A Filtering Scheme for Reducing Harmonics Penetration …apic/uploads/Research/sample14.pdf · low...
Transcript of A Filtering Scheme for Reducing Harmonics Penetration …apic/uploads/Research/sample14.pdf · low...
1
Abstract--This paper presents a novel scheme to reduce har-
monics penetration into transmission systems. The scheme utilizes
the tertiary winding of the substation transformer to construct a
low impedance path to trap harmonics at tuned frequencies. This
is achieved by inserting capacitors and inductors into the delta
loop of the tertiary winding for zero-sequence harmonics filtering
and by connecting shunt capacitors and inductors to the tertiary
winding for non-zero-sequence harmonics filtering. The proposed
topology is capable of trapping two zero-sequence harmonics and
three non-zero-sequence harmonics simultaneously. Design pro-
cedure is given in details. Simulations conducted on a detailed
modeled distribution system have demonstrated the effectiveness
of the tertiary winding. In addition, economic analysis further
confirms that the proposed tertiary winding is a much more cost-
effective solution compared to medium-voltage LC filter package.
Index Terms—Power quality, harmonics, filter.
I. INTRODUCTION
ARMONIC distortion is one of the main power quality
concerns for utility companies. Traditional approaches
for managing harmonic distortions are to limit the harmonic
currents injected by customers into the power supply systems.
An example is the IEEE Std. 519 [1]. The approach has been
very effective in mitigating the harmonic distortions caused by
large, concentrated harmonic sources such as industry facilities
with variable frequency drives. With the wide spread adoption
of standards such as the IEEE Std. 519, harmonics generated
by large industries and commercial facilities are no longer a
major concern to utility companies.
In recent years, the proliferation of energy efficient but
harmonic-producing home appliances and consumer electronic
devices has resulted in another type of harmonic distortions in
power distribution systems. These new harmonic sources have
comparable sizes and are distributed all over a network. Alt-
hough they produce insignificant amount harmonic currents
individually, the collective effect of a large number of such
loads can be substantial. Several power quality concerns have
been identified due to such distributed harmonic sources. One
of them is that residential feeders have become significant
harmonic sources, injecting unnegligible harmonic currents
into power transmission systems. The consequences could be
the overloading of transmission capacitors and transmission
level harmonic resonances etc [2].
This work was supported by the Natural Sciences and Engineering Re-
search Council of Canada and Alberta Power Industry Consortium.
The authors are with the department of Electrical and Computer Engineer-
ing, University of Alberta, Edmonton, AB T6G 2V4, Canada (email:
Two types of solutions have been proposed to address this
emerging harmonic issue so far. One solution is to reduce the
harmonic emission from individual electronic devices. IEC
61000 3-2 has been established for this purpose [3]. The sec-
ond solution is to reduce the harmonic distortions in power
distribution systems through, for example, medium and low
voltage filters [4]. Both solutions can reduce the amount of
harmonic currents injected into the transmission systems.
The penetration of harmonics from distribution systems into
transmission systems is a sensitive issue since transmission and
distribution systems often have different owners. Both types of
companies will, therefore, benefit from a solution that is dedi-
cated to preventing distribution system harmonics from pene-
trating into the transmission systems. Distribution system own-
ers may use the solution to meet the interconnection require-
ments of the transmission system regardless the harmonic dis-
tortion levels inside the distribution systems. The transmission
owner can easily verify the effectiveness of the solution in
meeting its requirements.
The objective of this paper is to investigate schemes that
can reduce the harmonic injection from distribution systems
into transmission systems. A novel filtering scheme, called the
tertiary winding filter, is proposed and its advantages and ef-
fectiveness are demonstrated through simulation studies. Eco-
nomic analysis further confirms that the proposed filter scheme
is a cost-effective solution.
This paper is organized as follows: Section II reviews the
techniques that are applicable to reduce harmonic injections
into transmission systems. Section III presents the proposed
tertiary winding filter and explains its principles. The design
method for the proposed tertiary winding filter is given in Sec-
tion IV. Section V demonstrates the effectiveness of the pro-
posed scheme through computer simulation studies and inves-
tigates the overall system performance when a few tertiary
winding filters are installed. Economic comparison is conduct-
ed in Section VI.
II. REVIEW OF APPLICABLE HARMONIC MITIGATION SCHEMES
Although little research work has been done in the area of
preventing harmonics from entering transmission systems,
techniques that can be adopted for the purpose do exist. These
techniques can be classified into two types. One is to prevent
or reduce the injection of zero sequence harmonics into the
transmission system. The other type is to deal with the non-
zero sequence harmonics.
J. W. Hagge, Senior Member, IEEE, and L. L. Grigsby, Fellow, IEEE
A Filtering Scheme for Reducing Harmonics
Penetration into Transmission Systems (V1.0)
H
2
A. Zero Sequence Harmonic Mitigation Techniques
Zero Sequence (ZS) harmonics are those harmonic compo-
nents whose are in zero sequence according to the definition of
symmetrical components. ZS components are dominant in the
3rd, 9th, 15th and other triple-order harmonics. Single phase
non-linear loads such as energy efficient home appliances are
the most significant source of ZS harmonics. It is quite com-
mon to observe high levels of ZS harmonics in a distribution
substation feeding residential loads these days.
1) Transformer Connection
For multi-grounded neutral (MGN) configuration widely
adopted in North America distribution systems, the secondary
side windings of the substation transformer are connected as
grounded Wye, while the primary side windings' connection
may vary according to corresponding requirements of the
transmission systems. The simplest way to prevent ZS harmon-
ics' propagation into transmission systems is to modify the
primary side windings' of substation transformer connection as
ungrounded Wye as shown in Fig. 1. For such a connection,
there is no pathway for ZS harmonic currents to pass through
from the secondary side to the primary side of the substation
transformer. Thus no ZS harmonics could propagate from dis-
tribution systems to transmission systems.
H XDistribution
Feeders and Loads
Transmission
System
MV BusHV Bus Substation
Transformer
Grounding
Transformer
Fig. 1 Substation transformer connection that can prevent ZS harmonics'
propagation into transmission systems.
For cases where the primary side must be grounded, a
grounding transformer may be installed at the primary bus as
shown in Fig. 1 with the dotted connection. The most common
grounding transformer is the unloaded Yg/Delta transformer
with Yg side connected to the primary bus.
2) Shunt Passive ZS Filter
A shunt filter installed at the secondary side of the substa-
tion transformer can also reduce the injection of distribution
system harmonics into the transmission system.
Shunt passive ZS filters create shunt low ZS impedance to
trap the ZS harmonics. They have various topologies (as
shown in Fig. 2) and can be broadly classified into two types.
The first type is the LC ZS filter which only consists of ca-
pacitors and inductors. It has positive/negative sequence im-
pedance so it affects the flow of non-ZS harmonics. A repre-
sentative example of such filters is the star-connected capaci-
tors grounded through an inductor (Fig. 2(a)) which is tuned to
create a low ZS impedance. The main attractive characteristic
of this topology is that by adding a three-phase inductor (Fig. 2
(b)), the capacitors can be tuned to filter positive and negative
sequence harmonics as well. The downside of this filter is that
it can affect the fundamental frequency power flow and can
lead to positive or negative sequence resonances at other fre-
quencies.
The second type of ZS filter is the transformer based ZS fil-
ter. It is developed based on the concept of grounding trans-
former. Such a filter behaves as open circuit at positive and
negative sequences so it has no impact on normal power sys-
tem operation and on non-zero-sequence harmonics. One of
the examples is the zig-zag transformer based filter (Fig. 2(c)).
A drawback of this filter is that it needs a nonstandard trans-
former. Another example consists of a Yg/delta transformer
with tuned capacitors and inductors inserted into the delta loop
(Fig. 2 (d) (e)). By proper selection of the capacitors and in-
ductors, a ZS impedance as low as the transformer’s resistance
could be achieved at desired harmonic frequencies. This leads
to attractive ZS filter topologies without using non-standard
transformers.
A B C
A B C
(a) LC Fitler 1 (b) LC Filter 2
A B C
A
B
C
A
B
C
(c) Zig-zag Trans-
former
(d) Transformer-based
Single Tuned Filter
(e) Transformer-based
Double Tuned Filter
Fig. 2 Topologies of ZS shunt filters.
It should be noted that the ZS filter can be installed at the
either side of the substation transformer theoretically. Howev-
er, because of high voltage, the primary side scheme is uneco-
nomic and hard to implement. The practical implementation,
therefore, is to install the ZS filter at the secondary side (as
shown in Fig. 3).
H XDistribution
Feeders and Loads
Transmission
System
MV BusHV Bus Substation
Transformer
ZS
Filter
Fig. 3 ZS filter installation location.
B. Non Zero Sequence Harmonic Mitigation Technique
Non Zero Sequence (non-ZS) harmonics are those harmon-
ic components whose are in positive sequence or negative se-
quence according the definition of symmetrical components.
Non-ZS components are dominant in the 5th, 7th, 11th and
other non-triple order harmonics. All the non-linear loads in-
cluding the single phase non-linear load, the two phase non-
3
linear load and the three phase non-linear loads generate non-
ZS components. This results in that the non-ZS harmonic dis-
tortion level is usually more serious than the ZS harmonic dis-
tortion level in the system.
Considering the connection types of the substation trans-
former have no impacts on the non-ZS harmonic currents’ flow
path, the only effective way to prevent the non-ZS harmonics'
propagation into the transmission system is by installing filters.
Active filters sound attractive to be applied for the MV ap-
plication due to its great flexibility. In terms of cost and relia-
bility, however, they still could not compete with the passive
filters of similar filtering performance. Similar to that in ZS
harmonics mitigation techniques, passive filters are also play-
ing a leading role in non-ZS harmonics mitigation techniques.
Among all passive filters, shunt passive filters which are
designed to be connected in parallel with the load are the most
widely used in the MV level because of their lower installation
and maintenance cost and higher operation reliability. Shunt
passive filters could be further categorized as LC non-ZS fil-
ter, LC ZS filter and transformer based ZS filter. While LC ZS
filter and transformer based ZS filter have been discussed in
the former section, Fig. 4 gives the topologies of some com-
monly used LC non-ZS filter. It should be noted that these
topologies could be used for the LC ZS filter as well, as long
as the three phase filter branches are connected in delta or
grounded Wye.
L
C
L
R
2C
1C
L
R
2C
1C
(a)LC Filter 3 (b)LC Filter 4 (c)LC Filter 5
Fig. 4 Topologies of LC non-ZS filters.
As shown in Fig. 5, similar to the ZS filter installation loca-
tion, the practical scheme to trap non-ZS harmonics also install
the filter at the secondary side of the substation transformer,
instead of the primary side considering the high cost and im-
plementation difficulty of high voltage filter.
