managementsystem.

Type EUR 6 C Ref. no. 1321See electro nic control system pagefor description.

� Specification ETWSeven-step electronic trans-former control unit for speedcontrol of 1 ph. fans. Robustand low-loss power units forventilation systems controlledby central building managementsystems.

� Possible settings / Display� Built-in operating switch allows

on, off and direct supply switch-ing.

� Power step rotary switch allowsmanual operation of steps (1–7)or automatic operation.In “auto” mode, the transformercontrol unit is automatically con-trolled by the on-site ventilationcontrol.

� The operating step is displayedby a LED.

� The built-in minimum air volumeswitch can be totally switchedoff from the ventilation controllervia the analogue input.

Type Ref. no. Output current

Output voltagesStep

� � � � � �

Protectionto

Wiringdiagram

ETW 5 1263 5.0 80 95 115 135 165 195 230 683 54

ETW 10 1264 10.0 80 95 115 135 165 195 230 683 54

A V No. IP

For single phase fans, 1~, 230 V, 50/60 Hz

Type Ref. no. Outputcurrent

Power con-sumption

Protec-tionto

Wiringdiagram

ESD 5 0501 5.0 2.2 831 160 115 165 23 1.5 65

ESD 11.5 0502 11.5 5.5 831 160 160 165 68 1.7 65

A kW kg IP

Type Dim. in mm

H W D

Weight kg

ETW 5 315 240 210 8

ETW 10 315 240 210 10

� Specification ESDConvenient, stepless, electronicspeed controller for 3 ph. fans,which can be controlled viaphase control through voltagereduction (except KVD Ex types).Latest technology through useof micro-controllers.

� Possible settings / Display� On/off and stepless speed

selection via rotary poten- tiometer.� 0 –10 V input. Thus, remote

control possible with on-siterotary potentiometer (22 kOhm).

� 3 ph. phase monitoring, protec-tion against phase failure.

� Smooth start-up function.� Automatic minimum initial

voltage 80 V.� Fulfils EMC requirements

class B, shielded cable not re-quired between unit and motor.

� LEDs as status and fault display.� Integrated protection for elec-

tronics against overload.� Full motor protection by moni-

toring the thermal contacts ofmotors.

� Casing� Polymer casing, light grey with

wide cooling element.� Can be used directly even in

dirty areas (e.g. kitchen) due toprotection class IP 65.

� Overload protectionETW types are protectedagainst permanent overload bya built-in temperature switch.When the overload protectiontrips, the unit switches automati-cally to direct supply.After cooling down, the unitswitches back to normal opera-tion. The interference can orshould be signalised via the out-put to an on-site alarm system.

� Casing� Polymer casing, light grey.

For three phase fans, 3~, 400 V, 50/60 Hz

� Model range � Model range

� Dimensions

Electronic speed controller for 3 ph. fans 400 V, 50/60 HzElectronic transformer controller for 1 ph. fans 230 V, 50/60 Hz

Page 50: Accessories to optimally

536

Frequency inverterfor alternating current fans 3 ph., 400 V, 50/60 Hz

FU-C and FU-CS

Analogue inputs 2 x 0-10 V, Ri 100 kOhm or 0-20 mA, or KTY

Logic inputs 2 x digital 24 V, function parametrisable

Analogue output 1 x 0-10 V DC, 10 mA

Relay output 2 x changeover contact 250 V / 2 A ind.

Power supply for modules 1 x 10 V DC, 10 mA (in analogue output), 1 x 24 V DC, 70 mA

Motor temp. monitoring Thermal contact or PTC thermistor

FU-B and FU-BS

FU-CS

0-10 V0-20 mA

PU/A

400 V~

3 ~Motor

oder

oder

°C °C m/sonoff p

3 ~Motor

oderTK KL

n Motorenbis I max.

0-10V

FU-C

FU-C and FU-CS

3 ~Motor

oder

FU-BS

0-10 V0-20 mA

PU/A

400 V~

TK KL

oder

oder

onoff

3 ~Motor

oderTK KL

n Motorenbis I max.

FU-B

� SpecificationFU-B “Basic”

� Frequency inverter FU-B in basicdesign without sine filter to con-trol the speed of a single fan.

� Speed specified by a 0-10 Vcontrol signal (e.g. potentiome-ter PU/PA, accessories).

� Maximum line length betweenFU-B and fan 10 m with shield-ed lines.

� The fan must be designed foroperation with a frequency in-verter (suitable EMC fan / motor,possibly with a special design).

� The FU-B is fixed to its nominalcurrent.

� For FU-B operation (without sinefilter), the suitability for the fre-quency inverter must be statedwhen ordering the fan.

� SpecificationFU-CS “Comfort-Sine”

� Frequency inverter FU-CS incomfort design with built-in sinefilter effective on all poles.

� To control the speed of one ormore fans. The permitted num-ber of fans is calculated fromthe maximum FU current.

� Includes display and three but-tons to set the fan and controlparameters.

� Parameters can be set and unitcan be controlled via modbus.

