A new algorithm for power distribution system planning
-
Upload
rakesh-ranjan -
Category
Documents
-
view
214 -
download
1
Transcript of A new algorithm for power distribution system planning
A new algorithm for power distribution system planning
Rakesh Ranjan a,*, B. Venkatesh a, D. Das b
a FET, Multimedia University, Ayer Keroh Lama, 75450 Melaka, Malaysiab Electrical Engineering Department, IIT Kharagpur, Kharagpur 721302, India
Received 3 August 2001; received in revised form 10 January 2002; accepted 25 January 2002
Abstract
In this paper, an attempt has been made to develop a new algorithm for distribution system planning. The proposed algorithm
does not require prior knowledge of candidate substation location and can automatically select location of a substation, the optimal
feeder configuration and the optimal sizes of branch conductors while satisfying constraints such as current capacity, voltage drop
and heuristic rules. Several algorithms are proposed for distribution systems planning. A generalized algorithm is developed for
obtaining the optimal feeder path and the optimal location of substation on minimum loss criterion. Heuristic rules are incorporated
in the above algorithm. Another algorithm is for branch conductor optimizations. Modified load flow method is also presented in
the paper, which can handle composite load models. The load flow algorithm is used for solving radial distribution networks (RDN)
and branch conductor optimization algorithm. The load flow algorithm and branch conductor optimization techniques are used as
subroutine in the generalized distribution systems planning algorithm. Through numerical example the validity of proposed method
is verified. # 2002 Elsevier Science B.V. All rights reserved.
Keywords: Distribution systems; Load flow; Conductor optimization; Expert system
1. Introduction
The problem of distribution system planning is to find
the optimum location of the substation and the opti-
mum feeder configuration to connect the loads to the
substation. Many approaches to solve the distribution
system planning have been proposed [1�/9] but they
assume that new installation candidates are known
before hand. However, the assumption of the known
candidate locations of feeder or substation may simplify
the problem but can not give the optimum solution. Few
other methods [10�/12] have also been reported to find
optimum distribution system plan. All these methods
are based on mathematical programming techniques
such as branch and bound technique and mixed integer
programming method. For a given forecasted load,
these methods can yield feeder configuration and
substation location. However, all these methods fail to
incorporate heuristic rules. For distribution systems
planning or feeder expansion in the urban area it is
very difficult to find the space for substation and feeder.
Therefore, finding the optimal candidate location itself
will not suffice to solve the problem, heuristic rules need
to be incorporated for a feasible optimal distribution
system planning. Some researchers have made an
attempt to develop expert system for distribution
systems planning. Wong and Cheng [13] have proposed
artificial intelligence approach for load allocation in
distribution system. Hsu and Chen [14] have proposed
knowledge based expert system for distribution systems
planning. Braunner and Zobel [15] have also proposed
distribution systems planning using expert systems.
In the present work a generalized distribution systems
planning algorithm has been developed. Three algo-
rithms are presented for generalized distribution systems
planning. The first algorithm determines the optimal
feeder configuration. Second algorithm finds optimum
location of substation. A third algorithm optimally
selects branch conductor sizes. A load flow algorithm
that can handle composite load models is also presented
in the paper. Load flow algorithm is highly useful for
optimal feeder configurations, branch conductor opti-
mizations and system solutions.* Corresponding author. Fax: �/606-231-6552.
E-mail address: [email protected] (R. Ranjan).
Electric Power Systems Research 62 (2002) 55�/65
www.elsevier.com/locate/epsr
0378-7796/02/$ - see front matter # 2002 Elsevier Science B.V. All rights reserved.
PII: S 0 3 7 8 - 7 7 9 6 ( 0 2 ) 0 0 0 4 4 - 5
2. Modified load flow method
Load Flow algorithm developed by Das et al. [16] is
modified to incorporate composite load model. Theconvergence criterion is such that if, the difference of
voltage at every node in successive iterations is less than
0.0001 p.u. the algorithm has then converged. The
modified load flow algorithm does not require any
specific branch and node numbering scheme, however,
a simplified numbering scheme, which can be easily
understood, is used and discussed in Section 2.3.