H XDistribution
Feeders and Loads
Transmission
System
MV BusHV Bus
Filter
Substation
Transformer
Fig. 5 Non-ZS filter installation location.
C. Combined Filter
Depending on the requirements of transmission companies,
both types of filters may be required at a substation. It is pos-
sible to combine the two types of filters into one unit for cost
savings. One possible solution is the combined filter shown in
Fig. 6.
Combined Filter
A
B
C
Fig. 6 Topology of the combined filter.
The generic theory of the combined filter is based on the
Yg/delta transformer and the tuned filter. It utilizes the leakage
inductance of the transformer to create a low impedance path
to trap harmonic current at tuned frequencies. This is achieved
by inserting capacitors and inductors into the delta loop of
secondary windings for ZS harmonic filtering and by connect-
ing shunt capacitor and inductors to the secondary winding for
non-ZS sequence harmonic filtering. Similar to other tuned
filters, at tuned frequencies, the combined filter’s impedance
will only contain the resistive component (i.e. the transformer
short circuit resistance) since the reactive component of the
combined filter will be canceled out by the tuning capacitor. If
this impedance is lower than the upstream equivalent harmonic
impedance (i.e. the transmission system equivalent harmonic
impedance plus the substation transformer equivalent harmon-
ic impedance), harmonics originated from the distribution sys-
tem will be trapped by the combined filter.
This filter is very compact and could reduce costs by using
low voltage LC components. However, as mentioned above,
for this filter to effectively reduce the harmonics penetrating
into transmission systems, the transformer short circuit re-
sistance should be less than the upstream equivalent harmonic
impedance, which means a large transformer comparable to
the substation transformer is needed.
D. Summary
Current available techniques for preventing harmonics
propagation into transmission systems are summarized as
shown in Fig. 7.
Fig. 7 Applicable techniques for preventing harmonics' propagation into
transmission systems.
To prevent the harmonics from distribution systems (which
usually has a wide spectrum) from entering transmission sys-
tems, both Zero Sequence harmonic mitigation techniques and
4
non-Zero Sequence harmonic mitigation techniques should be
used.
Among all combinations, the most compact one is to install
a combined filter at the secondary side of the substation trans-
former. However, this scheme requires a large transformer to
work effectively. And other schemes with transformer based
filters also have the same problem. Considering the high cost
of a large transformer, all these schemes are not optimal op-
tions.
Compared to the scheme of the combination of the LC ZS
filter and the LC non-ZS filter, the scheme with ungrounded
primary windings and LC non-ZS filter is of less cost because
of the absence of the LC ZS filter. Nevertheless, for the cases
that the grounding at the transmission side is a must, expensive
high voltage grounding transformer should be incorporated
into this scheme (as shown in Fig. 1) and this will make this
scheme loose its cost advantage.
Actually, the primary side winding connections of the sub-
station transformer is usually fixed and could not be changed
arbitrarily which further render the applicability of the un-
grounding scheme. It should be further noted that three wind-
ing transformers are widely used by utility companies as dis-
tribution substation transformer and their common connection
is Yg/yg/delta with no loads served by the delta connected
tertiary windings.
The above situation naturally leads to the research on other
feasible passive solutions to prevent harmonics' propagation
into the transmission system for the substation with
Yg/yg/delta configured substation transformer besides the
scheme using the combination of LC ZS filter and LC non-ZS
filter.
III. PROPOSED TERTIARY WINDING FILTER
As reviewed in the previous section, several options are
available to reduce the injection of distribution system har-
monics. Each option has its advantages and limitations. The
transformer based filters have several attractive features. How-
ever, they require a transformer with small short-circuit im-
pedance. In view that many substation transformers have a
tertiary winding, it may be possible to utilize the substation
transformer as a filtering transformer on top of its power
transmission function. The need for a dedicated transformer is
thus eliminated. This reasoning has led us to propose a new
filtering scheme called “Tertiary Winding Filter”.
A. Basic Principle of the Tertiary Winding Filter
Similar to the combined filter, the basic idea of the tertiary
winding filter is to utilize the leakage inductance of the tertiary
winding to create a low impedance path to trap harmonic cur-
rents at tuned frequencies. This is achieved by inserting capac-
itors and inductors into the delta loop of the tertiary winding
for ZS harmonic filtering and by connecting shunt capacitors
and inductors to the tertiary winding for non-ZS harmonic fil-
tering. Topology of the filter is depicted in Fig. 8. Frequency
response of a sample tertiary winding filter tuned to the 3rd
and
9th
ZS harmonics and 5th
, 7th
and 11th
non-ZS harmonics is
shown in Fig. 9.
Transmission System
VSA
VSB
VSC
Zup
Substation Transformer
Bus
#1 #2
C
B
A
N
Distribution
Feeders and Loads
Tertiary Winding Filter
#3
Fig. 8 Topology of the proposed tertiary winding filter.
1 3 5 7 9 11 13 15 17 190
100
200
300
400
500
600
700
800
900
1000
Harmonic Order
Filte
r Im
pe
da
ne
ce
()
Zero sequence
Positive/Negative sequence
Fig. 9 Frequency response of a sample tertiary winding filter.
The system equivalent circuit at these tuned frequencies
seen from the secondary side of the substation transformer is
shown in Fig. 10.
Transmission System
Substation Transformer
Distribution
Feeders and LoadsBus
/ /0( )eq
DownZ h / /0( )eq
DownI h / /0 ( )eq
UpZ h
_1 0 _1Xfrm XfrmR jh L _ 2 0 _ 2Xfrm XfrmR jh L
_ 3XfrmR
#1 #2
#3
Fig. 10 Equivalent circuit of the tertiary winding filter at tuned frequencies.
Where
_1XfrmR and _1XfrmL represent the resistance and leakage
inductance of the substation transform-
er's primary winding (referred to the
secondary side)
_ 2XfrmR and _ 2XfrmL represent the resistance and leakage
inductance of the substation transform-
er's secondary winding
_ 3XfrmR represent the resistance of the substation
transformer's tertiary winding (referred
to the secondary side)
5
/ /0 ( )eq
UpZ h represents equivalent transmission sys-
tem harmonic impedance seen at the
primary side of the substation trans-
former (but referred to the secondary
side)
/ /0 ( )eq
DownZ h represents equivalent harmonic imped-
ance of distribution feeders and loads
/ /0 ( )eq
DownI h represents equivalent harmonic current
source of distribution feeders and loads
It can be seen that the tertiary winding’s impedance only
contains the resistive component since the reactive component
has been canceled out by the tuning capacitor. As a result, a
low impedance path separates the transmission and distribution
systems. Harmonics originated from the distribution system
will be bypassed by the tertiary winding before it can reach the
transmission system. In addition, typical voltage of a substa-
tion tertiary winding is 4.16kV to 13.8kV. Low voltage LC
components can be used to construct the filter, which results in
cost savings.
B. Equivalent Circuits of Tertiary Winding Filter
As shown in Fig. 8, the tertiary winding filter is composed
of two parts, i.e., the delta connection part (the delta loop) and
the star connection part (the shunt components at the tertiary
side).
Since for ZS harmonics, the star connected shunt compo-
nents at the tertiary side behaves as open circuit, the tertiary
winding filter ZS equivalent circuit only consists of the delta
connection parts (see Fig. 11(a)). For non-ZS harmonics, the
star connected shunt components at the tertiary side behave as
normal loads. Thus the tertiary winding filter non-ZS equiva-
lent circuit consists of both the delta connection part and the
star connection part (see Fig. 11(b)).
Based on the above characteristics of the tertiary filter's
equivalent circuit, the delta connection part is designed to form
a double tuned filter for the ZS harmonics and the delta con-
nection part and the star connection part together are designed
to form a triple tuned filter for the non-ZS harmonics.
Since the delta connection part is essentially the same as the
conventional double tuned filter, its components selection can
use the existing approach directly. The selection of star con-
nection part components can be illustrated intuitively by Fig.
12. As shown in Fig. 12, the delta connection part has a fre-
quency response with two series resonant tuned points (at the
two designed ZS harmonic orders h1 and h2), and one parallel
resonant point (between the two designed ZS harmonic or-
ders). The desired three non-ZS harmonic orders to filter de-
termine the crossing points of the delta connection part fre-
quency response and the star connection part. Thus the rough
shape of the star connection part frequency response is deter-
mined. According to this, the components size of the star con-
nection part could be obtained based on rigorous mathematical
equations described in Section IV.
2
2a C2
2 / aL
2
_ 3 / aXfrmL
2
_ 3 / aXfrmR
Delta connection part2
1a C
2
1 / aL
2
3a / 3C2
4a / 3C
Star connection part
2
33 / aL
2
2a C2
2 / aL
2
_ 3 / aXfrmL
2
_ 3 / aXfrmR
2
1a C
2
1 / aL
Delta connection part
2
43 / aL
(a) Equivalent ZS circuit (b) Equivalent non-ZS circuit
Fig. 11 Equivalent circuit of the tertiary winding filter.
Fig. 12 Frequency response of delta connection part and star connection part
of the tertiary winding filter.
C. Performance Analysis
This subsection is to compare the relative size of the prima-
ry impedance versus tuned tertiary impedance and show that
most harmonics will enter the tertiary path.
According to Fig. 10, for the tertiary winding filter to be ef-
fective, the equivalent impedance of the tertiary winding filter
should be less than the transmission system impedance plus
substation transformer primary side winding's impedance at
corresponding frequencies. This is an easily satisfied condi-
tion. Intuitively, the minimum impedance of the tertiary wind-
ing filter at tuned harmonic orders could be achieved as the
substation transformer tertiary winding resistance referred to
the secondary side by proper selection of the capacitors and
inductors. According to the typical parameters of three wind-
ing transformer, the tertiary winding resistance is comparable
to the primary winding resistance. And for a substation trans-
former, its reactance resistance ratio is usually very high which
means 0 _1 _1Xfrm XfrmL R .
Thus
'
_ 3 _1 0 _1
_1 0 _1 / /0 ( )
Xfrm Xfrm Xfrm
eq
Xfrm Xfrm Up
R R jh L
R jh L Z h
(1)
which means the impedance of the tertiary winding filter is far
smaller than upstream system impedance. In this way, harmon-
ics at tuned frequencies will be trapped into the tertiary side
6
rather than propagating into the transmission system.
A rough estimation of the percentage of the harmonic cur-
rent that will be trapped by the tertiary winding filter could be
obtained by the following equation:
0 _1
'
_ 3 0 _1
100%Xfrm
Xfrm Xfrm
h LRatio
R h L
(2)
where h is the tuned harmonic order.
To show the performance of the tertiary winding filter,
some of the typical sizes of the three winding transformers
used by the utility company are listed in Table I. The percent-
age of the third harmonic current that will be trapped by the
tertiary winding filter is provided in the last column. For high-
er tuned order harmonics, larger percentage will be trapped by
the tertiary winding filter.
