ABBREVATIONS LIST
Transcript of ABBREVATIONS LIST
INDEX OF DRAWINGS
E1.G.01
SYMBOLS, INDEX AND ABBREVIATIONS LIST
ES1.1
OVERALL SITE LIGHTING PLAN
E1.G.11
6-BAY GARAGE BUILDING WITH STORAGE
ELECTRICAL CODE SUMMARY
ELECTRICAL SYSTEMS - EACH BUILDING WILL BE SERVED BY A MULT-METER CENTER. EACH
UNIT WITHIN THE BUILDING WILL HAVE ITS OWN ELECTRIC METER. THERE WILL ALSO BE A
"HOUSE", OR GENERAL, METER FOR OTHER LOADS. WIRE AND CONDUIT SIZE TO EACH METER
CENTER IS SHOWN ON DRAWINGS. TYPICALLY, EACH UNIT WILL BE SERVED WITH A 125A
PANEL. EACH UNIT PANEL SCHEDULE, WHICH IS INCLUDED IN DRAWING SET, INDICATES ALL
BRANCH CIRCUITS WITHIN THE UNIT AND HAS ITS LOAD CALCULATED IN ACCORDANCE WITH
NEC ARTICLE 220. THE "HOUSE", OR GENERAL, METER AND PANELBOARD SCHEDULES ARE
ALSO INDICATED.
EACH APARTMENT BUILDING WILL BE PROTECTED BY NFPA 13R SPRINKLER SYSTEM. THIS
SUPPRESSION SYSTEM WILL BE MONITORED BY AN ADDRESSABLE FIRE ALARM SYSTEM. IN
ADDITION, EACH TENANT UNIT WILL BE EQUIPPED BY AN NFPA 72 COMPLIANT RESIDENTIAL
UNIT SMOKE DETECTOR/SOUNDER BASE IN AND ADJACENT TO EACH SLEEPING UNIT. ADA
COMPLIANT ACCESSIBLE UNITS WILL BE PROVIDED WITH AUDIBLE AND VISUAL ANNUNCIATION
IN ACCORDANCE WITH NFPA 72 AND ANSI A117.1 GUIDELINES. EACH BUILDING FIRE ALARM
SYSTEM WILL REPORT TO A CENTRALIZED FIRE ALARM PANEL PROVIDED WITH OFF-SITE
MONITORING AND EQUIPPED WITH AN NFPA 72 DIALER UNIT.
NEAR CIRCULATOR (REFER TO HVAC &
PROJECT ELECTRICAL CONTRACTOR
PHOTOCELL, # INDICATES PHOTOCELL
TEMPERATURE CONTROL CONTRACTOR
MAIN SWITCHBOARD
MANUAL SWITCH WITH PILOT LIGHT
DRWGS FOR EXACT LOCATION.)
PLUMBING CONTRACTOR
PUSH BUTTON STATION
PRE-WIRED CONTROL PANEL
PUSH BUTTON WITH PILOT LIGHT
PART WINGING STARTER
SOLENOID AIR VALVE
REDUCED VOLTAGE STARTER
REVERSE ACTING THERMOSTAT
POWER ROOF VENTILATOR
PNEUMATIC ELECTRIC SWITCH
SUPERVISORY SWITCH
START-STOP WITH PILOT LIGHT
UNDERGROUND DUCT
UNDERFLOOR DUCT
LIGHT DESIGNATION
TRACKLIGHT, # INDICATES TRACK
TEMPERATURE CONTROL PANEL
STERILIZER CONTROLS
VENDOR SUPPLYING EQUIPMENT
UNLESS OTHERWISE INDICATED
DRWGS FOR EXACT LOCATION.)
SELECTOR SWITCHSPS
EWH ELECTRIC WALL HEATER
MULTI-RECEPTACLE DESIGNATION
MULTI-RECEPTACLE, # INDICATES
LINE VOLTAGE THERMOSTAT (120V)
LOAD (KW OR HP)
KILOVOLT-AMPERES
MOTOR GENERATOR
MOTORIZED DAMPER
MAIN CIRCUIT BREAKER
PROJECT GENERAL CONTRACTOR
GROUND FAULT INTERRUPTER TYPE
HAND-OFF-AUTO SELECTOR SWITCH
HEATING/VENTILATING CONTRACTOR
MAGNETIC STARTER
IN STARTER COVER
KVA
KW
MCB
MG
MFR
MD
LD
LVT
MR#
MLO
KILOWATT
MANUFACTURER
MAIN LUGS ONLY
G, GFI
GC
FZS
FS
EX
GND, GRND
H, HV
HP
HOA
GV
GS
KS
IS
IL
IU
I
F
GATE VALVE
IN UNIT
KEY SWITCH
INTERLOCK
INSTALLED BY
HORSEPOWER
GROUND
FREEZESTAT
EXISTING
FURNISHED BY
FLOW SWITCH
UO
V
W/
WP
USS
XFMR
WT
UOI
W
UNIQUE OUTLET
WITH
WIRED BY
UNIT SUBSTATION
WIRING TROUGH
WEATHERPROOF
TRANSFORMER
SS
SVS
SWGR
SWBD
TC
STAT
SSP
TL#
TS
TO
TCP
TCC
UG
UGD
UH
UFD
TV
UNIT HEATER
TELEVISION
UNDERGROUND
TYPICAL OUTLET
TAMPER SWITCH
THERMOSTAT
TIME CLOCK
SWITCHGEAR
SWITCHBOARD
SPEED SWITCH
MSBACT ABOVE COUNTER TOP
ABOVE FINISHED GRADE
ABOVE FINISHED FLOOR
BY ELECTRICAL CONTRACTOR
EXPLOSION PROOF
ELECTRIC DUCT HEATER
ELECTRIC UNIT HEATER
COMBINATION CIRCUIT BREAKER
CONTROL POWER TRANSFORMER
FULL VOLTAGE STARTER
VOLTAGE STARTER
CEILING EXHAUST FAN
DISCONNECT SWITCH
DOOR MANUFACTURER
CABINET UNIT HEATER
COMBINATION STARTER
COMBINATION FUSIBLE FULL
DUCT DESIGNATION
BUILT-IN OVERLOAD
BELOW FINISHED GRADE
BUS DUCT, # INDICATES BUS
CIRCUIT BRACKER(S)
BOILER CONTROL PANEL
CEF
CF
CPT
CU
CS
CUH
CKT
DRWGS
DN
EDH
DM
D, DS
E, EC, X
ET
EUH
EM
EP
EF
DOWN
DRAWINGS
EMERGENCY
ELAPSED TIMER
EXHAUST FAN
COPPER
CIRCUIT
AFF
AQ
AU
B,JB
AS
ALT
AFG
BOL
BFG
BD#
CCB
CDT
CB, C/B
BCP
C CONTACTOR
CONDUIT
AQUASTAT
AS SHOWN
AT UNIT
ALTERNATE
JUNCTION BOX
PC
PCP
PRV
PEC
PW
R
PL
SC
SAV
RVS
RAT
RAI
RAF
PE
SPR
SPC
SP
SF
SSTERILIZER
SUPPLY FAN
SPACE
SPARE
SHOCK-PROOF
PILOT LIGHT
RECEPTACLE
REMAIN AS IS
RETURN AIR FAN
MSP
NC
NIC
NP
MTD
MT
OOS
NU
OU
NTS
PBL
PBS
P#
NOT TO SCALE
ON UNIT
ON-OFF SWITCH
DESIGNATION
MOUNTED
EMPTY
NOT IN CONTRACT
ABBREVATIONS LIST
A AMP MS MANUAL STARTER
CONDUIT, CAPPED
SD
