AC Drives MSc2016

download AC Drives MSc2016

of 21

Transcript of AC Drives MSc2016

  • 8/18/2019 AC Drives MSc2016

    1/21

    1

    Industrial AC Drives

    3. Selection and Applications

    2

    AC Drive selection

    Pumps

    Wind energy

    Multiple Centrifugal and energy management

    Others

  • 8/18/2019 AC Drives MSc2016

    2/21

    3. . Selection of AC Drive

    3

     

    The selection of ASD and MOTOR for any applicationrequires considerable experience to get the selection

    right.

    In design phase two main items are important

    SAFETY: System needed to safety margins when it is build

    COST: cost to be minimized ,by selecting the optimum size of

    MOTOR & CONVERTER for each application

    Design process start with

    Clear and accurate study for system requirements

    3. . Selection of AC Drive

    4

    i. The following checklist covers the factors to be considered:

    The nature of the application

    Maximum torque and power requirements and how they change with speed

    Starting torque requirements

    The speed range - minimum and maximum speed

    Acceleration & deceleration requirements (Is braking necessary?)

    Compatibility with the mains supply voltage

    Environmental conditions where the converter and motor will operate, ambient temperature,

    altitude, humidity, water, chemicals, dust, etc

    Ventilation and cooling for the converter and motor

    Direction (uni- or bi-directional)

    Accuracy of the speed control

    Dynamic response (speed and torque response requirements)

    Speed regulation requirements with changes in load, temperature and supply voltage

    The duty cycle, including the number of starts and stops per hour

    Overall power factor of the drive system and its effect on the mains supply

  • 8/18/2019 AC Drives MSc2016

    3/21

    3. . Selection of AC Drive

    5

    EMI and harmonics in the mains power supply and in the motor and motor cable

    Are EMI filters required?

    Earthing, shielding and surge protection requirements

    Torque pulsations in the rotor shaft

    Control method - manual, automatic, analog, digital, communications

    Control and communications interfaces required for the plant control system

    Indications required

    Reliability requirements, is a dedicated standby unit required

    Protection features, in-built and external features required

    Power and control cable requirements

    Parameter settings, local or remote programming

    Maintenance spares and repair considerations

    Cost of the alternative systems, taking into consideration the capital cost, performanceadvantages, energy savings, and efficiency or process improvements.

    Noise due to the harmonics in the motor

    Mechanical resonance at certain motor speeds

    3. . Selection of AC Drive

    6

    ii. The basic selection procedure

    Most problems result due to less experience

    incorrect selection and rating of AC Induction Motor

    incorrect selection and rating of AC Converter

    incorrect parameter settings installed in VSD control system

    The AC drive system is correctly selected and rated when: Motor specification is correct The correct type and size of electric motor has been selected, whose output

    torque, speed and accuracy are adequate for all load and environmentalconditions.

    AC converter specification is correct The correct type and size of AC converter has been selected, whose output

    (voltage, current, frequency) meets the motor requirements for all load and

    environmental conditions.

  • 8/18/2019 AC Drives MSc2016

    4/21

    3. . Selection of AC Drive

    7

    The correct procedure is:

    The first step is to select a correctly rated electric motor

    Only when this is completed, a suitable AC converter is chosen to

    match the requirements of the motor

    From the motor point of view, the main factors which need to

     be considered are

    1. the motor power rating (kW),

    2. the number of poles (speed) and

    3. the  frame size so that the load torque on the motor shaft

    remains within the continuous torque capability of the

    motor at all speeds within the speed range.

    3. . Selection of AC Drive

    8

    iii. load ability of converter fed squirrel cage motorsLoad ability: Is the continuous load torque capacity of a standard TEFC

    squirrel cage induction motor used with VVVF converters.

    • When selecting an AC motor for any drive application , the most important

    requirement is to ensure that the motor does not become overloaded or stall under

    all circumstances of speed and load.

    • For AC motors connected to the power supply direct-on-line (DOL) called fixed

    speed : It is usually sufficient to ensure that load torque is sufficiently below motor

    torque at the rated speed of the motor.

    • In the case of a variable speed drive. The load torque usually changes with speed, so

    it is essential to check that the motor torque exceeds the load torque at all

    speeds in the speed range. 

  • 8/18/2019 AC Drives MSc2016

    5/21

    3. . Selection of AC Drive

    9

    The AC VSD load ability curve:

    • Motors fed from VVVF converters can be loaded continuously at torques below the

    load ability limit line for the speed range.

