A nova geração de Solar-Log e o seu arranque
-
Upload
krannich-solar-portugal -
Category
Technology
-
view
621 -
download
8
description
Transcript of A nova geração de Solar-Log e o seu arranque
![Page 1: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/1.jpg)
www.solar-log.com 1 von 97
Solare Datensysteme GmbH
Installation Training
![Page 2: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/2.jpg)
www.solar-log.com 2 von 97
Solar-Log™ Installation Training
Agenda
Introduction Solar-Log™ 300, 1200 and 2000
Introduction Solar-Log™ WEB
Network basics and integration of Solar-Log™ into a network
Preparation of installation and inverter detection
Configuration of the Solar-Log™
Powermanagement (Feed-in Management)
![Page 3: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/3.jpg)
www.solar-log.com 3 von 97
Location
©2013 Google · GeoBasis-DE/BKG (©2009)
72351 Geislingen-Binsdorf
![Page 4: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/4.jpg)
www.solar-log.com 4 von 97
Company Introduction
Solare Datensysteme GmbH
Founded 2007 by
Thomas Preuhs and Jörg Karwath
Headquarter:
D–72351 Geislingen-Binsdorf
Employees in SDS: 80 (Jan 2014)
Employees in Company Group: 220 (Jan 2014)
Managing Directors and Partners:
Thomas Preuhs - Finance, Operations
Jörg Karwath - Technical Development
Guy Thouin - Marketing & Sales
Sold Solar-Log™ devices: > 217.000 SL units
(912,000 inverters, approx. 6,4 GWp)
![Page 5: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/5.jpg)
www.solar-log.com 5 von 97
Basics PV Monitoring
Inverter Monitoring
MPP Tracker Monitoring
Visualization
Smart-Home
Feed-in Management
![Page 6: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/6.jpg)
www.solar-log.com 6 von 97
Supported Inverter Brands
![Page 7: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/7.jpg)
www.solar-log.com 7 von 97
Solar-Log 300
Designed for residential plants <15 kWp
Basic Equipment
LCD-Status-Display
1x RS485/422
2x S0-In, 1x S0-Out
1x USB Port
Functions
Easy Installation
Monitoring via Solar-Log™ WEB
Smart-Home
Feed-in Management
Optional Equipment
WiFi
Bluetooth
GPRS
PM+
Meter
![Page 8: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/8.jpg)
www.solar-log.com 8 von 97
Solar-Log 300
Interfaces
![Page 9: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/9.jpg)
www.solar-log.com 9 von 97
Solar-Log 1200
Designed for plants <100 kWp
Basic Equipment
TFT-Touch-Screen 4,3“
LCD-Status-Display
1x RS485
1x RS485/422
2x S0-In, 1xS0-Out
1x Relay
1x USB Port
Functions
Easy Installation
Monitoring via Solar-Log™ WEB
Smart-Home
Feed-in Management
Mixed operation of different inverter brands possible
Optional Equipment
WiFi
Bluetooth
GPRS
PM+
Meter
![Page 10: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/10.jpg)
www.solar-log.com 10 von 97
Solar-Log 1200
Interfaces
![Page 11: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/11.jpg)
www.solar-log.com 11 von 97
Solar-Log 2000
Designed for plants <2 MWp, max. 100 inverters
Basic Equipment
TFT-Touch-Screen 4,3“
LCD-Status-Display
1x RS485
2x RS485/422 (1x with GPRS version)
2x S0-In, 1x S0-Out
1x Relay
1x Alarm
1x CAN
1x USB Port
Functions
Monitoring via Solar-Log™ WEB
Local monitoring
Mixed operation of different inverter brands possible
SCB / SMB connection possibe
Preconfigured Powermanagement packages
(at present, only available in Germany)
Optional Equipment
GPRS
PM+
![Page 12: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/12.jpg)
www.solar-log.com 12 von 97
Solar-Log 2000
Interfaces
![Page 13: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/13.jpg)
www.solar-log.com 13 von 97
Solar-Log™ Meter
PV Monitoring and Self-Consumption: measurement in and with one device!
