energies Article A High-Frequency Isolated Online Uninterruptible Power Supply (UPS) System with Small Battery Bank for Low Power Applications Muhammad Aamir 1,2, *, Wajahat Ullah Tareen 2 , Kafeel Ahmed Kalwar 3 , Mudasir Ahmed Memon 2 and Saad Mekhilef 2 1 Department of Electrical Engineering, Bahria University, Islamabad 44000, Pakistan 2 Power Electronics and Renewable Energy Research Laboratory (PEARL), Department of Electrical Engineering, University of Malaya, Kuala Lumpur 50603, Malaysia; [email protected] (W.U.T.); [email protected] (M.A.M.); [email protected] (S.M.) 3 Department of Electrical Engineering, DHA Suffa University, Karachi 75500, Pakistan; [email protected] * Correspondence: [email protected] Academic Editor: Gabriele Grandi Received: 22 December 2016; Accepted: 17 March 2017; Published: 23 March 2017 Abstract: Uninterruptible power supplies (UPSs) are widely used to deliver reliable and high quality power to critical loads under all grid conditions. This paper proposes a high-frequency isolated online UPS system for low power applications. The proposed UPS consists of a single-stage AC-DC converter, boost DC-DC converter, and an inverter. The single-stage AC-DC converter provides galvanic isolation, input power factor correction, and continuous conduction of both input and output current. The low battery bank voltage is stepped up to high dc-link voltage by employing a high voltage gain boost converter, thus allows the reduction of battery bank to only 24 V parallel connected batteries. Operating batteries in parallel improves the battery performance and resolves the issues related to conventional battery banks that arrange the batteries in series combination. The inverter provides regulated output voltage to the load. A new cascaded slide mode (SM) and proportional-resonant (PR) control for the inverter has been proposed, which regulates the output voltage for both linear and non-linear loads. The controller shows excellent performance during load transients and step changes. Besides, the controller for boost converter and AC-DC converter is presented. Operating principle and experimental results of 1 kVA laboratory setup have been presented for the validation of proposed system. Keywords: uninterruptible power supply (UPS); single-stage AC-DC converter; high-frequency isolation; boost converter; power factor correction 1. Introduction Uninterruptible power supplies (UPSs) deliver clean, conditioned, and reliable power to critical loads such as communication systems, network servers, medical equipment, etc. [1]. Typically, the UPS provides unity power factor, high efficiency, high reliability, low cost, and continuous power supply, irrespective of the grid conditions [24]. UPS systems can be categorized as online, offline, and line interactive UPS systems [5]. Among them online UPS systems are the most popular and common configuration, as they provide isolation to the load from the grid and have negligible switching times. A conventional online UPS system consists of a rectifier for PFC, battery bank, and an inverter connected with the load. Grid frequency transformers are normally employed to reduce the battery bank voltage and provide isolation from Energies 2017, 10, 418; doi:10.3390/en10040418 www.mdpi.com/journal/energies

Transcript of A High-Frequency Isolated Online Uninterruptible …...system. The single-stage AC-DC converter...

Page 1: A High-Frequency Isolated Online Uninterruptible …...system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency

energies

Article

A High-Frequency Isolated Online UninterruptiblePower Supply (UPS) System with Small Battery Bankfor Low Power Applications

Muhammad Aamir 1,2,*, Wajahat Ullah Tareen 2, Kafeel Ahmed Kalwar 3,Mudasir Ahmed Memon 2 and Saad Mekhilef 2

1 Department of Electrical Engineering, Bahria University, Islamabad 44000, Pakistan2 Power Electronics and Renewable Energy Research Laboratory (PEARL), Department of Electrical

Engineering, University of Malaya, Kuala Lumpur 50603, Malaysia; [email protected] (W.U.T.);[email protected] (M.A.M.); [email protected] (S.M.)

3 Department of Electrical Engineering, DHA Suffa University, Karachi 75500, Pakistan;[email protected]

* Correspondence: [email protected]

Academic Editor: Gabriele GrandiReceived: 22 December 2016; Accepted: 17 March 2017; Published: 23 March 2017

Abstract: Uninterruptible power supplies (UPSs) are widely used to deliver reliable and high qualitypower to critical loads under all grid conditions. This paper proposes a high-frequency isolatedonline UPS system for low power applications. The proposed UPS consists of a single-stage AC-DCconverter, boost DC-DC converter, and an inverter. The single-stage AC-DC converter providesgalvanic isolation, input power factor correction, and continuous conduction of both input andoutput current. The low battery bank voltage is stepped up to high dc-link voltage by employinga high voltage gain boost converter, thus allows the reduction of battery bank to only 24 V parallelconnected batteries. Operating batteries in parallel improves the battery performance and resolvesthe issues related to conventional battery banks that arrange the batteries in series combination.The inverter provides regulated output voltage to the load. A new cascaded slide mode (SM) andproportional-resonant (PR) control for the inverter has been proposed, which regulates the outputvoltage for both linear and non-linear loads. The controller shows excellent performance duringload transients and step changes. Besides, the controller for boost converter and AC-DC converteris presented. Operating principle and experimental results of 1 kVA laboratory setup have beenpresented for the validation of proposed system.

Keywords: uninterruptible power supply (UPS); single-stage AC-DC converter; high-frequencyisolation; boost converter; power factor correction

1. Introduction

Uninterruptible power supplies (UPSs) deliver clean, conditioned, and reliable power to criticalloads such as communication systems, network servers, medical equipment, etc. [1]. Typically, the UPSprovides unity power factor, high efficiency, high reliability, low cost, and continuous power supply,irrespective of the grid conditions [2–4].

UPS systems can be categorized as online, offline, and line interactive UPS systems [5]. Amongthem online UPS systems are the most popular and common configuration, as they provide isolationto the load from the grid and have negligible switching times. A conventional online UPS systemconsists of a rectifier for PFC, battery bank, and an inverter connected with the load. Grid frequencytransformers are normally employed to reduce the battery bank voltage and provide isolation from

Energies 2017, 10, 418; doi:10.3390/en10040418 www.mdpi.com/journal/energies

Page 2: A High-Frequency Isolated Online Uninterruptible …...system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency

Energies 2017, 10, 418 2 of 20

the transients and spikes generated inside the grid. Since the transformer is operating at the gridfrequency, it increases the volumetric size and weight of the system significantly.

High-frequency transformer-based UPSs offer an effective solution to the problems mentionedabove by reducing the size of the system as well as providing suitable galvanic isolation between theload and grid. Besides, these UPS systems have high power factor correction, zero voltage switching(ZVS) of the chopper and converter stage, and low-cost design [6,7]. However, due to high dc-linkvoltage, several batteries are connected in a series arrangement, which reduces the reliability ofthe system.

Table 1. Comparison of high-frequency transformer UPSs for different battery banks.

Reference Rated Power Input/Output Voltage Battery Bank Voltage Number of Batteries

[8] 300 VA 120 48 4[9] 2 kVA 220 108 9

[10] 150 VA 120 48 4[11] 2 kVA 110 180 15[12] 3.3 kVA 220 120 10

Table 1 shows a comparison of the different high-frequency transformer-based UPS with seriesconnected batteries. Series battery arrangement has major drawbacks and limitations in chargingand discharging. A small imbalance in voltages occurs across the battery cells during chargingand discharging because the voltages across each cell is not equal. Hence, their performance isdifferent during charging and discharging operations. Severe overheating, low performance, and evendestruction may be caused by battery overcharging [13]. Similarly, deep discharge will permanentlydamage the battery cells [14]. Due to this reason, a small battery bank with batteries operating inparallel improves the performance of the battery bank significantly. The batteries operating in parallelhave the following advantages:

(1) The number of batteries is not restricted to the dc-link voltage. The volume, weight, and backuptime of the battery bank should be designed according to the specific application.

(2) Cost reduction as no extra voltage balancing circuit is required.(3) Damaged batteries can be isolated or replaced in the battery bank leaving the sensitive system

operation uninterrupted. This is a prime function of UPS systems.(4) Since the discharging currents of the batteries can be profiled individually, hence the stored

energy in the batteries can be utilized more efficiently.

In this paper, a new high-frequency isolated online UPS system configuration is proposed.The proposed UPS consists of a single-stage AC-DC converter, DC-DC boost converter, and H-bridgeinverter as shown in Figure 1. The single-stage AC-DC converter provides galvanic isolation, highinput power factor, continuous flow of input and output current, with minimum semiconductordevices within the circuit. A high-gain DC-DC converter is introduced to step up the low batterybank voltage to high dc-link voltage in order to feed it to the inverter. This allows the use of a lowvoltage battery bank in the UPS system. Besides, the converter follows the condition of ZVS andsynchronous rectification (SR), which increases the system efficiency. A new cascaded slide mode (SM)and proportional-resonant (PR) controller have been implemented in the inverter control which showgood performance with low total harmonics distortion (THD) and high stability for both non-linearand impulsive loads. The volumetric size and cost of the proposed system are comparatively verysmall as no bulky grid frequency transformer has been used, with a small battery bank, and highefficiency. Hence, the proposed UPS system with its low cost and weight is an excellent choice for lowpower applications. A 1 kVA laboratory prototype has been constructed to verify the performance ofthe system. The proposed UPS system shows excellent steady state and dynamic performance.

