AM-LON Part.-No. 349049 Communication module for ECblue fans Operating Instructions L-BAL-E166-GB 1204 Index 001 Part.-No. 00163375-GB english

Transcript of a bis e: Kapitelzähler ('titel') -...

AM-LON

Part.-No. 349049

Communication module for ECblue fans

Operating Instructions

L-BAL-E166-GB 1204 Index 001 Part.-No. 00163375-GB

english

Content

1 General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

1.1 Structure of the operating instructions . . . . . . . . . . . . . . . . . . . . 3

1.2 Exclusion of liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

3 General description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

3.1 Operational area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

3.2 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

3.3 Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

3.4 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

3.5 Disposal / recycling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

4 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

5 Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

5.1 Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

5.2 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

5.2.1 Connecting at the AM-LON Modul . . . . . . . . . . . . . . . . . . 6

5.2.2 Wiring and terminating resistor in the LON® network . . . . . 6

6 Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

6.1 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

6.2 Manufacturer reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

6.3 Service information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Operating Instructions AM-LON

L-BAL-E166-GB 1204 Index 001 Part.-No. 00163375-GB2/9

1 General notes

1.1 Structure of the operating instructionsThese operating instructions are valid only in connection with the device's operat-

ing instructions into which this module is being integrated. The remarks concern-

ing safety, installation and connection described in those operating instructions

must be followed!

Before installation and start-up, read this manual carefully to ensure correct use!

1.2 Exclusion of liabilityConcurrence between the contents of these operating instructions and the described

software has been examined.It is still possible that non-compliances exist; no guarantee

is assumed for complete conformity.To allow for future developments given are subject

to alteration.We do not accept any liability for possible errors or omissions in the

information contained in data, illustrations or drawings provided.

Ziehl-Abegg AG is not liable for damage due to misuse, incorrect or improper use.

2 Safety instructions• Mounting, electrical connection, and start-up operation may only be carried

out by an electrical specialist in accordance with electrotechnical regula-

tions (e.g. DIN EN 50110 or DIN EN 60204)!

• It is strictly forbidden for work to be carried out on any components while

they are connected to live voltage. The open equipment is protected to IP00.

It is possible to come into direct contact with dangerous voltages!

3 General description

3.1 Operational areaThe add-on module can only be used together with compatible Ziehl-Abegg devices.

3.2 FunctionECblue fans with integrated auxiliary module AM-LON offer the following func-

tions:

• The “AM-LON” module can be used to communicate with the controller of the fan.

• ECblue fans can be integrated into existing LON® networks.

• A LON® network of several ECblue fans can be built up. The communication

between the fans happens via LONWORKS® FT10.

• Networkk interface description R-TIL11_01-GB.

Operating Instructions AM-LON General notes

L-BAL-E166-GB 1204 Index 001 Part.-No. 00163375-GB3/9

3.3 Transport• The device is packed ex factory to suit the transport method previously agreed.

• Always use the original packaging materials when transporting the device.

• Avoid shocks and impacts to the device during the transport.

• During manual handling the human lifting and carrying restrictions must be

observed and adhered to.

3.4 Storage• The device must be stored in its original packaging in a dry and weather-proof

room.

• Avoid exposure to extreme heat and cold.

• Avoid over-long storage periods (we recommend a maximum of one year).

3.5 Disposal / recyclingDisposal must be carried out professionally and environmentally friendly in accordance

with the legal stipulations.

Operating Instructions AM-LON General description

L-BAL-E166-GB 1204 Index 001 Part.-No. 00163375-GB4/9

4 Mounting• Before installation remove the device from the packing and check for any possible

shipping damage!

• For installation the cover of the controller housing must be removed. The module

is then put into the intended slot of the ECblue fan. ( Assembly instructions /

Operating Instructions for fan / Electrical Installation).

• Install afterwards module with both enclosed screws in the controller housing

(permissible tightening torque MA = 1.3 Nm).

Danger due to electric currentVoltage supply for motor must be interrupted and secured against restoration!