� With built-in, fully-fledged controlsystem for temperature, pres-sure and air speed. The requiredsensors LDF 500, LGF 10, LT..can be delivered as accessories(see page EUR 6 C).

� See FU-BS description forspeed specification, line length,EMC precautions.

� When using the frequency in-verter with a built-in sine filter,conventional standard fans /motors can be used.

FU-B and FU-BS

Analogue inputs 1 x 0-10 V, Ri 100 kOhm or 0-20 mA

Logic inputs 1 x digital 24 V, release

Analogue output —

Relay output 1 x closing contact 250 V / 2 A ind.

Power supply for modules 1 x 10 V DC, 10 mA, 1 x 24 V DC, 70 mA

Motor temp. monitoring Thermal contact or PTC thermistor

� SpecificationFU-BS “Basic-Sine”

� Frequency inverter FU-BS inbasic design with built-in sinefilter effective on all poles.

� To control the speed of one ormore fans. The permitted num-ber of fans is calculated fromthe maximum FU current.

� The speed is specified by a0-10 V control signal (e.g. poten-tiometer PU/PA, accessories).

� Line lengths between FU-BSand fan greater than 10 m arepossible.

� No additional EMC shielding ofthe electrical lines required.The fans, including motor, donot require any specific EMCprecautions to operate the fre-quency inverter.

� The FU-BS is fixed to its nomi-nal current.

� When using the frequency in-verter with a built-in sine filter,conventional standard fans /motors can be used.

� SpecificationFU-C “Comfort”

� Frequency inverter FU-C incomfort design without sine filterto control the speed of a singlefan.

� Includes display and three but-tons to set the fan and controlparameters.

� Parameters can be set and unitcan be controlled via modbus.

� With built-in, fully-fledged controlsystem for temperature, pres-sure and air speed. The requiredsensors LDF 500, LGF 10, LT..can be delivered as accessories(see page EUR 6 C).

� Speed specified by a 0-10 Vcontrol signal (e.g. potentiome-ter PU/PA, accessories) ordirect entry on the display.

� Line length and suitability of thefan for operation with frequencyinverter, see FU-B description.

� For FU-C operation (without sinefilter), the suitability for the fre-quency inverter must be statedwhen ordering the fan.

n motorsup to l max.

or

n motorsup to l max.

or

or

or or

or or

Page 51: Accessories to optimally

537 Mea

sure

Cont

rol ·

Reg

ulat

e

Frequency inverter FUfor alternating current fans 3 ph., 400 V, 50/60 Hz

FU-B 7.0 5455 7.0 3.0 4 x 1.51) 1020 302 250 196 4.7

FU-C 4.2 5865 4.2 1.5 4 x 1.51) 1030 302 250 195.5 6.4

FU-C 8.5 5868 8.5 4.0 4 x 1.51) 1030 302 250 195.5 7.3

FU-C 12 5869 12.0 5.5 4 x 1.51) 1030 302 250 195.5 7.5

FU-C 17 5870 17.0 7.5 4 x 2.51) 1030 302 250 195.5 7.5

FU-CS 2.5 5871 2.5 2) 4 x 1.5 1032 284 240 115 3.3

FU-CS 8 5873 8.0 2) 4 x 1.5 1032 302 250 195.5 7.9

FU-CS 10 5874 10.0 2) 4 x 1.5 1032 302 250 195.5 8.2

FU-CS 14 5875 14.0 2) 4 x 1.5 1032 302 250 195.5 8.7

FU-C 25 5464 25.0 11 5 x 4.01) 1030 355 280 239 12.5

FU-C 32 5465 32.0 15 4 x 6.01) 1030 524 386 283 24.5

FU-C 39 5466 39.0 18.5 4 x 10.01) 1030 524 386 283 26.3

FU-C 46 5467 46.0 22 4 x 10.01) 1030 524 386 283 26.3

FU-C 62 5468 62.0 30 4 x 16.01) 1030 524 386 283 26.3

FU-CS 18 5469 18.0 2) 4 x 2.5 1032 302 250 196 9.1

FU-CS 22 5470 22.0 2) 5 x 4.0 1032 355 280 239 14.5

FU-CS 32 5471 32.0 2) 4 x 6.0 1032 525 386 283 29.6

FU-CS 40 5472 40.0 2) 4 x 10.0 1032 525 386 283 29.6

FU-CS 50 5473 50.0 2) 4 x 16.0 1032 525 386 283 32.8

Type Ref. no. Max. power Output Motor current

Cable cross sectionfrom mains to motor

cable

Dimensions

Height Width Depth

Weight net

approx.