Page 3: A High-Frequency Isolated Online Uninterruptible …...system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency

Energies 2017, 10, 418 3 of 20

Energies 2017, 10, 418 3 of 19

Figure 1. Circuit diagram of the proposed UPS system.

2. Circuit Description

The proposed system consists of a single-stage AC-DC converter at the front end, a H-bridge inverter at the back end, and a high-gain boost converter connected with the battery bank of the UPS system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency isolation between the load and grid. The boost converter with high-voltage gain steps up the low battery bank voltage to high dc-link voltage in order to feed it to the inverter. The H-bridge inverter with a new robust control scheme is proposed for operation under the non-linear loading condition and provides the fast transient response during change of modes.

2.1. Modes of Operation

The UPS operates in two modes, i.e., grid mode and battery mode, as shown in the Figure 2.

Figure 2. Modes of operation of proposed UPS system.

2.1.1. Grid Mode

When the grid voltage is stable and there is no power failure, the UPS system operates in grid mode. The single-stage AC-DC converter regulates the voltage across Cr. Meanwhile; the boost converter steps up battery bank voltage across Cr and provides it to the inverter. The inverter provides regulated output voltage to the connected load.

2.1.2. Battery Mode

In case of utility power disruption or any voltage sag, the magnetic contactor (MC) is opened, and the single-stage AC-DC converter stops operation. Now the battery supplies power to the load via the boost converter and inverter connected to it. The arrangement of the battery is such that it provides uninterruptible energy to the boost converter at the time of utility line failure. The value of the dc-link capacitor is kept high in order to provide sufficient energy to the inverter during the transition between the power modes.

A bypass switch has been added in the system to increase the reliability of the system. In case of internal faults in the system or overloading and overheating of the circuit, the bypass switch turns ON and provides a direct path for the power from the utility grid to the connected load [15].

Figure 1. Circuit diagram of the proposed UPS system.

2. Circuit Description

The proposed system consists of a single-stage AC-DC converter at the front end, a H-bridgeinverter at the back end, and a high-gain boost converter connected with the battery bank of the UPSsystem. The single-stage AC-DC converter provides rectification, with power factor correction (PFC)as well as high-frequency isolation between the load and grid. The boost converter with high-voltagegain steps up the low battery bank voltage to high dc-link voltage in order to feed it to the inverter.The H-bridge inverter with a new robust control scheme is proposed for operation under the non-linearloading condition and provides the fast transient response during change of modes.

2.1. Modes of Operation

The UPS operates in two modes, i.e., grid mode and battery mode, as shown in the Figure 2.

Energies 2017, 10, 418 3 of 19

Figure 1. Circuit diagram of the proposed UPS system.

2. Circuit Description

The proposed system consists of a single-stage AC-DC converter at the front end, a H-bridge inverter at the back end, and a high-gain boost converter connected with the battery bank of the UPS system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency isolation between the load and grid. The boost converter with high-voltage gain steps up the low battery bank voltage to high dc-link voltage in order to feed it to the inverter. The H-bridge inverter with a new robust control scheme is proposed for operation under the non-linear loading condition and provides the fast transient response during change of modes.

2.1. Modes of Operation

The UPS operates in two modes, i.e., grid mode and battery mode, as shown in the Figure 2.

Figure 2. Modes of operation of proposed UPS system.

2.1.1. Grid Mode

When the grid voltage is stable and there is no power failure, the UPS system operates in grid mode. The single-stage AC-DC converter regulates the voltage across Cr. Meanwhile; the boost converter steps up battery bank voltage across Cr and provides it to the inverter. The inverter provides regulated output voltage to the connected load.

2.1.2. Battery Mode

In case of utility power disruption or any voltage sag, the magnetic contactor (MC) is opened, and the single-stage AC-DC converter stops operation. Now the battery supplies power to the load via the boost converter and inverter connected to it. The arrangement of the battery is such that it provides uninterruptible energy to the boost converter at the time of utility line failure. The value of the dc-link capacitor is kept high in order to provide sufficient energy to the inverter during the transition between the power modes.

A bypass switch has been added in the system to increase the reliability of the system. In case of internal faults in the system or overloading and overheating of the circuit, the bypass switch turns ON and provides a direct path for the power from the utility grid to the connected load [15].

Figure 2. Modes of operation of proposed UPS system.

2.1.1. Grid Mode

When the grid voltage is stable and there is no power failure, the UPS system operates in gridmode. The single-stage AC-DC converter regulates the voltage across Cr. Meanwhile; the boostconverter steps up battery bank voltage across Cr and provides it to the inverter. The inverter providesregulated output voltage to the connected load.

2.1.2. Battery Mode

In case of utility power disruption or any voltage sag, the magnetic contactor (MC) is opened,and the single-stage AC-DC converter stops operation. Now the battery supplies power to the loadvia the boost converter and inverter connected to it. The arrangement of the battery is such that itprovides uninterruptible energy to the boost converter at the time of utility line failure. The valueof the dc-link capacitor is kept high in order to provide sufficient energy to the inverter during thetransition between the power modes.

Page 4: A High-Frequency Isolated Online Uninterruptible …...system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency

Energies 2017, 10, 418 4 of 20

A bypass switch has been added in the system to increase the reliability of the system. In case ofinternal faults in the system or overloading and overheating of the circuit, the bypass switch turns ONand provides a direct path for the power from the utility grid to the connected load [15].

2.2. AC-DC Converter

A number of single-stage AC/DC converters have been proposed in the literature [16–21].Commonly a full bridge diode rectifier has been employed at the front-end of DC/DCconverters [22–26], but four diodes operating at line frequency results in high conduction losses,thus dropping the efficiency of the converter. In order to eliminate the aforementioned problems,a bridgeless single-stage PFC AC/DC converter has been implemented in our design.

In [27], a bridgeless single-stage half bridge AC/DC converter has been proposed. It uses only twoactive switches and two diodes as passive switches to achieve the AC/DC conversion with reducedsize and efficient operation. However, the circuit operates in DCM and is not suitable for high powerapplications. A totem-pole bridgeless PFC connected with high frequency linked DC/DC regulatorhas been analyzed in [28]. The dc-link capacitor is reduced, which helps in reducing the total cost andsize of the system, but the circuit still operates under critical conduction mode of operation.

A single-stage AC/DC converter has been proposed in [29]. The converter operates in continuouscondition mode (CCM) and is designed for high power applications, but extra diodes have been usedin the circuit which reduces the overall efficiency of the circuit. Also, two separate controllers havebeen used, which increases the cost and complexity of the circuit.

A new AC-DC converter topology has been introduced, which combines an asymmetrical dc-dcconverter with a half bridge PFC rectifier forming a single-stage AC-DC converter. No front end dioderectifier has been used in the circuit. Using the proposed converter, galvanic isolation as well as highefficiency are achieved with only four active switches that reduces the volumetric size of the circuitconsiderably. Other features of the single-stage converters include continuous conduction of the inputand output current, ZVS condition, and excellent input power factor.

The operation of the AC-DC converter in both the positive and negative cycle is symmetrical.Therefore, only the positive cycle is considered in the discussion. Duty cycle D controls the switchesS2 and S3, while duty cycle (1-D) controls switches S1 and S4. Figure 3 presents the waveforms andoperating modes of the AC-DC converter.

2.2.1. Mode 1

In this mode, switches S2 and S3 turn ON under ZVS conditions. The boost inductor Lin is chargedby input AC line voltage Vin through the switch S2 and S3. The inductor current is represented by thefollowing equation:

∆iLin =1

Lin(Vin + Vd)DTs (1)

The blocking capacitor Cb is charged by the dc-link capacitor Cd through S3 and the secondaryside of the high-frequency transformer is fed by the energy stored in the magnetizing inductor Lm.The magnetizing inductor current iLm is represented under the initial condition iLm(0) by Equation (2):

iLm(t) = iLm(0) +(Vd −Vb)DTs

Lm(2)

The secondary voltage is Vsec1 = − NsNp

Vp = − NsNp

(Vd −Vb), Vsec2 = NsNp

(Vd −Vb). The currentthrough the diode D1 is same as the output filter inductor current, and is given as:

iD1 = iLo(max) = iLo(0) +1Lo

(N(Vd −Vb)−Vout)DTs (3)

Page 5: A High-Frequency Isolated Online Uninterruptible …...system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency

Energies 2017, 10, 418 5 of 20

Energies 2017, 10, 418 5 of 19

(a)

(b)

Figure 3. Single-stage AC-DC Converter: (a) Operation waveforms; (b) Modes of operation during one switching cycle TS.