2.1. Circuit model
In this section, a circuit model of Radial Distribution
Network (RDN) is presented. It is assumed that three-
phase RDN is balanced and can be represented by
equivalent single line diagram. Line shunt capacitance at
distribution voltage level is negligibly small. Fig. 1
shows the single line diagram of a sample RDN, andthe electrical equivalent of one branch of RDN is shown
in Fig. 2
2.2. Mathematical model of radial distribution networks
Mathematical model of RDNs can easily be derived
from Fig. 2 [16]:
I(j)�½V (m1)½ � d(m1) � ½V (m2)½ � d(m2)
Z(j)(1)
and,
P(m2)� jQ(m2)�V�(m2)I(j) (2)
where Z (j)�/R (j)�/jX(j), m1 and m2, the sending and
receiving end nodes, respectively; P(m2), sum of the real
power loads of all the nodes beyond node m2 plus the
real power load of the node m2 itself plus sum of the real
power losses of all the branches beyond node m2;
Q (m2), sum of the reactive power loads of all the nodes
beyond node m2 plus the reactive power load of thenode m2 itself plus sum of the reactive power losses of
all the branches beyond node m2.
From Eqs. (1) and (2) we can get:
½V (m2)½�ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiB(j)�A(j)
p(3)
where
A(j)�P(m2)R(j)�Q(m2)X (j)�0:5½V (m1)½2 (4)
B(j)�A2(j)�ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiZ2(j)(P2(m2)�Q2(m2))
p(5)
Real and reactive power losses in the branch j are:
LP(j)�R(j)(P2(m2) � Q2(m2))
½V (m2)½2(6)
and
LQ(j)�X (j)(P2(m2) � Q2(m2))
½V (m2)½2(7)
Since in this paper composite load modeling is
considered for the systems, therefore, flat voltage start(jV (i)j�/1.0 p.u. for i�/1. . .NB) is incorporated in the
algorithm. Using Eq. (3) voltage at each receiving end
node is computed. The new voltage is compared with the
old voltage in each iteration, and if the difference is less
than 0.0001 p.u. for each node the algorithm is assumed
to have converged.
½V (m2)�V (m2)?½B0:0001 p:u: for m2�1 . . . NB (8)
2.3. Node and branch numbering scheme
No systematic numbering scheme of laterals, sublat-erals, branches and nodes is required for the proposed
load flow solution of RDN. The numbering scheme does
not affect the convergence of algorithm or its computa-
tional efficiency. However, the numbering scheme
adopted for the program is presented considering Fig.
3 as test system. First, the nodes in the main feeder
(feeder starting from substation node 1) are numbered.
As it is seen in Fig. 3, these nodes are numbered 1, 2, 3,4, 5 and (1), (2), (3), (4) are branch numbers. The node
numbering and branch numbering starts from substa-
Fig. 1. Radial distribution networks.
Fig. 2. Equivalent of Fig. 1.
Fig. 3. Numbering scheme of RDN.
R. Ranjan et al. / Electric Power Systems Research 62 (2002) 55�/6556
tion that is assigned node number 1. Thereafter, the
nodes on the main feeder other than substation are
explored for the laterals. In Fig. 3 node 2 is having a
lateral. Then, node numbers and branch numbers areassigned starting from the parent node {node 2} of the
lateral 6, 7 and 8 are node number of the first lateral
from the substation and (5), (6) and (7) are the branch
numbers. Further, lateral under consideration is ex-
plored for the sublaterals, it is seen that node 7 is having
sublateral. Number is assigned for the sublateral node
starting from child node (node 7) as 9 and branch
number as (8). Again the main feeder is investigated forthe laterals and node 3 is observed to have lateral. Node
numbers 10 and 11 are assigned to the nodes ahead of
parent node (node 3) and branch numbers are (9) and
(10), respectively. There is no sublateral seen. So other
nodes of main feeder is examined and it is found that
process of node numbering is complete as there is no
further lateral emerging from the main feeder.
