Contents

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Optional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Microprocessor Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Performance Specifications—Air Cooled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Performance Specifications—Water Cooled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Performance Specifications—Glycol Cooled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Air-Cooled Condensers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Fluid Coolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Pump Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

Guidelines for Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

AFX Capacity(kW) Configuration Voltage Air Pattern

AFX 020 A= Air Cooled BA= 208-230/3/60 D= Downflow

027 W= Water Cooled KA= 480/3/60 U= Upflow (front return)

034 G=Glycol Cooled MA= 600/3/60 R= Upflow (rear return)

041

048

062

070

090

098

AFX XXX X XX X

APC NetworkAIR™ AFX i

ii APC NetworkAIR™ AFX

Overview

The APC NetworkAIR AFX com-puter room air conditioning system provides a quiet, efficient, and reli-able solution for heat sensitive equipment areas. The NetworkAIR AFX is offered in a wide variety of capacities, configurations, and air patterns within a compact cabinet size.Precision environmental require-ments now reach far beyond the confines of the traditional data cen-ter or computer room to encompass a larger suite of applications, referred to as technology rooms. Critical environment applications include:

• Computer rooms• Telecommunication facilities• Clean rooms• Power equipment• Medical equipment rooms• Archives• LAN/WAN environments

A worldwide network of APC rep-resentatives is fully qualified to provide engineering, sales, installa-tion and service for our products. APC warrants all parts for 12 months from shipment. Extended warranties are available.

CapacityAFX is available from 20-98 kW (6-28 tons).

Room Air DistributionDownflow systems discharge air into the raised floor plenum. These systems are suitable for areas with raised floors greater than 12" (305 mm) high. Return air is drawn in through the top of the system. Upflow systems discharge air into either a plenum or ductwork. These systems are suitable for areas with-out raised floors, as well as areas with raised floors. Air is drawn in through the front on the standard design or optionally from the rear of the system.

Configuration• Glycol Cooled• Water Cooled• Air Cooled

Compliance Approval• ETL/CETL• UL Listed to UL 1995 and CSA

C22.2 No. 236• MEA #223-99-E (City of New

York)

Standard Features• Scroll Compressor(s)• Centrifugal Blower Assembly• Heavy Gauge Steel Frame• Main Power Circuit Breaker• Microprocessor Controller• Bearing Life, L10 - 200,000 hrs• Front Service Access Only

Optional Features• Pure Steam Canister Humidifier • 30% ASHRAE 52.1 Filters• Three Phase Electric Reheat• 2 or 3 Way Fluid Regulating

Valves (Water or Glycol)• Brazed Plate Condenser (Water or

Glycol)• Plenums (with or without grilles)• Floorstand (with or without air

deflectors, seismic)• Discharge Duct Collar• Downflow Return Duct• Casters• Environmental Monitoring• ModBus/JBus Gateway• OHE Disconnect• High Efficiency Filters• 1” Prefilters• Spot or Cable Water Detector(s)• Firestat• Smoke Detector• Condensate Pump• Remote Relay Shutdown• Reheat/Humidity or Compressor

Lockout• Remote Display and/or Sensor• Redundant Group Control• Hot Water/ Steam Reheat• Hot Gas Reheat (Water or Glycol)• Hot Gas Bypass• Secondary Drain Pan• 3-Way Valve Flowswitch• Optional 5HP Motors• Custom Alarm Contacts

C US

APC NetworkAIR™ AFX 1

Standard FeaturesCabinetThe frame is constructed of heavy gauge steel for maximum strength. Steel access panels are insulated for quieter operation. The unit has been designed for full service access from the front. The flush mounted panels are removable using conve-nient quarter-turn fasteners. The access doors for the electronic con-troller and electrical panel can be opened without interrupting the operation of the unit.

Evaporator Coil/Drain PanThe AFX utilizes dual distributors on one circuit of the refrigeration system. During dehumidification the smaller distributor is turned off effectively reducing the active cir-cuits of the evaporator coil. During this mode of operation the evaporat-ing temperature is decreased, resulting in a lower coil surface temperature. This reduction of the coil temperature decreases the sen-sible heat ratio of the coil allowing a greater percentage of moisture removal. Additionally, the warmer air leaving the inactive circuits of the evaporator coil blends with the near saturated air from the active circuits raising the dry bulb temper-ature of the blended air well above saturation. Evaporator coil is 1/2” rifled, copper tube, with raised, lanced, rippled, aluminum fins. Condensate pan is constructed of stainless steel. Evaporator is config-ured as a “V” coil.

Electrical PanelThe electrical panel contains the contactors, starters, overload pro-tection devices, and input power disconnects. Each wire (except jumpers) is numbered every 3” (80mm), or color coded to facilitate circuit tracing when installing and servicing the unit. Each AC power circuit is individually branch circuit fused on all three phases. All com-pressor and motor devices are thermally and short circuit pro-tected. The electrical panel is easily accessible from the front of the unit. An emergency cool override switch can be manually activated to initiate cooling and a field wired thermostat can be utilized to control cooling operation. All electrical compo-nents are UL-listed and -recognized and all wiring conforms to NFPA 70 (NEC) and UL 1995 requirements.

Fan/Motor SectionThe NetworkAIR AFX includes multiple, centrifugal blower assem-blies that have been engineered for quiet, reliable operation. Lower blower speeds reduce noise and extend belt and bearing life to 200,000L10 hours. Permanently lubricated bearings, a single-belt variable pitch drive, and an adjust-able motor base all ensure dependable operation. In addition, the return air is evenly distributed across the cooling coil.

Refrigeration System and CompressorThe refrigeration system operates under an automatic microprocessor controller for greater efficiency and accuracy. The heavy-duty compres-sor is designed for year-round operation with a 15-year life expectancy. The performance of the refrigeration system is enhanced by use of Scroll Compressor Technol-ogy. Vibration in the system is greatly reduced by elimination of the reciprocating masses found in the semi-hermetic compressor. Risk of refrigeration leaks at compressor gaskets are eliminated with the scroll compressors fully welded hermetic shell. The design of the scroll is more tolerant to liquid flood back than the traditional reciprocating compressor. Power consumption at full load is greatly reduced with higher EER’s of the scroll. In addition reliability is enhanced due to the fewer moving parts required using scroll technol-ogy. The end result is a refrigeration system that offers the user opti-mized performance, efficiency, and reliability.

Main Power DisconnectA nonautomatic main power circuit breaker disconnects all high voltage power to the unit if necessary. The disconnect switch is accessible without removing the electric box cover.

2 APC NetworkAIR™ AFX

Optional Features

Air FilterThe filtration of conditioned air is extremely vital to maintaining the clean, particle-free environment required by electrical equipment. The system uses 30% efficient (100 microns) (ASHRAE 52.1-92), 4” (102 mm) deep filters, with full depth filter pleats. Deeper filters produce a lower pressure drop, requiring less energy during normal operation. Filters are replaceable through the front of the upflow unit, through the top of the downflow unit, and from either side of the fil-ter box on the back of the upflow rear return unit.

HumidifierThe humidifier utilizes a pure steam generator specifically designed for hi-tech area environmental control. The pure steam eliminates contami-nating mineral deposits, bacteria, white dust and excessive humidity. The humidifier requires little or no scheduled maintenance. Automatic flushing combined with an indicator that signals when the canister is to be change changed, ensure mainte-nance free operation.

Electric ReheatA three-phase electrical resistance heater sized to offset the sensible cooling capacity in the dehumidifi-cation mode is incorporated in each NetworkAIR AFX. The reheat ele-ments are low watt density sheathed components. The reheat is three phase to provide even phase load-ing. Reheat elements are electrically and thermally protected. 20-27kW (6-8 ton) models come with one stage standard with a max-imum of two stages available. 34-98kW (10-28 ton) models come with 2 stages.

CondenserWater- and Glycol-cooled systems employ a brazed plate condenser that uses the latest heat transfer technology. Type 316L stainless plates are brazed together in a vac-uum furnace and comply with ASME pressure vessel code. Pres-sure rating is 450 psi (3100 kPa).

Water-Regulating ValveThe Water-and Glycol systems maintain proper performance by sensing refrigerant discharge pres-sure and regulating the among of water or glycol supplied to the con-denser. A two-way or three-way valve is available. The standard valve pressure rating is 150 psi (1030kPa).

Discharge Duct CollarA 1” (25.4 mm) duct flange is shipped loose from the factory for field installation to provide conve-nient connection to external ductwork for either supply or return as needed.

Secondary Drain PanSystems are provided with two drain pans. The primary stainless steel condensate drain pan lies directly under the cooling coil. A secondary emergency drain pan provides additional protection by catching and water before it reaches the subfloor and becomes a problem.

Spot Water Detector(s)The solid-state spot water detector activates an audible alarm on the controller when moisture is detected.

Compressor LockoutPrevents compressor operation in emergency situations where limited back-up power is available.

Cable Water DetectorA 50 ft. leak detection sensing cable is placed on the floor or subfloor around all possible leak sources. If water or other conductive liquids contact the cable anywhere along its length, an alarm is triggered.