TABLE I: TRAPPED RATIO FOR DIFFERENT SIZES OF THREE WINDING
TRANSFORMERS
Transformer Trapped
Ratio
(%)
Rated
Capacitya
(MVA)
Rated
Voltageb
(kV)
Short Circuit
Impedance
(%)
On-Load
Loss
(kW)
20/20/10 144/25/6.3
H-M 10.5
106.3 98.41 H-L 18
M-L 6.5
25/25/8 144/25/13.8
H-M 10.5
125.8 97.67 H-L 18
M-L 6.5
40/40/13.3 144/25/6.3
H-M 10.5
178.5 97.91 H-L 17
M-L 6.5
50/50/16.7 144/25/13.8
H-M 10.5
212.5 95.73 H-L 18
M-L 6.5 a The rated capacity of each winding. b The nominal line-to-line voltage (LL-rms)
IV. TERTIARY WINDING FILTER DESIGN
Similar to the design of the transformer based double tuned
ZS filter [5], the design of the tertiary winding filter is also an
iterative process based on the system harmonic load flow study
and components loading assessment. However the tertiary
winding filter design does not need to select the transformer
size, since the size of the distribution substation transformer is
primarily determined by the loads served by the substation.
The tertiary winding filter design is just the proper selection of
LC components to coordinate the transformer to trap corre-
sponding harmonics into its tertiary windings. The flowchart of
design procedure for the tertiary winding filter is shown as Fig.
13.
A. LC Components' Size Determination
As shown in Fig. 13, the determination of components’ size
consists of two steps. The first step is to determine the delta
connection part components size. As seen from Fig. 11(a), the
delta connection part is actually the same to the conventional
double tuned filter. Therefore, the proper component sizes of
the delta connection part can be derived by using the same
mathematical approach derived for the conventional double
tuned filter. According to [5] [6], the component sizes of the
delta connection part can be determined by the following equa-
tion set (3).
Set
1 _ 3XfrmL L
0, 0
Calculate the delta connection part
components’parameters
Are the delta connection part
components’ parameters reasonable?No
3 _ 3
1
3XfrmL L
Yes
0.1
Calculate the star connection part
components’ parameters
Are the star connection part
components’ parameters’ reasonable?No 0.1
Perform HLF to examine the filter performance in the system
Yes
Can the filter mitigate the problem effectively?
Overloading of the transformer winding (TLL>1)?
Yes
Overloading in capacitors?
No
The Final Filter Design
No
No
Yes
Increase the capacitor rating and Kvar without changing its
capacitance (uF)Yes
Fig. 13 Flowchart of design procedure for the tertiary winding filter.
1
2 2
2
_ 3 1
2 2
2 2
0 _ 3 1
2 2
0 _ 3 1
2
2 ( )
( )
( )( )
( )
1
( )
1
( )
i j
i j i j
i j
Xfrm i j
i j
i
i Xfrm
j
j Xfrm
C CC
C C C CC
C C
L L C CL
C C
Ch L L
Ch L L
(3)
where hi and hj represent the ZS tuned order of the tertiary
winding filter.
Once C1, C2 and L2 are determined, the star connection part
components parameter could be determined by the following
way. The non-ZS impedance of the tertiary winding filter at
harmonic order could be expressed as
2
_ 3 / _ 3
( )( ) 1/ a
( )
eq
Xfrm Xfrm
f hZ h R j
g h
(4)
7
where
2 2
0 1 1 3 _ 3
2 2 2 2
0 2 2 0 2 1
2 2
3 4 0 4 3 4
2 2 2 2
1 0 2 2 0 4 3
( ) 1 ( )
(1 )
( )
3 (1 )(1 )
Xfrmf h h C L L L
h L C h L C
C C h L C C
C h L C h L C
(5)
2 2 2 2
0 1 0 2 2 3 4 0 4 3 4( ) (1 )( )g h h C h L C C C h L C C (6)
Since the filter is tuned to have three tuned posi-
tive/negative frequencies, then f(h)=0 at corresponding har-
monic orders h1, h2 and h3, i.e.,
1
2
3
( ) 0
( ) 0
( ) 0
f h
f h
f h
(7)
By solving equations set (7), C3, C4 and L4 are determined.
It is important to note that two compensation inductors L1
and L3 are used in the tertiary winding filter, due to the leakage
inductance of the transformer which is usually small may result
in extremely large capacitance needed. By adjusting the com-
pensation ratios α and β (shown in Fig. 13), tertiary winding
filter with capacitors and inductors of achievable parameters
could be obtained and the reactive power compensated by the
filter could also be set to be the required value.
B. Components Loading Assessment
Components are susceptible to failures and even breakdown
if the voltages across them or the currents flowing through
them exceed a certain degree during a certain period of time
[4]. Thus the components loading assessment is an important
part of the filter design.
1) Transformer Loading Assessment
The transformer loading condition is evaluated by the index
TLL (Transformer Loading Level) which is developed in [5].
The TLL is defined as follows:
TLL
TLL rated
PTLL
P
(8)
where PTLL represents the winding total load loss during filter
operation, the winding maximum permissible loading capacity
is represented by PTLL-rated, which is the winding loading loss
under a rated sinusoidal current. Therefore, as long as TLL of
each winding does not exceed 1 pu, the transformer operates
safely without overheating. If the TLL of one winding exceeds
1pu (indicating the winding is overloaded), the compensation
ratio should be adjusted.
2) Capacitor Loading Assessment
For assessing the loading of the capacitors, the equivalent
loading index based on research findings of partial-discharge
caused capacitor aging is used. This equivalent loading index
is described by the following equation.
( ) ( ) ( )p frmsn nn
eq p rms fV K K K (9)
where
pn , rmsn and
fn are coefficients that describe the signifi-
cance of each factor. Their values are
dependent on the type of films used in
the capacitor.
pK , rmsK and
fK are indices describing the waveform
experienced by the capacitor, as follows
*
1
p
p
p
VK
V (10)
*
1
rms
rms
rms
VK
V (11)
2
2
1 1
Nh
p
h
VK h
V
(12)
where
pV is the peak value of the distorted voltage
*
1pV is the peak value of the rated fundamental frequen-
cy voltage
rmsV is the rms value of the distorted voltage
*
1rmsV is the rms value of the rated fundamental frequen-
cy voltage
h is the harmonic order
hV is the h order harmonic voltage.
The physical meaning of this index is that it represents a
normalized composite or equivalent voltage applied to a ca-
pacitor. If the voltage is above one, the capacitor is considered
as overloaded and its life will be shortened. If the value is less
than one, the capacitor is considered as operating within its
design limits.
3) Inductor Loading Assessment
As for the inductor, the current flowing through it should be
less than its current rated rms value. Thus the loading level of
the inductor could be defined as
*
1
rms
eq
rms
II
I (13)
where
rmsI is the rms value of the distorted current
*
1rmsI is the rms value of the rated fundamental frequen-
cy current.
V. SIMULATION STUDIES
Two test systems are selected to verify the proposed tertiary
winding filter and its design procedure as well as to examine
8
its system performance.
A. Simulation Studies on Distribution System
This subsection conducts the simulation studies on test sys-
tem #1 a generic distribution system supplying residential
loads which are evenly distributed along five feeders. Fig. 14
depicts the network configuration of test system #1, in which
each section block consists of three service transformers which
are connected to the secondary system serving 10 residential
houses. Transmission
System
Zup
Substation
Transformer
#1 #2
#3
Primary System
S72
VSC
VSA
VSB
A B C N
Line
S1
Rg
S2
Feeder 1
S72S1 S2
Feeder 2
S72S1 S2
Feeder 5
Section
Fig. 14 Network configuration of test system #1.
1) Tertiary Winding Filter Design Results
The introduced iterative process (Fig. 13) was employed to
determine the final filter design. Table II presents the compo-
nents size of the designed tertiary winding filter.
TABLE II: DESIGNED COMPONENTS SIZE OF THE TERTIARY WINDING FILTER
Delta connection part
L1 None
C1 160.43kvar (0.6 kV)a
L2 0.235mH(794A)b
C2 90.24kvar (0.6kV)
Star connection part
L3 0.490mH(794A)
C3 1033.35kvar(4.16kV)
L4 1.702mH(794A)
C4 637.08kvar (4.16kV) a The voltage in the bracket is the capacitor rated voltage. b The current in the bracket is the inductor rated current, the inductor rated
voltage is 6.3kV.
2) Simulation Results
All the developed models are employed in a multiphase
harmonic power flow program to perform the simulation stud-
ies. As the residential loads are time-varying during a day,
time-varying simulation results are obtained.
In order to establish a sound understanding of the proposed
tertiary winding filter performance, the simulation results for
both the case without tertiary winding filter and the case with
tertiary winding filter are shown in Fig. 15 to Fig. 18.
As seen from Fig. 15 to Fig. 18, both the harmonic currents
propagating into the transmission system and the harmonic
voltages at the primary side of the substation transformer have
been greatly reduced, which demonstrates the effectiveness of
the proposed filter.
1 3 5 7 9 11 13 15 17 19 21 230
2
4
6
8
10
Time (h)
%
TDD -- Without Tertiary Winding Filter
Phase A
Phase B
Phase C
1 3 5 7 9 11 13 15 17 19 21 230
2
4
6
8
10
Time (h)
%
TDD -- With Tertiary Winding Filter
Phase A
Phase B
Phase C
(a) (b)
Fig. 15 TDD variation of the currents propagating into the transmission sys-
tem.
(a) (b)
1 3 5 7 9 11 13 150
1
2
3
4
5
Harmonic Order
%
IDD Spectrum -- Without Tertiary Winding Filter
Positive sequence
Negative sequence
Zero sequence
1 3 5 7 9 11 13 150
1
2
3
4
5
Harmonic Order
%
IDD Spectrum -- With Tertiary Winding Filter
Positive sequence
Negative sequence
Zero sequence
Fig. 16 Typical IDD spectrum of the currents propagating into the transmis-
sion system.
(a) (b)
1 3 5 7 9 11 13 15 17 19 21 230
1
2
3
4
5
Time (h)
%
THD -- Without Tertiary Winding Filter
Phase A
Phase B
Phase C
1 3 5 7 9 11 13 15 17 19 21 230
1
2
3
4
5
Time (h)
%
THD -- With Tertiary Winding Filter
Phase A
Phase B
Phase C
Fig. 17 THD variation of the voltages at the primary side of the substation
transformer.
(a) (b)
1 3 5 7 9 11 13 150
0.5
1
1.5
2
2.5
Harmonic Order
%
IHD Spectrum -- Without Tertiary Winding Filter
Positive sequence
Negative sequence
Zero sequence
1 3 5 7 9 11 13 150
0.5
1
1.5
2
2.5
Harmonic Order
%
IHD Spectrum -- With Tertiary Winding Filter
Positive sequence
Negative sequence
Zero sequence
Fig. 18 Typical IHD spectrum of the voltages at the primary side of the sub-
station transformer.