2.4. Load modeling
The balanced loads can be represented either asconstant power, constant current, and constant impe-
dance or as exponential load. The exponential loads are
basically combination of these based on proportion of
the type of consumer loads. At each node of the
distribution network the proposed algorithm is capable
of performing load flow calculations considering either
of load or combinations of all the above said loads. The
loads are modeled as:
P0(m2)�P(m2)(a0�a1V�a2V 2�a3V e1) (9)
Q0(m2)�Q(m2)(b0�b1V 2�b2V 2�b3V e2) (10)
In the algorithm e1�/1.38 and e2�/3.22 are consid-
ered for exponential load [17]. The first term of Eqs. (9)
and (10) represents constant power load, second term
represents constant current load and subsequent terms
represent constant impedance and exponential load.P (m2) and Q (m2) is the total real and reactive load at
the receiving node m2. For all the cases loads are
modeled such that:
a0�a1�a2�a3�1:0 (11)
b0�b1�b2�b3�1:0 (12)
2.5. Load flow calculation
The first step of load flow calculation is to find P (m2)
and Q (m2). A computer algorithm is developed tocompute it internally. Considering m2�/2 mathematical
expression for P (m2) and Q (m2) computation is given
below:
P(2)�XNB
i�2
PL(i)�XNB�1
i�2
LP(i) (13)
Q(2)�XNB
i�2
QL(i)�XNB�1
i�2
LQ(i) (14)
Once P (m2) and Q (m2) is computed, they are
updated for the composite load model by Eqs. (9) and
(10). Initially constant voltage for all the nodes is
assumed and real and reactive losses are set to zero.
After that, voltage at each node is calculated using Eq.
(3) and real and reactive power loss is calculated. Afterthe new voltage jV (i)?j of all the nodes (i�/1. . .NB) are
computed, convergence of the solution is checked from
Eq. (8). If it does not converge whole process is repeated
with the new set of voltages until convergence criterion
is satisfied.
3. Optimal branch conductor selection algorithm
Selection of optimal branch conductor size is extre-mely important in distribution system planning. The aim
of optimal conductor size selection is to design a feeder
so as to minimize an objective function, which is sum of
capital investment and capitalized energy loss costs for
the feeders. Optimal size of the branch conductor is
obtained using the load flow technique described in
Section 2.
3.1. Objective function
The basic problem is that of selecting a conductor
type for each branch of radial distribution feeder such
that the sum of the cost of capital investment and cost of
real power losses are minimized while maintaining an
acceptable voltage level.
The Levelized annual cost for the real power loss in
branch j can be calculated by:
c(j)�Kp�LP(j)�LP(j)�KE�T�Lsf (15)
where, LP(j) is real power loss in branch j ; Kp, levelized
annual demand cost of losses (Rs/kW); KE, energy cost
of losses (Rs/kWh); T�/8760 h and Lsf is loss factor.
While computing the annual cost by Eq. (15) load
growth is considered as:
Load�(1�g)n
where, g�/7% annual growth rate and n is the number
of years.
The levelized annual cost of capital investment for
branch j is:
z(j)�a�A(j)C�LEN(j) (16)
where, C is cost of the line (Rs/mm2 per Km); A (j ), the
R. Ranjan et al. / Electric Power Systems Research 62 (2002) 55�/65 57
cross sectional area of branch j (mm2); LEN(j ), length
of branch j and a is the carrying charge rates (feeder).
The objective function of branch j can be:
j(c; z)�c(j)�z(j) (17)
3.2. Constraints
1) Voltage: The voltage at every node in the RDN
must be above the acceptable voltage level i.e.
½V (i)½�Vmin for all i
2) Maximum current carrying capacity: Current flow-
ing through branch j with k type of conductor
should be less than the maximum current carrying
capacity of k type conductor. i.e. jI(j , k )jB/
CMAX(k ).
Optimal selection of conductor is obtained by branch
wise minimization technique using load flow algorithmdescribed earlier. Here all necessary steps for optimal
conductor selections are summarize for branch j :
1) Compute P (m2) and Q (m2) using Eqs. (13) and
(14).
2) Obtain P0(m2) and Q0(m2) using Eqs. (9) and (10)
for different load models.
3) Change the variables P (m2)�/P0(m2) and
Q (m2)�/Q0(m2).
4) Compute A (j) and B (j) using Eqs. (4) and (5) andthen compute jV (m2)j using Eq. (3) for all types of
conductor.
5) Compute real and reactive power loss LP(j ) and
LQ(j) using Eqs. (6) and (7) for all type of
conductors.
6) Compute c (j ) and z (j) using Eqs. (15) and (16) and
then compute j (c , z ) using Eq. (17) for all types of
conductor and store the values in the name ofvariablej j (j , k ) for k�/1, 2. . .