The voltage across the switches S1 and S4 reduces to zero while the voltage across the switch S2 and S3 increases to Vd. At the secondary side, the output filter inductor current freewheels through the diodes D1 and D2.

Figure 3. Single-stage AC-DC Converter: (a) Operation waveforms; (b) Modes of operation during oneswitching cycle TS.

2.2.2. Mode 2

Both the switches S2 and S3 turn OFF during this mode. The parasitic capacitance CS2 is chargedand CS1 is discharged using inductor current iLin. Similarly, the capacitance CS3 is charged andcapacitance CS4 is discharged by the primary current iP of the transformer.

Page 6: A High-Frequency Isolated Online Uninterruptible …...system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency

Energies 2017, 10, 418 6 of 20

The voltage across the switches S1 and S4 reduces to zero while the voltage across the switch S2

and S3 increases to Vd. At the secondary side, the output filter inductor current freewheels through thediodes D1 and D2.

2.2.3. Mode 3

In Mode 3, the dc-link film capacitor Cd starts charging by getting energy from the boost inductorand as a result iLin starts decreasing. As the voltage across S1 reduces to 0, the body diode DS1 turnsON. Similarly, the blocking capacitor is fed by the magnetizing inductance Lm through the body diodeDS4. As a result, iLm will induce the flux in the high-frequency transformer secondary winding, andthe power will be fed to the output capacitor Cr.

2.2.4. Mode 4

In the start of Mode 4, both the switches S1 and S4 turn ON following the ZVS condition.The DC-link capacitor Cd is charged by the stored energy released by the boost inductor Lin.The inductor current is given by:

∆iLin =1

Lin(Vin −Vd)(1− D)Ts (4)

The input current flows through Lin, S1, Cd, and S2. Similarly, the magnetising current iLm startsdecreasing from maximum as represented by the following Equation (5):

iLm(t) = iLm(max)− VbLm

(1− D)Ts (5)

The high-frequency transformer secondary winding feed energy to the output capacitor D2.The output filter inductor current iLO is represented by Equation (6):

iLo = iLo(t) = iLo(0)−1Lo

N(Vd −Vb)(1− D)Ts (6)

2.2.5. Mode 5

In Mode 5, the switches S1 and S4 turn OFF. The parasitic capacitor CS2 is discharged and CS1 ischarged by both the current from the transformer primary windings and the input inductor Lin to andfrom Vd, respectively. Now the voltage across S2 is zero, and the voltage across S1 is Vd. Similarly, thecapacitance CS4 is charged and CS3 is discharged by the primary current iP of the transformer. Thus,the voltage across S4 is Vd. At the secondary side, the output filter current freewheels through thediode D1 and D2.

2.2.6. Mode 6

In Mode 6, the body diode DS2 turns ON because of charging of the inductor. Similarly,the voltage across the switch S3 is zero. This causes the body diode DS3 to be turned ON andthe primary current starts flowing through it. In the end of Mode 6, both the S2 and S3 turn ON underthe condition of ZVS.

2.2.7. Continuous condition mode (CCM) of operation of input inductor

The proposed AC-DC converter operates in CCM with continuous input current. The minimuminductor for CCM operation can be determined by (7):

Lin >V2

d TsD(1− D)2

2Po(7)

Page 7: A High-Frequency Isolated Online Uninterruptible …...system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency

Energies 2017, 10, 418 7 of 20

The average current ripple is given by Equation (8):

∆iLin =|Vm sin ωt|DTs

2Lin(8)

The peak current is given by (9):

iLin

∣∣peak = iLin(avg) + ∆iLin =

|Vm sin ωt|Re

+|Vm sin ωt|DTs

2Lin(9)

where Re is the emulative resistance of the converter. Equation (9) shows that the inductor peak currentis not very high because large value of inductor is selected which maintains the continuous conduction.

2.2.8. Discontinuous conduction mode (DCM) of operation of the input inductor

If the proposed UPS system is designed for low power applications, the input inductor can beoperated in discontinuous conduction mode [30]. The peak boost inductor current follows the linevoltage with a fixed duty ratio to supply the output power for a constant output voltage. Suppose theconverter is lossless and the duty ratio is fixed, the boost inductor Lb should be determined by (10):

Lin <V2

inDTs

2Po(10)

where Po is the maximum output power. For positive line period, the peak boost inductor currentduring TS is expressed as (11):

iLb, peak =VinDTs

Lb(11)

2.3. Boost Converter

A high-gain DC-DC converter has been introduced to obtain high dc-link voltage from the lowvoltage battery bank [31]. SR has been applied to decrease the conduction losses and force the circuit tooperate under ZVS conduction. In order to get the high-voltage gain, coupled inductor is utilized withLP and LS as primary and secondary winding inductance respectively. The characteristic waveformand modes of operation of the DC-DC converter is shown in the Figure 4.

Energies 2017, 10, 418 7 of 19

where Re is the emulative resistance of the converter. Equation (9) shows that the inductor peak current is not very high because large value of inductor is selected which maintains the continuous conduction.

2.2.8. Discontinuous conduction mode (DCM) of operation of the input inductor

If the proposed UPS system is designed for low power applications, the input inductor can be operated in discontinuous conduction mode [30]. The peak boost inductor current follows the line voltage with a fixed duty ratio to supply the output power for a constant output voltage. Suppose the converter is lossless and the duty ratio is fixed, the boost inductor Lb should be determined by (10): < 2 (10)

where Po is the maximum output power. For positive line period, the peak boost inductor current during TS is expressed as (11):

, = (11)

2.3. Boost Converter

A high-gain DC-DC converter has been introduced to obtain high dc-link voltage from the low voltage battery bank [31]. SR has been applied to decrease the conduction losses and force the circuit to operate under ZVS conduction. In order to get the high-voltage gain, coupled inductor is utilized with LP and LS as primary and secondary winding inductance respectively. The characteristic waveform and modes of operation of the DC-DC converter is shown in the Figure 4.

(A) Characteristic waveform of the boost converter

(B) Topological stages: (a) Mode 1; (b) Mode 2; (c) Mode 3; (d) Mode 4; (e) Mode 5; (f) Mode 6

Figure 4. DC-DC boost converter; (A) Characteristic waveform; (B) Topological stages.

Figure 4. Cont.

Page 8: A High-Frequency Isolated Online Uninterruptible …...system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency

Energies 2017, 10, 418 8 of 20

Energies 2017, 10, 418 7 of 19

where Re is the emulative resistance of the converter. Equation (9) shows that the inductor peak current is not very high because large value of inductor is selected which maintains the continuous conduction.

2.2.8. Discontinuous conduction mode (DCM) of operation of the input inductor

If the proposed UPS system is designed for low power applications, the input inductor can be operated in discontinuous conduction mode [30]. The peak boost inductor current follows the line voltage with a fixed duty ratio to supply the output power for a constant output voltage. Suppose the converter is lossless and the duty ratio is fixed, the boost inductor Lb should be determined by (10): < 2 (10)

where Po is the maximum output power. For positive line period, the peak boost inductor current during TS is expressed as (11):

, = (11)

2.3. Boost Converter

A high-gain DC-DC converter has been introduced to obtain high dc-link voltage from the low voltage battery bank [31]. SR has been applied to decrease the conduction losses and force the circuit to operate under ZVS conduction. In order to get the high-voltage gain, coupled inductor is utilized with LP and LS as primary and secondary winding inductance respectively. The characteristic waveform and modes of operation of the DC-DC converter is shown in the Figure 4.

(A) Characteristic waveform of the boost converter

(B) Topological stages: (a) Mode 1; (b) Mode 2; (c) Mode 3; (d) Mode 4; (e) Mode 5; (f) Mode 6

Figure 4. DC-DC boost converter; (A) Characteristic waveform; (B) Topological stages. Figure 4. DC-DC boost converter; (A) Characteristic waveform; (B) Topological stages.

2.3.1. Mode 1 (t0~t1)

During Mode 1, the switch S5 is ON, while the switch S6 is OFF. Low battery bank voltage isapplied at the input of the DC-DC boost converter. Capacitor Cb2 remains charged before Mode 1 andthe magnetizing current iLm of the coupled inductor increases linearly, as shown in the Figure 5.

Energies 2017, 10, 418 8 of 19

2.3.1. Mode 1 (t0~t1)

During Mode 1, the switch S5 is ON, while the switch S6 is OFF. Low battery bank voltage is applied at the input of the DC-DC boost converter. Capacitor Cb2 remains charged before Mode 1 and the magnetizing current iLm of the coupled inductor increases linearly, as shown in the Figure 5.