FIRE ALARM - SMOKE DUCT DETECTOR
(#/#)
CIM
FIRE ALARM - CONTROL INTERFACE MODULE
FIRE ALARM - MONITOR INTERFACE MODULE
MIM
DH
TS
FS
T
S
TELEVISION OUTLET, (COAX)
TELEPHONE/DATA OUTLET, (TWO CAT 5)
SD
CEILING AS SHOWN (COMBO SMOKE/CO DETECTOR WHERE NOTE)
SMOKE DETECTOR - SELF CONTAINED, SURFACE MOUNTED ON WALL OR
FIRE ALARM - VISUAL ONLY SIGNAL
FIRE ALARM - AUDIO/VISUAL SIGNAL
FIRE ALARM - AUDIO ONLY SIGNAL
FIRE ALARM - SMOKE DETECTOR
FIRE ALARM - THERMAL DETECTOR
FIRE ALARM - WATER FLOW SWITCH
FIRE ALARM - VALVE TAMPER SWITCH
FIRE ALARM - DOOR HOLDER
SUBSCRIPTS:
FIRE ALARM - MANUAL PULL STATION
FA
ANN
FA
CP
FIRE ALARM CONTROL PANEL - SURFACE OR RECESSED AS SHOWN
#
MDP
AS SHOWN, # INDICATES ALPHA-NUMERIC PANEL DESIGNATION
PP
#
POWER PANEL - MOUNTED ON/IN WALL, SURFACE OR RECESSED
AS SHOWN, # INDICATES ALPHA-NUMERIC PANEL DESIGNATION
# INDICATES PANELBOARD DESIGNATION
PANELBOARD, SURFACE OR RECESSED MOUNTED, AS SHOWN.
PROTECTIVE DEVICE - DISCONNECT SWITCH
MOTOR
(PP) TELE-POWER POLE IN CEILING
(C) COMMUNICATIONS, (AL) AISLE LIGHT,
(S) SURFACE MOUNTED, (F) FLUSH MOUNTED,SUBSCRIPTS:
JUNCTION BOX, TWO-GANG
SPECIAL PURPOSE OUTLET - SEE SCHEDULE
CONVIENCE OUTLET - DUPLEX RECEPTACLE, MOUNTED 6" ABOVE
SUBSCRIPTS:
GROUND, (TSS) TRANSIENT SURGE SUPPRESSOR
FURNISHED BY OTHERS, (H) MOUNTED HORIZONTALLY,
TOE SPACE, (EP) EXPLOSION PROOF, (IG) ISOLATED
CONVIENCE OUTLET - DUPLEX RECEPTACLE, WALL MOUNTED 15" AFF
SWITCHED CIRCUIT
UNSWITCHED CIRCUIT
P PHOTOCELL
C CONTACTOR
TCTIME CLOCK
OCCUPANCY SENSOR - MOUNTED IN CEILING
SUBSCRIPTS:
LOCAL SWITCH, SINGLE POLE
(WP) WEATHERPROOF, (K) KEY OPERATED,
(3) THREE-WAY, (4) FOUR-WAY, (PL) PILOT LIGHT,
(I) INNER LAMP(S) SWITCHED, (OS) OCCUPANCY SENSOR
(MS) DUAL TECH OCC SENSOR, WATTSTOPPER #DW100
LT
#
EMERGENCY BATTERY UNIT
LIGHT FIXTURE - BRACKET-ARM, MOUNTED ON POLE
LIGHT FIXTURE - POST-TOP, MOUNTED ON POLE
ARROWS AS SHOWN
EXIT SIGN -
WALL MOUNTED, SINGLE FACED WITH DIRECTIONAL
ARROWS AS SHOWN
EXIT SIGN -
WALL MOUNTED, DOUBLE FACED WITH DIRECTIONAL
ARROWS AS SHOWN
EXIT SIGN -
CEILING MOUNTED, SINGLE FACED WITH DIRECTIONAL
ARROWS AS SHOWN
EXIT SIGN -
CEILING MOUNTED, DOUBLE FACED WITH DIRECTIONAL
SHADED FIXTURES INDICATE EMERGENCY OR 24 HOUR LIGHTING
LIGHT FIXTURE - WALL WASHER - RECESSED IN CEILING
LIGHT FIXTURE - RECESSED IN CEILING
LIGHT FIXTURE - RECESSED IN WALL
LIGHT FIXTURE - SURFACE MOUNTED ON WALL
LIGHT FIXTURE - SURFACE MOUNTED ON CEILING
LIGHT FIXTURE - FLUORESCENT, MOUNTED UNDER CABINET
LIGHT FIXTURE - FLUORESCENT, SURFACE MOUNTED ON WALL
RECESSED AS SPECIFIED IN LIGHTING FIXTURE SCHEDULE
LIGHT FIXTURE - FLUORESCENT, MOUNTED ON/IN CEILING, SURFACE OR
SYMBOLS LIST
COUNTER
GARAGE DOOR SENSOR - WIRE TO OPENER
GARAGE DOOR SENSOR - WIRE TO OPENER
CEILING MOUNTED PADDLE FAN
FLUSH MOUNTED FLOOR BOX WITH POWER, DATA AND COAX
FLUSH MOUNTED FLOOR BOX WITH POWER AND DATA
SUBSCRIPTS:*
CEILING SPEAKER - ROUGH IN
SWITCH DESIGNATION
SUBSCRIPTS: SPEAKER DESIGNATIONV,*
SPEAKER VOLUME CONTROL - ROUGH IN
ELECTRIC STRIKE - ROUGH IN
ES
DOOR CONTACT - ROUGH IN
DC
KEYPAD - ROUGH IN
KP
SECURITY CAMERA - ROUGH IN TV
SECURITY MOTION SENSOR - ROUGH IN
REMOTE EMERGENCY HEAD
BATTERY PACK FOR REMOTE EM. HEAD
OR EQUIVALENT
CO
ON WALL OR CEILING AS SHOWN
CARBON MONOXIDE DETECTOR - SELF CONTAINED, SURFACE MOUNTED
DAYLIGHT SENSOR - MOUNTED IN CEILING
CONTINENTAL 422 FUND LLCW134 N8675 EXECUTIVE PARKWAYMENOMONEE FALLS, WI 53051
262.502.5500 * FAX 262.502.5522
LPA #8374
Consulting Electrical Engineers/Planners
Ph. (262) 860-1544, Fax (262) 860-1566
Elm Grove, Wisconsin 53122
12970 W. Bluemound Road - Suite 101
E1.G.02
ELECTRICAL SPECIFICATIONS
Reviewed for CodeCompliance
PRBD20180209312
ReviewedCCEPR-dae.
16.00 ELECTRICAL SPECIFICATION INDEX:
16.10 Basic Requirements16.12 Wires and Cables16.13 Raceways16.14 Wiring Devices16.30 Electrical Service and Distribution16.46 Grounding16.47 Panelboards16.48 Motors and Special Outlets16.51 Interior Lighting16.52 Site Lighting16.70 Fire Alarm System16.76 Telephone System16.79 Television Cable and/or Satellite System16.80 Security System
16.10 BASIC REQUIREMENTS:A. General:
