ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2....

29
DATA SHEET: ACCC® 194/28/173 (383 kcmil)* Metric and US Units are considered separate Aluminum Specification Nominal Aluminum Cross-sectional Area*** 194.2 mm 2 383.2 kcmil Layer 1 %IACS/Aluminum Type (inner) Layer 2 %IACS/Aluminum Type Aluminum Nominal Weight** 535.6 kg/km 360.0 lb/kft Coefficient of Thermal Expansion 23.0 x10 -6 /°C 12.8 x10 -6 /°F Aluminum Heat Capacity 501.1 W-s/m-C 84.9 W-s/ft-F ACCC® Core Specification Nominal Cross-sectional Area of Core 28.0 mm 2 0.0434 in 2 Nominal Diameter of Composite Core (CTC Part Number F-730-203) 5.97 mm 0.235 in. Core Nominal Weight 52.4 kg/km 35.2 lb/kft Rated Strength of Core - 310 ksi (2137 MPa) 59.6 kN 13.4 kips Coefficient of Thermal Expansion 1.61 x10 -6 /°C 0.894 x10 -6 /°F Modulus of Elasticity 112.3 GPa 16.29 Msi Core Heat Capacity 42.6 W-s/m-°C 7.2 W-s/ft-°F ACCC® Conductor Specification Overall Diameter of Conductor 1 17.27 mm 0.680 in. Nominal Cross-sectional Area of the Conductor 222.2 mm 2 0.344 in 2 Ultimate Tensile Strength of Conductor 2 70.3 kN 15.8 kips Conductor Nominal Weight** 588.0 kg/km 395.2 lb/kft Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10 -6 /°C 0.894 x10 -6 /°F Coefficient of Linear Expansion Below Thermal Kneepoint 18.1 x10 -6 /°C 10.08 x10 -6 /°F Final Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi Final Modulus of Elasticity Below Thermal Kneepoint 61.5 GPa 8.9 Msi Maximum Allowable Operating Temperature at Surface 3 180 o C 356 o F Electrical Specification Nominal DC Resistivity at 20ºC 0.1441 ohm/km 0.2319 ohm/mile Temperature Coefficient of Resistance 0.00404 /°C 0.00209 / o F Frequency 60 Hz 60 Hz AC Nominal Resistance at 25ºC 0.1475 ohm/km 0.2374 ohm/mile AC Nominal Resistance at 75ºC 0.1765 ohm/km 0.2841 ohm/mile AC Nominal Resistance at 180ºC 0.2375 ohm/km 0.3822 ohm/mile 938 987 GMR (estimated) 7.04 mm 0.0231 ft. Inductive Reactance 0.284 ohm/km 0.4572 ohm/mile Capacitive Reactance 0.170 Mohm-km 0.1057 Mohm-mile F-730-501-F www.ctcglobal.com Date Produced: 3/25/2019 Metric US Units Metric US Units AC Current Rating at Given Temperatures 4 ACCC® is produced using 1350-O (fully annealed) aluminum. **ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540. 4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun 3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor) ***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in accordance with the stated specification Metric US Units 1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032. 2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa). *ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum) For questions, please contact CTC Application Engineering Department: [email protected] Metric US Units ACCC® OCEANSIDE 1350-O 63% 63% @ 180C & 60 Hz @ 200C & 60 Hz 1350-O

Transcript of ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2....

Page 1: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 194/28/173 (383 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 194.2 mm2 383.2 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Aluminum Nominal Weight** 535.6 kg/km 360.0 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 501.1 W-s/m-C 84.9 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 28.0 mm2 0.0434 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-203) 5.97 mm 0.235 in.

Core Nominal Weight 52.4 kg/km 35.2 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 59.6 kN 13.4 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 42.6 W-s/m-°C 7.2 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 17.27 mm 0.680 in.

Nominal Cross-sectional Area of the Conductor 222.2 mm2 0.344 in2

Ultimate Tensile Strength of Conductor2 70.3 kN 15.8 kips

Conductor Nominal Weight** 588.0 kg/km 395.2 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 18.1 x10-6/°C 10.08 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 61.5 GPa 8.9 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.1441 ohm/km 0.2319 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.1475 ohm/km 0.2374 ohm/mileAC Nominal Resistance at 75ºC 0.1765 ohm/km 0.2841 ohm/mileAC Nominal Resistance at 180ºC 0.2375 ohm/km 0.3822 ohm/mile

938987

GMR (estimated) 7.04 mm 0.0231 ft.Inductive Reactance 0.284 ohm/km 0.4572 ohm/mileCapacitive Reactance 0.170 Mohm-km 0.1057 Mohm-mile

F-730-501-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® OCEANSIDE

1350-O63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

Page 2: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 218/28/183 (430 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 218.1 mm2 430.5 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Aluminum Nominal Weight** 601.3 kg/km 404.1 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6

/°C 12.8 x10-6

/°F

Aluminum Heat Capacity 563.0 W-s/m-C 95.3 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 28.00 mm2 0.0434 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-203) 5.97 mm 0.235 in.

Core Nominal Weight 52.4 kg/km 35.2 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 59.6 kN 13.4 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°F

Modulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 42.6 W-s/m-°C 7.2 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 18.29 mm 0.720 in.

Nominal Cross-sectional Area of the Conductor 246.1 mm2 0.382 in2

Ultimate Tensile Strength of Conductor2 71.6 kN 16.1 kips

Conductor Nominal Weight** 653.7 kg/km 439.3 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 18.6 x10-6/°C 10.32 x10-6/°F

Final Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 60.8 GPa 8.8 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oF

Electrical Specification

Nominal DC Resistivity at 20ºC 0.1277 ohm/km 0.2055 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.1307 ohm/km 0.2103 ohm/mileAC Nominal Resistance at 75ºC 0.1564 ohm/km 0.2517 ohm/mileAC Nominal Resistance at 180ºC 0.2104 ohm/km 0.3386 ohm/mile

10141067

GMR (estimated) 7.42 mm 0.0244 ft.Inductive Reactance 0.280 ohm/km 0.4508 ohm/mileCapacitive Reactance 0.167 Mohm-km 0.1040 Mohm-mile

F-730-502-F www.ctcglobal.com Date Produced: 4/23/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

#NAME?