7) First find the minimum value of j j (j , k ) and check
whether voltage and current constraints are satisfied
or not. If constraints are satisfied then choose the
corresponding type of conductor. Otherwise next
lowest value of j j (j , k ) should be considered to
satisfy the constraints and so on till optimal branch
conductor is chosen optimally. This process isrepeated for all branches.
4. Expert system
Fig. 4 shows the architecture of proposed expert
system. It comprises rule base and database. Databaseincludes the load data, location of load points and
obstacles. Rule base includes the heuristic rules. Infer-
ence machine is designed to reach a proper distribution
network plan based on the data and rules in the
knowledge base.
5. Optimum location of substation
Total KVA load fed through a particular node is
TKVA (i) for i�/2. . .NB. TKVA (i) is always available
from the load flow computation. Optimal location of
substation is computed through an iterative algorithm.It is worth mentioning here that substation is chosen as
node 1 (i.e. S�/1). By minimizing real power loss, the
optimal location of substation {X (s ), Y (s )} for substa-
tion S , can be computed through the following iterative
algorithm [14,18]:
X (s)�
XNB
i�2
W (i)X (i)
XNB
i�2
W (i)
; Y (s)�
XNB
i�2
W (i)Y (i)
XNB
i�2
W (i)
(18)
where X (i), Y (i)�/X and Y coordinates of the load
point for i�/2. . .NB.
W (i)�TKVA(i)R(KT)
(½V (i)½2Ds(i)(19)
KT�/K (i�/1) stores optimum type of branch conductor
for i�/2. . .NB, which is obtained using load flow and
optimal branch conductor algorithm as described in
Sections 2 and 3.
Ds(i)�f(X (s)�X (i))2�(Y (s)�Y (i))2g1=2(20)
New initial location of the substation is chosen as:
X (s)�
XNB
i�2
X (i)P(i)
XNB
i�2
P(i)
; Y (s)�
XNB
i�2
Y (i)Q(i)
XNB
i�2
Q(i)
(21)
6. Description of the algorithm for optimal feeder path
For simplicity, only the investment costs of feeder are
compared for each distribution system plan. As the
investment cost is proportional to the feeder length, the
problem of minimizing investment cost reduces to that
of minimizing feeder length. Minimal path algorithm is
extremely suitable for distribution system planning.Taking nine load points shown in Fig. 5 as an example
whose X , Y coordinates are known it is logical to start
computation with new substation.
R. Ranjan et al. / Electric Power Systems Research 62 (2002) 55�/6558
6.1. Single feeder case
For single feeder case it is assumed that only one
feeder is emerging from the new substation. The set of
‘connected nodes’ S contains one node (new substation)
initially. All the other load points are in set of
unconnected nodes, i.e. S̄ :/
S�/{new substation}.
/S̄/�/{all the load points}.
The distance from any node in S̄ to the node in S is
computed and the one with shortest distance is added to
S . Let load point 5 be this node. Connect new
substation to node 5, the new set S and S̄/ will be:
S�/{new substation, 5}.
/S̄/�/{1, 2, 3, 4, 6, 7, 8, 9}.
A new feeder connecting the new substation and node
5 is implied in this process. Now compare the distancefrom any node in S̄ to any node in S . The node in S̄/ with
the shortest distance is added to S . Let load point 4 be
the node. Connect node 5 to 4. The set S & S̄/ will be:
S�/{new substation, 5, 4}.
/S̄/�/{1, 2, 3, 6, 7, 8, 9}.
Again compare the distance from any node in S̄ to
any node in S and find the minimum distance. Say
shortest distance exists between node 5 and 9. Therefore,
connect node 5 to 9. Now,
S�/{new substation, 5, 4, 9};
/S̄/�/{1, 2, 3, 6, 7, 8}.
This procedure is repeated until all the load points are
connected i.e. all the nodes are in S and S̄/ � /f (null). Itis worth mentioning here that through out the procedure
all the heuristic rules are satisfied.
6.2. Two feeder case
For this case it is assumed that only two feeders are
emerging from the new substation. The distance from
any node in S̄ to the node in S is computed and the two
nodes, which are close to the new substation (two
shortest distances), are added to S i.e. for two feedercase:
S�/{new substation, new substation}.
