MINISTRY OF EDUCATION AND TRAINING THE UNIVERSITY OF DANANG NGO MINH KHOA A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORK SPECIALIZATION: ELECTRICAL ENGINEERING CODE: 62.52.02.02 DISSERTATION IN BRIEF Danang 2016

Transcript of A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION...

Page 1: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

MINISTRY OF EDUCATION AND TRAINING

THE UNIVERSITY OF DANANG

NGO MINH KHOA

A STUDY OF VOLTAGE DISTURBANCES

IN DISTRIBUTION NETWORK

SPECIALIZATION: ELECTRICAL ENGINEERING

CODE: 62.52.02.02

DISSERTATION IN BRIEF

Danang – 2016

Page 2: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

This dissertation has been finished at: Danang University of

Technology, The university of Danang

Supervisor 1: Assoc, Prof. PhD. Dinh Thanh Viet

Supervisor 2: PhD. Nguyen Huu Hieu

Examiner 1: GS.VS.TSKH. Trần Đình Long

Examiner 2: PGS.TS. Võ Ngọc Điều

Examiner 3: TS. Lê Hữu Hùng

The dissertation will be defended at the Thesis Assessment

Committee at Da Nang University Level at Room No:

............................................................................................

.............................................................................................

............................................................................................

At date month 2016

The dissertation is available at:

1. The National Library.

2. The Information Resources Center, The university of Danang.

Page 3: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

1

INTRODUCTION

1. The reason for choosing the dissertation

Nowadays, electrical equipment in modern industry uses more

and more electronic devices, controllers (such as motor speed drive

controllers, programmable logic controllers, etc.) with the

involvement of the distributed generation using renewable energy

sources (wind, solar, etc.) in distribution networks. These devices

require high voltage quality in order to ensure their normal operation

conditions.

2. The purposes of the research

- The dissertation researches about signal processing methods

used in voltage disturbance analysis problems. Then a new method

based on discrete wavelet transform (DWT) and linear adaptive

neural network (ADALINE) is proposed in order to determine and

classify accurately voltage disturbances which appear at a

monitoring position in distribution network.

- The dissertation researches characteristics, effects, solutions

and standards of voltage sag. Then the authors proposes a research

method of voltage sag effects to sensitive loads in distribution

network based on modeling and simulating by using Matlab/Simulink

software.

- Application of the proposed method in chapter 2 to determine

voltage sag indices according to the IEEE Std. 1564-2014 standard

and evaluate voltage quality for sensitive loads in Vietnam’s

distribution networds.

- Application of voltage sag mitigation methods by using

mitigation equipments at connection point between sensitive loads

and distribution network.

Page 4: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

2

3. Research methods

To build up the system to monitor, classify and mitigate

voltage disturbances especially voltage sag/swell, the research

method of the dissertation will study problems below:

+ The background of signal processing methods in modern

signal processing applied in power system are researched in this

dissertation.

+ Highlights of characteristic identification methods of signals

follow artificial intelligent are studying and then the efficiency of

voltage disturbance classification system is improved.

+ Data in this work is gathered by simulating transient

process in power system by Matlab/Simulink software, real data is

also gathered to evaluate the proposed methods.

4. The object and scope of research

The research object: The dissertation researches on voltage

disturbances in distribution networks including types of short-term

voltage variations (voltage sag, voltage swell, voltage interruption)

and long-term voltage variations which impact on voltage quality in

distribution network.

The research scope: The dissertation researches voltage

disturbance classification methods aforementioned, and studies

effects and determinating indices of voltage sag in order to improve

voltage quality for sensitive loads in distribution networks. In

addition, this dissertation also studies voltage sag mitigation

solutions in distribution networks.

5. The meaning of science and practice of the dissertation

The meaning of science: With the previous content, the

dissertation results will have the meaning of sience as following:

Page 5: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

3

- A voltage disturbances classification method meets

requirements on monitoring voltage quality in distribution network.

The system can handle a large volume of input data collected from

the monitoring locations on the grid.

- It shows that the necessery of voltage disturbances

classification especially in the context of increasing the power

electronic devices as well as distributed generation involved in

distribution network.

- Discrete wavelet transform (DWT) method is a effective tool

in signal processing, its detail and approximation coefficients are the

typical characteristics of voltage disturbances.