FirestatA firestat is available for factory installation in the air stream of the unit. If the return air temperature reaches 125°F (52°C), an audible and visual alarm on the micropro-cessor will be activated and the unit will immediately shutdown.

Smoke DetectorThe factory-installed smoke detec-tor is designed to sense smoke in the return air stream. Upon detec-tion of smoke, an audible and visual alarm on the microprocessor will be activated and the unit will be imme-diately shutdown.

Condensate PumpThe factory-installed and wired condensate pump will pump 36 gal/h (0.06 L/s) at 15 ft. (4.6 m) head.

Remote Relay ShutdownShutdown of the NetworkAIR sys-tem can be done remotely by a factory installed relay. The relay can be ordered with a 24V, 120V, or 240V coil. The relay must be pow-ered by others to disable the NetworkAIR system.

Reheat/Humidity LockoutWhen facilities have limited backup power capacity, this lockout pre-vents the operation of electrical loads that are not essential for con-tinued site operation.

APC NetworkAIR™ AFX 3

Optional Features

Redundant Group ControlAllows up to six NetworkAIR units the ability to communicate with each other to automatically switch upon alarm condition, or timed rotation. Can also allow standby units the ability to assist the running system.

Remote Display PanelThe microprocessor controller allows facility or building mainte-nance personnel to evaluate and control the unit from up to 50ft. away from the unit, without having to enter the secured space.

Remote Sensor(s)Environmental sensor(s) can be strategically placed, up to 50ft. from the unit to better meet the site’s cooling needs. The sensor must be positioned to permit air movement across the sensors.

Hot Gas ReheatHot gas reheat is optional on water- and glycol-cooled systems. The copper tube, aluminum fin hot gas reheat coil maintains the leaving dry bulb temperature when the sys-tem is in dehumidification mode. The coil is controlled by the proces-sor through a factory piped and wired three-way heat reclaim regu-lator and check valve.

Hot Water Reheat (Modulating)A 2- or 3-way modulating control valve controls hot water reheat. The system is supplied with a factory-installed copper tube and an alumi-num fin hot water coil.

Steam/Hot Water Reheat (2-Way On/Off)An on/off solenoid valve maintains the dry bulb temperature when the system is in dehumidification and reheat mode. Completely factory pre-piped, the system includes a copper tube, aluminum fin reheat coil, float, and thermostatic steam trap.

Optional Blower/Motor HPAn optional 5HP motor can be used for increased CFM or to accommo-date special air filters, high external static pressure, etc. while maintain-ing the standard CFM rating.

High Efficiency Filter(s)Pleated final filters with an efficien-cies of 45% or 65%, 4” (102mm) deep, allow for the removal of a greater percentage of airborne par-ticulate contaminates.

Prefilter(s)The prefilters capture large airborne particulate contaminates, thereby extending the life of the high-effi-ciency filter. Prefilters are 1” (25mm) deep and easily disposed.

Hot Gas BypassAn auxiliary side-port hot gas bypass circuit. The activation of the hot gas bypass circuit will maintain the evaporator coil temperature dur-ing low load conditions. This optional feature will minimize com-pressor cycling and temperature fluctuations.

3-Way Valve Flow SwitchA Single-Pole, Double-Throw flow switch can be wired to energize one device and de-energize another device powered from the same source when fluid flow either exceeds or drops below the set flow rate.

PlenumAir discharge plenums are available with upflow configurations. Heights are offered in 20” (508mm) and 24” (610mm). Manually adjust-able, double deflecting grilles are provided on 3 or 4 sides.

Air deflectorA field installed air deflector runs the length of the unit and attaches to the floorstand for changing air direction from vertical to horizontal.

FloorstandThe floorstand raises the unit above the subfloor to match the height of the raised floor. Heights are avail-able (from 6” (142 mm) to 36” (914 mm)) in 3” (76.2 mm) increments and are adjustable +/- 1.5” (38.1 mm). APC recommends at least 12” (305 mm) high floorstands for their downflow units. Adjustment is pro-vided by threaded pedestals. Vibration absorbing pads are included. The floorstand, pedestal, and pads ship loose. In areas where earthquakes are a concern, seismic floorstands are available in 12” (305mm), 18” (457 mm) and 24” (610 mm) heights.

CastersA set of 6” plated rolling caster wheels are available for handling of equipment.

Environmental Monitoring UnitA stand-alone unit performs contact monitoring and continuous temper-ature and humidity sensing through two probes (one included). The unit is controlled by available web, con-trol console, or SNMP interface with a network connection. In the event of an environmental anomaly, notification is sent via e-mail or SNMP. The unit is 18.25” x 9” x 2.75” (464mm x 229mm x 70mm).

Environmental Management SystemA browser-accessible, 1U, rack-mountable appliance allows monitoring of environmental condi-tions. Monitoring of one temperature, one humidity, and one vibration sensor ship standard. When conditions change, notifica-tions are sent via email to appropriate personnel. The EMS provides 8 input contacts, 2 output relays, and controllable power out-lets for defining actions remotely should conditions warrant it.

4 APC NetworkAIR™ AFX

Optional Features

ModBus/JBus GatewayThe Gateway translates transmis-sion protocol from the system’s network into ModBus/JBus com-munication protocol. One gateway can support up to 16 units.

OHE DisconnectA non-fused disconnect switch may be wired to an outdoor heat exchanger to disconnect high volt-age power if necessary.

Custom Alarm Contact ClosuresEach unit is equipped with dry con-tact closures. Upon activation of the associated alarm, a discreet Nor-mally open or Normally closed contact is available for remote mon-itoring of that discrete alarm.

Downflow Return DuctA return duct the length and width of the unit may be field installed on a downflow unit to provide conve-nient connection to external ductwork.

APC NetworkAIR™ AFX 5

Microprocessor Controller

Microprocessor Controller The microprocessor controller is standard on the main module of each system. The controller pro-vides precision control for the demanding requirements of:

• Data centers• Control rooms• Clean rooms• Switch rooms• UPS rooms

The easy-to-use display allows the operator to select options from the device’s menu-driven interface to control and monitor the connected air conditioning system.

StatusComplete status monitoring is pro-vided within the status menu of the microprocessor controller. Avail-able information includes:

• Current Temperature/Humidity• Temperature/Humidity Setpoint• Cooling/Heating Status• Humidification/Dehumidification

Status

AlarmsQuick access to any alarm condition is facilitated through the menu structure. The alarm key acts as a hot key providing immediate access to the alarm display menu. Presence of a new alarm will sound the audi-ble alarm. The red alarm LED on the display panel will remain illu-minated until all alarms have been cleared. The temperature and humidity alarm setpoints are adjust-able. Alarm annunciations include:

• Loss of airflow• Clogged filter• High head pressure• Low suction pressure• High/Low temperature• High/Low humidity

Automatic setpoint crossover pro-tection will prevent the setting of the heat setpoint above the cool set-point and the humidification setpoint above the dehumidification setpoint. Setpoint adjustment can be restricted to only operators with knowledge of the security codes set within the security menu structure.

ConfigurationFlexibility is offered through he use of the configuration menu. Operat-ing requirements are satisfied by changing the configuration set-tings. New configurations are stored in EEPROM and protected from unauthorized tampering by the four-digit security password, selected in the security menu. Con-figuration options include:

• Fahrenheit or celsius display• Compressor minimum on/off time• Power loss restart time delay• Redundant unit grouping• Alarm input polarity• Alarm enable• Temperature/Humidity deadbands• Small room delay

Common Alarm ContactA common alarm relay is installed on every microprocessor. In the event of an alarm condition, the relay will change state. The user can select which alarms change the state of the relay. This feature allows for remote enunciation of alarm status.

Run TimesThe major components within the unit have independent run timers that monitor and store accumulated run hours on the components. The run timers are provided with opera-tor adjustable run time alarms.

SecurityMultiple security levels prevent unauthorized adjustment of impor-tant system parameters. The user may select a four-digit password for setpoint and configuration changes. Should the password be forgotten, APC can provide temporary access.

MonitoringWith the addition of a supervisory network communications card the microprocessor may interface with the locally installed APC remote monitoring and control system. Gateways are available for interfac-ing with building management systems. Please check with APC for compatibility with your building management system.

Cool InhibitPrevents the unit from over-cooling during the dehumidification cycle. If the space temperature falls below a user adjustable setpoint, cooling will become inhibited until the space temperature returns to setpoint.

Cool OverrideA manual toggle switch will allow the compressor to operate in the event of a microprocessor failure. The cool override can be field wired to a snap acting thermostat for cool-ing control.

Remote ShutdownEvents external to the unit, such as activation of a fire suppression sys-tem may require the unit to shut down remotely. Additionally this feature may be tied into a BMS that would allow remote control of the units on/off status.

