AC Motor Group Controller Installer’s · PDF file4 Determine a Mounting Location •...
Transcript of AC Motor Group Controller Installer’s · PDF file4 Determine a Mounting Location •...
A Step-by-Step Guide for Installing, Operating and Maintaining a LutronAC Motor Group ControllerPlease Read Before Installing
Models:WC-2M-GC 2 Motor ControllerWC-4M-GC 4 Motor Controller
AC Motor Group ControllerInstaller’s Guide
2
Table of ContentsDescription and Ratings . . . . . . . . . . . . . . . . . . . . . . .2
Important Information . . . . . . . . . . . . . . . . . . . . . . . . .2
System Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Determine a Mounting Location . . . . . . . . . . . . . . . . .4
Pre-installation Motor Wiring Check . . . . . . . . . . . . . .5
Line Voltage Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Configuring the Motor Direction for Open and Close Functions . . . . . . . . . . . . . . . . . . . . .7
Contact Closure Input Control Wiring . . . . . . . . . . . .7
Example of Individual Control (no dedicated stop input) . . . . . . . . . . . . . . . . . . .8
Example of individual Control (with dedicated stop input) . . . . . . . . . . . . . . . . . .9
Example of Master Control (with dedicated stop input) . . . . . . . . . . . . . . . . .10
Connecting Multiple Group Controllers . . . . . . .11
Setting the Contact Closure Input Type . . . . . . . . . .12
Appendix A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Important Information• Before starting the installation, please completely read
these installation instructions.
• This control must be installed by a certified electrician.
• Install in accordance with all local and national electricalcodes.
• Turn power OFF at circuit breaker or remove fusebefore installing and wiring the controller. Do not wirewith power ON.
• Operating environment should be between 32° F to104° F (0° C to 40° C).
• Proper short circuit protection and overload protectionmust be provided at the distribution panel. You can useup to a 20 A breaker for your application, whereapplicable.
DescriptionThe WC-2M-GC and WC-4M-GC Group Controllers aredesigned to control AC motorized window treatments andprojection screens. Both control single phase, bi-directionalAC motors (three wire motors: open, close, neutral). Twomodels are available to control up to two motors (WC-2M-GC) or up to four motors (WC-4M-GC). Both accept inputsfrom controls that provide low-voltage, Class 2, dry contactclosures. Each Group Controller has individual motorcontrol inputs as well as a master control input. This allowsindividual control of each motor or control of all motors atthe same time.
RatingsInput110–127 V~, 60 Hz Single Phase20 A maximum input current
Load Capacity5 A, 1/4 HP motor load per channel @ 120 V~
3
12
34
5
ON
COM1
CLOSE1
STOP1
OPEN1OPE
N1CL
OSE
1O
PEN2
CLO
SE2
OPE
N3CL
OSE
3O
PEN4
CLO
SE4
OPE
N AL
LCL
OSE
ALL
MAS
TER
CONT
ROLS
PRO
GRA
M
STAT
US
POW
ER
OPT
IONS
MS
240V
120V
NN
C1O
1N
C2O
2N
C3O
3N
C4O
4
COM2
CLOSE2
STOP2
OPEN2
COM3
CLOSE3
STOP3
OPEN3
COM4
CLOSE4
STOP4
OPEN4
COM
CLOSE
STOP
OPEN
System Diagram
AC MotorizedWindow
Treatment
WC-4M-GC Group Controller
Distribution Panel
Class 2/PELV Wiring
Line-Voltage 3 Wire AC Motor Wiring
3 conductors plus ground
Line-Voltage Wiring
AC MotorGroup Controller
Coopersburg, PA 18036 USAwww.lutron.com
®
WC-4M-GC4 MOTOR GROUP CONTROLLER110-127 V~ 60 Hz20 A Max. Input Current
LOAD TYPESSingle Phase, Bi-directional Motor5 A, 1/4 HP per Channel at 120 V~
TYPES DE CHARGESPhase Simple, Moteur Bidirectionel5 A, 1/4 HP par Canal a 120 V~
Listed 243CInd. Cont. Eq.