- ADALINE shows ability for voltage amplitude identification

comparing with traditional methods. ADALINE can also determine

both the amplitude and phase angle of different frequency

components of voltage disturbance signals.

The meaning of practice: The research problems in the

dissertation will have the meaning of practice as following:

- Classification is an essential task in the management and

operation of the power grid to deliver the best performance.

- With the huge data of real waveforms recorded by power

quality monitoring equipment which are located at difference points

in distribution networks, and the considering period can be long

(weeks, months, years). Therefore, we need a classification system to

classify that data.

- The classification results will help the selection, design and

installation of suitable equipment to prevent the consequences which

voltage disturbances can cause impact on the electrical equipment

customers and the electricity unit.

Page 6: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

4

CHAPTER 1. VOLTAGE DISTURBANCE CLASSIFICATION

OVERVIEW IN DISTRIBUTION NETWORK

1.1. Introduction

Voltage quality monitoring is a process of gathering, analyzing

and describing the real data into useful information. Data collection

process is usually done by continuously measuring the voltage as

shown in Figure 1.1. Normally the process of analysis and evaluation

is done in the traditional way, but with the recent advantages in the

fields of signal processing and artificial intelligence has opened up

many opportunities to be able to design and application intelligent

systems use to automatically analyze and evaluate real data with

human intervention [17]. The main goal of the data collection is to

identify and control the disturbances. This can be done by detecting,

analyzing and defining characteristic of different NLDA.

Figure 1.1. Voltage quality measurment and monitoring diagram.

Figure 1.2. The meaning of extracting characteristic input signal.

Measurement Pre-

processing

Average Saving data

Triggering Calculating

indicies Saving data

Statistics and

publishing

Variations

Các sự kiện

1 2

3

x x

x

x x

x

x

0

0

0

0 0

0

0 0

Input space

(x) (x)

(x) (x)

(x)

(x)

(x) (0)

(0)

(0)

(0) (0)

(0) (0)

(0)

F

Feature space

C1

C2

Y

Decision space

Page 7: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

5

1.2. Voltage disturbance classification methods

There are many different methods to determine the

characteristics and to classify voltage disturbances, however they can

be classified into two main groups as follows:

+ The traditional methods: They are the methods commonly

used in the protection relay and power quality monitoring devices in

distribution network.

The root mean square (RMS) method

The fundamental voltage method

The peak voltage method

+ The morden methods: Because the traditional methods have

weaknesses in detecting the voltage disturbance characteristics so we

need to find out the modern methods to quickly and accurately detect

voltage disturbances.

The short-time Fourier transform

The adaptive linear neural network (ADALINE)

The wavelet transform

1.3. Conclusion

Based on the content presented on the voltage disturbance

classification method of in distribution network. It shows that there

are many methods of classifying voltage disturbance, but each

method has different advantages and disadvantages. Therefore

finding a more suitable method to apply to the classification of

voltage disturbance types to bring high efficiency in monitoring,

operation distribution network.

Although classic methods has advantages but also exist certain

disadvantage in determining the characteristics to classify the voltage

disturbance types. Therefore the trend will study application of

Page 8: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

6

methods of modern signal processing to determine parameters and

accurate classification of voltage disturbance types. A review of

existing methods for determining the characteristics and classification

voltage disturbance shows that usually we have to combine modern

methods to maximize efficiency as well as overcoming disadvantages

each other in determining the characteristics and classification

voltage disturbances. Hence using DWT and ADALINE combined to

determine voltage disturbance characteristics.

CHAPTER 2. A METHOD FOR DETERMING

CHARACTERISTICS AND CLASSIFYING VOLTAGE

DISTURBANCES IN DISTRIBUTION NETWORK

2.1. Introduction

Voltage disturbance monitoring becomes necessary in the

management and operation in order to improve the quality of

electricity supply to customers especially for modern industrial

customers such as electronic manufacture, semiconductor material

manufacture, computer data centers, etc. as shown in Figure 2.1.

Figure 2.1. The necessary of voltage disturbance monitoring.

2.2. Characteristics and classification of voltage disturbances

The monitoring system includes three modules as shown in

Figure 2.3. Voltage disturbance characteristics as shown in Figure

2.4.

Sensitive

equipment

Factories

Grid

Page 9: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

7

Figure 2.3. Modules of voltage disturbance monitoring system.

Figure 2.4. Definition of voltage disturbances according to 1159-2009 [32].

