A fault annunciator of theMSM-Product family

BSM Basic fault annunciator for panel mounting

MSM-BSM-BA-UK-00017.0

7.20

06

Page 2: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

MSM-BSM-BA-UK-000

The basic fault annunciator

Page 2 of 23

Contents overview

1 Validity 32 General notes 3 2.1 Used symbols 4 2.2 Used definitions 4 2.3 Safety instructions 5 2.4 Correct and proper usage 5 2.5 Device description 5 2.5.1 Construction of the BSM-annunciator 5 2.5.2 Signal processing 7 2.5.2.1 Reporting procedures 8 2.5.2.2 Collective report 8 2.5.2.3 Horn triggering 93 Assembly and installation 94 Configuration of BSM annunciator per DIP-switch 10 4.1 Standard variant without external relay modules 10 4.2 Standard variant with external relay modules 105 Parameterizing the BSM annunciator via PC 13 5.1 Device selection 14 5.2 Reporting sequence 14 5.3 Processing of the inputs 15 5.3.1 Signal inputs 15 5.3.2 Function inputs 17 5.3.3 Horn acknowledgement 17 5.4 Buttons and function inputs 17 5.5 Functional relays 18 5.6 Data transmission 19 5.7 Labelling strips 196 Monitoring lights and operating elements 197 Technical data 20

Page 3: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

MSM-BSM-BA-UK-000

The basic fault annunciator

Page 3 of 23

1 ValidityThe description applies to all device types of the BSM family:

• Standard type without CAN bus connection without software parameter setting • Standard type with CAN bus connection for relay modules without software

parameter setting• Software parameterizable type with CAN bus connection for relay modules in

connection with the Parameter setting software version 1.0.2

The BSM 08 is deliverable in many designs. All available configurations are listed in the sepa-rate document „equipment configurations of the BSM“.

The major characteristics of the device are encoded as follows in the ordering name:

Syntax: BSM XX-VM-SFX-AA

2 General notes

BSM XX Device type (e.g. BSM 08 or BSM 16) V Supply voltage (the meaning of the keys can be found in the technical data) M Signal voltage S Interfaces

X – no interfaces C – CAN bus for relay modules P – CAN bus and service / parameterising interface

F LED colour (applies to the whole module) R – red G – green Y – yellow W – white B – blue S / M - mixed configuration

X Dummy character AA Configuration variant (00 ... ZZ)

This operator‘s manual describes the function and handling of the basic-fault annunciator BSM and requires general knowledge about alarm sequences.For secondary information we refer to the following EES documentations

SM-MA-ZI-UK - Description of the reporting procedures of EES-fault annunciators MSM-RM-DB-UK - Description of MSM-relay modules

The operator‘s manual applies to several device types. It is possible that single device features are described which don‘t apply to your device.

The contents of the documentation were examined in agreement with the described hard and software. Deviations nevertheless cannot be excluded so that we don‘t take on any liability for the complete correctness.

Page 4: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

MSM-BSM-BA-UK-000

The basic fault annunciator

Page 4 of 23

Safety instructionThis symbol marks warnings, prohibitions and directions relating to hazards. It is essential that they are observed and obeyed.

The following symbols are used in this document:

Additional noteThis symbol indicates additional information.Important sectionThis symbol indicates particularly important information.

Cross-referenceThis symbol refers to diagrams and to other locations within the document.

2.1 Used symbols

New value reporting with 1 frequency flashlight.In case of new value reporting all messages are treated equal. If a signal lines up with a period which is longer than the response delay, the accompanying LED flashes. Horn and collective report are triggered, the message stored. All incoming messages are indicated with flashing light. Already gone, but not yet acknowledged messages are indicated by flashing light up to the acknowledgment. Now pressing the buttons for horn and acknowledgement, the horn relay falls off and the flashing light changes into steady light provided that the message still lines up. If the message is not present any more, the LED goes out.

New value reporting with 2 frequency flashlight.A message can be indicated in a slow and fast flashing light. When a signal lines up with a period which is longer than the response delay the accompanying LED flashes fast. Horn and collective report are triggered and the message stored. All incoming messages are indicated with a fast flashing light. Messages already cleared but not yet acknowledged, are indicated by fast flashing light up to the acknowledgment. If the acknowledgement buttons for horn and fast flashing light are pressed now as long as the message still lines up, the horn relay falls off and the flashing light indication changes into steady light. If the message is removed and therefore no longer present, the LED goes out automatically. If the message is no longer present when pressing the acknow-ledgement buttons for horn and fast flashing, the corresponding LED begins to flash slowly. In this case the LED goes out only by pressing the acknowledgement button for slow flashing.