Additional interface for the connection of up to 6 current transformers (CT)
Target group:
Plants for self-consumption without ripple control receiver (no PM+ model required)
Basic types:
Solar-Log™ 300 (up to 15kWp)
Solar-Log™ 1200 (up to 100kWp)
Interfaces:
6 CT can be connected
1, 2 oder 3 phases in different
combinations
Current transformers by SDS:
Closed types
CT 16 A primary current max.16A
CT 100 A-c primary current max.100A
Open types
CT 100 A-o primary current max.100A
Secondary current for all CTs: max. 200mA
Secondary current also to apply
for converters of other manufacturers.
CT 16 A
CT 100 A-c
CT 100 A-o
![Page 14: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/14.jpg)
www.solar-log.com 14 von 97
Solar-Log™ Meter
Operating Mode
Current transformers measure AC potential-free.
Current transformers have a defined ratio between primary and secondary current.
Solar-Log™ to calculate the power as follows:
Secundary current Isec is measured with the meter interface of the Solar-Log™
Voltage U is either configured in the Solar-Log™ or
the measured values of the inverters are being used.
Calculation of the power P by the Solar-Log™:
(Isec x ratio) x U = P
Isec
Iprimary
Quelle: Wikipedia User Biezl
![Page 15: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/15.jpg)
www.solar-log.com 15 von 97
Solar-Log™ Meter
Cabling
Installation of appliance,
single phase
Installation of appliance,
three phases
Installation of total consumption
Wiring symbol for current transformer (CT)
![Page 16: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/16.jpg)
www.solar-log.com 16 von 97
Smart-Home
Operating Mode
Solar-Log™
Control Logic
Configurable
pre-programmed
control logics
available
Smart-Plug
up to ten
switches can
be configured
Appliance
Consumption
Meter
Σ
Inverter
![Page 17: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/17.jpg)
www.solar-log.com 17 von 97
Solar-Log™ Operation
Via local Web Server
![Page 18: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/18.jpg)
www.solar-log.com 18 von 97
Solar-Log™ Visualization (Day)
Classic 2nd Edition Local user interface
![Page 19: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/19.jpg)
www.solar-log.com 19 von 97
Solar-Log™ Visualization (Month)
Classic 2nd Edition Local user interface
![Page 20: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/20.jpg)
www.solar-log.com 20 von 97
Solar-Log™ Visualization (Year)
Classic 2nd Edition Local user interface
![Page 21: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/21.jpg)
www.solar-log.com 21 von 97
Solar-Log™ Operation
Via Touch-Display (only Solar-Log™ 1200 and 2000)
![Page 22: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/22.jpg)
www.solar-log.com 22 von 97
Solar-Log™ WEB
Solar-Log™ WEB „Classic 2nd Edition“
Yield visualization
Inverter event protocol
Publicly visible or password protected
Access via home.solarlog-web.eu
Plant sizes <30 kWp* free of charge for web service
+ Basic features for (private) plant owners/end customers
+ Easy and fast registration process
*to differ in some countries (free up to 20 or 50 kWp , Italy, Spain, Portugal, Israel)
![Page 23: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/23.jpg)
www.solar-log.com 23 von 97
Solar-Log™ WEB
Solar-Log™ WEB „Commercial Edition“
• Central plant administration
• Remote configuration
• Clearly arranged overview
• Plant logbook for operation and maintenance
• Individual layout (CI) possible
• User-defined access rights
• Yield and error reports
• Costs according to plant size (first 30 days free of charge)
+ Professional „Full Service“ monitoring, ideal tool for O&M approach
+ Time and cost saving
www.demo.solarlog-web.com
(user: demo; password: demo)
![Page 24: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/24.jpg)
www.solar-log.com 24 von 97
Installation Training
Network basics
![Page 25: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/25.jpg)
www.solar-log.com 25 von 97
Network Setup
Starting point:
(WiFi) Router
Tasks:
To establish an internet connection
To administrate connected devices
(PC, notebook, mobile phones, Solar-LogTM
)
Solar-Log™
WEB
WiFi
Router
Solar-Log™ Smart-Plug
Internet
APP PC or laptop
![Page 26: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/26.jpg)
www.solar-log.com 26 von 97
To establish a connection (Router - Solar-Log™)
Connection Solar-Log™ - Router
• Directly via network cable
• Network sockets
Router
Solar-Log™ Smart-Plug
Internet
PC or
laptop
Printer
![Page 27: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/27.jpg)
www.solar-log.com 27 von 97
To establish a connection (Router - Solar-Log™)
PowerLAN
Solar-LogTM
in a network:
Connection via PowerLAN (dLAN®, Powerline)
Existing power lines are used for data transfer
To cross limitations created by house or flat
Solar-Log™ Router
Attention!
