engineering for a better world GEA Heat Exchangers
The future of high-performance air conditioning
GEA DENCO®-OfficeCool with HX-Factor
PR-2013-0008-GB · Subject to modification · K0-11/2013
26 °C High level, high temperature return air back to the Zone Unit to complete the cycle
Conditioned air under the floor12 – 16 °C
Energy savings
Quiet operation
Installation can be deferred until final build/let
Quick easy office modifications possible
Easy to design
Construction savings
No requirement for large plant rooms
[ 2 ]
PR-2013-0008-GB · Subject to modification · K0-11/2013
Occupants control their own local environment
depending on their needs
24 °C
Mixed air supply from LECU to room at low velocity
20 °C Quick installation
Individual control of local environment
Office space quickly and easily adapted for new occupants
System redundancy
Reduced “slab to slab” height
[ 3 ]
GEA Chillers
GEA Air Handling Units (AHUs)
BMS or GEA Standalone Control System
Zone UnitThe Zone Unit provides the primary air conditioning to its zone, with each zone
measuring up to 300 m2. Zone Units are drawn through vertical type, either top return
(ZD type) or bottom return (ZU type) supplying conditioned air into a raised floor void.
Zone Units have all necessary components such as filters, cooling coils, control valves,
microprocessor controllers, and inverter driven fan motors to achieve the required
underfloor condition with the maximum efficiencies. Options include heating (electrical,
low-pressure hot water, or direct expansion), and dehumidification and humidification
using water vapour. Zone Unit configuration can be either top return bottom discharge
or bottom return bottom discharge, and are available in three standard sizes (from
10 kW – 30 kW). Other sizes are available on request.
Complete system solutions from GEA
GEA DENCO®-OfficeCool
components and connections
PR-2013-0008-GB · Subject to modification · K0-11/2013[ 4 ]
Zone Unit LECUs
GEA offers complete system solutions
Local Environmental Control Unit (LECU)Each Zone Unit is connected to up to 35 LECUs, which gives the GEA DENCO®-
OfficeCool Air Conditioning System the exceptional ability to cope with changing office
layout requirements. The LECU is an intelligent fan tile, easily positioned anywhere
in the raised floor and provides the user with control over their “micro-climate”. Each
LECU includes a fan, a modulating damper and intelligent controller and will main-
tain the locally desired set temperature by re-circulating a varying mixture of air from
the room and conditioned air from under the raised floor.
Air Handling Unit (AHU)The AHU is sized to meet the fresh air requirements of the offices and delivers the
fresh air to the return air side of the Zone Unit.
ChillerThe Chiller is sized to meet the cooling requirements of the entire building.
PR-2013-0008-GB · Subject to modification · K0-11/2013 [ 5 ]
1
1
1
2
2
2
2
3
44
4
4
4
56
1 Zone Unit
2 LECU
3 Return air grilles
4 Ceiling grille
5 AHU
6 Heat pump
7 Chiller
7
PR-2013-0008-GB · Subject to modification · K0-11/2013[ 6 ]
The GEA DENCO®-OfficeCool concept –
designed to users´ specifications
Configurations for every room size, every requirement and condition
External plant spaceThe heat rejection equipment, such as Chillers, Heat Pumps and Air Handling Units
can all be installed externally.
Bottom air supply and return (ZU type Zone Unit and LECU) Where no ceiling is installed or where the integrity of the space above the raised floor
is important, the Zone Unit supplies and returns the air within the access floor space.
This space is simply divided into supply and return air plenums with underfloor
barriers. Cooling and heating can be provided by chilled water and low pressure hot
water or by heat pumps. The space is conditioned by the Zone Unit, and the LECUs
provide the occupants with the ability to control their space.
Bottom air supply and high level return (ZD type Zone Unit and LECU) The Zone Unit supplies conditioned air into the access floor void and hot air is returned
to the Zone Unit at high level. Cooling and heating can be provided by chilled water
and low pressure hot water or by heat pumps. The space is conditioned by the Zone
Unit, and the LECUs provide the occupants with the ability to control their space.