1. Design and build the electrical facilities for the Continental Properties, Springsat Hammock Cove apartment campus, Naples, Florida as outlined in thesespecifications and associated electrical design parameter schedules.
2. The electrical material counts specified in the electrical design parameterschedule establishes the minimum acceptable design. Increases in this designmay be necessary based on conditions that develop in the design phases.The electrical contractor is responsible for all costs involved in changesrequired from this specification.
3. Provide all materials, equipment, apparatus, electrical systems and incidentalsas necessary and/or herein specified for a complete installation.
4. The electrical work shall also include installation of equipment furnished byothers and equipment furnished and installed by others which shall be wiredand connected by the Electrical Contractor.
B. Work Included:1. Visit site and verify conditions.2. Temporary power service to be used for heating, lighting and power during
construction.3. Electric service from local Electrical Utility Company.4. Panelboards, and metering equipment as shown on drawings.5. Grounding system and bonding. Service metering board(s) shall be separately
grounded to cold water main and to supplementary grounding electrodes. Sizeground conductors as required by NEC 250.
6. Distribution systems for tenant loads.7. Equipment disconnect switches fused and non-fused in strict compliance with
code.8. Power wiring and controls for electrical heating equipment.9. Power and control wiring for kitchen equipment and electric controls for water
heaters.10. Power wiring for appliances, laundry equipment and vending machines.11. Outlets, receptacles, special power outlets and power wiring.12. Power wiring for ventilation, duct heaters, VAV boxes, boilers, air conditioning,
plumbing and fire protection equipment.13. Power wiring and interlocking with the fire alarm system for electrically operated
dampers where required.14. Indoor lighting, lamps, mounting accessories and controls.15. Outdoor lighting, lamps, mounting accessories, pole bases and controls.16. Exit and emergency lighting system, complete with associated conduit and
wiring.17. Provide battery unit with lamps where shown.18. Addressable fire alarm system in conformance with the applicable Codes.19. Residential smoke detectors.20. Telephone/data system.21. T.V. and cable system.22. Gate Access and Door security system.23. All permits, testing and inspection fees.24. One year guarantee on labor and materials.
C. Specified Elsewhere:1. The following will be provided under other Sections of the Specifications:
a. Motors for mechanical equipment.b. Controllers that are part of mechanical equipment.c. Temperature control wiring for the HVAC systems.d. Telephone/data instruments and terminals (not in Contract).e. Kitchen equipment.f. Appliances.
D. References:1. The electrical work shall be in accordance with the 2017 Florida Building
Codes, based upon 2015 IBC, 2015 IRC, 2015 IFC, 2015 IECC Energy Code,2014 NEC, with all applicable local, state and federal codes, and localinspection authority, Americans with Disabilities Act (ADA) and rules andregulations of the local power utility.
2. Applicable standards published by NEMA, IEEE, ANSI and NFPA shall befollowed.
3. Underwriters Laboratories (UL) label is required on equipment where suchstandards have been established.
4. Permits, Licenses and Inspection Fees: The PEC shall prepare and submitapplications and submittals required, obtain necessary permits and certificatesof compliance and approvals required, and shall deliver these to the A/Epaying all necessary fees.
5. All materials and equipment shall be new and in perfect condition wheninstalled and shall be of the best grade and of the same manufacturerthroughout for each class or group of equipment. Materials shall meet withapproval of the Division of Industrial Safety and all governing bodies havingjurisdiction. Materials shall be manufactured in accordance with applicablestandards established by ANSI, NEMA, and NBFU.
