ABB Medium Voltage MV Indoor Voltage Transformers VT'S - 3.3kV to 40.5kV - ABB KGUG, ABB TDC, ABB...

14
Indoor Voltage Transformers KGUG Description The KGUG voltage, double-pole insulated transformers are casted in epoxi resin and designed mostly for insu- lation voltages of 24 kV to 36 kV. Other insulation values are to be the subject of an agreement between the manufacturer and the customer. If no other value is required the transformers are manufactured with a voltage factor of 1.2 x Un. All the parts of the primary winding of the transformer are insulated from the earth, including the terminals, to an insulation level identical with the rated insulation level. When operating in a three-phase system the primary inlets of the transformer are connected across the respective lines, to the phase-to-phase voltage, mostly in the „V“ type of connections. The majority of transformers is equipped with one secondary winding, intended to be used for either the measurement or protection purposes. One of the terminals of each secondary winding has to be earthed during the transformer operation. If not required other wise, the secondary winding is lead out into a casted secondary terminal board. The transformer may be mounted in any position. The transformers are fixed by four screws, The M8 bolted earthing clamp is located on the transformer base plate. The secondary, sealable terminal board is covered with a transparent cover. Rated primary voltages ... 15 kV; 20 kV; 22 kV; 30 kV; 33 kV; 35 kV Other primary voltages based on customer‘s request may be delivered, too. Rated secondary voltages... 100 V; 110 V – 0.2; 0.5 and 1 accuracy classes (measuring winding), or 3P; 6P (protection winding) Other secondary voltages based on customer‘s request may be delivered, too. Rated frequency ... 50 Hz; 60 Hz The transformers are manufactured and delivered conformably to the requirements and recommendations of the following standards and regulations: IEC, SEV, VDE, ANSI, BS, GOST and »SN. Highest voltage for equipment [kV] 24, 36 Power frequency test voltage, 1 min. [kV] 50, 70 Lightning impulse test voltage [kV] 125, 170 Rated burden, classes [VA/cl] 80/0.2 - 300/0.5 - 600/1 Max. thermanl output [VA] 2000

description

ABB MV Medium Voltage Transformers - Voltage Transformers VT's Up to 40.5kV Medium Voltage MV Indoor Transformers VT's ABB Power Products ABB MV Medium Voltage Transformers - Voltage Transformer Features Indoor dry type, cast resin insulated transformers for medium voltages (MV). ABB transformers are suitable for measuring and protection of MV medium voltages with up to 2 secondary windings. ABB MV Medium Voltage Transformer : Unearthed Double-Pole Voltage Transformer ABB KGUG ABB KGUG voltage transformer for medium voltage systems has all parts of its primary winding, including terminals, insulated from the earth at a level corresponding to its rated insulation level. ABB KGUG voltage, double-pole insulated transformers are casted in epoxy resin and designed mostly for insulation voltages of 24kV to 36kV. ABB KGUG Voltage Transformer ABB MV Medium Voltage Transformer : Indoor Voltage Transformer Double Pole ABB TDC ABB TDC voltage transformer for medium voltage systems has all parts of its primary winding, including terminals, insulated from the earth at a level corresponding to its rated insulation level . Indoor dry type, cast resin insulated medium voltage (MV) transformer for measuring and protection with up to 2 secondary windings. ABB TDC Voltage Transformer ABB MV Indoor Voltage Transformer : Indoor Voltage Transformer ABB TJP ABB TJP voltage transformer is a single phase voltage transformer which is intended to have one end of its primary winding directly earthed. Indoor dry type, cast resin insulated medium voltage transformer for measuring and protection with up to 2 secondary windings. With or without fuses. Most electrical standards available. Reconnectable MV medium voltage versions available. ABB TJP Voltage Transformer ABB MV Indoor Voltage Transformer : Indoor Voltage Transformer Single Pole ABB KGUGI ABB KGUGI voltage transformer is 36kV indoor dry type, cast resin insulated medium voltage transformers for measuring and protection with up to 2 secondary windings. With or without fuses. Most electrical standards available. Reconnectable versions available. ABB KGUGI Voltage Transformer ABB MV Indoor Voltage Transformer : Indoor Voltage Transformer Single Pole ABB TJC ABB TJC is a single phase voltage transformer which is intended to have one end of its primary winding directly earthed. Indoor dry type, cast resin insulated medium voltage transformer for measuring and protection with up to 2 secondary windings. With or without fuses. Most electrical standards available. Reconnectable MV medium voltage versions available.