Bottom air supply and ceiling return (ZD type Zone Unit and LECU)The Zone Unit supplies conditioned air into the access floor void and hot air is returned
to the Zone Unit through a suspended ceiling. Cooling and heating can be provided by
chilled water and low pressure hot water or by heat pumps. The space is conditioned
by the Zone Unit, and the LECUs provide the occupants with the ability to control their
space.
Conditioning by external Air Handling Unit (AHU and LECU)The air conditioning of the space can be done by an externally mounted Air Handling
Unit, which supplies conditioned air through ducts into the access floor. The hot air is
returned to the Air Handling Unit through the ceiling and duct system. The LECUs
provide the occupants with the ability to control their space.
Benefits at a glance Almost cost free relocation
capability
Exceptionally quiet operation
Local environment control for
individuals
Control of temperature and
humidity for a healthier
environment
Filtration of both fresh air and
re-circulated air for a healthier
environment
Economical operation
Easy maintenance with all
services at low level in the
raised floor
Elimination of draughts
PR-2013-0008-GB · Subject to modification · K0-11/2013 [ 7 ]
Components
Zone Unit and LECU
Cooling coils
Heating
Filter
Inverter driven fans
Zone Unit
Q� CW or DX multi-row constructedQ� 3/8" OD copper tubes with mechanically bonded aluminium finsQ� Coils are tested up to 33 bar
Q� High-quality EU4 Z-Line filterQ� F7 filters, EU7 and washable filters are also availableQ� Differential pressure switch in the microprocessor control system indicates necessary filter change
Q� Low pressure hot water, with coils constructed of 3/8” OD copper tube, and mechanically bonded aluminium finsQ� In heat pump installations, reverse cycle heat pump provides heating through the evaporator/condenser coilQ� Electric Heating (optional), with stainless steel fins on heating elements and over temperature thermostatic safety cut out
Q� Quantity (1, 2 or 3) depending on unit sizeQ� Double inlet, double width with forward curved impellerQ� Directly driven by an integral motorQ� Fans will automatically modulateQ� EC Plug Fans are now available on some models
PR-2013-0008-GB · Subject to modification · K0-11/2013[ 8 ]
Controls
Q� Several controller options availableQ� Standard controller pC05Q� All units can be fitted, as an option, with a Trend IQ3Xact controlQ� Various interfaces for building management systems, etc.Q� Monitoring display
Sensors
Q� Water sensor (optional)Q� Sensors for measuring air conditions
Steam humidifier (optional)
Q� Proportional control electrode steam humidifierQ� Microprocessor control with alarm and diagnosis unit
Chilled water control valves
Q� Continously modulated 2- or 3-way valvesQ� Provided with vapour sealed insulation
LECU and components
GrillesQ� Rectangular and circular grilles available
Fan sectionQ� Single forward curved crossflow fanQ� Integrated single IP 44 closed type central electric motorQ� EC Centrifugal Fans are available on request
Filter (optional)Q� G2 filter in sheet metal frame
Electric heaterQ� 250 or 500 W electric heater
Control system and accessoriesQ� Handheld IR Remote Controller with IR Receiver PCB or IR Remote Controller Q� LED display with ability to change air-flow or set point
ComponentsQ� PlantWatch Pro touch screen displayQ� PlantVisor for remote system monitoring Trend IQ View 8 with touch screen display
LECU
PR-2013-0008-GB · Subject to modification · K0-11/2013 [ 9 ]
Technical data
Energy savings, carbon footprint and cost-efficiency
Design advice provided by local GEA DENCO®-OfficeCool specialist office. Specifications and unit schedules provided by local GEA
office for inclusion into design schedules. Life cycle cost analyses (LCCA) can be provided on request. Selection data below, for
standard chilled water units. Full selection carried out by local GEA DENCO®-OfficeCool specialist office. DX, heat pump and AHU
selections provided on request.
Unit size ZD 12 ZD 28 ZD 42 ZU 12 ZU 28 ZU 42
Min. cap. Recommended Max. cap. Min. cap. Recommended Max. cap. Min. cap. Recommended Max. cap. Min. cap. Recommended Max. cap. Min. cap. Recommended Max. cap. Min. cap. Recommended Max. cap.