E. Performance Requirements:1. General:
a. Work shall be done by skilled persons qualified and competent to performthe best grade of workmanship.
b. The electrical contractor shall carefully check the heating and ventilating,plumbing and architectural drawings and the existing conditions todetermine exact location and manner of installing electrical outlets andconnections.
c. The electrical contractor shall cooperate with the other contractors inrunning of conduit and installation of boxes, etc.
d. Contractor shall perform all verification, observations, test, and examinationof work prior to the ordering of the electrical equipment and actualconstruction. Contractor shall issue a written notice of all findings to theContracting Officer listing all malfunctions, faulty equipment anddiscrepancies.
e. Patch, repair, and paint any area that has been damaged in the course ofthe electrical work.
f. Penetrations in fire rated walls shall be sealed in accordance with
applicable codes.
2. Equipment Identification:a. Materials and electrical equipment installed under this contract shall be
clearly and permanently identified.b. Engraved plastic nameplates shall be securely attached to all panelboards,
disconnect switches and motor starters.c. Identify each new conductor at each panel, pull box and at each outlet with
permanently attached adhesive markers.
3. Equipment Grounding:a. Metal boxes, cabinets, switch enclosures; motor frames and other metallic
enclosures shall be bonded with green color coded equipment groundwires.
b. The ground wires shall be run in the same raceway with the feeder orbranch circuit wires.
c. Provide separate equipment grounding conductor within all raceway sizedper NEC for all lighting and receptacle branch circuit conduits.
d. Terminate ground wires at the panelboard ground bus.
F. Assurance Submittals:1. Shop Drawings:
a. Submit shop drawings, product data and manufacturer's instructions for thefollowing:
1) Lighting Fixtures.2) Panelboards.3) Wiring Devices.4) Service Metering and Distribution Equipment.5) Fire Alarm System.
2. Load Calculations:a. Electrical load calculation including panel schedule, panel load, feeder
sizes, voltage drop and main distribution panel sizing shall be provided withfinal design review. Also, short circuit calculations and coordination ofcircuit protection devices shall be provided to meet NEC requirements.
G. Quality Assurance:1. After completion, all electrical systems shall be tested and demonstrated to
show satisfactory compliance with the specified performance criteria andinstallation requirements. A written record of the results of performance testsmade on special systems and equipment shall be furnished to the Owner.Special systems shall include fire alarm and smoke detection systems, all otheralarm systems and lighting systems.
2. Make such changes as directed to make installation comply with thespecifications.
3. Repair or replace all faulty work or equipment.4. Provide the Owner with a written certificate that all parts of the electrical
system have been inspected and final approval has been obtained from theappropriate authority.
5. Submit data and certificates of final inspection and approval as issued by localinspection authority or affidavit attesting to compliance with applicable codes.
6. Provide the Owner with reproducible set of “As-Built” Record Drawingsdepicting electrical construction at job completion. Drawings shall bedimensioned showing equipment locations, ratings and circuits.
7. Complete job shall be guaranteed for a period of one year after date of jobacceptance by Owner. Any work, material or equipment found to be faultyduring that period shall be corrected at once upon written notification, at theexpense of the contractor.
16.12 WIRES AND CABLES:
A. General: All building wires and cables and associated splices, connectors andterminations for the wiring system shall be rated for 600 volts.
B. Feeders:1. Type THWN copper or aluminum conductors with ground in raceway.2. Type SE or USE cable, copper or aluminum conductor, 75C insulation
minimum where allowed by local codes and Authority Having Jurisdiction (AHJ).
C. Branch Circuits:1. Type THHN/THWN, copper conductor in raceway.2. Type MC, AC or NM cable, copper conductor, 75C insulation minimum where
allowed by local codes and Authority Having Jurisdiction (AHJ).
16.13 RACEWAY:A. General: Raceways shall be installed as a complete system continuous from
service to outlet or equipment, mechanically and electrically connected, constitutinga continuous ground system.
B. Conduit Installation Schedule:1. Electric metallic tubing, dry interior locations only.2. Rigid Steel Conduit:
a. Exposed outdoor locations.b. Wet interior locations.c. Floor slab or foundation wall penetrations, within 5-feet from foundation
wall.
3. Schedule 40 PVC Conduit:a. Under concrete slab on grade.b. Underground more than 5-feet from foundation wall, wet locations.
C. Raceway shall generally be concealed whenever possible. Surface raceways shallbe employed in unfinished areas and where impossible to conceal and wheredirected by the A/E.
D. Flexible metal conduit as approved and required by Code. Employ liquidtightflexible metal or nonmetallic conduit with ground wire for final connections tomotors, vibrating equipment, etc. Employ “greenfield” flexible metal conduit for finalconnection to recessed lighting fixtures, etc.
E. All rigid steel conduit and IMC fittings shall be threaded type.
F. All connectors shall have insulated throats. Connectors for use with flexible metalconduit shall be threaded type.
G. Indentation type, set-screw type and push-on type fittings are not acceptable for
rigid steel, EMT or flexible metal conduits. Fittings with die-cast bodies, wholly orpartially, are not acceptable.
16.14 WIRING DEVICES:A. General:
1. Convenience receptacles shall be commercial grade 15- or 20-amperegrounding type similar to Hubbell Nos. BR15 or BR20. Switches used shall becommercial grade 15- and 20-ampere quiet type, rated for use on 120 voltsystems similar to Hubbell No. CSB120 (CSB15), CSB320 (CSB315) andCSB420 (CSB415). All devices shall be commercial specification grade.
2. GFCI receptacles shall be 15- or 20-ampere specification grade with lockoutcapability upon GFCI failure.
3. Exterior receptacles shall be marked “WEATHER RESISTANT” per NEC.4. Receptacles utilized in dwelling units, and elsewhere required by Code shall bemarked “TAMPER RESISTANT” per NEC.