B. Simulation Studies on Transmission System
This subsection conducts several simulation studies on test
system #2 an extension of the IEEE 14 bus transmission sys-
tem proposed in [10] aiming to further examine:
Will the distribution harmonic loads at other bus lead to the
tertiary winding filter overloading?
Is it essential to equip all the buses with distribution har-
monic loads with the tertiary winding filter?
Fig. 19 presents the network configuration of test system
#2.
1) Influence of Distribution Harmonic Loads at Other Bus-
es
In the previous sections, the tertiary winding filter was
thoroughly examined in the distribution system. However in
the tertiary winding filter design, loading assessment was con-
ducted without considering the influence of distribution har-
monic loads at other buses. Will this be an issue for the tertiary
9
winding filter if there are multiple distribution harmonic loads
at other buses in the transmission system? To answer this ques-
tion, eight sets of cases are studied. Each set of cases consists
of two cases: 1) for the first case there is no other distribution
harmonic load at other buses except where the tertiary winding
filter is installed; 2) for the second case all the load buses are
modified as distribution harmonic loads. The detailed descrip-
tion of these cases is follows:
Case
Set Case
Filter
Placement Distribution Harmonic Loads Location
1
i Bus 4 Bus 4
ii Bus 4 Bus 4, Bus 5, Bus 9, Bus 10, Bus 11,
Bus 12, Bus 13, Bus 14
2
i Bus 5 Bus 5
ii Bus 5 Bus 4, Bus 5, Bus 9, Bus 10, Bus 11,
Bus 12, Bus 13, Bus 14
3
i Bus 9 Bus 9
ii Bus 9 Bus 4, Bus 5, Bus 9, Bus 10, Bus 11,
Bus 12, Bus 13, Bus 14
4
i Bus 10 Bus 10
ii Bus 10 Bus 4, Bus 5, Bus 9, Bus 10, Bus 11,
Bus 12, Bus 13, Bus 14
5
i Bus 11 Bus 11
ii Bus 11 Bus 4, Bus 5, Bus 9, Bus 10, Bus 11,
Bus 12, Bus 13, Bus 14
6
i Bus 12 Bus 12
ii Bus 12 Bus 4, Bus 5, Bus 9, Bus 10, Bus 11,
Bus 12, Bus 13, Bus 14
7
i Bus 13 Bus 13
ii Bus 13 Bus 4, Bus 5, Bus 9, Bus 10, Bus 11,
Bus 12, Bus 13, Bus 14
8
i Bus 14 Bus 14
ii Bus 14 Bus 4, Bus 5, Bus 9, Bus 10, Bus 11,
Bus 12, Bus 13, Bus 14
G
G
G
1
2
3
5
6
12
13
11 10
14
9
4
7
8
SVC
Converter
Fig. 19 Network configuration of test system #2
Loading assessment for all eight case sets show that the dis-
tribution harmonic loads at other buses do have influence on
the loading level of the tertiary winding filter. But the influ-
ence is different for the tertiary winding filter at different loca-
tions. According to Case Set 4, 5 and 6, the tertiary winding
filter designed based on the distribution harmonic load infor-
mation at its own bus will be overloaded by distribution har-
monic loads at other buses. Thus if multiple distribution har-
monic loads exist, the transmission system harmonic power
flow should be incorporated into the tertiary winding filter
loading assessment and components of larger size should be
adopted when overloading issues are identified.
2) Installation Density Study
This subsection presents the sensitivity study to assess the
influence of the installation density of the tertiary winding fil-
ter on the overall transmission system harmonic distortion lev-
el. Simulation results for the following cases are compared in
Table IV and Table V.
i. Test system # 2 with the loads at bus 4, bus 5, bus 9, bus
10, bus 11, bus 12, bus 13 and bus 14 all modified as a
distribution harmonic load.
ii. Based on i, install one tertiary winding filter at any one
of the buses with distribution harmonic loads.
iii. Based on i, install one tertiary winding filter at any two
of the buses with distribution harmonic loads respective-
ly.
iv. Based on i, install one tertiary winding filter at any
three of the buses with distribution harmonic loads re-
spectively.
…
ix. Based on i, install one tertiary winding filter at all buses
with distribution harmonic loads respectively.
In Table III, the average voltage THD for 230kV buses,
115kV buses and the overall system is given, while in Table
IV the average current TDD for 230kV lines, 115kV lines,
transmission transformers and the overall system is given. As
shown in these two tables, the more the tertiary winding filter
installed the lower the overall transmission system harmonic
distortion level is in terms of both the bus voltage THD and
transmission equipment TDD.
TABLE III: VOLTAGE DISTORTION LEVEL
Case
Average Voltage THD (%)
230kV
Buses
115kV
Buses Overall System
i 8.45 9.83 9.24
ii 8.26 8.90 8.63
iii 8.10 8.05 8.07
iv 7.82 7.23 7.48
v 7.21 6.31 6.70
vi 6.17 5.26 5.65
vii 4.81 4.12 4.41
viii 3.32 3.02 3.15
ix 1.70 1.94 1.84
TABLE IV: CURRENT DISTORTION LEVEL
Case
Average Current TDD (%)
230kV Lines 115kV Lines Transmission
Transformers
Overall
System
i 6.56 18.88 18.34 14.23
ii 6.20 18.79 17.68 13.92
iii 5.89 18.44 16.96 13.50
iv 5.54 17.90 16.18 12.98
v 5.02 17.15 15.33 12.30
vi 4.28 16.11 14.37 11.39
vii 3.37 14.76 13.31 10.26
viii 2.39 12.92 12.17 8.88
ix 1.35 11.46 10.90 7.62
10
Fig. 20 depicts the average and minimum voltage distortion
level and current distortion level for each filter installation
density.
Fig. 20 Average minimum harmonic distortion level for different cases
Table V further gives the filter placement which results the
minimum harmonic distortion level for case ii ~ case viii and
the corresponding overall system voltage distortion level and
current distortion level with such placement.
TABLE V: OPTIMUM FILTER PLACEMENT FOR DIFFERENT CASES
Case Optimum Filter Placement
Overall System
Harmonic Distortion
Voltage
THD* (%)
Current TDD*
(%)
ii Bus 9 6.70(8.63) 12.14(13.92)
iii Bus 9, Bus 14 5.61(8.07) 10.49(13.50)
iv Bus 9, Bus 10, Bus 14 4.92(7.48) 10.09(12.98)
v Bus 9, Bus 10, Bus 14, Bus 4 3.86(6.70) 8.83(12.30)
vi Bus 9, Bus 10, Bus 14,
Bus 4, Bus 5 2.93(5.65) 8.37(11.39)
vii Bus 9, Bus 10, Bus 14,
Bus 4, Bus 5, Bus 13 2.25(4.41) 8.31(10.26)
viii Bus 9, Bus 10, Bus 14, Bus 4,
Bus 5, Bus 13, Bus 12 2.01(3.15) 7.87(8.88)
*Figure in the bracket is the average value for each case.
As indicated by Fig.20 and Table V, with optimum filter
placement, better harmonic mitigation effects can be achieved.
Another useful information could be extracted from Table V is
the distribution harmonic loads at Bus 9 have the largest im-
pacts on the overall system distortion level since for all the
optimum filter placement one tertiary winding filter should be
placed at Bus 9. Possible explanation for this is that the trans-
fer impedance between Bus 9 and other buses are much larger
than that between other buses. Further frequency scan studies
are needed to confirm this.
VI. COMPARATIVE ECONOMIC ANALYSIS
The cost of the proposed tertiary winding filter has been in-
vestigated using the test system #1. It is also compared with
the cost of the MV LC filter package.
To obtain a meaningful comparison, the MV LC filter
package is designed to achieve the same harmonic distortion
reduction with the tertiary winding filter specified by Table II.
The designed MV LC filter package shown as Fig. 21 consists
of two inductor grounded single tuned LC filters which are
tuned to filter the 3rd , 5th and 9th and 11th harmonics respec-
tively and one directly grounded single tuned LC filter which
is tuned to filter the 7th harmonic. The designed components
size of the MV LC filter package is given in Table VI.
TABLE VI: DESIGNED COMPONENT SIZE OF MV LC FILTER PACKAGE
Filter
Design
Tuned Harmonic
Order Component Size
Filter 1 3, 5
L 56.141mH (208A)
C 1875.28kvar (31.5kV)
L0 33.269mH (416A)
Filter 2 7 L 28.071mH (69A)
C 488.77kvar (15.92kV)
Filter 3 9, 11
L 11.228mH (69A)
C 494.84kvar (15.92kV)
L0 1.848mH (69A) a The voltage in the bracket is the capacitor rated voltage.
b The current in the bracket is the inductor rated current, the
inductor rated voltage is 14.4kV.
For the cost estimation, the data collected from [5] and the
internet are used. Table VII to Table X show the approximate
expenses with filter components and installation.
TABLE VII: COST OF CAPACITORS
Rated
voltage <1kV 1kV~10kV 10kV~25kV 25kV~50kV
Cost $15/kvar $20/kvar $40/kvar $65/kvar
TABLE VIII: COST OF INDUCTORS
Voltage Level
1kV~10kV 10kV~25kV
Rated Current
<100A $1400 $2800
100A~500A $1700 $3400
500A~1000A $1900 $3800
TABLE IX: COST OF OTHER COMPONENTS
1kV~10kV 10kV~25kV
Switching Device $17,000 $34,000
Protection Device $3,500 $7,000
TABLE X: ESTIMATED COST FOR FILTER INSTALLATION
Civil $7,000
Engineering & Design $28,000
Labor Costa $12,000
a Labor cost is based on: 3 persons * 8hour/day *5days *$100/hour
By the above set of information, the overall cost of the ter-
tiary winding filter and MV LC filter package is estimated as
presented in Table XI. As seen from Table XI, the tertiary
winding filter is found be much more economical.
TABLE XI: OVERALL ESTIMATED COST
Tertiary Winding Filter MV LC Filter Package
Components
Cost $149,110 $557,910
Installation
Cost $40,700 $40,700
Total Cost $189,810 $598,610
VII. CONCLUSIONS
This paper presented a novel and effective filter to prevent
harmonic currents propagating into the transmission system.
The design issues of the proposed filters are fully investigated.
The main findings and contributions of this paper could be
summarized as follows.
The proposed tertiary winding filter could trap two ZS har-
monics and three non-ZS harmonics simultaneously. It be-
comes a very desirable method to mitigate harmonic cur-
rents with a wide spectrum.
11
The proposed filter and its design method have been tested
through two comprehensive test systems. The results have
demonstrated the effectiveness of the filter and also reveal
proper placement could achieve the same reduction of the
overall system harmonic distortion level with fewer filters.
