ABB LV SWITCHGEAR M10x-M User's Guide

72
Motor Control and Protection Unit M10x-M User’s Guide

description

ABB LV SWITCHGEAR M10x-M User's Guide

Transcript of ABB LV SWITCHGEAR M10x-M User's Guide

Page 1: ABB LV SWITCHGEAR M10x-M User's Guide

Motor Control and Protection Unit M10x-M User’s Guide

Page 2: ABB LV SWITCHGEAR M10x-M User's Guide

The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document.

In no event shall ABB be liable for direct, indirect, special, incidental, or consequential damages of any nature or kind arising from the use of this document, nor shall ABB be liable for incidental or consequential damages arising from use of any software or hardware described in this document.

This document and parts thereof must not be reproduced or copied without ABB's written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. The software described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.

All rights reserved.

Copyright © 2010 Xiamen ABB Low Voltage Equipment Co., Ltd.

Page 3: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Content

1TNC911112D0204

3

Table of content

General ........................................................................................................................... 4 Target Group .................................................................................................................................... 4 Use of Warning, Caution, Information and Tip icon ............................................................................ 4 Terminology ...................................................................................................................................... 5 Related Documentation ..................................................................................................................... 6 Related System Version .................................................................................................................... 6 Document Revision History ............................................................................................................... 6

Product Overview .......................................................................................................... 7 Introduction ....................................................................................................................................... 7 Structure ........................................................................................................................................... 8

Mounting ........................................................................................................................ 9 Mounting of M10x-M ......................................................................................................................... 9

Interfaces ........................................................................................................................ 9 Terminal Designations..................................................................................................................... 10 Typical Diagram .............................................................................................................................. 16

Functionality ................................................................................................................ 18 Starter Types .................................................................................................................................. 18

Operating Sequence in NR-2N (Dahlander) ..............................................................................26

Operating Sequence in NR-2N (Separate Windings).................................................................27 Protection Function ......................................................................................................................... 31 Function and Supervision ................................................................................................................ 48

Communication Interface ............................................................................................ 60 Overview......................................................................................................................................... 60 RS485 Interface Cable .................................................................................................................... 60 Function Description ....................................................................................................................... 60

Parameterization .......................................................................................................... 61 Overview......................................................................................................................................... 61 Parameterization via MD2/MD3 ....................................................................................................... 61 Parameterization via MODBUS ....................................................................................................... 61 M10x-M Parameters ........................................................................................................................ 61

Accessories ................................................................................................................. 62 MD2/MD3 Operator Panel ............................................................................................................... 62 Parameterization Software: MCUsetup ............................................................................................ 66

Appendix A Technical Data ...................................................................................... 69

Page 4: ABB LV SWITCHGEAR M10x-M User's Guide

General M10x-M User's Guide

1TNC911112D0204 4

General

Target Group The manual is primarily intended for those requiring information on the applications of M10x for the purpose of understanding, engineering, wiring & operating of the product.

The objective of this manual is to provide the technical functions description of M10x-M.

This manual should be studied carefully before installing, parameterizing or operating the motor control unit. It is assumed that the user has a basic knowledge of physical and electrical fundamentals, electrical wiring practices and electrical components.

This document should be used along with M10x-M Parameter Description, which provides detailed information about parameters and their applications.

Use of Warning, Caution, Information and Tip icon

Page 5: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide General

1TNC911112D0204

5

Terminology List of the terms, acronyms, abbreviations and definitions that used in this document.

Abbreviation Term Description

Alarm Alarm is defined as status transition from any state to abnormal state. Status transition to abnormal state can be data crossing over the pre-defined alarm limit.

DCS Distributed Control System

See also PCS

Local Hardwiring A Control Access term describing that the M10x accepts its commands from the Hardwired inputs, when the Local control authority is enabled.

MODBUS Fieldbus communication protocol

MODBUS RTU Fieldbus communication protocol

PCS Process Control System

High level process control system

PTC Positive Temperature Coefficient

PTC thermistors are semiconductor elements with a very high positive temperature coefficient.

RCU Remote Control Unit Local control unit with pushbutton and indicator to operate a device (e.g. motor) from field level.

Remote fieldbus A Control Access term describing that the M10x accepts its commands from the fieldbus inputs, when the remote control authority is enabled.

RS485 Communication interface standard from EIA (Electronics Industries Association, USA), operating on voltages between 0V and +5V. RS-485 is more noise resistant than RS-232C, handles data transmission over longer distances, and can drive more receivers.

TOL Thermal Overload Protection against overheated caused by overload

Trip A consequence of an alarm activated or an external trip command from another device to stop the motor or trip the circuit breaker.

Page 6: ABB LV SWITCHGEAR M10x-M User's Guide

General M10x-M User's Guide

1TNC911112D0204 6

Related Documentation 1TNC 911105 M0203 M10x-M Parameter Description

1TNC 911505 M0204 Modbus Protocol Implementation for M10x-M

1TNC911104 M0202 MCUSetup (Software Tool) User Guide

Related System Version

The content of this document is related to firmware revision release,

M101-M, FV1.2

M102-M, FV1.7

Until further notice, this document is also applicable for future firmware versions other than those listed above. The described functions are designed but may not be fully implemented in all details. Please refer to the current system guides and release notes regarding possible restrictions.

Document Revision History

D0201 Initial Edition 10/2003

D0202 Product Revision 10/2005

D0203 Revise COM terminals; Revise terminology of control authority. Revise earth fault setting.

10/2007

D0204 Template Changed as per BU Guideline. 10/2010

Page 7: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Product Overview

1TNC911112D0204

7

Product Overview

Introduction M10x is an intelligent motor control and protection device based on current measurement or current measurement and voltage measurement. Installed in and supplied as part of ABB Low Voltage switchgear MNS ®, it is part of low voltage system family to provide customers another ABB intelligent system solution.

M10x is of microprocessor-based product providing comprehensive but standard features into one device. It is designed to use in individual motor starter. By setting/changing parameters into the device, M10x provides specific control, monitoring, protection functions tailored for each motor. .

Standard features simplify maintenance and plant expansion.

M10x-M is M10x with Modbus interface. M10x-M is with dual RS485 interfaces which support full redundancy network and are able to communicate with upstream control system in parallel and in high speed and reliable way. Any M10x-M may be interrogated on demand to determine both actual and operating parameters. Fast response time for alarm or trip status makes real time control of a complete process possible. Statistical recording of running hours and number of operations assists with predictive maintenance scheduling.

For AC motor and the operated installation this means:

Reliable protection

Maximum utilization

Continuous supervision

Flexibility

Fig. 1 Network connection of M10x-M

Fieldbus capacity: 32 nodes

Communication Connection

Redundancy Communication Connection

Page 8: ABB LV SWITCHGEAR M10x-M User's Guide

Product Overview M10x-M User’s Guide

1TNC911112D0204 8

Structure M10x-M consists of two parts:

Main unit (with current converter unit)

Operator Panel MD2/MD3

Main Unit Main unit is a unit contains the electronics of the motor control unit and integrated CT.

There are 6 types of M10x main unit in terms of different CT range. For motor rating larger than 63A, interposing CTs are to select.

Main unit is fixed to a mounting rail.

Operator Panel MD2/MD3 The Operator panel is the user interface mounted on the front door or drawer. With control buttons, LED, LCD module (MD2 only), MD2/MD3 provides the functions as motor control, supervision and parameterizing. One operator panel is provided for each main unit at request.

M10x-M Enclosure material The enclosure of the M10x-P is made of polycarbonate. Flammability rating of the material is UL 94 V-0 and material is halogen free.

Colour of the enclosure is RAL 7012.

For detail description of MD2/MD3 please refer to chapter – Accessories

Fig. 2 M10x-M

Page 9: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Interfaces

1TNC911112D0204

9

Mounting

Mounting of M10x-M Basic dimension of M10x-M W X H X D=110mm X 140mm X 75mm

Typical Installation of M10x-M DIN rail or installation to horizontal plane

Basic dimension of MD2 W X H X D=88mm X 72mm X 30mm

Mounting dimension of MD2 W X H=84mm X 68mm

Basic dimension of MD3 W X H X D=88mm X 50mm X 28mm

Mounting dimension of MD3 W X H=83mm X 45mm

The installation details of M10x-M and MD2/MD3, please see the related documentation installation manual

Interfaces Terminal blocks of M10x are located on the top of the main unit for easy access. There are 3 sets of I/O terminal blocks and 1 set of RJ11 connector as shown.

L

Digital Inputs Thermistor Input (M102 Only)

MD2/3 Connector

Integrated CT

Dual RS485 Interfaces

RCT Input

Relay Output Ground Safety and Surge

Vo ltage Input (M102 Only)

T

Power Supply

Fig. 4 Terminals viewed from top

M102-M MD3

Fig. 3 M10x-M in 8E/4 module

Page 10: ABB LV SWITCHGEAR M10x-M User's Guide

Interfaces M10x-M User's Guide

1TNC911112D0204 10

Terminal Designations

Terminal Block Terminal Number

Designation… Plug/Contacts

Remark

X1 X1:1…X1:13 I/O block, switch input Cross section

1.5mm2 X1:14…X1:16 PTC input (M102-M)

X2 X2:1…6 Interface for MD2/3 Cable with RJ11 Connector provided

X3

X3:1…5 Fieldbus for external communication

Cross section 2.5mm2 X3:6,7 RCT input

X3:8…13 Voltage Input (M102-M)

X4

X4:1…9 Relay output

Cross section 2.5mm2 X4:10,11 24VDC Supply

X4:12 Ground

L1-T1;L2-T2;L3-T3 Lead-through Current Measurement 10mm window

Table 1 Device terminals

Power Supply The standard power supply is 24V DC preferably from a UPS.