Wiringdiagram

FU-B 3.6 5453 3.6 1.5 4 x 1.51) 1020 284 240 115 2.6

FU-B 5.0 5454 5.0 2.2 4 x 1.51) 1020 302 250 196 4.6

FU-B 8.5 5456 8.5 4.0 4 x 1.51) 1020 302 250 196 5.6

FU-B 12 5457 12.0 5.5 4 x 1.51) 1020 302 250 196 5.7

FU-B 17 5458 17.0 7.5 4 x 1.51) 1020 302 250 196 5.9

FU-BS 2.5 5459 2.5 2) 4 x 1.5 1028 284 240 115 2.7

FU-BS 5.0 5460 5.0 2) 4 x 1.5 1028 302 250 196 5.2

FU-BS 8.0 5461 8.0 2) 4 x 1.5 1028 302 250 196 6.3

FU-BS 10 5462 10.0 2) 4 x 1.5 1028 302 250 196 6.8

FU-BS 14 5463 14.0 2) 4 x 1.5 1028 302 250 196 6.9

A kW mm2 No. kg mm mm mm

Basic design without sine filter for 3 ph. AC fans, 400 V, 50/60 Hz, protection to IP 54

Basic design with all-pole sine filter for 3 ph. AC fans, 400 V, 50/60 Hz, protection to IP 54

1) max. 10 m shielded, motor supply and motor protection laid separately 2) The max. current for all connected fans is decisive for design

Comfort design without sine filter for 3 ph. AC fans, 400 V, 50/60 Hz, protection to IP 54

Comfort design with all-pole sine filter for 3 ph. AC fans, 400 V, 50/60 Hz, protection to IP 54

� General properties� Inverter specially designed for

HLK use.� Saves energy thanks to stepless

speed adjustments.� Specially tailored to the fan mo-

tor, i.e. minimal energy con-sumption and noise in partialload operations.

� Use of zero-maintenance alter-nating current asynchronousmotors with all construction de-signs and powers.

� No power restriction when usingstandard motors.

� Operating notification via poten-tial-free contact.

� Potentiometer voltage supply:E.g. 10 V DC / 10 mA for poten-tiometer with 10 kOhm

� Analogue input for speed speci-fication (0-10 V, 0(4)-20 mA).

� Short-circ.-proof and grounded.� Built-in electronic motor protec-

tion via thermal contacts or PTCthermistors.

� Electrically isolated control unit.� Overvoltage protection� Also suitable for installation into

a control cabinet.� At amb. temp. of 40 °C – 55 °C,

consider a loss of performance.

� Information� Internal sine filter effective onall poles (types FU-..S)Filters the voltages between theindividual phases and string volt-age between phase and protec-tive conductor. Thus the outputvoltage of the frequency inverteris purely sinusoidal and matchesthe quality of a standard mainsvoltage.

� Ground fault circuit inter-rupters (all types)When using the frequency in-verter in an environment that re-quires a ground fault circuit in-terrupter, this must match typeB+, 300 mA sensitive to univer-sal currents.

� EMCAll FU types comply with theEMC Dir. 2004/108/EG and theapplicable standards such asDIN EN 60335-1 and DIN EN550011. Radio interference fil-ters are built in to ensure cl. B(res. area). For FU-B and FU-C,the line between the fan and fre-quency inverter must be shield-ed and must be no more than10 m long. Motor supply/temp.monitoring lines laid separately.

� Design motor current /frequencyWhen selecting the right fre-quency inverter, the maximummotor current is to be used as astarting point. When operatingmultiple fans, the sum of the in-dividual currents is to be usedTo prevent faults and failures, a10% reserve should be includedin the plans. A maximum fre-quency of 50 Hz must not beexceeded when controlling thespeed of a series fan, as other-wise the motor will be over-loaded and broken.A higher-frequency operation isonly possible upon request.

� Motor protectionMaximum motor protection isachieved through monitoring(thermal contacts / PTC thermis-tors); a maximum of 6 PTC ther-mistors can be connected to thedevice in series. It is possible toincrease the number of PTCthermistors by using monitoringdevices (type MSA, acces-sories).

� Accessories for all FU types

PU 24 / PA 24 No. 1736/1737Speed potentiometer, flush / sur-face, LED 24 V, Poti 10 V / 1.3-10 V

SU-3 10 / SA-3 10No. 4266/4267Three-step speed switch,flush / surface, 10 V / 1.7-10 V

Type WSUP Ref. no. 9990Week timer with LCD-display,potential-free contact

Type WSUP-S Ref. no. 9577Week timer potential-free contact,for DIN rails

Type EDR Ref. no. 1437Electronic differential pressure con-troller 0-1000 Pa, 10-24 V / 0-10 V

Type ETR Ref. no. 1438Electronic temperature controller (sensor see accessory ETR)

Type EUR EC Ref. no. 1347Electronic universal controller (sensor see accessory EUR EC)

Type MSA Ref. no. 1289Full motor protection for PTC ther-mistor

� General technical dataMains voltage 3~, 208 – 480 VMains frequency 50/60 HzOutput voltage 95% of Umains

Output frequency 50 HzProtection class IP 54Ambient temperature 0 to +40 °C

(–20 °C not currentless)

� Type-based propertiesBasic types:� Additional voltage supply: 24 V

DC / 70 mA for wiring digitalinputs and additional externalcomponents.

Sine types:� Includes internal sine filter

effective on all poles.� For the simple, subsequent en-

hancement of existing ventilationsystems.

Comfort types:� Free specification of the acceler-

ation and delay times to reducenoise on start-up.