First value reportingUnlike the new value reporting only the message arriving at first is indicated by first value repor-ting as a current message. All further messages which arrive up to the acknowledgment of every message are indicated as present and already acknowledged. Only after all messages have gone and acknowledges and therefore the collective report doesn‘t line up any more either, a message can be allocated and reported as first value again. The first value reporting can be combined with 1 or 2 frequency flashing light.

Response delay time:Is the time period with which a signal must be lined up to be allocated by the fault annuciator as one. Signals with a shorter duration are ignored.

2.2 Used definitions

Page 5: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

MSM-BSM-BA-UK-000

The basic fault annunciator

Page 5 of 23

These operating instructions must be carefully read, understood and followed!

Risk of interferencewith electronic devices! When operating the fault annunciator close to devices that are subject to interference, the special regulations for these areas must be observed!

Risk of ignition from electromagnetic fields!The BSM devices must not be operated in the neighbourhood of inflammable gases or liquids (fuel depots, petrol stations, chemical works, gas containers etc.)!

2.3 Safety instructions

The fault annunciator is intended exclusively for the applications described in these operating instructions. Any other usage can be hazardous and is forbidden. The manufacturer cannot be held liable for the consequences of improper use of the BSM devices or for any application that does not accord with the contents of these operating instructions.

2.4 Correct and proper usage

Risk of damage!The BSM devices must not be opened or subjected to improper modification!

2.5 Device description

2.5.1 Construction of the BSM-annunciator

The basic fault annunciator BSM for panel mounting is manufactured into 4 variants with 8, 16, 32 or 48 message inputs. The sealed front area contains 4 buttons and LED displays. The fault annunciator is built up into groups to 8 messages each. The essential functions of the fault annunciator are adjustable in the standard variant by DIP switches. Custom-designed alarm sequences can be realized factory set. The fault annunciator also can optionally be obtained with a connectivity for external relay modules and in a software parameterizable variant.

Page 6: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

MSM-BSM-BA-UK-000

The basic fault annunciator

Page 6 of 23

Depending on size, the fault annunciator includes the following functional components:

Reporting inputs The fault annunciator features reporting inputs that can be configuredfor different voltages and can be pre-processed. All 8 inputs of a reporting group can be configured together via DIPswitches for normally open or normally closed contacts.

Reporting groups 8 reporting inputs are consolidated to form a reporting group featuring 8 LED displays and a common label pocket.

LED colours red, green, yellow, white or blue (mixed configuration available on request)

Buttons The function of the four buttons that are integrated in the front panel depends on the implemented reporting procedure (e.g. message acknowledgement, delete, lamp test etc.)

Function inputs The two function inputs of the fault annunciator are used according to the selected reporting procedure, e.g. external acknowledgement.

Relay outputs 1 x live contact3 x message-specific function (e.g. collective report 1, collective report 2, horn etc.)

Collective report The function of the collective report depends on the reporting procedure and is specified in the type data sheet.

Name Equipment Dimensions H x W x D [mm]BSM08 8 reporting inputs

4 buttons 2 function inputs4 relay outputs

96 x 96 x 100

BSM16 16 reporting inputs 4 buttons2 function inputs4 relay outputs

96 x 96 x 100

BSM32 32 reporting inputs 4 buttons 2 function inputs4 relay outputs

96 x 192 x100

BSM48 48 reporting inputs 4 buttons 2 function inputs4 relay outputs

96 x 282 x100

Page 7: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

MSM-BSM-BA-UK-000

The basic fault annunciator

Page 7 of 23

DIP switches The following settings can be selected by DIP switches in the basic variant• Function of collective report (standard / inverted)• Horn control (subsequent alarm signal will trigger horn again / not again) • Reporting procedure 1 or 2 • Open circuit working or closed circuit working in common for all 8 inputs of a reporting group

Relay modules Maximal 6 external relay modules installed on a DIN rail can be connected to the optional interface CAN bus. These modules enable incoming messages to be relayed in parallel with inputs or outputs (PCS contacts). More detailed information may be found in the data sheet MSMRM.