Questions? Call Lutron Technical Support1-800-523-9466 (24 hrs/7 days)
110-127 V~ USA: Class 2
AC MotorizedWindow
Treatment
AC MotorizedWindow
Treatment
AC MotorizedProjection Screen
Contact Closure Device (provided by others)
2 conductorsplus ground
44
Determine a Mounting Location • Mount the WC-2M-GC, WC-4M-GC on a dry, flat indoor
surface such as an electrical closet wall.
• Mount unit in a location that is accessible to allow forsystem programming and setup.
• Unit may be mounted in any orientation.
• The unit’s relays will click audibly in normal use. Mountin a location where this is acceptable.
• The keyholes accept a maximum of 3/16" (5 mm)mounting bolt. No. 8 (M4) bolt recommended.
• Knockouts are 7/8" (22 mm) in diameter.
12
34
5
ON
STATUS POWER
OPTIONS
Neutral
120V
240V
MotorSupply
ON
OPEN 1
CLOSE 1
OPEN ALL
CLOSE ALL
OPEN 4
CLOSE 4
OPEN 3
CLOSE 3
OPEN 2
CLOSE 2
SW Live1B
SW Live1A
Neutral
SW Live2B
SW Live2A
Neutral
SW Live3B
SW Live3A
Neutral
SW Live4B
SW Live4A
Neutral
9.5 in.
12 in.
6.2 in.
1.25 in.
7.9 in.
.735 in.
AC MotorGroup Controller
Coopersburg, PA 18036 USAwww.lutron.com
500-
9575
Rev
. B
®
WC-4M-GC4 MOTOR GROUP CONTROLLER110-127 V~ 60 Hz20 A Max. Input Current
LOAD TYPESSingle Phase, Bi-directional Motor5 A, 1/4 HP per Channel at 120 V~
TYPES DE CHARGESPhase Simple, Moteur Bidirectionel5 A, 1/4 HP par Canal a 120 V~
Listed 243CInd. Cont. Eq.
Questions? Call Lutron Technical Support1-800-523-9466 (24 hrs/7 days)
110-127 V~ USA: Class 2
COM
Open
Stop
Close
COM
Open4
Stop4
Close4
COM
Open3
Stop3
Close3
COM
Open2
Stop2
Close2
COM
Open1
Stop1
Close1
Neutral
120 V
MotorSupplyJumper
SW Live 4B
SW Live4A
Neutral
SW Live3B
SW Live3A
Neutral
SW Live2B
SW Live2A
Neutral
SW Live1B
SW Live1A
Neutral
Line-voltage input power andmotor power wiring entry
Class 2/PELVwiring entry
2.75 in.
Front View
Side View
55
DistributionPanel
Neutrals Earth/Grounds
Hot/Live
Danger - Locate and lock the supply breaker inthe OFF position or remove the supply fusebefore working on any circuit.
MomentarySPDT Switch(wallbox not
shown)
AC MotorizedWindow
Treatment Shown
Pre-installation Motor Wiring CheckTest your wiring before connecting to the Group Controller.Use either a momentary, Single Pole Double Throw(SPDT) switch (as described below) or a motor wiring testkit (available from Lutron). To order the motor wiring testkit, contact Lutron at 1-888-SIVOIA1 (1-888-748-6481) andask for model 6020086.
Note: If using the motor wiring test kit, please refer to theinstructions provided with the kit.
Testing motor wiring using a SPDT switch:1. Turn power OFF at circuit breaker (MCB) or remove
fuse.
2. Connect the motor ground wire to earth ground.Connect earth ground to the ground terminal on theswitch.
3. Connect the motor neutral wire to supply neutral.
4. Using one momentary, Single Pole Double Throw(SPDT) switch for each motor, connect hot/live to thecommon terminal on the switch.
5. Connect one each of the motor power wires to theoutput terminals on the switch. Never wire more thanone motor to a switch.
6. Mount switch in a wallbox. Be sure no bare wires orterminals on the switch are exposed.
7. After verifying it is safe to restore power, turn powerON.
8. Verify motor will raise/open and lower/close properly. Ifnecessary, remove power and correct wiring.
66
Line-Voltage WiringConnect line voltage and the AC Motors to the GroupController.