Transcript of ABB Medium Voltage MV Indoor Voltage Transformers VT'S - 3.3kV to 40.5kV - ABB KGUG, ABB TDC, ABB...

Page 1: ABB Medium Voltage MV Indoor Voltage Transformers VT'S -  3.3kV to 40.5kV - ABB KGUG, ABB TDC, ABB TJP, ABB KGUGI, ABB TJC

Indoor Voltage Transformers KGUG

Description

The KGUG voltage, double-pole insulated transformers are casted in epoxi resin and designed mostly for insu-lation voltages of 24 kV to 36 kV.Other insulation values are to be the subject of an agreement between the manufacturer and the customer.If no other value is required the transformers are manufactured with a voltage factor of 1.2 x Un. All the partsof the primary winding of the transformer are insulated from the earth, including the terminals, to an insulationlevel identical with the rated insulation level. When operating in a three-phase system the primary inlets of thetransformer are connected across the respective lines, to the phase-to-phase voltage, mostly in the „V“ type ofconnections. The majority of transformers is equipped with one secondary winding, intended to be used for eitherthe measurement or protection purposes. One of the terminals of each secondary winding has to be earthedduring the transformer operation.If not required other wise, the secondary winding is lead out into a casted secondary terminal board.The transformer may be mounted in any position. The transformers are fixed by four screws, The M8 boltedearthing clamp is located on the transformer base plate. The secondary, sealable terminal board is covered witha transparent cover.

Rated primary voltages ... 15 kV; 20 kV; 22 kV; 30 kV; 33 kV; 35 kVOther primary voltages based on customer‘s request may be delivered, too.Rated secondary voltages... 100 V; 110 V – 0.2; 0.5 and 1 accuracy classes (measuring winding), or 3P; 6P(protection winding)Other secondary voltages based on customer‘s request may be delivered, too.Rated frequency ... 50 Hz; 60 HzThe transformers are manufactured and delivered conformably to the requirements and recommendations of thefollowing standards and regulations: IEC, SEV, VDE, ANSI, BS, GOST and »SN.

Highest voltage for equipment [kV] 24, 36Power frequency test voltage, 1 min. [kV] 50, 70Lightning impulse test voltage [kV] 125, 170Rated burden, classes [VA/cl] 80/0.2 - 300/0.5 - 600/1Max. thermanl output [VA] 2000

Page 2: ABB Medium Voltage MV Indoor Voltage Transformers VT'S -  3.3kV to 40.5kV - ABB KGUG, ABB TDC, ABB TJP, ABB KGUGI, ABB TJC

Dimensions

Double pole voltage transformers

A 3440-530-I/2001

epyT ecnadroccanituptuodetaR,EDVdnaSB,VES,CEIhtiw

sessalcni,zH06dna05AV

ecnadroccaninedrubdeaR,ISNAhtiw

sessalcni,zH06AV

mumixaMtuptuolamreht

AVni.t.vrep

zH06dna05AV2.0 5.0 1 3 3.0 6.0 2.1

42GUGK63GUGK

0808

003003

006006

00810081

ZYXWZYXW

ZZ,ZYXWZZ,ZYXW

ZZ,ZYXWZZ,ZYXW

00020002

Type A B C D E F D H J K L m/kgKGUG 24 391 202 455 376 320 200 222 215 260 179 72 approx. 60KGUG 36 443 227 505 427 348 310 248 230 300 186 72 approx. 80

KGUG 2436

KGU

2

ABB s.r.o.Videnska 117 Tel.: +420 547 152 602619 00 Brno, Czech Republic +420 547 152 604E-mail: [email protected] Fax: +420 547 152 626http://www.abb.com

The data and ilustrations in this catalogue are not binding.We reserve the right to make changes of the content, inthe course of technical development of the product.