(a)

(b)

Figure 5. Proposed control scheme: (a) Inverter control; (b) Control circuit UPS system.

Applying KVL, we get: = = ⁄ (12)

The voltage across the primary winding can be find using voltage second balance: (1 − ) = (13)

2.3.2. Mode 2 (t1~t2)

The switch S5 turns OFF in Mode 2. The primary current iLP charges the parasitic capacitance across the switch S5 and the secondary current iLS discharges the parasitic capacitance across switch S6. When the voltage across switch S5 equals to the capacitor voltage VCb1, this mode finishes.

2.3.3. Mode 3 (t2~t3)

Since the switch S5 is OFF, the primary current iLP decreases due to leakage inductance. However, the secondary current iLS increases, which results in the turning ON of the body diode of switch S6. As the voltage across the switch S5 is higher than capacitor Cb1, it charges Cb1 through diode Db1. Hence, the voltage stress across the switch S5 has been reduced. VCb1 is the voltage across the capacitor Cb1, and is represented by Equation (14):

Figure 5. Proposed control scheme: (a) Inverter control; (b) Control circuit UPS system.

Applying KVL, we get:VL = VLp = VLS/N (12)

The voltage across the primary winding can be find using voltage second balance:

VLP(1− D) = VLD (13)

Page 9: A High-Frequency Isolated Online Uninterruptible …...system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency

Energies 2017, 10, 418 9 of 20

2.3.2. Mode 2 (t1~t2)

The switch S5 turns OFF in Mode 2. The primary current iLP charges the parasitic capacitanceacross the switch S5 and the secondary current iLS discharges the parasitic capacitance across switch S6.When the voltage across switch S5 equals to the capacitor voltage VCb1, this mode finishes.

2.3.3. Mode 3 (t2~t3)

Since the switch S5 is OFF, the primary current iLP decreases due to leakage inductance.However, the secondary current iLS increases, which results in the turning ON of the body diode ofswitch S6. As the voltage across the switch S5 is higher than capacitor Cb1, it charges Cb1 throughdiode Db1. Hence, the voltage stress across the switch S5 has been reduced. VCb1 is the voltage acrossthe capacitor Cb1, and is represented by Equation (14):

VCb1 = VL + VLP (14)

Using (13):VCb1 = VL/(1− D) (15)

2.3.4. Mode 4 (t3~t4)

In Mode 4, the switch S6 turns ON under ZVS conditions. Both the windings of the coupledinductor and the capacitor Cb2 series connected together transfer maximum energy to the outputcapacitor Cdin of the converter. The iLS starts increasing until it reaches the iLP, then it follows theiLP till the end of the Mode 4. Thus, the energy stored in both the windings of the coupled inductordischarges across the high voltage side of the circuit. Db1 and Db2 are reverse biased during this mode.Applying voltage second balance, we get Equation (16):

VH = VL + VLS + VCb2 + VLp (16)

VH = VL + VCb2 + (N + 1)VLP (17)

2.3.5. Mode 5 (t4~t5)

During this mode, the switch S6 turns OFF. The current iLS charges the parasitic capacitance ofthe switch S6. Capacitor Cb2 is charged by the capacitor Cb1 through the diode Db2:

VCb2 = VCb1 = VL/(1− D) (18)

By substituting (13) and (18) into (17), presents the voltage gain of the converter:

VH = VL + VL/(1− D) + (N + 1)D/(1− D)VL (19)

Gboost = VH/VL = (2 + ND)/(1− D) (20)

The body diode of the switch S5 turns ON because of the polarities of capacitor Cb2 andinductor LP.

2.3.6. Mode 6 (t5~t6)

During this mode, the switch S5 turns to ON state under ZVS conditions. Since no current isderived by switch S5 from the clamped circuit, thus the switching losses remains low due to ZVS,results in increasing the efficiency of the converter. Mode 6 finishes at the point when both the VCb1and VCb2 become equal. The turn ratio N = 4 is selected to satisfy the Gboost gain in order to step up thebattery bank voltage to required dc-link of inverter.

Page 10: A High-Frequency Isolated Online Uninterruptible …...system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency

Energies 2017, 10, 418 10 of 20

3. Control Strategy

The control schemes for regulating different parts of the proposed UPS, in different modes ofoperation are shown in Figure 5. The control scheme for inverter and boost converter keeps operatingin both the normal and battery powered mode. On the other hand, for a single-stage converter thecontrol scheme operates only in normal mode of operation for charging the battery as well as supplyingpower to the boost converter.

3.1. Inverter Control

A conventional full bridge voltage source inverter has been used to perform DC to AC conversion.SM control is famous for its excellent performance against non-linear loading conditions. SMC isalso robust in operation and easy to implement for a full bridge inverter. In order to control theoutput voltage of the inverter, cascaded control algorithm of SMC and PR has been proposed for thecontrol of inverter. The inner current loop is controlled by the SM control while the outer voltage loopis controlled by the PR control. Smoothed control law in narrow boundary layer has been used toeliminate the phenomena of chattering SMC. The smoothed control law is applied to the pulse widthmodulator that results in the fixed switching frequency of the inverter. Thus, the proposed controlleradopted the characteristic of both SMC and PR control.

The circuit diagram of a single phase inverter with LC filter and proposed controller for non-linearload is shown in Figure 5a, where Vd is the applied DC-link voltage, Vout the filter capacitor Cfoutput voltage. iLf is the inductor Lf current and io the output current through the load R, given byio = Vout/RLoad. The state equations of the inverter are given as:

ddt

[Vout

iL f

]=

[0 1/C f

1/L f 0

][Vout

iL f

]+

[0

Vd/L f

]u +

[0

io/C f

](21)

where u = Control input = {−1, 0, +1}.In order to implement the sliding mode control, the voltage error x1, and its derivative x2 =

.x1

need to be find:x1 = Vout −Vre f (22)

x2 =.x1 =

.Vout −

.Vre f = iC f/C f −

.Vre f (23)

where Vre f = Vm sin(ωt). Consider the slide surface equation:

S = λx1 + x2 (24)

Now to apply the sliding control law to the inverter, putting the value of x1 and x2:

S = λ(

Vout −Vre f

)+

iC f

C f−

.Vre f (25)

S = λ(

Vout −Vre f

)+

1C f

(iC f − ire f

)(26)

The sliding mode controller has the common inherent property of chattering. Chattering affectsthe control accuracy and reduces the efficiency of the circuit. In order to overcome the chattering,a smoothed SM control has been implemented. This can be achieved by smoothing out the controldiscontinuity in a thin boundary layer neighboring the sliding surface:

B(t) = {x, |S (x; t)| ≤ ∅} ∅ > 0 (27)

Page 11: A High-Frequency Isolated Online Uninterruptible …...system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency

Energies 2017, 10, 418 11 of 20

where ∅ is the boundary layer thickness and ε = ∅λ is the boundary layer width. Hence, interpolating

S inside B(t), for instance, and replacing S by an expression S/∅, Equation (26) will be:

S(x)∅ =

λ

[Vout −Vre f

]+

1C f∅

[iC f − ire f

](28)

The smoothing control discontinuity assigns a low pass filter structure to the local dynamics thuseliminating chattering. The control law needs to be tuned very precisely in order to achieve a trade-offbetween the tracking precision and robustness to the uncontrolled dynamics. Hence, the final equationfor the control of the inverter can be derived by combining the proportional resonant control and SMcontrol for the current loop:

S(x)∅ =

1C∅

[iC − ire f

]+

λ

[Kp

(Vout −Vre f

)+ ki

(2s

s2 + 2ωcs + ω2o

)(Vout −Vre f

)](29)

Thus Equation (29) shows the dynamic behavior in both SM and PR compensator control.The error in the voltage loop is compensated by the appropriate PR parameters, thus, the outputvoltage is compelled to follow the reference AC voltage leading to system stability while the SMCdrives the system to the zero sliding surface with maximum stability. Since the capacitor error currentcontains the ripples from the inductor, the current peak may reach high values, so ∅ should be carefullyassigned a value in order to compensate the slope from the high current ripple of the capacitor. Hence,the PR controller eliminates the steady-state error at resonant frequency or harmonic at that frequency.The response time of the system λ determines the dynamics and robustness of the system. It is clearfrom Equation (29), that a smaller value of λ leads to a slow response time, while higher λ valuesthough increase the response time, but take a longer time to reach the sliding surface. Thus the optimalvalue for λ is equal to the switching frequency of the inverter.

According to [32], the slope of the carrier wave is 4Vm × f s, where Vm is the magnitude andfs is the frequency of carrier wave. The slope of the error signal to the modulator is given byVDC/4LC∅. According to the limitation of the pulse width modulator, slope of error signal < slope ofthe carrier signal:

4Vm × f s < VDC/4LC∅ (30)

Thus, the minimum value of ∅ can be calculated using (30):

∅ ∼=10VDC

16LCVm fS(31)

Table 2 shows the comparison of the proposed control scheme with the SM control and othercommon controllers. The proposed controller shows an improvement in terms of reducing the THDand transient response (TS) with robust control of the inverter.