12
34
5
ON
STATUS POWER
OPTIONS
Neutral
120V
240V
MotorSupply
ON
OPEN ALL
CLOSE ALL
OPEN 4
CLOSE 4
OPEN 3
CLOSE 3
OPEN 2
CLOSE 2
OPEN 1
CLOSE 1
SW Live1B
SW Live1A
Neutral
SW Live2B
SW Live2A
Neutral
SW Live3B
SW Live3A
Neutral
SW Live4B
SW Live4A
Neutral
WC-4M-GC Group Controller
AC Motor 1
Motor 4 Power Wires
Motor 3 Power Wires
Motor 2 Power Wires
Motor 1 Power Wires
Power Feed Wiring
Danger - Locate and lock the supply breaker inthe OFF position or remove the supply fusebefore working on any circuit.
• Only connect one motor to each output. Never wiremotors in parallel.
• The WC-2M-GC and WC-4M-GC accepts 110-127 V~,60 Hz.
• Strip 1/2" of insulation from all power feed and motorpower wires.
• Run power to the Motor Supply Jumper terminal.Connect the Motor Supply Jumper terminal to the120 V Input Voltage terminal using a piece of wire ofthe same gauge as the power feed wiring.
• Connect the motor power wires to the appropriateterminals indicated in the diagram below.
• There is a dedicated earth/grounding block to land theground connections for the power feed and each motor.The recommended tightening torque is 9.0 in-lbs forline-voltage connections and 10 in-lbs for earth groundconnections.
• Run all power feed and motor power wiring through theknockout holes on the sides of the unit.
Wiring Detail
Neutral
120V
240V
MotorSupply
SW Live1B
SW Live1A
Neutral
SW Live2A
Neutral
Power Feed Wiring
Motor 1 Power Wires SW Live 1B
SW Live 1A
Neutral
Neutral
120 V Input
Motor Supply Jumper
Wiring Overview
Note: Motor power wire colors mayvary depending on the motormanufacturer. Refer to the motormanufacturer’s instructions for moredetailed wiring information.
Earth/GroundingBlock
AC Motor 2 AC Motor 3 AC Motor 4
Ground *
* Motor earth/ground wire is not shown inthis diagram. See Wiring Detail below.
Wiring entry knockouts
AC MotorGroup Controller
Coopersburg, PA 18036 USAwww.lutron.com
500-
9575
Rev
. B
®
WC-4M-GC4 MOTOR GROUP CONTROLLER110-127 V~ 60 Hz20 A Max. Input Current
LOAD TYPESSingle Phase, Bi-directional Motor5 A, 1/4 HP per Channel at 120 V~
TYPES DE CHARGESPhase Simple, Moteur Bidirectionel5 A, 1/4 HP par Canal a 120 V~
Listed 243CInd. Cont. Eq.
Questions? Call Lutron Technical Support1-800-523-9466 (24 hrs/7 days)
110-127 V~ USA: Class 2
COM
Open
Stop
Close
COM
Open4
Stop4
Close4
COM
Open3
Stop3
Close3
COM
Open2
Stop2
Close2
COM
Open1
Stop1
Close1
Neutral
120 V
MotorSupplyJumper
SW Live 4B
SW Live4A
Neutral
SW Live3B
SW Live3A
Neutral
SW Live2B
SW Live2A
Neutral
SW Live1B
SW Live1A
Neutral
77
Contact Closure Input Control WiringThe WC-2M-GC and WC-4M-GC accept Class 2, drycontact closure inputs. The contact closure inputs for thisunit may be either momentary or maintained. The contactclosure type selected using the Options switch #5 (OFF =Momentary, ON = Maintained). Momentary dry contactclosure inputs require a minimum closure time of 0.2seconds.
The contact closure device must be able to switch 2 mAat 30 Vdc. If multiple channels or Group Controllers arewired in parallel to one contact closure, the contactclosure device must be rated for the total current of all thechannels or Group Controllers wired together (totalcurrent = 2 mA times the number of Group Controllers orchannels in parallel). Example, if you connect 4 GroupControllers in parallel, the contact closure device wouldneed to be rated for at least 8 mA, at 30 Vdc.