5. Flush mount wiring devices under a smooth nylon device plate with a whitefinish.
B. Outlet Requirements:1. Provide minimum number of 15- and 20-ampere, 120 volt receptacle required
by NEC 210.2. Provide GFI type receptacles when located within 6'-0” of sinks and basins and
where required elsewhere by NEC.3. Provide convenience receptacles for housekeeping in corridors and other
common areas at a maximum of 50 feet on center.
16.30 ELECTRICAL SERVICE AND DISTRIBUTION:A. General:
1. Provide single phase, 120/240V electrical service with local utility approvedmetering gear at each separately metered building or structure as shown ondrawings.
2. Ratings of switchgear and switchboard assemblies shall ensure that maximumavailable short-circuit currents are safely interrupted.
B. Provide temporary electric power and lighting during the construction period asnecessary to meet OSHA requirements.
16.46 GROUNDING:A. Systems grounding conductors from neutral bus in main service equipment to water
service in accordance with Code requirements -- terminate grounding conductorson service side of water meter using O.Z./Gedney Type CG connector orequivalent. Extend copper grounding electrode conductor(s) from serviceequipment to supplemental driven electrodes and water service entrance as well asother grounding electrodes required by NEC 250.
B. In accordance with Code, provide supplementary service ground as follows:
1. Provide ground grid consisting of at least (3) 8'-0" by 5/8" copper-claddriven ground rods, 10'-0" on centers and minimum 6'-0" from building. Thedriven rods may form a triangular pattern.
2. Ground resistance shall be 25 ohms or less. Provide additional rods orelectrodes as required to obtain proper resistance to ground.
C. All grounding connections must be approved for the purpose, as manufactured byO.Z./Gedney or equivalent.
D. Metallic raceway system shall be grounded as required by Code, so that groundwill be electrically continuous from the service entrance conduit to all outlet boxes.
E. Motors shall be grounded with a separate green ground conductor routed viaflexible metal conduit.
16.47 PANELBOARDS:A. Distribution Equipment:
1. Panelboards and cabinets shall accommodate active and spare circuit breakersin voltage ratings as required. Cabinets shall be flush or surface mounted.Minimum 20" wide by 5-3/4" deep, common keyed, complete with directoryholder mounted on door interior. Panels served on a riser feeder shall includean auxiliary 6" wiring gutter. Circuit breakers shall be plug-in type in ratingsand interrupting capacity as scheduled. Square D “QO” or “NQOD”panelboards.
2. Panelboards shall include a main circuit breaker.3. Panelboards supplying lighting and receptacle and appliance-branch circuits
shall be located in each respective dwelling unit and as shown on drawings.4. Approved Manufacturers: Eaton, Square D (EXCLUDING Homeline series
equipment), G.E, Siemens.
16.48 MOTORS AND SPECIAL OUTLETS:A. Feeders to be extended from the service equipment panel to feed mechanical and
building service equipment and from remote panelboards to feed minor mechanicalequipment. Circuit breakers to be provided to feed all equipment shall be permanufacturer's recommendations. Disconnect switches to be provided at the unitsto comply with Code.
16.51 INTERIOR LIGHTING:A. All Areas:
1. Provide and install light fixtures per drawings and fixture schedule(s).2. All fluorescent ballasts shall be electronic type with total harmonic distortion
(THD) of less than 10%.
16.52 SITE LIGHTING:A. Provide lighting for the entry drive, parking lot and walkways. Refer to the site plan
for areas requiring lighting.B. Provide flagpole illumination as shown on drawings and fixture schedule.C. Provide electrical connection to monument sign and mail kiosk. See site plan.D. Fixtures shall be cut-off type luminaires with HID, LED lamps or other light sources
as shown on drawings and fixture schedule.E. Poles shall be as shown on drawings and fixture schedule.F. Fixtures are to be controlled by a photo-cell and/or time clock.G. Provide 2'-0” AFG bases for all poles and install in accordance with the
manufacturer's instructions.H. Provide a ground rod in each pole base.
I. Branch wiring to lighting poles shall be #10 THWN minimum copper wire in3/4-inch minimum PVC conduit. Wiring shall include #10 green equipmentgrounding conductor that shall be bonded to the metal pole, luminaire and thepanelboard ground bus.
16.70 FIRE ALARM SYSTEM:A. Provide a zoned fire alarm system in each Apartment building for Sprinkler System
supervision. Each Apartment building shall be monitored for Alarm, Supervisoryand Trouble conditions by an addressable fire alarm system in the Clubhouse. TheClubhouse fire alarm system shall protect the clubhouse, monitor the Apartmentbuildings and transmit status of the system to an approved supervising station. AllFire Alarm Systems shall comply with NFPA 72 (2013), International Fire Code(IFC), ADA (ANSI A117.1), Florida Building Code 2017 (FBC), Florida AccessibilityCode (2014), NEC (2014) and all State and Local Codes and the requirements ofthe local fire department.
B. Pull stations shall be provided at each exit door of public areas.
C. Combination strobe/horn units shall be provided to be effective throughout thefacility.
D. Strobe/horn unit shall comply with the ADA requirements.
E. Smoke detectors to be provided in the return air duct of each air handling unitwhere required.
F. Sleeping area smoke detectors shall include an 88dBA low frequency sounder baseproviding a minimum 70 dBA at the pillow.
G. The fire alarm control panel shall monitor flow switches and valve tamper switchesfor the flow of water and the positioning of sprinkler system valves.
16.76 TELEPHONE SYSTEM:A. The Telephone System shall be provided by the Owner under separate contract.
The Electrical Contractor shall coordinate with the Owner and/or his contractor toprovide a raceway and back box system as required.
B. The telephone service and main distribution frame shall be provided by the Ownerunder separate contract.
C. Telephone instruments, switching equipment and other accessories shall befurnished and installed by the Owner.
D. All wall type telephone/data outlet shall be 4-inch square boxes with single gangplaster frame.
E. Provide a conduit, raceway or cable from each telephone/data outlet to telephoneservice point.
F. UTP type Level 5 for data and Level 3 for voice wiring shall be provided. Wiringshall be grouped and neatly bundled, run at right angles, secured with nylon cableties of proper size and supported every four feet from either structural supports orby placing new wire hangers. All cables shall be identified at each end.