Please use wall sockets!
![Page 28: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/28.jpg)
www.solar-log.com 28 von 97
To establish a connection (Router - Solar-Log™)
Cable
Default: DHCP
IP address, subnet mask and Gateway can be set up manually, if requested
DNS can be defined optionally
Solar-Log™ Router Internet
![Page 29: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/29.jpg)
www.solar-log.com 29 von 97
optional
WiFi
Repeater
To establish a connection (Router - Solar-Log™)
Solar-Log™ WiFi and WiFi Router
Steps:
1. Activate WiFi with Solar-Log™
2. Search for networks / WPS
3. Encryption / Password
4. Check Status
Solar-Log™
WiFi
WiFi
Router
Internet
![Page 30: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/30.jpg)
www.solar-log.com 30 von 97
To establish a connection (Router - Solar-Log™)
Direct connection via cross-over cable
Solar-Log™ be connected directly via cross-over cable to a PC or a laptop
Solar-Log™ WiFi PC or laptop
![Page 31: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/31.jpg)
www.solar-log.com 31 von 97
Successful connection
Access the internal web server via internet browser
4 possibilities:
Solar-Log™ URL:
http://solar-log
Solar-Log™ URL, if more than one Solar-Log™ in the network:
http://solar-log-wxyz
IP address in DHCP range:
169.254.wx.yz
IP address defined at start up:
type in defined IP address
wxyz : last four digits of the serial
number of the Solar-Log™.
![Page 32: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/32.jpg)
www.solar-log.com 32 von 97
Successful connection
Access the internal web server via internet browser
Solar-Log™ menu can be
handled like a regular website
Welcome page of Solar-Log™
Start configuration
![Page 33: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/33.jpg)
www.solar-log.com 33 von 97
Connection established
Displaying the internal web server of the Solar-Log™
The menu is divided into four areas:
Main navigation (A)
Left navigation (B)
Tabs (C)
Configuration area(D)
The configuration site „Ethernet“ can be
found via the following path:
Configuration | Network | Ethernet
![Page 34: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/34.jpg)
www.solar-log.com 34 von 97
Installation Training
Installation
![Page 35: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/35.jpg)
www.solar-log.com 35 von 97
Preparation of installation
Inverter interfaces
In general:
all inverters have to be provided with one of the following
interfaces compatible with Solar-Log™
RS 485
RS 422
Ethernet
CAN
SMA:
different interfaces for different inverter series
RS485 – PiggyBack from SMA or Solare Datensysteme
SMA RS485 Data Module DM-485-CB
Quick Module
Speed Wire Module
RS 485 Data Module Type B
Fronius:
ComCard has to be retrofitted
Fronius inverters can only be used with RS 485/422 B interface
Not compatible with „Fronius Power Control Card“
![Page 36: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/36.jpg)
www.solar-log.com 36 von 97
Cabling Advices
Please use high quality cables:
LIYCY >=0,14mm2 or CAT 5/7 SSTP
Please consider manufacturers‘ requirements concerning UV stability and installation
For long distances, please use cables with a bigger diameter
Please use cable end sleeves for flexible wires
Please twist pairs and shielding
Please wire/cable from left to right
Please wire/cable from bright to dark colors
Wrong cabling = problem #1!
Please work very accurately.
Please do not try to save material.
![Page 37: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/37.jpg)
www.solar-log.com 37 von 97
Solar-Log™ RS485 Wireless Package
To replace the RS485 cabling by radio signals
Completely configured for specific inverter brands
Flexible use
Complete cable set including connecting cable for the inverter
Solar-Log™
RS485
RS485
![Page 38: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/38.jpg)
www.solar-log.com 38 von 97
Complete cabling of inverters to Solar-LogTM
Detection of inverters without Wireless Package (with Solar-LogTM
directly)
Connection cable set Wireless Package and inverter connection cable (socket plug)
No new detection of inverters required
Solar-Log™ RS485 Wireless Package
Installation
Attention: Please do not cut the original cable!