12
34
5
ON
PROGRAMSTATUS POWER
OPTIONS
ON
OPEN ALL
CLOSE ALL
OPEN 4
CLOSE 4
OPEN 3
CLOSE 3
OPEN 2
CLOSE 2
OPEN 1
CLOSE 1
Operate thechannel using theOpen and Closebuttons
ntroller
8036 USA
500-
9575
Rev
. B
®
CCONTROLLER
rrent
rectional Motorannel at 120 V~
RGESeur Bidirectionelnal a 120 V~
43Ct. Eq.
Technical Supports/7 days)
USA: Class 2
COM
Open
Stop
Close
COM
Open4
Stop4
Close4
COM
Open3
Stop3
Close3
COM
Open2
Stop2
Close2
COM
Open1
Stop1
Close1
Change thedesired channel’soutput direction byswitching thecorrespondingOptions switch
Configuring the Motor Direction for theOpen and Close FunctionsFor each Channel of the unit, the motor’s direction ofrotation needs to be configured for the Open and Closefunctions so that the AC Motor will move in the properdirection. This is accomplished using the OptionsSwitches, #1 through #4. This step needs to be performedwhether each channel is controlled individually or allchannels are controlled together.
1. Restore power to unit. Once the appropriate linevoltage and motor connections have been made to theunit, replace the cover on the line voltage wiringcompartment. Remove the cover from the Class 2wiring compartment. Turn power back ON.
2. Determine AC motor position. Determine whetherthe AC Motor that is controlled by Channel 1 is openor closed. If it is open, press the Close 1 manualoverride button. If it is closed, press the Open 1manual override button. If the AC Motor moves to thedesired position, the Channel is configured properly.Proceed to Step 4. If the AC Motor does not move tothe desired position, proceed to Step 3.
3. Verify motor movement. If the AC Motor did notmove to the desired position in the prior step, slide theOptions Switch #1 to the opposite position. Press thesame button again that was pressed in Step 2 (Openor Close). If the AC Motor moves to the desiredposition Channel 1 is now configured properly.Proceed to Step 4.
4. Repeat for remaining motors. Repeat Steps 2 and 3for the rest of the Channels that are connected to ACMotors. Options Switch #2 configures Channel 2,Options Switch #3 configures Channel 3*, and OptionsSwitch #4 configures Channel 4*.
Each motor channel has a contact closure input terminalblock. In addition, the unit has a master control contactclosure input terminal block. The master control contactclosure input will operate all four motor channelssimultaneously. See the wiring diagrams on pages 10–11.
The stop function can be achieved either by providing acontact closure input to the stop terminal of the inputterminal block, or by simultaneously providing a closureon the open and close terminals of the input terminalblock. Both stop methods will be addressed in the wiringdiagrams on pages 8–11.
2
3
Note: Do not change the position of Options Switch #5.This switch is used to change the contact closure inputtype. See section Setting the Contact Closure Input Typeon page 12 for more details on the Options Switch #5.
* Channel 3 and 4 are only available on Group Controller model GRX-4M-GC.
88
12
34
5
ON
STATUS POWER
OPTIONS
ON
OPEN ALL
CLOSE ALL
OPEN 4
CLOSE 4
OPEN 3
CLOSE 3
OPEN 2
CLOSE 2
OPEN 1
CLOSE 1
WC-4M-GC Group Controller Shown
Class 2/PELV Wiring
Com 1Open 1
Close 1
Com 2Open 2
Close 2
Com 3Open 3
Close 3
Com 4Open 4
Close 4
Example of Individual Control (no dedicated stopinput)
In this wiring example, the stop function is achieved bysimultaneously providing a closure on the open and closeterminals of the input terminal block. No connection ismade to the stop terminal on the input terminal block.