Air supply Downflow Upflow
Cooling capacity
Total (1) kW 5.1 11.3 14.2 10.4 22.3 27.8 15.5 32.0 42.0 5.1 11.3 14.2 10.4 22.3 27.8 15.5 32.0 42.0
Sensible (1) kW 3.6 8.6 10.8 7.5 17.3 21.6 11.0 25.5 32.7 3.6 8.6 10.8 7.5 17.3 21.6 11.0 25.5 32.7
Fan
Fan type Inverter controlled forward curved centrifugal fan
Fan no. n. 1 1 1 2 2 2 3 3 3 1 1 1 2 2 2 3 3 3
Air flow (4) m3/h 700 2,200 2,900 1,400 4,400 5,800 2,100 6,600 8,700 700 2,200 2,900 1,400 4,400 5,800 2,100 6,600 8,700
m3/s 0.2 0.6 0.8 0.4 1.2 1.8 0.6 1.8 2.4 0.2 0.6 0.8 0.4 1.2 1.8 0.6 1.8 2.4
Ext. static pressure Pa 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
Fan Power kW 0.05 0.3 0.6 0.1 0.6 1.2 0.2 0.9 1.8 0.05 0.3 0.6 0.1 0.6 1.2 0.2 0.9 1.8
Specific fan power W/l/s 0.25 0.5 0.75 0.25 0.5 0.75 0.33 0.5 0.75 0.25 0.5 0.75 0.25 0.5 0.75 0.33 0.5 0.75
Cooling coil Copper tube / aluminium fin
Water flow (3) l/s 0.2 0.4 0.5 0.5 0.8 1.0 0.6 1.0 1.4 0.2 0.4 0.5 0.5 0.8 1.0 0.6 1.0 1.4
Water temperature °C (3) kPa 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0
Pressure drop-coil & valve (1)
kPa 8.0 23.0 35.0 10.0 24.0 36.0 8.0 20.0 36.0 8.0 23.0 35.0 10.0 24.0 36.0 8.0 20.0 36.0
Electric heater (optional) Low watt density finned tube
Capacity kW 3.0 3.0 3.0 6.0 6.0 6.0 6.0 6.0 6.0 3.0 3.0 3.0 6.0 6.0 6.0 6.0 6.0 6.0
Current A 4.5 4.5 4.5 9.0 9.0 9.0 9.0 9.0 9.0 4.5 4.5 4.5 9.0 9.0 9.0 9.0 9.0 9.0
Heating steps n. 1.0 1.0 1.0 2.0 2.0 2.0 2.0 2.0 2.0 1.0 1.0 1.0 2.0 2.0 2.0 2.0 2.0 2.0
Humidifier (optional) Fail safe electrode boiler
Capacity kg/h 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3
Power kW 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
Power supply
Power source 400 V / 3 Ph / 50 or 60 Hz
Cooling only power kW 0.2 0.5 0.8 0.3 0.8 1.4 0.4 1.1 2.0 0.2 0.5 0.8 0.3 0.8 1.4 0.4 1.1 2.0
Max. power kW 5.1 5.3 5.6 8.1 8.6 9.2 8.2 8.9 9.8 5.1 5.3 5.6 8.1 8.6 9.2 8.2 8.9 9.8
Piping connection Copper tube
Condensate drain mm 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0
Humidifier in. mm 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
Chilled water in & out mm 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0
Dimension
Length mm 647 647 647 1,247 1,247 1,247 1,847 1,847 1,847 647 647 647 1,247 1,247 1,247 1,847 1,847 1,847
Depth mm 654 654 654 654 654 654 654 654 654 850 850 850 800 800 800 800 800 800
Height mm 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940
Weight (2) kg 215 215 215 355 355 355 430 430 430 230 230 230 370 370 370 445 445 445
(1) Rated at return air 26 °C / 50 % and outdoor air temperature 35 °C; (2) For cooling only unit; (3) 7 / 13 °C; (4) Recommended airflows used to maintain office noise level
PR-2013-0008-GB · Subject to modification · K0-11/2013[ 10 ]
Unit size ZD 12 ZD 28 ZD 42 ZU 12 ZU 28 ZU 42
Min. cap. Recommended Max. cap. Min. cap. Recommended Max. cap. Min. cap. Recommended Max. cap. Min. cap. Recommended Max. cap. Min. cap. Recommended Max. cap. Min. cap. Recommended Max. cap.