6 APC NetworkAIR™ AFX

Performance Specifications—Air CooledNET COOLING CAPACITY - BTU/HR (kW) 20 kW

(6 ton)27 kW(8 ton)

34 kW(10 ton)

41 kW(12 ton)

48 kW(14 ton)

62 kW(18 ton)

70 kW(20 ton)

90 kW(26 ton)

98 kW(28 ton)

80F DB, 67F WB (26.7C DB, 19.4C WB) 50% RH

Total 78,000(22.9)

111,000(32.6)

133,000(38.9)

147,000(43.0)

158,000(46.3)

227,000(66.3)

267,000(78.3)

297,000(86.9)

330,000(86.9)

Sensible 73,000(21.3)

89,000(26.0)

125,000(36.6)

134,000(39.3)

152,000(44.3)

185,000(54.0)

240,000(70.3)

258,000(75.6)

283,000(83.0)

75F DB, 62.5F WB (23.9C DB, 16.9C WB) 50% RH

Total 73,000(21.3)

103,000(30.3)

123,000(36.0)

136,000(39.9)

149,000(43.6)

210,000(61.6)

249,000(72.9)

279,000(81.9)

305,000(89.3)

Sensible 71,000(20.9)

88,000(25.9)

122,000(35.9)

132,000(38.6)

149,000(43.6)

182,000(53.3)

237,000(69.6)

256,000(75.0)

278,000(81.3)

75F DB, 61F WB (23.9C DB, 16.1C WB) 45% RH

Total 73,000(21.3)

102,000(29.9)

125,000(36.6)

137,000(40.0)

149,000(43.6)

206,000(60.3)

252,000(73.6)

281,000(82.3)

308,000(90.3)

Sensible 73,000(21.3)

95,000(27.9)

125,000(36.6)

137,000(40.0)

149,000(43.6)

196,000(57.3)

252,000(73.6)

281,000(82.3)

308,000(90.3)

72F DB, 60F WB (22.2C DB, 15.5C WB) 50% RH

Total 70,000(21.3)

99,000(28.9)

119,000(34.9)

130,000(38.3)

143,000(41.9)

202,000(59.0)

239,000(69.9)

269,000(78.9)

293,000(85.6)

Sensible 69,000(20.0)

86,000(25.3)

119,000(34.9)

128,000(37.3)

143,000(41.9)

178,000(52.0)

231,000(67.6)

251,000(73.6)

273,000(79.9)

72F DB, 58.6 WB (22.2D DB, 14.8C WB) 45% RH

Total 70,000(20.6)

98,000(28.6)

120,000(35.0)

132,000(38.6)

143,000(41.9)

198,000(57.9)

242,000(70.9)

272,000(79.6)

297,000(86.9)

Sensible 70,000(20.6)

93,000(27.0)

120,000(35.0)

132,000(38.6)

143,000(41.9)

191,000(56.0)

242,000(70.9)

272,000(79.6)

297,000(86.9)

70F DB, 58.5F WB (21.1C DB, 14.8C WB) 50% RH

Total 68,000(19.9)

96,000(28.0)

116,000(34.0)

127,000(37.0)

139,000(40.6)

196,000(57.3)

232,000(68.0)

263,000(76.9)

284,000(83.3)

Sensible 67,000(19.6)

84,000(24.6)

116,000(34.0)

125,000(36.6)

139,000(40.6)

174,000(51.0)

226,000(66.3)

247,000(72.3)

266,000(78.0)

70F DB, 57.2F WB (21.1C DB, 14.0C WB) 45% RH

Total 68,000(19.9)

95,000(27.9)

116,000(34.0)

128,000(37.6)

139,000(40.6)

192,000(56.3)

236,000(69.0)

266,000(77.9)

288,000(84.3)

Sensible 68,000(19.9)

90,000(26.6)

116,000(34.0)

128,000(37.6)

139,000(40.6)

187,000(54.6)

236,000(69.0)

266,000(77.9)

288,000(84.3)

AIR SYSTEM -- BELT DRIVE CENTRIFUGAL

Air Volume -- CFM (L/s) 4,200(1,982)

4,400(2,077)

7,000(3,304)

7,200(3,398)

8,400(3,965)

8,800(4,154)

12,600(5,947)

13,200(6,230)

14,200(6,702)

Blower Motor -- HP (kW) 3 (2.2)

3 (2.2)

3(2.2)

3(2.2)

3(2.2)

3(2.2)

3(2.2)

3(2.2)

3(2.2)

External Static Pressure -- inches of water (Pa)

0.5(125)

0.5(125)

0.5(125)

0.5(125)

0.5(125)

0.5(125)

0.5(125)

0.5(125)

0.5(125)

Number of Blowers/Motors 1 1 2 2 2 2 3 3 3COMPRESSOR -- SCROLL

EER 14.6 14.6 14.2 14.7 14.6 14.6 14.5 14.6 14.2Quantity 1 1 2 2 2 2 2 2 2

EVAPORATOR COIL -- V FRAME, COPPER TUBE/ALUMINUM FIN

Face Area -- ft2 (m2) 9.5(0.88)

9.5(0.88)

21.3(1.98)

21.3(1.98)

21.3(1.98)

21.3(1.98)

33.0(3.07)

33.0(3.07)

33.0(3.07)

Rows Deep 4 4 4 4 4 4 4 4 4

Face Velocity -- FPM (m/s) 442(2.25)

463(2.35)

329(1.67)

338(1.72)

394(2.00)

413(2.10)

382(1.94)

400(2.03)

430(2.18)

HUMIDIFICATION --- SOLID STATE ELECTRODE CANISTERFlush Cycle automatic automatic automatic automatic automatic automatic automatic automatic automatic

Capacity -- Lbs/hr (Kg/hr) 10(4.5)

10(4.5)

10(4.5)

10(4.5)

10(4.5)

10(4.5)

20(9.0)

20(9.0)

20(9.0)

kW 3.4 3.4 3.4 3.4 3.4 3.4 6.8 6.8 6.8FILTERS

Quantity 2 2 4 4 4 4 6 6 6Depth -- Inches (mm) 4 (102) 4 (102) 4 (102) 4 (102) 4 (102) 4 (102) 4 (102) 4 (102) 4 (102)

Size (Downflow) -- Inches (mm) 30 x 15.5(762 x394)

30 x 15.5(762 x394)

30 x 15.5(762 x394)

30 x 15.5(762 x394)

30 x 15.5(762 x394)

30 x 15.5(762 x394)

30 x 15.5(762 x394)

30 x 15.5(762 x394)

30 x 15.5(762 x394)

Size (Upflow) -- Inches (mm) 27 x 18(686 x457)

27 x 18(686 x457)

27 x 18(686 x457)

27 x 18(686 x457)

27 x 18(686 x457)

27 x 18(686 x457)

27 x 18(686 x457)

27 x 18(686 x457)

27 x 18(686 x457)

APC NetworkAIR™ AFX 7

Performance Specifications—Air Cooled

Performance Specifications—Air CooledAFX (kW-tons) 20 kW

(6 ton)27 kW(8 ton)

34 kW(10 ton)

41 kW(12 ton)

48 kW(14 ton)

62 kW(18 ton)

70 kW(20 ton)

90 kW(26 ton)

98 kW(28 ton)

REHEATElectric -- Equally Loaded Three (3) Phase, Finned Tubular, Low-Watt Density

Capacity -- BTU/HR (kW) Includes Motor Heat*

28,000(8.3)

28,000(8.3)

57,000(16.6)

57,000(16.6)

57,000(16.6)

57,000(16.6)

85,000(24.9)

85,000(24.9)

85,000(24.9)

Stages 1 1 2 2 2 2 2 2 2Hot Water -- 180F (82.2C) EWT, 160F (71.1C) LWT

Capacity -- BTU/HR (kW) Includes Motor Heat

79,000(23.0)

81,000(23.9)

152,000(44.6)

155,000(45.6)

176,000(50.9)

179,000(52.6)

259,000(75.9)

268,000(78.3)

281,000(82.6)

GPM (L/s) 7.8(0.49)

8.0(0.50)

15.1(0.95)

15.4(0.97)

17.2(1.09)

17.7(1.12)

25.6(1.62)

26.4(1.67)

27.6(1.74)

Pressure Drop -- PSI (kPA) 0.3(1.8)

0.3(1.8)

0.9(6.3)

0.9(6.3)

1.1(7.6)

1.2(8.3)

2.5(17.2)

2.7(18.6)

2.9(20.0)

Steam -- 15 psig (103.3 kPa)Capacity -- BTU/HR (kW) Includes Motor Heat

79,000(23.0)

87,000(25.6)

134,000(39.3)

143,000(42.0)

164,000(47.9)

188,000(55.3)

243,000(71.3)

273,000(79.9)

298,000(87.3)

Control Valve solenoid solenoid solenoid solenoid solenoid solenoid solenoid solenoid solenoidPHYSICAL DATA

Weight -- lbs (kg) 850(386)

975(442)

1,175(533)

1,250(567)

1,400(635)

1,550(703)

1,750(794)

1,900(862)

2,100(953)

Height -- Inches (mm) 76.0(1,930)

76.0(1,930)

76.0(1,930)

76.0(1,930)

76.0(1,930)

76.0(1,930)

76.0(1,930)

76.0(1,930)

76.0(1,930)

