Hytronik Microwave motion sensor 46
Model: HC003V/RF Mechanical structure
This is a combination of motion sensor and RF radio wave wireless
transmission. The motion at 1 sensor (the master unit) can be passed onto
other pre-defined individuals (the slave units) through R F transmission. Up
to 15 units can be programed and grouped by means of Teach-and-Learn
method.
With KEELOQ coding technology, 1 master can triger max. 15 slaves , and
1 slaves can respond up to 15 masters respectively.
With both 1-10v output signal and 220-240v signal, it can switch on/off &
dim any lighting applications.
The motion signal from 1 sensor (the master sensor) can be transmitted
to and trigger on other sensors (the slave unit) by RF transsmmion. This
wireless radio wave transmission can reach 100 meters in open area.
detection area
Motion Hold-time
Stand-by period
Stand-by dimming level
installation hole
Antenna moduleDetachablelight sensor
N L L,
L,,
1-10V
Daylight sensor
Brightness on RF signal
Wireless Transmission Control
This is a combination of motion sensor and RF radio wireless, wireless transmission is the perfect solution for retrofit projects, easy installation and free of wiring. with KEELOQ coding system, by "Teach & Learn" method, selected and directional communication can be easily setup.Up to 15 channels can be grouped and programmed, and up to 30 meters indoor transmission and 100 meters in open area.
10%
100%
Off
Off
100%
10%
100%
Off
Function and options
while the 1st sensor detects motion at 1st floor, the 1st sensor switch on 100%, the 2nd one to be standby brightness
The person walks to 2nd floor, the 2nd sensor at 100% and 3rd sensor to be standby brightness
1
1
2
2
R F communication version
Model: HC003V/RF
Hytronik Microwave motion sensor 47
Detection Pattern
area of high sensitivity area of lower sensitivity
wal
l mou
ntin
g he
ight
wall mounting pattern(m)
2
3
4
5
2
1
0
1
3
4
5
1 2 3 4 5 6 7 8 9 10ceiling mounting pattern(m)
ceili
ng m
ount
ing
heig
ht
1
2
3
4
5
101 22 33 44 55
100%
100%
10%
10% Off
10%
100%
100%
The person walks to 3rd floor, the 3rd sensor at 100% and 4th to be standby brightness,at same time, 1st sensor dims to standby brightness after hold time
The person walks to 4th floor, the next sensor is 100%...... and at the same time, 1st sensor is off after standby period and 2nd sensor dims to standby brightness
3
4
3 4
HC003V/RF HC003V/RF
sensorDIM Wiring Diagram 1-10VDmimable Wiring Diagram
Hytronik Microwave motion sensor 48
Settings
RF grouping (max. 15 channels)
I - maximum range up to 100% II – 75%III – 50%IV- 30%V- 10%
Detection area can be reduced by selecting the combination on the DIP switches to fit precisely for each specific application.
I – 5SII – 30SIII – 1 minuteIV – 5 minutesV – 10 minutesVI – 20 minutes
Hold-time means the time period you would like to keep the lamp on 100% after the person has left the detection area.
Hold-time
Detection area1
2
I – DisableII – 1 hourIII – 30 minIV – 10 minV – 5 minVI – 1 min
I – 5V (45~50%)II – 4V (35~40%)III – 3V (25~30%)IV – 2V (15~20%)V – 1.4V (5~10%)
This is the time period you would like to keep at the low light output level before it is completely switched off in the long absence of people.
This is the dimmed low light output level you would like to have after the hold-time in the absence of people.
Press LEARN button on the recieving unit , the sensor goes into a 180s of teach-and-learn period, in which electrician have enough time to go back to master unit to release transmission.
red LED is on, and the beeper gives long indication:
Press the SEND button on the master unit to send RF signal, the green
LED on the master unit is then on to indicate the success of
transmission. and the beeper turns to short indication:
Upon receiving the transmission signal, the red LED on receiving unit will
flash 2-3 times, which is the indication of successful teach-and-learn;
and the beeper turns to short indiction:
Stand-by period(corridor function)
Stand-by dimming level
4
5
1 short press this Learn button
Red LED is on
beeper is on
master unit
beeper is on
Press this send buttonGreen LED is on
Red LED flashes 2-3 times.
step1
step2
slave unit
slave unit
The daylight threshold can be set on the potentiometer, from 2 lux up to 2000 lux, to fit for any particular application.
Detachable daylight sensor32 lux 2000 lux
Hytronik Microwave motion sensor 49
Wait for 180s period elapses, till the short beeper stops as well as the
red LED on receiving unit goes off. The whole teach-and-learn process is
completed. Or--
Short press the Learn button again within the 180s period to finish the
whole teach-and-learn process.
Red LED goes off after 180s.
beeper is off after 180s
800w
<1mw
Max. ( x H ): 8m x 5m
30--150 O
Detection area
Daylight threshold
Standby period
2--2000 lux
Max. 5m.
-20 +60
220-240v
5s/30s/1min/5min/10min/20min
1min/5min/10min/30min/1hour / disable
RF. Transmission distance 100 meters in open area
RF. Communicatin Chanels 15 channels for grouping
RF Frequency 433 MHz
Coding Keeloq rolling code (tech/learn/reset/memory)
~
step3
step4
beeper is offRed LED goes off.2nd short press this Learn button
slave unit
beeper keeps on beeping, , then goes off in 10s
Long press this Learn button
Red LED keeps on flashing then goes off in 10s.
(if necessary) ( slave unit )
slave unit (Optional )
If you want to RESET:A long press on Learn button (about 10s) resets and clears all previous commands it has received–-
The red LED keeps on flashing and then goes off in the end ; this is the indication of a successful reset and erase of all the previous groupings.