Self-monitoring The fault annunciator features integrated self-monitoring signalling fault-free function via LED and relay contact.

Software-parameterising

The fault annunciators can optionally be ordered in a version parameterisable with a PC program based on Windows. Transferring theparameters to PC is done via connection between RS-232 COM-port and service- and parameterisation interface of the BSM. Following parameters can be adjusted:• Reporting sequence with single- or double frequency flashing light• Horn priority acknowledgement• Collective report statically or dynamically• Assignment of external lamp test input on available relay output• Inputs configurable for operating- or closed-circuit current per each• Response delay adjustable per input between 5 ms und 60 s• Free assignment of the inputs to the two collective reports• Automatic horn acknowledgement adjustable (horn duration time 1 ... 250 s)

2.5.2 Signal processingThe functional specification of a fault annunciator includes signal processing, which is structured in three groups:

• Reporting procedure• Formation of collective reports

• Horn control

Page 8: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

MSM-BSM-BA-UK-000

The basic fault annunciator

Page 8 of 23

2.5.2.1 Reporting procedures

One of the two reporting procedures deposited in the BSM can be selected by DIP switch. In the following the most required reporting procedures are listed.

• new-value reporting with single flashing light and single acknowledgement• first-value reporting with single flashing light and single acknowledgement

Which of the reporting procedures in the special fault annunciator is available, depends on therespective variant of the BSM. Many more sequences are applicable by using the software parameterizable version.

For detailed information please request our separate description of the reporting procedures.

2.5.2.2 Collective report

The different fault reporting procedures use different options for forming collective reports. Inprinciple, the following variants may be used:

Name Procedurestatic / input parallel The collective report is set with the first incoming

message and sent with the last outgoing message.static / output parallel The collective report is set with the first incoming

message. Once all messages have been sent and acknowledged the collective report is deleted.

static / dynamic / input parallel

The collective report is set with the first incoming message. For each further report, the collective report is cancelled for approx. 0.8 s and then set again. Once all messages have been sent, the collective report is deleted permanently.

static / dynamic / output parallel

The collective report is set with the first incoming message. For each further message, the collective report is cancelled for approx. 0.8 s and then set again. Once all messages have been sent and acknowledged, the collective report is deleted permanently.

dynamic The collective report is activated for approx. 0.8 s with each incoming message.

Page 9: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

MSM-BSM-BA-UK-000

The basic fault annunciator

Page 9 of 23

2.5.2.3 Horn triggering

Function Name MeaningHorn excitation(can be set via DIP switch)

retriggerable The horn is retriggered by new incoming messages, even if messages are already present.

not retriggerable The horn is retriggered for new incoming messages only if no messages are already present.

Horn acknowledgement

manual (continuous tone) The horn is acknowledged manually via a key or function input.

automatic (pulse tone) The horn is acknowledged automatically according to the set time.

manual with acknowledge-ment

The horn is acknowledged together with the lamp acknowledgement via the acknowledgement button. There is no special horn acknowledgement.

3 Assembly and installation

1. Unpack all the fault annunciator’s devices, and check them for transport damage. Report any transport damage immediately to the responsible carrier.

Please check that the delivery is complete. It can consist of the fault annunciator and perhaps further accessories (e.g. relay modules and system cable).

2. Configuration of the fault annunciator ( ► see section: Configuration of BSM annunciator per DIP-switch )

3. Slide fault annunciator in prepared panel hole and fasten with the clamps on top and bottom of the annunciator.

4. Attach in and output cables

Length of the in and output cables should not exceed 3 m.

Page 10: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

MSM-BSM-BA-UK-000

The basic fault annunciator

Page 10 of 23

4.1 Standard variant without external relay modules

4 Configuration of BSM annunciator per DIP-switch

5. Configure relay modules if necessary, mount onto DIN rail and connect with the fault annunciator over the enclosed system cable.

6. Attach supply voltage

The length of the supply lines should be max. 10 m.

7. Switch on power supply

8. Parameterize now fault annunciator parameterization variant. ( see section „Parameterizing the BSM annunciator via PC“).

Watchdog light [1] shines. The fault annunciator is operational.