Terminal No.

Name Description

X4:11 24VDC Power supply 24VDC +

X4:10 GND Power supply 0VDC Table 2 Power supply terminals

Digital Input M101-M has 6 and M102-M has 13 digital inputs of the type 5mA/24VDC. Digital inputs are cyclically read. The contact is detected as closed if the input current is over 2.5mA and open if current is under 0.8mA. There are three programmable inputs included, which can be assigned to a defined function.

Page 11: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Interfaces

1TNC911112D0204

11

Terminal No. Name Description X1:1 IN_COM Digital input common terminal (0VDC)

X1:2 NC Spare

X1:3 LOC/R Locate/remote control switch input

X1:4 NC Spare

X1:5 F_Ca Contactor control A feedback

X1:6 NC Spare

X1:7 F_Cb Contactor control B feedback

X1:8 NC Spare

X1:9 PROG_IN0 Programmable input 0

X1:10 NC Spare

X1:11 PROG_IN1 Programmable input 1

X1:12 NC Spare

X1:13 PROG_IN2 Programmable input 2 Table 3 Digital input terminals and pins of M101-M

Terminal No. Name Description X1:1 LIMIT1 Limit position switch 1 input

X1:2 LIMIT2 Limit position switch 2 input

X1:3 START1 Motor start 1 switch input

X1:4 START2 Motor start 2 switch input

X1:5 STOP Motor stop switch input

X1:6 LOC/R Locate/remote control switch input

X1:7 F_Ca Contactor control A feedback

X1:8 F_Cb Contactor control B feedback

X1:9 F_Cc Contactor control C feedback

X1:10 PROG_IN0 Programmable input 0

X1:11 PROG_IN1 Programmable input 1

X1:12 PROG_IN2 Programmable input 2

X1:13 MCB Auxiliary contact from main switch Table 4 Digital input terminals and pins of M102-M

Page 12: ABB LV SWITCHGEAR M10x-M User's Guide

Interfaces M10x-M User's Guide

1TNC911112D0204 12

PTC Input (M102-M Only) M102-M utilizes type A temperature sensor with a characteristic curve according to IEC 60947-8 to follow the temperature of motor winding. PTC connector is located on the top of M102-M unit, terminal X1.

In 2-wire connection application, PTCA and PTCB are to be wired to both ends of PTC sensor which is embedded inside motor. M10x-M also supports 3-wire connection by introducing third wire connection from temperature sensor to eliminate the impact of cable resistance.

i) PTC measurement is available in M102-x only!

ii) In 2-wires application, terminals X1:15 and X1:16 shall be shorted to avoid

potential disturbance.

Terminal No. Name Description

X1:14 PTCA PTC measurement input A

X1:15 PTCB PTC measurement input B

X1:16 PTCG PTC measurement input G (Option) Table 5 PTC input terminals

Page 13: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Interfaces

1TNC911112D0204

13

Fieldbus Interface M10x-M is with dual RS485 communication interfaces which support full redundancy network design.

Shielded twisted pair (STP) shall be used for communication wiring.

The shield terminal X3: 3 is connection with the ground terminal X4: 12 which is

solidly earthed via internal circuit.

Terminal No. Name Description

X3:1 2B Serial RS485 B

X3:2 2A Serial RS485 A

X3:3 SHIELD Shield

X3:4 1B Serial RS485 B

X3:5 1A Serial RS485 A Table 6 Fieldbus interface terminals

Residual Current Transformer M10x-M supports earth fault measurement through Residual Current Transformer (RCT ).

Terminal No. Name Description X3:6 Ioa Residual current transformer input A

X3:7 Iob Residual current transformer input B Table 7 Residual current transformer terminals

i) For information on different types of RCTs, please refer to “M10x Ordering Guide”.

ii) In the case that RCT is not required, terminals X3:6 and X3:7 shall be shorted to avoid potential external disturbance.

Voltage Measurement (M102-M Only) M102-M continuously measures three phase voltages. The voltage data is used for protection functions and power calculation.

Voltage measurement is only available in M102-x!

Page 14: ABB LV SWITCHGEAR M10x-M User's Guide

Interfaces M10x-M User's Guide

1TNC911112D0204 14

Terminal No. Name Description

X3:9 Vc Phase C voltage input

X3:11 Vb Phase B voltage input

X3:13 Va Phase A voltage input

X3:8 N Neutral input Table 8 Voltage input terminals of M102-M only Current Measurement Terminal M10x-M measures continuously three motor phase currents. The phase current data will be used by the protection functions and is reported to the fieldbus. Phase currents are reported as a value –relative to the motor nominal current In.

Current wires are lead through current sensors from either side of the terminal.

Direction can be either L->T or T->L considering that all currents must have the same direction.

Motor nominal currents above 63A are not measured directly, but instead intermediate current transformer’s secondary side is connected through M10x-M current measurement terminal.

When one phase system is selected, current measurement is via phase A.

Contactor Control Output M10x-M supports several motor starter types. The control of the contactor is performed with internal relays (Output CCA, CCB, CCC) by the microprocessor.

Internal relays CCA and CCB are hardwire-interlocked to prevent both contactors being closed at the same time.

M101-M is of CCA and CCB contactor relays only.

Terminal No. Name Description M101-M M102-M

X4:6… CCLI Contactor control voltage input

X4:7 CCA Contactor control A

X4:8 CCB Contactor control B

X4:9 CCC Contactor control C Table 9 Contactor control terminals

Page 15: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Interfaces

1TNC911112D0204

15

Programmable Output M10x-M has two auxiliary programmable output relays. Each programmable output can be assigned to a defined function.

Terminal No. Name Description M101-M M102-M

X4:1 GR1_A Programmable relay output 1 (NO+NC) X4:2 GR1_B

X4:3 GR1_C

X4:4 GR2_A Programmable relay output 2 (NO)

X4:5 GR2_B Table 10 Programmable output terminals

M101-M programmable relay output 1.

Interface for MD2/MD3 M10x-M has a RJ11 interface for operator panel MD2/MD3.

Terminal No. Name Description

X2:1 RS485 B Communication ports with operator panel

X2:2 RS485 A

X2:3 SHIELD Shield

X2:4 SHIELD

X2:5 Vcc Power supply for operator panel

X2:6 GND Table 11 Operator panel interface terminals

Ground Terminal

Terminal No. Name Description

X4:12 GROUND Ground safety and surge Table 12 Ground terminal

This is an additional ground terminal provided for dissipating transient signals and surges. This must be connected by a thick wire or braid to the system ground for reliable operation.

Page 16: ABB LV SWITCHGEAR M10x-M User's Guide

Interfaces M10x-M User's Guide

1TNC911112D0204 16

Typical Diagram A typical wiring diagram is show below

MOTOR

X3:13X3:11X3:9X3:8

Internal Connector

X3:6 X3:7

CT Module

X1:1

X1:2

X1:3

X1:4

X1:5

X1:6

X1:7

X1:8

X1:9

X1:10

X1:11

X1:12

X1:13

X1:14

X1:15

X1:16

X3:1

X3:2

X3:3

X3:4

X3:5

X4:10

X4:11

X4:6

X4:7

X4:8

X4:9

X4:1

X4:2

X4:3

X4:4

X4:5

DC24V

Loc/R

F_Ca

NCNC

NC

SHIELD

DC24VGND

CCLICCA

CCBNC

GR1_A

NC

Phone jack RJ11

+ KM

KMN

L1

MCB KML1

L2

L3

PE

to MD2/MD3

Residual CT

RS485redundancy

RS485

-

+

NC

F_Cb

PROG_IN1

PROG_IN2

PROG_IN0

NC

NC

NC

NC

NCIN_COM

NC

GR1_BGR1_C

NC NCNCNC I0A I0B-

DC24V

GROUND X4:12

2B2A

1B1A

Fig. 5 Typical wiring diagram for M101-M

--------------- Internal Connection Line: terminal X3: 3 (Shield) is connected to terminal X4: 12 (Ground) internal of M10x-M. .

Programmable output contacts (GR1_A, GR1_B &GR1_C) as shown in Fig5 are floating N/C and N/O contacts from the same relay and respond to parameter settings. E.g. when ‘Trip’ is set to programmable output, N/O contact will close under healthy situation. In the case of power loss, contact status will restore as shown in Fig5.

Page 17: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Interfaces

1TNC911112D0204

17

MOTOR

X3:13X3:11X3:9X3:8

Internal Connector

X3:6X3:7

CT Module

X1:1

X1:2

X1:3

X1:4

X1:5

X1:6

X1:7

X1:8

X1:9

X1:10

X1:11

X1:12

X1:13

X1:14

X1:15

X1:16

X3:1

X3:2

X3:3

X3:4

X3:5

X4:10

X4:11

X4:6

X4:7

X4:8

X4:9

X4:1

X4:2

X4:3

X4:4

X4:5

DC24V

LIMIT1LIMIT2

START1START2STOP

LOC/R

F_Ca

PROG_IN0

MCB

PTCAPTCB

PTCG

SHIELD

DC24VGND

CCLICCACCBCCC

GR2_A

Phone jack RJ11

DC24V+KM

MCB

KMN

L1

MCB KML1

L2

L3

N

PTC

PE

to MD2/MD3

Residual CT

RS485redundancy

RS485

-

+

F_Cb

F_Cc

PROG_IN1

PROG_IN2

GR2_B

GR1_AGR1_BGR1_C

VA VB VCN I0AI0B

GROUND X4:12

2B2A

1B1A

Fig. 6 Typical wiring diagram for M102-M

--------------- Internal Connection Line: the shield terminal X3: 3 is connected with the ground terminal X4: 12 via internal circuit.