Air supply Downflow Upflow
Cooling capacity
Total (1) kW 5.1 11.3 14.2 10.4 22.3 27.8 15.5 32.0 42.0 5.1 11.3 14.2 10.4 22.3 27.8 15.5 32.0 42.0
Sensible (1) kW 3.6 8.6 10.8 7.5 17.3 21.6 11.0 25.5 32.7 3.6 8.6 10.8 7.5 17.3 21.6 11.0 25.5 32.7
Fan
Fan type Inverter controlled forward curved centrifugal fan
Fan no. n. 1 1 1 2 2 2 3 3 3 1 1 1 2 2 2 3 3 3
Air flow (4) m3/h 700 2,200 2,900 1,400 4,400 5,800 2,100 6,600 8,700 700 2,200 2,900 1,400 4,400 5,800 2,100 6,600 8,700
m3/s 0.2 0.6 0.8 0.4 1.2 1.8 0.6 1.8 2.4 0.2 0.6 0.8 0.4 1.2 1.8 0.6 1.8 2.4
Ext. static pressure Pa 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
Fan Power kW 0.05 0.3 0.6 0.1 0.6 1.2 0.2 0.9 1.8 0.05 0.3 0.6 0.1 0.6 1.2 0.2 0.9 1.8
Specific fan power W/l/s 0.25 0.5 0.75 0.25 0.5 0.75 0.33 0.5 0.75 0.25 0.5 0.75 0.25 0.5 0.75 0.33 0.5 0.75
Cooling coil Copper tube / aluminium fin
Water flow (3) l/s 0.2 0.4 0.5 0.5 0.8 1.0 0.6 1.0 1.4 0.2 0.4 0.5 0.5 0.8 1.0 0.6 1.0 1.4
Water temperature °C (3) kPa 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0
Pressure drop-coil & valve (1)
kPa 8.0 23.0 35.0 10.0 24.0 36.0 8.0 20.0 36.0 8.0 23.0 35.0 10.0 24.0 36.0 8.0 20.0 36.0
Electric heater (optional) Low watt density finned tube
Capacity kW 3.0 3.0 3.0 6.0 6.0 6.0 6.0 6.0 6.0 3.0 3.0 3.0 6.0 6.0 6.0 6.0 6.0 6.0
Current A 4.5 4.5 4.5 9.0 9.0 9.0 9.0 9.0 9.0 4.5 4.5 4.5 9.0 9.0 9.0 9.0 9.0 9.0
Heating steps n. 1.0 1.0 1.0 2.0 2.0 2.0 2.0 2.0 2.0 1.0 1.0 1.0 2.0 2.0 2.0 2.0 2.0 2.0
Humidifier (optional) Fail safe electrode boiler
Capacity kg/h 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3 1.5 – 3
Power kW 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
Power supply
Power source 400 V / 3 Ph / 50 or 60 Hz
Cooling only power kW 0.2 0.5 0.8 0.3 0.8 1.4 0.4 1.1 2.0 0.2 0.5 0.8 0.3 0.8 1.4 0.4 1.1 2.0
Max. power kW 5.1 5.3 5.6 8.1 8.6 9.2 8.2 8.9 9.8 5.1 5.3 5.6 8.1 8.6 9.2 8.2 8.9 9.8
Piping connection Copper tube
Condensate drain mm 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0
Humidifier in. mm 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
Chilled water in & out mm 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0 28.0
Dimension
Length mm 647 647 647 1,247 1,247 1,247 1,847 1,847 1,847 647 647 647 1,247 1,247 1,247 1,847 1,847 1,847
Depth mm 654 654 654 654 654 654 654 654 654 850 850 850 800 800 800 800 800 800
Height mm 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940 1,940
Weight (2) kg 215 215 215 355 355 355 430 430 430 230 230 230 370 370 370 445 445 445