Configuration | Devices| Definition | Interfaces
![Page 39: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/39.jpg)
www.solar-log.com 39 von 97
Sensor Box Commercial
Sensor Basic
Reference measurement of solar irradiation
Measurement of module temperature integrated in device
Optional
Wind sensor
Ambient temperature
sensor
Up to 9 Sensor
boxes can be
connected in RS485
bus
Only one Sensor
basic can be
used
For residential
plants
Sensor Technology
RS 485 Irradiation Sensor
Not compatible with
inverters using RS422
SMA Tripower inverter series
![Page 40: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/40.jpg)
www.solar-log.com 40 von 97
Recording Self-Consumption
Via consumption meter (S0 or RS485) or Solar-Log™ Meter and current transformers (CT)
NS-Netz
Solar-Log™
PV plant Bi-directional Meter
Consumption meter or
current transformer CT
Appliance
Grid
Purchased
electricity
Self-consumption
Data line
![Page 41: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/41.jpg)
www.solar-log.com 41 von 97
Installation Summary
Steps
Registration with Solar-Log™ WEB services (portals)
Preparation of the inverters (e. g. to combine the interface, to define device address)
Correct cabling Solar-LogTM
and inverter(s)
Recommendation: please use pre-configured connecting cables of Solar-Log™
Select inverter brand in Solar-LogTM
device – start detection
Wait for the completion of the detection (please do not interrupt!)
Inverter configuration (MPP tracker power, module fields, names)
![Page 42: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/42.jpg)
www.solar-log.com 42 von 97
Installation Training
Configuration
![Page 43: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/43.jpg)
www.solar-log.com 43 von 97
Easy Installation
Step 1
Step 2
Step 3
Inverter detection (all relevant inverter manufacturers).
Specific to country, e.g. Germany: SMA / PowerOne / Kaco / SolarMax / Fronius
Establishing an internet connection.
Solar-Log™ to send basic configuration to the pool server.
WEB Commercial oder
Classic 2nd Server
When providing the Easy Installation Code, the Solar-Log™ „moves“ to the
selected server (SL WEB Commercial or Classic 2nd Edition). Configuration
can be performed via WEB then.
Easy
Installation
Server
(WiFi)
Router
Inverters
![Page 44: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/44.jpg)
www.solar-log.com 44 von 97
Easy Installation
Take over of the Solar-Log™ from Easy Installation Server to SL
WEB Server triggered by providing the Easy Installation Code
Final and complete configuration of Solar-Log™ via web interface
After final configuration, the Solar-Log™ to receive the final login
data for the portal server and to send yield data
Easy Installation Server
SL WEB Server
Commercial or Classic 2nd Edition
![Page 45: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/45.jpg)
www.solar-log.com 45 von 97
Configuration
Configuration | Network | Ethernet
Network settings:
- Ethernet
- WiFi
- GPRS
- Proxy (activation via Display advanced configuration at Configuration | System | Access control)
Network
Internet
Devices
Plant
Notifications
Special functions
Data
System
specific to Solar-Log™ version
![Page 46: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/46.jpg)
www.solar-log.com 46 von 97
Configuration
Configuration | Network | WiFi
Network
Internet
Devices
Plant
Notifications
Special functions
Data
System
![Page 47: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/47.jpg)
www.solar-log.com 47 von 97
Configuration
Configuration | Network | GPRS
Network
Internet
Devices
Plant
Notifications
Special functions
Data
System
![Page 48: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/48.jpg)
www.solar-log.com 48 von 97
Konfiguration
Configuration | Internet | Access type
Access type
Please select type of internet access
Network
Internet
Devices
Plant
Notifications
Special functions
Data
System
![Page 49: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/49.jpg)
www.solar-log.com 49 von 97
Configuration
Configuration | Internet | Portal
Settings for SL WEB Commercial Edition
Activate data transfer
Define Portal Server
Select Transfer interval
Save settings
Data transfer to portal server via HTTP
Network
Internet
Devices
Plant
Notifications
Special functions
Data
System
![Page 50: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/50.jpg)
www.solar-log.com 50 von 97
Configuration
Configuration | Internet | Portal
Settings for SL WEB Classic 2nd Edition
Activate data transfer
Define Portal Server
Select Transfer interval
Save settings
When selecting Classic 2nd Edition, local monitoring
is activated automatically.