Programmable output contacts GR1 as shown in Fig6 are floating N/C and N/O contacts from the same relay. GR1 & GR2 contacts respond to parameter settings. E.g. when ‘Trip’ is set to programmable output, N/O contact will close (N/C open)

under healthy situation. In the case of power loss, contact status will restore as shown in Fig6.

Page 18: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 18

Functionality

Starter Types M10x offers several kinds of motor starting control modes via the control of relay output. It supervises the operating state of the contactor according to the feedback of auxiliary contact.

The following starting control modes are offered:

Starter type M101-M M102-M

NR-DOL

REV-DOL

NR-DOL/RCU

REV-DOL/RCU

Actuator

NR-S/D

NR-2N

Autotransformer

NR_softstater

REV_softstater

Feeder Table 13 Starter types supported by M10x-M

NR_DOL: Non Reversing Direct Online

REV_DOL: Reversing Direct Online

NR_DOL/RCU: Non Reversing Direct Online with RCU

REV_DOL/RCU: Reversing Direct Online with RCU

Actuator: Actuator with limit switch input

NR_S/D: Non Reversing Star-Delta

NR_2N: Two speed driver for Non Reversing starter

Autotransformer: Autotransformer starter

NR_Softstarter: Non Reversing softstarter control

REV_Softstarter: Reversing softstarter control

Feeder: Feeder is regarded as a specific starter mode in M10x

Starter type is selected with a dedicated parameter to match the wiring for contactor and motor control circuits.

Page 19: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Functionality

1TNC911112D0204

19

NR-DOL STARTER NR_DOL starter is a basic starter type for driving motor to one direction. When start command has been received from field or local I/O, the contactor control output will be energized and remains this condition until stop command has been received or any protection function activated.

Name Pin Description

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

LOC/R X1:3 Local/remote control switch input

F_Ca X1:5 Contactor control A feedback Table 14-1 NR-DOL starter contactor control interface(for M101-M) Name Pin Description

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

LOC/R X1:6 Local/remote control switch input

F_Ca X1:7 Contactor control A feedback

Table 14-2 NR-DOL starter contactor control interface(for M102-M)

M101-M/M102-M

Fig. 7 Control circuit for NR-DOL starter (for M10x-M)

Page 20: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 20

NR-DOL STARTER (RCU) RCU (Remote Control Unit) is a starter type where contactors are directly controlled by a special RCU-switch located near the motor. This allows controlling the motor even if the M10x-M is not on duty.

Name Pin Description Remark

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

GR1_C X4:3 Programmable relay output M101-M Only

F_Ca X1:5 Contactor control A feedback

LOC/R X1:3 Local/remote control switch input Table 15-1 NR-DOL starter contactor control interface (for M101-M)

Name Pin Description Remark

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

CCC X4:9 Contactor control C

F_Ca X1:7 Contactor control A feedback

LOC/R X1:6 Local/remote control switch input Table 15-2 NR-DOL starter contactor control interface (for M102-M)

M101-M

Fig. 8 Control circuit for NR-DOL/RCU starter(for M101-M)

Page 21: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Functionality

1TNC911112D0204

21

M102-M

Fig. 9 Control circuit for NR-DOL/RCU starter(for M102-M)

REV-DOL STARTER REV-DOL uses contactor control output A for controlling the contactor which drives motor to direction CW and correspondingly contactor control output B is used for direction CCW. When starting motor to either direction contactor will be energized and is stopped (not energized) by command (fieldbus or local I/O) or active protection function.

Name Pin Description

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

CCB X4:8 Contactor control B

F_Ca X1:5 Contactor control A feedback

F_Cb X1:7 Contactor control B feedback

LOC/R X1:3 Local/remote control switch input Table 16-1 REV-DOL starter contactor control interface (for M101-M)

Name Pin Description

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

CCB X4:8 Contactor control B

F_Ca X1:7 Contactor control A feedback

F_Cb X1:8 Contactor control B feedback

LOC/R X1:6 Local/remote control switch input Table 16-2 REV-DOL starter contactor control interface (for M102-M)

Page 22: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 22

M101-M/M102-M

Fig. 10 Control circuit for REV-DOL starter (for M10x-M)

REV-DOL/RCU STARTER The functionality of this starter type is according to NR-DOL/RCU starter with support for reversing use of motor.

Name Pin Description Remark

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

CCB X4:8 Contactor control B

GR1_C X4:3 Programmable relay output M101-M Only

F_Ca X1:5 Contactor control A feedback

F_Cb X1:7 Contactor control B feedback

LOC/R X1:3 Local/remote control switch input Table 17-1 REV-DOL starter contactor control interface (for M101-M)

Name Pin Description Remark

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

CCB X4:8 Contactor control B

CCC X4:9 Contactor control C M102-M Only

F_Ca X1:7 Contactor control A feedback

F_Cb X1:8 Contactor control B feedback

LOC/R X1:6 Local/remote control switch input Table 17-2 REV-DOL starter contactor control interface (for M102-M)

Page 23: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Functionality

1TNC911112D0204

23

M101-M

Fig. 11 Control circuit for REV-DOL/RCU starter (for M101-M)

M102-M

Fig. 12 Control circuit for REV-DOL/RCU starter (for M102-M)

Actuator STARTER (M102-M Only) This starter type is for controlling valves and actuators by using limit switches

Name Pin Description

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

CCB X4:8 Contactor control B

LIMIT1 X1:1 Limit position switch 1 input

LIMIT2 X1:2 Limit position switch 2 input

PROG_IN0 X1:10 Programmable input 0 (configured as Torque switch input)

Page 24: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 24

F_Ca X1:7 Contactor control A feedback

F_Cb X1:8 Contactor control B feedback

LOC/R X1:6 Local/remote control switch input Table 18 Actuator starter contactor control interface

M102-M

Fig. 13 Control circuit for Actuator starter

Limit switch causes the motor to be stopped when activated. Event message is sent to the fieldbus according to activated limit switch and additionally start command is allowed only to reverse direction. Torque switch is selectable by parameterization and can be connected to programmable input 0.

NR-S/D STARTER (M102-M Only) Motor start current is reduced in star connection to 1/3 rd of the current in delta connection, with lower torque during the same time.

Start to delta starting sequence is based on the presented control logic Figure. The changeover condition is time.

The following guideline applied for selecting parameter values

Changeover time < Motor startup time

Name Pin Description

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

CCB X4:8 Contactor control B

CCC X4:9 Contactor control C

F_Ca X1:7 Contactor control A feedback

Page 25: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Functionality

1TNC911112D0204

25

F_Cb X1:8 Contactor control B feedback

F_Cc X1:9 Contactor control C feedback

LOC/R X1:6 Local/remote control switch input Table 19 NR_S/D starter contactor control interface

M102-M

CT

Fig. 14 Control circuit for NR-S/D starter

NR-2N STARTER (M102-M Only) NR-2N/Dahlander uses three contactors control motor rotation speed where motor is equipped with a three phase winding. Rotation speed can be changed “on the fly” without stop command in between.

Current measurement for NR-2N utilizes two external current transformers measuring current from motor main supply. External current transformers can be selected separately for both speeds.

Name Pin Description

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

CCB X4:8 Contactor control B

CCC X4:9 Contactor control C

F_Ca X1:7 Contactor control A feedback

F_Cb X1:8 Contactor control B feedback

F_Cc X1:9 Contactor control C feedback

Page 26: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 26

LOC/R X1:6 Local/remote control switch input

Table 20 NR-2N starter contactor control interface

M102-M

CT for N1CT for N2

Fig. 15 Control circuit for NR_2N starter, Danlander

M102-M

CT1 for N1 CT2 for N2

Fig. 16 Control circuit for NR_2N starter, separate windings

NR-2N starter is basically design for 3 contactors control with Dahlander winding

connection. Special instruction listed below has to follow when 2 contactors control (separate winding) is applied.

Operating Sequence in NR-2N (Dahlander)

Sending command ‘Speed1’ to close contactor CCA. Sending command ‘Speed2’ to close contactor CCB and CCC. Contactors are latched Sending stop command to open CCA or CCB + CCC.

.

Page 27: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Functionality

1TNC911112D0204

27

Operating Sequence in NR-2N (Separate Windings)

Sending command ‘Speed1’ to close contactor CCA. Sending command ‘Speed2’ to close contactor CCB and CCC Stop command opens CCA or CCB and CCC.

Instruction Note: Although CCC has no actual function in separate winding application, CCC and F_CC are still required to be wired as shown in Fig15 & Fig16 to complete NR-2N control function internal of M10x. “KA” relay as shown in Figs is the dummy control relay only to replace the third contactor.