At delivery the fault annunciator is pre-parameterized and therefore in most cases easy to adjust with the attached DIP-switches on the backside for the respective application. The meaning of the DIP-switches for the respective variant can be taken out of device configuration sheet (document MSM-BSM-GK-UK).

The following settings can generally be chosen:

• Function of the collective report (s) (standard/inverted)• Horn triggering (subsequent message triggers horn again/not again) • Choice of the reporting sequence (1 or 2) • Processing of 8 inputs to a common reporting group (Open or closed circuit working) common configuration of all 8 inputs of one input array

4.2 Standard variant with external relay modules

A maximum of 6 MSM relay modules can be attached to the fault annunciator in this variant. The relay modules are mounted on DIN rail and connected with the BSM over system cables. Relay modules make it possible to pass on lined up messages either input- or output parallel (for use of PCS-contacts).

1

Page 11: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

MSM-BSM-BA-UK-000

The basic fault annunciator

Page 11 of 23

DIP-switch

Meaning

1…3 Assignment of group 1 (relays 1…8) to the input array of the annunciator

4 Inversion of group 1 OFF – normal (relay outputs follows the annunciator according to the set up of the relay function) ON - Relay contacts get inverted

5 Relay control group 1OFF – input parallel

Relay output follows the assigned input on the annunciator.The relay is switched on, as long as the according alarm is active

ON – output parallelRelay output follows the according LED on the annunciator. Contact is connected, as long a message is active. (LED flashes or shines permanently).

Versions: The modules are delivered in the three following equipment configurations of relays:

• 16 normally closed contacts (NC)• 16 normally open contacts (NO)• 8 NC- / 8 NO-contacts

Assignment of relays By DIP switch the relays can be assigned in groups by 8 to the array of inputs of a fault annunciator.

Triggering of relays By DIP switch the triggering of every relay group whether in- or output parallel to the annunciator can be set up

Connenction to the fault annunciator

The connection between module and annunciator is made by preconfectioned cables with RJ45-plugs.

DIP-switches Every relay module has 10 DIP-switches, configuring• the assignment of relays to the input array of the annunciator• the triggering of relays in- or output parallel• the invertion of relay outputs

The configuration of the BSM is done as described in the section „standard design without external relay modules“. The following DIP switch settings are available at the relay modules:

DIP-Switch Inputs1 2 3OFF OFF OFF 1 … 8ON OFF OFF 9 … 16OFF ON OFF 17 … 24ON ON OFF 25 … 32OFF OFF ON 33 … 40ON OFF ON 41 … 48

Page 12: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

MSM-BSM-BA-UK-000

The basic fault annunciator

Page 12 of 23

6…8 Assignment of group 2 (relays 9…16) to the input array of the annunciator

9 Inversion of group 2OFF – normal (relay outputs follows the annunciator according to the set up of the relay function) ON - Relay contacts get inverted

10 Relay control group 2OFF – input parallel

Relay output follows the assigned input on the annunciator.The relay is switched on, as long as the according alarm is active

ON – output parallelRelay output follows the according LED on the annunciator. Contact is connected, as long a message is active. (LED flashes or shines permanently).

DIP-Switch Inputs6 7 8OFF OFF OFF 1 … 8ON OFF OFF 9 … 16OFF ON OFF 17 … 24ON ON OFF 25 … 32OFF OFF ON 33 … 40ON OFF ON 41 … 48

The state of relay contacts depend on: • the group assignment• the type of relay contacts (NO-/NC-contacts)• the inversion (normal or inverted)• the control of relays (in- or output parallel)

The state of the relay contacts is represented in the following table in dependence of the alarm inputs, the type of the relay contacts and the position of the DIP switch „inverted“

DIP-switch „inverted“(4 or 10)

Relay contact type

Relay contact if alarm present

Relay contact if alarm not present

Relay contact without supply voltage

OFF normally open closed open openOFF normally closed open closed closedON normally open open closed open

Further details of the relay modules can be taken from the data sheet of the relay modules (document name MSM-RM-DB-UK).

Page 13: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

MSM-BSM-BA-UK-000

The basic fault annunciator

Page 13 of 23

5 Parameterization of the fault annunciator per PCBy using the parameterizable variant the fault annunciator can be adjusted most flexible to arbi-trary applications. Therefore additional parameters are modificable as follows:

• Reporting procedures • Processing of inputs • Horn triggering• Assignment of buttons and functional inputs• Control of functional relays

The construction of the parameter file is done confortable by the enclosed PC-program based on Windows and is loaded in the fault annunciator via the connection cable available as accessory.In the following context the parameter setting possibilities of the program are described.