Email access data has to be provided for notifications.
Data transfer to portal server via HTTP.
Network
Internet
Devices
Plant
Notifications
Special functions
Data
System
![Page 51: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/51.jpg)
www.solar-log.com 51 von 97
Configuration
Configuration | Internet | Local Monitoring
Local Monitoring
Activation via switch
- Configuration email data for SL WEB Classic 2nd Edition
- Emails, data export and backup to third-party server
- Extended data transfer export via FTP to „third“ external server – only one time per day (evening time) –
(more than 1 data transfer per day possible with FTP licence code)
Network
Internet
Devices
Plant
Notifications
Special functions
Data
System
![Page 52: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/52.jpg)
www.solar-log.com 52 von 97
Configuration
Configuration | Devices| Definition |Interfaces
Devices-Definition-Interfaces
The connected devices at each interface
are configured in this menu
Interfaces connected to Solar-Log™ Wireless
Package have to be activated
Page specific to Solar-Log™ version
Network
Internet
Devices
Definition
Detection
Configuration
…
![Page 53: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/53.jpg)
www.solar-log.com 53 von 97
Configuration
Configuration | Devices| Definition | Meter
Definition of current transformers (CT)
Operating mode:
Definition:
Select Solar-Log™ CT or type in ratio
= primary current/secundary current
Reference voltage:
measure voltage or use the voltage values provided by the inverters
Only for
Solar-Log™
Meter!
Network
Internet
Devices
Definition
Detection
Configuration
…
![Page 54: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/54.jpg)
www.solar-log.com 54 von 97
Configuration
Configuration | Devices| Definition | Smart-Home
Definiton of switch for Smart-Home functions
Select switch slot (max. 10)
Switch type:
Activate switch
Define Interface/Adress and Subadress
Save settings
Status and test:
Switch ON/OFF manually, switch status (0 or 1) and, if necessary, measured values (W, V and °C)
Network
Internet
Devices
Definition
Detection
Configuration
…
![Page 55: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/55.jpg)
www.solar-log.com 55 von 97
Hardware - Smart-Home
SmartPlugs
Allnet All 3075 V2, metering, 16A, Ethernet Art.No. 255429
Allnet All 3073 WLAN, no metering, 8 A, WiFi and Ethernet Art.No. 255616
Gude 1100 / 1101 metering, optionally temperature sensor, switch on wall plug
Gude 1102 / 1103 no metering, optionally temperature sensor, switch on wall plug
Relay
Smart-Home Relay Box (ADAM 4068) Art.No. 255656
8 Relays, switchable range from 30V/1A to 230V/250mA ,
own RS485 interface required (no inverters in the same bus, please!)
More compatible relays
Gude Expert PowerControl 1002: 4 relays, 230V, switch at device – top hat rail mounting
Gude Expert NetControl 2301: 4 relays, 230V, 1 sensor interface, switch at device – top hat rail mounting
![Page 56: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/56.jpg)
www.solar-log.com 56 von 97
Configuration
Configuration | Devices| Detection
Device-Detection
Start detection after definition
Inverters have to feed into the grid
Meters have to be connected
CTs will get automatically assigned to the meter
Network
Internet
Devices
Definition
Detection
Configuration
…
![Page 57: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/57.jpg)
www.solar-log.com 58 von 97
Configuration
Configuration | Devices| Configuration
List of all detected devices
Inverters
Maximum AC power
PAC correction factor
MPP tracker data
Module field
Generator power
Description
Meter
Operating mode
Maximum AC power
Description
Network
Internet
Devices
Definition
Detection
Configuration
…
![Page 58: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/58.jpg)
www.solar-log.com 59 von 97
Excursion Module Fields
Module fields are defined by equal solar panel types, same module pitch and same module direction:
All modules of same type and same pitch and direction –> same module field
Different pitch and direction and/or different module types –> different module fields
Inv1 – MPP1
Module field 1
Inv1 – MPP 2
Module field 1
Inv1 – MPP3
Module field 2
Ro
of rid
ge
![Page 59: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/59.jpg)
www.solar-log.com 60 von 97
Configuration
Configuration | Devices| Order