Stephanie Appleby
Page 3: ABB Medium Voltage MV Indoor Voltage Transformers VT'S -  3.3kV to 40.5kV - ABB KGUG, ABB TDC, ABB TJP, ABB KGUGI, ABB TJC

DescriptionThe TDC 4 voltage, double-pole insulated transformers are cast in epox resin and designed mostly for insulation voltages of 3.6 kV to 12 kV.If no other value is required the transformers are manufactured with a voltage factor of 1.2 x Un. All the parts of the primary winding of the transformer are insulated from the earth, including the terminals, to an insulation level identical with the rated insulation level. When operating in a three-phase system the primary inlets of the transformer are connected across the respective lines, to the phase-to-phase voltage, mostly in the „V“ type of connection. The majority of the transformers is equipped with one secondary winding, intended to be used for either the measurement or protection purposes. One of the terminals of each secondary winding has to be earthed during the transformer operation.If not required otherwise, the secondary winding is lead out into a cast secondary terminal board.The transformer may be mounted in any position. The transformers are fixed by four screws, The M8 bolted earthing clamp is located on the transformer base plate. The secondary, sealable terminal board is covered with a transparent cover made of plastic material.

Rated primary voltages ... 3 kV; 3.3 kV; 6 kV; 6.6 kV; 10 kV; 11 kVOther primary voltages based on customer‘s request may be delivered, too.Rated secondary voltages... 100 V; 110 V – 0.2; 0.5; and 1 accuracy classes (measuring winding), or 3P; 6P (protection winding)Other secondary voltages based on customer‘s request may be delivered, too.Rated frequency ... 50 Hz; 60 HzDesign for two primary voltages is also possible, based on a consultancy to be conducted with the manufacturer (change over secondary side).The transformers are manufactured and delivered conformably to the requirements and recommendations of the following standards and regulations: IEC, VDE, ANSI, BS, GOST and CSN.

Highest voltage for equipment [kV] 3.6 - 12

Power frequency test voltage, 1 min. [kV] 10 -

Lightning impulse test voltage [kV] 40 - 75

Max. rated burden, classes [VA/cl] 25/0.2 - 75/0.5 - 150/1

TDC 4Indoor voltage transformers

Medium Voltage Product

Jonathan Hewitt
Page 4: ABB Medium Voltage MV Indoor Voltage Transformers VT'S -  3.3kV to 40.5kV - ABB KGUG, ABB TDC, ABB TJP, ABB KGUGI, ABB TJC

2

Dimensions

100

220

20

116139

22

9

4

M10x15

M8

Pg1

6 14

(125

)

2x 11

148

27010

1196

30

82 188

110

338

Marking of the voltage transformer outlets

a) Single-pole insulated transformer | b) Single-pole insulated transformer with a tap | c) Double-pole insulated transformer | d) Double-pole insulated transformer with a tap | e) Single-pole insulated transformer with two secondary windings | f) Single-pole insulated transformer with two secondary windings, with one of which being the auxiliary (residual) winding | g) Single-pole insulated transformer with two secondary, tapped windings, with one which being the auxiliary (residual) winding.

Page 5: ABB Medium Voltage MV Indoor Voltage Transformers VT'S -  3.3kV to 40.5kV - ABB KGUG, ABB TDC, ABB TJP, ABB KGUGI, ABB TJC

3

Standartized transformers

Primary

voltage,V

Secondary voltage

voltage,V accuracy burden, VA

3000 100 0,2 10,15,25

3000 100 0,5 15,25,50

3000 100 1 50,75,100

3300 110 0,2 10,15,25

3300 110 0,5 15,25,50

3300 110 1 50,75,100

6000 100 0,5 15,25,50

6000 100 0,5 15,25,50

6000 100 1 50,75,100

6600 110 0,2 10,15,25

6600 110 0,5 15,25,50

6600 110 1 50,75,100

10000 100 0,2 10,15,25

10000 110 0,2 10,15,25

10000 100 0,5 15,25,50

10000 110 0,5 15,25,50

10000 100 1 50,75,100

10000 110 1 50,75,100

11000 100 0,2 10,15,25

11000 110 0,2 10,15,25

11000 100 0,5 15,25,50

11000 110 0,5 15,25,50

11000 100 1 50,75,100

11000 110 1 50,75,100

Page 6: ABB Medium Voltage MV Indoor Voltage Transformers VT'S -  3.3kV to 40.5kV - ABB KGUG, ABB TDC, ABB TJP, ABB KGUGI, ABB TJC

1VLC

0005

22 -

Rev

1, e

n 20

10.x

x.xxABB s.r.o.