Compared to other transformer based filters, the most im-
portant benefit of the proposed tertiary filter is that it utiliz-
es the existing substation transformer which greatly reduces
the filter cost. Furthermore, actually three winding trans-
formers are widely used by utility companies in Canada as
distribution substation transformer and their common con-
nection is Yg/yg/delta with no loads served by the delta
connected tertiary windings. This means the proposed ter-
tiary filter has a bright application prospect.
Economic analysis further confirmed that the proposed ter-
tiary winding filter is a cost effective solution for prevent-
ing harmonics' propagation from the distribution system in-
to the transmission system.
VIII. REFERENCES
[1] "IEEE Recommended Practices and Requirements for Harmonic Con-
trol in Electrical Power Systems," IEEE Std 519-1992, pp. 1-112, 1993.
[2] J. Aririllaga, D. A. Bradley , P. S. Bodger, Power System Harmonics:
John Wiley & Sons Ltd, 1985.
[3] IEC Standard 61000-3-2: Electromagnetic compatibility (EMC) Part 3-
2: Limits - Limits for harmonic current emissions (equipment input cur-
rent ≤16A per phase), 2009.
[4] A. B. Nassif, X. Wilsun, and W. Freitas, "An Investigation on the Selec-
tion of Filter Topologies for Passive Filter Applications," Power Deliv-
ery, IEEE Transactions on, vol. 24, pp. 1710-1718, 2009.
[5] P. Bagheri, "Methods to mitigate harmonics in residential power distri-
bution systems," M. Sc. dissertation, Dept. Elect. Comput. Eng., Univ.
Alberta, Edmonton, AB, Canada, 2013.
[6] P. Bagheri and W. Xu, "A Technique to Mitigate Zero-Sequence Har-
monics in Power Distribution Systems," IEEE Trans. Power Del., vol.
29, pp. 215-223, Feb. 2014.
[7] D. Salles, J. Chen, W. Xu, W. Freitas, and H. E. Mazin, "Assessing the
Collective Harmonic Impact of Modern Residential Loads - Part I
Methodology," IEEE Trans. Power Del., vol. 27, pp. 1937-1946, Oct.
2012.
[8] J. Chen, D. Salles, W. Xu, and W. Freitas, "Assessing the Collective
Harmonic Impact of Modern Residential Loads - Part II: Application,"
IEEE Trans. Power Del., vol. 27, pp. 1947-1955, Oct. 2012.
[9] W. Xu, J. R. Marti, and H. W. Dommel, "A multiphase harmonic load
flow solution technique," Power Systems, IEEE Transactions on, vol. 6,
pp. 174-182, 1991.
[10] R. Abu-Hashim, R. Burch, G. Chang, M. Grady, E. Gunther, M. Halpin,
et al., "Test systems for harmonics modeling and simulation," Power
Delivery, IEEE Transactions on, vol. 14, pp. 579-587, 1999.
Pooya Bagheri obtained the B.Sc. degree in electrical engineering from
Sharif University of Technology, Tehran, Iran, in 2010 and the M.Sc. degree
in electrical engineering from the University of Alberta, Edmonton, AB,
Canada, in 2013. Currently, he is with the Electrical Engineering Department,
Oil & Gas segment, Stantec Consulting Ltd., Edmonton, AB, Canada. His
research interests are power quality and power distribution systems.
Wilsun Xu (M’90-SM’95-F’05) obtained the Ph.D. degree from the Universi-
ty of British Columbia, Vancouver, in 1989. Currently, he is a
NSERC/iCORE Industrial Research Chair Professor at the University of
Alberta. His current main research interests are power quality and power
disturbance analytics.
Tianyu Ding (S'12) obtained the B.Sc. degree in electrical engineering from
Shandong University, Jinan, China, in 2010. Currently, he is pursuing his
Ph.D. degree in Electrical and Computer Engineering at the University of
Alberta, Edmonton, AB, Canada. His main research interest is power quality.
1
Abstract—The widespread adoption of energy efficient but
harmonic-producing loads in residential homes has led to in-
creased injection of harmonic currents into transmission systems.
In response to this situation, a novel filtering scheme that can
reduce the harmonic penetration into transmission systems is
proposed. The scheme utilizes the tertiary winding of a substation
transformer to construct a tuned low impedance path for the
harmonic currents. The proposed scheme is capable of trapping
two zero-sequence harmonics and three non-zero-sequence har-
monics simultaneously. Design procedure has been developed.
Performance of the scheme is evaluated and demonstrated
through simulation studies. In addition, economic analysis reveals
that the scheme is a cost-effective solution in comparison with
other applicable methods.
Index Terms—Power quality, harmonics, passive filter.
I. INTRODUCTION
N recent years, the proliferation of energy efficient but har-
monic-producing home appliances and consumer electronic
devices has resulted in a new type of harmonic distortions in
power distribution systems. These new harmonic sources have
comparable sizes and are distributed all over a network. Alt-
hough they produce insignificant amount harmonic currents
individually, the collective effect of a large number of such
loads can be substantial [1-6]. Several power quality concerns
have been identified due to such distributed harmonic sources
[1-3, 5-9]. One of them is that distribution systems are inject-
ing significant amount of harmonic currents into transmission
systems [2, 6]. The consequences include overloading of
transmission capacitors, tripping of HVDC filters, and in-
creased incidents of transmission harmonic resonances [10-12].
It is common nowadays that transmission and distribution
systems are owned by different owners due to electricity mar-
ket deregulation. The penetration of harmonic currents from
distribution systems into transmission systems is becoming a
sensitive issue. For example, several jurisdictions have im-
posed limits on such harmonics [13-14]. Therefore, both types
of companies will benefit from a solution that can prevent dis-
tribution system harmonics from penetrating into the transmis-
sion systems. Distribution system owners may use the solution
to meet the interconnection requirements regardless the har-
monic distortion levels inside the distribution systems. The
This work was supported by the Natural Sciences and Engineering Re-
search Council of Canada and Alberta Power Industry Consortium.
The authors are with the department of Electrical and Computer Engineer-
ing, University of Alberta, Edmonton, AB T6G 2V4, Canada (email:
transmission owner can easily recognize the solution taken by
the distribution company and verify its effectiveness.
Motivated by the above considerations, this paper presents
a novel filtering scheme that can reduce the harmonic injection
from distribution systems into transmission systems. The basic
idea is to utilize the tertiary winding of the substation trans-
former to create a tuned low impedance path for the harmon-
ics. The proposed filtering scheme is therefore called “tertiary
winding filter”. In the following sections, subjects such as fil-
ter topology, design method, performance assessment and cost
analysis are presented.
II. REVIEW OF APPLICABLE MITIGATION SCHEMES
Although little research work has been done in the direction
of preventing harmonics from entering transmission systems,
techniques that can be adopted for the purpose do exist. These
techniques can be classified into two types. One is to prevent
or reduce the injection of zero-sequence (ZS) harmonics into
the transmission system. The other type is to deal with the pos-
itive and negative harmonics. These harmonics are collected
termed as non-zero-sequence (NZS) harmonics in this paper.
A. Zero-Sequence Harmonic Mitigation Techniques
ZS components are dominant in the 3rd
, 9th
and other triple-
order harmonics. Single phase non-linear loads such as energy
efficient home appliances are the most significant source of ZS
harmonics. It is quite common to observe high levels of ZS
harmonics in a distribution substation feeding residential loads
these days [2, 5, 9].
1) Transformer Connection
The simplest way to prevent ZS harmonics' propagation in-
to transmission systems is to configure the substation trans-
former’s primary side into delta or ungrounded Wye connec-
tion. For such connections, there are paths for the ZS harmonic
currents to flow into the primary side. For cases where the
primary side must be grounded, a grounding transformer [15]
may be installed at the primary bus to serve as the grounding
point.
2) Passive Zero-Sequence Filter
Shunt passive ZS filters create low ZS impedance to trap
the ZS harmonics. They have various topologies and can be
broadly classified into two types. The first type is the LC filter.
A representative example of such filters is the star-connected
capacitors grounded through an inductor [16]. This filter has
positive/negative sequence impedance so it affects the flow of
NZS harmonics. The second type is the transformer based ZS
Tianyu Ding, Student Member, IEEE, and Wilsun Xu, Fellow, IEEE
A Filtering Scheme to Reduce the Penetration of
Harmonics into Transmission Systems (Final)
I
2
filter which is derived from the grounding transformer. This
type has no impact on the normal power system operation and
on NZS harmonics since they behave as open circuit at posi-
tive and negative sequences. Examples include the zig-zag
transformer based filter [17] and the Yg/delta transformer
based single tuned ZS filter [18] and double tuned ZS filter
[19].
B. Non-Zero-Sequence Harmonic Mitigation Technique
NZS components are dominant in the 5th
, 7th
and other non-
triple order harmonics. All non-linear loads generate NZS
harmonics. As a result, NZS harmonic distortion level is usual-
ly higher than the ZS harmonic distortion level. At present, the
only known method to mitigate NZS harmonic in medium-
voltage (MV) or high-voltage (HV) systems is the passive
shunt filters. Commonly used LC NZS filters include the tuned
filter, damped filter and the C type filter [20-22]. These filters
can be installed in the secondary side of the substation, creat-
ing a low impedance path to trap the harmonics originated
from the distribution systems.
C. Summary
It can be seen that the options to prevent the harmonics
from entering transmission systems are limited. Some of them
are adopted from the methods developed for other applica-
tions. It is, therefore, worthwhile to investigate solutions that
are dedicated to addressing the problem and, thus, can take
advantages of the specific characteristics of the substation con-
figurations.
III. PROPOSED TERTIARY WINDING FILTER
In view that many substation transformers have a tertiary
winding [23], it may be possible to utilize the substation trans-
former as a filtering transformer on top of its power transmis-
sion function. The need for a dedicated filtering transformer is
thus eliminated. This reasoning has led us to propose a new
filtering scheme called “Tertiary Winding Filter”.
A. Basic Principle of the Tertiary Winding Filter
The basic idea of the tertiary winding filter is to utilize the
leakage inductance of the tertiary winding to create a low im-
pedance path to trap harmonic currents at tuned frequencies.
This is achieved by inserting capacitors and inductors into the
delta loop of the tertiary winding for ZS harmonic filtering and
by connecting shunt capacitors and inductors to the tertiary
winding for NZS harmonic filtering. Topology of the filter is
depicted in Fig. 1.
The system equivalent circuit at these tuned frequencies
seen from the secondary side of the substation transformer is
shown in Fig. 2.