Motor can be controlled with sequences.e.g. Stop -> Speed N1->Stop Stop -> Speed N2 -> Stop Stop -> Speed N1 -> Speed N2 ->Stop Stop -> Speed N2 -> Speed N1 -> Stop

AUTOTRANSFORMER STARTER (M102-M Only) This starter type is used to control autotransformer unit in order to minimize the voltage drop during motor startup. Autotransformer starter with three contactors supports motor starting with reduced voltage thus providing reduced motor startup current. The starting torque will be reduced accordingly.

The following guideline applied for selecting parameter values

Changeover time < Motor startup time

Name Pin Description

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

CCB X4:8 Contactor control B

CCC X4:9 Contactor control C

F_Ca X1:7 Contactor control A feedback

F_Cb X1:8 Contactor control B feedback

F_Cc X1:9 Contactor control C feedback

LOC/R X1:6 Local/remote control switch input

Table 21 Autotransformer starter contactor control interface

Page 28: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 28

M102-M

Fig. 17 Control circuit for Autotransformer starter

NR-SOFTSTARTER (M102-M Only) Softstarter applications are for controlling motor accessory softstarter device. M102-M gives start and stop commands to the softstarter unit. The softstarter is set for adjusting motor voltage with it’s own parameters. More information about softstarter can be found from softstarter’s manual.

This starter type supports all protection functions during normal “Running” situation. For motor start and stop period some of the protection functions are disabled by these parameters.

Name Pin Description

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

F_Ca X1:7 Contactor control A feedback

LOC/R X1:6 Local/remote control switch input Table 22 NR_Softstarter starter contactor control interface

M102-M

softstarterKA

Page 29: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Functionality

1TNC911112D0204

29

Fig. 18 Control circuit for NR-softstarter

REV-Softstarter (M102-M Only) This starter is of similar functionality as NR-softstarter starter with additional function on supporting reversing motor.

Name Pin Description

CCLI X4:6 Contactor control voltage input

CCA X4:7 Contactor control A

CCB X4:8 Contactor control B

CCC X4:9 Contactor control C

F_Ca X1:7 Contactor control A feedback

F_Cb X1:8 Contactor control B feedback

LOC/R X1:6 Local/remote control switch input Table 23 REV-softstarter starter contactor control interface

softstarter

M102-M

Fig. 19 Control circuit for REV-Softstarter

Feeder ‘Feeder’ mode is regarded in M10x as a specific starter type to provide measurement and control functionality. The protection of feeder is not covered in M10x and is normally done by main circuit breaker. The ‘feeder’ mode in M10x is designed to provide a complete intelligent solution in MCC plant where the feeder circuits are usually small but important parts from the whole MCC plant management point of view.

Name Pin Description

Page 30: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 30

CCLI X4:6 Contactor control voltage input

CCA X4:7 Control YC /motor drive in MCCB (2 seconds holding)

CCB X4:8 Control YO/motor drive in MCCB (2 seconds holding)

F_Ca X1:5 Circuit breaker position aux. feedback *

MCCB Trip Input X1:11 Circuit breaker trip aux. feedback * Table 24-1 Feeder control interface(for M101-M)

Name Pin Description

CCLI X4:6 Contactor control voltage input

CCA X4:7 Control YC /motor drive in MCCB (2 seconds holding)

CCB X4:8 Control YO/motor drive in MCCB (2 seconds holding)

F_Ca X1:7 Circuit breaker position aux. feedback *

MCCB Trip Input X1:11 Circuit breaker trip aux. feedback * Table 24-2 Feeder control interface(for M102-M

M101/102-M

Fig. 20 Control circuit for Feeder

Feeder application in M10x is confined to certain features. End user needs to be informed on these confines when feeder application is required through M10x.

Page 31: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Functionality

1TNC911112D0204

31

Fig. 21a MD2 Faceplate for Feeder Application

Wirings:-

Wiring of feeder application in M10x is through predefined inputs.

CB status auxiliary is wired through Contactor Feedback A (C_Fa) input.

CB ‘General Trip’ contact is wired through ‘MCCB Trip Input’. In M10x-M, ‘MCCB Trip Input’ is predefined to Programmable Input 1, i.e. terminal X1.11. In M10x-P, it is wired to the digital input which is defined as ‘ MCCB Trip Input’.

Control Features:-

‘Close’ command activates contactor output relay CCA for 2 seconds.

‘Open’ command activates contactor output relay CCB for 2 seconds.

‘Reset’ command clear fault annunciation after fault is cleared. Supervisory Features:-

CB status

CB trip- ‘cause of trip’ message shown on MDx

Com- ‘ cause of alarm: serial com’ or ‘ cause of trip: serial com’ displayed on MDx in

the case of communication failure.

Protection:-

No protection function is designed for feeders application!

Measuring:-

Current, Voltage are measured by M10x. Power, energy and other parameters related to Power factor are NOT correct and should not be refer to!

Protection Function The module provides full protection for motor by supervising three phases voltage, three phases current, earth fault current, PTC sensor, the state of contactors and the state of main switch.

Page 32: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 32

Responding of protection functions is based on the parameters given by user. The operation of separate functions is independent thus protection functions can be active at the same time but the one which indicates the situation first initiate a trip/alarm.

Varies on different applications, protection functions can be activated or deactivated by the upper level system or through parametering tool. Protection characteristics can be adjusted in the same way.

Protection type M101-M M102-M

Thermal overload protection

Stall protection

Phase failure protection

Unbalance protection

Underload protection

Noload protection

Earth fault protection

PTC protection

Undervoltage protection

Start limitation protection Table 24 Protection Functions in M10x-M

Thermal overload protection Thermal overload protection (TOL) protects the motor against overheating. The motor thermal condition is simulated by a calculation. The result of the calculation is stored in a thermal register and can be reported via operator panel or fieldbus interface.

Calculation is accomplished in a different motor operation conditions, principle presented below, thermal increase and decrease are simulated by TOL protection function for running and stopped motor.

Fig. 21 Principle Fig. of motor thermal simulation

M10x-M simulates thermal conditions in the motor for all operating modes ( Running or Stopped) . This permits maximum utilization of an installation and assures safe protection of the

Page 33: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Functionality

1TNC911112D0204

33

motor. Thermal overload protection simulation accounts for the temperature rise of both the stator winding and the iron mass of the motor, it gives thorough consideration on the effect of motor overheating due to three phase unbalance during the simulation calculation of motor thermal overload.

There are two thermal models supported by M102-M: Standard or EEx e, but M101-M only supports Standard thermal model. The standard model makes use of parameters Trip class, t6 in thermal overload calculation. The protection of explosion proof three-phase motors with type of protection ‘increased safety’ EEx e is done with two special parameters, the Ia/In ratio ( stall/nominal current ratio ) and Te time.

The following diagram offers the characteristic curve of overload protection, in which the character is adjusted by changing t6( trip time for current ILmax=6 In from the cold state).

Fig. 22 Trip curve from cold condition

The Maximum thermal capacity level is 100%. Maximum level is reached when motor as been running with a current 6xIn at the time t6 starting from the cold state in ambient temp. 40 C

Trip class T6

10A 3-7

10 7-12

20 10-25

30 15-38 Table 25 IEC 60947-4-1 trip class when ambient temp. 40 C, balanced motor current

In some applications it is beneficial to be able to bypass the TOL protection momentarily because of the process reasons. The lifetime of the motor will be shortened but it will be more costly to stop the process. TOL-bypass is a special command given through the fieldbus.

Page 34: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 34

There is a dedicated parameter to enable the execution of this command. TOL-bypass function is available only inTOL standard model, thus it cannot be enabled if TOL EEx e model is in use.

When thermal level is above parameterised alarm level there is a possibility to send a bypass command to M10x-M. When bypass function is activated, the thermal image is allowed to rise to 200% level before a trip will occur.

If motor is in overload condition, i.e. ILmax > 1,14 x TFLC (Thermal full load current multiplier reduced by motor ambient temperature), the Overload alarm is active to indicate overload, but time to trip is not updated if the thermal capacity level ( ) is not going to rise above 200% (ITOL < 2). If motor is stopped before trip and the thermal capacity decreases below TOL alarm level the bypass functionality is disabled.

Bypass command is ignored when running under alarm level.

Function Enable/Disable

Setting range 0=Disabled 1=Enabled

Default value Enabled

Step value 1

Thermal model

Setting range 0=Standard model 1=EEX e

Default value 0

Step value 1

T6

Setting range 3-40s

Default value 6s

Step value 1

Ia/In

Setting range 1.2-8.0

Default value 5.0

Step value 0.1

Te

Setting range 1-250s

Default value 5s

Step value 1s

Cool coe.

Setting range 1-10

Default value 4

Step value 1

TOL Alarm Level

Page 35: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Functionality

1TNC911112D0204

35

Setting range 60-100%

Default value 90%

Step value 1%

TOL Trip Level

Setting range 60-100%

Default value 100%

Step value 1%

TOL Reset Level

Setting range 10-60%

Default value 50%

Step value 1%

Trip Reset Mode

Setting range 1=.Auto 2=Local 3=Remote 4=Remote&Local

Default value 4

Step value 1

TOL bypass

Setting range 0=Disable 1=Enable

Default value Disable

Ambient Temperature

Setting range 0-80 C

Default value 40 C

Step value 5 C Table 26 TOL protection parameters

When Standard thermal model is selected

When thermal models is selected

EExe thermal model is NOT supported in M101-M.