Length -- Inches (mm) 34.4(873)

34.4(873)

66.4(1,685)

66.4(1,685)

66.4(1,685)

66.4(1,685)

98.3(2,997)

98.3(2,997)

98.3(2,997)

Depth -- Inches (mm) 34.4(873)

34.4(873)

34.4(873)

34.4(873)

34.4(873)

34.4(873)

34.4(873)

34.4(873)

34.4(873)

CONNECTION SIZES**Air

Liquid Line -- inches OD 1/2 5/8 1/2 1/2 5/8 5/8 5/8 5/8 5/8Discharge Line -- inches OD 5/8 1-1/8 5/8 5/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8

Hot WaterSupply Line -- inches OD 5/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8Return Line -- inches OD 5/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8

SteamSupply Line -- inches OD 5/8 5/8 5/8 5/8 5/8 5/8 7/8 7/8 7/8

HumidifierSupply Line -- inches OD 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4

Condensate DrainDrain Line -- inches ID 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8

*With equal loading on each phase, rated at 208-230V / 3-phase, 480V / 3-phase and 600V / 3-phase**Connections sizes, not recommended piping sizes

8 APC NetworkAIR™ AFX

Performance Specifications—Water CooledNET COOLING CAPACITY - BTU/HR (kW) 20 kW

(6 ton)27 kW(8 ton)

34 kW(10 ton)

41 kW(12 ton)

48 kW(14 ton)

62 kW(18 ton)

70 kW(20 ton)

90 kW(26 ton)

98 kW(28 ton)

80F DB, 67F WB (26.7C DB, 19.4C WB) 50% RH

Total 86,000(25.0)

121,000(35.3)

145,000(42.3)

161,000(47.0)

171,000(50.3)

246,000(72.0)

299,000(87.3)

340,000(99.6)

362,000(105.9)

Sensible 76,000(22.3)

94,000(27.3)

130,000(38.0)

140,000(40.9)

158,000(46.3)

193,000(56.6)

253,000(74.0)

277,000(81.0)

296,000(86.6)

75F DB, 62.5F WB (23.9C DB, 16.9C WB) 50% RH

Total 79,000(23.3)

112,000(32.6)

133,000(39.0)

148,000(43.3)

158,000(46.3)

227,000(66.3)

284,000(83.0)

312,000(91.3)

332,000(97.3)

Sensible 74,000(21.9)

92,000(27.0)

127,000(37.3)

137,000(40.3)

154,000(45.0)

190,000(55.6)

223,000(65.3)

272,000(79.6)

291,000(85.0)

75F DB, 61F WB (23.9C DB, 16.1C WB) 45% RH

Total 74,000(21.6)

110,000(32.3)

126,000(36.9)

148,000(43.3)

152,000(44.6)

222,000(65.0)

281,000(82.3)

305,000(89.3)

324,000(95.0)

Sensible 74,000(21.6)

100,000(29.3)

126,000(36.9)

148,000(43.3)

152,000(44.6)

204,000(59.6)

229,000(67.0)

293,000(85.9)

312,000(91.6)

72F DB, 60F WB (22.2C DB, 15.5C WB) 50% RH

Total 76,000(22.0)

107,000(31.3)

127,000(37.3)

141,000(41.3)

151,000(44.3)

217,000(63.6)

263,000(77.0)

298,000(87.3)

317,000(92.9)

Sensible 72,000(21.0)

90,000(26.3)

124,000(36.3)

134,000(39.3)

150,000(43.9)

185,000(54.3)

243,000(71.0)

266,000(77.9)

283,000(83.0)

72F DB, 58.6 WB (22.2D DB, 14.8C WB) 45% RH

Total 72,000(21.0)

105,000(30.9)

122,000(35.9)

133,000(38.9)

148,000(43.3)

213,000(62.3)

265,000(77.6)

291,000(85.3)

310,000(90.9)

Sensible 72,000(21.0)

97,000(28.3)

122,000(35.9)

133,000(38.9)

148,000(43.3)

199,000(58.3)

265,000(77.6)

284,000(83.3)

304,000(89.0)

70F DB, 58.5F WB (21.1C DB, 14.8C WB) 50% RH

Total 73,000(21.3)

104,000(30.3)

123,000(36.0)

137,000(40.0)

149,000(43.6)

210,000(61.6)

255,000(74.9)

289,000(84.6)

307,000(90.0)

Sensible 71,000(20.9)

88,000(25.9)

121,000(35.3)

131,000(38.3)

149,000(43.6)

182,000(53.3)

238,000(69.6)

260,000(76.0)

278,000(81.3)

70F DB, 57.2F WB (21.1C DB, 14.0C WB) 45% RH

Total 71,000(20.6)

102,000(30.0)

120,000(35.0)

129,000(37.9)

149,000(43.6)

206,000(60.3)

257,000(75.3)

283,000(82.6)

301,000(88.3)

Sensible 71,000(20.6)

95,000(27.6)

120,000(35.0)

130,000(38.0)

149,000(43.6)

194,000(56.9)

257,000(75.3)

277,000(81.3)

297,000(86.9)

COOLANT REQUIREMENTS

THR -- MBH (kW) 114,000(33.6)

161,000(47.0)

195,000(57.0)

216,000(63.3)

229,000(67.0)

324,000(94.9)

375,000(109.6)

444,000(130.0)

456,000(133.6)

65 F (18.3 C) Water In -- GPM (L/s) 6.2(0.4)

8.9(0.6)

10.1(0.6)

11.7(0.7)

11.4(0.7)

17.9(1.1)

20.2(1.3)

23.1(1.5)

23.4(1.5)

Pressure Drop -- psig (kPa) 1.4(9.7)

2.1(14.5)

2.1(14.5)

2.8(19.3)

1.3(9.0)

2.1(14.5)

2.3(15.9)

2.0(13.8)

2.0(13.8)

75 F (23.9 C) Water In -- GPM (L/s) 8.3(0.5)

11.8(0.7)

13.4(0.8)

15.6(1.0)

15.2(1.0)

23.9(1.5)

26.9(1.7)

30.8(1.9)

31.2(2.0)

Pressure Drop -- psig (kPa) 2.5(17.2)

3.8(26.2)

3.7(25.5)

5.0(34.5)

2.3(15.9)

3.7(25.5)

4.0(27.6)

3.5(24.1)

3.6(24.8)

85 F (29.4 C) Water In -- GPM (L/s) 18.6(1.2)

25.7(1.6)

28.4(1.8)

33.8(2.1)

30.7(1.9)

52.1(3.3)

58.1(3.7)

65.8(4.2)

69.3(4.4)

Pressure Drop -- psig (kPa) 11.8(81.4)

17.3(119.3)

16.3(112.4)

22.9(157.9)

9.0(62.1)

17.0(117.2)

18.2(125.5)

15.6(107.6)

17.3(119.3)

WATER REGULATING VALVESSize -- 2 Way Ball Valve -- Inches, NPT (Cv)*

1-1/4 (1)(14)

1-1/4 (1)(14)

3/4 (2)(20)

3/4 (2)(20)

1 (2)(24)

1-1/4 (2)(28)

1-1/4 (2)(28)

1-1/2 (2)(40)

1-1/2 (2)(40)

Size -- 3 Way Ball Valve -- Inches, NPT (Cv)**

1-1/4 (1)(14)

1-1/4 (1)(14)

3/4 (2)(20)

3/4 (2)(20)

1 (2)(24)

1-1/4 (2)(28)

1-1/4 (2)(28)

1-1/2 (2)(40)

1-1/2 (2)(40)

AIR SYSTEM -- BELT DRIVE CENTRIFUGAL

Air Volume -- CFM (L/s) 4,200(1,982)

4,400(2,077)

7,000(3,304)

7,200(3,398)

8,400(3,965)

8,800(4,154)

12,600(5,947)

13,200(6,230)

14,200(6,702)

Blower Motor -- HP (kW) 3 (2.2)

3 (2.2)

3(2.2)

3(2.2)

3(2.2)

3(2.2)

3(2.2)

3(2.2)

3(2.2)

External Static Pressure -- inches of water (Pa)

0.5(125)

0.5(125)

0.5(125)

0.5(125)

0.5(125)

0.5(125)

0.5(125)

0.5(125)

0.5(125)

Number of Blowers/Motors 1 1 2 2 2 2 3 3 3COMPRESSOR -- SCROLL

EER 18.7 18.4 17.9 18.7 18.7 18.4 18.2 18.3 17.8Quantity 1 1 2 2 2 2 2 2 2

APC NetworkAIR™ AFX 9

Performance Specifications—Water Cooled

Performance Specifications—Water CooledAFX (kW-tons) 20 kW

(6 ton)27 kW(8 ton)

34 kW(10 ton)

41 kW(12 ton)

48 kW(14 ton)

62 kW(18 ton)

70 kW(20 ton)

90 kW(26 ton)

98 kW(28 ton)

EVAPORATOR COIL -- V FRAME, COPPER TUBE/ALUMINUM FIN

Face Area -- ft2 (m2) 9.5(0.88)

9.5(0.88)