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® LINNET

PRELIMINARY

1350-O63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

Page 3: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 222/40/188 (439 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 222.3 mm2 438.6 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Aluminum Nominal Weight** 613.0 kg/km 412.0 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 573.6 W-s/m-C 97.1 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 39.7 mm2 0.0616 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-204) 7.11 mm 0.280 in.

Core Nominal Weight 74.2 kg/km 50.0 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 85.0 kN 19.1 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 60.3 W-s/m-°C 10.2 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 18.82 mm 0.741 in.

Nominal Cross-sectional Area of the Conductor 262.0 mm2 0.406 in2

Ultimate Tensile Strength of Conductor2 97.5 kN 21.9 kips

Conductor Nominal Weight** 687.2 kg/km 462.0 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 17.2 x10-6/°C 9.57 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 63.1 GPa 9.1 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.1255 ohm/km 0.2019 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.1283 ohm/km 0.2065 ohm/mileAC Nominal Resistance at 75ºC 0.1535 ohm/km 0.2471 ohm/mileAC Nominal Resistance at 180ºC 0.2065 ohm/km 0.3324 ohm/mile

10331087

GMR (estimated) 7.74 mm 0.0254 ft.Inductive Reactance 0.277 ohm/km 0.4457 ohm/mileCapacitive Reactance 0.166 Mohm-km 0.1032 Mohm-mile

F-730-503-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® ORIOLE

1350-O63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

Page 4: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 230/47/196 (454 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 230.1 mm2 454.0 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Aluminum Nominal Weight** 634.7 kg/km 426.6 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 593.8 W-s/m-C 100.5 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 47.2 mm2 0.0731 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-205) 7.75 mm 0.305 in.

Core Nominal Weight 88.3 kg/km 59.3 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 101.0 kN 22.7 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 71.8 W-s/m-°C 12.2 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 19.56 mm 0.770 in.

Nominal Cross-sectional Area of the Conductor 277.3 mm2 0.430 in2

Ultimate Tensile Strength of Conductor2 113.9 kN 25.6 kips

Conductor Nominal Weight** 723.0 kg/km 485.9 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 16.7 x10-6/°C 9.26 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 64.1 GPa 9.3 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.1212 ohm/km 0.1951 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.1240 ohm/km 0.1996 ohm/mileAC Nominal Resistance at 75ºC 0.1488 ohm/km 0.2395 ohm/mileAC Nominal Resistance at 180ºC 0.2009 ohm/km 0.3233 ohm/mile

10601115

GMR (estimated) 8.08 mm 0.0265 ft.Inductive Reactance 0.274 ohm/km 0.4405 ohm/mileCapacitive Reactance 0.164 Mohm-km 0.1020 Mohm-mile

F-730-504-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® WACO

1350-O63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

Page 5: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 268/40/205 (530 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 268.5 mm2 529.8 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Aluminum Nominal Weight** 740.1 kg/km 497.4 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 692.8 W-s/m-C 117.3 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 39.7 mm2 0.0616 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-204) 7.11 mm 0.280 in.

Core Nominal Weight 74.2 kg/km 50.0 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 85.0 kN 19.1 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 60.3 W-s/m-°C 10.2 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 20.50 mm 0.807 in.

Nominal Cross-sectional Area of the Conductor 308.2 mm2 0.478 in2

Ultimate Tensile Strength of Conductor2 99.7 kN 22.4 kips

Conductor Nominal Weight** 814.3 kg/km 547.4 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 18.0 x10-6/°C 9.99 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 61.8 GPa 9.0 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.1038 ohm/km 0.1671 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.1064 ohm/km 0.1712 ohm/mileAC Nominal Resistance at 75ºC 0.1276 ohm/km 0.2053 ohm/mileAC Nominal Resistance at 180ºC 0.1720 ohm/km 0.2769 ohm/mile

11621223

GMR (estimated) 8.36 mm 0.0274 ft.Inductive Reactance 0.271 ohm/km 0.4365 ohm/mileCapacitive Reactance 0.162 Mohm-km 0.1006 Mohm-mile

F-730-505-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® LAREDO

1350-O63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

Page 6: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 310/40/218 (611 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 309.8 mm2 611.3 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Aluminum Nominal Weight** 853.8 kg/km 573.8 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 799.4 W-s/m-C 135.4 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 39.7 mm2 0.0616 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-204) 7.11 mm 0.280 in.

Core Nominal Weight 74.2 kg/km 50.0 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 85.0 kN 19.1 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 60.3 W-s/m-°C 10.2 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 21.79 mm 0.858 in.

Nominal Cross-sectional Area of the Conductor 349.5 mm2 0.542 in2

Ultimate Tensile Strength of Conductor2 102.3 kN 23.0 kips

Conductor Nominal Weight** 928.0 kg/km 623.8 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 18.5 x10-6/°C 10.29 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 60.9 GPa 8.8 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0900 ohm/km 0.1448 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0923 ohm/km 0.1485 ohm/mileAC Nominal Resistance at 75ºC 0.1094 ohm/km 0.1760 ohm/mileAC Nominal Resistance at 180ºC 0.1452 ohm/km 0.2338 ohm/mile

12891358

GMR (estimated) 8.85 mm 0.0290 ft.Inductive Reactance 0.267 ohm/km 0.4296 ohm/mileCapacitive Reactance 0.159 Mohm-km 0.0988 Mohm-mile

F-730-507-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® HAWK

1350-O63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

Page 7: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 309/60/224 (609 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 308.8 mm2 609.5 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Aluminum Nominal Weight** 851.8 kg/km 572.5 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 797.1 W-s/m-C 135.0 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 60.3 mm2 0.0935 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-208) 8.76 mm 0.345 in.