The window of the parameter setting program is divided in 7 functional sections :

1 Device selection2 Reporitng procedures3 Processing of the inputs4 Assignment of buttons and functional inputs

5 Functional relays6 Progress window of data communication to BSM7 Button-block

1

2

3

4

5

6

7

Page 14: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

MSM-BSM-BA-UK-000

The basic fault annunciator

Page 14 of 23

5.2 Reporting sequence

5.1 Device selection

After starting the program at first the respective fault annunciator has to be selected.

Two reporting procedures can be realised by the BSM with one assigned collective report per each. Every input will then be assigned to these reporting procedures and corresponding collective reports. For adjusting the reporting procedures flexibly to the respective requirement, they are build up by single components.

Description Selection possibilities Selection for function1/2 frequency reporting sequence

1-frequency 1-frequency-flashlight2-frequency 2-frequency-flashlight

reporting sequence First value/ New value upon selection

Setting according to position „First value / New value“

steadylight - steadylight (2-frequency)

New value message with 2-fre-quency-flashlight and double ack-nowledgement (flashlight-steady light-steady light)

Operating fault annunciator (only BSM 16)

State indication steady light

First value / New value

New value annunciator New value annunciatorFirst value annunciator First value annunciatorFirst value annunciator group parallel

For both reporting sequences there is only one common first value determined

According to DIP-switches acc. to DIP-switch-setting ( Section „Configuration of the fault annunciator)“

Page 15: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

MSM-BSM-BA-UK-000

The basic fault annunciator

Page 15 of 23

Collective report not inverted standardinverted invertedacc. to DIP-switch acc. to DIP-switch-setting

( Section „Configuration of the fault annunciator)“

Output static / output parallel Output of collective report ( Section „Collective report“)static / dynamically / input parallel

static / dynamically / output parallel dynamically

Example:• First-up message with 1-frequency flashlight and single acknowledgement• Horn retriggerable on follow-up message• The collective report is set by the first upcoming message. Only if all messages are gone

and are acknowledged, the collective report is deleted.

Settings:1/2 frequency reporting sequence - 1-frequencyReporting sequence - First-up / New value acc. to selectionFirst-up / New value - First-up annunciatorHorn triggering - retriggerableCollective report - not invertedOutput - statisch / ausgangsparallel

Detailed information of reporting sequences and signal processing can be taken from the seperate datasheet „SM-MA-ZI-UK“.

5.3 Input processing

Within the input processing the features and functions of the following components are defined.:

• Message inputs and the assignment to the reporting procedures• Functional inputs• Labelling for messages and buttons• Horn control

5.3.1 Message inputs

After the device selection the respective available inputs groups (i.e. for the BSM 16 e.g. 2 input groups) are released to edit. For every group (8 inputs per each) can be decided, if the DIP-switch-setting or the software parameter setting is authorative for message processing.

Page 16: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

MSM-BSM-BA-UK-000

The basic fault annunciator

Page 16 of 23

In the next part of the dialog the settings can be taken for every single message listed in the following table.

Description Selection possibilities Selection for functionsText for module labelling 20 characters Text to print labelling strips later onMeldungstyp Operating message State indication steady light

Fault message Fault message acc. to selected reporting procedure

Normally open / Normally closed

Normally open Applying a voltage triggers a message.

Normally closed Dropping off a voltage triggers a message.

Response delay 5 ms ... 60 s Time period of a message has to line up until being registered

Activates collective report Collective report 1 Reporting procedure and collective report 1

Collective report 2 Reporting procedure and collective report 2

Collective report 1 and 2

Collective report 1 and 2Within this selection, both reporting procedures should be identical, otherwise the message will be assigned to the reporting procedure with the highest priority. Message is not assigned to a collective report, however to the first reporting sequence

Horn is activated as Horn without locking

Horn can always be acknowledged

Horn with locking Horn acknowledgement is only pos-sible

No horn triggering

Message does not trigger horn.

Page 17: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

MSM-BSM-BA-UK-000

The basic fault annunciator

Page 17 of 23

With the buttons „copy dataset“ or „paste dataset“ the settings of a message input can be transfered to another input..