Energy comparison GEA DENCO®-OfficeCool vs traditional FCU and AHU model
600
400
200
0
Jan Feb
Mar M
ayJu
n Jul
Apr Aug Sep
Oct Nov Dec
GEA DENCO®-OfficeCool
Traditional
A 0-25
26-50
51-75
76-100
101-125
126-150
Over 150
BCDEFG
47 This is how efficientthe building is.
Typical building rating achieved in UK
Co
sts
in €
PR-2013-0008-GB · Subject to modification · K0-11/2013 [ 11 ]
LECU operation and control
For flexible office concepts
Cooling modeIf the room sensor detects that the local tem-
perature is too warm, it interrogates the un-
derfloor sensor. If the underfloor tempera-
ture is below that of the room air, the
damper is modulated open to allow cooling
to the space. The damper is modulated suffi-
ciently to offset the heat gain to the space.
Heating modeIf the room sensor detects that the local tem-
perature is too cold, it interrogates the under-
floor sensor. If the underfloor temperature is
above that of the room air, the damper is
modulated open to allow heating to the space.
The damper is modulated sufficiently to off-
set the heat loss to the space.
Recirculation modeWhen the room sensor detects that the local
temperature matches the set point, the damp-
er will be closed and the unit will be in recir-
culation mode. An adjustable bleed damper
allows sufficient air from the floor void to
provide the fresh air requirements for the
space.
Electric heater mode (optional)Under exceptional circumstances, if the
room sensor detects that the local tempera-
ture is too cold and upon interrogation of the
underfloor sensor it is determined that there
is insufficient heat available, the controller
will modulate the damper fully closed and
initiate the electric heater battery. The heater
will be on until such time that either the un-
der floor temperature increases sufficiently
to meet the heating requirement, or the room
temperature increases to the set point.
Cooling mode
Heating mode
Recirculation mode
Electric heater mode
heater(optional)
heater(optional)
heater(optional)
heater(optional)
fan
fan
fan
fully modulating damper
fully modulating damper
fully modulating damper
independent controller
independent controller
independent controller
independent controller
return air sensor
return air sensor
return air sensor
return air sensor
floor voidsensor
floor voidsensor
floor voidsensor
raised modularfloor
raised modularfloor
raised modularfloor
raised modularfloor
chos
en t
emp
chos
en t
emp
chos
en t
emp
chos
en t
emp
fan fully modulating damper
floor voidsensor
PR-2013-0008-GB · Subject to modification · K0-11/2013[ 12 ]
Local Environment Control Unit (LECU)The LECU gives the GEA DENCO®-OfficeCool Air Conditioning System an exceptional
ability to cope with the changing work space layout requirements. It is an intelligent
fan tile, easily positioned anywhere in the floor of any work space. The LECU has 3
selectable fan speeds as standard (although 0-10 volt versions are now available on
some models) and an adjustable set-point to meet users requirements. It maintains the
locally desired set temperature by re-circulating a varying mixture of air from the
room and conditioned underfloor air.
The LECU has its own frame and can be used with stringerless raised floors. It exactly
matches a 600 x 600 raised floor panel and only weighs 18 Kg. Relocation of LECUs can
be accomplished in minutes and enables the GEA DENCO®-OfficeCool Air Conditioning
System to adapt to your changing work space layout.
Adjustment of the LECU operation is available in different forms. At its simplest,
adjustment of the set point and fan speed can be done directly via an infra red, hand-
held remote control or the optional display mounted on the LECU.
The Building Management System (BMS) allows monitoring or adjustment of the set
point and fan speed as well as monitoring of the entire system using selectable vari-
ables. When the LECU and the Zone Units are networked, the Zone Unit can be con-
trolled by the average of the readings on the room sensors of the LECUs within any
particular zone.
PR-2013-0008-GB · Subject to modification · K0-11/2013 [ 13 ]
Control configuration possibilities
Under what conditions which configuration is used?