Stall Protection Stall protection is used to protect the driven mechanical system from jams and excessive overload. Stall protection function uses Imax as the criterion. There are other parameters to be determined as followed.

Function Enable/Disable

Setting range 0=Disable 1=Enable

Default value 1

Step value 1

Page 36: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 36

Trip Level

Setting range 120-800%

Default value 400%

Step value 10%

Trip Delay

Setting range 0.0-25.0s

Default value 0.5s

Step value 0.1s

Trip Reset Mode

Setting range 2=Local 3=Remote 4=Remote&Local

Default value 4

Step value 1

Table 27 Stall protection parameters

I N

t

I Lmax

Trip Delay

Trip

Startup current Trip Level

Startup Function activated Fig. 23 Stall protection

Stall function activates after motor nominal startup time elapsed.

The highest measured phase current (ILmax) is compared against the Trip level. When ILmax remains over the trip level at a time longer than Trip delay, a “Stall trip” alarm is issued and the contactor tripped.

Phase failure protection M10x-M protects the motor against phase current loss condition. Phase failure protection function uses ILmin/ILmax (the ratio of lowest ILmin and highest measured phase value ILmax ) as the criterion. Function is suppressed by parameters Motor startup time, Number of phases and Softstart ramp time.

Function Enable/Disable

Setting range 0=Disabled 1=Enabled 3=Alarm only

Default value Disabled

Page 37: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Functionality

1TNC911112D0204

37

Step value 1

Alarm Level

Setting range 10-90%

Default value 80%

Step value 1%

Trip Level

Setting range 5-90%

Default value 70%

Step value 1%

Trip Delay

Setting range 0-60s

Default value 10s

Step value 1s

Trip Reset Mode

Setting range 2=Local 3=Remote 4=Remote&Local

Default value 4

Step value 1

Table 28 Phase failure parameters

1. alarm 2. start trip delay 3. clear trip delay 4. start trip delay

5. trip 6. trip reset

Alarm level

Trip level

1.

(I LMIN / I LMAX )

t

Trip delay

2. 3. 4. 5. 6.

Fig. 24 Phase failure protection

ILmin/ILmax is compared against the phase failure Alarm level. When ILmin/ILmax decreases below the Alarm level, a “Phase failure alarm” alarm is issued.

ILmin/ILmax is compared against the phase failure Trip level. When ILmin/ILmax remains below the Trip level at a time longer the Trip delay, a “Phase failure trip” alarm is issued and the contactor tripped.

Unbalance protection

Page 38: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 38

M10x-M protects the motor against unbalance condition. Unbalance protection function also uses ILmin/ILmax as the criterion. Function is suppressed by parameters Motor startup time, Number of phases and softstart ramp time.

Function Enable/Disable

Setting range 0=Disabled 1=Enabled 3=Alarm only

Default value Disabled

Step value 1

Alarm Level

Setting range 50-90%

Default value 90%

Step value 1%

Trip Level

Setting range 50-90%

Default value 85%

Step value 1%

Trip Delay

Setting range 0-60s

Default value 10s

Step value 1s

Trip Reset Mode

Setting range 2=Local 3=Remote 4=Remote&Local

Default value 4

Step value 1 Table 29 Unbalance protection parameters

1. alarm 2. start trip delay 3. clear trip delay 4. start trip delay

5. trip 6. trip reset

Alarm level

Trip level

1.

(I LMIN / I LMAX )

t

Trip delay

2. 3. 4. 5. 6.

Fig. 25 Unbalance protection

Page 39: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Functionality

1TNC911112D0204

39

ILmin/ILmax is compared against the unbalance Alarm level. When ILmin/ILmax decreases below the Alarm level, a “Unbalance alarm” alarm is issued.

ILmin/ILmax is compared against the unbalance Trip level. When ILmin/ILmax remain below the Trip level at a time longer the Trip delay, an “Unbalance Trip” alarm is issued and the contactor tripped.

Underload protection M10x-M protects the motor against underload condition. Underload protection function uses ILmax/In ( the ratio of highest measured phase value ILmax and the rated current of the motor In ) as the criterion. There are other parameters to be determined, such as alarm level, trip level and trip delay. The protection characteristic is as follows:

Function Enable/Disable

Setting range 0=Disabled 1=Enabled 3=Alarm only

Default value Disabled

Step value 1

Alarm Level

Setting range 20-90%

Default value 30%

Step value 1%

Trip Level

Setting range 5-90%

Default value 20%

Step value 1%

Trip Delay

Setting range 0-1800s

Default value 10s

Step value 1s

Trip Reset Mode

Setting range 2=Local 3=Remote 4=Remote&Local

Default value 4

Step value 1

Table 30 Underload protection parameters

Page 40: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 40

Alarm level

1. warning 2. start trip delay 3. clear trip delay 4. start trip delay

5. trip 6. trip reset

Trip level

1 .

(I Lmax / I n )

t

Trip delay

2 .

3 .

4 .

5 .

6 .

Fig. 26 Underload protection

The ILmax/In is compared against the Underload Alarm level. When ILmax/In decreases below the Alarm level an “Underload alarm” alarm is issued.

The ILmax/In is compared against the Underload trip level. When ILmax/In remains below the Trip level at a time longer than underload Trip delay, a “ Underload trip” alarm is issued and the contactor tripped.

Noload protection M10x-M protects the motor against noload condition. Practically noload protection is the same function as underload protection. The function also uses ILmax/In as the criterion.

Function Enable/Disable

Setting range 0=Disabled 1=Enabled 3=Alarm only

Default value Disabled

Step value 1

Alarm Level

Setting range 5-50%

Default value 20%

Step value 1%

Trip Level

Setting range 5-50%

Default value 15%

Step value 1%

Trip Delay

Setting range 0-1800s

Default value 5s

Page 41: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Functionality

1TNC911112D0204

41

Step value 1s

Trip Reset Mode

Setting range 2=Local 3=Remote 4=Remote&Local

Default value 4

Step value 1 Table 31 Noload protection parameters

A la rm level

1. w arn ing 2. s tart trip de lay 3. c lear trip de lay 4. s tart trip de lay

5. trip 6. tr ip reset

Trip level

1 .

(I Lmax / I n )

t

Trip delay

2 .

3 .

4 .

5 .

6 .

Fig. 27 Noload protection

The ILmax/In is compared against the Noload Alarm level. When ILmax/In decreases below the Alarm level

an “Noload alarm” alarm is issued.

The ILmax/In is compared against the Noload trip level. When ILmax/In remains below the Trip level at a time longer than Noload Trip delay, a “Noload trip” alarm is issued and the contactor tripped.

Earth fault protection M10x-M protects the motor against the earth fault condition with an additional residual current transformer. The function is suppressed by parameters Motor startup time and Softstart ramp time.

Earth fault protection uses parameters as in the following table.

Function Enable/Disable

Setting range 0=Disabled 1=Enabled 3=Alarm only

Default value Disabled

Step value 1

Earth fault protection is activated during motor startup time

Setting range Setting range

Default value Default value

Step value Step value

Page 42: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 42

Alarm Level

Setting range 100-3000mA (Earth Fault Primary = 1A)

500-15000mA (Earth Fault Primary = 5A)

Default value 500mA

Step value 100mA

Trip Level

Setting range 100-3000mA (Earth Fault Primary = 1A)

500-15000mA (Earth Fault Primary = 5A)

Default value 800mA

Step value 100mA

Trip Delay

Setting range 0.2-60.0s

Default value 10.0s

Step value 0.1s

Trip Reset Mode

Setting range 2=Local 3=Remote 4=Remote&Local

Default value 4

Step value 1 Table 32 Earth fault protection parameters

Trip Delay

Trip Delay

Alarm Level

t

Trip Level

(I0)

Earth Fault Current Alarm

Earth Fault Current TripAlarm

Fig. 28 Earth fault protection

I0 is compared against the earth fault current fault Alarm level. When I0 exceeds above the Alarm level, an “Earth fault alarm” alarm is issued.

I0 is compared against the earth fault current Trip level. When I0 remains above the earth fault current Trip level at a time longer than Trip delay, an “Earth fault trip” alarm is issued and the contactor tripped.

PTC protection (M102-M Only)

Page 43: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Functionality

1TNC911112D0204

43

PTC protection protects the motor against too high temperature by using PTC-sensor embedded in the stator winding or the bearings. The measuring principle is the current measurement according the transmitters are supposed to be of the 3-wire type. Thus the circuit is independent of the cable-length limitations and the voltage drop in the cable. For M102, you can use a type A temperature sensor with a characteristic curve according to IEC 60947-8.

Function Enable/Disable

Setting range 0=Disabled 1=Enabled 3=Alarm only

Default value Disabled

Step value 1

Alarm Level

Setting range 1000-10000

Default value 1600

Step value

Trip Level

Setting range 1000-10000

Default value 3600

Step value

Trip Delay

Setting range 1-1800s

Default value 1s

Step value 1s

Reset Level

Setting range 100-10000

Default value 1600

Step value

Trip Reset Mode

Setting range 1=Auto 2=Local 3=Remote 4=Remote&Local

Default value 4

Step value 1 Table 33 PTC protection parameters

Page 44: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 44

t

Alarm Level

( )

PTC Temperature alarm

PTC trip

Trip delay

Alarm clear

Trip Level

Reset Level

Trip reset

Fig. 29 PTC protection

The resistance of PTC input is compared against the Alarm level. When resistance of PTC input exceeds above the Alarm level, a “PTC alarm” message is issued.