Table 2. Comparison of different control methods.

Parameters Model PredictiveControl [33]

SPWMControl [34]

RotatingSMC [35]

Fix-FreqSMC [36] Proposed Work

VDC 529 405 300 360 350VRMS 150 220 200 220 220

Cf (uF) 40 202 100 9.4 6.6Lf (mH) 2.4 0.03 0.250 0.357 0.84THD (L) 2.85% 1.11% - 1.1% 0.45%

THD (NL) 3.8% 3.8% 2.66% 1.7% 1.25%TS (ms) 50 60 - 0.5 0.3

Page 12: A High-Frequency Isolated Online Uninterruptible …...system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency

Energies 2017, 10, 418 12 of 20

3.2. Battery Charger Control

The AC-DC converter of the UPS system acts as a battery charger as shown in Figure 5.In this control scheme, the faster inner current loop regulates the inductor current so that its averagevalue during each period follows the rectified input voltage. The slower outer voltage loop maintainsthe battery voltage close to reference voltage and generates the control signal for the current loop.The steady state analysis of the AC-DC converter shows stable performance during grid mode.The state space equations of the rectifier are derived as:

diLdt

=VinLin

D +(Vin −Vd)

Lin(1− D) (32)

dvddt

= − VdRCd

D +

(iLCd− Vd

RCd

)(1− D) (33)

Assuming the current loop has high bandwidth as compared to the voltage loop, and dc-linkcapacitor Cd is large enough to give approximately constant voltage i.e., dvd/dt = 0. With Vin = 0, thesmall signal control d to input current iL transfer function GiLd(s) of the inner current loop is give by:

GiLd(s) =iL

d=

Vds(Lin)

(34)

The stability of the current loop depends on the current loop gain, hence a suitableproportional-integral (PI) controller Gi(s) = kpi +

kiis , is used for compensating the current loop.

The Bode plot of the current loop gain Ti = GiLd(s)·Gi(s) is obtained considering the circuit parametersshown in Table 4. The values of the proportional gain Kpi and integral gain Kii are selected as 2.3 and1200, respectively, for the stable operation of the current loop. Figure 6a presents the Bode plot of thecurrent loop gain with phase margin of 89◦ and stable operation of the rectifier.

Energies 2017, 10, 418 12 of 19

(a)

(b)

Figure 6. Bode response of rectifier; (a) Current loop gain; (b) Voltage loop gain.

The same approach is used to compensate the voltage loop of the average current control scheme. is the reference current for the current loop. Assuming constant input voltage, the small signal control to output transfer function ( ) of the voltage loop is derived as: ( ) = = 2 ( + 2) (35)

In order to force the output voltage to follow the reference voltage VRef, a proportional-integral (PI) compensator has been employed. Combining the power stage with the PI controller ( ) =+ provides the overall loop gain. = . ( ) of the voltage loop. The values of Kpv and Kiv in voltage loop are selected as 1.2 and 13, respectively. The stability of the voltage loop can be analyzed using the Bode plot obtained by considering the parameters from Table 4, as shown in Figure 6b. The system shows good stability with a positive phase margin.

In charging mode, the controller operates as constant current mode CC or constant voltage mode CV depending on the battery voltage as shown in the Figure 5b. In current loop, the battery input current iBat is forced to follow the reference current iRef using a PI compensator in (36):

∗ = ( − ) + − (36)

Similarly, the battery voltage is regulated by the voltage loop using the PI compensator that forces the output battery voltage VBat to follow the reference voltage Vref. The current limiter is introduced to limit the maximum charging current of the battery. If the iref is greater than ilimit, the battery is charged at constant current (CC Mode), in contrast if the iref is less than ilimit, the battery is charged at constant voltage (CV mode).

Figure 6. Bode response of rectifier; (a) Current loop gain; (b) Voltage loop gain.

Page 13: A High-Frequency Isolated Online Uninterruptible …...system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency

Energies 2017, 10, 418 13 of 20

The same approach is used to compensate the voltage loop of the average current control scheme.vc is the reference current for the current loop. Assuming constant input voltage, the small signalcontrol vc to output transfer function GVdVc(s) of the voltage loop is derived as:

GVdVc(s) =vdvc

=VinR

2Vd(sCR + 2)(35)

In order to force the output voltage to follow the reference voltage VRef, a proportional-integral (PI)

compensator has been employed. Combining the power stage with the PI controller Gv(s) = kpv +kivs

provides the overall loop gain.Tv = Gv.GVdVc(s) of the voltage loop. The values of Kpv and Kiv in voltage loop are selected as 1.2

and 13, respectively. The stability of the voltage loop can be analyzed using the Bode plot obtained byconsidering the parameters from Table 4, as shown in Figure 6b. The system shows good stability witha positive phase margin.

In charging mode, the controller operates as constant current mode CC or constant voltage modeCV depending on the battery voltage as shown in the Figure 5b. In current loop, the battery inputcurrent iBat is forced to follow the reference current iRef using a PI compensator in (36):

i∗ = Kp

(iRe f − iBat

)+ Ki

∫ (iRe f − iBat

)dt (36)

Similarly, the battery voltage is regulated by the voltage loop using the PI compensator that forcesthe output battery voltage VBat to follow the reference voltage Vref. The current limiter is introduced tolimit the maximum charging current of the battery. If the iref is greater than ilimit, the battery is chargedat constant current (CC Mode), in contrast if the iref is less than ilimit, the battery is charged at constantvoltage (CV mode).

3.3. Boost Converter Control

The steady state analysis of the boost converter is performed using average state variablemethod [30]. The state space equation for the converter with coupled inductor is derived as:

diPdt

=VBatdt

D +(VBat −Vd)

Lm(N + 1)(1− D) (37)

dVo

dt=

ip

C(N + 1)(1− D)− Vo

RC(38)

Now we perturb the system and consider only the dynamic terms and eliminate the product ofthe AC terms because of very small value. The final equation after Laplace transform is:

svo = iP

(1− D

C(N + 1)

)− vd

RC− IP

C(N + 1)d (39)

siP = vBat

(DLm

+1− D

Lm(N + 1)

)− vd

(1− D

Lm(N + 1)

)+ d(

VBatLm− VBat + Vd

Lm(N + 1)

)(40)

Solving (37) and (38) gives the transfer function of the converter:

vo

d=

s(− IP

C(N+1)

)+ (1−D)

C(N+1)

(VBatLm

+ Vd−VBatLm(N+1)

)s2 + s 1

RC + (1−D)2

(1+N)2LmC

(41)

Page 14: A High-Frequency Isolated Online Uninterruptible …...system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency

Energies 2017, 10, 418 14 of 20

Considering the gain due to clamp capacitor Cb2, the transfer equation is given by:

vo

d=

s(− IP

C(N+1)

)+ (1−D)

C(N+1)

(VBatLm

+ Vd−VBat(D/1−D)Lm(N+1)

)s2 + s 1

RC + (1−D)2

(1+N)2LmC

(42)

The stability of the converter can be analyzed using the Bode plot shown in Figure 7. The systemshows good stability with a positive phase margin and it has no right half plane poles. It is easyto achieve high crossover frequencies by adjusting a suitable gain of the compensators as the phasenever reaches −180. The voltage across DC-link capacitor Cdin is regulated by using a suitable voltagecompensator [37]. The PI compensator is used to track the DC-link voltage Vd to follow the referencevoltage, as shown in Figure 7.

Energies 2017, 10, 418 13 of 19

3.3. Boost Converter Control

The steady state analysis of the boost converter is performed using average state variable method [30]. The state space equation for the converter with coupled inductor is derived as: = + ( − )( + 1) (1 − ) (37)

= ( + 1) (1 − ) − (38)

Now we perturb the system and consider only the dynamic terms and eliminate the product of the AC terms because of very small value. The final equation after Laplace transform is: = 1 −( + 1) − − ( + 1) (39) = + 1 −( + 1) − 1 −( + 1) + − +( + 1) (40)

Solving (37) and (38) gives the transfer function of the converter:

= − ( + 1) + (1 − )( + 1) + −( + 1)+ 1 + (1 − )(1 + ) (41)

Considering the gain due to clamp capacitor Cb2, the transfer equation is given by:

= − ( + 1) + (1 − )( + 1) + − ( 1 − )⁄( + 1)+ 1 + (1 − )(1 + ) (42)

The stability of the converter can be analyzed using the Bode plot shown in Figure 7. The system shows good stability with a positive phase margin and it has no right half plane poles. It is easy to achieve high crossover frequencies by adjusting a suitable gain of the compensators as the phase never reaches −180. The voltage across DC-link capacitor Cdin is regulated by using a suitable voltage compensator [37]. The PI compensator is used to track the DC-link voltage Vd to follow the reference voltage, as shown in Figure 7.