On the right next to the labelling texts for the messages the assignment of labelling texts for the buttons can be made. The text should not consist of more than 5 characters.

5.3.2 Functional inputs

In the lower part of the dialog the following specifications are to be set:

• Response delay (5 ms ... 60 s)• Normally open or normally closed

5.3.3 Horn acknowledgement

In the last part of this section the type of horn acknowledgement is to be set.

Manual acknowledgement (Continuous tone)Horn is acknowledged manually by button or functional input.

Automatic acknowledgement (Pulsed tone)Horn is acknowledged automatically according to the set time.

Horn priority acknowledgement A message can only be acknowledged, if the horn is acknowledged before.

The setting „horn priority acknowledgement“ contradicts to the setting „horn locking“, which can be single set for every input. For this case by choosing „horn priority acknowledgement“ the setting „horn lock“ of all message inputs is deactivated automatically

5.4 Buttons and functional inputs

In this part of the dialog the functions of the annunciator listed below are assigned to the buttons T1...T4 as well as to the functional inputs 1 and 2. Multiple assignments are possible.

Within the parameterization softwarethe assignment is done by a matrix.The lines correspond to the functions, the rows represent buttons or functional inputs. Realised links are check marked.

Page 18: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

MSM-BSM-BA-UK-000

The basic fault annunciator

Page 18 of 23

Function MeaningAcknowledgement Gr. 1 Acknowledgement of all messages of reporting sequence 1 Acknowledgement Gr. 2 Acknowledgement of all messages of reporting sequence 1Reset Group 1 Reset of all messages of reporting sequence 1

(e.g. in case of 2-frequency-flashlight)Reset Group 2 Reset of all messages of reporting sequence 2

(e.g. in case of 2-frequency-flashlight)Acknowledgement horn Acknowledgement hornLamp test Lamp testFunction test Simulation to exitate all inputsToggle relays Bistable relay, switching over with every exitation

(Flip-flop-function)Wipe relays Relay switches by every excitation and drops off again after

the wipe duration ( 4 ms ... 1 s).

Respectively only one of the two functions „toggle relays“ oder „wipe relays“ can be used alternatively. The selected relay function can again only be assigned to one button. Multiple assignments are here not possible!

5.5 Functional relays

The functional relays R1 ... R4 can be free assigned to the functions given in the following table.

Function MeaningCollective report 1 Collective report of the reporting sequence 1 Collective report 2 Collective report of the reporting sequence 2Horn Horn triggeringToggle / Wipe Toggling or wiping of the relay output (acc. to the setting in the

dialog „Buttons and functional inputs“) Alive Live-contact of self-monitoringButton 1 … 4 Button controls relay outputFunctional input 1 / 2 Functional input controls relays output

Within the parameterization software the assignment is done by a matrix. The lines correspond to the functions, the rows represent buttons or functional inputs. Realised links are check marked.

Page 19: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

MSM-BSM-BA-UK-000

The basic fault annunciator

Page 19 of 23

Multiple assignments, e.g. combiation of collective reports, are possible. The button line „relays inversion“ defines for every relay either the use of the switching function or its negated execution. For example then the relay drops off on appearance of the collective report.

5.6 Data transmission

With the two buttons „read data from BSM“ and „write data to BSM“ the parameterization can be read out from BSM or overwritten in the BSM device.

Please be aware to set-up the used COM-port and the baud rate ( factory set 9600 Baud) of your personal computer before data transmission.

State messages of the course of the data transmission are displayed in the data traffic window.

With the two buttons „save data record“ and „open data record“ the parameterization file can be saved for later use or loaded from a existing file.

5.7 Labelling strips

The texts for the description of the messages and buttons defined in the parameterization program can be printed automatically on labelling strips. This function has to be invoked by the button„print labels“. In the background a MS-Word form opens automatically, which can be printed.

For using the labelling print MS-Word has to be installed on your personal computer .

6 Monitoring lights and operating elements

1 Signalling lights 1 ... 8, Function is dependend from reporting procedure

2 Signalling lights 9 ... 16, Function is dependend from reporting procedure3 Buttons 1 ... 4

4 Watchdog „OK“ Goes out on trouble

The representation of the BSM 16 is given here only as an example to the clarification of the principle. The number of reporting groups or the LED colours of the signalling lights can differ depending on configuration and size of the fault annunciator.