The resistance of the PTC input is compared against the Trip level. When resistance of PTC input is above the Trip level “PTC trip” alarm is issued and the contactor tripped.

After PTC trip is executed the resistance of PTC input is compared against the PTC reset level. When resistance of PTC input decreases below the reset level, the PTC protection function executes the function parametrised by “PTC Reset Mode”.

PTC short circuit protection is not supported in M10x.

Undervoltage protection (M102-M Only) M102-M protects the motor against undervoltage condition as “voltage dip”. The undervoltage protection function uses ULmin as the criterion. There are other parameters to be determined, such as alarm level, trip level and trip delay, reset voltage level. The protection characteristic is as follows:

3

Fig. 30 Undervoltage protection

The lowest measured main voltage (Ulmin) is compared against the undervoltage alarm level. When Ulmin decreases below the undervoltage alarm level, an “Undervoltage alarm” alarm is issued.

The lowest measured main voltage (Ulmin) is compared against the undervoltage Trip level and voltage restore level. When ULmin recovers above undervoltage Restore level before Trip delay

Page 45: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Functionality

1TNC911112D0204

45

expires and motor continues running. If ULmin remains below the restore level at a time longer than Trip delay, “ Undervoltage trip “ is issued and contactor will be opened.

When “Autorestart” function is active, “Autoreclose” time acts as the trip delay. “Undervoltage trip delay” setting is then ignored.

Function Enable/Disable

Setting range 0=Disabled 1=Enabled 3=Alarm only

Default value Disabled

Step value 1

Alarm Level

Setting range 50-100%

Default value 80%

Step value 1%

Trip Level

Setting range 50-100%

Default value 65%

Step value 1%

Trip Delay

Setting range 0.2-5.0s

Default value 1.0s

Step value 0.1s

Reset Level

Setting range 50-100%

Default value 90%

Step value 1%

Trip Reset Mode

Setting range 1=Auto 2=Local 3=Remote 4=Remote&Local

Default value 4

Step value 1 Table 34 Undervoltage protection parameters

Start limitation Start limitation helps to protect the motor and also the process against excess number of starts in a given interval. When the number of starts is reached and the motor is switched off, a new start is prevented. The time interval starts from the first start. After the elapse of the time interval the counter is reset to the pre-set value. The permissible motor starts per hour can be obtained from the manufacturers motor and apparatus data sheet. However, the minimum waiting time between two starts shall be complied.

Page 46: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 46

The parameterization of the protection function can be the number of starts per time interval or the time between two consecutive starts. In the first case the user must wait after the trip for the reset to take place before making a start.

Independent of this function, the motor is protected by TOL function and a start is possible only if the thermal capacity is below the startup inhibit level. If motor data specifies the number of starts during a certain time span the advantage of this protection function can be taken of supervising the number of starts. On some other cases process may put requirements for the motor start number thus this protection can be employed.

Functionality is presented in the following example. The next Fig., presents the start limitation protection with 3 starts allowed.

1) Normal situation, after stop command motor can be started normally, “Start 2”. Every start activates an internal timer for the time defined by time interval parameter. The number of active timers are reviewed after every stop command and compared to value of number of starts parameter. Stop command can thus exist during active or elapsed timer.

2) Two timers are still active, thus stop command generates alarm message "Start limitation alarm" and one more start is allowed, “Start 3”.

3) The 3rd start has been executed. A contactor trip and trip message "Start Limitation Trip" alarm will follow when motor is stopped while there are two active timers, here starting from “Start 1”.

4) Trip can be automatically reset when the first timer from “Start 1” is finished. Motor start is possible when all pending trips are reset. Supervision continues with a new timer from “Start 4”

Fig. 31 Start limitation protection

Function Enable/Disable

Setting range 0=Disable 1=Enable

Default value Disabled

Step value 1

Time interval

Page 47: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Functionality

1TNC911112D0204

47

Setting range 1-600min

Default value 1min

Step value 1

Number of starts

Setting range 2-100

Default value 2

Step value 1

Table 35 Start limitation parameters

Page 48: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 48

Function and Supervision Autorestart (M102-M Only) The phase voltage (Ua) is supervised continuously. It is possible to automatically restart the motor after momentary power loss. Two alternative models of auto restart function are provided in M102-M: Standard and enhanced.

M101-M does not support autorestart function

Function Enable/Disable

Setting range 0=Disabled 1=Enabled

Default value Disabled

Step value 1

Function mode

Setting range 0=standard 1=enhanced

Default value 0

Step value 1

Max. autoreclose time

Setting range 100-5000ms

Default value 200ms

Step value 100ms

Max. power down time

Setting range 0-1200s

Default value 5s

Step value 1s

Staggered start delay

Setting range 0-1200s

Default value 5s

Step value 1s

Table 36 Autorestart function parameters

Auto restart function (standard) In standard mode, the reaction of the auto restart function depends on the length of the voltage dip.The following cases show the different reactions of M102-M in different voltage dip situations.

Case 1: Voltage dip< autoreclose time

Page 49: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Functionality

1TNC911112D0204

49

Fig. 32 Autorestart (Voltage dip< autoreclose time)

If voltage is restored within autoreclose time, motor restarts immediately.

Case 2: autoreclose time<voltage dip< Max. power down time

Fig. 33 Autorestart (autoreclose time<voltage dip< Max. power down time)

If power is restored after autoreclose time but before max power down time, motor will be restarted after the staggered start delay time.

Page 50: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 50

Case 3: Voltage dip> Max. power down time

Fig. 34 Restart (Voltage dip> Max. power down time)

If supply voltage remains below restore level long enough and exceeds max power down time, no automatic restart will be initiated.

Auto restart function (enhanced) If the voltage dip is taken more serious, the enhanced autorestart function can be applied.

In the enhanced mode, the reaction of the auto restart function not only depends on the length of the voltage dip, but also the number of voltage dips within short period of time.

The following cases show the different reactions of M102-M in different voltage dip situations.

Case1: Voltage dip< autoreclose time

Identical to Case1 of standard mode

Case2: autoreclose time<voltage dip< Max. power down time

Identical to Case2 of standard mode

Case3: Voltage dip> Max. power down time

Identical to Case3 of standard mode

Case4: 2xdip<200ms within 1s

Page 51: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Functionality

1TNC911112D0204

51

Fig. 35 Restart (2xdip<200ms within 1s)

If the interval between two voltage dips (which length less than 200ms ) is less than 1 second. Automatic delay restart is triggered after second voltage restore.

Number of Starts M10x-M counts number of start. For each operation cycle M10x-M updates the number of operating cycle in memory map. When start number alarm level is exceeded, M10x-M issues an alarm.

Motor Running Time M10x-M counts motors running hours. When operating running hours limit will be crossed M10x-M issues an “running time” alarm.

Failsafe Functionality M10x-M failsafe function supervises the network interface and connection to the remote devices controlling the motor/starter equipment by M10x-M. Remote device have to refresh the certain M10x-M network input variable to indicate that the control is operating normally and the network interface is in good condition.

When M10x detects loss of communications, failsafe mode will be switched on automatically and corresponding operations will be followed as per parameters settings, i.e.

No operation

Start motor direction 1

Start motor direction 2

Stop motor

Besides, control access to motor will be switched to/remain in local control (hardwire control) and MD control while ignoring previous control access settings. When the communication restore, the control access will recover to the original setting.

Page 52: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 52

Time Synchronization The last alarm, trip and operation message generated by the M10x-M are with time-tag, which is based on the synchronized absolute system time.

M10x-M supports message-based time synchronization. Whenever receiving time synchronization message, M10x-M synchronizes its internal clock with new absolute time received in the message.

M10x-P Control Authority Control Authority M10x Control Authority is the term describing the privileges on allowing motor control operation through M10x. It is also a setting parameter in M10x to define which control access group has privilege to operate the motor via M10x.

Control Access There are three control access groups defined in M10x,

Local Hardwiring:- M10x accepts its commands from the hardwired inputs

Remote Fieldbus:-M10x accepts its commands from PLC or higher control system viia fieldbus. i.e. Modbus or PROFIBUS.

MDx Control:- M10x accepts its commands from operator panel MDx which locates on the front panel of each starter unit on switchgear.

Assign Control Authority There are several means in M10x to assign control authority and decide which control access group has the privilege to control.

Parameter Setting: Select the access group from parameter setting window (Fig 36a). This is the most direct means where control access is defined by parameterization software.

Page 53: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Functionality

1TNC911112D0204

53

Fig. 36a Parameter Setting of Control Authority

Multi control access group is supported!

Local/Remote Selector Switch: M10x supports hardwired local remote selector switch function which allows selecting control access groups via hardwired inputs. Local/Remote option has to be enabled as shown in Fig36b in this application. Local/Remote Selector Switch wiring is via predefined digital inputs. Please refer to Fig 5 & 6 for detail wiring.

Fig. 36b Enable “Local/Remote” function

Page 54: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 54

Local/Remote Selector Switch will then define if control access goes to “Local “(Local Hardwired ) or “Remote” (Remote Fieldbus). This function does not include the selection of operator panel MDx control which is independent of either “Local” or “Remote” and has to be further defined in this case.