Zone Unit 1
RS 485Field Card
RS 485Field Card
RS 485Field Card
Serial Card Serial Card Serial Card
Data Cable
Control System / BMS
Remote access or user terminal access
5 m network cable supplied with each LECU
LECU 1 LECU 1 LECU 1
LECU 2 LECU 2 LECU 2
LECU 15 LECU 15 LECU 15
Zone Unit 2 Zone Unit 3
On Floor Touch Screen Group Controller
Building IT infrastructure
Intranet /Internet
PR-2013-0008-GB · Subject to modification · K0-11/2013[ 14 ]
On Floor Touch Screen Group Controller
Zone Unit Field Cards
Standard ethernet cable RJ45
Linked Zone Unit Controllers
Building IT backbone switch
A fully linked control system provides communica-
tion between end users and individual LECUs. With
integration possible between the building s own BMS
and/or a purpose built control system just for GEA
DENCO®-OfficeCool.
GEA’s own purpose written software allows for seam-
less communication of all GEA DENCO®-OfficeCool
components, with data logging, alarm warnings as
standard. User input is possible from many locations
for ease of access, quick and easily adjustable temper-
ature settings for maximum flexibility and comfort
for all.
Other options for layout and operationThere are a number of additional features which
allow the users to get the maximum benefit from the
GEA DENCO®-OfficeCool Air Conditioning System.
An on floor touch screen group controller, or IQView 8,
can be installed in the system. These provide a “mini-
headend” capability for smaller installations that
have no BMS, or where a BMS is installed, it provides
tenants, or users, with the control over the equipment
installed at floor plate level.
Standalone Control System
PR-2013-0008-GB · Subject to modification · K0-11/2013 [ 15 ]
Dimensional drawings and technical data
Zone Unit
ZD version ZU version
Model size ZD 12 ZD 28 ZD 42 ZU 12 ZU 28 ZU 42
Weights and dimensions
Weight kg 215 355 430 230 370 445
Height (H) mm 1,940 1,940 1,940 1,940 1,940 1,940
Width (W) mm 647 1,247 1,847 647 1,247 1,847
Depth (D) mm 654 654 654 850 800 800
ZU 12
647
W D
850
1,9
40
H
ZU 28
1,247
W D
800
1,9
40
H
ZU 42
1,847
W D
800
1,9
40
H
&QYPƃQY��DQVVQO�TGVWTP
ZD 12
647
W D
654
1,9
40
H
ZD 28
1,247
W D
654
1,9
40
H
ZD 42
1,847
W D
654
1,9
40
H
&QYPƃQY��VQR�TGVWTP
Unit Front
ServiceAccess
60
0 m
in
PR-2013-0008-GB · Subject to modification · K0-11/2013[ 16 ]
LECU
LECU
Weights and dimensions
Weight kg 18
Top dimension mm 600 x 600
Height (H) mm 222
Width 1 (W1) mm 494
Width 2 (W2) mm 500
Width 3 (W3) mm 595
Depth 1 (D1) mm 637
Depth 2 (D2) mm 595
W1: 494 W2: 500
H: 2
22
D1: 637D2: 595
W3:
595
Concept Rule of Thumb
Zone UnitApprox. capacity
Area covered
Approx. no. of LECUs required
ZD 42 30 kW 300 m2 15
ZD 28 20 kW 200 m2 10
ZD 12 10 kW 100 m2 5
To calculate approximate number of Zone Units:No. of Zone Units = total load / approx. capacity
To calculate approximate number of LECUs:Number of LECUs = supply airflow / 0.11
To double check the number of LECUs:Number of LECU = floor plate area / 15 m2
* Approximate distance between unit outlet 25 m
.'%7�'NGEVTKE�FGVCKNU�CV�����8����2J� �0����QT����*\
Fan FLA 0.5
W 40
Electric heater FLA 2.2
W 50
Unit without heater fitted FLA 0.5
Unit with heater fitted FLA 2.7
LECU underfloor pressure 0 (Pa)
Fan Speed Airflow Noise Level
m3/s m3/hr NR
1 0.08 288 28
2 0.1 360 33
3 0.12 432 40
PR-2013-0008-GB · Subject to modification · K0-11/2013 [ 17 ]
Quality
Always focusing on the customer
Quality management with HX-Factor from development to after-salesWe, the GEA experts for climate and environment solutions, are the European market
leaders for the entire spectrum of air treatment. Quality is one of our key success factors.