2.3. Background of wavelet transform

2.3.1. Wavelet transform (WT)

2.3.2. Discrete wavelet transform (DWT)

2.3.3 Mother wavelet selection

2.4. The proposed method

The algorithm of proposed method is shown in Figure 2.7.

There are 3 main parts: (1) – This is the signal processing unit using

low-pass filters and A/D conversion to get the voltage digital signal

form. (2) - This component combines DWT and ADALINE to extract

the characteristics of voltage signal that is: duration and magnitude of

the event from the input voltage signal. (3) – This is voltage

Thresholds and

settings

Reference

data

Steady state measurement

Module of

DAQ and

trigger

Module of

classification

system

Module of

monitoring

results

Alarm/

Trip

Event log:

Type, amplitude,

duration

statistics:

Trends, charts.

TU

Grid

Monitoring point

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

0.5 cycles 30 cycles

Instantaneous

Momentary

Temporary

Short-term voltage variations Long-term voltage

variations

3 s 1 min

Over-

voltage

Under-

voltage

Long

interruption

Sag Swell Interruption

Ev

ent

ma

gn

itu

de

(p.u

)

Duration of event

Note:

Page 10: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

8

disturbance classification unit from the characteristic extracted earlier

to return the result of the types of voltage disturbance. The

classification algorithm is shown in Figure 2.8.

Figure 2.7. Characteristic determination and voltage disturbance

classification

2.4.1. Determine J levels in DWT

DWT multi-resolution analysis transforms the original signal

in time domain to time domain-frequency. Assuming voltage signal

with sampling frequency is fs, while the approximation coefficients

(Aj) and detail coefficients (Dj) with different frequency bands.

2.4.2. Voltage amplitude estimate by ADALINE

ADALINE is a form of adaptive filter used to extract the signal

in the noise environment using two-layer feedforward neural

network, with N inputs and one output [66], [8]. ADALINE has

many advantages as follows: online training based on the change in

the input and output response; Self-adaptive algorithm is applied to

train the network weights; Simple structure and easy integration of

the hardware.

2.4.3. Voltage disturbance classification

Signal

processing;

Lowpass filter

u(t) A/D conversion

u(n)

D1(n) AJ(n)

ADALINE

U1(n)

Idendifying:

- Duration

- Magnitude

Classifying

voltage

disturbances

Classification

results

DWT using Db6

with J levels

(1) (2)

(3)

Page 11: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

9

Figure 2.9. Voltage sag

characteristics using the method.

Figure 2.10. Voltage swell

Characteristics using the method.

2.5. The results of the proposed method

2.5.1. Signal mathematical model of voltage disturbances

To evaluate the effectiveness of the proposed method, voltage

disturbance data is created by using mathematical equations:

sin |( )

sin

m s e

dis dis s e

U t if t t t tu t

U t if t t t

(2.27)

Using Matlab software to create signal samples by using (2.27)

with a sampling frequency of 512 samples/cycle for the fundamental

frequency of 50 Hz, with the voltage disturbance parameters within

the limits according to IEEE Std. 1159-2009 standard.

2.5.2. Electromagnetic transient software by Matlab/Simulink

Matlab/Simulink software is used as a tool for modeling IEEE

34 buses distribution netword [77], some simulation cases are

considered to simulate and voltage in a number of buses are kept to

create a database for studies assessing the effectiveness of the

proposed method.

Error! No text of specified style in document..1.

b) D1, (c) (U1 .

ts te

50% sag

Error! No text of specified style in document..1.

1 1

ts te

30% swell

Page 12: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

10

Figure 2.12. The voltage profile is in grid IEEE 34 when faults occurs at bus 836.

2.5.3. Accuracy assessment of the method estimates the V-D-A

The time and amplitude estimation error:

890 890

890

'

% 100u

t dt dt

U U

U

(2.34)

2.5.4. Application for the voltage waveforms

Figure 2.17. Case 1.

Figure 2.18. Case 2.

Page 13: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

11

Figure 2.19. Case 3.

2.7. Conclusion

DWT is used in this dissertation to extract the typical

characteristics of voltage disturbances: voltage sag, voltage swell and

voltage interruption. Detail level 1 (D1) coefficients of DWT is very

sensitive to sudden changes in the signal, so it is used to determine

the beginning and end of the signal disturbance.