Core Nominal Weight 113.0 kg/km 75.8 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 129.0 kN 29.0 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 91.9 W-s/m-°C 15.6 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 22.40 mm 0.882 in.

Nominal Cross-sectional Area of the Conductor 369.1 mm2 0.572 in2

Ultimate Tensile Strength of Conductor2 146.3 kN 32.9 kips

Conductor Nominal Weight** 964.8 kg/km 648.3 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 16.7 x10-6/°C 9.30 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 64.3 GPa 9.3 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0903 ohm/km 0.1454 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0926 ohm/km 0.1491 ohm/mileAC Nominal Resistance at 75ºC 0.1111 ohm/km 0.1788 ohm/mileAC Nominal Resistance at 180ºC 0.1498 ohm/km 0.2411 ohm/mile

12801348

GMR (estimated) 9.25 mm 0.0303 ft.Inductive Reactance 0.264 ohm/km 0.4243 ohm/mileCapacitive Reactance 0.158 Mohm-km 0.0980 Mohm-mile

F-730-506-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® IRVING

1350-O63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

Page 8: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 362/47/235 (714 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 361.6 mm2 713.5 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Aluminum Nominal Weight** 996.5 kg/km 669.7 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 933.1 W-s/m-C 158.0 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 47.2 mm2 0.0731 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-205) 7.75 mm 0.305 in.

Core Nominal Weight 88.3 kg/km 59.3 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 101.0 kN 22.7 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 71.8 W-s/m-°C 12.2 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 23.55 mm 0.927 in.

Nominal Cross-sectional Area of the Conductor 408.8 mm2 0.634 in2

Ultimate Tensile Strength of Conductor2 121.0 kN 27.2 kips

Conductor Nominal Weight** 1084.8 kg/km 729.0 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 18.5 x10-6/°C 10.27 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 60.9 GPa 8.8 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0771 ohm/km 0.1240 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0792 ohm/km 0.1274 ohm/mileAC Nominal Resistance at 75ºC 0.0947 ohm/km 0.1524 ohm/mileAC Nominal Resistance at 180ºC 0.1273 ohm/km 0.2049 ohm/mile

14101486

GMR (estimated) 9.57 mm 0.0314 ft.Inductive Reactance 0.261 ohm/km 0.4200 ohm/mileCapacitive Reactance 0.155 Mohm-km 0.0965 Mohm-mile

F-730-508-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® DOVE

1350-O63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

Page 9: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 398/71/251 (785 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 397.6 mm2 784.7 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Aluminum Nominal Weight** 1096.7 kg/km 737.1 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 1026.1 W-s/m-C 173.8 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 71.30 mm2 0.1100 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-207) 9.53 mm 0.375 in.

Core Nominal Weight 133.0 kg/km 89.2 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 151.7 kN 34.1 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 108.1 W-s/m-°C 18.3 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 25.14 mm 0.990 in.

Nominal Cross-sectional Area of the Conductor 468.9 mm2 0.726 in2

Ultimate Tensile Strength of Conductor2 173.9 kN 39.1 kips

Conductor Nominal Weight** 1229.7 kg/km 826.3 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 17.4 x10-6/°C 9.68 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 65.2 GPa 9.5 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0702 ohm/km 0.1131 ohm/mile

Temperature Coefficient of Resistance 0.00416 /°C 0.00215 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0725 ohm/km 0.1168 ohm/mileAC Nominal Resistance at 75ºC 0.0870 ohm/km 0.1400 ohm/mileAC Nominal Resistance at 180ºC 0.1174 ohm/km 0.1890 ohm/mile

14991579

GMR (estimated) 10.34 mm 0.0339 ft.Inductive Reactance 0.255 ohm/km 0.4105 ohm/mileCapacitive Reactance 0.152 Mohm-km 0.0946 Mohm-mile

F-730-510-F www.ctcglobal.com Date Produced: 3/29/2019

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

1350-O63%

63%

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® AMARILLO

PRELIMINARY

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

Page 10: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 416/52/251 (821 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 416.2 mm2 821.4 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Aluminum Nominal Weight** 1147.0 kg/km 770.9 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 1074.1 W-s/m-C 181.9 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 51.9 mm2 0.0804 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-206) 8.13 mm 0.320 in.

Core Nominal Weight 97.1 kg/km 65.2 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 110.8 kN 24.9 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 78.9 W-s/m-°C 13.4 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 25.15 mm 0.990 in.

Nominal Cross-sectional Area of the Conductor 468.1 mm2 0.726 in2

Ultimate Tensile Strength of Conductor2 133.9 kN 30.1 kips

Conductor Nominal Weight** 1244.1 kg/km 836.1 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 18.7 x10-6/°C 10.37 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 60.6 GPa 8.8 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0672 ohm/km 0.1081 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0692 ohm/km 0.1114 ohm/mileAC Nominal Resistance at 75ºC 0.0829 ohm/km 0.1334 ohm/mileAC Nominal Resistance at 180ºC 0.1116 ohm/km 0.1796 ohm/mile

15371620

GMR (estimated) 10.20 mm 0.0335 ft.Inductive Reactance 0.256 ohm/km 0.4121 ohm/mileCapacitive Reactance 0.152 Mohm-km 0.0946 Mohm-mile

F-730-511-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® GROSBEAK

1350-O63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

Page 11: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 458/60/264 (904 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 458.0 mm2 903.9 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Aluminum Nominal Weight** 1261.7 kg/km 848.0 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 1182.0 W-s/m-C 200.2 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 60.3 mm2 0.0935 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-208) 8.76 mm 0.345 in.

Core Nominal Weight 113.0 kg/km 75.8 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 129.0 kN 29.0 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 91.9 W-s/m-°C 15.6 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 26.42 mm 1.040 in.