16.79 TELEVISION CABLE OR SATELLITE SYSTEM:A. The Television or Satellite System shall be provided by the Owner under a
separate contract. The Electrical Contractor shall coordinate with the Ownerand/or his contractor to provide a raceway and back box system as required.
16.80 SECURITY SYSTEM:A. General: This specification section in conjunction with the drawings shall serve as
the basis for the scope of the system.1. EC to coordinate with local vendor and owner's representative(s) to provide
and install complete and functional system to the satisfaction of the owner.2. Final design and layout (including, but not limited to, devices, cabling, DVR,
monitors, amplifiers, locations, head-end and peripheral equipment, etc.) shallbe specified by contractor's vendor, in coordination with owners localrepresentative.
02
CONTINENTAL 422 FUND LLCW134 N8675 EXECUTIVE PARKWAYMENOMONEE FALLS, WI 53051
262.502.5500 * FAX 262.502.5522
LPA #8374
Consulting Electrical Engineers/Planners
Ph. (262) 860-1544, Fax (262) 860-1566
Elm Grove, Wisconsin 53122
12970 W. Bluemound Road - Suite 101
01
02
Reviewed for CodeCompliance
PRBD20180209312
ReviewedCCEPR-dae.
1/4" = 1'-0"
1
TYPE 6G GARAGE BUILDING (TYPICAL)
COMMON/GARAGE - LIGHTING FIXTURE SCHEDULE
LAMP DATA
UTILITY GLOBEGG
DES.
1
DESCRIPTION
12010W LED A19
TYPE
VOLT
SURFACE RECESS
LIGHTING FIXTURE
MFR.
P3408-09
CAT. NO.
GF
1' x 4' FLUORESCENT
2 12032W T8 -
XEM4-232-DCA-EU
WET LABELED
UBV 3 120 -
GJ STANDARD STRIP 1 12032W T8 P7267-30EB
GH
7.25" LED FLUSH MOUNT FIXTURE
1 120
17W LED
-
PROGRESS
P8222-28-30K
WET LABELED, PROVIDE WITH
3000KLIGHTING
COLUMBIA
LIGHTING
PROGRESS
LIGHTING
-
-
OVER THE MIRROR 3 LT VANITY
BATHROOM
P2006-09
PROGRESS
LIGHTING
GEMH
EMERGENCY BATTERY UNIT-
2 6V -
WITH HEADS
LM-50-
12WDUAL-LITE
GEMO
EMERGENCY EGRESS
2 6V -
REMOTE HEADS, WP
OCR-D-W-0603L
3W LEDDUAL-LITE
SRHSW0612
*LIGHT FIXTURES SPECIFIED ARE THE STANDARD PRODUCT FOR ALL CONTINENTAL PROPERTIES INC. PROJECTS*
**FURNISH LIGHT FIXTURES AS SPECIFIED WITHOUT SUBSTITUTION**
***ALL LIGHT FIXTURE MUST BE APPROVED BY OWNER PRIOR TO PURCHASE***
PROGRESS
LIGHTING
20W LED
A19
GB
GARAGE BUILDING/MAITENANCE
WALL PACK, DARK BRNZ
- 120 -
26W LED
DSXW1 LED-10C-
700-40K-T3M-
4000K
LITHONIA
LIGHTING
120-DDBXD4000K LED
4" JBOX FOR INSTALLATION.
0' 6'2' 4'1'
CONTINENTAL 422 FUND LLCW134 N8675 EXECUTIVE PARKWAYMENOMONEE FALLS, WI 53051
262.502.5500 * FAX 262.502.5522
LPA #8374
Consulting Electrical Engineers/Planners
Ph. (262) 860-1544, Fax (262) 860-1566
Elm Grove, Wisconsin 53122
12970 W. Bluemound Road - Suite 101
01
NO SCALE
3
ELECTRICAL SERVICE RISER
02
02
Reviewed for CodeCompliance
PRBD20180209312
ReviewedCCEPR-dae.
FLAG POLE
LTG
6
SIGN
8
KP
3
5
KP
3
ENTRY
GATES
TC
PANEL
AV4S-20
AV4S-20
AV4S-20
AV4S-20
AV3-20
AV3-20AV3-20
AV5-20
AV5-20
AV5-20
AV3-20
AV3-20
AV3-20
AV3-20
AV3-20
W
W
AV3-20
POOL GATE
HARDWARE
POOL GATE
HARDWARE
TYP. OF 7 GATES
AV3-20AV3-20
2
34
27
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
AV3-20
AV3-20
AV4S-20
BV3-20
BV3-20
CV2-8
CV2-8
15
1
777
7
7
7
7
7
7
33
16
13
17
1
METERS
1
METERS
1
METERS
1
METERS
1
METERS
1
METERS
1
METERS
1
METERS
1
METERS
1
METERS
1
METERS
1
METERS
1
1212 10
9
B20
PANEL
G24
PANEL
BUILDING #1
G28IIE
BUILDING #2
G24E
PET
PLAYGROUND
BUILDING #3
B20E
BUILDING #10
B20E
BUILDING #5
G28IIE
BUILDING #7
G28IIE
BUILDING #4
G24E
BUILDING #6
G24E
BUILDING #8
G24E
BUILDING #9
G24E
BUILDING #11
G24E
BUILDING #12
G24E
BUILDING #13
G24E
BUILDING #14
G24E
CLUBHOUSE
35
3535
3535
4
11
MG
PANEL
GARAGE 1
-6GS-
GARAGE 2
-8G-
GARAGE 3
-8G-
GARAGE 4
-8G-
PET
PLAYGROUND
MAINTENANCE
GARAGE
MAIL KIOSK
SHEET NOTES
1
2
3
4
5
6
7
MAINTAIN FOUR FEET (4'-0") CLEARANCE IN FRONT OF ELECTRICAL
METERS.
PROVIDE POOL DECK LIGHTING POWER FROM PANEL 'CH' LOCATED
WITHIN CLUBHOUSE - 3 #10 & #10G IN 3/4"C. PROVIDE PHOTOCELL
CONTROL.