Using the number of analysis levels consistent with the

sampling frequency of the signal voltage to generate approximately

AJ coefficients which contain only the fundamental frequency range

desired. AJ approximation coefficient is considered as input of

ADALINE to estimate the amplitude of the voltage signal.

Modeling data to assess the effectiveness of the proposed

method is done by mathematical modeling and simulation of

electromagnetic transients using Matlab/Simulink software for IEEE

34 buses network. Short-circuits are simulated at several locations as

well as the changes in value of the fault impendance and event

duration to create database to evaluate the proposed method.

Page 14: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

12

CHAPTER 3. DETERMINING VOLTAGE SAG INDICES FOR

SENSITIVE LOADS IN DISTRIBUTION NETWORK

3.1. Introduction

3.2. Determining voltage sag indices in power systems

3.2.1. The method of sequence components

3.2.2. The method of six RMS voltages

3.3. Voltage sag indices according to IEEE Std. 1564-2014

3.3.1. The single event indices

3.3.2. The site indices

3.3.3. The system indices

3.4. Voltage sag indices according to IEEE Std. 1564-2014

Figure 3.7. The proposed method for determining voltage sag indices.

n = 1

Application of the proposed method

in Chapter 2

1 Determining duration and magnitude of

voltage sag

2 Calculating voltage sag energy and severity

3 Classifying types of voltage sag

Voltage sag?

n = n + 1

n > N ?

Calculating the site indicies: SARFIX,

SARFISEMI, SARFIITIC and IEC table

The input database

including N samples

No

Yes

Yes

No

Voltage quality evaluation based on the

voltage sag indicies

Page 15: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

13

The proposed method for determining voltage sag indices in

order to evaluate voltage quality in distribution network are

implemented by using the proposed method in Chapter 2. The

algorithm is shown in Figure 3.7. The inputs are database of voltage

disturbance events which were gathered from different sources such

as the power quality monitoring, fault record equipment, protection

relay, intelligent measurement equipment, etc. The database is

voltage signals sampled from events occurred at monitoring points.

3.5. Calculating voltage sag indices

3.5.1. Determining the single-event indices of voltage waveforms

The author uses voltage waveforms occurred in three-phase

power systems to evaluate the proposed method in determining

voltage sag characteristics and indices. The database of voltage

waveforms are used from the sample sources in the power quality

analysis program PQDiffractor [80]. From the sample database

available in the program, the author chooses 3 voltage sag waveforms

as shown in Figure 3.8(a), Figure 3.9(a) and Figure 3.10(a) to

calculate voltage indices. Figure 3.8(b), Figure 3.8(b) and Figure

3.10(b) are the results of their RMS voltages. The single-event

indices are also determined using the proposed method.

Figure 3.8. The results of the single-event voltage sag (Sample 1).

0 0.05 0.1 0.15 0.2 0.25-1

-0.5

0

0.5

1x 10

5

uabc (

V)

a) Dien ap ba pha

Ua

Ub

Uc

0 0.05 0.1 0.15 0.2 0.250.7

0.8

0.9

1

Uabc (

p.u

)

t (s)

b) Dien ap RMS

Error! No text of specified style in document..1 theo

K các c s sự kiện

Biên độ lõm áp: U% = 76.39%

h i gian t n t i: c k

ng l ng mất: Esv = 3.1340 s

độ nghiệm trọng: Se = 0.3922 (p.u)

D ng lõm áp: Ca

iện áp đ tr ng: V = 0.7480 (p.u)

ệ s thu n ngh h: F = 0.9420

Page 16: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

14

Figure 3.9. The results of the single-event voltage sag (Sample 2).

Figure 3.10. The results of the single-event voltage sag (Sample 3).

3.5.2. Application for the tower Dang Minh, HCM city

3.5.2.1. The results of single-event indices

This dissertation uses the real database from events occurred

and recorded by power quality monitoring PQube installed at the

tower Dang Minh, HCM city. Figure 3.11 shows the results of

severity, non-severity voltage sag and other events in July and

August, 2015 at the tower Dang Minh.

Figure 3.11. The analysis results of voltage sags in July and August, 2015.