Nominal Cross-sectional Area of the Conductor 518.3 mm2 0.803 in2

Ultimate Tensile Strength of Conductor2 154.4 kN 34.7 kips

Conductor Nominal Weight** 1374.7 kg/km 923.8 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 18.3 x10-6/°C 10.19 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 61.4 GPa 8.9 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0608 ohm/km 0.0979 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0628 ohm/km 0.1011 ohm/mileAC Nominal Resistance at 75ºC 0.0752 ohm/km 0.1210 ohm/mileAC Nominal Resistance at 180ºC 0.1011 ohm/km 0.1628 ohm/mile

16401729

GMR (estimated) 10.74 mm 0.0352 ft.Inductive Reactance 0.252 ohm/km 0.4061 ohm/mileCapacitive Reactance 0.150 Mohm-km 0.0931 Mohm-mile

F-730-512-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® LUBBOCK

1350-O63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

Page 12: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 512/60/277 (1011 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 512.5 mm2 1011.3 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Layer 3 %IACS/Aluminum Type

Aluminum Nominal Weight** 1412.0 kg/km 949.0 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 1322.6 W-s/m-C 224.0 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 60.3 mm2 0.0935 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-208) 8.76 mm 0.345 in.

Core Nominal Weight 113.0 kg/km 75.8 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 129.0 kN 29.0 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 91.9 W-s/m-°C 15.6 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 27.69 mm 1.090 in.

Nominal Cross-sectional Area of the Conductor 572.8 mm2 0.888 in2

Ultimate Tensile Strength of Conductor2 157.5 kN 35.4 kips

Conductor Nominal Weight** 1525.0 kg/km 1024.8 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 18.7 x10-6/°C 10.42 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 60.7 GPa 8.8 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0544 ohm/km 0.0875 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0564 ohm/km 0.0907 ohm/mileAC Nominal Resistance at 75ºC 0.0674 ohm/km 0.1084 ohm/mileAC Nominal Resistance at 180ºC 0.0905 ohm/km 0.1456 ohm/mile

17601856

GMR (estimated) 11.21 mm 0.0368 ft.Inductive Reactance 0.249 ohm/km 0.4007 ohm/mileCapacitive Reactance 0.148 Mohm-km 0.0917 Mohm-mile

F-730-518-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® GALVESTON

1350-O63%

63%

0%

@ 180C & 60 Hz@ 200C & 60 Hz

0

1350-O

Page 13: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 520/71/281 (1026 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 519.7 mm2 1025.6 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Aluminum Nominal Weight** 1432.6 kg/km 962.8 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 1341.2 W-s/m-C 227.1 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 71.3 mm2 0.1100 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-207) 9.53 mm 0.375 in.

Core Nominal Weight 133.0 kg/km 89.2 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 151.7 kN 34.1 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 108.1 W-s/m-°C 18.3 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 28.14 mm 1.108 in.

Nominal Cross-sectional Area of the Conductor 591.0 mm2 0.916 in2

Ultimate Tensile Strength of Conductor2 180.6 kN 40.6 kips

Conductor Nominal Weight** 1565.6 kg/km 1052.0 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 18.3 x10-6/°C 10.18 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 61.2 GPa 8.9 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0536 ohm/km 0.0863 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0554 ohm/km 0.0892 ohm/mileAC Nominal Resistance at 75ºC 0.0662 ohm/km 0.1065 ohm/mileAC Nominal Resistance at 180ºC 0.0888 ohm/km 0.1428 ohm/mile

17861884

GMR (estimated) 11.46 mm 0.0376 ft.Inductive Reactance 0.247 ohm/km 0.3981 ohm/mileCapacitive Reactance 0.147 Mohm-km 0.0912 Mohm-mile

F-730-513-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® DRAKE

1350-O63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

Page 14: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 537/60/286 (1059 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 536.9 mm2 1059.5 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Layer 3 %IACS/Aluminum Type

Aluminum Nominal Weight** 1483.4 kg/km 997.0 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 1385.5 W-s/m-C 234.6 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 60.3 mm2 0.0935 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-208) 8.76 mm 0.345 in.

Core Nominal Weight 113.0 kg/km 75.8 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 129.0 kN 29.0 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 91.9 W-s/m-°C 15.6 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 28.63 mm 1.127 in.

Nominal Cross-sectional Area of the Conductor 597.2 mm2 0.926 in2

Ultimate Tensile Strength of Conductor2 158.8 kN 35.7 kips

Conductor Nominal Weight** 1596.4 kg/km 1072.8 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 18.9 x10-6/°C 10.50 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 60.4 GPa 8.8 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0522 ohm/km 0.0840 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0544 ohm/km 0.0876 ohm/mileAC Nominal Resistance at 75ºC 0.0649 ohm/km 0.1045 ohm/mileAC Nominal Resistance at 180ºC 0.0870 ohm/km 0.1400 ohm/mile

18131913

GMR (estimated) 11.57 mm 0.0379 ft.Inductive Reactance 0.247 ohm/km 0.3971 ohm/mileCapacitive Reactance 0.146 Mohm-km 0.0907 Mohm-mile

F-730-516-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® PLANO

1350-O63%

63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

1350-O

Page 15: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 523/87/290 (1033 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 523.4 mm2 1033.0 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Aluminum Nominal Weight** 1455.3 kg/km 978.1 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 1350.9 W-s/m-C 228.8 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 87.25 mm2 0.1350 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-211) 10.54 mm 0.415 in.

Core Nominal Weight 163.0 kg/km 110.0 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 185.9 kN 41.8 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 132.5 W-s/m-°C 22.5 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 28.96 mm 1.140 in.