    • Many AC converters have an over-current capacity of up to 150% for 60 sec to cover

    starting and transient operation.

    The speed range and load torque capacity (load ability) of a TEFC squirrel cage motor when controlled by a

    PWM-type VVVF converter

    solid line marks the maximum

    limits of continuous load torque

    3. . Selection of AC Drive

    10

    Load power capacity of a TEFC squirrel cage motor

    In the region below base speed, 

    known as the constant torque

    region, the power capability

    increases linearly from zero at zero

    speed to full power at the base

    speed.

    Above base speed, the power output

    capability cannot increase furtherand remains constant for further

    increases in speed with frequency

    and torque is reduced. This is

    known as the constant power

    region.

  • 8/18/2019 AC Drives MSc2016

    6/21

    3. . Selection of AC Drive

    11

    iv. The Nature of the Machine load

    For fixed speed drives:  the power requirement in kW at the rated speed.

    On larger drives: motor manufacturers usually ask for more information about the load

    1-the moment of inertia

    2- the acceleration requirements.

    3- more details about the load characteristics are always necessary.

    The output torque of an AC VSD is considered to be adequate when it:

    • Exceeds the breakaway torque of the machine load.

    • Can accelerate the load from standstill to its preset speed within the acceleration time

    required by the process.

    • Exceeds the load torque by an adequate margin during continuous operation at any speed inthe speed range and under all conditions.

    • Motor current does not exceed the thermal ratings of all electrical components and remains

     below the load ability curve during continuous operation.

    3. . Selection of AC Drive

    12

    iv. The Nature of the Machine load

    what needs to be known about the machine load can be

    covered by the following:

    1. The load torque, the type, magnitude and characteristics of the load

    torque connected to the output shaft of the motor

    2. The speed range, the minimum and maximum speed of the variable speed

    drive

    3. The inertia of the motor and mechanical load connected to shaft of the

    motor

  • 8/18/2019 AC Drives MSc2016

    7/21

    3. . Selection of AC Drive

    13

    The load torque

    The torque required by the driven machine determines the

    size of the motor because the continuous rated torque of the

    motor must always be larger than the torque required by the

    driven machine.

    The load torque determines the cost of the motor because

    the cost of an electric motor is Approximately proportional

    to its rated output torque (not its rated power!).

    3. . Selection of AC Drive

    14Torque characteristics of typical types of machine loads as a function o f speed, angle and time

  • 8/18/2019 AC Drives MSc2016

    8/21

    3. . Selection of AC Drive

    15

    The load torque

    Another important aspect of the load torque is that the figure

    should apply at the shaft of the motor. When gearboxes, conveyers or

    hoists are involved, the actual torque at the machine must be

    converted to torque at the motor shaft.

    The conversion formula to convert the load torque, speed and moment

    of inertia to motor shaft values depends on the transformation ratio.

    The load requirements are often given as the mechanical absorbed

    power (Pm kW) at a particular speed (n rpm).

     The mechanical load torque may then be calculated from the following

    formula:

    3. . Selection of AC Drive

    16

    The load torque

  • 8/18/2019 AC Drives MSc2016

    9/21

    Variable torque machine loads

    Machines with variable torque over

    their entire speed range, such as

    centrifugal pumps and fans.

    The following are some of the important factors associated with this type

    of load:

    The starting torque for normal centrifugal pumps and fans is very low and below the

    loadability curve of the AC motor for all speeds. Slurry pumps can some times be a

    problem, as they can have a high breakaway torque.

    The required starting current is low, so the overload capacity of converters is seldom

    required during acceleration.

    Running for long periods at low speeds is seldom a problem.

    However, running at speeds above the motor base speed could be a problem because

    the power requirement of this drive increases as the cube of the speed. This is

    incompatible with the capabilities of the constant power region

    3. . Selection of AC Drive

    17

    Constant torque machine loads

    Constant torque machine loads are those which

    exhibit a constant torque over their entire speed

    range, such as conveyors, positive displacement

    pumps.

    The following are the potential problems when driving constant torque

    loads from a converter fed electric motor:

    The starting torque is theoretically equal to the full speed load torque but, in practice, the real

    starting torque can be much higher due to the additional requirements of:

    Breakaway torque

    Acceleration torque (dynamic torque)

    Running for long periods at low speeds can result in motor thermal over-load, if the load

    torque is above the motor loadability curve.