21.3(1.98)

21.3(1.98)

21.3(1.98)

21.3(1.98)

33.0(3.07)

33.0(3.07)

33.0(3.07)

Rows Deep 4 4 4 4 4 4 4 4 4

Face Velocity -- FPM (m/s) 442(2.25)

463(2.35)

329(1.67)

338(1.72)

394(2.00)

413(2.10)

382(1.94)

400(2.03)

430(2.18)

HUMIDIFICATION --- SOLID STATE ELECTRODE CANISTERFlush Cycle automatic automatic automatic automatic automatic automatic automatic automatic automatic

Capacity -- Lbs/hr (Kg/hr) 10(4.5)

10(4.5)

10(4.5)

10(4.5)

10(4.5)

10(4.5)

20(9.0)

20(9.0)

20(9.0)

kW 3.4 3.4 3.4 3.4 3.4 3.4 6.8 6.8 6.8FILTERS

Quantity 2 2 4 4 4 4 6 6 6Depth -- Inches (mm) 4 (102) 4 (102) 4 (102) 4 (102) 4 (102) 4 (102) 4 (102) 4 (102) 4 (102)

Size (Downflow) -- Inches (mm) 30 x 15.5(762 x394)

30 x 15.5(762 x394)

30 x 15.5(762 x394)

30 x 15.5(762 x394)

30 x 15.5(762 x394)

30 x 15.5(762 x394)

30 x 15.5(762 x394)

30 x 15.5(762 x394)

30 x 15.5(762 x394)

Size (Upflow) -- Inches (mm) 27 x 18(686 x457)

27 x 18(686 x457)

27 x 18(686 x457)

27 x 18(686 x457)

27 x 18(686 x457)

27 x 18(686 x457)

27 x 18(686 x457)

27 x 18(686 x457)

27 x 18(686 x457)

REHEATElectric -- Equally Loaded Three (3) Phase, Finned Tubular, Low-Watt Density

Capacity -- BTU/HR (kW) Includes Motor Heat***

28,000(8.3)

28,000(8.3)

57,000(16.6)

57,000(16.6)

57,000(16.6)

57,000(16.6)

85,000(24.9)

85,000(24.9)

85,000(24.9)

Stages 1 1 2 2 2 2 2 2 2Hot Water -- 180F (82.2C) EWT, 160F (71.1C) LWT

Capacity - BTU/HR (kW) Includes Motor Heat

79,000(23.0)

81,000(23.9)

152,000(44.6)

155,000(45.6)

176,000(50.9)

179,000(52.6)

259,000(75.9)

268,000(78.3)

281,000(82.6)

GPM (L/s) 7.8(0.49)

8.0(0.50)

15.1(0.95)

15.4(0.97)

17.2(1.09)

17.7(1.12)

25.6(1.62)

26.4(1.67)

27.6(1.74)

Pressure Drop -- PSI (kPA) 0.3(1.8)

0.3(1.8)

0.9(6.3)

0.9(6.3)

1.1(7.6)

1.2(8.3)

2.5(17.2)

2.7(18.6)

2.9(20.0)

Hot Gas ReheatCapacity -- BTU/HR (kW) Includes Motor Heat

26,000(7.6)

33,000(9.6)

83,000(24.3)

91,000(26.6)

93,000(27.3)

93,000(27.3)

147,000(43.0)

147,000(43.0)

147,000(43.0)

Steam -- 15 psig (103.3 kPa)Capacity -- BTU/HR (kW) Includes Motor Heat

79,000(23.3)

87,000(25.6)

134,000(39.3)

143,000(42.0)

164,000(47.9)

188,000(55.3)

243,000(71.3)

273,000(79.9)

298,000(87.3)

Control Valve solenoid solenoid solenoid solenoid solenoid solenoid solenoid solenoid solenoidPHYSICAL DATA

Weight -- lbs (kg) 1,000(454)

1,050(477)

1,800(818)

1,850(841)

1,900(863)

1,950(886)

2,650(1,204)

2,700(1,227)

2,750(1,250)

Height -- Inches (mm) 76.0(1,930)

76.0(1,930)

76.0(1,930)

76.0(1,930)

76.0(1,930)

76.0(1,930)

76.0(1,930)

76.0(1,930)

76.0(1,930)

Length -- Inches (mm) 34.4(873)

34.4(873)

66.4(1,685)

66.4(1,685)

66.4(1,685)

66.4(1,685)

98.3(2,997)

98.3(2,997)

98.3(2,997)

Depth -- Inches (mm) 34.4(873)

34.4(873)

34.4(873)

34.4(873)

34.4(873)

34.4(873)

34.4(873)

34.4(873)

34.4(873)

CONNECTION SIZES****Water In/Out -- Inches OD 1-3/8 1-3/8 1-3/8 1-5/8 1-5/8 1-5/8 1-5/8 2-1/8 2-1/8Hot Water

Supply Line -- Inches OD 5/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8Return Line -- Inches OD 5/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8

SteamSupply Line -- Inches OD 5/8 5/8 5/8 5/8 5/8 5/8 7/8 7/8 7/8

HumidifierSupply Line -- Inches OD 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4

Condensate DrainDrain Line -- Inches ID 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8

*2-Way Single Seated, 400 psig W.W.P. max**3-Way Single Seated, 400 psig W.W.P. max***With equal loading on each phase, rated at 208-230V / 3-phase, 480V / 3-phase and 600V / 3-phase****Connections sizes, not recommended piping sizes

10 APC NetworkAIR™ AFX

Performance Specifications—Glycol CooledNET COOLING CAPACITY - BTU/HR (kW) 20 kW

(6 ton)27 kW(8 ton)

34 kW(10 ton)

41 kW(12 ton)

48 kW(14 ton)

62 kW(18 ton)

70 kW(20 ton)

90 kW(26 ton)

98 kW(28 ton)

80F DB, 67F WB (26.7C DB, 19.4C WB) 50% RH

Total 78,000(22.9)

111,000(32.3)

130,000(38.0)

146,000(42.6)

155,000(45.6)

225,000(65.9)

270,000(79.1)

296,000(86.9)

329,000(96.3)

Sensible 72,000(21.3)

89,000(26.0)

123,000(36.0)

134,000(39.0)

150,000(44.0)

184,000(53.9)

241,000(70.6)

258,000(75.6)

283,000(82.9)

75F DB, 62.5F WB (23.9C DB, 16.9C WB) 50% RH

Total 72,000(21.0)

102,000(29.9)

122,000(35.6)

134,000(39.3)

146,000(42.6)

207,000(60.6)

256,000(75.0)

274,000(80.3)

302,000(88.6)

Sensible 70,000(20.6)

87,000(25.6)

122,000(35.6)

131,000(38.3)

146,000(42.6)

180,000(52.6)

211,000(61.6)

252,000(73.6)

278,000(81.3)

75F DB, 61F WB (23.9C DB, 16.1C WB) 45% RH

Total 70,000(20.3)

101,000(29.6)

122,000(35.6)

129,000(37.9)

146,000(42.6)

202,000(59.0)

254,000(74.6)

279,000(81.6)

305,000(89.3)

Sensible 70,000(20.3)

94,000(27.6)

122,000(35.6)

129,000(37.9)

146,000(42.6)

194,000(56.6)

217,000(63.3)

279,000(81.6)

305,000(89.3)

72F DB, 60F WB (22.2C DB, 15.5C WB) 50% RH

Total 69,000(20.3)

97,000(28.6)

116,000(34.0)

128,000(37.3)

139,000(40.9)

197,000(57.6)

238,000(69.6)

266,000(78.0)

285,000(83.6)

Sensible 69,000(20.3)

85,000(25.0)

116,000(34.0)

126,000(36.6)

139,000(40.9)

176,000(51.3)

231,000(67.6)

252,000(73.6)

265,000(77.6)

72F DB, 58.6 WB (22.2D DB, 14.8C WB) 45% RH

Total 68,000(20.0)

96,000(28.3)

116,000(34.0)

124,000(36.3)

139,000(40.9)

193,000(56.6)

242,000(70.6)

269,000(78.6)

293,000(85.6)

Sensible 68,000(20.0)

91,000(26.6)

116,000(34.0)

124,000(36.3)

139,000(40.9)

189,000(55.3)

242,000(70.6)

269,000(78.6)

293,000(85.6)

70F DB, 58.5F WB (21.1C DB, 14.8C WB) 50% RH

Total 67,000(19.6)

94,000(27.6)

113,000(32.9)

125,000(36.6)

135,000(39.6)

191,000(56.0)

231,000(67.6)

259,000(75.9)

279,000(81.6)

Sensible 67,000(19.6)

84,000(24.3)

113,000(32.9)

125,000(36.6)

135,000(39.6)

172,000(50.3)

225,000(66.0)

247,000(72.3)

265,000(77.6)

70F DB, 57.2F WB (21.1C DB, 14.0C WB) 45% RH

Total 67,000(19.6)

93,000(27.3)

113,000(32.9)

125,000(36.6)

135,000(39.6)

187,000(54.9)

235,000(68.6)