Contactclosure inputs3 and 4 areonly availableon the WC-4M-GC
ler
SA
500-
9575
Rev
. B
®
ROLLER
l Motor120 V~
rectionel0 V~
al Support)
Class 2
COM
Open
Stop
Close
COM
Open4
Stop4
Close4
COM
Open3
Stop3
Close3
COM
Open2
Stop2
Close2
COM
Open1
Stop1
Close1
99
12
34
5
ON
STATUS POWER
OPTIONS
ON
OPEN ALL
CLOSE ALL
OPEN 4
CLOSE 4
OPEN 3
CLOSE 3
OPEN 2
CLOSE 2
OPEN 1
CLOSE 1
Example of Individual Control (with dedicated stopinput)
In this wiring example, the stop function is achieved byproviding a closure to the stop terminal of the inputterminal block.
WC-4M-GC Group Controller Shown
Class 2/PELV Wiring
Com 1
Open 1
Stop 1
Close 1
Com 2
Open 2
Stop 2
Close 2
Com 3
Open 3
Stop 3
Close 3
Com 4
Open 4
Stop 4
Close 4Contactclosure inputs3 and 4 areonly availableon the WC-4M-GC
ler
SA
500-
9575
Rev
. B
®
ROLLER
l Motor120 V~
rectionel0 V~
al Support)
Class 2
COM
Open
Stop
Close
COM
Open4
Stop4
Close4
COM
Open3
Stop3
Close3
COM
Open2
Stop2
Close2
COM
Open1
Stop1
Close1
1010
Example of Master Control (with dedicated stop input)
In this wiring example, each master function is achievedby providing a closure to the open, stop, or close terminalof the input terminal block. Activating any closure willaffect all motors connected to this Group Controller.
12
34
5
ON
STATUS POWER
OPTIONS
ON
OPEN ALL
CLOSE ALL
OPEN 4
CLOSE 4
OPEN 3
CLOSE 3
OPEN 2
CLOSE 2
OPEN 1
CLOSE 1
WC-4M-GC Group Controller Shown
Class 2/PELV Wiring
Com
Open All
Stop All
Close All
Input controlschannel 1motor only(optional)
Input controlschannel 2motor only(optional)
Input controlschannels 3and 4 motorsonly(optional)*
Input simulta-neouslycontrols allfour channels
* Contact closure inputs 3 and 4 are only available on the WC-4M-GC
ler
SA
500-
9575
Rev
. B
®
ROLLER
l Motor120 V~
rectionel0 V~
al Support)
Class 2
COM
Open
Stop
Close
COM
Open4
Stop4
Close4
COM
Open3
Stop3
Close3
COM
Open2
Stop2
Close2
COM
Open1
Stop1
Close1
1111
Connecting Multiple Group Controllers
Multiple Group Controllers can be wired in parallel on theClass 2/PELV side to obtain simultaneous control ofmultiple shades. To do this, parallel wire the control wiresfrom the contact closure device to each Group Controller’scontact closure input terminal block. See the diagrambelow. This may be used for the individual inputs and/ormaster control input.
12
34
5
ON
STATUS POWER
OPTIONS
ON
OPEN ALL
CLOSE ALL
OPEN 4
CLOSE 4
OPEN 3
CLOSE 3
OPEN 2
CLOSE 2
OPEN 1
CLOSE 1
12
34
5
ON
STATUS POWER
OPTIONS
ON
OPEN ALL
CLOSE ALL
OPEN 4
CLOSE 4
OPEN 3
CLOSE 3
OPEN 2
CLOSE 2
OPEN 1
CLOSE 1
WC-4M-GC Group Controller Shown
Class 2/PELV Wiring
To Additional GroupControllers
WC-4M-GC Group Controller Shown
Input controls channels1 and 2 motors on thisunit only
Input simultaneouslycontrols all fourchannels on all unitsparallel wired together
Note: When connecting multiple Group Controllers inparallel, make sure the contact closure device is rated forthe total amount of current delivered by each GroupController (total current = 2 mA times the number of GroupControllers). Example, if you connect 4 Group Controllersin parallel, the contact closure switch would need to berated for at least 8 mA, at 30 Vdc.