Figure 7. Bode plot of the boost converter.

4. Experimental Results

In order to validate the performance of our UPS system, a laboratory prototype has been implemented. The specifications of the UPS are shown in Table 3. The control scheme for the single-

20

40

60

80

100

120

140

Mag

nitu

de (d

B)

102

103

104

180

225

270

315

360

Phas

e (d

eg)

Frequency (rad/s)

Figure 7. Bode plot of the boost converter.

4. Experimental Results

In order to validate the performance of our UPS system, a laboratory prototype has beenimplemented. The specifications of the UPS are shown in Table 3. The control scheme for thesingle-stage converter, boost converter, and H-bridge inverter has been implemented using DSPTMS320F28335. The design parameters of the single-stage converter and DC-DC converter are shownin Tables 4 and 5, respectively. The backup storage system consists of two batteries (each batteryis 24 V/35 Ah), or parallel batteries, depending upon the backup time for the connected load.

Table 3. Specifications of the proposed UPS system.

Parameters Symbol Value

Input Voltage Vin 220 VOutput Voltage Vout 220 VGrid Frequency fr 50 Hz

Output Frequency fo 50 HzNumber of Batteries Vb 2 Parallel connected (24 V/35 Ah)

Maximum Output Power Po,max 1 kVADC-link Voltage Vd 360 V

Page 15: A High-Frequency Isolated Online Uninterruptible …...system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency

Energies 2017, 10, 418 15 of 20

Table 4. Design parameters of the single-stage AC-DC converter.

Parameters Symbol Value

Input Inductor Lin 1.2 mHSwitches S1~S4 SPP11N60C3

Fast Diodes D1, D2 C3D10060ASwitching frequency fs 50,000 Hz

H. F Transformer T Lm = 600 uH, TDK core PQ-40/40DC-Link Capacitor Cd 1900 uF

Table 5. Specifications of the boost DC-DC converter.

Parameters Symbol Value

DC-Link Voltage Vd_INV 360 VBattery Bank Voltage Vb 24 VSwitching Frequency fs 30,000 Hz

Coupled Inductor LP, LS Turns ratio N = 4; Magnetizing Inductor Lm = 107 uH; PQ-5050 coreCapacitor Cb1, Cb2 Cb1, Cb2 = 2 × 2.2 uF (ceramic), Cd = 1900 uFSwitches S5 ,S6 IPW60R045CP MOSFET (Infineon Technologies, Santa Clara, CA USA)Diodes Db1, Db2 Ultrafast Recovery diode UF5408

The utility input voltage and current waveform in normal mode of operation is shown in Figure 8a.The input is sinusoidal, with unity power factor and THD less than 5%. The output voltage and currentwaveform during linear loads and non-linear load are shown in Figure 8b,c. The waveform is sinusoidalfor linear loads with THD less than 1%. For a non-linear load designed according to the standard ofIEC62040-3, the THD is 1.25% [38].

Energies 2017, 10, 418 14 of 19

stage converter, boost converter, and H-bridge inverter has been implemented using DSP TMS320F28335. The design parameters of the single-stage converter and DC-DC converter are shown in Tables 4 and 5, respectively. The backup storage system consists of two batteries (each battery is 24 V/35 Ah), or parallel batteries, depending upon the backup time for the connected load.

Table 3. Specifications of the proposed UPS system.

Parameters Symbol ValueInput Voltage Vin 220 V

Output Voltage Vout 220 V Grid Frequency fr 50 Hz

Output Frequency fo 50 Hz Number of Batteries Vb 2 Parallel connected (24 V/35 Ah)

Maximum Output Power Po,max 1 kVA DC-link Voltage Vd 360 V

Table 4. Design parameters of the single-stage AC-DC converter.

Parameters Symbol ValueInput Inductor Lin 1.2 mH

Switches S1~S4 SPP11N60C3 Fast Diodes D1, D2 C3D10060A

Switching frequency fs 50,000 Hz H. F Transformer T Lm = 600 uH, TDK core PQ-40/40

DC-Link Capacitor Cd 1900 uF

Table 5. Specifications of the boost DC-DC converter.

Parameters Symbol ValueDC-Link Voltage Vd_INV 360 V

Battery Bank Voltage Vb 24 V Switching Frequency fs 30,000 Hz

Coupled Inductor LP, LS Turns ratio N = 4; Magnetizing Inductor Lm = 107 uH; PQ-5050 core Capacitor Cb1, Cb2 Cb1, Cb2 = 2 × 2.2 uF (ceramic), Cd = 1900 uF Switches S5 ,S6 IPW60R045CP MOSFET (Infineon Technologies, Santa Clara, CA USA) Diodes Db1, Db2 Ultrafast Recovery diode UF5408

The utility input voltage and current waveform in normal mode of operation is shown in Figure 8a. The input is sinusoidal, with unity power factor and THD less than 5%. The output voltage and current waveform during linear loads and non-linear load are shown in Figure 8b,c. The waveform is sinusoidal for linear loads with THD less than 1%. For a non-linear load designed according to the standard of IEC62040-3, the THD is 1.25% [38].

(a)

Energies 2017, 10, 418 15 of 19

(b) (c)

Figure 8. Experimental waveform of the input output voltage and current of the UPS system. (a) Input line voltage and current; (b) Inverter with linear Load; (c) Inverter with Non-linear load.

Figure 9a shows the drain to source voltage and current of the switches S3 and S4. Both the switches are operating under the condition of ZVS. Figure 9b shows the drain to source voltage of the switches S5 and S6 of the boost converter. Both switches are operating under the condition of ZVS. Also the voltage stress across the switches is also limited. When the grid power is interrupted, the system switches from grid mode to battery mode. The rectifier is no longer in operation and the boost converter provides regulated dc-link voltage.

(a)

(b)

Figure 9. Drain to source voltage and current of the switches. (a) S3 and S4 of single-stage AC-DC Converter; (b) S5 and S6 of boost DC-DC converter.

The transient effect in the output voltage is very small and the UPS system provides uninterruptible power to the load as shown in Figure 10a. Similarly, the transition from battery mode back to grid mode upon the restoration of the grid power is shown in Figure 10b. There is a small transient at the turning ON point of the AC-DC converter. This transient is due to the inductor which remains charged due to previous grid mode of operation. However the small transient can be controlled by a suitable snubber circuit. Figure 10 also shows that the inverter keeps operating in both the grid and battery powered mode of operation and the load is getting power without any interruption. Figure 11 shows a photograph of our laboratory prototype. Figure 12 shows the

Figure 8. Experimental waveform of the input output voltage and current of the UPS system. (a) Inputline voltage and current; (b) Inverter with linear Load; (c) Inverter with Non-linear load.

Page 16: A High-Frequency Isolated Online Uninterruptible …...system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency

Energies 2017, 10, 418 16 of 20

Figure 9a shows the drain to source voltage and current of the switches S3 and S4. Both theswitches are operating under the condition of ZVS. Figure 9b shows the drain to source voltage of theswitches S5 and S6 of the boost converter. Both switches are operating under the condition of ZVS.Also the voltage stress across the switches is also limited. When the grid power is interrupted, thesystem switches from grid mode to battery mode. The rectifier is no longer in operation and the boostconverter provides regulated dc-link voltage.

Energies 2017, 10, 418 15 of 19

(b) (c)

Figure 8. Experimental waveform of the input output voltage and current of the UPS system. (a) Input line voltage and current; (b) Inverter with linear Load; (c) Inverter with Non-linear load.

Figure 9a shows the drain to source voltage and current of the switches S3 and S4. Both the switches are operating under the condition of ZVS. Figure 9b shows the drain to source voltage of the switches S5 and S6 of the boost converter. Both switches are operating under the condition of ZVS. Also the voltage stress across the switches is also limited. When the grid power is interrupted, the system switches from grid mode to battery mode. The rectifier is no longer in operation and the boost converter provides regulated dc-link voltage.

(a)

(b)

Figure 9. Drain to source voltage and current of the switches. (a) S3 and S4 of single-stage AC-DC Converter; (b) S5 and S6 of boost DC-DC converter.

The transient effect in the output voltage is very small and the UPS system provides uninterruptible power to the load as shown in Figure 10a. Similarly, the transition from battery mode back to grid mode upon the restoration of the grid power is shown in Figure 10b. There is a small transient at the turning ON point of the AC-DC converter. This transient is due to the inductor which remains charged due to previous grid mode of operation. However the small transient can be controlled by a suitable snubber circuit. Figure 10 also shows that the inverter keeps operating in both the grid and battery powered mode of operation and the load is getting power without any interruption. Figure 11 shows a photograph of our laboratory prototype. Figure 12 shows the

Figure 9. Drain to source voltage and current of the switches. (a) S3 and S4 of single-stage AC-DCConverter; (b) S5 and S6 of boost DC-DC converter.