In Fig.2, _1XfrmR and _1XfrmL represent the leakage re-
sistance and leakage inductance of the substation transformer's
primary winding (referred to the secondary side), _ 2XfrmR and
_ 2XfrmL represent the leakage resistance and leakage induct-
ance of the substation transformer's secondary winding,
_ 3XfrmR represents the leakage resistance of the substation
transformer's tertiary winding (referred to the secondary side),
/ /0 ( )eq
UpZ h represents equivalent transmission system harmon-
ic impedance seen at the primary side of the substation trans-
former (but referred to the secondary side), / /0 ( )eq
DownZ h and
/ /0 ( )eq
DownI h represent equivalent harmonic impedance and
harmonic current source of distribution feeders and loads.
Transmission System
Substation Transformer
#1 #2
C
B
A
N
Distribution
Feeders and Loads
Tertiary Winding Filter
#3
SAV
SBV
SCV
up
Z
Bus
Fig. 1 Topology of the proposed tertiary winding filter.
Transmission System
Substation Transformer
Distribution Feeders and Loads
Bus
/ /0( )eq
DownZ h / /0( )eq
DownI h / /0 ( )eq
UpZ h
_1 0 _1Xfrm XfrmR jh L _ 2 0 _ 2Xfrm XfrmR jh L
_ 3XfrmR
#1 #2
#3
Fig. 2 Equivalent circuit of the tertiary winding filter at tuned frequencies.
It can be seen that the tertiary winding’s impedance only
contains the resistive component, i.e. the leakage resistance of
the tertiary winding, since the reactive component has been
canceled out by the tuning capacitors. As a result, a low im-
pedance path separates the transmission and distribution sys-
tems. Harmonics originated from the distribution system will
be bypassed by the tertiary winding before it can reach the
transmission system. In addition, typical voltage of a substa-
tion transformer tertiary winding is 4.16kV to 13.8kV. Low
voltage LC components can be used to construct the filter,
which results in cost savings.
B. Equivalent Circuits of Tertiary Winding Filter
As shown in Fig. 1, the tertiary winding filter is composed
of two parts, i.e., the delta connection part (the delta loop) and
the star connection part (the shunt components at the tertiary
side).
Since for ZS harmonics, the star connected shunt compo-
nents at the tertiary side behaves as open circuit, the tertiary
winding filter ZS equivalent circuit only consists of the delta
connection parts (see Fig. 3(a)). For NZS harmonics, the star
3
connected shunt components at the tertiary side behave as
normal loads. Thus the tertiary winding filter NZS equivalent
circuit consists of both the delta connection part and the star
connection part (see Fig. 3(b)). It should be noted that in Fig.
3, a represents the tertiary winding to secondary winding turn
ratio.
2
2a C2
2 / aL
2
_ 3 / aXfrmL
2
_ 3 / aXfrmR
Delta connection part2
1a C
2
1 / aL
2
3a / 3C2
4a / 3C
Star connection part
2
33 / aL
2
2a C2
2 / aL
2
_ 3 / aXfrmL
2
_ 3 / aXfrmR
2
1a C
2
1 / aL
Delta connection part
2
43 / aL
(a) Equivalent ZS circuit (b) Equivalent NZS circuit
Fig. 3 Equivalent circuit of the tertiary winding filter.
Based on the above characteristics of the tertiary winding
filter's equivalent circuit, the delta connection part is designed
to form a double tuned filter for the ZS harmonics and the del-
ta connection part and the star connection part together are
designed to form a triple tuned filter for the NZS harmonics.
C. Feasibility Analysis
This subsection is to compare the relative size of the prima-
ry impedance versus tuned tertiary impedance and to show that
most harmonics will enter the tertiary path.
According to Fig. 2, for the tertiary winding filter to be ef-
fective, the equivalent impedance of the tertiary winding filter
should be less than the transmission system impedance plus
substation transformer primary side winding's impedance at
corresponding frequencies. This is an easily satisfied condi-
tion. Intuitively, the minimum impedance of the tertiary wind-
ing filter at tuned harmonic orders could be achieved as the
substation transformer tertiary winding resistance referred to
the secondary side by proper selection of the capacitors and
inductors. According to the typical parameters of three wind-
ing transformer, the tertiary winding resistance is comparable
to the primary winding resistance. And for a substation trans-
former, its reactance resistance ratio is usually very high [24]
which means 0 _1 _1Xfrm XfrmL R .
Thus
'
_ 3 _1 0 _1
_1 0 _1 / /0 ( )
Xfrm Xfrm Xfrm
eq
Xfrm Xfrm Up
R R jh L
R jh L Z h
(1)
which means the impedance of the tertiary winding filter is far
smaller than upstream system impedance. In this way, harmon-
ics at tuned frequencies will be trapped into the tertiary side
rather than propagating into the transmission system.
A rough estimation of the percentage of the harmonic cur-
rent that will be trapped by the tertiary winding filter could be
obtained by the following equation:
0 _1
'
_ 3 0 _1
100%Xfrm
Xfrm Xfrm
h LRatio
R h L
(2)
where h is the tuned harmonic order.
To show the performance of the tertiary winding filter,
some of the typical sizes of the three winding transformers
used by the utility company are listed in Table I. The percent-
age of the third harmonic current that will be trapped by the
tertiary winding filter is provided in the last column. For high-
er tuned order harmonics, larger percentage will be trapped by
the tertiary winding filter.
TABLE I: TRAPPED RATIO FOR DIFFERENT THREE WINDING TRANSFORMERS
Transformer Parameter Trapped
Ratio
(%)
Rated
Capacitya
(MVA)
Rated
Voltageb
(kV)
Short Circuit
Impedance
(%)
On-Load
Loss
(kW)
20/20/10 144/25/6.3
H-M 10.5
106.3 98.41 H-L 18
M-L 6.5
25/25/8 144/25/13.8
H-M 10.5
125.8 97.67 H-L 18
M-L 6.5
32/32/16 144/25/4.16
H-M 10.5
148.8 98.55 H-L 17
M-L 6.5
40/40/13.3 144/25/6.3
H-M 10.5
178.5 97.91 H-L 17
M-L 6.5
50/50/16.7 144/25/13.8
H-M 10.5
212.5 98.11 H-L 18
M-L 6.5 a The rated capacity of each winding. b The nominal line-to-line voltage (LL-rms)
IV. TERTIARY WINDING FILTER DESIGN
The design of the tertiary winding filter is an iterative pro-
cess based on the system harmonic load flow study and com-
ponents loading assessment. The design objective is to deter-
mine proper LC component parameters based on the trans-
former parameters. The flowchart of design procedure is
shown as Fig. 4.
A. LC Components' Size Determination
As shown in Fig. 4, the determination of components’ size
consists of two steps. The first step is to determine the delta
connection part components size. As seen from Fig. 3(a), the
delta connection part is actually the same to the double tuned
filter. Based on analytical derivations, the component parame-
ters of the delta connection part can be determined by the
equation set (3).
4
Set
1 _ 3XfrmL L
0, 0
Size delta connection part components
Increase the
capacitor rated
voltage and kvar
Size star connection part components
Final Filter Design
Increase the
inductor rated
current and kvar
Overloading in
inductors?
Are the parameters
reasonable?
Overloading in capacitors?
Yes
No
Yes
3 _ 3 / 3XfrmL L
Are the parameters
reasonable?
Overloading in transformer windings?
No
No
Yes
No
Yes
0.1
No0.1
Yes
Fig. 4 Flowchart of design procedure for the tertiary winding filter.
1
2 2
2
_ 3 1
2 2
2 2
0 _ 3 1
2 2
0 _ 3 1
2
2 ( )
( )
( )( )
( )
1
( )
1
( )
i j
i j i j
i j
Xfrm i j
i j
i
i Xfrm
j
j Xfrm
C CC
C C C CC
C C
L L C CL
C C
Ch L L
Ch L L
(3)
where hi and hj represent the ZS tuned order of the tertiary
winding filter.
Once C1, C2 and L2 are determined, the star connection part
components parameter could be determined by the following
way. The NZS impedance of the tertiary winding filter at har-
monic order could be expressed as
_ 3 / _ 32
1 ( )( )
( )a
eq
Xfrm Xfrm
f hZ h R j
g h
(4)
where
2 2
0 1 1 3 _ 3
2 2 2 2
0 2 2 0 2 1
2 2
3 4 0 4 3 4
2 2 2 2
1 0 2 2 0 4 3
( ) 1 ( )
(1 )
( )
3 (1 )(1 )
Xfrmf h h C L L L
h L C h L C
C C h L C C
C h L C h L C
(5)
2 2 2 2
0 1 0 2 2 3 4 0 4 3 4( ) (1 )( )g h h C h L C C C h L C C (6)
Since the filter is tuned to three NZS frequencies, then
f(h)=0 at corresponding harmonic orders h1, h2 and h3, i.e.,
1 2 3( ) 0, , ,f h h h h h (7)
By solving equations set (7), C3, C4 and L4 are determined.
It is important to note that two compensation inductors L1
and L3 are used in the tertiary winding filter, due to the leakage
inductance of the transformer which is usually small may result
in extremely large capacitance needed. By adjusting the com-
pensation ratios α and β (shown in Fig. 4), tertiary winding
filter with capacitors and inductors of achievable parameters
could be obtained and the reactive power compensated by the
filter could also be set to be the required value.
B. Components Loading Assessment
Components are susceptible to failures and even breakdown
if the voltages across them or the currents flowing through
them exceed a certain degree during a certain period of time
[22]. Thus the components loading assessment is an important
part of the filter design. In the tertiary winding filter design,
the transformer loading condition is evaluated by the index
TLL (Transformer Loading Level) which is developed in [19].
For assessing the loading of the capacitors, the equivalent
loading index based on research findings of partial-discharge
caused capacitor aging is used [25]. As for the inductor, its
loading level is evaluated by the current flowing through it
normalized by its current rated rms value [20]. As long as the
components overloading is identified, corresponding adjust-
ments should be made as shown in Fig. 4.
V. SIMULATION STUDIES
Two test systems are selected to verify the proposed tertiary
winding filter and its design procedure as well as to examine
its system performance.
A. Simulation Studies on Distribution System
This subsection conducts the simulation studies on test sys-
tem #1 a generic distribution system supplying residential
loads which are evenly distributed along five feeders mainly in
support of the effectiveness of the proposed tertiary winding
filter and its design procedure. Table II gives the main parame-
ters of test system #1. Fig. 5 depicts its network configuration,
in which each section block consists of three service trans-
formers which connects secondary systems serving 10 residen-
tial houses.
5
Primary System
S72
A B C N
Line
S1
Rg
Feeder 1
S72S1
Feeder 5
Section
Transmission System
Substation Transformer
#1 #2
#3
SAV
SBV
SCV
up
Z
Fig. 5 Network configuration of test system #1.