     Separate forced cooling may be necessary in some cases.

    Running at speeds above the motor base speed could also be a problem, with increased motor

    slip and a higher possibili ty of stalling the motor.

    3. . Selection of AC Drive

    18

  • 8/18/2019 AC Drives MSc2016

    10/21

    3. . Selection of AC Drive

    19

    The speed range 

    The selection of the correct size of electric motor for a VSD is affected

     by the speed range within which it is expected to run continuously.

    The important factor is that the motor should be able to drive the load

    continuously at any speed within the speed range without stalling or

    overheating the motor

    Running the motor at below base speeds (f < 50 Hz ) with a standard TEFC

    cage motor has the following effects on the motor:

    Reduces the motor cooling because the cooling fan, which is

    attached to the motor shaft, runs at reduced speed. Therefore,

    the temperature rise in the motor will tend to be much higher

    than expected.

    3. . Selection of AC Drive

    20

    Figure shows an example of the torque – speed curve for a variable speed pump drive, operating in

    the range from 10 Hz to 50 Hz Some comments are:

    1. The load torque is well within the load ability limits at all speeds.

    2. The maximum speed is below the base speed of 50 Hz. The speed range should NOT be increased above

    50 Hz because the load torque will exceed the load ability limit of the drive. (Load torque increases as the

    square of the speed.)

    3. Starting torque is low, so there should be no problems with breakaway.

    4. The acceleration torque is high, so the drive can be expected to quickly reach its maximum speed, if fast

    acceleration is required. However, with pumps, a long acceleration time is normally desirable to prevent

    water hammer .

    Load curve

    Example of speed range and torque curve of a v ariable

    speed pump drive when controlled by a PWM-type

    VVVF converter

  • 8/18/2019 AC Drives MSc2016

    11/21

    3. . Selection of AC Drive

    21

    Running the motor at above base speeds (f > 50 Hz ) with a standard TEFC

    cage motor has the following effect on the motor The air-gap flux is reduced because the V/f ratio is reduced. Consequently, there is a

    reduction in the output torque capability of the motor. The torque is reduced in

    proportion to the frequency. The load torque is not permitted to exceed the pullout

    torque of the motor, even for a short period, otherwise the motor will stall.

    The maximum torque allowed at above-synchronous speeds depends on the motor

    characteristics and frequency as follows:

    3. . Selection of AC Drive

    22

    Some comments on the conveyer application are:

    1. The load torque falls outside the load ability limits at low speeds below 28 Hz there could be problems

    running the motor continuously at speeds below 28 Hz.

    2. Although the maximum speed is below the base speed of 50 Hz, but the speed range could be increased

    above 50 Hz to take advantage of the load ability characteristic above 50 Hz. (Load torque remains constant

    with increases in speed.)

    3. Starting torque is high, with a high breakaway, so there may be some problems with breakaway.

    4. Acceleration torque is small, so the drive ramp-up time may have to take place over a long period to avoid

    exceeding the VSD current limit.

    Torque-speed curve for a variable speed conveyor

    drive, operating in a range from 10 Hz to 50 Hz.

    Load curve

  • 8/18/2019 AC Drives MSc2016

    12/21

    3. . Selection of AC Drive

    23

    The Inertia of machine loads

    During acceleration and deceleration, the moment of inertia of the load imposes an

    additional dynamic acceleration torque on the motor.

    The moment of inertia and the required acceleration time together affect the motor

    torque and consequently the size and cost of the motor.

    The dynamic acceleration torque TA is calculated as follows:

    This can be rewritten as follows, with the speed in rev/min:

    3. . Selection of AC Drive

    24

    Example:

    A conveyer drive is to be accelerated from zero to a speed of 1500 rpm in 10 seconds.

    The moment of inertia of the load  J L  = 4.0 kgm2. The torque of the conveyer load,

    referred to the motor shaft, is a constant at 520 Nm. The motor being considered is a

    110 kW, 1480 rpm with J M  = 1.3 kgm2. Is this motor adequate for this duty?

    The moment of inertia of the drive system is

     J Tot = 4.0 + 1.3 = 5.3 kgm2 

    During acceleration, the dynamic torque required is

    T  A = 5.3 (2π/60)((1500-0)/10)=83.25 Nm

    The machine load is a constant torque type with a value given above asT L = 520 Nm

    During acceleration, the motor supply a total torque of

    T Tot = T L + T  A

    T Tot = 520 +83.25 = 603.25 Nm

  • 8/18/2019 AC Drives MSc2016

    13/21

    3. . Selection of AC Drive

    25

    The rated motor torque may be obtained from the manufacturer’s tables or calculated

    from the rated power as follows:T N  = (9550*110/1480)= 709.8 Nm

    Because T N ≥T Tot , the motor is evidently suited for the drive requirements.