Devices-Configuration-Order
Order of inverters can be changed by Drag&Drop
Network
Internet
Devices
Definition
Detection
Configuration
…
Inverter address or serial number
Inverter description
Internal number
![Page 60: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/60.jpg)
www.solar-log.com 61 von 97
Configuration
Configuration | Plant| Plant Groups
Plant Groups
Activate function
Define description
Klicking on symbol opens
a drop-down menu
Select inverters of this group
Save settings
Network
Internet
Devices
Plant
…
![Page 61: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/61.jpg)
www.solar-log.com 62 von 97
Configuration
Configuration | Plant
Menu items:
Plant groups
Graphic
Graphic scaling options
Forecast
Monthly shares
Time of sunrise and sunset
Yearly target [kW/kWp]
Compensation for electricity fed into the grid – several options:
Compensation for electricity fed into the grid
Compensation for electricity fed into the grid & remuneration for self-consumption
Compensation for electricity fed into the grid + self-consumption
Self-consumption
Costs (Electricity price) [€/kWh]
![Page 62: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/62.jpg)
www.solar-log.com 63 von 97
Configuration
Configuration | Plant | Tariff
Calculation of break even point
Different types of remuneration:
Feed-in tariff
Feed-in & self-consumption
Feed-in tariff
+ self-consumption
Self-consumption
![Page 63: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/63.jpg)
www.solar-log.com 64 von 97
Configuration
Configuration | Notifications| Addressee
Notifications - Address
Defining the email address
Second address separated by semicolon (;)
Further information by clicking on question mark
Network
Internet
Devices
Plant
Notifications
…
![Page 64: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/64.jpg)
www.solar-log.com 65 von 97
Configuration
Configuration | Notifications | Device Notifications
Device Notifications
Device notifications specific
for the inverters
Default settings do normally not
require adjustments
Network
Internet
Devices
Plant
Notifications
…
![Page 65: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/65.jpg)
www.solar-log.com 66 von 97
Configuration
Configuration | Notifications| Yield
Three different types of notifications
Yield (short)
Yield overview (all inverters)
Yield overview (all inverters & groups)
Yield notifications via email
or SMS
Defining the days and times
of the reports
Network
Internet
Devices
Plant
Notifications
…
![Page 66: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/66.jpg)
www.solar-log.com 67 von 97
Configuration
Configuration | Notifications| Power & Failure
Configuration of the monitoring parameters
Clicking „SAVE ALL…“ will result in
accepting the parameters for all devices
Clicking „SAVE MULTIPLE…“will result in
accepting the parameters for all connected
devices
Duration of interval = 5 min
Network
Internet
Devices
Plant
Notifications
…
![Page 67: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/67.jpg)
www.solar-log.com 68 von 97
Configuration
Configuration | Notifications| Power & Failure
Solar-Log™ to send emails if PM Powermanagement
is activated in order to monitor this function.
Configuration | Notifications| Alarm
Only applicable for Solar-Log 2000
The following actions can be triggered
by the alarm contact: email, SMS, relay, speaker.
Network
Internet
Devices
Plant
Notifications
…
![Page 68: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/68.jpg)
www.solar-log.com 69 von 97
Configuration
Configuration | Special functions | Smart-Home
Smart-Home - Control Logic:
Configurable pre-programmed control logics do
control the configured switches
(Configuration | Devices| Definition | Smart-Home)
Network
Internet
Devices
Plant
Notifications
Special functions
Smart-Home
Feed-In Management
…
![Page 69: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/69.jpg)
www.solar-log.com 71 von 97
Configuration
Configuration | Special functions | Smart-Home
Solar-Log™ calculating the surplus
Production:
• Based on information sent by the inverter
Consumption:
• Based on information sent by the connected consumption meter
Solar-Log™ always calculates average values within 5 minutes.
Changes and switchings only take into effect every within 5 minutes.
Please consider this when testing profiles!