TABLE II: MAIN PARAMETERS OF TEST SYSTEM #1
System Parameters Values
Transmission
System
Voltage level (LL-rms) 144 kV
Equivalent impedance Z+/-=10.18+j32.95 Ω
Z0=2.42+j33.63 Ω
Substation
Transformer
Rated Capacity 20MVA/20MVA/10MVA
Rated Voltage (LL-rms) 144kV/25kV/6.3kV
Connection Type Yg/yg/delta
Short Circuit Impedance
H-M 10.5%
H-L 18%
M-L 6.5%
On-Load Loss 106.3kW
Main Trunk
Number of Feeders 5
Power Line Type Overhead line
# of Sections per Feeder 72
Length of Each Section 0.12km
Grounding Span 100m
Grounding Resistance (Rg) 15 Ω
1) Tertiary Winding Filter Design Results
The introduced iterative process (Fig. 4) was employed to
determine the final filter design. Table III presents the compo-
nent size of the designed tertiary winding filter.
TABLE III: DESIGNED COMPONENTS SIZE OF THE TERTIARY WINDING FILTER
Component Parameters Values
Delta connection part
L1 None
C1 160.43kvar (0.6 kV)a
L2 0.235mH(794A)b
C2 90.24kvar (0.6kV)
Star connection part
L3 0.490mH(794A)
C3 1033.35kvar(4.16kV)
L4 1.702mH(794A)
C4 637.08kvar (4.16kV) a The voltage in the bracket is the capacitor rated voltage. b The current in the bracket is the inductor rated current, the inductor rated
voltage is 6.3kV.
2) Simulation Results
All the developed models are employed in a multiphase
harmonic power flow program [4] to perform the simulation
studies. As the residential loads are time-varying during a day,
time-varying simulation results are obtained.
In order to establish a sound understanding of the proposed
tertiary winding filter performance, the simulation results for
both the case without tertiary winding filter and the case with
tertiary winding filter are shown in Fig. 6 to Fig. 9.
As seen from Fig. 6 to Fig. 9, both the harmonic currents
propagating into the transmission system and the harmonic
voltages at the primary side of the substation transformer have
been greatly reduced when the tertiary winding filter is in-
stalled, which demonstrates the effectiveness of the tertiary
winding filter.
1 3 5 7 9 11 13 15 17 19 21 230
2
4
6
8
10
Time (h)
%
TDD -- Without Tertiary Winding Filter
Phase A
Phase B
Phase C
1 3 5 7 9 11 13 15 17 19 21 230
2
4
6
8
10
Time (h)
%
TDD -- With Tertiary Winding Filter
Phase A
Phase B
Phase C
(a) (b)
Fig. 6 TDD variation of currents propagating into transmission system.
1 3 5 7 9 11 13 150
1
2
3
4
5
Harmonic Order
%
IDD Spectrum -- Without Tertiary Winding Filter
Positive sequence
Negative sequence
Zero sequence
1 3 5 7 9 11 13 150
1
2
3
4
5
Harmonic Order
%
IDD Spectrum -- With Tertiary Winding Filter
Positive sequence
Negative sequence
Zero sequence
(a) (b)
Fig. 7 Typical IDD spectra of currents propagating into transmission system.
1 3 5 7 9 11 13 15 17 19 21 230
1
2
3
4
5
Time (h)
%
THD -- Without Tertiary Winding Filter
Phase A
Phase B
Phase C
1 3 5 7 9 11 13 15 17 19 21 230
1
2
3
4
5
Time (h)
%
THD -- With Tertiary Winding Filter
Phase A
Phase B
Phase C
(a) (b) Fig. 8 THD variation of voltages at primary side of substation transformer.
1 3 5 7 9 11 13 150
0.5
1
1.5
2
2.5
Harmonic Order
%
IHD Spectrum -- Without Tertiary Winding Filter
Positive sequence
Negative sequence
Zero sequence
1 3 5 7 9 11 13 150
0.5
1
1.5
2
2.5
Harmonic Order
%
IHD Spectrum -- With Tertiary Winding Filter
Positive sequence
Negative sequence
Zero sequence
(a) (b) Fig. 9 Typical IHD spectra of voltages at primary side of substation trans-
former.
B. Simulation Studies on Transmission System
This subsection conducts several simulation studies on test
system #2 (see Fig. 10) an extension of the IEEE 14 bus
transmission system proposed in [26] aiming to further exam-
ine:
Will the distribution harmonic loads at other bus lead to the
tertiary winding filter overloading?
Is it essential to equip all the buses with distribution har-
monic loads with the tertiary winding filter?
6
G
1
2
3
5
6
12
13
11 10
14
9
47
8
SVC
Converter
G
G
Fig. 10 Network configuration of test system #2.
The major difference of test system #2 from IEEE 14 bus
transmission system includes:
All components in the system are modeled in phase domain.
The loads at Bus 4, Bus 5, Bus 9, Bus 10, Bus 11, Bus 12,
Bus 13 and Bus 14 are selected to be modified as distribu-
tion system loads as test system #1. To reduce the complex-
ity, the aggregated distribution system load model (see Fig.
11) is adopted. It should be noted that the total fundamental
frequency loads at Bus 4, Bus 5, Bus 9, Bus 10, Bus 11,
Bus 12, Bus 13 and Bus 14 keep the same with that in the
IEEE 14 bus transmission system, while their harmonic
characteristic parameters which include the harmonic cur-
rent spectrum of each phase and harmonic impedance ma-
trix are derived from test system #1 at peak load instant.
To simplify the analysis, the harmonic currents injected by
HVDC and SVC are neglected.
Substation Transformer MV Bus
#1 #2
C
B
#3
A
HV BusA AP jQ
B BP jQ
C CP jQC
B
A
(a) Fundamental frequency model
#1 #2
C
B
#3
A
C
B
A
3 3{ }Z h
( )AI h ( )BI h ( )CI h
Substation Transformer
MV BusHV Bus
(b) Harmonic frequency model
Fig. 11 Aggregated distribution system load model.
1) Influence of Distribution Harmonic Loads at Other Bus-
es
In the previous sections, the tertiary winding filter was
thoroughly examined in the distribution system. However in
the tertiary winding filter design, loading assessment was con-
ducted without considering the influence of distribution har-
monic loads at other buses. Will this be an issue for the tertiary
winding filter if there are multiple distribution harmonic loads
at other buses in the transmission system? To answer this ques-
tion, eight sets of cases are studied. Each set of cases consists
of two cases: i) there is no distribution harmonic loads at other
buses except where the tertiary winding filter is installed; ii) all
the load buses (Bus 4, Bus 5, Bus 9, Bus 10, Bus 11, Bus 12,
Bus 13, Bus 14) are modified as distribution harmonic loads.
The detailed description of these case sets and overloaded
components for different cases are given in Table IV.
Loading assessment for all eight case sets show that the dis-
tribution harmonic loads at other buses do have influence on
the loading level of the tertiary winding filter. But the influ-
ence is different for the tertiary winding filter at different loca-
tions. According to Table IV, indicated by Case Set 4, 5 and 6,
the tertiary winding filter designed based on the distribution
harmonic load information at its own bus will be overloaded
by distribution harmonic loads at other buses. Thus if multiple
distribution harmonic loads exist, the transmission system
harmonic power flow should be incorporated into the tertiary
winding filter loading assessment and components of larger
size should be adopted when overloading issues are identified.
TABLE IV: LOADING ASSESSMENT RESULT
Case
Set Case
Filter
Placement
Distribution Harmonic
Loads Location
Overloaded
Components
1 i Bus 4 Bus 4 None
ii Bus 4 All load buses None
2 i Bus 5 Bus 5 None
ii Bus 5 All load buses None
3 i Bus 9 Bus 9 None
ii Bus 9 All load buses None
4 i Bus 10 Bus 10 None
ii Bus 10 All load buses C4
5 i Bus 11 Bus 11 None
ii Bus 11 All load buses C4
6 i Bus 12 Bus 12 None
ii Bus 12 All load buses C4
7 i Bus 13 Bus 13 None
ii Bus 13 All load buses None
8 i Bus 14 Bus 14 None
ii Bus 14 All load buses None
2) Installation Density Study
This subsection presents the sensitivity study to assess the
influence of the installation density of the tertiary winding fil-
ter on the overall transmission system harmonic distortion lev-
el. Simulation results for the following case sets are compared
in Fig. 12.
i. Test system # 2 with the loads at bus 4, bus 5, bus 9, bus
10, bus 11, bus 12, bus 13 and bus 14 all modified as a
distribution harmonic load.
ii~ix, based on i, install one tertiary winding filter at any
one, any two,…, all of the buses with distribution harmon-
ic loads.
In Fig. 12, the average voltage THD is the voltage THD av-
erage over all buses under each cases for each case set and the
average current TDD is the current TDD average over all
transmission lines and transmission transformers under each
cases for each case set, while minimum voltage THD is the
minimum voltage THD average over all buses for each case set
7
and minimum current TDD is the minimum current TDD aver-
age over all transmission lines and transmission transformers
for each case set. As shown in Fig. 12, the more the tertiary
winding filter installed the lower the overall transmission sys-
tem harmonic distortion level is in terms of both the bus volt-
age THD and transmission equipment TDD.
Fig. 12 Average minimum harmonic distortion level for different cases.
Table V further gives the filter placement which results the
minimum harmonic distortion level for Case Set ii ~ viii and
the corresponding overall system voltage distortion level and
current distortion level with such placement.
TABLE V: OPTIMUM FILTER PLACEMENT FOR DIFFERENT CASES
Case Optimum Filter
Placement
Overall System
Harmonic Distortion
Voltage
THD* (%)
Current
TDD* (%)
ii Bus 9 6.70(8.63) 12.14(13.92)
iii Bus 9, Bus 14 5.61(8.07) 10.49(13.50)
iv Bus 9, Bus 10, Bus 14 4.92(7.48) 10.09(12.98)
v Bus 9, Bus 10, Bus 14,
Bus 4 3.86(6.70) 8.83(12.30)
vi Bus 9, Bus 10, Bus 14,
Bus 4, Bus 5 2.93(5.65) 8.37(11.39)
vii Bus 9, Bus 10, Bus 14,
Bus 4, Bus 5, Bus 13 2.25(4.41) 8.31(10.26)
viii Bus 9, Bus 10, Bus 14, Bus
4, Bus 5, Bus 13, Bus 12 2.01(3.15) 7.87(8.88)
*Figure in the bracket is the average value for each case set.
As indicated by Fig.12 and Table V, with optimum filter
placement, better harmonic mitigation effects can be achieved.
Another useful information could be extracted from Table V is
the distribution harmonic load at Bus 9 has the largest impacts
on the overall system distortion level since for all the optimum
filter placement one tertiary winding filter should be placed at
Bus 9.
VI. COMPARATIVE ECONOMIC ANALYSIS
The cost of the proposed tertiary winding filter has been in-
vestigated using test system #1. It is also compared with the
cost of the MV LC filter package.
To obtain a meaningful comparison, the MV LC filter
package is designed to achieve the same harmonic distortion
reduction with the tertiary winding filter specified by Table III.