� Additional voltage supply: 24 VDC / 120 mA for wiring digitalinputs and additional externalcomponents.

� Easy to adjust and controlvalues using the display

� Extensive diagnostic display incase of an error.

� Speed specification directly onthe device via the display.

� Serial interface RS 485 / Mod-bus-RTU.

� Adjustment of performanceaccording to needs and config-urable parameters.

Page 52: Accessories to optimally

538

� Universal controller EUR 6 CElectronic control unit withpower supply unit on thephase control principle.

� Area of applicationFor control of central ventilationsystems or for stepless controlof one or more speed control-lable 1 ph. fans.In domestic, commercial, indus-trial and agricultural applications.

� Control functionsSimple and quick start-up of pa-rameters via integrated “startupwizard”. Depending on the con-nected sensor a control can becarried out according to follow-ing control variables:

– Manual speed control, e.g.adjustable via keyboard

– Temperature (required accesso-ry temperature sensor LTR 40 orLTK 40)

– Temperature with additionalfunctions pre-programmed,(required accessory temperaturesensor LTR 40 or LTK 40)

– Differential temperature con-trol (required accessory temper-ature sensor LTR 40 or LTK 40)

– Differential pressure (requiredaccessory differential air pres-sure sensor LDF 500)

– Differential pressure with out-side air temperature compen-sation (required accessory diff-ferential air pressure and tem-perature sensor LDF 500 andLTR 40 or LTK 40). Ideal for cen-tral ventilation systems accord-ing to DIN 18017 in residentialconstruction.

– Air velocity (required accessoryair velocity sensor LGF 10)

The required sensor is to be or-dered separately as an accessory.The control ranges are freely ad-justable within the sensor’s range.

The aligned output voltage accord-ing to nominal value and currentvalue is between 0 % (35 V) to100 % (approx. 80 V – 230 V).The specification of minimum andmaximum values is possible.

– Main switch with positions:“0” = Controller off“I” = Automatic operation“230 V” = uncontrolled directsupply.

Inputs and outputs:Outputs:– 1 x motor connection based on

phase control principle– 1 x analogue output 0–10 V

for control of e.g. frequencyinverter, shutter, EC motor.

– 2 x potential-free relay, program-mable, alarm, heating or statussignals

Type EUR 6 C Ref. no. 1321Voltage 230 V~, 50/60 Hzmax. current 6 ARequired minimum current 0.2 AControlled output voltage 0 – 100 %Control range temperature 0 – 40 °CControl range pressure 0 – 500 PaControl range velocity 0 – 10 m/sPermitted ambient temp. 0 to +40 °CProtection class IP 54Casing surface mounted installation,

polymer, light greyDim. mm W 223 x H 200 x D 131Weight approx. 1.4 kgWiring diagram no. SS-911

EUR 6 C

Ventilator

0-10V DC

K1/K2

TK

Alarm

°C

z.B.

onoff

°C

oder

Inputs:– 2 x sensor inputs, programma-

ble on the respective necessarysensor type

– Connection of thermal contactsfor motor protection

The whole system stops when athermal contact TK trips. It mustbe restarted manually once themotor has cooled down. – 2 x digital inputs, programmable

ro release, external interference,limit on/off, switching nightreduction, internal/external,control/manual operation, reset,max. speed on/off

Possible settings – Stepless selection of setpoints

and control range– Min./max. power (speed) limit– On/off switching of minimum air

flow volume– Switching e.g. heating via pro-

grammable relay– Stepless selection for alarm indi-

cation at low and high tempera-ture, output on display or addi-tionally on relay

– Min. and max. shutter opening– Reverse control functions– Continuous control of ventilation

dampers– Adjustments made via a dirt- resistant membrane keypad.

� Display– Multi-function LC display– Numerical setpoint and actual

value display with scale– Symbols (alarm, heating,

release)– Bar graph/level indicator– Text display for menu, status

and fault indications � NoteElectronic speed controllers mayproduce motor humming.Transformer controllers are to be used for noise critical applications.

EUR 6 C

Ventilator

0-10V DC

K1/K2

TK

Alarm

P

z.B.

onoff

m/s

oder

Mode 2.05: Differential temperature control

Mode 4.01: Differential pressure controlMode 6.01: Air velocity control

Mode 2.03: Temperature control with additional function

*

* e.g. for shutter, frequency inverter

� Necessary accessories

Type LDF 500 Ref. no. 1322Differential air pressure sensorRange 0 – 500 Pa

Type LGF 10 Ref. no. 1325Air velocity sensorRange 0 – 10 m/s

Type LTA 40 Ref. no. 1336Temperature sensor for outsideRange –20 to +60 °CProtection class IP 54

Type LTK 40 Ref. no. 1324Temperature sensor for ductinstallationRange 0 to +40 °C

Type LTR 40 Ref. no. 1323Room temperature sensor Range 0.5 to +40 °C

* e.g. for shutter, frequency inverter

*

EUR 6 C

Electronic control system EUR 6 C1~, 230 V, control variables: Temperature, pressure, air velocity

or

or

E.g.

E.g.