0 0.1 0.2 0.3 0.4 0.5 0.6-2

-1

0

1

2x 10

4

uabc (

V)

a) Dien ap ba pha

Ua

Ub

Uc

0 0.1 0.2 0.3 0.4 0.5 0.60.7

0.8

0.9

1

Uabc (

p.u

)

t (s)

b) Dien ap RMS

Error! No text of specified style in document..1 theo

K các c s theo sự kiện

Biên độ lõm áp: % = 80.96%

h i gian t n t i: c k

ng l ng mất: Esv = 2.423 s

độ nghiêm trọng: Se = 0.6283 (p.u)

D ng lõm áp: Cb

iện áp đ tr ng: V = 0.7770 (p.u)

ệ s thu n ngh h:

Error! No text of specified style in document..1 theo

0 0.02 0.04 0.06 0.08 0.1 0.12

-1

0

1

x 104

uabc (

V)

a) Dien ap ba pha

Ua

Ub

Uc

0 0.02 0.04 0.06 0.08 0.1 0.120.7

0.8

0.9

1

Uabc (

p.u

)

t (s)

b) Dien ap RMS

K các c s theo sự kiện

Biên độ lõm áp: U% = 81.16%

h i gian t n t i: c k

ng l ng mất: Esv = 2.3160 s

độ nghiêm trọng: Se = 0.6283 (p.u)

D ng lõm áp: Cc

iện áp đ tr ng: V = 0.807 (p.u)

ệ s thu n ngh h: F = 0.9350

(a)

(b)

Error! No text of specified style in document..1 phân tích

Page 17: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

15

3.5.2.2. The results of the site indices

Figure 3.12. SARFICurve indices according to type of curve of July, 2015.

3.6. Conclusion

From the analysis results in this chapter, every type of voltage

sag in three-phase power system is characteristed by type, magnitude

and duration time.

When all events at single monitoring position are determined

the characteristics and indices of the single-event then the site indices

are also indentified to evaluate voltage quality at the position. The

site indices are used in this dissertation including: SARFIX, SARFIITIC,

SARFISEMI, voltage sag table, energy of voltage sags and severity of

voltage sags.

In this chapter, a calculation program indices and statistic the

voltage sag events are build-up in Matlab software. Applying the

method which is proposed in Chapter 2 to calculate voltage sags and

compare with the standard method according to IEEE Std. 1564-

2014.

In order to evaluate the proposed method, a database of voltage

sag waveforms are extracted from the power quality analysis program

PQDiffrator to evaluate the proposed method. In addition, voltage

sag events recorded at the tower Dang Minh, HCM city are also used

to calculate the voltage sag indices.

T ng i n: 545

S vi ph ITIC: 349

T ng i n: 545

S vi ph SEMI: 349

Page 18: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

16

CHAPTER 4. VOLTAGE SAG/SWELL MITIGATION FOR

SENSITIVE LOADS IN DISTRIBUTION NETWORK

4.1. Introduction

4.2. The main characteristics of voltage sag

4.2.1. Voltage sag magnitude

Let we consider a 22 kV power system as shown in Figure 4.4.

The influence of short-circuit power of grid source to voltage sag

magnitude as shown in Figure 4.5.

Figure 4.5. The influence of short-

circuit power to magnitude.

Figure 4.6. The influence of cross

area of power lines to magnitude.

4.2.2. Time duration

4.2.3. Phase angle jump

4.3. The impacts of voltage sags

4.4. Voltage sag/swell mitigation methods

4.5. Voltage sag/swell mitigation using DVR

4.6. The proposed method of voltage sag impact study to the

sensitive loads

The impact evaluation of voltage sag to sensitive loads in

distribution network often implement by using physical models [12].

However the evaluation by using that method needs to have a real

voltage sag source equipment, high cost and difficult implemention.

0 5 10 15 20 250

0.2

0.4

0.6

0.8

1

L (km)

Usa

g (

p.u

)

SN

= 750 MVA

SN

= 200 MVA

SN

= 75 MVA

0 5 10 15 20 250

0.2

0.4

0.6

0.8

1

L (km)

Usa

g (

p.u

)

F = 50 mm2

F = 120 mm2

F = 240 mm2

Page 19: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

17

Therefore in this dissertation, the author proposes a method based on

function modules in Matlab/Simulink software to determine

charateristics of voltage sag and its effects to sensitive loads in

distribution networks. The algorithm of the proposed method is

shown in Figure 4.20.

Figure 4.20. The proposed method for studying voltage sag impacts to

sensitive loads.

4.6.1. Voltage sag source module

4.6.2. Voltage sag characteristic determination module

4.6.3. Voltage sag impacts to AC-DC-AC conversion

+ Object description: Figure 4.24 shows the study model of

voltage sag impacts to AC-DC-AC conversion [76].