262,000(76.6)

284,000(83.3)

Sensible 67,000(19.6)

89,000(26.3)

113,000(32.9)

125,000(36.6)

135,000(29.6)

184,000(53.9)

235,000(68.6)

262,000(76.6)

284,000(83.3)

COOLANT REQUIREMENTS

THR -- MBH (kW) 111,000(32.3)

156,000(45.6)

188,000(55.0)

209,000(61.0)

221,000(64.6)

313,000(91.9)

362,000(105.9)

432,000(126.6)

443,000(129.6)

105 F (40.6 C) Glycol In -- GPM (L/s) 17.5(1.1)

25.2(1.6)

31.0(2.0)

31.7(2.0)

34.9(2.2)

50.8(3.2)

61.4(3.9)

66.9(4.2)

67.8(4.3)

Pressure Drop -- psig (kPa) 5.2(35.9)

9.3(64.1)

11.3(77.9)

11.3(77.9)

7.8(53.8)

8.8(60.7)

12.3(84.8)

9.4(64.8)

9.7(66.9)

WATER REGULATING VALVESSize -- 2 Way Ball Valve -- Inches, NPT (Cv)*

1-1/4 (1)(14)

1-1/4 (1)(14)

3/4 (2)(20)

3/4 (2)(20)

1 (2)(24)

1-1/4 (2)(28)

1-1/4 (2)(28)

1-1/2 (2)(40)

1-1/2 (2)(40)

Size -- 3 Way Ball Valve -- Inches, NPT (Cv)**

1-1/4 (1)(14)

1-1/4 (1)(14)

3/4 (2)(20)

3/4 (2)(20)

1 (2)(24)

1-1/4 (2)(28)

1-1/4 (2)(28)

1-1/2 (2)(40)

1-1/2 (2)(40)

AIR SYSTEM -- BELT DRIVE CENTRIFUGAL

Air Volume -- CFM (L/s) 4,200(1,982)

4,400(2,077)

7,000(3,304)

7,200(3,398)

8,400(3,965)

8,800(4,154)

12,600(5,947)

13,200(6,230)

14,200(6,702)

Blower Motor -- HP (kW) 3 (2.2)

3 (2.2)

3(2.2)

3(2.2)

3(2.2)

3(2.2)

3(2.2)

3(2.2)

3(2.2)

External Static Pressure -- inches of water (Pa)

0.5(125)

0.5(125)

0.5(125)

0.5(125)

0.5(125)

0.5(125)

0.5(125)

0.5(125)

0.5(125)

Number of Blowers/Motors 1 1 2 2 2 2 3 3 3COMPRESSOR -- SCROLL

EER 13.4 13.5 13.1 13.5 13.4 13.5 13.4 13.4 13.1Quantity 1 1 2 2 2 2 2 2 2

EVAPORATOR COIL -- V FRAME, COPPER TUBE/ALUMINUM FIN

Face Area -- ft2 (m2) 9.5(0.88)

9.5(0.88)

21.3(1.98)

21.3(1.98)

21.3(1.98)

21.3(1.98)

33.0(3.07)

33.0(3.07)

33.0(3.07)

Rows Deep 4 4 4 4 4 4 4 4 4

Face Velocity -- FPM (m/s) 442(2.25)

463(2.35)

329(1.67)

338(1.72)

394(2.00)

413(2.10)

382(1.94)

400(2.03)

430(2.18)

APC NetworkAIR™ AFX 11

Performance Specifications—Glycol Cooled

Performance Specifications—Glycol CooledAFX (kW-tons) 20 kW

(6 ton)27 kW(8 ton)

34 kW(10 ton)

41 kW(12 ton)

48 kW(14 ton)

62 kW(18 ton)

70 kW(20 ton)

90 kW(26 ton)

98 kW(28 ton)

HUMIDIFICATION --- SOLID STATE ELECTRODE CANISTERFlush Cycle automatic automatic automatic automatic automatic automatic automatic automatic automatic

Capacity -- Lbs/hr (Kg/hr) 10(4.5)

10(4.5)

10(4.5)

10(4.5)

10(4.5)

10(4.5)

20(9.0)

20(9.0)

20(9.0)

kW 3.4 3.4 3.4 3.4 3.4 3.4 6.8 6.8 6.8FILTERS

Quantity 2 2 4 4 4 4 6 6 6Depth -- Inches (mm) 4 (102) 4 (102) 4 (102) 4 (102) 4 (102) 4 (102) 4 (102) 4 (102) 4 (102)

Size (Downflow) -- Inches (mm) 30 x 15.5(762 x394)

30 x 15.5(762 x394)

30 x 15.5(762 x394)

30 x 15.5(762 x394)

30 x 15.5(762 x394)

30 x 15.5(762 x394)

30 x 15.5(762 x394)

30 x 15.5(762 x394)

30 x 15.5(762 x394)

Size (Upflow) -- Inches (mm) 27 x 18(686 x457)

27 x 18(686 x457)

27 x 18(686 x457)

27 x 18(686 x457)

27 x 18(686 x457)

27 x 18(686 x457)

27 x 18(686 x457)

27 x 18(686 x457)

27 x 18(686 x457)

REHEATElectric -- Equally Loaded Three (3) Phase, Finned Tubular, Low-Watt Density

Capacity -- BTU/HR (kW) Includes Motor Heat***

28,000(8.3)

28,000(8.3)

57,000(16.6)

57,000(16.6)

57,000(16.6)

57,000(16.6)

85,000(24.9)

85,000(24.9)

85,000(24.9)

Stages 1 1 2 2 2 2 2 2 2Hot Water -- 180F (82.2C) EWT, 160F (71.1C) LWT

Capacity - BTU/HR (kW) Includes Motor Heat

79,000(23.0)

81,000(23.9)

152,000(44.6)

155,000(45.6)

176,000(50.9)

179,000(52.6)

259,000(75.9)

268,000(78.3)

281,000(82.6)

GPM (L/s) 7.8(0.49)

8.0(0.50)

15.1(0.95)

15.4(0.97)

17.2(1.09)

17.7(1.12)

25.6(1.62)

26.4(1.67)

27.6(1.74)

Pressure Drop -- PSI (kPA) 0.3(1.8)

0.3(1.8)

0.9(6.3)

0.9(6.3)

1.1(7.6)

1.2(8.3)

2.5(17.2)

2.7(18.6)

2.9(20.0)

Hot Gas ReheatCapacity -- BTU/HR (kW) Includes Motor Heat

26,000(7.6)

33,000(9.6)

83,000(24.3)

91,000(26.6)

93,000(27.3)

93,000(27.3)

147,000(43.0)

147,000(43.0)

147,000(43.0)

Steam -- 15 psig (103.3 kPa)Capacity -- BTU/HR (kW) Includes Motor Heat

79,000(23.3)

87,000(25.6)

134,000(39.3)

143,000(42.0)

164,000(47.9)

188,000(55.3)

243,000(71.3)

273,000(79.9)

298,000(87.3)

Control Valve solenoid solenoid solenoid solenoid solenoid solenoid solenoid solenoid solenoidPHYSICAL DATA

Weight -- lbs (kg) 1,000(454)

1,050(477)

1,800(818)

1,850(841)

1,900(863)

1,950(886)

2,650(1,204)

2,700(1,227)

2,750(1,250)

Height -- Inches (mm) 76.0(1,930)

76.0(1,930)

76.0(1,930)

76.0(1,930)

76.0(1,930)

76.0(1,930)

76.0(1,930)

76.0(1,930)

76.0(1,930)

Length -- Inches (mm) 34.4(873)

34.4(873)

66.4(1,685)

66.4(1,685)

66.4(1,685)

66.4(1,685)

98.3(2,997)

98.3(2,997)

98.3(2,997)

Depth -- Inches (mm) 34.4(873)

34.4(873)

34.4(873)

34.4(873)

34.4(873)

34.4(873)

34.4(873)

34.4(873)

34.4(873)

CONNECTION SIZES****Glycol In/Out -- Inches OD 1-3/8 1-3/8 1-3/8 1-5/8 1-5/8 1-5/8 1-5/8 2-1/8 2-1/8Hot Water

Supply Line -- Inches OD 5/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8Return Line -- Inches OD 5/8 5/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8

SteamSupply Line -- Inches OD 5/8 5/8 5/8 5/8 5/8 5/8 7/8 7/8 7/8

HumidifierSupply Line -- Inches OD 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4

Condensate DrainDrain Line -- Inches ID 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8

*2-Way Single Seated, 400 psig W.W.P. max**3-Way Single Seated, 400 psig W.W.P. max***With equal loading on each phase, rated at 208-230V / 3-phase, 480V / 3-phase and 600V / 3-phase****Connections sizes, not recommended piping sizes

12 APC NetworkAIR™ AFX

Electrical Data

AIR COOLED - Standard 3HPREHEAT Electric Hot Gas, Steam, Hot Water

or None Electric Hot Gas,Steam, Hot Water or None

HUMIDIFIER Electrode Canister - Steam Electrode Canister - Steam Steam or None Steam or NoneVOLTAGE 208 230 480 600 208 230 480 600 208 230 480 600 208 230 480 600