    When the motor drives the mechanical load through a gearbox or pulleys, the inertia of

    the load must be ‘referred’ to the motor shaft using the formula given below:

     J M  = J L ( )

    ( )  kgm2

    Where  J M = Inertia of the motor shaft

     J L = Inertia of the load shaft

    3. . Selection of AC Drive

    26

    The selection procedure may now be summarized as follows:STEP 1: Specify the initial data for the drive application

    To select the correct motor/converter combination, the following information must be available:

    Voltage and frequency of the power supply

    The breakdown or starting torque

    The load torque and its dependence on speed

    Speed range of the variable speed drive

    Acceleration requirements or ‘ramp times’

    The moment of inertia of the motor and load

    STEP 2: Specify the number of poles of the motor

    The number of poles determines the synchronous speed of the motor and its usually selected

    according to the maximum speed required by the application. Modern VVVF converter are

    available with output frequencies of up to 400 Hz.

    Above-synchronous speeds are of particular advantage for constant torque loads, where the

    maximum speed should ideally, be in the range of 50-100 Hz.

  • 8/18/2019 AC Drives MSc2016

    14/21

    3. . Selection of AC Drive

    27

    STEP 3: Select the motor power rating

    Using the load torque requirements, the power rating of the motor can be selected from a motormanufacturer’s catalogue using the formula

    STEP 4: Select a suitable frequency converter

    A converter with a rating suitable for the motor selected should then be selected from the

    manufacturer’s catalogue. Converters are usually manufactured for power ratings that match the

    standard sizes of squirrel cage motors. Catalogues usually give the current rating as well as a check

    to ensure that the motor current is below that of the converter.

    The following factors must be considered:

    Supply voltage and frequency

    Rated current of the motor Duty type (variable torque or constant torque)

    A converter is selected as that the rated current of the converter is higher than the rated current of

    the motor. Also, the type of converter should be suitable for the duty required. Some

    manufacturers have different converters for the two duty types.

    3. . Selection of AC Drive

    28

    STEP 5: Final Checks

    The following final checks should be made:

    Is the continuous power rating of the motor (de-rated fro altitude, temperature,

    harmonics, etc) greater than the continuous power requirements of the load?

    Is the starting torque capability of the variable speed drive high enough to exceed the

     breakaway torque of the load?

    If the VSD is operating in the over-synchronous speed area, is the motor torque

    capability at maximum speed adequate for the load torque?

    Is the speed accuracy adequate for the application?

  • 8/18/2019 AC Drives MSc2016

    15/21

    3. . Selection of AC Drive

    29

    Example Conveyer Application

    Problem description

    A variable speed drive application has been proposed for a conveyer designed to

    transport a package of product from arriving point (initial distribution point ) to another

    point .The required speed range is 600 rpm to 1400 rpm . The calculated power

    requirement of the load, reduced to the motor shaft , is 66 kw at 1400 rpm The

     breakaway torque is expected to be 110% of rated torque. The supply voltage is 415

    volts, 50 Hz. Select the optimum size and rating of squirrel cage motor and converter

    for the most cost effective solution

    3. . Selection of AC Drive

    30

    According to the system description

    1- Motor torque required calculation :

    The load is a typical constant torque load type. From the pervious equations, the

    constant load torque requirement across the speed range is

    MOTOR selected must be with Toque TM > TB

  • 8/18/2019 AC Drives MSc2016

    16/21

    3. . Selection of AC Drive

    31

    1- Selecting number of poles:

    According to speed range the number of poles selected that determine base speed, so

    two options available from catalogs :

    4 – Pole Motor

    Speed Range 1480 rpm

    110 kw,415 V,188 A

    Frame Size 280MRated Torque = 710 Nm

    Needed =495 Nm

    6 – Pole Motor

    Speed Range 985 rpm

    75 kw,415 V,135 A

    Frame Size 280M

    Rated Torque = 727 Nm

    Needed =495 Nm

    3. . Selection of AC Drive

    32

    Which is the Motor from the two available is the best choice?