And say two nodes that are close to substation are 4
and 5, respectively.
Therefore,
S�/{(new substation, 4), (new substation, 5)};
Or S�/{S1, S2}.
where,
Fig. 4. Knowledge based expert system.
Fig. 5. Distribution system load points location (Taken as an
example).
R. Ranjan et al. / Electric Power Systems Research 62 (2002) 55�/65 59
S1�/{new substation, 4};S2�/{new substation, 5}.
Connect new substation to node 4 and new substation
to node 5. Thus:
/S̄/�/{1, 2, 3, 6, 7, 8, 9}.
Now compare the distances from any node in S1 and
S2 to any node in S̄ and find out the shortest distances,
say node 3 is nearest to node 4 (i.e. shortest distance is
D43) and node 9 is nearest to node 5 (i.e. shortest
distance is D59). Now find out minimum of D43 and
D59. Say D59 is minimum, so node 5 belongs to set
S2.Therefore,
S1�/{new substation, 4};
S2�/{new substation, 5, 9}.
Now connect node 5 to 9.Thus:
/S̄/�/{1, 2, 3, 6, 7, 8}.
Again compare the distances from any node in S1 and
S2 to any node in S̄/and find out the shortest distances.
Say node 3 is nearest to node 4 (i.e. shortest distance is
D43) and node 7 is nearest to node 9 (D79) and node 2 is
nearest to node 5 (D25). Find out minimum of the D43,
D79 and D25. Say D43 is minimum; connect node 4 to
3. Now node 4 belongs to set S1. Therefore,
S1�/{new substation, 4, 3};S2�/{new substation, 5, 9}.
and
/S̄/�/{1, 2, 6, 7, 8}.
This process is repeated until all load points areconnected, i.e. all the load points are in S and S̄/ � /f
(null). Through out the process all the heuristic rules are
checked.
Based on the procedure described above a generalized
algorithm for optimal feeder path has been developed
which can handle any number of feeder emerging from a
new substation and which also satisfies all the heuristic
rules.
7. Heuristic rules for distribution system planning
Following heuristic rules have been used for present
study:
. Distribution line is curved or discarded if there is a
big pond between two load points.
. If the line passes through cotton industries, it iscurved or discarded.
. If the line passes through commercial plantation area,
it is curved or discarded.
Fig. 6. Load points location (S/S not shown).
R. Ranjan et al. / Electric Power Systems Research 62 (2002) 55�/6560
Fig. 7. Optimal feeder configuration (Single Feeder Case).
Fig. 8. Optimal feeder configuration (Double Feeder Case).
R. Ranjan et al. / Electric Power Systems Research 62 (2002) 55�/65 61
. If the line passes through commercial complex, it is
curved or discarded.
. If the line passes through the residential area, it is
curved or discarded.
. Substation location is discarded if the land is too
expensive.. Substation location is discarded if it creates social
and environmental problem.
. Substation location is discarded if it falls near to
school; children play ground or boarding.
. Substation location is discarded if it falls nearer to the
shopping mall.
. Substation is discarded for any geographical installa-
tion restrictions.
8. Complete algorithm for distribution system planning
All necessary steps for the distribution systems
planning are summarized below:
1) Assume any initial location of substation.
2) Obtain optimal feeder path using optimal feeder
path algorithm.
3) Obtain load flow solution and optimum branch
conductors using load flow and optimum branch
conductor selection algorithm. Also compute total
real power loss {TP (1)}.
4) IT�/1.
5) Calculate substation location using Eq. (18).
6) Obtain optimal feeder path using optimal feeder
algorithm.
7) Obtain load flow solution and optimum branch
conductors using load flow and optimum branch
conductor selection algorithms and compute {TP
(IT�/1)}.
8) DIF�/jTP (IT�/1)�/TP (IT)j.9) IF DIFB/o go to Step-11.
10) IT�/IT�/1, go to Step-5.
11) Check whether heuristic rules for substation loca-
tion are violated or not? If rules are violated then
Fig. 9. Optimal feeder configuration (Three Feeder Case).
