ABB FOCS – Fiber-Optic Current Sensors
Data Sheet
ABB Switzerland LtdFiber-Optic Current SensorsDept. ATPR/FOCS AustrasseCH-5300 TurgiSwitzerland
Web: www.abb.com/powerelectronicsemail: [email protected] Tel: +41 - 58 - 589 39 39Fax: +41 - 58 - 589 30 00
© Copyright 2005 ABB. All rights reserved.Specifications are subject to change without notice. 3
B H S 2 0 9 6 0 3
Z A B E
0 1_
R E V
–
Physical Dimensions
• Sensor Electronics dimensions (W x H x D):
450 mm x 101 mm x 136 mm.• Sensor Electronics weight: 5 kg.
• Sensor fiber cable length
(Sensor Head to Sensor Electronics):
– 15 m standard cable
– Minimum length: 10 m
– Maximum length: 70 m.
• Sensor Head weight: <15 kg.
• Optional control cubicle dimensions
(W x H x D):
800 mm x 1000 mm x 300 mm. Sensor Head Type Code
Standard Sensor Head dimensions (other sizes
may be available)
Head-
Type
Code
B
out
[mm]
H
out
[mm]
B
max.
[mm]
H
max.
[mm]
C
Seg. hor.
[mm]
C
Seg. vert.
[mm]
H-1 855 855 441 441 105 105
H-2 1250 1250 836 836 500 500
H-3 1750 1250 1336 836 1000 500
H-4 1750 1750 1336 1336 1000 1000
H-5 2250 1750 1836 1336 1500 1000
H-6 2750 1750 2336 1336 2000 1000
H-7 3250 1750 2836 1336 2500 1000
Bout
Bmax
Chor
C v e r t
H o u t
H
m a x
Ordering Information
Product Name Ordering Type Code
Main
Type Code
Accessories
Type Code
Sensor Head
Type Code
ABB FOCS ABB FOCS-xxx-Lxx ASVn – PLn – PBmn – CCmnopq – PNLn Hx
Example: ABB FOCS-225-L18 ASV1 – PL0 – PB10 – CC11111 – PNL0 H3
focs_data_sheet.indd 12-1 25.01.2005 09:34:06
7/21/2019 abb focs data sheet sensor corriente.pdf
http://slidepdf.com/reader/full/abb-focs-data-sheet-sensor-corrientepdf 2/2
2 3
The new ABB FOCS Fiber-Optic Current
Sensor is a family of high accuracy sensors
for industrial high current measurement
applications based on the magneto-optic
effect.
ABB FOCS is available for uni- or bi-direc-
tional dc current measurement up to 500 kA.
With corresponding sensor head sizes, itoffers an easily installed, interference-free
alternative to the Hall effect current trans-
ducers.
Highlights
ABB FOCS is an unique fiber optic current
measurement device designed for simplified
installation, easy commissoning, increased
accuracy, and a digital signal for greatly enhan-
ced data acquisition management and negligi-
ble power consumption.
The Sensor Head is connected to the Sensor
Electronics via a glass sensor fiber cable. This
cable cannot be detached from the Sensor
Electronics.
All data conditioning and monitoring functions
provided by ABB FOCS, including scaling and
calibration, are designed and tested at works.
No software engineering is necessary on site.
ABB FOCS is delivered with standard firmware
installed and ready for operation.
SensorElectronics
Control Cubicle (optional)
Sensor Fiber
Cable
Current Carrying
Busbars
Sensor Head
Performance
• Measuring range: 0 to ± 500 kA (dependingon type), 20 % overcurrent capacity.
• Accuracy (1 to 120 % of rated current):
± 0.1 % of the measured value.
• Repeatability: ± 0.02 %.
• Linearity (1 to 120 % of rated current): ± 0.1 %.
• Sampling rate: 4 kHz.
• Temperature sensitivity: <± 0.002 % / °C.
Features
• Available in different standard dimensions,
according to the dimensions of the busbar
(see Physical Dimensions).
• Sensor Electronics galvanically separated
from Sensor Head and current busbar.