Looking back on more than 100 years of experience we have continuously improved
and optimized our products and business operations, keeping one central goal in focus:
Exceeding our customers expectations. Our major quality feature is the HX-Factor. It
is our performance commitment and stands for unique expertise in heat exchange (HX
= HEAT EXCHANGE). The HX-Factor is the one special personal strength that every
single employee invests into the production processes. In order to keep our staff as
healthy and motivated as possible, we are committed to comply with applicable regu-
lations and requirements. Regular training ensures that our employees maintain their
skills in accordance with the latest developments. The HX-Factor is also the sum of all
attributes that make our products convincing – in the case of DENCO®-OfficeCool it is
cost and energy efficiency as well as flexibility. Finally, the HX-Factor is what we live
in the heat exchange business to be engineering for a better world. Numerous certifi-
cations prove our competence.
Certificates Quality Assurance –
EN ISO 9001:2008
CE marking for all EU
relevant products
Safety of Machinery:
EN 60204-1:2006+A1:2009
Safety of Machinery:
N ISO 12100-1:2003
Safety of Machinery:
EN ISO 12100-2:2003
EMC Emissions:
EN 61000-6-3:2007
EMC Immunity:
EN 61000-6-2:2005
Refrigeration Systems:
EN 378-1/2/3/4:2008
ASME 9
Solutions with HX-Factor
The HX-Factor is our promise. It stands for our
unique expertise in heat exchange (HX = HEAT
EXCHANGE) and marks out all our products
and services. GEA DENCO®-OfficeCool is a very
modular solution with systematic sophistication,
which promises the following: made-to-measure
and space-saving climate control with maximum
reliability and energy-efficiency.
PR-2013-0008-GB · Subject to modification · K0-11/2013[ 18 ]
Manufacturing Centers
Air treatment competence around the globe
Over the past 100 years the GEA experts for room climate solutions have established
an international network of manufacturing sites. Centers of excellence for air handling
units, close control units, decentral air treatment, and clean rooms are located in several
countries throughout Europe and Asia. All of them deal constantly with the continu-
ous improvement in production processes and optimization according to the latest
international standards. With a clear focus on standardization, all sites can assure a
high level of production flexibility. Furthermore, just in time production with short
delivery times helps fulfil customer requirements. With integrated research and devel-
opment facilities, we are able to handle even the most technically demanding projects.
One of our special skills is advanced knowledge in metal sheet processing. No matter
what our customers ask of us – reliability is the most decisive feature that character-
izes all GEA sites.
Global approach
International quality standards
Constant improvement
Flexible standardization
Just in time production
Customer in focus
Production facility in Pune, India The Turkey location in Istanbul
Production facility in Wuhu, China Factory in Wurzen, Germany
Aerial photograph showing the factory
in Liberec, Czech Republic
Looking inside the GEA site at Hereford, UK
PR-2013-0008-GB · Subject to modification · K0-11/2013 [ 19 ]
References
Solutions for every climatic demand
MEPC LimitedMEPC manages some of the UK's best known commercial prop-
erty, with seven Business Estates set in prime locations through-
out the UK. Together they provide over 7 million sq ft of high
quality space for more than 1,000 organizations, employing over
20,000 people. MEPC chose the GEA DENCO®-OfficeCool un-
derfloor air conditioning system for over 10,000 sq m office ac-
commodation, across 6 new buildings. In total, GEA installed
70 Zone Units and 850 Local Environmental Control Units
(LECU). MEPC desired the flexibility offered by GEA DENCO®-
OfficeCool system, due to the relatively high fit-out alteration
requirements of their tenants. The system also met MEPC’s cor-
porate sustainability objectives. GEA has worked closely with
MEPC to deliver the energy efficient solution, through chilled
water cooling and DX heat pumps systems, which will achieve
Class B Energy Performance Certification.
Public Authority for Applied Education and Training (PAAET) – AESS Building, KuwaitPAAET selected the GEA DENCO®-OfficeCool underfloor air
conditioning system for its new education campus in the Shu-
waikh district of Kuwait. GEA Middle East FZE supplied 416 x
Zone type Air Handling Units and 5,000 x GEA LECUs for
the central tower and administrative wings of this building.
All of the equipment supplied for this project was manufac-
tured at our GEA Liberec factory in the Czech Republic. This
system is independently controlled via GEA’s own central con-
trol system which is fully integrated into the PAAET building
management system.
