The BHS Electrical Distribution System (EDS) provides flexible power distribution to all 480 V / 3 ph components in an Operator Aboard Battery Extractor System including the Battery Extractor, chargers, and Battery Wash Equipment. The EDS is a stand mounted, high-density system that is customized using track busway that can be tapped at any location with a simple turn-n-lock connection.
Electrical Distribution SystemAccessories
BHS1.com
Equipment Comparison
• 2JunctionBoxes• Modifiableandexpandable• Installcostsapproximatelyathirdoftraditionalsystems,andcostsavingsincreaseasthe
EDSsystemgrows
• 100fusedbladedisconnects• 100runsofconduit(1toeachcharger)• Multiplerunsofwireway• Costlyanddifficulttomodify
TheEDSrunsthelengthofthebatterysystemstandsandeasilyaccommodatesgrowth.Themaintenance-freedesignsavesspace,andtheuniqueconnectionmethodeliminatesinterruptionsinpower,providingreliablepowerdistribution.Whetherconnectingsectionsoftrackbuswayorconnectingmodularunitsintothetrackbusway,aturn-n-lock“compression-fit”connectionisusedtolockeverythinginplace.
Operator Aboard Battery Extractor System with EDS:
Operator Aboard Battery Extractor System with Traditional Wiring:
Electrical Distribution SystemAccessories
TheBHSElectricalDistributionSystem(EDS)providesafavorableoptionforpoweringanOperatorAboardBatteryExtractorSystem,inplaceoftraditionalalternativesthatutilizeadisarrayofcables.ThestreamlineddesignoftheEDSallowsforeasymodificationorexpansiontothesystemduetotheinnovativeconnectionofthecomponents.
EDS, Sixteen outlets pictured
Traditional Wiring
BHS1.com
EDS Equipment Components
Track BuswayTrackbuswayconsistsoffourconductorsallowingforamaximumcapacityof800A.Eachcompositecopper-aluminumconductorishousedinacontinuousinsulator,andtheextrudedaluminumcasecanbeusedasa100%groundpath.Thecontinuousplug-indesignallowsfortwistinplug-inunitstobeinstalledanywherealongthelengthofthetrackbusway.
• Availablein5’and10’(1.5mand3m)lengthsections• Accommodatesupto800A/600Vacordc• Aluminumhousing• Compositecopper-aluminumconductors• Shortcircuitcapacityof50kA• 60Hz/50Hzfrequencyrating
Dual Outlet Units with 20 A (or 30 A) Breakers
Joint Kit
Installation Tool
End Power Feed Unit
End Power Feed Unit• Theendpowerfeedunitconnectstotheendofanybuswaysectionandsuppliespower• 24”x20”x20”(610mmx508mmx508mm)steeljunctionbox,withremovablesides,
connectedtoa1’(305mm)sectionofbusway
Available Units:
1. 800ACapacity–24”x20”x20”(610mmx508mmx508mm)steeljunctionboxwithlugconnectionsforparallelrunsofMCM600Cuwire,andissizedtoallowfor(2)4”(102mm)conduitstobeinstalledtothebox
2. 400ACapacity–16”x12”x10”(406mmx305mmx254mm)steeljunctionboxwithlugconnectionsforMCM500,andissizedtoallowfora4”(102mm)conduittobeinstalledtothebox
Circuit Breaker Units• Usedtotapoffpowerfromthebusway• Plugheadisreversibletofaceinoppositeposition• Lockedintopositionwithasingleboltonmountingtab
Available Units:
1. Dualoutletunitswith20Abreakers(NemaL16-20)
2. Dualoutletunitswith30Abreakers(NemaL16-30)
3. Hardwiredbreaker
-Accommodates480V/3phpowersupply
-IdealforusewithanOperatorAboardBatteryExtractororWashEquipment
Track Busway
Joint Kit & Installation ToolAjointkitisrequiredateachjointwhenconnectingadjacentsectionsoftrackbusway.Ajointkitincludesahousingcouplerpair(two12-screwcouplers)andbusconnectorset(silver-platedcopperbladessecuredtoinsulatingmountingplate).
Aninstallationtoolisusedforinstallationofthe‘busconnector’electricaljointbetweentwoadjacentsectionsoftrackbusway.Theinstallationtoolisusedinconjunctionwiththejointkittocreateasecureelectricalconnection.
P.O.Box28990•St.Louis,MO63132USA•1.800.BHS.9500•Fax:314.423.6444•Email:[email protected]•Web:BHS1.comSpecificationsaresubjecttochangewithoutnotice.©2013–2014BatteryHandlingSystemsInc.St.Louis,MODataSheet:PL-380001/14
Product Specifications
Standards & Certifications
Maximum Voltage 600V
Ampacity 800A
Frequency 50or60Hz
Conductors Qty4(PhasesA,B,CandNeutral)
Rated Short Circuit Capacity 50kA
Ambient Operating Temp 40°C/104°F60°C/140°F–0.8AmpRatingMultiplier
Grounding AluminumCasing,100%GroundingPath
Voltage Drop (1)voltper50ft(15m)
Housing Material ExtrudedAluminum
Conductor NickelplatedAluminumandCopper
Housing Exterior Dimensions 5’or10’(L)x6.4”(W)x5.05”(H)1.5mor3m(L)x162.6mm(W)x128.3mm(H)
Thebuswayisdesignedandmanufacturedtothefollowingstandards:1. LowVoltageDirective(73/23/EEC)includingAmendment(93/68/EEC)
2. LowVoltageSwitchgearandControlgearAssemblies,Part1:TypeTestedAssemblyandPartiallyTypeTestedAssemblies,IEC60439-1:1999
3. LowVoltageSwitchgearandControlgearAssemblies,Part2:ParticularRequirementsforBusbarTrunkingsystems(busways),IEC60439-2:2000
4. UnderwritersLaboratoriesStandard,UL857–ThecommonUL,CSA,andANCEStandardforBuswaysthatisderivedfromthefiftheditionofCSAStandardsC22.2No.27,thetwelftheditionofUL857,andthesecondeditionofNMX-J-148-1998-ANCE.
5. ETLClassifiedto(US/Canada)UL857
6. NationalElectricCode(NEC)–Article368-Busways
7. NEMAAB1,MoldedCaseCircuitBreakersandMoldedCaseSwitches
8. NEMAKS-1,EnclosedandMiscellaneousDistributionEquipmentSwitches(600VAC)
9. NFPA70–NationalFireProtectionAgency
Charger ShutdownTheoptionalchargershutdownconnectstotheBHSBatteryRoomVentilationSystem(BRVS)ortoaHydrogenGasDetector(HGD)inordertodisablethechargers.Ifanexcessiveamountofhydrogen(morethan2%)isdetectedinthearea,thepowersupplytothechargersthroughtheEDSwillautomaticallybeinterrupted.Bydisablingthechargers,theproductionofhydrogengasisstopped.ReferenceliteraturePL-3900 Battery Room Ventilation SystemformoreinformationontheBRVSandHGD.