PROVIDE ROUGH-IN FOR NEW CARD-READER COORDINATE WITH
CARD-READING SYSTEM
PROVIDE ENTRY GATE POWER FROM PANEL 'CH' LOCATED WITHIN
CLUBHOUSE - 3 #10 & #10G IN 3/4"C. PROVIDE ALL ROUGH-IN FOR
ENTRY GATE SYSTEM, INCLUDING EXIT VEHICLE DETECTION LOOP.
PROVIDE MAIL KIOSK POWER FROM PANEL 'B20' LOCATED
WITHIN BUILDING #3 - 2 #10 & #10G IN 3/4"C.
PROVIDE FLAG POLE LIGHTING POWER FROM PANEL 'CH' LOCATED
WITHIN CLUBHOUSE - 3 #10 & #10G IN 3/4"C. VERIFY EXACT LOCATION
WITH OWNER IN FIELD.
PROVIDE UNIT BUILDING MOUNTED LIGHTING FROM HOUSE PANEL
CIRCUIT. REFER TO ELECTRICAL SECOND FLOOR PLANS FOR
FIXTURE LOCATIONS & ARCHITECTURAL PLANS FOR ELEVATIONS.
SHEET NOTES
PROVIDE SIGN LIGHTING POWER [(2) 20A/1P CIRCUIT BREAKERS]
FROM PANEL 'CHA' LOCATED WITHIN CLUBHOUSE - 3 #10 & #10G IN
3/4" C. PROVIDE TIMECLOCK IN MEP2 TO CONTROL SIGN LIGHTING.
PROVIDE '6G' GARAGE PANEL 'GB6' POWER FROM PANEL 'G24'
LOCATED WITHIN BUILDING #4 - 3 #6 & #8G IN 1"C.
PROVIDE '8G' GARAGE PANEL 'GB8' POWER FROM PANEL 'G28'
LOCATED WITHIN BUILDING #5 - 3 #6 & #8G IN 1"C.
PROVIDE MAINTENANCE GARAGE PANEL 'MG' POWER FROM
ELECTRICAL METERS LOCATED ON BUILDING #3 - 3 #1 & #6G IN
1-1/2"C.
PROVIDE '8G' GARAGE PANEL 'GB8' POWER FROM PANEL 'G28'
LOCATED WITHIN BUILDING #7 - 3 #6 & #8G IN 1"C.
PROVIDE SITE LIGHTING POWER FROM PANEL 'G24' LOCATED WITHIN
BUILDING #12 - 3 #10 & #10G IN 3/4"C.
PROVIDE TRASH COMPACTOR POWER FROM METER CENTER
LOCATED ON BUILDING #2- 3 #1 & #6G IN 1-1/4"C.
PROVIDE SITE LIGHTING POWER FROM PANEL 'CH' LOCATED WITHIN
CLUBHOUSE - 3 #10 & #10G IN 3/4"C.
8
9
11
10
12
13
14
15
SHEET NOTES
PROVIDE SITE LIGHTING POWER FROM PANEL 'G28' LOCATED WITHIN
BUILDING #1 - 3 #10 & #10G IN 3/4"C.
PROVIDE SITE LIGHTING POWER FROM PANEL 'G24' LOCATED WITHIN
BUILDING #13 - 3 #10 & #10G IN 3/4"C.
PROVIDE SITE LIGHTING POWER FROM PANEL 'B20' LOCATED WITHIN
BUILDING #3 - 3 #10 & #10G IN 3/4"C.
PROVIDE SITE LIGHTING POWER FROM PANEL 'G24' LOCATED WITHIN
BUILDING #4 - 3 #10 & #10G IN 3/4"C.
PROVIDE SITE LIGHTING POWER FROM PANEL 'G28' LOCATED WITHIN
BUILDING #5 - 3 #10 & #10G IN 3/4"C.
PROVIDE SITE LIGHTING POWER FROM PANEL 'G24' LOCATED WITHIN
BUILDING #6 - 3 #10 & #10G IN 3/4"C.
PROVIDE SITE LIGHTING POWER FROM PANEL 'G28' LOCATED WITHIN
BUILDING #7 - 3 #10 & #10G IN 3/4"C.
PROVIDE SITE LIGHTING POWER FROM PANEL 'G24' LOCATED WITHIN
BUILDING #8 - 3 #10 & #10G IN 3/4"C.
16
17
18
19
22
23
20
21
SHEET NOTES
PROVIDE SITE LIGHTING POWER FROM PANEL 'G24' LOCATED WITHIN
BUILDING #9 - 3 #10 & #10G IN 3/4"C.
PROVIDE SITE LIGHTING POWER FROM PANEL 'B20' LOCATED WITHIN
BUILDING #10 - 3 #10 & #10G IN 3/4"C.
PROVIDE SITE LIGHTING POWER FROM PANEL 'G24' LOCATED WITHIN
BUILDING #11 - 3 #10 & #10G IN 3/4"C.
PROVIDE POWER TO THE POOL GATE HARDWARE FROM THE
CLUBHOUSE.
PROVIDE 240V, 40A 1-PHASE CONNECTION TO FOUNTAIN FROM
BUILDING 5 HOUSE PANEL. INSTALL FUSED DISCONNECT PEDESTAL
WITHIN 15 FEET OF LAKE EDGE WITH CONDUIT THAT RUNS 3 FEET
INTO LAKE FOR FOUNTAIN CONTROL WIRING CONNECTION.
PROVIDE 240V, 40A 1-PHASE CONNECTION TO FOUNTAIN FROM
BUILDING 13 HOUSE PANEL. INSTALL FUSED DISCONNECT PEDESTAL
WITHIN 15 FEET OF LAKE EDGE WITH CONDUIT THAT RUNS 3 FEET
INTO LAKE FOR FOUNTAIN CONTROL WIRING CONNECTION.
24
25
26
27
28
29
SHEET NOTES
PROVIDE 240V, 40A 1-PHASE CONNECTION TO FOUNTAIN FROM
BUILDING 11 HOUSE PANEL. INSTALL FUSED DISCONNECT PEDESTAL
WITHIN 15 FEET OF LAKE EDGE WITH CONDUIT THAT RUNS 3 FEET
INTO LAKE FOR FOUNTAIN CONTROL WIRING CONNECTION.