Surplus:
• One profile:
production
– consumption
= surplus
• Several profiles:
production
– sum (typical nominal power of the activated profiles)
= surplus
![Page 70: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/70.jpg)
www.solar-log.com 74 von 97
Configuration
Configuration | Special functions | Smart-Home
Configuration of the Feed-in Management
The parameters are described in the next section of our training
Network
Internet
Devices
Plant
Notifications
Special functions
Smart-Home
Feed-In Management
…
![Page 71: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/71.jpg)
www.solar-log.com 75 von 97
Configuration
Configuration | Data | Initial Yield
Inital yield can be uploaded as CSV file
Data format:
DD.MM.JJ;Energy [Wh]
01.04.13;136435
02.04.13;138219
File can be created using MS EXCEL, Open Office Calc or any other text editor
Existing data will be overwritten
Network
Internet
Devices
Plant
Notifications
Special functions
Data
System
![Page 72: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/72.jpg)
www.solar-log.com 76 von 97
Configuration
Configuration | Data| Data Correction
Add or correct daily values
Values of a month or year must be defined for one specific day
Network
Internet
Devices
Plant
Notifications
Special functions
Data
System
![Page 73: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/73.jpg)
www.solar-log.com 77 von 97
Configuration
Configuration | Data | System Backup and Configuration | Backup| Reset
System and data backups
can be done separately
Options:
Restore from hard disk
Save settings to hard disk
Save settings to USB
Restore settings from USB
Network
Internet
Devices
Plant
Notifications
Special functions
Data
System
Backup will be saved daily if USB stick
is connected!
![Page 74: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/74.jpg)
www.solar-log.com 78 von 97
Configuration
Configuration | Data | Reset
Reset to factory settings
Reset yield data
Yield data can be deleted; Solar-Log™ does not need to get configured again
Reset inverter configuration (recommended before redetection, yield data reseted)
Factory settings
No change of firmware version
Solar-Log 1200 and 2000 will keep their network settings
Solar-Log 300 will activate DHCP then
Network
Internet
Devices
Plant
Notifications
Special functions
Data
System
![Page 75: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/75.jpg)
www.solar-log.com 79 von 97
Configuration
Configuration | System | Access Control
Network
Internet
Devices
Plant
Notifications
Special functions
Data
System
Display Access control -
protection with PIN code
Browser access control -
parts of the Solar-Log™'s browser menu can be
restricted with a password
Advanced configuration enabled:
Configuration | Network | Proxy
Configuration | Network | Large External Display
Configuration | Network | Forecast
Configuration | Special functions | Direct sales
![Page 76: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/76.jpg)
www.solar-log.com 80 von 97
Configuration
Configuration | System | …
Other Functions:
Language / Country / Time settings
Display
intensity setup, Slide Show
Licence administration
Firmware administration
Network
Internet
Devices
Plant
Notifications
Special functions
Data
System
![Page 77: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/77.jpg)
www.solar-log.com 81 von 97
Installation Training
Feed-in Management
![Page 78: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/78.jpg)
www.solar-log.com 82 von 97
Solutions from Solare Datensysteme GmbH
• Powermanagement: autonomous and remote controlled functions
• Active Power solutions
• Remote Control
• Reactive Power solutions
• Examples from Germany
Agenda
![Page 79: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/79.jpg)
www.solar-log.com 83 von 97
Preparation of installation
Solar-Log™ to provide different functions for active and reactive power requirements:
• Power reduction to a
specific percentage
• Optional: calculation
of self-consumption
• Fixed shift factor and
fixed Reactive Power
• Reactive Power based
on characteristic curve
P/Pn
• Voltage dependent
Reactive Power Q(U)
• Remote controlled Active Power
• Optional: calculation of self-
consumption
• Remote controlled Reactive Power
Autonomous
Active Power
Reactive Power
Remote
![Page 80: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/80.jpg)
www.solar-log.com 84 von 97
Active Power
Power reduction to a specific percentage
•To limit the inverter‘s power to the set percentage (X%) of the module‘s output
•To control Active and Reactive Power of the inverters through Solar-Log™
![Page 81: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/81.jpg)
www.solar-log.com 85 von 97
Active Power
Reduction to a specific percentage with the calculation of self-consumption
• Innovative solution to minimize losses from the fixed regulation (e. g. 70% or x%)