Table 1
Comparative results of single, double and three feeder configurations
Total length of feeder (km) Real power loss (kW) Reactive power loss (kVAr) jVminj in the feeder
Single feeder 97.63 173.50 125.06 jV33j�0.84916
Two feeder 99.00 56.18 37.49 jV33j�0.95282
Three feeder 100.67 50.12 31.43 jV33j�0.96081
R. Ranjan et al. / Electric Power Systems Research 62 (2002) 55�/6562
Fig. 10. Sub-optimal feeder configuration (Three Feeder Case).
Fig. 11. Optimal feeder configuration considering load growth after Vth year (Three Feeder Case).
R. Ranjan et al. / Electric Power Systems Research 62 (2002) 55�/65 63
compute new initial location of substation using
Eq. (21) and go to Step-2 otherwise go to Step-12.
12) Final Distribution plan is obtained.
9. Example
A study system of 54 nodes is considered. The
substation is numbered as node-1. Whole service area
is divided into several service squares and their X �/Y
coordinates are known. Load points data are given in
Appendix A. Fig. 6 shows the location of load points.
For the study four different types of conductor Squirrel,Weasel, Rabbit and Raccoon are considered. Computer
simulation has been carried out for single feeder, two
feeder and three feeder configurations of RDNs. It is
mentioned that for all the calculation constant power
loads are considered. Figs. 7�/9 shows the single, double
and three feeder radial distribution systems obtained by
the proposed algorithm. A comparison of results is given
in Table 1.Comparing the results it is observed that utility
should use two or three feeder configurations, since
power losses and total length of the feeder improves
significantly. Two and three feeder configuration shows
close competition as losses and voltage profile improves
but total feeder length increases. However, for over all
reliability considerations three feeder configurations are
finally selected as optimum planned radial distributionsystem. One of the suboptimal results is also presented
in Fig. 10 as reference for comparative study. After
incorporation of load growth of 7% in the algorithm the
simulation results indicate no change in the planned
distribution systems until fourth year. However, in the
fifth year due to load growth some of the feeder
capacities becomes inadequate and thus replacement of
those feeders by conductors of higher ratings is sug-gested in Fig. 11.
10. Conclusions
In this paper an attempt has been made to develop a
generalized algorithm for distribution system planning.
Novel algorithm has been developed for optimum feederpath configuration and optimum location of substation
based on minimum loss criterion. Proposed method is
able to determine the least cost plan by searching
through all the possible candidate locations and it also
satisfies constraints such as current capacity, voltage
drops and heuristic rules. Inference machine has been
developed to reach feasible distribution plan based on
data and heuristic rules in the knowledge base. Modifiedload flow algorithm incorporating composite load
model is developed; the load flow method is repeatedly
used to find optimum conductor size of branches and
optimum location of the substation. Three different
algorithms namely optimum location of substation,
optimal feeder path and optimal branch conductor
selection has been developed for the proposed methodof distribution system planning. Load growth is also
incorporated in the algorithm to compute future repla-
cement/reinforcement of line due to inadequate size of
conductors. The developed algorithm has been imple-
mented on PIII in C�/�/ and several realistic problems
have been tested. From the numerical results it is
verified that the proposed algorithm obtains an accep-
table distribution plan that satisfies current and voltageconstraints and the heuristic rules.