Nominal Cross-sectional Area of the Conductor 610.7 mm2 0.946 in2

Ultimate Tensile Strength of Conductor2 215.3 kN 48.4 kips

Conductor Nominal Weight** 1618.3 kg/km 1088.1 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 17.5 x10-6/°C 9.75 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 62.5 GPa 9.1 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0535 ohm/km 0.0862 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0558 ohm/km 0.0898 ohm/mileAC Nominal Resistance at 75ºC 0.0664 ohm/km 0.1069 ohm/mileAC Nominal Resistance at 180ºC 0.0888 ohm/km 0.1429 ohm/mile

18021901

GMR (estimated) 11.87 mm 0.0389 ft.Inductive Reactance 0.245 ohm/km 0.3939 ohm/mileCapacitive Reactance 0.145 Mohm-km 0.0904 Mohm-mile

F-730-514-F www.ctcglobal.com Date Produced: 3/29/2019

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

1350-O63%

63%

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® CURLEW

PRELIMINARY

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

Page 16: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 559/60/291 (1103 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 558.9 mm2 1103.0 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Layer 3 %IACS/Aluminum Type

Aluminum Nominal Weight** 1543.0 kg/km 1037.0 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 1442.4 W-s/m-C 244.3 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 60.3 mm2 0.0935 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-208) 8.76 mm 0.345 in.

Core Nominal Weight 113.0 kg/km 75.8 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 129.0 kN 29.0 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 91.9 W-s/m-°C 15.6 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 29.11 mm 1.146 in.

Nominal Cross-sectional Area of the Conductor 619.2 mm2 0.960 in2

Ultimate Tensile Strength of Conductor2 160.1 kN 36.0 kips

Conductor Nominal Weight** 1656.0 kg/km 1112.8 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 19.0 x10-6/°C 10.58 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 60.2 GPa 8.7 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0501 ohm/km 0.0806 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0524 ohm/km 0.0843 ohm/mileAC Nominal Resistance at 75ºC 0.0625 ohm/km 0.1005 ohm/mileAC Nominal Resistance at 180ºC 0.0836 ohm/km 0.1346 ohm/mile

18601962

GMR (estimated) 11.75 mm 0.0385 ft.Inductive Reactance 0.246 ohm/km 0.3952 ohm/mileCapacitive Reactance 0.145 Mohm-km 0.0902 Mohm-mile

F-730-515-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® CORPUS CHRISTI

1350-O63%

63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

1350-O

Page 17: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 583/71/299 (1151 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 583.2 mm2 1151.0 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Layer 3 %IACS/Aluminum Type

Aluminum Nominal Weight** 1612.9 kg/km 1084.0 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 1505.2 W-s/m-C 254.9 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 71.3 mm2 0.1100 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-207) 9.53 mm 0.375 in.

Core Nominal Weight 133.0 kg/km 89.2 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 151.7 kN 34.1 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 108.1 W-s/m-°C 18.3 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 29.90 mm 1.177 in.

Nominal Cross-sectional Area of the Conductor 654.5 mm2 1.014 in2

Ultimate Tensile Strength of Conductor2 184.2 kN 41.4 kips

Conductor Nominal Weight** 1745.9 kg/km 1173.2 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 18.7 x10-6/°C 10.40 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 60.5 GPa 8.8 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0480 ohm/km 0.0773 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0502 ohm/km 0.0809 ohm/mileAC Nominal Resistance at 75ºC 0.0599 ohm/km 0.0964 ohm/mileAC Nominal Resistance at 180ºC 0.0802 ohm/km 0.1290 ohm/mile

19152021

GMR (estimated) 12.11 mm 0.0397 ft.Inductive Reactance 0.243 ohm/km 0.3915 ohm/mileCapacitive Reactance 0.144 Mohm-km 0.0894 Mohm-mile

F-730-517-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® ARLINGTON

1350-O63%

63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

1350-O

Page 18: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 619/60/304 (1222 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 619.1 mm2 1221.8 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Layer 3 %IACS/Aluminum Type

Aluminum Nominal Weight** 1709.6 kg/km 1149.0 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 1597.8 W-s/m-C 270.6 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 60.3 mm2 0.0935 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-208) 8.76 mm 0.345 in.

Core Nominal Weight 113.0 kg/km 75.8 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 129.0 kN 29.0 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 91.9 W-s/m-°C 15.6 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 30.43 mm 1.198 in.

Nominal Cross-sectional Area of the Conductor 679.4 mm2 1.053 in2

Ultimate Tensile Strength of Conductor2 163.7 kN 36.8 kips

Conductor Nominal Weight** 1822.6 kg/km 1224.8 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 19.4 x10-6/°C 10.76 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 59.7 GPa 8.7 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0452 ohm/km 0.0728 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0473 ohm/km 0.0762 ohm/mileAC Nominal Resistance at 75ºC 0.0563 ohm/km 0.0906 ohm/mileAC Nominal Resistance at 180ºC 0.0751 ohm/km 0.1208 ohm/mile

19902101

GMR (estimated) 12.25 mm 0.0402 ft.Inductive Reactance 0.242 ohm/km 0.3900 ohm/mileCapacitive Reactance 0.143 Mohm-km 0.0889 Mohm-mile

F-730-519-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® CARDINAL

1350-O63%

63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

1350-O

Page 19: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 659/71/315 (1300 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 658.9 mm2 1300.4 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Layer 3 %IACS/Aluminum Type

Aluminum Nominal Weight** 1819.7 kg/km 1223.0 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 1700.5 W-s/m-C 288.0 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 71.3 mm2 0.1100 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-207) 9.53 mm 0.375 in.

Core Nominal Weight 133.0 kg/km 89.2 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 151.7 kN 34.1 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 108.1 W-s/m-°C 18.3 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 31.50 mm 1.240 in.

Nominal Cross-sectional Area of the Conductor 730.2 mm2 1.131 in2

Ultimate Tensile Strength of Conductor2 188.6 kN 42.4 kips

Conductor Nominal Weight** 1952.7 kg/km 1312.2 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 19.1 x10-6/°C 10.63 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 59.9 GPa 8.7 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0425 ohm/km 0.0684 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0448 ohm/km 0.0721 ohm/mileAC Nominal Resistance at 75ºC 0.0533 ohm/km 0.0858 ohm/mileAC Nominal Resistance at 180ºC 0.0711 ohm/km 0.1145 ohm/mile

20672183

GMR (estimated) 12.72 mm 0.0417 ft.Inductive Reactance 0.240 ohm/km 0.3855 ohm/mileCapacitive Reactance 0.141 Mohm-km 0.0879 Mohm-mile

F-730-520-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® FORT WORTH

1350-O63%

63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

1350-O

Page 20: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 684/60/318 (1350 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 684.0 mm2 1349.9 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Layer 3 %IACS/Aluminum Type

Aluminum Nominal Weight** 1888.2 kg/km 1269.0 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 1765.3 W-s/m-C 298.9 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 60.3 mm2 0.0935 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-208) 8.76 mm 0.345 in.