20 kW (6 ton)FLA 42.4 42.4 21.1 17.5 42.4 40.0 19.9 16.0 41.6 42.4 21.1 17.5 26.0 25.2 12.5 10.0

WSA 55.2 55.4 27.3 22.8 55.2 52.4 25.8 21.0 55.2 55.4 27.3 22.8 34.7 33.9 16.5 13.5MOP 70.0 70.0 35.0 30.0 70.0 60.0 30.0 25.0 70.0 70.0 35.0 25.0 50.0 50.0 25.0 20.0

27 kW (8 ton)FLA 51.1 51.1 25.5 21.0 51.1 48.7 24.3 19.5 50.3 51.1 25.5 21.0 34.7 33.9 16.9 13.5

WSA 71.3 71.5 36.4 29.5 71.3 68.5 34.9 27.6 70.3 71.5 36.4 29.5 50.8 50.0 25.6 20.1MOP 100.0 100.0 50.0 45.0 100.0 90.0 50.0 35.0 100.0 100.0 50.0 45.0 80.0 80.0 40.0 30.0

34 kW (10 ton)FLA 64.5 64.5 31.9 26.7 61.1 57.9 28.7 22.9 62.0 63.6 31.5 26.3 44.7 43.1 21.3 16.9

WSA 81.5 83.1 42.0 35.0 81.5 77.9 39.8 31.6 80.7 83.1 42.0 35.0 61.0 59.4 30.5 24.1MOP 90.0 90.0 45.0 35.0 90.0 90.0 45.0 35.0 90.0 90.0 45.0 35.0 80.0 70.0 40.0 30.0

41 kW (12 ton)FLA 66.9 66.5 32.3 26.7 66.9 63.7 30.3 23.5 64.9 66.5 32.3 26.6 50.5 48.9 22.9 17.5

WSA 84.7 84.9 42.0 35.4 84.7 81.1 39.8 32.4 82.5 84.9 42.0 35.4 64.2 62.6 30.5 24.9MOP 100.0 90.0 45.0 35.0 100.0 90.0 45.0 35.0 90.0 90.0 45.0 35.0 100.0 80.0 40.0 30.0

48 kW (14 ton)FLA 68.4 67.4 33.5 28.0 68.4 65.2 32.4 26.0 65.8 67.4 33.5 28.0 52.0 50.4 25.0 20.0

WSA 84.7 84.9 42.0 35.4 84.7 81.1 39.8 32.4 82.5 84.9 42.0 35.4 64.2 62.6 30.5 24.9MOP 100.0 90.0 45.0 35.0 100.0 90.0 45.0 35.0 90.0 90.0 45.0 35.0 80.0 80.0 40.0 30.0

62 kW (18 ton)FLA 85.7 82.5 41.1 32.9 85.7 82.5 41.1 32.9 74.5 76.1 37.9 31.5 69.3 67.7 33.7 26.9

WSA 113.7 110.1 56.2 44.3 113.7 110.1 56.2 44.3 98.6 101.0 51.1 42.0 93.2 91.6 46.9 36.8MOP 125.0 125.0 70.0 50.0 125.0 125.0 70.0 50.0 125.0 125.0 60.0 50.0 125.0 125.0 60.0 50.0

70 kW (20 ton)FLA 104.8 105.0 52.2 43.5 104.8 100.4 49.9 39.9 102.6 105.0 52.2 43.5 85.8 83.4 41.4 33.0

WSA 144.7 141.0 68.3 55.0 144.7 139.8 65.8 49.3 137.4 141.0 68.3 55.0 120.9 118.5 55.2 40.7MOP 175.0 175.0 80.0 60.0 175.0 175.0 80.0 80.0 150.0 150.0 80.0 60.0 150.0 150.0 70.0 50.0

90 kW (26 ton)FLA 118.9 108.6 54.2 45.1 118.9 107.4 53.6 42.8 109.7 108.6 54.2 45.1 99.9 90.4 45.1 35.9

WSA 156.1 151.2 68.8 57.5 156.1 151.2 66.7 53.8 143.8 147.4 68.8 57.5 132.4 130.0 56.1 45.2MOP 175.0 175.0 80.0 60.0 175.0 175.0 80.0 80.0 175.0 175.0 80.0 60.0 175.0 175.0 70.0 60.0

98 kW (28 ton)FLA 115.2 107.1 53.5 44.7 115.2 104.1 52.0 41.7 108.1 107.1 53.5 44.7 96.2 87.1 43.5 34.8

WSA 156.1 151.2 78.9 63.0 156.1 151.2 78.9 63.0 143.8 147.4 75.5 62.6 132.4 130.0 68.3 54.4MOP 175.0 175.0 100.0 80.0 175.0 175.0 100.0 100.0 175.0 175.0 90.0 70.0 175.0 175.0 90.0 70.0

FLA = Full Load AmpsWSA = Wire Size AmpsMOP = Maximum Overcurrent Protection

APC NetworkAIR™ AFX 13

Electrical Data

WATER COOLED - Standard 3HPREHEAT Electric Hot Gas,Steam, Hot Water

or None Electric Hot Gas,Steam, Hot Water or None

HUMIDIFIER Electrode Canister - Steam Electrode Canister - Steam Steam or None Steam or NoneVOLTAGE 208 230 480 600 208 230 480 600 208 230 480 600 208 230 480 600

20 kW (6 ton)FLA 40.1 40.1 20.0 16.5 40.1 37.7 18.8 15.0 39.3 40.1 20.0 16.5 23.7 22.9 11.4 9.0

WSA 55.2 55.4 27.3 22.8 55.2 52.4 25.8 21.0 55.2 55.4 27.3 22.8 34.7 33.9 16.5 13.5MOP 70.0 70.0 35.0 30.0 70.0 60.0 30.0 25.0 70.0 70.0 35.0 25.0 50.0 50.0 25.0 20.0

27 kW (8 ton)FLA 47.9 47.9 23.9 19.7 47.9 45.5 22.7 18.2 47.1 47.9 23.9 19.7 31.5 30.7 15.3 12.2

WSA 71.3 71.5 36.4 29.5 71.3 68.5 34.9 27.6 70.3 71.5 36.4 29.5 50.8 50.0 25.6 20.1MOP 100.0 100.0 50.0 45.0 100.0 90.0 50.0 35.0 100.0 100.0 50.0 45.0 80.0 80.0 40.0 30.0

34 kW (10 ton)FLA 64.5 64.5 31.9 26.7 56.5 53.3 26.3 21.1 59.7 61.3 30.3 25.4 40.1 38.5 18.9 15.1

WSA 81.5 83.1 42.0 35.0 81.5 77.9 39.8 31.6 80.7 83.1 42.0 35.0 61.0 59.4 30.5 24.1MOP 90.0 90.0 45.0 35.0 90.0 90.0 45.0 35.0 90.0 90.0 45.0 35.0 80.0 70.0 40.0 30.0

41 kW (12 ton)FLA 64.5 64.5 31.9 26.7 62.7 59.5 27.9 21.7 62.8 64.4 31.1 25.7 46.3 44.7 20.5 15.7

WSA 84.7 84.9 42.0 35.4 84.7 81.1 39.8 32.4 82.5 84.9 42.0 35.4 64.2 62.6 30.5 24.9MOP 100.0 90.0 45.0 35.0 100.0 90.0 45.0 35.0 90.0 90.0 45.0 35.0 100.0 80.0 40.0 30.0

48 kW (14 ton)FLA 64.8 65.1 32.4 27.0 63.8 60.6 30.2 24.0 63.5 65.1 32.4 27.0 47.4 45.8 22.8 18.0

WSA 84.7 84.9 42.0 35.4 84.7 81.1 39.8 32.4 82.5 84.9 42.0 35.4 64.2 62.6 30.5 24.9MOP 100.0 90.0 45.0 35.0 100.0 90.0 45.0 35.0 90.0 90.0 45.0 35.0 80.0 80.0 40.0 30.0

62 kW (18 ton)FLA 79.3 76.1 37.9 30.3 79.3 76.1 37.9 30.3 71.3 72.9 36.3 30.2 62.9 61.3 30.5 24.3

WSA 113.7 110.1 56.2 44.3 113.7 110.1 56.2 44.3 98.6 101.0 51.1 42.0 93.2 91.6 46.9 36.8MOP 125.0 125.0 70.0 50.0 125.0 125.0 70.0 50.0 125.0 125.0 60.0 50.0 125.0 125.0 60.0 50.0

70 kW (20 ton)FLA 98.6 101.0 50.2 41.9 96.8 92.4 45.9 36.7 98.6 101.0 50.2 41.9 77.8 75.4 37.4 29.8

WSA 144.7 141.0 68.3 55.0 144.7 139.8 65.8 49.3 137.4 141.0 68.3 55.0 120.9 118.5 55.2 40.7MOP 175.0 175.0 80.0 60.0 175.0 175.0 80.0 80.0 150.0 150.0 80.0 60.0 150.0 150.0 70.0 50.0