Fan

Fan

Page 53: Accessories to optimally

539

� Universal control systemEUR ECElectronic control unit with0–10 V DC control output.

� Area of applicationFor stepless control or regulationof single and three phase ECfans with a setpoint input of0–10 V DC.

� Control functionsSimple and quick start-up of pa-rameters via integrated “startupwizard”. Depending on the con-nected sensor a control can becarried out according to follow-ing control variables:

– Manual speed control, e.g.adjustable via keyboard

– Temperature (required accesso-ry temperature sensor LTR 40or LTK 40)

– Temperature with additionalfunctions pre-programmed,(required accessory temperaturesensor LTR 40 or LTK 40)

– Differential temperature con-trol (required accessory temper-ature sensor LTR 40 or LTK 40)

– Differential pressure (requiredaccessory differential air pres-sure sensor LDF 500)

– Differential pressure with out-side air temperature compen-sation (required accessory diff-ferential air pressure and tem-perature sensor LDF 500 andLTR 40 or LTK 40). Ideal for cen-tral ventilation systems accord-ing to DIN 18017 in residentialconstruction.

– Air velocity (required accessoryair velocity sensor LGF 10)

The required sensor is to be or-dered separately as an accessory.The control ranges are freely ad-justable within the sensor’s range.

The aligned output voltage accord-ing to nominal value and currentvalue is between 0 % (0 V DC) to100 % (10 V DC). The specificationof minimum and maximum valuesis possible.

Type EUR EC Ref. no. 1347Voltage 230 V~, 50/60 HzControl output 0–10 V / max. 10 mAControlled output voltage 0 – 100 %Control range temperature 0 – 40 °CControl range pressure 0 – 500 PaControl range velocity 0 – 10 m/sPermitted ambient temp. 0 to +40 °CProtection class IP 54Casing surface mounted installation,

polymer, light greyDim. mm W 223 x H 200 x D 131Weight approx. 1.0 kgWiring diagram no. SS-1001

Inputs and outputs:Outputs:– 2 x analogue outputs 0–10 V to

control e.g. EC motor, frequencyinverter, shutter

– 2 x potential-free relay, pro-grammable, alarm, heating orstatus signals

Inputs:– 2 x sensor inputs, programma-

ble on the respective necessarysensor type

– 3 x digital inputs, programmablero release, external interference,limit on/off, switching nightreduction, internal/external,control/manual operation,reset, max. speed on/off

Possible settings – Stepless selection of setpoints

and control range– Min./max. power (speed) limit– On/off switching of minimum

air flow volume– Switching e.g. heating via pro-

grammable relay– Stepless selection for alarm

indication at low and high tem-perature, output on display oradditionally on relay

– Min. and max. shutter opening– Reverse control functions– Continuous control of ventilation

dampers – Adjustments made via a dirt- resistant membrane keypad.

� Display– Multi-function LC display– Numerical setpoint and actual

value display with scale– Symbols (alarm, heating,

release)– Bar graph/level indicator– Text display for menu, status

and fault indications

Mode 4.01: Differential pressure controlMode 6.01: Air velocity control

Mode 2.03: Temperature control with additional functionMode 2.05: Differential temperature control

� Necessary accessories

Type LDF 500 Ref. no. 1322Differential air pressure sensorRange 0 – 500 Pa

Type LGF 10 Ref. no. 1325Air velocity sensorRange 0 – 10 m/s

Type LTA 40 Ref. no. 1336Temperature sensor for outsideRange –20 to +60 °CProtection class IP 54

Type LTK 40 Ref. no. 1324Temperature sensor for ductinstallationRange 0 to +40 °C

Type LTR 40 Ref. no. 1323Room temperature sensor Range 0.5 to +40 °C

EUR EC

Electronic control system EUR EC0–10 V, control variables: Temperature, pressure, air velocity

Mea

sure

Cont

rol ·

Reg

ulat

e

� NoteDepending on the fan type tobe connected, multiple fanscan be connected in para llelto an EUR EC.

or

or

E.g.

E.g.

EC fan

EC fan

Page 54: Accessories to optimally

540

Electronic controllers, 0–10 V DC control outputControl variables: Differential pressure, temperature

� Electronic controller fordifferential pressure ortemperature

� Area of applicationFor stepless control of 1 ph. and3 ph. EC fans or frequency in-verters with a setpoint input of0-10 V DC. If the EC fan or fre-quency inverter provides a sup-ply voltage of 10-24 V DC/6 mA(safety extra-low voltage), thecontroller can be directly pow-ered or alternatively via a powersupply unit (NG 24, acces-sories).

� Display– Multi-function LCD display– Numerical setpoint and actual

value display with measurementunit

– Alarm, day/night mode– Text display for menu, status

� Control functionsSimple and quick start-up of pa-rameters using LCD display andthree internal input keys. Perma-nent measurement display onLCD display.Optional parameterisation as

– regulator = 0-10 V analogueoutput proportional to the meas-ured actual value as control vari-able for external controls or as

– controller = controlled 0-10 Vanalogue output in relation tothe set setpoint value and themeasured actual value.The controlled output voltagebetween the actual and setpointvalue lies between 0 % (0 V DC)and 100 % (10 V DC). Thespecification of min. and max.values is possible, two setpointvalues (e.g. for day/night mode)are also adjustable. Switchingby means of week timer (typesWSUP, WSUP-S, see acces-sories).