2 1 3

4

Page 20: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

MSM-BSM-BA-UK-000

The basic fault annunciator

Page 20 of 23

Supply voltage

7 Technical data

Signal voltage

Key Rated voltage Voltage range Input resist-ance

0 12 V AC/DC 7 … 35 V AC/DC ~ 5 kΩ1 24 V AC/DC 16 … 50 V AC/DC ~ 10 kΩ

3 48 V AC/DC60 V AC/DC 28 … 75 V AC/DC ~ 22 kΩ

4 110 V AC/DC 55 … 130 V AC/DC ~ 70 kΩ5 220 V AC/DC 150 … 260 V AC/DC ~ 200 kΩ

Mechanical data

Type Front frame H x W x D [mm]

Front panel cut-out [mm]

Depth with front frame and terminals [mm]

BSM 08 96 x 96 x 100 91 x 91 +0.5 100BSM 16 96 x 96 x 100 91 x 91 +0.5 100BSM 32 96 x 192 x 100 92 x 187 +0.5 100BSM 48 96 x 287 x 100 92 x 282 +0.5 100

Key Rated voltage Voltage rangePower consumptionBSM 08 BSM 16 BSM 32 BSM 48

0 12 V AC/DC 10…19 V DC8…13 V AC < 2.5 W < 3 W < 4,5 W < 5.5 W

1 24 V AC/DC 19…37 V DC14…26 V AC < 2.5 W < 3 W < 4,5 W < 5.5 W

2 48 V AC/DC60 V DC

37V…73 V DC26…51 V AC < 3 W < 3,5 W < 5 W < 6.5 W

5 110 V AC/DC220 V AC/DC

100…370 V DC85…264 V AC < 3.5 W < 4 W < 5.5 W < 6.5 W

* versions with CAN bus connection + 0.5 W

General data

Buffer time in the event of failure / short circuit 100 msResponse delay pre-set in the factory 5 ms ... 50 s; standard 100 msFlashing frequency Single frequency 2 Hz Slow flashing: 0.5 HzLoad capacity of relay contacts 24 ... 250 V AC 2 A; 110 V DC 0.5 A; 220 V DC / 0.3 A

Page 21: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

MSM-BSM-BA-UK-000

The basic fault annunciator

Page 21 of 23

Mounting panel mountingrequired installation depth 120 mmminimal horizontal gap between2 devices 15 mmConnection terminals cross section 1.5 mm2

Ambient environment

Operating temperature -20°C .... +60°C without condensationStorage temperature -20°C .... +70°C without condensationDuty cycle 100 %Protection class at the front IP 54Protection class at the rear IP 20Humidity 75% r.H. max. on average over the year;

up to 93% r.H. during 56 days; condensation during operation not permitted [Test: 40°C, 93% r.H. >4days]

Power frequency electric strengthall circuits except:relay contacts against each other,CAN bus interface 4 kVeff / 50 Hz 1 min

surge voltage resistanceall circuits except:relay contacts against each other,CAN bus interface 2.5 kV; 1.2 / 50 µs; 0.5 J; according to IEC60255-5:2000Power frequency electric strengthrelay contacts against each other, CAN bus interface 500 Veff / 50 Hz 1 min

Electromagnetic compatibility Noise immunity acc. to EN 61000-4-2,3,4,5,6,12 Noise irradiation acc. to EN 61000-3-3, EN 55011

The devices are designed and manufactured for industrial applications according to EMC-standard.

Page 22: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

MSM-BSM-BA-UK-000

The basic fault annunciator

Page 22 of 23

Subject to changes without prior notice.

Page 23: A fault annunciator of the MSM-Product family THE … · THE SOLUTION OPERATING MANUAL INFO A fault annunciator of the MSM-Product family BSM Basic fault annunciator for panel mounting

TH

E S

OLU

TIO

NO

PE

RA

TIN

G M

AN

UA

L

Elektra Elektronik GmbH & Co Störcontroller KGHummelbühl 7-9 • 71522 Backnang/Germany Phone: +497191/182-0 • Telefax: +497191/182-200

HOTLINE+497191-182-235/214

INTERNETwww.ees-online.de

e-Mail: [email protected]

BSM Panel mounted fault annunciator

Terminal assignment

BSM 08 BSM 16

BSM 32

BSM 48