ller
USA
500-
9575
Rev
. B
®
ROLLER
al Motort 120 V~
irectionel20 V~
cal Supports)
Class 2
COM
Open
Stop
Close
COM
Open4
Stop4
Close4
COM
Open3
Stop3
Close3
COM
Open2
Stop2
Close2
COM
Open1
Stop1
Close1
ller
USA
500-
9575
Rev
. B
®
ROLLER
al Motort 120 V~
irectionel20 V~
cal Supports)
Class 2
COM
Open
Stop
Close
COM
Open4
Stop4
Close4
COM
Open3
Stop3
Close3
COM
Open2
Stop2
Close2
COM
Open1
Stop1
Close1
1212
Setting the Contact Closure Input TypeWhen operating from contact closure inputs, the WC-2M-GC and WC-4M-GC can accept either momentary ormaintained contact closure inputs. See Appendix A onpage 13 for a more detailed description
Momentary Inputs: The unit will accept a momentaryclosure input of greater than 0.2 seconds to activate thedesired function, i.e. raise, lower, or stop. The powerrelays will open 2 minutes after either the open or closecontact closure is received, or when another contactclosure is received, whichever comes first. The relays willopen immediately upon receiving the stop contactclosure.
Maintained Inputs: The power relays remain closed aslong as the input closure remains closed. However, themost recent command received will be executed even ifthe previous contact closure is still maintained.
Momentary or maintained inputs are selected usingOptions switch #5. In the ON position, maintained modeis selected. In the OFF position, momentary operation isselected.
1 2 3 4 5
ON
1 2 3 4 5
ON
ON =Maintained Inputs
Options DIP Switch
Options DIP Switch
OFF =Momentary Inputs
13
Contact Closure Inputs:Maintained Mode OperationIn maintained mode, the Switched Live output for achannel, for instance SW Live 1A, is energized only whilethe contact closure is provided to the input for thatchannel. As soon as the contact closure is removed fromthe input, the Switched Live output is de-energized. Thisgives rise to possible conflicts if a contact closure isprovided during the time another contact closure isprovided. Below are descriptions of how the GroupController addresses these situations.
Inputs on a single channelWhen a contact closure is provided to a single input on anindividual channel, the Group Controller will energize theappropriate Switched Live output. If a contact closure isthen provided to another input on that same channel whilethe first contact closure is provided, the Group Controllerwill recognize this combination as a request to stop. Thiswill happen regardless of how much time elapses betweenthe application of the two contact closure inputs.
For example, if a contact closure is provided to Close 1,the Group Controller will energize the Switched Liveoutput to close the AC motor on Channel 1. If a contactclosure is provided to Open 1 while a contact closure isstill provided to Close 1, the Group Controller will de-energize the Switched Live output on Channel 1, stoppingthe AC motor.
If contact closures are provided to both the Open andClose inputs on a particular channel, the Group Controllerwill de-energize the Switched Live outputs for thatchannel. If one of the contact closures is then released,the Group Controller will NOT recognize that as a requestto move the AC motor to the position indicated by thecontact closure that is still provided. Instead, the GroupController will leave the Switched Live outputs de-energized. In order for the Group Controller to recognize anew input signal, the contact closure must be removedand then provided again.
Note: It is not recommended to connect two or morecontact closure devices on the same channel ifMomentary mode is selected. If this is done, it is possiblefor a channel to become unresponsive to inputs if contactclosures are provided by the two devices at the sametime.
For instance, if one device provides a contact closure tothe Open input, the Group Controller energizes theSwitched Live output that opens the AC motor. If thesecond device then provides a contact closure to theClose input, the Group Controller will then de-energize theSwitched Live output, stopping the AC motor. At this point,both contact closures must be removed before the GroupController will recognize a new request.
If it is desired to connect two or more contact closuredevices on the same channel, use Maintained mode.
Inputs on a single channel and Master ControlWhen a contact closure is provided to a single input on anindividual channel, the Group Controller will energize theappropriate Switched Live output. If a contact closure isthen provided to a Master Control input while the firstcontact closure is still provided, the Group Controller willenergize the Switched Live outputs requested by theMaster function on all channels of the Group Controller.