� Differential pressure controllerEDRWith firmly integrated pressuresensor and connections forpressure hoses (DN 5 mm,on-site).

� Adjustable pressure ranges:0-1000 Pa, 0-500 Pa, 0-300 Pa,0-200 Pa

Type EDR Ref. no. 1437Supply voltage 10-24 V DC, 6 mAAnalogue outputs 0-10 V DC

10 V / 0.3 mA24 V / 10 mA

Signal input 10-24 V DC / 6 mA Switching setpoint 1/2 (day/night)Permitted humidity 85 %

non-condensingProtection class IP 54Protection category III

(safety extra-low voltage,galvanically isolated)

Permitted ambient temp. 0 to +50 °CCasing Surface installation,

Polymer, light greyDim. mm W 114 x H 108 x D 56Weight 250 gWiring diagram no. SS-1039

� Necessary accessories forEDR and ETR

Type NG 24 Ref. no. 1439Power supply unit for DIN railmounting, input 100-240 V AC,output 24 V DC / 1.75 A. Required if fan type does notsupply 10-24 V DC / 6 mA.

Type WSUP Ref. no. 9990Week timer

Type WSUP-S Ref. no. 9577Week timer for DIN rail mounting

� Necessary accessories forETR

Type LTA 40 Ref. no. 1336Temperature sensor for outsideMeasuring range –20 to +60 °CProtection class IP 54

Type LTK 40 Ref. no. 1324Temperature sensor for in-ductinstallationMeasuring range 0 to +40 °C

Type LTR 40 Ref. no. 1323Room temperature sensor Measuring range 0.5 to +40 °C

� Temperature controller ETRThe controller is freely adjustablewithin the sensor measuringranges, with the optional func-tions of cooling or heating, withadjustable minimum air shut-off.

� Temperature control range–50 to +150 °C.

� Appropriate sensors (types LTA,LTK, LTR, see accessories) areavailable for temperature meas-urement.

Type ETR Ref. no. 1438Supply voltage 10-24 V DC, 6 mAAnalogue outputs 0-10 V DC

10 V / 0.3 mA24 V / 10 mA

Signal input 10-24 V DC / 6 mA Switching setpoint 1/2 (day/night)Permitted humidity 85 %

non-condensingProtection class IP 54Protection category III

(safety extra-low voltage,galvanically isolated)

Permitted ambient temp. 0 to +50 °CCasing Surface installation,

Polymer, light greyDim. mm W 114 x H 108 x D 56Weight 200 gWiring diagram no. SS-1040

� NoteDepending on the fan type to be connected, multiple fans can be connected in para llel to an EDR or ETR.

EDR ETR

Page 55: Accessories to optimally

541 Mea

sure

Cont

rol ·

Reg

ulat

e

� Speed-potentiometer PU /PAwith additional functionsswitch and LED

� Area of applicationFor direct control/setpoint speci-fication of EC fans with poten-tiometer input.Additionally equipped with a re-lease switch and LED display forthe operating status (dependingon the fan type features).

� Control with potentiometerThe potentiometer is attacheddirectly to the potentiometer in-put of the fan control. This hasa potentiometer supply of e.g.10 V DC and an input controlsignal of 0-10 V DC.

� Minimum voltageA second potentiometer is firmlyintegrated in the PU/PA. Theminimum voltage (min. 1.3 V)is steplessly adjustable, thusa reliable motor start-up is guar-anteed on the lowest speed set-ting.

� Release switchThe rotary knob for the poten-tiometer is also a pressureswitch, which can be used toswitch the fan with release input(e.g. 24 V DC) on/off.

� LED light ringThe colour of the light ringsignals the operating status ofthe fan. For fans with operatingsignal relay, change from green(normal operation) to red (fault).See technical data for necessarysupply voltage.

� Delivery range� LED power supply 10 VType PU 10 Ref. no. 1734Installation standard flush mounted boxDim. mm W 80 x H 80 x D 21 overhang

Type PA 10 Ref. no. 1735Casing Surface installation,

Polymer, light greyDim. mm W 80 x H 80 x D 65

� LED power supply 24 VType PU 24 Ref. no. 1736Installation, dimensions see PU 10

Type PA 24 Ref. no. 1737Casing, dimensions see PA 10

� Technical data for all typesPotentiometer 10 kOhm(min. potentiometer approx. 7.9-16.5 kOhm)A Potentiometer supply of 10 V results in acontrol voltage 0-10 V DC.Min. voltage 1.3-6.7 V DC adjustable.LED supply voltage: 10/24 V DC (P 10/24), min. 6 mAPermitted ambient temp. 0 bis +40 °CProteciton class IP 40Wiring diagram no. SS-1000

PU / PA

� Three-step switch SU /SA10 V / 0-10 V

� Area of applicationThree-step switch for flush orsurface mounting.For three-step control of ECfans or frequency inverters,with a 0-10 V DC control input.