Appendix A: Data for load points
Node num-
ber
X coordinate Y coordi-
nate
Load
(kVA)
1 (substa-
tion)
To be obtained
from the proposedalgorithm
2 1.00 2.00 25.0
3 2.00 15.00 25.0
4 3.00 4.00 25.0
5 4.00 12.00 50.00
6 5.00 11.50 63.00
7 6.00 10.00 63.00
8 7.00 7.00 50.009 1.50 5.50 25.00
10 11.50 13.50 16.00
11 7.50 17.50 16.00
12 8.50 15.50 25.00
13 12.50 10.50 50.00
14 11.00 17.50 63.00
15 8.00 7.50 63.00
16 11.00 6.00 25.0017 5.50 5.50 16.00
18 3.50 8.50 16.00
19 13.00 8.00 16.00
20 14.00 13.00 63.00
21 16.50 14.00 25.00
22 5.50 17.00 25.00
23 20.50 12.00 50.00
24 8.00 9.00 100.0025 5.00 7.00 100.00
26 8.00 5.50 100.00
27 10.50 8.00 50.00
28 10.50 15.00 50.00
29 9.00 19.00 25.00
30 7.50 19.50 63.00
31 5.50 19.50 63.00
32 3.00 17.50 25.0033 13.00 15.50 50.00
34 14.00 16.50 50.00
35 12.50 19.00 25.00
R. Ranjan et al. / Electric Power Systems Research 62 (2002) 55�/6564
36 11.00 20.00 25.00
37 5.00 15.50 50.00
38 2.00 10.50 50.00
39 3.00 3.50 63.0040 6.00 4.00 25.00
41 9.00 4.50 25.00
42 14.00 11.50 50.00
43 15.00 10.00 50.00
44 15.00 14.50 25.00
45 15.50 12.50 25.00
46 12.00 12.00 63.00
47 14.50 7.50 63.0048 13.50 6.00 25.00
49 13.00 4.50 16.00
50 13.50 18.00 16.00
51 4.00 5.00 25.00
52 9.50 6.50 16.00
53 9.50 17.00 25.00
54 12.00 2.50 50.00
Power factor of the load 0.75Demand factor 1.00
References
[1] K. Nara, T. Satoh, K. Aoki, et al., Multilayer expansion planning
for distribution systems, IEEE Trans. PWRS 6 (1) (1991) 245�/
254.
[2] C.W. Hasselfield, P. Wilson, et al., An automated method of least
cost distribution planning, IEEE. Trans. PWRD 5 (2) (1992)
1188�/1194.
[3] K. Nara, T. Satoh, K. Aoki, et al., Distribution system planning
by multistage branch exchange, IEEE Trans. PWRS 7 (1) (1992)
208�/214.
[4] V.H. Quintana, et al., Two stage power system distribution
planning algorithm, IEE. Proc. 140 (1) (1993) 17�/29.
[5] N. Kagan, A bender’s decomposition approach to the multi
objective distribution planning problem, Electrical Power Energy
Syst. 15 (5) (1993) 259�/271.
[6] Y. Tang, Power distribution systems planning with reliability
modeling and optimization, IEEE Trans. PWRS 11 (1) (1995)
181�/189.
[7] G.L. Thompson, D.L. Wall, A branch and bound model for
choosing optimal substation locations, IEEE Trans. PAS 100
(1981) 2683�/2687.
[8] H.K. Youssef, R. Hackam, Dynamic solution of distribution
planning in intermediate time range, IEEE Trans. PWRD 3 (1)
(1988) 341�/348.
[9] O.M. Mikic, Mathematical dynamic model for long term
distribution system planning, IEEE Trans. PWRS 1 (1) (1986)
40�/46.
[10] D. Hongwei, et al., Optimal planning of distribution substation
locations and sizes-model and algorithm, Electrical Power Energy
Syst. 18 (6) (1996) 353�/357.
[11] K. Nara, Y. Hayashi, et al., A new algorithm for distribution
feeder expansion planning in urban area, Electrical Power Syst.
Res. 46 (1998) 185�/193.
[12] S. Bhowmik, S.K. Goswami, P.K. Bhattacherjee, A new power
distribution planning through reliability evaluation technique,
Electrical Power Syst. Res. 54 (2000) 167�/169.
[13] K.P. Wong, H.N. Chenung, Artificial intelligence approach to
load allocation in distribution substation, Proc. IEE 134 (5) (1987)
357�/364.
[14] Y.Y. Hsu, J.L. Chen, Distribution planning using a knowledge
based expert systems, IEEE PWRD 5 (3) (1990) 1514�/1519.
[15] G. Branner, M. Zobel, Knowledge based planning of distribution
networks, IEEE Trans. Power Syst. 9 (2) (1994) 942�/948.
[16] D. Das, D.P. Kothari, A. Kalam, Simple and efficient method for
load flow solution of radial distribution networks, Electrical
Power Energy Syst. 17 (5) (1995) 335�/346.
[17] D. Thukaram, H.M. Wijekoon, et al., A robust three phase power
flow algorithm for radial distribution systems, Electrical Power
Syst. Res. 50 (3) (1999) 227�/236.
[18] L. Coopper, U.N. Bhat, L.J. Leblanc, Introduction to Opera-
tional Research Models, Saunders 1977.
R. Ranjan et al. / Electric Power Systems Research 62 (2002) 55�/65 65