• Optional control cubicle with optional
Process Panel PP210.• Sensor Electronics mounted on standard DIN
rails.
• Two analog outputs corresponding to the
measured dc current with selectable combi-
nations:
– 0...20 mA and 0...1 V, unidirectional
– 4...20 mA and 0.2...1 V, unidirectional
– ± 20 mA and ± 1 V, bidirectional.
• Communication with external control
systems:
– ABB PowerLINK, used to interface the
Sensor Electronics with an AC 800PEC
controller by means of fiber optic cables.
Standard optical module UF D128 for plas-
tic optical fiber (POF) or optional optical
module UF D130 for glass optical fiber(GOF) can be used.
– PROFIBUS DP fieldbus (optional) to con-
nect the Sensor Electronics to any third
party external control system. The Sensor
Electronics operates as PROFIBUS DP
slave.
• Ah and kAh counter pulses: 100 Ampere-
hour and 1 kilo Ampere-hour pulses via
PROFIBUS and PowerLINK.
• DC-current protection
– Instantaneous overcurrent detection
– Inverse time overcurrent detection
– Reverse current detection.
• 3 status relays with changeover contacts.
Power Supply
• Redundant 24 Vdc input, –15 %, +20 %.
• Power consumption: <60 W.
Ambient Requirements
• Operating temperature
– Sensor Head: –40 to +80 °C.
– Sensor Electronics:
–25* to +65 °C (mounted in a cubicle with
forced air cooling)
–25* to +55 °C (with natural air
convection).
* With PROFIBUS module: min. temp. 0 °C.
• Storage temp.: –40 to +70 °C.
• Humidity: RH=5-95 % (compliance
with standard EN 61131-2).
• Pollution degree: Degree 2 (compliance withstandard IEC 60664).
• Altitude: ≤ 4000 m (compliance with
standard IEC 60068-2-13).
• Degree of protection
– Sensor Electronics: IP00, always to be
mounted in a control
cubicle
– Sensor Head: Not applicable, to be
protected against rain
and sunlight.
• Emitted noise: <55 dB (A).
Models and Ratings
Main Type Code
kA Type
20 ABB FOCS-20
30 ABB FOCS-30
45 ABB FOCS-45
60 ABB FOCS-60
80 ABB FOCS-80
100 ABB FOCS-100
130 ABB FOCS-130
155 ABB FOCS-155
180 ABB FOCS-180
225 ABB FOCS-225
260 ABB FOCS-260
300 ABB FOCS-300
350 ABB FOCS-350
400 ABB FOCS-400
450 ABB FOCS-450500 ABB FOCS-500
Measuring rangein kA
Length of sensorfiber cable inmeters (10–70 m)
AB B FOC S – 10 0 – L1 0
Accessories Type Code
ABB FOCS Measuring Principle
The sensor consists of a single-ended optical
fiber and the Sensor Electronics, including light
source, optical detection circuit and digital sig-nal processor. One sensing fiber loop is moun-
ted around the current carrying busbar.
The measured signal is independent of the par-
ticular busbar arrangement and insensitive to
magnetic stray fields from neighboring busbars.
The Sensor Electronics is galvanically isolated
from the Sensor Head and the busbars.
Auxiliary supply
0 24 Vdc from plant mains supply1 Variable (85 – 264 Vac, 47 – 65 Hz / 90 – 350 Vdc),
additional power supply2 Special on request
PowerLink
0 UF D128 (POF)1 UF D130 (GOF)
Profibus DP
00 None10 Slave module11 S lave module + OLM/P12 (POF)
12 S lave module + OLM/G12 (GOF)
AS Vn – PLn – PBm n – CCm nop q – PNL n
Wall mounted control cubicle
00000 None11111 Standard
Any 2 Customized
m ype o conro cu ce n Color for control cubicleo Lock type
p Size of control cubicleq Cable Entry
Process panel
0 None1 Process Panel 210
ABB FOCS Typical Layout
focs_data_sheet.indd 2-3 25.01.2005 09:34:18