For example, if a contact closure is provided to Close 1,the Group Controller will energize the Switched Liveoutput to close the AC motor on Channel 1. If a contactclosure is then provided to the Master Open input while acontact closure is still provided to the Close 1 input, theGroup Controller will energize the Switched Live outputsto open the AC motor on all channels.
When a contact closure is provided to a Master Controlinput, the Group Controller will energize the appropriateSwitched Live outputs on all channels of the GroupController. If a contact closure is then provided to a singleinput on an individual channel while the Master Controlcontact closure is still provided, the Group Controller willactivate the Switched Live output requested by theindividual input, while keeping the Switched Live output inthe same state for the other three channels.
For example if a contact closure is provided to the MasterOpen input, the Group Controller will energize theSwitched Live outputs to open the AC motor on allchannels. If a contact closure is then provided to theClose 1 input, the Group Controller will energize theSwitched Live output on Channel 1 to close the AC motoron Channel 1, but continue energizing the Switched Liveoutputs on Channels 2, 3 and 4
Appendix A
14
AC motor does not move in eitherdirection when manual overridebuttons pressed.
• Motor wired to Group Controllerimproperly.
• Limit switches on motor not setproperly.
• Motor Supply Jumper terminal is notjumpered to 120 V terminal.
Verify motor wiring.
Verify limit switch settings on motor.
Place a jumper wire of sufficient wiregauge between Motor Supply Jumperand 120 V Input Voltage terminals.See page 6.
Troubleshooting
Motors cannot be controlled from low-voltage contact closure inputs butoperate properly with the manualOpen/Close buttons.
• Contact closure miswire. Verify connections on contact closureinputs.
Motors only move while low-voltagecontact closure is applied.
• Options Switch #5 in ON position. Change position of Options Switch #5to OFF. See page 11.
Motor moves in the wrong direction. • Options Switch not set properly. Reverse the corresponding OptionsSwitch. See page 7.
Symptom Possible Cause Solution
15
Notes
Lutron Electronics Co., Inc.7200 Suter RoadCoopersburg, PA 18036-1299 U.S.A.Made and printed in U.S.A. 12/02 P/N 031-216 Rev. A
Worldwide Technical and SalesAssistanceIf you have questions concerning the installation or operation ofthis product, call the Lutron Technical Support Center. Pleaseprovide exact model number when calling.
(800) 523-9466 (U.S.A., Canada, and the Caribbean)
Other countries call (610) 282-3800
Fax (610) 282-3090
Visit our web site at www.lutron.com
LIMITED WARRANTYLutron will, at its option, repair or replace any unit that is defective in materials or manufacturewithin one year after purchase. For warranty service, return unit to place of purchase or mail toLutron at 7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid. THIS WARRANTY IS IN LIEU OF ALL OTHER EXPRESS WARRANTIES, AND THE IMPLIEDWARRANTY OF MERCHANTABILITY IS LIMITED TO ONE YEAR FROM PURCHASE. THISWARRANTY DOES NOT COVER THE COST OF INSTALLATION, REMOVAL ORREINSTALLATION, OR DAMAGE RESULTING FROM MISUSE, ABUSE, OR IMPROPER ORINCORRECT REPAIR, OR DAMAGE FROM IMPROPER WIRING OR INSTALLATION. THISWARRANTY DOES NOT COVER INCIDENTAL OR CONSEQUENTIAL DAMAGES. LUTRON’SLIABILITY ON ANY CLAIM FOR DAMAGES ARISING OUT OF OR IN CONNECTION WITHTHE MANUFACTURE, SALE, INSTALLATION, DELIVERY, OR USE OF THE UNIT SHALLNEVER EXCEED THE PURCHASE PRICE OF THE UNIT.This warranty gives you specific legal rights, and you may also have other rights which vary fromstate to state. Some states do not allow limitations on how long an implied warranty lasts, so theabove limitation may not apply to you. Some states do not allow the exclusion or limitation ofincidental or consequential damages, so the above limitation or exclusion may not apply to you.
Lutron is a registered trademark and RadioTouch is a trademark of Lutron Electronics Co., Inc. ©2002 Lutron Electronics Co., Inc.