The three-phase controlled

voltage source model

Sensitive load model

Voltage sag are created by

mathematic model,

simulation or real data

Three-phase voltage

sag source model

Three-phase measurement

The signals are amplified

according to voltage level

feed in sensitive loads

Determination model of

voltage sag characteristics:

magnitude and duration

Analysis model of

voltage sag impacts to

sensitive loads

Page 20: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

18

Figure 4.24. A study of voltage sag impacts to AC-DC-AC conversion.

+ The results: Voltage sag effects to the operation of AC-DC-

AC conversion if it make the DC voltage of the conversion decreases

below the minimum DC voltage (UDCmin) then the conversion will be

switch off the grid [14]. Howerver each type of voltage sag will have

the different impacts to the operation of AC-DC-AC conversion.

Let’ uppo e that V=0.5 (p.u), the i pact of voltage ag type A and

C to the AC-DC-AC conversion operation respectively in Figure 4.25

and Figure 4.26.

Figure 4.25. The impacts of voltage

sag type A to AC-DC-AC.

Figure 4.26. The impacts of voltage

sag type C to AC-DC-AC.

The dependence of DC minimum voltage (Udcmin) at output of

the conversion depend on the characteristic voltage (V) and duration

time of voltage sag types. This is shown in Figure 4.28 to Figure 4.34

re pectively voltage ag type A, B,…, G.

Page 21: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

19

Figure 4.28. The dependence of DC

minimum voltage (type A).

Figure 4.29. The dependence of DC

minimum voltage (type B).

4.7. DVR application to mitigate voltage sag/swell

4.7.1. The proposed configuration of DVR

The configuration of DVR is used in this section is shown in

Figure 4.35.

Figure 4.35. The configuration of DVR.

4.7.2. Control system of DVR

The block diagram of DVR control system uses the d-q-0

transform method shown in Figure 4.36.

Zs

Ngu n T i

Udvr

Us Ut

It

Error! No text of specified style in document..1

DVR.

Cfa

Lfa

S1 S3

S2 S4

C1

C2

Bộ điều hiển

Udc

Page 22: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

20

Figure 4.36. The DVR control algorithm base on the d-q-0 transform.

4.7.3. The results of DVR to mitigate voltage sag/swell

The DVR model proposed in this study is modeled in

Matlab/Simulink shown in Figure 4.37.

Figure 4.37. The DVR model to mitigate voltage sag/swell.

4.7.3.1. Voltage sag

Supply voltage Us Referrence voltage

Uref

Convert to d-q-0 Convert to d-q-0

Convert to abc

PWM signals

Comparator PLL

VSC

Page 23: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

21

Lets three-phase voltage sag has Usag = 0.5 pu occurs at source

side beginning at ts = 0.2 s and ending at te = 0.4 s. Three phase

source voltages decrease to 0.5 p.u in duration 0.2 – 0.4 s shown in

Figure 4.38(a). When voltage sag is detected, DVR will create

compensation voltages series to source voltages with waveforms in

Figure 4.38(b) to compensate voltage sag caussed.

The single-phase voltage sag occurs in source side is

considered in Figure 4.39. In this case, phase A occurs sag in

duration 0.2-0.4 s shown in Figure 3.39(a). When voltage sag is

detected the DVR will create compensation voltage on phase A

shown in Figure 4.39(b). The results of load voltage is remained at

nominal level in that duration as shown in Figure 4.39(c). Therefore

the load is not effected by voltage sag at source side.

Figure 4.38. Three-phase sag.

Figure 4.39. Single phase sag.

4.7.3.2. Voltage swell

Lets consider three-phase voltage swell with Uswell = 1.5 p.u

occurs in source side beginning at ts = 0.2 s and ending at te = 0.4 s.