• Only if feed-in power (production - self-consumption) exceeds the maximum
inverters are regulated accordingly
• Using Solar-Log™ Smart-Home functions to optimize self-consumption
![Page 82: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/82.jpg)
www.solar-log.com 86 von 97
70% fix
Active Power - Example
Benefit of reduction to 70% with the calculation of self-consumption
70% with self-consumption
![Page 83: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/83.jpg)
www.solar-log.com 87 von 97
Remote Control – Option 1
Solar-Log PM+ - the additional interface for potential-free contacts
• Can be controlled from the grid operator‘s control centre
• Up to two ripple control receivers can be connected
• For Active and Reactive Power commands
• Configuration matrix for individual settings
• Up to 16 different levels (4 Bit)
![Page 84: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/84.jpg)
www.solar-log.com 88 von 97
Remote Control - Option 1
Via Ripple Control Receiver
• One-way communication (only relay commands)
• Can handle Active and Reactive Power commands
• Optional: calculation of self-consumption (consumption meter required)
Ripple Control Receiver
![Page 85: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/85.jpg)
www.solar-log.com 89 von 97
Remote Control – Option 2
Solar-Log PM+ Packages
• Control and response with combination of analog and digital signals
• PM+ profile for pre-configured settings (depending on requirements of utility company)
• Simple installation
• Universal solution for many inverter manufacturers
![Page 86: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/86.jpg)
www.solar-log.com 90 von 97
Remote Control and Response Signals
Via Remote Control Technology
• Bi-directional communication (commands and responses)
• Control and response with analog (0/4-20mA) and digital signals (relays)
• Control of the inverter via Solar-Log 1000 PM+ and 2000 PM+
Remote Control
Technology
![Page 87: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/87.jpg)
www.solar-log.com 91 von 97
Remote Control – Option 3
Solar-Log Modbus TCP PM Interface
• Direct connection with Remote Control Technology via Modbus TCP
• Without analog and digital signals
• Modbus TCP PM Interface License needed
![Page 88: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/88.jpg)
www.solar-log.com 92 von 97
Reactive Power Control
Solar-Log Modbus TCP PM Interface
Fixed shift factor
Fixed reactive power in Var
![Page 89: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/89.jpg)
www.solar-log.com 93 von 97
Reactive Power Control
Characteristic Curve P/Pn
Switching between different Reactive Power functions via digital signals possible
![Page 90: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/90.jpg)
www.solar-log.com 94 von 97
Power Grid Management
Utility Meter
Application range
• Controlling Reactive Power – characteristic curve Q(U)
• Measuring the voltage at the feed-in connection
• Possibility to measure in medium or low voltage grids
• Universal (Utility) Meter for response of actual production values over PM+Package
• PAC, cosφ , U, I, Q
Utility Meter
![Page 91: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/91.jpg)
www.solar-log.com 95 von 97
Reactive Power Control
Characteristic Curve Q(U)
Utility Meter
![Page 92: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/92.jpg)
www.solar-log.com 96 von 97
Solar-Log™ Master-Slave Network
For large-scale PV plants
max. 9 Slaves
![Page 93: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/93.jpg)
www.solar-log.com 97 von 97
Thank you for your attention!
![Page 94: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/94.jpg)
www.solar-log.com 98 von 97
Installation Training
Appendix
![Page 95: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/95.jpg)
www.solar-log.com 99 von 97
Inverter Interfaces
SMA
![Page 96: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/96.jpg)
www.solar-log.com 100 von 97
Inverter Wiring
SMA mixed cabling - PiggyBack original and PiggyBack by SDS
SMA SDS
SMA
SDS SDS
SDS SDS SDS
![Page 97: A nova geração de Solar-Log e o seu arranque](https://reader038.fdocuments.in/reader038/viewer/2022103000/5554514fb4c905b7428b503b/html5/thumbnails/97.jpg)
www.solar-log.com 101 von 97
Measurement Self-consumption
Electric plan and installation notes
Relevant points for the configuration of Solar-Log™
Meter (S0 or RS485) has to record total consumption
Configuration password-protected
Define Feed-in Management type
-> customer can not manipulate Solar-Log™
At Configuration | Devices| Configuration
define maximum AC power
and
generator power accordingly
Detected meter to be configured as consumption meter
Configuration | Devices| Configuration | Meter configuration
als Verbrauchszähler konfigurieren
*
* This meter is not required for this function