The transient effect in the output voltage is very small and the UPS system providesuninterruptible power to the load as shown in Figure 10a. Similarly, the transition from batterymode back to grid mode upon the restoration of the grid power is shown in Figure 10b. There is asmall transient at the turning ON point of the AC-DC converter. This transient is due to the inductorwhich remains charged due to previous grid mode of operation. However the small transient canbe controlled by a suitable snubber circuit. Figure 10 also shows that the inverter keeps operatingin both the grid and battery powered mode of operation and the load is getting power withoutany interruption. Figure 11 shows a photograph of our laboratory prototype. Figure 12 shows theefficiency graph with maximum efficiency of 95% during battery mode and 91% during grid mode ofoperation. Thus utilizing soft switching in boost converter reduces the switch losses and increases theefficiency of the system. The efficiency in battery mode is high as compared to grid mode because lessnumber of power stages are operation during this mode. Table 6 shows a comparison of the differenthigh-frequency transformer isolated UPS systems. The proposed UPS shows a distinct improvement interms of increasing the efficiency, reducing the size of the battery bank, and decreasing the volumetricsize and weight of the system.

Page 17: A High-Frequency Isolated Online Uninterruptible …...system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency

Energies 2017, 10, 418 17 of 20

Energies 2017, 10, 418 16 of 19

efficiency graph with maximum efficiency of 95% during battery mode and 91% during grid mode of operation. Thus utilizing soft switching in boost converter reduces the switch losses and increases the efficiency of the system. The efficiency in battery mode is high as compared to grid mode because less number of power stages are operation during this mode. Table 6 shows a comparison of the different high-frequency transformer isolated UPS systems. The proposed UPS shows a distinct improvement in terms of increasing the efficiency, reducing the size of the battery bank, and decreasing the volumetric size and weight of the system.

(a)

(b)

Figure 10. Transition between two modes of operation, Input voltage Vin and current Iin, Output voltage Vout and current Iout. (a) Grid to battery mode and (b) Battery mode to grid mode.

Figure 11. Laboratory prototype.

Figure 10. Transition between two modes of operation, Input voltage Vin and current Iin, Outputvoltage Vout and current Iout. (a) Grid to battery mode and (b) Battery mode to grid mode.

Energies 2017, 10, 418 16 of 19

efficiency graph with maximum efficiency of 95% during battery mode and 91% during grid mode of operation. Thus utilizing soft switching in boost converter reduces the switch losses and increases the efficiency of the system. The efficiency in battery mode is high as compared to grid mode because less number of power stages are operation during this mode. Table 6 shows a comparison of the different high-frequency transformer isolated UPS systems. The proposed UPS shows a distinct improvement in terms of increasing the efficiency, reducing the size of the battery bank, and decreasing the volumetric size and weight of the system.

(a)

(b)

Figure 10. Transition between two modes of operation, Input voltage Vin and current Iin, Output voltage Vout and current Iout. (a) Grid to battery mode and (b) Battery mode to grid mode.

Figure 11. Laboratory prototype.

Figure 11. Laboratory prototype.Energies 2017, 10, 418 17 of 19

Figure 12. Efficiency graph of UPS in grid and battery mode.

Table 6. Comparison of the proposed system.

PropertiesUPS Topology

Efficiency Power

Ratings System

Specification Battery Bank

Size & Weight

An On-Line UPS System With Power Factor Correction and Electric Isolation Using BIFRED Converter [10]

- 150 VA 110 V 48 V Small

Two-Stage Uninterruptible Power Supply With High Power Factor [6]

84% 150 VA 120 V 60 V Small

A UPS With 110-V/220-V Input Voltage and High-Frequency Transformer Isolation [9]

86% 2 kVA 110/220 V 96 V High

Novel AC UPS With High Power Factor and Fast Dynamic Response [8]

- 300 VA 110 V 48 V -

Proposed UPS System 91% 1 kVA 220 V 24 V Medium

5. Conclusions

A single phase high-frequency transformer isolated online UPS has been proposed in this paper. A single-stage AC-DC converter provides galvanic isolation, efficient power conversion, and excellent power factor correction. Besides, the AC-DC converter also charges the battery bank of the UPS system during grid mode of operation. When there is a grid interruption, the low battery bank voltage is raised to high dc-link voltage using a boost converter which reduces the battery bank significantly. The boost converter provides high voltage gain with less number of active switches. A new inverter control of cascaded PR and SM control is used which provides regulated sinusoidal output voltage with low THD for both linear and non-linear load. Overall, the volume of the system is minimized by reducing the size, weight, and battery bank of the system. The experimental results show good dynamic and steady state performance.

Acknowledgments: The authors would like to acknowledge the financial support from Bahria University, Islamabad, Pakistan.

Authors Contribution: All the authors contributed in finalizing the Paper. The main idea of the paper was presented by Muhammad Aamir while Wajaht Ullah Tareen and Kafeel Ahmed Kalwar helped in the control of the circuit. Mudasser Ahmed Memon prepared the format of the paper. Saad Mekhilef is the head of research team.

Conflicts of Interest: The authors declare no conflict of interest.

References

1. Lahyani, A.; Venet, P.; Guermazi, A.; Troudi, A. Battery/supercapacitors combination in uninterruptible power supply (UPS). IEEE Trans. Power Electron. 2013, 28, 1509–1522.

2. Zhao, B.; Song, Q.; Liu, W.; Xiao, Y. Next-generation multi-functional modular intelligent UPS system for smart grid. IEEE Trans. Ind. Electron. 2013, 60, 3602–3618.

88

90

92

94

96

98

350 550 750 950

Effic

ienc

y %

Output Power (W)

Grid Mode Battery Mode

Figure 12. Efficiency graph of UPS in grid and battery mode.

Page 18: A High-Frequency Isolated Online Uninterruptible …...system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency

Energies 2017, 10, 418 18 of 20

Table 6. Comparison of the proposed system.

Properties

UPS TopologyEfficiency Power Ratings System Battery Size & WeightSpecification Bank

An On-Line UPS System With PowerFactor Correction and Electric IsolationUsing BIFRED Converter [10]

- 150 VA 110 V 48 V Small

Two-Stage Uninterruptible PowerSupply With High Power Factor [6] 84% 150 VA 120 V 60 V Small

A UPS With 110-V/220-V InputVoltage and High-FrequencyTransformer Isolation [9]

86% 2 kVA 110/220 V 96 V High

Novel AC UPS With High PowerFactor and Fast Dynamic Response [8] - 300 VA 110 V 48 V -

Proposed UPS System 91% 1 kVA 220 V 24 V Medium

5. Conclusions

A single phase high-frequency transformer isolated online UPS has been proposed in this paper.A single-stage AC-DC converter provides galvanic isolation, efficient power conversion, and excellentpower factor correction. Besides, the AC-DC converter also charges the battery bank of the UPS systemduring grid mode of operation. When there is a grid interruption, the low battery bank voltage israised to high dc-link voltage using a boost converter which reduces the battery bank significantly.The boost converter provides high voltage gain with less number of active switches. A new invertercontrol of cascaded PR and SM control is used which provides regulated sinusoidal output voltagewith low THD for both linear and non-linear load. Overall, the volume of the system is minimizedby reducing the size, weight, and battery bank of the system. The experimental results show gooddynamic and steady state performance.

Authors Contribution

All the authors contributed in finalizing the Paper. The main idea of the paper was presentedby Muhammad Aamir while Wajaht Ullah Tareen and Kafeel Ahmed Kalwar helped in the control ofthe circuit. Mudasser Ahmed Memon prepared the format of the paper. Saad Mekhilef is the head ofresearch team.

Acknowledgments: The authors would like to acknowledge the financial support from Bahria University,Islamabad, Pakistan.

Conflicts of Interest: The authors declare no conflict of interest.