PROVIDE 240V, 40A 1-PHASE CONNECTION TO FOUNTAIN FROM
BUILDING 6 HOUSE PANEL. INSTALL FUSED DISCONNECT PEDESTAL
WITHIN 15 FEET OF LAKE EDGE WITH CONDUIT THAT RUNS 3 FEET
INTO LAKE FOR FOUNTAIN CONTROL WIRING CONNECTION.
PROVIDE METER PEDESTAL FOR IRRIGATION SYSTEM, DESIGNED BY
A DESIGN-BUILD CONTRACTOR. FINAL LOCATION AND EXACT
REQUIREMENTS TO BE COORDINATED WITH OWNER AND
LANDSCAPE/IRRIGATION CONTRACTOR.
PROVIDE SITE LIGHTING POWER FROM PANEL 'G24' LOCATED WITHIN
BUILDING #14 - 3 #10 & #10G IN 3/4"C.
PROVIDE ELECTRICAL ROUGH-IN FOR POOL GATE HARDWARE.
CONFIRM EXACT REQUIREMENTS WITH POOL CONTRACTOR.
REFER TO ACCESSORY BUILDING SETS FOR WALL-MOUNT FIXTURE
MOUNTING DETAILS.
30
31
32
33
34
35
GENERAL NOTES
1. COLLIER COUNTY LOCAL LIGHTING ORDINANCES 6-143, 6-144, 6-145,
6-146, 6-147 ALL REFERENCE MAINTAINING A MAXIMUM LIGHT LEVEL
OF 1.0 FOOT CANDLES AT ADJOINING PROPERTY LINES.
2. POLE LOCATIONS ADJACENT TO PEDESTRIAN SIDEWALKS TO BE
INSTALLED WITHIN 1' OF SIDEWALK EDGE.
3. POLE FIXTURES MUST COMPLY WITH RISK CATEGORY 1 WIND
DESIGN LOAD OF 149 MPH WIND LOADS.
4. FINAL SITE LIGHTING POLE LOCATIONS AND LIGHTING
PHOTOMETRIC TO BE COORDINATED WITH FINAL LANDSCAPE
DESIGN.
2.
LIGHTING FIXTURE NOTES:
1.
PROVIDE PHOTOCELL ON FIXTURE.
PROVIDE ROUND DIRECT BURIAL POLE.
SITE LIGHTING FIXTURE SCHEDULE
LAMP DATA
DES. DESCRIPTION
TYPE
VOLT
SURFACE RECESS
LIGHTING FIXTURE
MFR. CAT. NO.
W 1 120 --
WALL-MOUNT LED FIXTURE
AV3-14 1 240 0.67
2,3,4
1,2,4
GB
WALL-MOUNT LED FIXTURE
1 120 --
DARK BRONZ, MAINTENANCE
4,5
AV3-20 1 240
55W LED
0.67
VPS-24NB-55-4K-
4000K
AREA LED FIXTURE, TYPE 3 DIST.
1,2,4
20'-0" ROUND POLE, DARK BRNZT3-UNV-PCR-TL-
BEACON
PRODUCTS
CV2-8 1 240 0.8
1,2,4
AV5-20
1 240 0.67 1,2,4
AV4S
1 240 0.67
1,2
-20
3. PROVIDE FIXTURE WITH HOUSE SIDE SHIELD.
4. ***NO SUBSTITUTIONS ACCEPTED.***
3,4
HOUSE-SIDE SHIELD, DARK BRNZ
UNIT BUILDING WALL PACK
BV3-20
1 240 0.67 1,2,4
AREA LED FIXTURE, TYPE 4 DIST.
20'-0" ROUND POLE, DARK BRNZ
AREA LED FIXTURE, TYPE 5 DIST.
AREA LED FIXTURE, TYPE 3 DIST.
HOUSE-SIDE SHIELD
55W LED
4000K
55W LED
4000K
72W LED
4000K
25W LED
4000K
26W LED
4000K
55W LED
4000K
26W LED
4000K
AREA LED FIXTURE, TYPE 3 DIST.
20'-0" ROUND POLE, DARK BRNZ
20'-0" ROUND POLE, DARK BRNZ
14'-0" ROUND POLE, DARK BRNZ
BEACON
PRODUCTS
BEACON
PRODUCTS
BEACON
PRODUCTS
BEACON
PRODUCTS
LITHONIA
LIGHTING
LITHONIA
LIGHTING
LITHONIA
LIGHTING
GARAGE / GARAGE BUILDINGS
AREA LED FIXTURE, TYPE 2 DIST.
8'-0" ROUND POLE, DARK BRNZ
RA-DBT
VPS-24NB-55-4K-
T4-UNV-PCR-TL-
BLC-RA-DBT
VPS-24NB-55-4K-
T5R-UNV-PCR-TL-
RA-DBT
VPS-30NB-70-4K-
T3-UNV-PCR-TL-
RA-DBT
VPS-24NB-55-4K-
T3-UNV-PCR-TL-
RA-DBT
DSXWPM-LED-10C-
700-40K-T2M-240-
DSXW2-LED-20C-
350-40K-T3M-120-
PE-HS-DDBXD
DSXW1-LED-10C-
700-40K-T3M-120-
DDBXD
5. CONTROLLED BY SEPARATE TIMECLOCK.
--
1.9
--
3.0
2.3
3.0
3.0
3.0
02
NORTH
0' 120'40' 80'20'
CONTINENTAL 422 FUND LLCW134 N8675 EXECUTIVE PARKWAYMENOMONEE FALLS, WI 53051
262.502.5500 * FAX 262.502.5522
LPA #8374
Consulting Electrical Engineers/Planners
Ph. (262) 860-1544, Fax (262) 860-1566
Elm Grove, Wisconsin 53122
12970 W. Bluemound Road - Suite 101
01
02
Reviewed for CodeCompliance
PRBD20180209312
ReviewedCCEPR-dae.