Core Nominal Weight 113.0 kg/km 75.8 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 129.0 kN 29.0 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 91.9 W-s/m-°C 15.6 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 31.80 mm 1.252 in.

Nominal Cross-sectional Area of the Conductor 744.3 mm2 1.154 in2

Ultimate Tensile Strength of Conductor2 167.3 kN 37.6 kips

Conductor Nominal Weight** 2001.2 kg/km 1344.8 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 19.7 x10-6/°C 10.92 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 59.2 GPa 8.6 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0409 ohm/km 0.0659 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0434 ohm/km 0.0698 ohm/mileAC Nominal Resistance at 75ºC 0.0515 ohm/km 0.0829 ohm/mileAC Nominal Resistance at 180ºC 0.0686 ohm/km 0.1104 ohm/mile

21112230

GMR (estimated) 12.76 mm 0.0419 ft.Inductive Reactance 0.239 ohm/km 0.3850 ohm/mileCapacitive Reactance 0.141 Mohm-km 0.0876 Mohm-mile

F-730-521-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® EL PASO

1350-O63%

63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

1350-O

Page 21: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 724/71/329 (1429 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 723.9 mm2 1428.6 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Layer 3 %IACS/Aluminum Type

Aluminum Nominal Weight** 2004.2 kg/km 1347.0 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 1868.2 W-s/m-C 316.3 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 71.3 mm2 0.1100 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-207) 9.53 mm 0.375 in.

Core Nominal Weight 133.0 kg/km 89.2 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 151.7 kN 34.1 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 108.1 W-s/m-°C 18.3 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 32.87 mm 1.294 in.

Nominal Cross-sectional Area of the Conductor 795.2 mm2 1.232 in2

Ultimate Tensile Strength of Conductor2 192.2 kN 43.2 kips

Conductor Nominal Weight** 2137.2 kg/km 1436.2 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 19.4 x10-6/°C 10.79 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 59.4 GPa 8.6 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0387 ohm/km 0.0623 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0411 ohm/km 0.0661 ohm/mileAC Nominal Resistance at 75ºC 0.0488 ohm/km 0.0785 ohm/mileAC Nominal Resistance at 180ºC 0.0649 ohm/km 0.1045 ohm/mile

21932317

GMR (estimated) 13.23 mm 0.0434 ft.Inductive Reactance 0.237 ohm/km 0.3807 ohm/mileCapacitive Reactance 0.139 Mohm-km 0.0866 Mohm-mile

F-730-522-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® BEAUMONT

1350-O63%

63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

1350-O

Page 22: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 747/75/334 (1475 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 747.4 mm2 1474.9 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Layer 3 %IACS/Aluminum Type

Aluminum Nominal Weight** 2068.2 kg/km 1390.0 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 1928.8 W-s/m-C 326.6 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 75.1 mm2 0.1160 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-209) 9.78 mm 0.385 in.

Core Nominal Weight 140.0 kg/km 94.1 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 160.1 kN 36.0 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 113.8 W-s/m-°C 19.3 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 33.40 mm 1.315 in.

Nominal Cross-sectional Area of the Conductor 822.5 mm2 1.274 in2

Ultimate Tensile Strength of Conductor2 201.9 kN 45.4 kips

Conductor Nominal Weight** 2208.2 kg/km 1484.1 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 19.4 x10-6/°C 10.75 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 59.5 GPa 8.6 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0375 ohm/km 0.0603 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0387 ohm/km 0.0623 ohm/mileAC Nominal Resistance at 75ºC 0.0458 ohm/km 0.0738 ohm/mileAC Nominal Resistance at 180ºC 0.0608 ohm/km 0.0978 ohm/mile

22782408

GMR (estimated) 13.46 mm 0.0441 ft.Inductive Reactance 0.235 ohm/km 0.3787 ohm/mileCapacitive Reactance 0.139 Mohm-km 0.0861 Mohm-mile

F-730-523-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® SAN ANTONIO

1350-O63%

63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

1350-O

Page 23: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 801/60/342 (1582 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 801.4 mm2 1581.6 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Layer 3 %IACS/Aluminum Type

Aluminum Nominal Weight** 2217.0 kg/km 1490.0 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 2068.3 W-s/m-C 350.2 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 60.3 mm2 0.0935 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-208) 8.76 mm 0.345 in.

Core Nominal Weight 113.0 kg/km 75.8 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 129.0 kN 29.0 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 91.9 W-s/m-°C 15.6 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 34.16 mm 1.345 in.

Nominal Cross-sectional Area of the Conductor 861.7 mm2 1.336 in2

Ultimate Tensile Strength of Conductor2 173.9 kN 39.1 kips

Conductor Nominal Weight** 2330.0 kg/km 1565.8 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 20.1 x10-6/°C 11.16 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 58.5 GPa 8.5 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0352 ohm/km 0.0566 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0375 ohm/km 0.0603 ohm/mileAC Nominal Resistance at 75ºC 0.0444 ohm/km 0.0714 ohm/mileAC Nominal Resistance at 180ºC 0.0589 ohm/km 0.0947 ohm/mile

23332466

GMR (estimated) 13.66 mm 0.0448 ft.Inductive Reactance 0.234 ohm/km 0.3768 ohm/mileCapacitive Reactance 0.138 Mohm-km 0.0855 Mohm-mile

F-730-524-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® BITTERN

1350-O63%

63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

1350-O

Page 24: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 910/75/369 (1795 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 909.5 mm2 1794.9 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Layer 3 %IACS/Aluminum Type

Layer 4 %IACS/Aluminum Type

Aluminum Nominal Weight** 2528.0 kg/km 1699.0 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 2347.2 W-s/m-C 397.5 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 75.10 mm2 0.1160 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-209) 9.78 mm 0.385 in.