References

1. Lahyani, A.; Venet, P.; Guermazi, A.; Troudi, A. Battery/supercapacitors combination in uninterruptiblepower supply (UPS). IEEE Trans. Power Electron. 2013, 28, 1509–1522. [CrossRef]

2. Zhao, B.; Song, Q.; Liu, W.; Xiao, Y. Next-generation multi-functional modular intelligent UPS system forsmart grid. IEEE Trans. Ind. Electron. 2013, 60, 3602–3618. [CrossRef]

3. Branco, C.G.; Torrico-Bascope, R.P.; Cruz, C.M.; de A Lima, F. Proposal of three-phase high-frequencytransformer isolation UPS topologies for distributed generation applications. IEEE Trans. Ind. Electron. 2013,60, 1520–1531. [CrossRef]

4. Hwang, J.-C.; Chen, J.-C.; Pan, J.-S.; Huang, Y.-C. Measurement method for online battery early faultsprecaution in uninterrupted power supply system. IET Electr. Power Appl. 2011, 5, 267–274. [CrossRef]

5. Karve, S. Three of a kind [UPS topologies, IEC standard]. IEE Rev. 2000, 46, 27–31. [CrossRef]6. Vázquez, N.; Villegas-Saucillo, J.; Hernández, C.; Rodríguez, E.; Arau, J. Two-stage uninterruptible power

supply with high power factor. IEEE Trans. Ind. Electron. 2008, 55, 2954–2962.7. Aamir, M.; Kafeel, A.K.; Mekhilef, S. Review: Uninterruptible power supply (UPS) system. Renew. Sust.

Energy Rev. 2016, 58, 1395–1410. [CrossRef]

Page 19: A High-Frequency Isolated Online Uninterruptible …...system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency

Energies 2017, 10, 418 19 of 20

8. Rodriguez, E.; Vázquez, N.; Hernández, C.; Correa, J. A novel AC UPS with high power factor and fastdynamic response. IEEE Trans. Ind. Electron. 2008, 55, 2963–2973. [CrossRef]

9. Torrico-Bascope, R.P.; Oliveira, D.S.; Branco, C.G.C.; Antunes, F.L.M. A UPS with 110-V/220-V input voltageand high-frequency transformer isolation. IEEE Trans. Ind. Electron. 2008, 55, 2984–2996. [CrossRef]

10. Nasiri, A.; Nie, Z.; Bekiarov, S.B.; Emadi, A. An on-line UPS system with power factor correction and electricisolation using BIFRED converter. IEEE Trans. Ind. Electron. 2008, 55, 722–730. [CrossRef]

11. Hirachi, K.; Yoshitsugu, J.; Nishimura, K.; Chibani, A.; Nakaoka, M. Switched-mode PFC rectifier withhigh-frequency transformer link for high-power density single phase UPS. In Proceedings of the IEEE 28thAnnual IEEE Power Electronics Specialists Conference, (PESC’97 Record), St. Louis, MO, USA, 27 June 1997;Volume 1, pp. 290–296.

12. De Rooij, M.A.; Ferreira, J.A.; van Wyk, D. A novel unity power factor low-EMI uninterruptible powersupply. IEEE Trans. Ind. Electron. 1998, 34, 870–877. [CrossRef]

13. Park, H.S.; Kim, C.H.; Park, K.B.; Moon, G.W.; Lee, J.H. Design of a charge equalizer based on batterymodularization. IEEE Trans. Veh. Technol. 2009, 58, 3216–3223. [CrossRef]

14. Lee, Y.S.; Cheng, M.W. Intelligent control battery equalization for series connected lithium-ion battery strings.IEEE Trans. Ind. Electron. 2005, 52, 1297–1307. [CrossRef]

15. Zhang, Y.; Yu, M.; Liu, F.; Kang, Y. Instantaneous current-sharing control strategy for parallel operation ofUPS modules using virtual impedance. IEEE Trans. Power Electron. 2013, 28, 432–440. [CrossRef]

16. Yang, S.; Chen, S.; Lin, J. Dynamics analysis of a low-voltage stress single-stage high-power factor correctionAC/DC flyback converter. IET Power Electron. 2012, 5, 1624–1633. [CrossRef]

17. Duarte, J.; Lima, L.R.; Oliveira, L.; Michels, L.; Rech, C.; Mezaroba, M. Single-stage high power factorstep-up/step-down isolated AC/DC converter. IET Power Electron. 2012, 5, 1351–1358. [CrossRef]

18. Ki, S.; Lu, D. Extension of minimum separable switching configuration modelling to single-stage AC/DCconverters with direct power transfer. IET Power Electron. 2012, 5, 1154–1163. [CrossRef]

19. Yang, L.-S.; Liang, T.-J.; Chen, J.-F.; Lin, R.-L. Analysis and design of a novel, single-stage, three-phaseAC/DC step-down converter with electrical isolation. IET Power Electron. 2008, 1, 154–163. [CrossRef]

20. Ma, H.; Ji, Y.; Xu, Y. Design and analysis of single-stage power factor correction converter with a feedbackwinding. IEEE Trans. Power Electron. 2010, 25, 1460–1470. [CrossRef]

21. Mahdavi, M.; Farzaneh-Fard, H. Bridgeless CUK power factor correction rectifier with reduced conductionlosses. IET Power Electron. 2012, 5, 1733–1740. [CrossRef]

22. Abasian, A.; Farzaneh-fard, H.; Madani, S. Single stage soft switching AC/DC converter without any extraswitch. IET Power Electron. 2014, 7, 745–752. [CrossRef]

23. Liang, T.-J.; Yang, L.-S.; Chen, J.-F. Analysis and design of a single-phase AC/DC step-down converter foruniversal input voltage. IET Electr. Power Appl. 2007, 1, 778–784. [CrossRef]

24. Lai, C.; Shyu, K. A single-stage AC/DC converter based on zero voltage switching LLC resonant topology.IET Electr. Power Appl. 2007, 1, 743–752. [CrossRef]

25. Lin, J.-L.; Yao, W.-K.; Yang, S.-P. Analysis and design for a novel single-stage high power factor correctiondiagonal half-bridge forward AC/DC converter. IEEE Trans. Circ. Syst. I Regul. Pap. 2006, 53, 2274–2286.[CrossRef]

26. Lu, D.-C.; Iu, H.-C.; Pjevalica, V. Single-stage AC/DC boost–forward converter with high power factor andregulated bus and output voltages. IEEE Trans. Ind. Electron. 2009, 56, 2128–2132. [CrossRef]

27. Choi, W.-Y.; Yoo, J.-S. A bridgeless single-stage half-bridge AC/DC converter. IEEE Trans. Power Electron.2011, 26, 3884–3895. [CrossRef]

28. Ribeiro, H.S.; Borges, B.V. High-performance voltage-fed AC–DC full-bridge single-stage power factorcorrectors with a reduced DC bus capacitor. IEEE Trans. Power Electron. 2014, 29, 2680–2692. [CrossRef]

29. Das, P.; Pahlevaninezhad, M.; Moschopoulos, G. Analysis and design of a new AC–DC single-stagefull-bridge PWM converter with two controllers. IEEE Trans. Ind. Electron. 2013, 60, 4930–4946. [CrossRef]

30. Erickson, R.W.; Maksimovic, D. Fundamentals of Power Electronics; Springer Science & Business Media:New York, NY, USA, 2001.

31. Aamir, M.; Mekhilef, S.; Hee-Jun, K. High-gain zero-voltage switching bidirectional converter with a reducednumber of switches. IEEE Trans. Circ. Syst. II Express Briefs 2015, 62, 816–820. [CrossRef]

32. Zargari, N.; Ziogas, P.; Joos, G. A two switch high performance current regulated DC/AC converter module.IEEE Trans. Ind. Appl. 1995, 31, 583–589. [CrossRef]

Page 20: A High-Frequency Isolated Online Uninterruptible …...system. The single-stage AC-DC converter provides rectification, with power factor correction (PFC) as well as high-frequency

Energies 2017, 10, 418 20 of 20

33. Cortes, P.; Ortiz, G.; Yuz, J.I.; Rodriguez, J.; Vazquez, S.; Franquelo, L.G. Model predictive control of aninverter with output LC filter for UPS applications. IEEE Trans. Ind. Electron. 2009, 56, 1875–1883. [CrossRef]

34. Tamyurek, B. A high-performance SPWM controller for three-phase UPS systems operating under highlynonlinear loads. IEEE Trans. Power Electron. 2013, 28, 3689–3701. [CrossRef]

35. Komurcugil, H. Rotating-sliding-line-based sliding-mode control for single-phase UPS inverters. IEEE Trans.Ind. Electron. 2012, 59, 3719–3726. [CrossRef]

36. Abrishamifar, A.; Ahmad, A.A.; Mohamadian, M. Fixed switching frequency sliding mode control forsingle-phase unipolar inverters. IEEE Trans. Power Electron. 2012, 27, 2507–2514. [CrossRef]

37. Ullah, W.; Mekhilef, S. Transformer-less 3P3W SAPF (three-phase three-wire shunt active power filter)with line-interactive UPS (uninterruptible power supply) and battery energy storage stage. Energy 2016,109, 525–536.

38. International Electro-technical Commission. Uninterruptible Power Systems (UPS)—Methods of Specifying thePerformance and Test Requirements; IEC62040-3 Standard; IEC: Geneva, Switzerland, 1999.

© 2017 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open accessarticle distributed under the terms and conditions of the Creative Commons Attribution(CC BY) license (http://creativecommons.org/licenses/by/4.0/).