The designed MV LC filter package shown as Fig. 13 consists
of two inductor grounded single tuned LC filters which are
tuned to filter the 3rd
, 5th
and 9th
and 11th
harmonics respec-
tively and one directly grounded single tuned LC filter which
is tuned to filter the 7th
harmonic. The designed components
size of the MV LC filter package is given in Table VI.
A B C A B CA B C
h=3, 5 h=9, 11h=7
L L L
C C
L L L
C C C C C C C
L L L
0L0L
Fig. 13 MV LC filter package.
TABLE VI: DESIGNED COMPONENT SIZE OF MV LC FILTER PACKAGE
Filter
Design
Tuned Harmonic
Order Component Size
Filter 1 3, 5
L 56.141mH (208A)
C 1875.28kvar (31.5kV)
L0 33.269mH (416A)
Filter 2 7 L 28.071mH (69A)
C 488.77kvar (15.92kV)
Filter 3 9, 11
L 11.228mH (69A)
C 494.84kvar (15.92kV)
L0 1.848mH (69A) a The voltage in the bracket is the capacitor rated voltage. b The current in the bracket is the inductor rated current, the inductor rated
voltage is 14.4kV.
For the cost estimation, the data collected from [27] and the
Internet are used. Table VII shows the approximate expenses
for filter components.
TABLE VII: ESTIMATED COST OF COMPONENTS
Capacitor
Rated
Voltage <1kV 1kV~10kV 10kV~25kV 25kV~50kV
Cost $15/kvar $20/kvar $40/kvar $65/kvar
Inductor Voltage Level
1kV~10kV 10kV~25kV
Rated
Current
<100A $1400 $2800
100A~500A $1700 $3400
500A~1000A $1900 $3800
Other Components 1kV~10kV 10kV~25kV
Switching Device $17,000 $34,000
Protection Device $3,500 $7,000
By the mentioned information, the overall cost of the ter-
tiary winding filter and MV LC filter package is estimated as
presented in Table VIII. As seen from Table VIII, the tertiary
winding filter is found to be much more economical.
TABLE VIII: OVERALL ESTIMATED COST
Tertiary Winding Filter MV LC Filter Package
Total Cost $149,110 $557,910
VII. APPLICATION CONSIDERATIONS
Most substation transformers are custom made and have
tertiary windings. It is relatively easy to make the six terminals
of the tertiary windings available for the proposed application.
Therefore, utility companies could order such a transformer
for new substations. The tertiary winding filter can then be
implemented by connecting corresponding LC components.
The same applies to the existing substations where six termi-
nals of the tertiary windings are accessible.
8
For existing substations where only three terminals of the
tertiary windings are accessible, the delta connection cannot be
achieved. As a result, ZS filtering is not doable. But the NZS
filtering can still be achieved by connecting shunt LC filters to
the tertiary windings. This configuration is similar to what is
proposed in [28]. Since the tertiary winding has lower rated
voltages than the secondary winding, this scheme is still cost
less than the traditional MV passive filter connected to the
secondary bus.
VIII. CONCLUSIONS
This paper presents a novel and effective scheme to prevent
harmonic currents from propagating into the transmission sys-
tems. The basic idea is to utilize the tertiary winding of a sub-
station transformer to create a tuned low impedance path for
the harmonics. The design issues of the proposed filters are
investigated and solved. The main findings and contributions
of this paper could be summarized as follows.
The proposed tertiary winding filter could trap two ZS har-
monics and three NZS harmonics simultaneously. It be-
comes a desirable method to mitigate multiple harmonic
currents.
The filter and its design method have been tested through
two comprehensive test systems. The results have demon-
strated the effectiveness of the filter and also revealed prop-
er placement could achieve the same reduction of the over-
all system harmonic distortion level with fewer filters.
Compared to other applicable schemes, the main benefit of
the proposed tertiary winding filter is its utilization of an
existing substation transformer to construct a low imped-
ance path. As a result, economic analysis showed it as a
cost effective solution to the problem.
IX. REFERENCES
[1] A. Mansoor, W. M. Grady, P. T. Staats, R. S. Thallam, M. T. Doyle, and
M. J. Samotyj, "Predicting the net harmonic currents produced by large
numbers of distributed single-phase computer loads," IEEE Trans.
Power Del., vol. 10, no. 1, pp. 2001-2006, Oct. 1995.
[2] CEATI Technical Report, “Power quality impact from mass penetration
of energy efficient and consumer electronic devices”, Project T084700-
5146 A&B, CEATI International Inc., Sept. 2011.
[3] S. Bhattacharyya, S. Cobben, P. Ribeiro, and W. Kling, “Harmonic
emission limits and responsibilities at a point of connection,” IET Gen.
Transmiss. Distrib., vol. 6, no. 3, pp. 256–264, Mar. 2012.
[4] D. Salles, J. Chen, W. Xu, W. Freitas, and H. E. Mazin, "Assessing the
collective harmonic impact of modern residential loads - Part I&II,"
IEEE Trans. Power Del., vol. 27, no. 4, pp. 1937-1955, Oct. 2012.
[5] H. Sharma, M. Rylander, and D. Dorr, "Grid impacts due to increased
penetration of newer harmonic sources," in Proc. IEEE Rural Electric
Power Conference (REPC), 2013, pp. B5-1-B5-5.
[6] K. D. McBee and M. G. Simoes, "Evaluating the long-term impact of a
continuously increasing harmonic demand on feeder-level voltage dis-
tortion," IEEE Trans. Ind. Appl., vol. 50, no. 3, pp. 2142-2149,
May./Jun. 2014.
[7] M. T. Au, J. S. Navamany, "The impact of small and medium power
loads on distribution network efficiency and harmonic propagation," in
Proc. 19th Int. Conf. Elect. Dis., May. 21-24, 2007, pp. 1-4.
[8] CSA Standard C22.3 No.6-13: Principles and Practices of Electrical
Coordination between Pipelines and Electric Supply Lines, 2013, Note
2 of Page 10.
[9] G. Todeschini, D. R. Mueller, and G. Y. Morris, "Telephone interfer-
ence caused by harmonics in distribution systems: Analysis and simula-
tions," in Proc. IEEE Power Eng. Soc. Summer Meeting, 2013, pp. 1-5.
[10] J. Arrillaga, D. A. Bradley, P. S. Bodger, Power System Harmonics,
John Wiley & Sons Ltd, 1985.
[11] V. E. Wagner, J. C. Balda, D. C. Griffith, A. McEachern, T. M. Barnes,
D. P. Hartmann, et al., "Effects of harmonics on equipment," IEEE
Trans. Power Del., vol. 8, no.2, pp. 672-680, Apr. 1993.
[12] S. B. Gin, J. H. Sawada, and T. R. Treasure, "BC Hydro harmonic reso-
nance experience," in Proc. IEEE Power Eng. Soc. Summer Meeting,
2000, pp. 1088-1093.
[13] Bonneville Power Administration (2013, Nov.). Technical Requirements
for Interconnection to the BPA Transmission Grid. [Online]. Available:
http://www.bpa.gov/transmission/Doing%20Business/Interconnection/D
ocuments/tech_requirements_interconnection.pdf
[14] NGET plc (2014, Aug.). The Grid Code. [Online]. Available:
http://www2.nationalgrid.com/uk/industry-information/electricity-
codes/grid-code/the-grid-code/
[15] E. R. Detjen and K. R. Shah, "Grounding transformer applications and
associated protection schemes," IEEE Trans. Ind. Appl., vol. 28, no. 4,
pp. 788-796, Jul./Aug. 1992.
[16] W. Jewell, W. L. Miller, and T. Casey, "Filtering dispersed harmonic
sources on distribution," IEEE Trans. Power Del., vol. 15, no. 3, pp.
1045-1051, Jul. 2000.
[17] J. Hurng-Liahng, W. Jinn-Chang, W. Kuen-Der, C. Wen-Jung, and C.
Yi-Hsun, "Analysis of zig-zag transformer applying in the three-phase
four-wire distribution power system," IEEE Trans. Power Del., vol. 20,
no. 2, pp. 1168-1173, Apr. 2005.
[18] E. Larsen, "Filter for removing harmonic current from a neutral conduc-
tor," US Patent 5 914 540, Jun. 22, 1999.
[19] P. Bagheri and W. Xu, "A technique to mitigate zero-sequence harmon-
ics in power distribution systems," IEEE Trans. Power Del., vol. 29, no.
1, pp. 215-223, Feb. 2014.
[20] IEEE Guide for Application and Specification of Harmonic Filters,
IEEE Standard 1531-2003, 2003.
[21] J. C. Das, "Passive filters - potentialities and limitations," IEEE Trans.
Ind. Appl., vol. 40, no.1, pp. 232-241, Jan./ Feb. 2004.
[22] A. B. Nassif, W. Xu, and W. Freitas, "An Investigation on the selection
of filter topologies for passive filter applications," IEEE Trans. Power
Del., vol. 24, no.3, pp. 1710-1718, Jul. 2009.
[23] IEEE Standard Terminology for Power and Distribution Transformers,
IEEE Std C57.12.80-2010, 2010.
[24] IEEE Application Guide for AC High-Voltage Circuit Breakers Rated
on a Symmetrical Current Basis, ANSI/IEEE C37.010-1979, pp. 1-54,
1979.
[25] G. C. Montanari and D. Fabiani, "The effect of nonsinusoidal voltage on
intrinsic aging of cable and capacitor insulating materials," IEEE Trans.
Dielectr. Electr. Insul., vol. 6, no. 6, pp. 798-802, Dec. 1999.
[26] R. Abu-Hashim, R. Burch, G. Chang, M. Grady, E. Gunther, M. Halpin,
et al., "Test systems for harmonics modeling and simulation," IEEE
Trans. Power Del., vol. 14, no.2, pp. 579-587, Arp. 1999.
[27] P. Bagheri, "Methods to mitigate harmonics in residential power distri-
bution systems," M. Sc. dissertation, Dept. Elect. Comput. Eng., Univ.
Alberta, Edmonton, AB, Canada, 2013.
[28] L. Helle, J. Nieuwenuizen, and M. Lidholm, "Low-voltage harmonic fil-
ter for full-scale converter systems," US Patent 2010/0118568 A1, May
13, 2010.
Tianyu Ding (S'12) obtained the B.Sc. degree in electrical engineering from
Shandong University, Jinan, China, in 2010. Currently, he is pursuing his
Ph.D. degree in Electrical and Computer Engineering at the University of
Alberta, Edmonton, AB, Canada. His main research interest is power quality.
Wilsun Xu (M’90-SM’95-F’05) obtained the Ph.D. degree from the Universi-
ty of British Columbia, Vancouver, in 1989. Currently, he is a
NSERC/iCORE Industrial Research Chair Professor at the University of
Alberta. His current main research interests are power quality and power
disturbance analytics.