    Two motors are adequate but the converter choice will give some other clear

    view For choice

    Motor current is less than choice one, so the converter current required

    is less in this case, and the initial cost is low.

    Converter suitable for this motor:

    110 Kw,415 V,220 A

    Converter suitable for this motor:

    75 Kw,415 V,140 A

    This is the best choice because:

  • 8/18/2019 AC Drives MSc2016

    17/21

    3.2. Application of ASD in pumps

    33

    3.2. Application of ASD in pumps

    34

    Power electrical = I ×Vx pfWhere: Power electrical = [W], V = voltage [V], I = Current [A]  

    Power mechanical=2 π* T* N/60Where: N = Speed [rpm], T = Torque [Nm],

    Power fluid = g Q H ρwaterWhere: Power fluid = [W], g = 9.81 m/s2 , Q = Flow quantity [m3 /s], 

    H=Pressure head [m], ρwater  = density of water

  • 8/18/2019 AC Drives MSc2016

    18/21

    3.2. Application of ASD in pumps

    35

    If you have a system using a motor that serves a varying load,

    an Adjustable Speed Drive (ASD) may benefit you. Examplesof such systems are fans that reduce flow for non-designconditions or pumps that use control valves to vary flow.ASDs tailor motor performance to match present conditions.

    Advantages include: Energy savings Improved process flow Softer/easier motor starting Faster response than valves or dampers

    3.2. Application of ASD in pumps

    36

    Throttling verses Speed change for pump system

    H-Q curves

  • 8/18/2019 AC Drives MSc2016

    19/21

    3.2. Application of ASD in pumps

    37

    Throttling verses Speed change for pump system

    H-Q curves

    Operating

    point

    Reduced speedoperating point

    flow

    head

    Throttled Operating

    Point

    q

    H

    q2

    Hs

    H2

    3

    2

    2

    1

    2

    2

    1

    2

    2

    1

    Q2

    Q

     

      

     

     

      

     

     N 

     N 

     P 

     P 

     N 

     N 

     H 

     H 

     N 

     N 

    P

    P2

    Ps

    3.2. Application of ASD in pumps

    38

    The following table shows the theoretical power required as

    the motor speed & system flow decrease

    P1/P2= (n1/n2)3

    Power RequiredFlowSpeed

    100%100%100%

    72.9%90%90%

    51.2%80%80%

    34.3%70%70%21.6%60%60%

    12.5%50%50%

    6.4%40%40%

    2.7%30%30%

  • 8/18/2019 AC Drives MSc2016

    20/21

    3.2. Application of ASD in pumps

    39

    The table shows that reducing motor speed results in a

    reduction in the power required. Significant energy savingsare the result. For example, to reduce the flow from 100percent to 50 percent cuts the required power to 12.5percent. Eight times less power is used (8 = 100%power/12.5% power).

    The power required drops exponentially when motor speedis reduced, providing you with substantial energy savings.

    ASD energy savings are estimated using computer analysis.

    The overall ASD energy savings is calculated as thetheoretical energy savings minus the losses due to runningthe ASD and the drop in motor efficiency at lower speeds.

    3.2. Application of ASD in pumps

    40

    Example:

    The following example show the energy saving when operate apump (rated flow=0.25m3/sec, at speed 1500 rpm) withconstant speed to fill a canal with dimension (500 m length,5m width, 3m height).

    The volume of water required = 5 x 3 x 500=7500 m3

    The number of hours required =7500/(.25 x 60 x 60)=8.33 hr

    Assume the input power to the pump = P kW

    The energy consumes 8.33P kWh

  • 8/18/2019 AC Drives MSc2016

    21/21

    3.2. Application of ASD in pumps

    41

    If operate the pump with VSD to fill the same volume

    Operate 2 hours at rated speedq=0.25m3/sec, V1=0.25 x 2 x 60 x 60=1800 m

    3

    Operate 4 hours at 0.75 x 0.25 m3/sec, V2=2700 m3

    V3=7500-2700-1800=3000 m3

    Operate at 0.5 x 0.25 m3/sec, it’s operating for 6.67 hr

    From affinity laws P proportional to cubic speed

    P (at 0.25)=P kW, P (at 0.75 x .25)=0.42P kW, P (0.5 x .25)=0.125PkW

    Energy required 2 x P+4 x 0.42 x P+0.125 x 6.67 x P=4.5P kW

    Percentage of energy saving = 8.33P-4.5P/8.33P=45.8%