A Quick Tutorial on RSLogix Emulator 5000
RSLogix Emulator 5000 is a software simulator for the Allen Bradley line of Logix 5000
controllers (ControlLogix®, CompactLogix®, FlexLogix®, SoftLogix5800® and
DriveLogix®). The goal is to mimic the function of a PLC without the actual hardware and
thus do advanced debugging. More information can be found in the AB publication
LGEM5K-GR015A-EN-P.
As a quick introduction we’ll go through a simple example of setting up a simulation. This
involves three major steps.
Setting up the Chassis Monitor
To start the Chassis Monitor, click Start > Programs > Rockwell Software >
RSLogixEmulate 5000 > RSLogix Emulate 5000 Chassis Monitor.
Search
Tools for PLC programming
Recent Posts
Home Products Tutorial Directory Glossary Contrib
Allen Bradley
Siemens
Modicon
► PLC Simulator
► PLC Software
► PLC Programming
TI IndustrialAutomation
ti.com
Apps Portfolio Includes
PLCs, HMI, Factory
Communication & Much
More.
1. Setting up the chassis monitor.
2. Creating a connection in RSLinx.
3. Creating a project with associated emulation hardware.
Popular Articles
Automation Geeks
Navigation
RSS
Feed Me! Firefox and
Thunderbird make it easy to
keep up on the latest articles
from PLCdev
User login
Username: *
Password: *
Log in
When the emulator opens up you’re confronted with what looks like an empty chassis.
In slot 0 is an RSLinx module which has to be there for the emulator communications to
work. Your slot 1 might have another irremovable RSLinx module depending if you are
running RSLogix Enterprise.
From here we set up our hardware configuration for simulation. Our first step will be to add
the CPU. In this case it is a special one called an Emulation Controller.
PLC Timeline
Rockwell Automation's
Retroincabulator!
PLC Basics
PLC Simulators
Cheap PLCs
Book reviews
Online books
Recent posts
About
Create new account
Request new password
1. Click Slot > Create Module.
2. Choose the Emulator RSLogix Emulate 5000 Controller.
3. Chose slot 2 for the controller
4. Click OK to add it to the chassis monitor.
5. At this point you may be accosted with a message about previous configurations.
Just select Reset the Configuration to Default Values and click NEXT.
6. The next two dialog screens are for setting up the controller details. Click NEXT and
FINISH to accept all the defaults.
Next we’ll add some input/output simulation.
1. Click Slot > Create Module.
2. Choose the 1789-SIM 32 Point Input/Output Simulator.
3. Chose slot 3 for the simulator and click OK.
4. Accept the defaults for the setup by clicking NEXT and FINISH.
The chassis monitor will now have two emulation modules in it ready to go.
Creating a connection in RSLinx
Using RSLogix Emulator in a Project
To use the emulator in a project you must setup the hardware correctly.
1. Start RSLinx under Start > Programs > Rockwell Software > RSLinx > RSLinx
Classic
2. Click Communications > Configure Drivers.
3. Select the Virtual Backplane (SoftLogix 58xx) driver from the Available Driver
Types list.
4. Click Add New. The Add New RSLinx Driver dialog box appears. Click OK.
5. The new driver appears in the Configured Drivers list. Click Close.
1. Start the RSLogix 5000 software and create a new project.
2. Under the New Controller window type select an Emulator – RSLogix Emulator
5000 Controller. Give it a name and assign it to the same slot as the one you
put in the Chassis Monitor which in our example is slot 2. Click OK.
3. In RSLogix 5000's Controller Organizer, right click on the I/O Configuration
folder, and then click New Module. The software displays the Select Module
window.
4. Open the Other folder. Select the 1756-MODULE from the modules list and then
click OK.
5. The software displays the New Module window.
a. Add a Name for the card.
b. In the Slot field put the number that corresponds with the Chassis Monitor.
c. For the Connection Parameters put in the following and click OK
Assembly
Instance Size
Input 1 2
Output 2 1
Configuration 16 0
6. On the next Module Properties screen make sure to change the Requested
Packet Interval to 50.0 ms.
Ready, Set, Go
You are now ready to use the emulator just like you would any other PLC. Open Who
Active and set the path to the RSLogix 5000 Emulator.
The inputs can be simulated in the emulator’s Chassis Monitor by right clicking on the
module and selecting Properties. Under the I/O Data tab is the ability to toggle each
of the inputs on or off.
‹ An Introduction to RSLogix5000
Tags
up Getting Started with the Logix5000
PIDE Function Block ›
Note:
RSLogix Emulator is sometimes erroneously called RSEmulator.
( categories: )
l;l
Submitted by dheerajska on Thu, 2007-10-18 08:30.
What is Ladder Logic?
Confused
Submitted by Anonymous (not verified) on Tue, 2008-08-26 19:45.
I know this is going to sound stupid, but I am so very used to the old addressing system in
the SLC 500 and older Siemens PLC's that I cannot get the newer stuff down. I would like
to know, if I am troublshooting and think I have a bad outout on Control Logix using
RSLogix 5000 hw do I know or fond out what input or output the tag name database is
attached to? The older stuff I knew where the physical address was but with this I am
lost. Any help would be great.
Printer-friendly version
Allen Bradley
The tags for I/O is in this
Submitted by Tim Young on Wed, 2008-08-27 07:47.
The tags for I/O is in this format:
[Chasis Name].[Slot Number].[Input or Output].[Type of Data].[Terminal #]
Error in Connection Parameters screenshot
Submitted by Anonymous (not verified) on Wed, 2008-09-24 10:45.
In the table listed for Connection Parameters you have the correct info,
However in your screen shot, you show the Size of Input as 1 instead of 2.