PPMV Brno

Videnska 117

619 00 Brno, Czech Republic

Tel.: +420 547 152 602

+420 547 152 614

Fax: +420 547 152 626

E-mail: [email protected]

www.abb.com

The data and ilustrations in this catalogue are not binding. We reserve the right to make changes of the content, in the course of technical development of the product.

Page 7: ABB Medium Voltage MV Indoor Voltage Transformers VT'S -  3.3kV to 40.5kV - ABB KGUG, ABB TDC, ABB TJP, ABB KGUGI, ABB TJC

Description

Highest voltage for equipment [kV] 3.6 – 12

Power frequency test voltage, 1 min. [kV] 10 – 28 (42)

Lightning impulse test voltage [kV] 40 - 75

Fuse : 2 or 6,3 A(IEC)

Max. rated burden, classes [VA/cl] 25/0.2 - 50/0.5 - 100/1

Residual winding [VA/cl] 50 - 200/6P

TJP 4.0-FIndoor Voltage Transformer

Medium Voltage Product

The TJP 4.0-F epoxi insulated voltage transformers are cast in epoxi resin and designed mostly for insulation voltages of 3.6 kV to 12 kV. If no a different value is required the transformers are manufactured with a overvoltage factor of 1.9 x Un/8 hrs. One outlet of the primary winding, including the respective terminal is insulated from the earth to a level which corresponds to the rated insulation value. The other outlet of primary winding with its terminal is earthed during the operation. Most of the transformers are equipped with two secondary windings, the first one for either measuring or protection purposes, the other for being connected into an open-delta connection in a three-phase system. One terminal of each secondary winding and one of the open-delta connected terminals have to be earthed during the transformer operation. The secondary windings are lead out into a cast-type secon-dary terminal board. The secondary terminal board is covered with a sealed plastic over. The transformer can be mounted in any position. The trans-former body is fixed by four screws, the bolted M8 earthing clamp is located on the transformer base plate. The TJP 4.0-F transformer is equipped with a fuse conformably to IEC standard. The design of TJP4.0-F is suitable for AIS panels (see HV terminal and the position of the secondary terminals) and the replacement of the fuse can be done from the front (HV terminal) or after removing the upper part of the fuseholder – see „fuse replacement instruction“. There are two options for the fuseholder position : above secondary terminal box (suitable for ABB AIS, drawing number 1VL4200251R0101) or on the opposite side (drawing number 1VL4200300R0101).

Rated primary voltages ... 3/V3 kV; 3,3/V3 kV; 6/V3 kV; 6,6/V3 kV; 10/V3 kV; 11/V3 kV. Other primary voltages can also be supplied on request. Rated secondary voltages... 100/V3 V; 110/V3 V – accuracy classes 0.2; 0.5; 1 (measuring winding) or 3P;6P(protection winding). Other secondary voltages can also be supplied on request. Rated voltages for open-delta connection: ... 100/3 V; 110/3 V- class 6P. Other voltages for open-delta connection can also be supplied based on customer requirement. Rated frequency ... 50 Hz; 60 Hz. Based on a discussion with the manufacturer the transformer can also be provided with primary winding designed for two different primary voltages (with secondary side changeover).The transformers are manufactured conformably to the requirements and recommendations of the following standards and regulations: IEC, VDE, ANSI, BS, GOST and CSN.

Jonathan Hewitt
Page 8: ABB Medium Voltage MV Indoor Voltage Transformers VT'S -  3.3kV to 40.5kV - ABB KGUG, ABB TDC, ABB TJP, ABB KGUGI, ABB TJC

1VLC

0005

22, R

ev.1

, en

2011

. 02.

15

The data and ilustrations in this catalogue are not binding. We reserve the right to make changes of the content, in the course of technical development of the product.

ABB s.r.o.

PPMV Brno

Videnska 117

619 00 Brno, Czech Republic

Tel.: +420 547 152 602

+420 547 152 614

Fax: +420 547 152 626

E-mail: [email protected]

www.abb.com

Dimensions

Marking of the voltage transformer outlets

a) Single-pole insulated transformer b) Double-pole insulated transformer with a tap c) Single-pole insulated transformer with two secondary windings d) insulated transformer with two secondary windings, with one of which being the auxiliary (residual) winding e) Single-pole insulated transformer with two secondary, tapped windings, with one which being the auxiliary (residual) winding.

a) b) c) d) e)

Page 9: ABB Medium Voltage MV Indoor Voltage Transformers VT'S -  3.3kV to 40.5kV - ABB KGUG, ABB TDC, ABB TJP, ABB KGUGI, ABB TJC

KGUGIIndoor Voltage Transformers

Medium Voltage Product

Dimensions

Highest voltage for equipment

Power frequency test voltage, 1 min.