Installing the add-on module

29.04.2009

v_modul_montage_ecblue.vsd

Operating Instructions AM-LON Mounting

L-BAL-E166-GB 1204 Index 001 Part.-No. 00163375-GB5/9

5 Electrical installation

5.1 Safety precautions

Danger due to electric current

• Work on electric components may only be carried out by trained electricians

or by persons instructed in electricity under the supervision of an electrician

in accordance with electrical engineering regulations.

• It is forbidden to carry out work on electrically live parts.

5.2 Communication

5.2.1 Connecting at the AM-LON ModulThe two-wire lead of the LON®-bus is connected to terminals “NET_A” and “NET_B”.

The correct choice of cable is essential for the proper operation of the network.

Recommended wire types

• 22AWG, twisted pair, typical solid an unshilded

• Remote control line JY (St) Y 2x2x0.6

• Wieland line system (gesis con)

The connection of the LON® bus is not polarity sensitive. When using cable with more

than two strands, ensure that two twisted strands only are used for the network line. The

parallel laying of several strands is not permitted!

InformationThe maximum line length for free wiring is 500 m and the maximum distance between

two devices is 400 m.

The maximum line length for wiring in bus topology is 1000 m.

( Wiring and terminating resistor in the LON® network)

5.2.2 Wiring and terminating resistor in the LON® network With bus wiring, a terminating resistor of 100 Ω / ≤ 0.25 W must be fitted to the beinning

and end of the line.

InformationThe stub lines to the individual devices should be kept as short as possible (max. 5 m).

If this is not possible, the terminating resistor must be connected after the free wiring.

Operating Instructions AM-LON Electrical installation

L-BAL-E166-GB 1204 Index 001 Part.-No. 00163375-GB6/9

Example 1: bus wiring

02.02.2012

v_busverdr_lon.VSD

100 ohm100 ohm

100 ohm = terminating resistor

If this type of wiring is not possible for routing reasons, then "free" wiring can be used as

an alternative. Please note the restrictions on line length.

InformationIf any matters are unclear, you can send for our technical information sheet "Network

structure of a LON®" - TIL00_70. It contains information about the topology, circuitry and

selection of types of cable.

With free wiring, i. e. no wiring rule is applied, a terminating resistor of 50 Ω / <0.25 W

must be fitted at a neutral point in the network or at one end of the line.

Example 2: Free wiring

02.02.2012

v_freie_verdraht_lon.VSD

100 ohm

100 ohm = terminating resistor

Operating Instructions AM-LON Electrical installation

L-BAL-E166-GB 1204 Index 001 Part.-No. 00163375-GB7/9

6 Enclosure

6.1 Connection diagram

AM-LON

ID1V- ID2

MOLN07K0

15.03.2011

LON® Service Pin

max. 5 VDC

V-

LON® Service Pin

max. 5 VDC

BA BA

Operating Instructions AM-LON Enclosure

L-BAL-E166-GB 1204 Index 001 Part.-No. 00163375-GB8/9

6.2 Manufacturer referenceOur products are manufactured in accordance with the relevant international regulations.

If you have any questions concerning the use of our products or plan special uses,

please contact:

Ziehl-Abegg AG

Heinz-Ziehl-Straße

74653 Künzelsau

Telephone: +49 (0) 7940 16-0

Telefax: +49 (0) 7940 16-504

[email protected]

http://www.ziehl-abegg.de

6.3 Service informationIf you have any technical questions while commissioning or regarding malfunctions,

please contact our V-STE support department for control systems - ventilation technol-

ogy.

Our worldwide contacts are available in our subsidiaries for deliveries outside of Ger-

many. www.ziehl-abegg.com.

If you make returns for inspections or repairs we need certain information in order to

facilitate focused trouble shooting and fast repair. Please use our repair tickets for this. It

is provided to you after you have consulted our support department.

In addition, you can download it from our homepage. Download - Ventilation Technology

- Topic: Control Engineering - Document type: General documents.

Operating Instructions AM-LON Enclosure

L-BAL-E166-GB 1204 Index 001 Part.-No. 00163375-GB9/9