Chassis Monitor
Submitted by Stewart (not verified) on Mon, 2008-11-03 21:17.
Under the chassis monitor i can't seem to pull throught the I/O controls. I can open the
I/O controls under the emulator, but this tab is not pulled through to RSLogix 5000.
Everything else here works perfectly - any thoughts.
Cheers
Stew
chassis monitor
Submitted by HURIS (not verified) on Tue, 2009-06-23 09:22.
Tenho um program do RSLOGIX emulaTE 5000 CHASSIS E TBM TENHO O CONTROL
LOGIX 5000 MAS NÃO CONSIGO ABRIE O EMUTATE, ENTRA UM TELA DIZENDO,
(UNABLE TO READ VIRTUAL BACKPLANE STATUS.PLEASE MAKE SURE THAT RSLINX
CLASSIC IS INTALALLED AND VIRTUAL BACKPLANE DRIVE IS RUNNING.)ALGUEM PODE
ME AJUDAR COMO RESOLVO ESSE PROBLEMA.
OBRIGADO.
Thanks..It worked really
Submitted by lovehurts (not verified) on Wed, 2009-12-16 05:56.
Thanks..It worked really well...But whenever I try to increase the no. of inputs
more than 2 and go online , the no. of inputs set to 2 only instead of my specified
number.
Hows it possible to emulate more than one inputs. This is because when you see
the I/O data tab in the 1789-Simulator module , we can change only one input.
Any suggestions?
I/O configuration
I/O configuration
Submitted by Anonymous (not verified) on Fri, 2010-03-05 21:48.
Hello All,
I am trying to understand a little more about the Emulator.
Let's say I have RSLogix5000 program with all the I/O cards already configured
(Not the simulated but actual I/O card). So when I am ready to download the
program I know I have match the processor slot # to match with the Emulator
processor slot #. But do I have to delete the actual I/O tree configuration
inside the program since the Emulator does not have the I/O cards configured?
or it does not matter, it will simply ignore the I/O configuration?
Thanks!
YOU CAN DELETE THE IO
Submitted by Anonymous (not verified) on Wed, 2012-08-08 10:35.
YOU CAN DELETE THE IO MODULES FROM IO CONFIGURATION ONLY IN
OFFLINE MODE AND THEN DOWNLOAD IT.
Estou com o mesmo problema.
Submitted by Anonymous (not verified) on Tue, 2011-11-29 07:07.
Estou com o mesmo problema. Como vc o resolveu?
Tks
Submitted by XCláudioX¬¬AmsterdaM (not verified) on Sun, 2010-12-05 10:34.
Muito obrigado pelo tutorial muito bom ótimo, deu certo aqui para cofigurar. com este eu
configurei e agora estou simulando minha I/O..
agradeço
HAHAHAHAHHA SPANISH !
Submitted by Anonymous (not verified) on Mon, 2011-01-31 20:21.
HAHAHAHAHHA SPANISH !
for full help of RSLogix
Submitted by Anonymous (not verified) on Thu, 2011-02-10 04:11.
for full help of RSLogix Emulator 500 visit
www.RSLogixEmulator500.blogspot.com
First, thanks for this
Submitted by Bill M (not verified) on Wed, 2011-02-23 11:57.
First, thanks for this tutorial, it really helped me figure out how to us the
RSLogix Emulate program. I was having problems getting the I/O modules
working, your info on how to configure them really helped.
Second, I think the right URL for the blog referenced above is
http://rslogixemulate500.blogspot.com
Oh Yes....!! Thanks My Dear
Submitted by Anonymous (not verified) on Mon, 2011-06-13 06:33.
Oh Yes....!!
Thanks My Dear Friend The Right URL Is:
http://rslogixemulate500.blogspot.com
RSEmulator500.blogspot.com
Submitted by Anonymous (not verified) on Wed, 2011-09-14 04:25.
RSEmulator500.blogspot.com doesn't seem to be out there
Its Portuguese...
Submitted by Anonymous (not verified) on Fri, 2011-04-29 10:46.
Its Portuguese...
That looks like Portuguese
Submitted by Anonymous (not verified) on Tue, 2012-11-13 12:41.
That looks like Portuguese to me
Muito Bom
Obrigado...
hahahahaha idiot
emulator mode controllogix
Submitted by Anonymous (not verified) on Mon, 2011-08-08 07:24.
dear sir,
i have done all the procedures what u have mentioned above but am not getting
programming screen to do program,if possible help me.
thank u
First,you should confirm
Submitted by Anonymous (not verified) on Sun, 2012-06-03 20:59.
First,you should confirm that the "input size" property of the
1789-SIM module is 2.Because the input in the "I/O DATA" property interface is for the
latter double word--I.Data[1].For the same reason, make sure you use I.Data[1] in
your program .OR, your toggle in 1789-sim module won't be reflected in the online
program. Second, you have to change the emulater CPU to "run" mode when you plan
to simulate your program. If you find you toggle in the 1789-SIM module can be
reflected in rslogix 5000 ,but your program don't work, one possible reason is your
emulater CPU is in "program" mode.
Don't work!!
Submitted by JoseCarlos (not verified) on Sun, 2011-08-28 16:28.
I've followed exactly all the steps shown in this tutorial but, i CANT change the status into
ladder program, into RSEmulate changed the status of the bits but into RsLogix 5000 do
nothing.
Any help??
Hi, I have done all the
Submitted by Itransition (not verified) on Fri, 2011-12-02 20:44.
Hi, I have done all the procedures that you have mentioned above but I am not getting
programming screen to do program, if possible help me please.