[ 20 ]
YONHAP Media Center – KoreaThis national television company has chosen a complete GEA
DENCO®-OfficeCool solution for their air conditioning require-
ments for their new state of the art studios in the centre of
Seoul. The system was supplied by GEA Middle East FZE and
encompasses 24 x GEA Air Handling Units all of which were
manufactured in our GEA Wurzen Plant in Germany, addition-
ally there are 48 x GEA DENCO® Ultra Zone Units and 1,500
GEA LECUs which were manufactured in our Liberec plant in
the Czech Republic.
AgustaWestland HelicoptersWhen AgustaWestland refurbished one of their office blocks
they selected the GEA DENCO®-OfficeCool underfloor air con-
ditioning system. The office was air conditioned by 14 Zone
Units and a number of Local Environmental Control Units
(LECU), which allows employees control over their workspace
temperature. When AgustaWestland install any new air con-
ditioning system, they carefully review the energy efficiency
of the system. The GEA DENCO®-OfficeCool System with each
Zone Unit is connected to a reverse cycle heat pump which pro-
vides a very energy efficient cooling and heating system. The
fresh air for the system is provided by two GEA Air Handling
Units, with heat recovery, which provide additional energy
savings.
[ 21 ]
Your GEA experts for air treatment systems
Sales network
Europe
GEA Klimatechnik GmbH
Gaspoltshofen, Austria
GEA Happel Belgiuim N.V./S.A.
Brussels, Belgium
GEA Klima-rashladna tehnika d.o.o.
Zagreb, Croatia
GEA Heat Exchangers a.s.
Liberec, Czech Republic
GEA Happel S.A.S.
Roncq, France
GEA Delbag S.A.S.
Montry, France
GEA Air Treatment GmbH
Herne, Germany
GEA Air Treatment Production GmbH
Wurzen, Germany
GEA Klimatechnika Kft
Budapest, Hungary
GEA Klimatechnik UAB
Vilnius, Lithuania
GEA Happel Nederland B.V.
Capelle an der Ijssel, Netherlands
GEA Klimatyzacja Sp. z.o.o.
Wroclaw, Poland
SC GEA Klimatechnik s.r.l.
Timisoara, Romania
GEA Klimatechnik GmbH & Co. KG
Moscow, Russia
GEA Klimatechnik GmbH Srbija
Belgrad, Serbia
GEA Klimatizacia s.r.o.
Bratislava, Slovakia
GEA Klimatizacijska tehnika d.o.o.
Ljubljana, Slovenia
GEA Isisan Tesisat Insaat
Taahhüt Ticaret ve Sanayi A.S.
Istanbul, Turkey
TOV GEA-Ukrayina
Kiev, Ukraine
Our competence centers for GEA DENCO®-OfficeCool systems
Middle East
GEA Middle East FZE
P.O. Box 261236, JAFZA Building LOB 17
4th Floor, Suite 412, Jebal Ali Free Zone, Dubai, UAE
Europe
GEA Heat Exchangers Limited
Dolphin House, Moreton Business Park, Moreton-on-Lugg
Hereford HR4 8DS, United Kingdom
China
GEA Industrial Heat Exchangers Systems
R535/538, South Block, Tower C, Raycom Info Tech Park
No. 2 Kexueyuan South Road, Zhong Guanchun
Beijing 100190, China
India
GEA Ecoflex India Pvt Ltd
Air Treatment Business Unit
713, 7th Floor, 98, Hemkunt Tower
Nehru Place, New Delhi – 110019, India
Sales / Distribution
Service
Production / Manufacturing
PR-2013-0008-GB · Subject to modification · K0-11/2013[ 22 ]
We live our values.Excellence r Passion r Integrity r Responsibility r GEA-versity
GEA Group is a global engineering company with multi-billion euro sales and operations in more than 50 countries. Founded in 1881, the company is one of the largest providers of innovative equipment and process technology. GEA Group is listed in the STOXX® Europe 600 Index.
www.gea-heatexchangers.com © G
EA H
eat E
xcha
nger
s. S
ubje
ct to
mod
ifica
tion.
11/
2013
– P
R-20
13-0
008
-GB