A Cyber Physical Approach to a Combined Hardware-Software

26
A Cyber Physical Approach to Combined HW-SW Monitoring for Improving Energy Efficiency in Data Centers Josué Pagán, Marina Zapater, Oscar Cubo, Patricia Arroba, Vicente Martín and José M. Moya Universidad Politécnica de Madrid 1 / 20

description

Presentation by Josué Pagán at DCIS 2013 conference, organized by CEIT (Nov 27th, 2013)

Transcript of A Cyber Physical Approach to a Combined Hardware-Software

Page 1: A Cyber Physical Approach to a Combined Hardware-Software

A Cyber Physical Approach to

Combined HW-SW Monitoring for

Improving Energy Efficiency in

Data Centers

Josué Pagán, Marina Zapater, Oscar Cubo, Patricia Arroba, Vicente Martín and José M. Moya

Universidad Politécnica de Madrid1 / 20

Page 2: A Cyber Physical Approach to a Combined Hardware-Software

Contents

1. Power consumption problem in Data Centers

I. Introduction

II. Related work

2. Optimization Framework & Data analysis

I. A Cyber-physical system

II. Data analysis and sensor configuration

3. Results

4. Conclusions

2

Page 3: A Cyber Physical Approach to a Combined Hardware-Software

1. POWER CONSUMPTION

PROBLEMS IN DATA CENTERS

Data Center. Consumption

3

Page 4: A Cyber Physical Approach to a Combined Hardware-Software

1. Power consumption

problems in Data Centers

• The numbers of the energy problem:– DC world power consumption >1.3%

– In urban areas >50% of DC exceeds power grid capacity

– USA: 80 TWh/year in 2011 = 1.5 x NY

4Projection of total electricity use by datacenters in the US and the world based on Koomey’s and EPA’s data

Power >600 TWhr expected in 2015 in the global footprint

Data Centers’ power consumption is unsustainable

Page 5: A Cyber Physical Approach to a Combined Hardware-Software

5

Cooling

• Allow the room temperature to increase

• Longer task → cooler server

Computation

• Balancing workload between servers

• Reducing voltage/ frequency (DVFS)

Holistic(IT+cooling)

• Room environment affects (environmental monitoring)

• Measuring server, workload and environmental variables to improve energy efficiency → usage of a CPS

1. Power consumption

problems in Data Centers

• Related work (approaches)

– These two approaches are not enough individually

Page 6: A Cyber Physical Approach to a Combined Hardware-Software

1. Consumption problems in

Data Centers

6

Requirements Our contributions

Energy optimization

Make a holistic optimization framework including environmental,

server and workload information

Dynamically adapt on runtime to workload and environment

Gather, monitor and analyze in real time

Gather useful data at the appropriate rate

In a non-intrusive way, reducing the data collected with an adaptable

sampling rate

Page 7: A Cyber Physical Approach to a Combined Hardware-Software

2. OPTIMIZATION FRAMEWORK

& DATA ANALYSIS

Cyber-Physical System. Data acquisition

7

Page 8: A Cyber Physical Approach to a Combined Hardware-Software

• One step ahead. Optimization– 80% Wpeak – 30% of workload (↓η)

– An energy model supposes apply optimizations over the Data Center

2. Optimization Framework &

Data analysis

8

GATHERDATA

GENERATEKNOWLEDGE

PROPOSEOPTIMIZATIONS

Page 9: A Cyber Physical Approach to a Combined Hardware-Software

• Monitoring– How a Data Center works?

– 30-50% cooling→ energy optimization 9

2. Optimization Framework &

Data analysis

Page 10: A Cyber Physical Approach to a Combined Hardware-Software

• What measure and why– Environmental monitoring

Inlet and outlet temperature

Differential pressure

10

2. Optimization Framework &

Data analysis

– Server monitoringServer consumption, CPU temperature, fan speed

• …to predict

Page 11: A Cyber Physical Approach to a Combined Hardware-Software

• How…

• exploring sampling intervals

2. Optimization Framework &

Data analysis

11

– Different sampling rates for different parameters

– Temperature and power values

for AMD server under the

benchmark SPEC CPU 2006

Page 12: A Cyber Physical Approach to a Combined Hardware-Software

• Using… Multilevel star topology architecture

12

Air conditioning- Exhaust

temperature, RH% and airflow

WSN- Reconfigurable low -power:

only useful data without information loss

- Adapt to changes in the environment

RM- Spatio-temporal allocation

- Possibly to change decisions if needed

Server Sensors- Internal sensors

- Polled via SW

Gateway-Fan-less, managed with a light OS

-Receive, store, analyze and convert data. Establishes a timestamp.

-Sends data to the opt. platform

2. Optimization Framework &

Data analysis

Page 13: A Cyber Physical Approach to a Combined Hardware-Software

3. RESULTS

13

Page 14: A Cyber Physical Approach to a Combined Hardware-Software

3. Results

14

WSN deployment• Applied over Magerit Supercomputer in CeSViMa Supercomputing and Visualization Center

of Madrid• Cluster 9 racks 260 servers

Page 15: A Cyber Physical Approach to a Combined Hardware-Software

3. Results

15

– The goal: develop techniques to allow energy optimization in real environments

– With reconfigurable sampling rate:

– we achieve up to 68 % of reduction in gathered data

– Increase the WSN’ s life time depending on the occupancy

Page 16: A Cyber Physical Approach to a Combined Hardware-Software

4. CONCLUSIONS

16

Page 17: A Cyber Physical Approach to a Combined Hardware-Software

4. Conclusions

17

Energy efficiency has to be faced in a holistic way

We propose an optimization framework monitoring environmental, server and workload parameters

After a first monitoring study: a WSN has been deployed to gather environmental data

Up to a 68% of reduction in the amount of gathered data

Maximizing the life time of WSN nodes

Solution applied in a real case study

Page 18: A Cyber Physical Approach to a Combined Hardware-Software

FIN

This project has been funded in part by the INNPACTO \ LPCLOUD: "Optimal Management Of low-power modes in cloud computing" IPT-2012-1041-430000, developed in collaboration with Elite Ermestel and Converging Technologies and the CDTI project \ CALEO:

Distribution of operational thermal and optimization of energy consumption in data centers, "developed in collaboration with INCOTEC. The author gratefully acknowledges the computer resources, technical expertise and assistance provided by the Supercomputing and

Visualization Center of Madrid (CeSViMa). 18

Thank you for your attention

Page 19: A Cyber Physical Approach to a Combined Hardware-Software

4. Results and Conclusions

19

• Results: gathering data• Inlet and outlet temperature

Page 20: A Cyber Physical Approach to a Combined Hardware-Software

Magerit Supercomputer

20

• Cluster 9 racks 260 servers 245 are IBM PS702 2S

o 16 Power7 processors @ 3.3 GHz

o 32 GB of RAM

15 are IBM HS22

o 8 Intel Xeon processors @ 2.5 GHz

o 96 GB of RAM

200 TB of storage

Page 21: A Cyber Physical Approach to a Combined Hardware-Software

21

Industry

Page 22: A Cyber Physical Approach to a Combined Hardware-Software

Software

22

• Pasarela

Page 23: A Cyber Physical Approach to a Combined Hardware-Software

Cyber-Physical System

23

Page 24: A Cyber Physical Approach to a Combined Hardware-Software

Psychrometric chart

24

Page 25: A Cyber Physical Approach to a Combined Hardware-Software

Differential pressure and

airflow

25

Page 26: A Cyber Physical Approach to a Combined Hardware-Software

Installing nodes [6T+1H]

26