0.1 0.2 0.3 0.4 0.5

-1

0

1

Us

(p.u

)

(a) Dien ap nguon

0.1 0.2 0.3 0.4 0.5

-1

0

1

Udvr

(p.u

)

(b) Dien ap DVR

0.1 0.2 0.3 0.4 0.5

-1

0

1

Ut

(p.u

)

(c) Dien ap tai

t (s)

0.1 0.2 0.3 0.4 0.5

-1

0

1

Us

(p.u

)

(a) Dien ap nguon

0.1 0.2 0.3 0.4 0.5

-1

0

1

Udvr

(p.u

)

(b) Dien ap DVR

0.1 0.2 0.3 0.4 0.5

-1

0

1

Ut

(p.u

)

(c) Dien ap tai

t (s)

Page 24: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

22

Three phase voltage at source side will increase to 1.5 p.u in that

duration as shown in Figure 4.39(a). When voltage swell is detected,

DVR will create the compensation voltage as waveform in Figure

4.41(b) to compensate voltage swell. The result of load voltage is

remained at nominal level 1.0 p.u as shown in Figure 4.41(c) in that

duration. Therefore the load is not effected by voltage swell in source

side.

The single phase voltage swell at source side is considered as

Figure 4.42. In this case, phase A is swell in duration 0.2 – 0.4 s as

Figure 4.42(a). When voltage swell is detected then DVR will create

voltage to compensate on phase A as shown in Figure 4.42(b). The

results of load voltage is remained at nominal level as shown in

Figure 4.42(c). Therefore load is not effected by swell in source side.

Figure 4.41. Three-phase swell.

Figure 4.42. The single-phase swell.

4.8. Conclusion

This chapter proposed a method to study voltage sag impacts

to sensitive loads in distribution networks based on modules and

0.1 0.2 0.3 0.4 0.5-2

0

2

Us

(p.u

)

(a) Dien ap nguon

0.1 0.2 0.3 0.4 0.5-2

0

2

Udvr

(p.u

)

(b) Dien ap DVR

0.1 0.2 0.3 0.4 0.5-2

0

2

Ut

(p.u

)

(c) Dien ap tai

t (s)

0.1 0.2 0.3 0.4 0.5-2

0

2

Us

(p.u

)

(a) Dien ap nguon

0.1 0.2 0.3 0.4 0.5-2

0

2

Udvr

(p.u

)

(b) Dien ap DVR

0.1 0.2 0.3 0.4 0.5-2

0

2

Ut

(p.u

)

(c) Dien ap tai

t (s)

Page 25: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

23

function blocks in Matlab/Simulink software contribute in the

research, evaluation of voltage sag impacts to the operation of

sensitive loads in distribution networks.

Application of the proposed method to research voltage sag

impacts to AC-DC-AC conversion operation. The simulation results

are based Matlab/Simulink model which shows voltage sag events

occurs in short-time duration but they can effect to the operation of

the sensitive equipment.

Application of DVR to mitigate voltage sag/swell for sensitive

loads in distribution networks. The configuration and control method

based on the d-q-0 transform are proposed and modeled in Matlab/

Simulink. Three-phase and single-phase voltage sag/swell are studied

in this work to evaluate the proposed method.

CONCLUSION AND RECOMMENDATION

1. Conclusion

Based on research purposes, dissertation entitled “A tudy of

voltage disturbances in distribution networks” has novel

contributions in the field of voltage disturbance classification and

mitigation research in distribution networks as following:

1. This dissertation proposes a voltage disturbance

classification method in distribution network based on discrete

wavelet transform (DWT) and adaptive neural network (ADALINE).

The proposed method uses DWT to analysis the input voltage signal

to J levels which is determined according to the sampling frequency

of the input voltage signal. Therefore this transform will create an

approximation coefficient at level J (AJ) which only contains the

fundamental frequency. Then the detail coefficient (D1) is very

Page 26: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

24

sensitive with the changes in the input signal, therefore it is used to

detect the beginning and ending time of the voltage disturbance.

2. Application of the proposed voltage disturbance

classification method to identify voltage sag indices according to the

IEEE Std. 1564-2014 standard for determining voltage sag indices

including the single-event, the site and the system indices. Then the

indices are used to evaluate the severity of each voltage sag event and

each monitoring site for sensitive loads in distribution network.

3. A method to analysis voltage disturbance effects to sensitive

loads especially voltage sag in distribution network. This method is

used to analysis the effects of different voltage sag types from

mathematic model, electromagnetic simulation software or real

waveforms recorded by power quality monitoring equipment.

4. The control system of dynamic voltage restorer (DVR) is

proposed to mitigate voltage sag/swell effects for loads which are

sensitive to voltage disturbances especially voltage sag/swell in

distribution network based on a-b-c to d-q-0 transform for voltage

signal at source side.