Lightning impulse test voltage

Rated burden, classes

Residual windin

[kV]

[kV]

[kV]

[ VA/cl ]

[ VA/cl ]

D

Technical parameters

escription

The KGUGI single-pole insulated voltage transformers are casted in epoxi resin and designed mostly for insu-lation voltages of 24 to 36 kV.Insulation voltages different from the above are to be the subject of an agreement between the manufacturer andthe customer.If no other value is required the transformers are manufactu-red with a overvoltage factor of 1.9 x Un/8 hrs. Oneoutlet of the primary winding, including the respective terminal is insulated from the earth to a level whichcorresponds to the rated insulation value. The other outlet of primary winding with terminal is earthed duringthe operation.The transformer is mostly equipped with two secondary windings, the first one for either measuring or protectionpur-poses, the other for being connected into an open-delta connection in a three-phase system. One terminalof each secondary winding and one of the open-delta connected terminals have to be earthed during thetransformer operation.When not required other wise the secondary windings are lead out into a casted-type secondary terminal board.The transformer can be mounted in any position. The transformers are fixed by four screws, the M8 boltedearthing clamp is located on the transformer base plate. The secondary terminal board is covered with voltagessealable cover.

Rated primary voltages ... 15/√3 kV; 20/√3 kV; 22/√3 kV; 30/√3 kV; 33/√3 kV; 35/√3 kVOther primary voltages can also be supplied on request.Rated secondary voltages... 100/√3 V; 110/√3 V – accuracy classes 0.2; 0.5; 1 (measuring winding) or 3P; 6P(protection winding).Other secondary voltages can also be supplied on request.Rated voltages for open-del-ta connection: ... 100/3 V; 110/3 V- class 6POther voltages for open-delta connection can also be supplied based on customer requirement.Rated frequency ... 50 Hz; 60 HzThe transformers are manufactured confor-mably to the requirements and recommendations of the followingstandards and regulations: IEC, SEV, VDE, ANSI, BS, GOST and ČSN.

24, 36

50, 70

125, 170

80/0.2 - 250/0.5 - 500/1

up to 600/6P

Jonathan Hewitt
Page 10: ABB Medium Voltage MV Indoor Voltage Transformers VT'S -  3.3kV to 40.5kV - ABB KGUG, ABB TDC, ABB TJP, ABB KGUGI, ABB TJC

1VLV

0005

31-R

ev.,

en,2

011.

02.2

5

ABB s.r.o.

PPMV Brno

Videnska 117

619 00 Brno, Czech Republic

Tel.: +420 547 152 602

+420 547 152 614

Fax: +420 547 152 626

E-mail: [email protected]

www.abb.com

Text: The data and illustrations are not binding. We reserve the right to make changes without notice in the course of technical development of the product.

©Copyright 2011 ABBAll rights reserved

Dimensions

Single pole voltage transformers

epy eT cnadroccanituptuodetaR,EDVdnaSB,VES,CEIhtiw

sessalcni,zH06dna05

ecnadroccaninedrubdeaR,ISNAhtiw

sessalcni,zH06

mumixaMtuptuolamreht

AVni.t.vrep

zH06dna052.0 5.0 1 3 3.0 6.0 2.1

42IGUGK63IGUGK

08051

052004

005057

00010051

YXW)YY(YXW

ZYXWZZ,ZYXW

ZZ,ZYXWZZ,ZYXW

00510002

KGUGI 24

36

KGU1

Type A B C D E F D H J K L m/kg

KGUGI 24 391 202 455 376 320 100 222 215 260 179 72 approx. 60

KGUGI 36 443 227 505 427 348 155 248 230 300 186 72 approx. 80

Jonathan Hewitt
Page 11: ABB Medium Voltage MV Indoor Voltage Transformers VT'S -  3.3kV to 40.5kV - ABB KGUG, ABB TDC, ABB TJP, ABB KGUGI, ABB TJC