Core Nominal Weight 140.0 kg/km 94.1 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 160.1 kN 36.0 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°F

Modulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 113.8 W-s/m-°C 19.3 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 36.88 mm 1.452 in.

Nominal Cross-sectional Area of the Conductor 984.6 mm2 1.526 in2

Ultimate Tensile Strength of Conductor2 211.3 kN 47.5 kips

Conductor Nominal Weight** 2668.0 kg/km 1793.1 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 19.9 x10-6/°C 11.07 x10-6/°F

Final Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 58.6 GPa 8.5 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oF

Electrical Specification

Nominal DC Resistivity at 20ºC 0.0309 ohm/km 0.0497 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0339 ohm/km 0.0546 ohm/mileAC Nominal Resistance at 75ºC 0.0398 ohm/km 0.0640 ohm/mileAC Nominal Resistance at 180ºC 0.0521 ohm/km 0.0839 ohm/mile

25412689

GMR (estimated) 14.77 mm 0.0485 ft.Inductive Reactance 0.228 ohm/km 0.3673 ohm/mileCapacitive Reactance 0.134 Mohm-km 0.0832 Mohm-mile

F-730-525-F www.ctcglobal.com Date Produced: 4/1/2019

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

1350-O

1350-O

1350-O63%

63%

63%

63%

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® DALLAS

PRELIMINARY

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

Page 25: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 988/75/382 (1949 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 987.6 mm2 1948.9 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Layer 3 %IACS/Aluminum Type

Aluminum Nominal Weight** 2743.7 kg/km 1844.0 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 2548.7 W-s/m-C 431.6 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 75.1 mm2 0.1160 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-209) 9.78 mm 0.385 in.

Core Nominal Weight 140.0 kg/km 94.1 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 160.1 kN 36.0 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 113.8 W-s/m-°C 19.3 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 38.20 mm 1.504 in.

Nominal Cross-sectional Area of the Conductor 1062.7 mm2 1.647 in2

Ultimate Tensile Strength of Conductor2 215.3 kN 48.4 kips

Conductor Nominal Weight** 2883.7 kg/km 1938.1 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 20.1 x10-6/°C 11.19 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 58.3 GPa 8.5 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0285 ohm/km 0.0458 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0315 ohm/km 0.0507 ohm/mileAC Nominal Resistance at 75ºC 0.0370 ohm/km 0.0595 ohm/mileAC Nominal Resistance at 180ºC 0.0485 ohm/km 0.0780 ohm/mile

26652821

GMR (estimated) 15.27 mm 0.0501 ft.Inductive Reactance 0.226 ohm/km 0.3633 ohm/mileCapacitive Reactance 0.132 Mohm-km 0.0822 Mohm-mile

F-730-527-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® LAPWING

1350-O63%

63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

1350-O

Page 26: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 977/87/383 (1927 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 976.7 mm2 1927.4 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Layer 3 %IACS/Aluminum Type

Aluminum Nominal Weight** 2713.9 kg/km 1824.0 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 2520.6 W-s/m-C 426.8 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 87.3 mm2 0.1350 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-211) 10.54 mm 0.415 in.

Core Nominal Weight 163.0 kg/km 110.0 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 185.9 kN 41.8 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 132.5 W-s/m-°C 22.5 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 38.25 mm 1.506 in.

Nominal Cross-sectional Area of the Conductor 1063.9 mm2 1.649 in2

Ultimate Tensile Strength of Conductor2 240.6 kN 54.1 kips

Conductor Nominal Weight** 2876.9 kg/km 1934.0 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 19.7 x10-6/°C 10.94 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 59.0 GPa 8.6 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0285 ohm/km 0.0459 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0317 ohm/km 0.0510 ohm/mileAC Nominal Resistance at 75ºC 0.0370 ohm/km 0.0596 ohm/mileAC Nominal Resistance at 180ºC 0.0482 ohm/km 0.0775 ohm/mile

26752833

GMR (estimated) 15.35 mm 0.0504 ft.Inductive Reactance 0.225 ohm/km 0.3625 ohm/mileCapacitive Reactance 0.132 Mohm-km 0.0821 Mohm-mile

F-730-526-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® HOUSTON

1350-O63%

63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

1350-O

Page 27: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 1036/87/392 (2045 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 1036.3 mm2 2045.1 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Layer 3 %IACS/Aluminum Type

Aluminum Nominal Weight** 2879.1 kg/km 1935.0 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 2674.4 W-s/m-C 452.9 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 87.3 mm2 0.1350 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-211) 10.54 mm 0.415 in.

Core Nominal Weight 163.0 kg/km 110.0 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 185.9 kN 41.8 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 132.5 W-s/m-°C 22.5 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 39.24 mm 1.545 in.

Nominal Cross-sectional Area of the Conductor 1123.5 mm2 1.741 in2

Ultimate Tensile Strength of Conductor2 244.2 kN 54.9 kips

Conductor Nominal Weight** 3042.1 kg/km 2045.0 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 19.9 x10-6/°C 11.03 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 58.7 GPa 8.5 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0271 ohm/km 0.0436 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0298 ohm/km 0.0479 ohm/mileAC Nominal Resistance at 75ºC 0.0350 ohm/km 0.0563 ohm/mileAC Nominal Resistance at 180ºC 0.0459 ohm/km 0.0739 ohm/mile

27612923

GMR (estimated) 15.73 mm 0.0516 ft.Inductive Reactance 0.223 ohm/km 0.3597 ohm/mileCapacitive Reactance 0.131 Mohm-km 0.0814 Mohm-mile

F-730-528-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® FALCON

1350-O63%

63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

1350-O

Page 28: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 1136/79/407 (2242 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 1135.8 mm2 2241.5 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Layer 3 %IACS/Aluminum Type

Aluminum Nominal Weight** 3155.9 kg/km 2121.0 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 2931.3 W-s/m-C 496.4 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 79.0 mm2 0.1230 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-210) 10.03 mm 0.395 in.