2. Recommendation

Based on the research results of this dissertation, some

tendicies in the future are proposed as follows:

1. Researching voltage disturbance detection and

classification with data connection through Internet.

2. Constructing voltage disturbance monitoring system at

control centers in order to collect, analysis and evaluate indices on

distribution network.

3. Selecting DVR location and capacity installed on

distribution network to decrease harmfuless of voltage sag/swell.

Page 27: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

PUBLICATIONS OF THE AUTHOR

1. Dinh Thanh Viet, Nguyen Huu Hieu, Ngo Minh Khoa (2016),

“A Method for Monitoring Voltage Di turbance Ba ed on

Discrete Wavelet Transform and Adaptive Linear Neural

Networ ”, International Review of Electrical Engineering

(SCOPUS), Vol. 11, No. 3 (2016), pp. 314-322.

2. Đinh Thành Vi t, Nguyễn Hữu Hiếu, Ngô Minh Khoa (2016),

“Xác định các đặc trưng của nhiễu lo n đi n áp d a trên biến đ i

wavelet rời r c và ng nơrôn tuyến tính thích nghi”, p hí

Khoa họ và Công nghệ - i họ à ẵng, S 7(104).2016,

Trang 21-26.

3. Đinh Thành Vi t, Nguyễn Hữu Hiếu, Ngô Minh Khoa, Đoàn

Đức Tùng (2016), “Ngăn chặn lõ /l i áp trên lưới đi n phân

ph i bằng thiết bị phục h i đi n áp động”, p hí Khoa họ và

Công nghệ - i họ à ẵng, S . 5(102).2016, Trang. 126-

131.

4. Đinh Thành Vi t, Nguyễn Hữu Hiếu, Ngô Minh Khoa (2015),

“Nghiên cứu các ch lõ áp nhằ đánh giá ch t lư ng đi n áp

trên lưới đi n phân ph i Vi t Na ”, p hí Khoa họ và Công

nghệ - i họ à ẵng, S . 11(96).2015, Quyển 1, Trang. 72-

75.

5. Đinh Thành Vi t, Nguyễn Hữu Hiếu, Ngô Minh Khoa (2015),

“Nghiên cứu nh hư ng của lõ áp đến các t i nh y c trên

lưới đi n phân ph i”, p hí Khoa họ và Công nghệ - i họ

à ẵng, S . 9(94).2015, Trang. 64-68.

6. Đinh Thành Vi t, Nguyễn Hữu Hiếu, Ngô Minh Khoa (2015),

“Phát hi n nhiễu lo n đi n áp bằng phương pháp biến đ i

Page 28: A STUDY OF VOLTAGE DISTURBANCES IN DISTRIBUTION NETWORKtailieuso.udn.vn/bitstream/TTHL_125/6207/2/NgoMinhKhoa.TT_E.pdf · distribution network. The root mean square (RMS) method The

wavelet rời r c”, p hí Khoa họ và Công nghệ - i họ à

ẵng, S . 5(90).2015, Trang. 110-115.

7. Dinh Thanh Viet, Nguyen Huu Hieu, Nguyen Le Hoa, Ngo

Minh Khoa (2015), “A Control Strategy for Dyna ic Voltage

Restorer”, Proceedings of The 11th IEEE International

Conference on Power Electronics and Drive Systems (PEDS

2015), 9 - 12 June 2015, Sydney, Australia.

8. Dinh Thanh Viet, Nguyen Huu Hieu, Ngo Minh Khoa (2014),

“S-Transform-based Decision Tree System for Power Quality

Di turbance Cla ification”, Journal of Science and

Technology, The University of Danang, No. 12(85).2014, pp.

100-105.

9. Ngo Minh Khoa, Dinh Thanh Viet, Nguyen Huu Hieu (2013),

“Classification of Power Quality Disturbances Using Wavelet

Transform and K-Neare t Neighbor Cla ifier”, Proceedings of

The 22nd IEEE International Symposium on Industrial

Electronics (ISIE 2013), May 28-31, 2013, Taipei, Taiwan.

10. Ngô Minh Khoa, Đinh Thành Vi t, Nguyễn Hữu Hiếu

(2013), “Sử dụng bộ lọc Kal an rộng giá át và phát hi n

i n ụt áp trên lưới đi n phân ph i”, p hí Khoa họ và

Công nghệ - i họ à ẵng, S . 8(69).2013, Trang. 25-30.