DescriptionThe TJC 4 single-pole insulated voltage transformers are cast in epoxi resin and designed mostly for insulation voltages of 3.6 kV to 12 kV.If no other value is required the transformers are manufactured with a overvoltage factor of 1.9 x Un/8 hrs.One outlet of the primary winding, including the respective terminal is insulated from the earth to a level which corresponds to the rated insulation value. The transformer is mostly equipped with two secondary windings, the first one for either measuring or protection purposes, the other for being connected into an open-delta connection in a three-phase system. One terminal of each secondary winding and one of the open-delta connected terminals have to be earthed during the transformer operation. When not required otherwise, the secondary windings are lead out into a cast-type secondary terminal board.The transformer can be mounted in any position. The transformer ore fixed by four screws, the M8 bolted earthing clamp is located on the transformer base plate. The secondary terminal board is covered with a transparent and sealable cover made of plastic material.

Rated primary voltages ... 3/√3 kV; 3,3/√3 kV; 6/√3 kV; 6,6/√3 kV; 10/√3 kV; 11/√3 kVOther primary voltages can also be supplied on request.Rated secondary voltages... 100/√3 V; 110/√3 V – accuracy classes 0.2; 0.5; 1 (measuring winding) or 3P; 6P (protection winding).Other secondary voltages can also be supplied on request.Rated voltages for open-delta connection: ... 100/3 V; 110/3 V- class 6POther voltages for open-delta connection can also be supplied based on customer requirement.Rated frequency ... 50 Hz; 60 HzBased on a discussion with the manufacturer the transformer can also be designed for two primary voltage levels (with change over secondary side).The transformers are manufactured conformably to the requirements and recommendations of the following standards and regulations: IEC, VDE, ANSI, BS, GOST and CSN.

Highest voltage for equipment [kV] 3.6 - 12

Power frequency test voltage, 1 min. [kV] 10 -

Lightning impulse test voltage [kV] 40 - 75

Max. rated burden, classes [VA/cl] 25/0.2 - 50/0.5 - 100/1

Residual winding [VA/cl] 50 - 200/6P

TJC 4Indoor voltage transformers

Medium Voltage Product

Jonathan Hewitt
Page 12: ABB Medium Voltage MV Indoor Voltage Transformers VT'S -  3.3kV to 40.5kV - ABB KGUG, ABB TDC, ABB TJP, ABB KGUGI, ABB TJC

2

Dimensions

WEIGHT: appr. 20kgCREEPAGE DISTANCE: 280mm

22 2022

0

8

174197

4

M8

Pg16 14

M10x15

125

148

11

280338

11 30

130140

96

Marking of the voltage transformer outlets

a) Single-pole insulated transformer | b) Single-pole insulated transformer with a tap | c) Double-pole insulated transformer | d) Double-pole insulated transformer with a tap | e) Single-pole insulated transformer with two secondary windings | f) Single-pole insulated transformer with two secondary windings, with one of which being the auxiliary (residual) winding | g) Single-pole insulated transformer with two secondary, tapped windings, with one which being the auxiliary (residual) winding.

Page 13: ABB Medium Voltage MV Indoor Voltage Transformers VT'S -  3.3kV to 40.5kV - ABB KGUG, ABB TDC, ABB TJP, ABB KGUGI, ABB TJC

3

Standard execution of the transformers

Primary

voltage,V

Secondary voltage Residual winding

voltage,V accuracy burden, VA voltage,V accuracy burden, VA3000/√3 100/√3 0,2 10,15,25 3000/√3 100/√3 0,2 10,15,25 100/3 6P 50