� FunctionsThree different setpoints can bespecified/issued using SU/SA.Each step is freely adjustable viaa separate potentiometer from0 to 10 V DC.A week timer (WSUP, WSUP-S,accessories) can also be con-nected to switch from 3-stepday mode to e.g. night mode.The night/reduction mode isfreely adjustable using anotherpotentiometer from 0 to 10 V DC.

� Delivery range� Flush mountingType SU-3 10 Ref. no. 4266Installation in deep flush box (D 65 mm)Dim. mm W 80 x H 80 x D 15 overhang

� Surface mountingType SA-3 10 Ref. no. 4267Protection class IP 40Casing Surface installation,

polymer, whiteDim. mm W 80 x H 80 x D 60

� Technical datafor all SU /SA types

Supply input: 10 VDC Ri = 12.5 kOhm(safety extra-low voltage)

Own consumption: 1.5 mAControl output: 0 to 10 V DC optional

via switch or external switchoverProteciton class IP 30 when installedProtection category IIIWiring diagram no. SS-1022

SU / SA

Basic circuit diagram Basic circuit diagram

Speed-potentiometerThree-step switch

� NoteDepending on the fan type to be connected, multiple fans can be connected in para llel to a speed-potentiometer or three-step switch.

3-stepspeed setting

Steplessspeed settingwith potentiometer

Release*

Operating status /Error display*

*Depending on fan type

EC fan

EC fan

Page 56: Accessories to optimally

542

Differential pressure switch DDSType DDS Ref. no. 0445

� Area of application� Complete kit to monitor air filter,

system pressure and fan opera-tion.

� Suitable for DDC applications(24 V DC/0.1 A) due to gold-plated connection contacts.Once the unit has been con-nected conventionally (230 VAC /1.5 A), subsequent use inDDC applications is no longerpossible.

� Suitable for applicationsaccording to VDI 6022.

� Technical dataAdjustable pressure range 50 – 500 PaSwitching difference Dp 20 Pamax. operating overpressure 5 kPaCurrent 230 V AC 1.5 (0.4) A

24 V DC 0.1 AAmbient temp. -20 to +85 °CAir flow temp. -20 to +85 °CHumidity 0...50% RH,

non-condensingProtection class IP 54Dim. mm Ø 104, D 58Weight approx. 0.23 kgWiring diagram no. SS-490 � Function

Adjustable opener/closer tomonitor pressure loss and thusthe amount of dust in air filters,the pressure increase of fansand the pressure level withinthe ventilation system.

� DeliveryComplete kit including:

– Differential pressure switch DDS – 4 fastening screws – 2 pipe connections – Connection pipe

Ø 6 mm x 1.5 mm x 2000 mm – Drilling template for connecting points– Retaining plate + 3 fastening screws– 3 screw terminals

Ventilation hygrostatType HY 3 Ref. no. 1359

Ventilation hygrostatType HY 3 SI Ref. no. 1360Internal scale.

� Area of application� Electromechanical humidity

controller for on/off operation offans (in 3 ph. models control viacontactor) to reduce the relativehumidity in a room through airexchange.

� Technical dataRelative humidity level 30 to 90 %Switching sensitivity approx. ± 6 %Voltage max. 230 V~, 50/60 HzCurrent 3 A (ind.)Ambient temperature 0 – 40 °CProtection class IP 20Dim. mm W 76 x H 76 x D 34Weight approx. 0.25 kgWiring diagram no. SS-168.1

� Specification� Universal hygrostat housed in an

attractive polymer casing forsurface mounting. Colour white.

� Setpoint adjustment via externalrotary knob. In HY 3 SI via theinner scale.

� Not suitable for dusty oraggressive air.

� Sensor element made ofpolyamide fibres.

� Also suitable for humidificationthrough optional connection.

One-step thermostat TME 1Type TME 1 Ref. no. 1334

� Area of application� Robust, electronic thermostat for

temperature-dependent on/offoperation of fans or heaters.Suitable for installation in humidand dusty rooms. Surfacemounting in any position.

� Technical dataVoltage 230 V~, 50/60 HzCurrent 16 AMax. current (AC 3) 6 ATemperature range 0 to +50 °CSwitching sensitivity +/- 0.8 K at 20 °CProtection category IIProtection class IP 54Ambient temp. 0 to +60 °CDim. mm W 82 x H 80 x D 75Weight approx. 0.2 kgWiring diagram no. SS-701Connection cable NYM-O 4 x 1.5 mm2

� Function� Single step control thermostat

for direct switching of one or anumber of fans.

� Also suitable for heater controlthrough optional connection.

� Potential-free switch-overcontact.

� Specification� Enclosed casing made of impact

resistant, light grey polymer.Cable entry on the bottom ofcasing via self-sealing grommetPG 11.

� Connection via terminal block,after removing the casing cover.