Loc/R Selector Switch Input

Control Authority

Local Hardwiring Remote Fieldbus MDx Enabled in

Local MDx Enabled in Remote

False (open input) Disabled Enabled Disabled Enabled

True (close input) Enabled Disabled Enabled Disabled

Fig. 36c “Local/Remote” Selector Switch

There are also two ways of defining MDx control access when Local/Remote selector switch function is enabled, i.e. through “parameter setting” in parameterization software or through hardwired input.

Parameter Setting (Fig 36b)

Hardwired Input,

Use external selector switch to select MDx control. One of the programmable inputs has to be defined as ‘MD Control” to enable the function.

Fig. 36d “MD Control” Selector Switch

When “Loc/R” is enabled (via predefined input, refer to Fig5&6), the control access group options under ‘Control Authority” tab (Fig36b) are limited to

“MD” only. Same as in selecting MDx control. When “ MDx control” is enabled in one of the DIs, the MD control access option under “Control Authority” tab will be gray out.

Page 55: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Functionality

1TNC911112D0204

55

In another word, Hardwired Selection has privilege over Parameter Setting Selection in terms of assigning control authority. Main Switch Status (M102-M Only Only) Main switch input (MCB) indicates the status of main switch.

There is no direct main switch input in M101-M. It can be configured through one of the programmable inputs if required.

Programmable Inputs There are three separate programmable inputs in M10x-M. These three inputs can be assigned any of the functions listed below.

Programmable inputs can be used to:

Start1 To use start1 function, local control authority must be enabled.

The start1 input is used to start motor via hardwire. Motor can be running CW/N1 via Start1. This input works in edge triggering mode.

Start 2 To use start2 function, local control authority must be enabled.

The start2 input is used to start motor via hardwire. Motor can be running CCW/N2 via Start2. This input works in edge triggering mode.

Stop To use stop function, local control authority must be enabled.

The stop input is used to stop motor via hardwire. This input works in edge triggering mode.

Process interlock1 The process interlock1 input is used to provide time dependent trip/alarm/stop features based on a switch input. This function is used together with Operation Delay and Operation parameters.

The parameter of Operation Delay sets the amount of time that the Process interlock1 switch can remain inactive on the occurrence of a motor start. If the switch remains inactive for longer than this time, a trip/stop will occur. If there is valid active process interlock1 input detected in the defined operation delay, motor will keep running. And after the operation delay time, the inactive status of process interlock1 input will not affect the running of motor. If the parameter of Operation Delay is set to 0, that the process interlock1 switch must be active while motor is started, which means motor start will not be allowed if the input is inactive.

The parameter of Operation determines whether process interlock1 feature is a trip (reset required in order to restart the motor), a stop (no reset required) or an alarm.

This input works in level check mode.

Page 56: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 56

Case 1: when t1>t2, motor can run normally;

Case 2: when t1<t2, a trip or stop will be performed according to the predefined operation.

Process interlock2 Process interlock2 function is used to provide time dependent trip/alarm/stop features based on a switch input. This function is used together with OPERATION DELAY and OPERATION parameters.

The parameter of OPERATION DELAY sets the amount of time that the process interlock2 switch can be remain active when motor is in running. If the switch remains active for longer than this time, a trip/stop will occur. . If the parameter of OPERATION DELAY is set to 0, that the process interlock2 switch must be inactive while motor is started, which means motor start will not be allowed if the input is active.

OPERATION: this parameter determines whether process interlock feature is a trip (reset required in order to restart the motor), a stop (no reset required) or an alarm.

This input works in level check mode.

Page 57: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Functionality

1TNC911112D0204

57

Case 1: when t1>t2, motor can run normally;

Case 2: when t1<t2, a trip or stop will be performed according to the predefined operation.

Test Switch This input is used to indicate whether the main switch is in the test-position. While in test position, M10x monitors the I/O status and phase current will be zero. Contactor operations by M10x are allowed but all protection functions based on the current and voltage measurement are disabled and the test of control circuit is allowed.

If the current is detected nonzero, all protection functions defined enabled in parameter setting would be enabled automatically. It’s for protecting motor in the case of test switch input is out of work.

This input works in level check mode.

ESD Input (Emergency stop) The emergency stop input is used for the emergency stop device. When the input is active, the motor will be stopped and can’t be restarted until the input is inactive. This input works in level check mode that is different from “Stop” function.

PLC Contact1 To use PLC contact1 function, local hardwiring control authority must be enabled.

M10x accepts the commands from PLC to control motor when programmable DI is configured as ‘PLC Contact1’. This input works in edge triggering mode. When the digital input is detected rising edge triggering, the motor runs CW/N1. When the digital input is detected falling edge triggering, the motor stops.

PLC Contact2 To use PLC contact2 function, local hardwiring control authority must be enabled.

Page 58: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 58

M10x accepts the commands from PLC to control motor when programmable DI is configured as ‘PLC Contact2’. This input works in edge triggering mode. When the digital input is detected rising edge triggering, the motor runs CCW/N2. When the digital input is detected falling edge triggering, the motor stops.

Trip Reset The trip reset input is used to reset trip after trip occur.

This input works in edge triggering mode.

Torque Switch Input The input is used to check the status of torque switch used for Actuator Starter. When the input is different from normal state, M10x-M will release all contactor control relays to stop the motor. This input works in level check mode.

NOP No special operation for the NOP function, only for the check of digital input status. This input can be used as status transfer of digital input. This input works in level check mode.

MD Control It will decide whether the control command from MD is active or not. When one of DIs is assigned for ‘MD Control’, the control authority of MD will not be changed via parameterization but relying on the input status of the DI. If the input status is active, motor can be controlled via MD. Whereas the control command from MD is inactive.

This input works in level check mode.

Programmable Outputs M101-M has one and M102-M has tow programmable relays output. These outputs can be assigned any of the functions listed below.

Energize on Motor Start Delay : Provides a delayed energization of relay when motor is started.

De-energize on Motor Stop Delay: Provides a delayed de-energization of relay when motor is stopped.

Fieldbus Control: The relay can be energized or de-energized via the serial port.

Interlock0: The relay will energize while the programmable input 0 switch is closed

Interlock1: The relay will energize while the programmable input 1 switch is closed

Interlock2: The relay will energize while the programmable input 2 switch is closed

Page 59: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Functionality

1TNC911112D0204

59

Trips: The relay is energized when there is no trip. When a trip occurs, the relay will be de-energized.

Resetting M10x-M will energize the relay.

Ground Fault Trip: The relay is energized when no ground fault trip occurs. When ground fault trip occurs, the relay will

be de-energized. Resetting M10x-M will energize the relay.

TOL: The relay is energized when no thermal overload trip occurs. When thermal overload trip occurs, the relay will be de-energized. Resetting M10x-M will energize the relay.

Watchdog Output: M10x-M has an internal hardware watchdog supervising the behavior of the microprocessor software. Programmable output can be used as signaling output relay for indicating the status of the unit’s internal watchdog. In case of fault the watchdog activates and the relay is energized.

Communication Failure: The relay is energized when no communication failure occurs. When the failure occurs, the relay will be de-energized.

RCU Mode (M101-M Only): This definition is assigned to the programmable out when ‘NR DOL/RCU ‘ or ‘REV DOL/RCU' is selected as motor starter mode. The relay output serves the same function of ‘ de-energized the contactor coil’ as ‘CCC’ output in M102.

Local Remote Output: The relay is energized when the control authority is Remote only .The relay will be de-energized when the control authority is Local and Remote or Local only.

Metering The M10x-M meters and displays:

RMS current

RMS voltage (M102-M Only)

Ground fault current

Frequency (M102-M Only)

Power factor (M102-M Only)

Power (M102-M Only)

Energy (M102-M Only)

Page 60: ABB LV SWITCHGEAR M10x-M User's Guide

Functionality M10x-M User's Guide

1TNC911112D0204 60

Communication Interface

Overview The physical fieldbus interface inM10x-M is RS485. There are two identical RS485 interfaces built in M10x-M to support full redundancy network design.

The M10x-M implements a subset of the Modicon Modbus RTU serial communication standard. Modbus is a single master/multiple slave type of protocol suitable for a multi drop configuration as provided by RS485 hardware. The M10x-M is always a Modbus slave. They could not be programmed as Modbus masters. Commonly computers or PLCs are acted as masters.

Both monitoring and control are possible using read and write register commands. Other commands are supported to provide additional functions.

RS485 Interface Cable All devices are connected in bus structure. In one segment up to 32 modules can be connected. At the beginning and the end of one segment, the cable is terminated with resistor. The maximum length depends on cable type and baud-rate.

Function Description The following functions are supported by the M10x-M:

FUNCTION CODE 02H - Read Settings and Actual Values

FUNCTION CODE 03H - Read Settings and Actual Values

FUNCTION CODE 04H - Read Settings and Actual Values

FUNCTION CODE 05H - Execute Operation

FUNCTION CODE 06H - Store Single Setting

FUNCTION CODE 08H – Loop Back Test

FUNCTION CODE 10H - Store Multiple Settings

For more information on Modbus implementation in M10x-M, please refer to separate document “ 1TNC 911505 M0204 Modbus Protocol Implementation for M10x-M”.

Page 61: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Communication Interface

1TNC911112D0204

61

Parameterization

Overview Parameterization means entering values to M10x-M parameters. Before integrated in a system, the parameters of communication should be set correctly only via the parameterization interface on operator panel.

M10x-M parameters can be uploaded by and downloaded via the parameterization device.