3000/√3 100/√3 0,2 10,15,25 100/3 6P 100

3000/√3 100/√3 0,5 15,25,50

3000/√3 100/√3 0,5 15,25,50 100/3 6P 50

3000/√3 100/√3 0,5 15,25,50 100/3 6P 100

3000/√3 100/√3 1 50,75,100

3000/√3 100/√3 1 50,75,100 100/3 6P 50

3000/√3 100/√3 1 50,75,100 100/3 6P 100

3300/√3 110/√3 0,2 10,15,25

3300/√3 110/√3 0,2 10,15,25 110/3 6P 50

3300/√3 110/√3 0,2 10,15,25 110/3 6P 100

3300/√3 110/√3 0,5 15,25,50

3300/√3 110/√3 0,5 15,25,50 110/3 6P 50

3300/√3 110/√3 0,5 15,25,50 110/3 6P 100

3300/√3 110/√3 1 50,75,100

3300/√3 110/√3 1 50,75,100 110/3 6P 50

3300/√3 110/√3 1 50,75,100 110/3 6P 100

6000/√3 100/√3 0,2 10,15,25

6000/√3 100/√3 0,2 10,15,25 100/3 6P 50

6000/√3 100/√3 0,2 10,15,25 100/3 6P 100

6000/√3 100/√3 0,5 15,25,50

6000/√3 100/√3 0,5 15,25,50 100/3 6P 50

6000/√3 100/√3 0,5 15,25,50 100/3 6P 100

6000/√3 100/√3 1 50,75,100

6000/√3 100/√3 1 50,75,100 100/3 6P 50

6000/√3 100/√3 1 50,75,100 100/3 6P 100

6600/√3 110/√3 0,2 10,15,25

6600/√3 110/√3 0,2 10,15,25 110/3 6P 50

6600/√3 110/√3 0,2 10,15,25 110/3 6P 100

6600/√3 110/√3 0,5 15,25,50

6600/√3 110/√3 0,5 15,25,50 110/3 6P 50

6600/√3 110/√3 0,5 15,25,50 110/3 6P 100

6600/√3 110/√3 1 50,75,100

6600/√3 110/√3 1 50,75,100 110/3 6P 50

6600/√3 110/√3 1 50,75,100 110/3 6P 100

10000/√3 100/√3 0,2 10,15,25

10000/√3 100/√3 0,2 10,15,25 100/3 6P 50

10000/√3 100/√3 0,2 10,15,25 100/3 6P 100

10000/√3 110/√3 0,2 10,15,25

10000/√3 110/√3 0,2 10,15,25 110/3 6P 50

10000/√3 110/√3 0,2 10,15,25 110/3 6P 100

10000/√3 100/√3 0,5 15,25,50

10000/√3 100/√3 0,5 15,25,50 100/3 6P 50

10000/√3 100/√3 0,5 15,25,50 100/3 6P 100

10000/√3 110/√3 0,5 15,25,50

10000/√3 110/√3 0,5 15,25,50 110/3 6P 50

10000/√3 110/√3 0,5 15,25,50 110/3 6P 100

10000/√3 100/√3 1 50,75,100

10000/√3 100/√3 1 50,75,100 100/3 6P 50

10000/√3 100/√3 1 50,75,100 100/3 6P 100

10000/√3 110/√3 1 50,75,100

10000/√3 110/√3 1 50,75,100 110/3 6P 50

10000/√3 110/√3 1 50,75,100 110/3 6P 100

11000/√3 100/√3 0,2 10,15,25

11000/√3 100/√3 0,2 10,15,25 100/3 6P 50

11000/√3 100/√3 0,2 10,15,25 100/3 6P 100

11000/√3 110/√3 0,2 10,15,25

11000/√3 110/√3 0,2 10,15,25 110/3 6P 50

11000/√3 110/√3 0,2 10,15,25 110/3 6P 100

11000/√3 100/√3 0,5 15,25,50

11000/√3 100/√3 0,5 15,25,50 100/3 6P 50

11000/√3 100/√3 0,5 15,25,50 100/3 6P 100

11000/√3 110/√3 0,5 15,25,50

11000/√3 110/√3 0,5 15,25,50 110/3 6P 50

11000/√3 110/√3 0,5 15,25,50 110/3 6P 100

11000/√3 100/√3 1 50,75,100

11000/√3 100/√3 1 50,75,100 100/3 6P 50

11000/√3 100/√3 1 50,75,100 100/3 6P 100

11000/√3 110/√3 1 50,75,100

11000/√3 110/√3 1 50,75,100 110/3 6P 50

11000/√3 110/√3 1 50,75,100 110/3 6P 100

Page 14: ABB Medium Voltage MV Indoor Voltage Transformers VT'S -  3.3kV to 40.5kV - ABB KGUG, ABB TDC, ABB TJP, ABB KGUGI, ABB TJC

1VLC

0005

20 -

Rev

1, e

n 20

11, 0

1.15ABB s.r.o.

PPMV Brno

Videnska 117

619 00 Brno, Czech Republic

Tel.: +420 547 152 602

+420 547 152 614

Fax: +420 547 152 626

E-mail: [email protected]

www.abb.com

The data and ilustrations in this catalogue are not binding. We reserve the right to make changes of the content, in the course of technical development of the product.