Core Nominal Weight 148.0 kg/km 99.8 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 169.5 kN 38.1 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 120.3 W-s/m-°C 20.4 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 40.74 mm 1.604 in.

Nominal Cross-sectional Area of the Conductor 1214.8 mm2 1.884 in2

Ultimate Tensile Strength of Conductor2 233.1 kN 52.4 kips

Conductor Nominal Weight** 3303.9 kg/km 2220.8 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 20.3 x10-6/°C 11.30 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 58.0 GPa 8.4 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0247 ohm/km 0.0398 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0277 ohm/km 0.0445 ohm/mileAC Nominal Resistance at 75ºC 0.0324 ohm/km 0.0521 ohm/mileAC Nominal Resistance at 180ºC 0.0423 ohm/km 0.0681 ohm/mile

29133085

GMR (estimated) 16.25 mm 0.0533 ft.Inductive Reactance 0.221 ohm/km 0.3558 ohm/mileCapacitive Reactance 0.129 Mohm-km 0.0803 Mohm-mile

F-730-529-F www.ctcglobal.com Date Produced: 3/25/2019

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® CHUKAR

1350-O63%

63%

63%

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

1350-O

Page 29: ACCC® OCEANSIDE...18.29 mm 0.720 in. Nominal Cross-sectional Area of the Conductor 246.1 mm. 2. 0.382 in Ultimate Tensile Strength of Conductor. 2. 71.6 kN 16.1 kips Conductor Nominal

DATA SHEET:

ACCC® 1389/87/448 (2741 kcmil)*

Metric and US Units are considered separate

Aluminum Specification

Nominal Aluminum Cross-sectional Area*** 1388.7 mm2 2740.6 kcmil

Layer 1 %IACS/Aluminum Type (inner)

Layer 2 %IACS/Aluminum Type

Layer 3 %IACS/Aluminum Type

Aluminum Nominal Weight** 3858.1 kg/km 2593.0 lb/kft

Coefficient of Thermal Expansion 23.0 x10-6/°C 12.8 x10-6/°FAluminum Heat Capacity 3584.0 W-s/m-C 606.9 W-s/ft-F

ACCC® Core Specification

Nominal Cross-sectional Area of Core 87.3 mm2 0.1350 in2

Nominal Diameter of Composite Core (CTC Part Number F-730-211) 10.54 mm 0.415 in.

Core Nominal Weight 163.0 kg/km 110.0 lb/kft

Rated Strength of Core - 310 ksi (2137 MPa) 185.9 kN 41.8 kips

Coefficient of Thermal Expansion 1.61 x10-6/°C 0.894 x10-6/°FModulus of Elasticity 112.3 GPa 16.29 Msi

Core Heat Capacity 132.5 W-s/m-°C 22.5 W-s/ft-°F

ACCC® Conductor Specification

Overall Diameter of Conductor1 44.75 mm 1.762 in.

Nominal Cross-sectional Area of the Conductor 1476.0 mm2 2.288 in2

Ultimate Tensile Strength of Conductor2 263.7 kN 59.3 kips

Conductor Nominal Weight** 4021.1 kg/km 2703.0 lb/kft

Coefficient of Linear Expansion Above Thermal Kneepoint 1.61 x10-6/°C 0.894 x10-6/°F

Coefficient of Linear Expansion Below Thermal Kneepoint 20.6 x10-6/°C 11.43 x10-6/°FFinal Modulus of Elasticity Above Thermal Kneepoint 112.3 GPa 16.29 Msi

Final Modulus of Elasticity Below Thermal Kneepoint 57.7 GPa 8.4 Msi

Maximum Allowable Operating Temperature at Surface3 180 oC 356 oFElectrical Specification

Nominal DC Resistivity at 20ºC 0.0203 ohm/km 0.0326 ohm/mile

Temperature Coefficient of Resistance 0.00404 /°C 0.00209 /oFFrequency 60 Hz 60 HzAC Nominal Resistance at 25ºC 0.0240 ohm/km 0.0387 ohm/mileAC Nominal Resistance at 75ºC 0.0278 ohm/km 0.0447 ohm/mileAC Nominal Resistance at 180ºC 0.0356 ohm/km 0.0573 ohm/mile

32743474

GMR (estimated) 17.82 mm 0.0585 ft.Inductive Reactance 0.214 ohm/km 0.3445 ohm/mileCapacitive Reactance 0.125 Mohm-km 0.0775 Mohm-mile

F-730-531-F www.ctcglobal.com Date Produced: 3/25/2019

@ 180C & 60 Hz@ 200C & 60 Hz

1350-O

1350-O

1350-O63%

63%

63%

For questions, please contact CTC Application Engineering Department: [email protected]

Metric US Units

ACCC® BLUEBIRD

Metric US Units

Metric US Units

AC Current Rating at Given Temperatures4

ACCC® is produced using 1350-O (fully annealed) aluminum.

**ACCC® Conductors are required to exhibit lay lengths (ratios) that conform to ASTM B 857 or EN 50540.

4) Conditions: 2 ft/s (0.61 m/s) wind, 0 ft (0 m) Elevation, 0.5 Emis. 0.5 absorp., 25°C Ambient temp., 96 W/sq. ft (1033 W/sq. m) sun

3) Maximum operating temperature of ACCC® is 180°C and a maximum emergency temperature of 200°C. (10,000 hours over the life of the conductor)

***Different configurations among conductor manufacturers may result in slight variations within the parameters of indicated values for a given size in

accordance with the stated specification

Metric US Units

1) Minimum hub diameter of the conductor reel must meet the requirements of CTC F-750-032.

2) Strength at ambient temperature. Based on 96% of the 1350-O minimum tensile strength (8500 psi/58.6 Mpa).

*ASTM name designation: mm² nominal aluminum area/mm² nominal core area/mm nominal diameterx10 (nominal kcmil aluminum)