Parameterization via MD2/MD3 There is a USB-Pin physical interface on MD2 or MD3, which is for parameterization via a laptop.

Parameterization via MODBUS M10x-M parameters are listed in the MODBUS memory map. The user can parameterize M10x-M by using Function code 06H/10H. For detail information, refer to the MODBUS Protocol Implementation for M10x-M document.

M10x-M Parameters M10x-M Parameters are listed together with explanations, possible ranges and default values in separate document “1TNC 911105 M0203 M10x-M Parameter Description ’’.

Page 62: ABB LV SWITCHGEAR M10x-M User's Guide

Accessories M10x-M User's Guide

1TNC911112D0204 62

Accessories

MD2/MD3 Operator Panel Overview You can use the MD2/MD3 operator panel to control a motor from the control-cubicle door or from a drawer. You can use additional pushbutton functions and LED displays as alternatives. There are also more message available on a LCD display unit (MD2 only).

The operator panel can be connected to the M10x-M basic unit via a RS485 communication port ( which physical interface is RJ11 ) . It is supplied with power from the basic unit also via RJ11 interface.

The faceplate of operator panel are shown below

Fig. 36 MD2

Fig. 37 MD3

Page 63: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Accessories

1TNC911112D0204

63

LED indicator

LED Indicator State Description

READY

On Unit is ready for operation

Blinking Unit is yet not initialized

START1 On Motor is running CW/N1

START2 On Motor is running CCW/N2

FAULT

On Fault trip

Blinking Alarm

Table 37 LED indicator

Buttons

Button Function

Window Scoll

To Start motor CW/N1

To start motor CCW/N2

Stop/Reset

Table 38 MD2/3 Buttons

Actual value display

Ia 1.78A Ib 1.79A

Ic 1.77A

This message displays the actual RMS current in each phase in amps

Format: 1.00 at CT primary 1A

10.0 at CT primary 50A

100 at CT primary>50A

Ia/In 25% Ib/In 25%

This message displays the curret as a percentage of motor nominal current.

Page 64: ABB LV SWITCHGEAR M10x-M User's Guide

Accessories M10x-M User's Guide

1TNC911112D0204 64

Ua 219V Ub 220V

This message displays L-N voltage.

Note: M101-M can’t measurer voltage

Uab 379V Ubc 380V

This message displays L-L voltage.

Note: M101-M can’t measurer voltage

S 145KVA P 141KW COSØ 0.97

This messge displays apparent power, active power and power factor.

Note: M101-M can’t measure S,P,COSø

Energy used 12345 kWhr

This message displays the total accumulated energy used since last cleared.

Ground current 0mA

This message displays ground fault current.

Frequency 49.98Hz

This message displays the frequency of power supply.

Note: M101-M can’t measure frequency

Therm Capacity : 53%

This message displays the thermal memory of the motor. The max thermal capacity is 100%. A thermal capacity value equal to Trip level will cause overload trip.

Cause of Trip: Overload

This message displays the cause of the current trip. The cause of trip message will override the currently selected default message. The possible causes of trip are:

TOL Stalled rotor

Phase failure Unbalance

Underload Noload

Earth fault PTC

Undervoltage Feedback

Prog. IN0 Prog. IN1

Prog. IN2 Serial COM

Start limitation

Page 65: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Accessories

1TNC911112D0204

65

Parameterization port The parameterization port is a USB-pin interface. After communication plug is inserted, the communication between the M10x-M and operator panel is terminated. The message on LCD shows the parameterization state, and the functions of buttons are invalid.

M10x-M parameters can be upload and downloaded from the parameterization device via the interface.

Connection Operator panel is connected to the X2 terminal on M10x-M via RJ11 interface. The connection shown below includes power supply and communication.

Cause of Alarm: Overload

Any alarm conditions that are currently active will be display. The cause of alarm message will override the currently selected default message. The possible causes of alarm are:

Overload Thermal capacity

Phase failure Unbalance

Underload Noload

Earth fault Welded

Feedback Fail to stop

Fail to start Serial COM

Start limitation Start number

Running time Prog. IN1

Prog. IN0 Prog. IN2

PTC (only inM102-M)

Addr. 3 M102-M v2.0 MD v2.0

This message displays network ID, Firmware version of the M10x-M and MD2 after pressing the select key for 5 seconds. (Only MD2 v2.0 or above supported this function)

Parameter setting

Page 66: ABB LV SWITCHGEAR M10x-M User's Guide

Accessories M10x-M User's Guide

1TNC911112D0204 66

Fig. 38 Connection between M10x-M and MD2/3

If MD2 can’t get information from M10x-P, “No Message” will be shown in LCD the window.

Parameterization Software: MCUsetup MCUsetup software is used to set parameter. It exchanges data with M10x-M via RS485.

Fig. 39 Parameterization interface

No message

Page 67: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Accessories

1TNC911112D0204

67

Fig. 40 MCUSetup interface

The parameterization software available with following function:

Edit parameters

Export parameter to a file

Import parameter from a file

Update M10x-M’s parameters

Download M10x-M’s parameters

Read M10x-M’s parameters

Page 68: ABB LV SWITCHGEAR M10x-M User's Guide

Accessories M10x-M User's Guide

1TNC911112D0204 68

User management

The parameterization software can run on all of the following PC operation system:

Windows 2000, Windows XP and Win 7.

For more information on how to do the parameter setting through MCUSetup software, please

refer to separate document “1TNC911104M0202 MCUSetup (Software Tool) User Guide“

Page 69: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Appendix A Technical Data

1TNC911112D0204

69

Appendix A Technical Data Technical data

Main circuit Rated operation voltage (Ue) 230/400V or 400/690V

Rated insulation voltage (Ui) 690V

Rated impulse withstand voltage (Uimp) 6kV

Degree of pollution 3

Rated operation current (Ie) 0.5-1A 1-2.5A 2.5-5A

5-12.5A 12.5-30A 30-63A

Rated frequency 50/60Hz

Control circuit Rated operational voltage (Ue) 24V DC or 230 VAC

Rated insulation voltage (Ui) - or 250V

Rate impulse withstand voltage (Uimp) - or 4 kV

Rated operational current (Ie)

Contactor Control relay output 2A (DC-13)

2A (AC-15)

Programmable relay output 2A (DC-13)

2A (AC-15)

Rated frequency 50/60 Hz

DC Power supply Rated operational voltage (Ue) 24VDC

Voltage operation range 85%-110% Ue

DC Power consumption Typical 4.5W

Maxium 8W

Maximum starting current 600mA

Digital input Number of digital input 6(M101-M) / 13(M102-M)

Close contact current (peak) 2.5…5mA

Open contactor current (peak) 0…0.8 mA

Page 70: ABB LV SWITCHGEAR M10x-M User's Guide

Appendix A Technical Data M10x-M User's Guide

1TNC911112D0204 70

Filedbus interface Protocol Modbus RTU

Baud-rate 1200/4800/9600/19200 bps

Fieldbus capacity 32

Environmental conditions Storage -25-+85

Normal operation -5-+60

Humidity 15% up to 95% without dew

EMC Environment 1) Equipments in the system comply with EMC requirement of CE / CCC certificate.

2) Power supply system complies with IEC61000-2-1, IEC61000-2-2, especially the system in which VSD / Frequency Converters are used.

Metering accuracy Phase current Range: 0.1-8 ×phase CT primary amps

Accuracy: ±(2%+1)

Earth fault current Full scale: 1.2 × RCT nominal current

Accuracy: ±2% RCT primary

Phase voltage (M102-M Only) Voltage metering range: 110V-440V

Accuracy: ±2%

Power (M102-M Only) Accuracy: ±5% nominal or ±5% reading, whichever is greater

Thermistor Input (M102-M Only) Sensor type: positive temperature coefficient PTC RHOT=100-10,000

Accuracy: ±5% or 100 which is greater

Standards

Low voltage switchgears IEC60947-1 Low voltage switchgear and controlgear”

Part1: General rules IEC60947-4-1 Low voltage switchgear and controlgear”

Part4: Contactors and motor-starters, Section one-Electromechanical contactors and motor-starters

Page 71: ABB LV SWITCHGEAR M10x-M User's Guide

M10x-M User's Guide Appendix A Technical Data

1TNC911112D0204

71

EMC Electrostatic discharge IEC61000-4-2, Level 3

Electromagnetic field immunity IEC61000-4-3, Level 3

Electrical fast transient/burst immunity IEC61000-4-4, Level 4

Surge immunity IEC61000-4-5, Level 3

Conducted disturbance immunity IEC61000-4-6, Level 2

Radiated disturbance EN55011, Class A

i) Precautious measures shall be taken in system designs to avoid potential high electromagnetic disturbance which may result in unstable network and malfunction of M10x relays. For example, in applications that Variable Speed Drives are used in a large scale, harmonic filter devices shall be required in system design to reduce the

impact to the network.

ii) Surge Suppressors are required to use with contactor coils to limit high pre-damping voltage frequencies.

Fig. 44 Surge Suppressors for Contactor Coils

Page 72: ABB LV SWITCHGEAR M10x-M User's Guide

Contact us ABB Low Voltage Systems Publication Editor: Xiamen ABB Low Voltage Equipment Co.,Ltd Fujian, China Local Contacts on www.abb.com

Copyright© 2010 ABB All rights reserved. Publication No. 1TNC911112D0204