HY 3 HY 3 SI

Temperature and humidity controllerDifferential pressure switch

Page 57: Accessories to optimally

543 Mea

sure

Cont

rol ·

Reg

ulat

e

Air quality controllerType ACL Ref. no. 0492

� Area of application� Electronic air quality controller

to control:– 1 ph. fans

up to max. 1 A.– 3 ph. fans

via contactor.� For ventilation systems in con-

ference rooms, restaurants,shops, manufacturing plants,living/meeting rooms.

� Function� On and off operation of one or a

number of fans in relation to theroom’s air quality.

� The unit has an integrated sen-sor which reacts on oxidablegases and pollutants such ascarbon mo noxide, alcohol,formaldehydes, benzene, sol-vents, methane, tobacco etc.

� Possible settings� The unit switches the fan on if

the set value is exceeded or ifthe concentration rises quickly.

� Adjustable (from outside) over-run timer after the sensor hasswitched off.

� Indicator lamp for operationtype (automatic/manual) andfan operation and overrun time.

� Functional and operationalswitch on the front casing

� Technical dataVoltage 230 V, 1~, 50/60 HzOverrun time, adjustable 1 – 10 min. Power-up delay approx. 5 sec.Current 2 A (ind.)Protection class IP 30Dim. mm W 125 x H 75 x D 30Weight approx. 0.2 kgWiring diagram no. SS-485.1

� CasingCompact casing with air exchangeslots, made of light grey polymer,for surface installation.

Mechanical air flow monitorType SWT Ref. no. 0080� Area of application� Mechanical air flow monitor with

adjustable trigger power tomonitor the minimum air flowvelocity in ducting minimumdiameter 315.

� DesignRobust design with a paddlemade of high-grade steel andsupplied with mounting plate tofix the unit outside of the duct-ing.

Electronic air flow monitorType SWE Ref. no. 0065� Area of application

To monitor air flow in ducting.Open or closed circuit principlesare available as options.

� FunctionThe air flow sensor (connectedto controller) registers the airflow and compares it with thepreset value. That can be set onthe front side of the control unit(in the range of 1 – 20 m/s).The relay contacts if the set

value is reached or exceeded.Two LED’s show UN and theposition of the output relay. It ispossible to connect an externalfailure display via a relay output(1 change-over, voltage free,max. current 5 A / AC 250 V).

� Installation Control unit suitable for mount-

ing in switch cabinet for fixing ona 35 mm support rail.

Air flow sensor with mounting rosette for in-duct installation with cable (length 2.5 m; up to

� Technical dataVoltage 24-230 V AC, 50/60 HzCurrent 15 (8) A (ind.)Air temperature limits -40...+ 85 °CProtection class IP 65Dim. mm– Paddle W 55, L 200, D 0.15– Casing W 140 x H 65 x D 62Weight approx. 0.4 kgWiring diagram no. SS-557.1

Differential temp. controllerType EDTW Ref. no. 1613� Area of application andadvantages

� Electronic, stepless differentialtemperature controller forconnection of electronicallycontrolled

– Ceiling fans and all– 1 ph. fans.� For continuous speed control

in relation to the temperaturedifference.

� Designed for use in combinationwith ceiling fans or fans whichmove the room air towards thefloor to save heating energy.The unit optimises the differencebetween the floor and ceilingtemperature.

� Function� Stepless speed control between

(0 – 100%) in relation to thetemperature difference betweenboth temperature sensors andthe equalisation with the set-point specification.

� Includes tempera ture sensorswith a flying lead (1 x 10 m long,for mounting below the ceiling;1 x 2 m long, for mountingabove the floor.

� If the temperature differencerises the fan speed increasesproportionally and slows downfor decreasing temperatures.

� Proportional range can beadjusted steplessly from 1–10 K.

� Technical dataVoltage 230 V, 1~, 50/60 HzCurrent max. 2.5 A (T 40 E)Adjustable control range 1 – 10 KProtection class IP 20Dim. mm W 210 x H 85 x D 55Weight approx. 0.7 kgWiring diagram no. SS-438

� Possible settings� On/off (with function display)� Automatic/manual operation.� Reverse of air flow direction.� Proportional range.� Summer operation:

as manual speed controller.Depending on the fan type,motor humming might beproduced.

max. 10 m extendible), that is tobe connected to the control unit.

� Technical dataVoltage 230 V, 1~, 50/60 HzCurrent 5 A (ind.) cosj 0.4Setpoint adjustment range 1-20 m/sAir flow temperature max. 60 °CAmbient temperature max. 60 °CProtection class IP 20Dim. mm W 35 x H 90 x D 66Sensor length mm 140Weight approx. 0.4 kgWiring diagram no. SS-689.1

� Function� Can be used as a switch to make

or break circuit connections.� The unit can be set to respond if

a minimum or maximum air flowvelocity is achieved.

� Adjustable minimum air flowvelocity:

– Lower than approx. 1.5 m/sec.– Higher than approx. 3 m/sec.� Installation

Unit must be installed in a waythat the weight of the paddledoes not affect the springmechanism inside the unit.

� CasingImpact-resistant white polymer,for surface and flush mounting.