90 kW (26 ton)FLA 110.5 104.8 52.3 43.6 110.5 99.8 49.8 39.8 105.5 104.8 52.3 43.6 91.5 82.8 41.3 32.9

WSA 156.1 151.2 68.8 57.5 156.1 151.2 66.7 53.8 143.8 147.4 68.8 57.5 132.4 130.0 56.1 45.2MOP 175.0 175.0 80.0 60.0 175.0 175.0 80.0 80.0 175.0 175.0 80.0 60.0 175.0 175.0 70.0 60.0

98 kW (28 ton)FLA 107.7 103.7 51.8 43.3 107.7 97.3 48.6 39.0 104.3 103.7 51.8 43.3 88.7 80.3 40.1 32.1

WSA 156.1 151.2 78.9 63.0 156.1 151.2 78.9 63.0 143.8 147.4 75.5 62.6 132.4 130.0 68.3 54.4MOP 175.0 175.0 100.0 80.0 175.0 175.0 100.0 100.0 175.0 175.0 90.0 70.0 175.0 175.0 90.0 70.0

FLA = Full Load AmpsWSA = Wire Size AmpsMOP = Maximum Overcurrent Protection

14 APC NetworkAIR™ AFX

Electrical Data

GLYCOL COOLED - Standard 3HPREHEAT Electric Hot Gas,Steam, Hot Water

or None Electric Hot Gas,Steam, Hot Water or None

HUMIDIFIER Electrode Canister - Steam Electrode Canister - Steam Steam or None Steam or NoneVOLTAGE 208 230 480 600 208 230 480 600 208 230 480 600 208 230 480 600

20 kW (6 ton)FLA 43.9 43.9 21.9 18.1 43.9 41.5 20.7 16.6 43.1 43.9 21.9 18.1 27.5 26.7 13.3 10.6

WSA 55.2 55.4 27.3 22.8 55.2 52.4 25.8 21.0 55.2 55.4 27.3 22.8 34.7 33.9 16.5 13.5MOP 70.0 70.0 35.0 30.0 70.0 60.0 30.0 25.0 70.0 70.0 35.0 25.0 50.0 50.0 25.0 20.0

27 kW (8 ton)FLA 53.2 53.2 27.0 21.8 53.2 50.8 25.8 20.3 52.4 53.2 27.0 21.8 36.8 36.0 18.4 14.3

WSA 71.3 71.5 36.4 29.5 71.3 68.5 34.9 27.6 70.3 71.5 36.4 29.5 50.8 50.0 25.6 20.1MOP 100.0 100.0 50.0 45.0 100.0 90.0 50.0 35.0 100.0 100.0 50.0 45.0 80.0 80.0 40.0 30.0

34 kW (10 ton)FLA 64.5 65.1 32.2 26.9 64.1 60.9 30.1 24.1 63.5 65.1 32.2 26.9 47.7 46.1 22.7 18.1

WSA 81.5 83.1 42.0 35.0 81.5 77.9 39.8 31.6 80.7 83.1 42.0 35.0 61.0 59.4 30.5 24.1MOP 90.0 90.0 45.0 35.0 90.0 90.0 45.0 35.0 90.0 90.0 45.0 35.0 80.0 70.0 40.0 30.0

41 kW (12 ton)FLA 69.7 67.9 33.1 27.2 69.7 66.5 31.9 24.7 66.3 67.9 33.1 27.2 53.3 51.7 24.5 18.7

WSA 84.7 84.9 42.0 35.4 84.7 81.1 39.8 32.4 82.5 84.9 42.0 35.4 64.2 62.6 30.5 24.9MOP 100.0 90.0 45.0 35.0 100.0 90.0 45.0 35.0 90.0 90.0 45.0 35.0 100.0 80.0 40.0 30.0

48 kW (14 ton)FLA 71.4 68.9 34.3 28.6 71.4 68.2 34.0 27.2 67.3 68.9 34.3 28.6 55.0 53.4 26.6 21.2

WSA 84.7 84.9 42.0 35.4 84.7 81.1 39.8 32.4 82.5 84.9 42.0 35.4 64.2 62.6 30.5 24.9MOP 100.0 90.0 45.0 35.0 100.0 90.0 45.0 35.0 90.0 90.0 45.0 35.0 80.0 80.0 40.0 30.0

62 kW (18 ton)FLA 89.9 86.7 44.1 34.5 89.9 86.7 44.1 34.5 76.6 78.2 39.4 32.3 73.5 71.9 36.7 28.5

WSA 113.7 110.1 56.2 44.3 113.7 110.1 56.2 44.3 98.6 101.0 51.1 42.0 93.2 91.6 46.9 36.8MOP 125.0 125.0 70.0 50.0 125.0 125.0 70.0 50.0 125.0 125.0 60.0 50.0 125.0 125.0 60.0 50.0

70 kW (20 ton)FLA 110.0 107.6 53.5 44.5 110.0 105.6 52.5 41.9 105.2 107.6 53.5 44.5 91.0 88.6 44.0 35.0

WSA 144.7 141.0 68.3 55.0 144.7 139.8 65.8 49.3 137.4 141.0 68.3 55.0 120.9 118.5 55.2 40.7MOP 175.0 175.0 80.0 60.0 175.0 175.0 80.0 80.0 150.0 150.0 80.0 60.0 150.0 150.0 70.0 50.0

90 kW (26 ton)FLA 122.4 110.6 55.2 45.7 122.4 110.6 55.2 44.1 111.5 110.2 55.0 45.7 103.4 93.6 46.7 37.2

WSA 156.1 151.2 68.8 57.5 156.1 151.2 66.7 53.8 143.8 147.4 68.8 57.5 132.4 130.0 56.1 45.2MOP 175.0 175.0 80.0 60.0 175.0 175.0 80.0 80.0 175.0 175.0 80.0 60.0 175.0 175.0 70.0 60.0

98 kW (28 ton)FLA 117.9 108.3 54.1 45.1 117.9 106.5 53.2 42.7 109.4 108.3 54.1 45.1 98.9 89.5 44.7 35.8

WSA 156.1 151.2 78.9 63.0 156.1 151.2 78.9 63.0 143.8 147.4 75.5 62.6 132.4 130.0 68.3 54.4MOP 175.0 175.0 100.0 80.0 175.0 175.0 100.0 100.0 175.0 175.0 90.0 70.0 175.0 175.0 90.0 70.0

FLA = Full Load AmpsWSA = Wire Size AmpsMOP = Maximum Overcurrent Protection

APC NetworkAIR™ AFX 15

Electrical Data

AIR COOLED - Optional 5HPREHEAT Electric Hot Gas,Steam, Hot Water

or None Electric Hot Gas,Steam, Hot Water or None

HUMIDIFIER Electrode Canister - Steam Electrode Canister - Steam Steam or None Steam or NoneVOLTAGE 208 230 480 600 208 230 480 600 208 230 480 600 208 230 480 600

20 kW (6 ton)FLA 48.4 48.4 24.1 19.9 48.4 46.0 22.9 18.4 27.6 48.4 24.1 19.9 32.0 31.2 15.5 12.4

WSA 61.2 61.4 30.3 25.2 61.2 58.4 28.8 23.4 60.2 61.4 30.3 25.2 40.7 39.9 19.5 15.9MOP 70.0 70.0 35.0 40.0 70.0 70.0 35.0 30.0 70.0 70.0 35.0 30.0 60.0 60.0 25.0 20.0

27 kW (8 ton)FLA 57.1 57.1 28.5 23.4 57.1 54.7 27.3 21.9 56.3 57.1 28.5 23.4 40.7 39.9 19.9 15.9

WSA 77.3 77.5 39.4 31.9 77.3 74.5 37.9 30.0 76.3 77.5 39.4 31.9 56.8 56.0 28.6 22.5MOP 100.0 100.0 50.0 50.0 100.0 100.0 50.0 40.0 100.0 100.0 50.0 40.0 90.0 80.0 45.0 35.0

34 kW (10 ton)FLA 76.5 76.5 37.9 31.5 73.1 69.9 34.7 27.7 74.0 75.6 37.5 31.1 56.7 55.1 27.3 21.7

WSA 93.5 95.1 48.0 39.8 93.5 89.9 45.8 36.4 92.7 95.1 48.0 39.8 73.0 71.4 36.5 28.9MOP 100.0 100.0 50.0 40.0 100.0 100.0 50.0 40.0 100.0 100.0 50.0 40.0 90.0 90.0 45.0 35.0

41 kW (12 ton)FLA 78.9 78.5 38.3 31.5 78.9 75.7 36.3 28.3 76.9 78.5 38.3 31.4 62.5 60.9 28.9 22.3

WSA 96.7 96.9 48.0 40.2 96.7 93.1 45.8 37.2 94.5 96.9 48.0 40.2 76.2 74.6 36.5 29.7MOP 100.0 100.0 50.0 40.0 100.0 100.0 50.0 40.0 100.0 100.0 50.0 40.0 90.0 90.0 45.0 35.0

48 kW (14 ton)FLA 80.4 79.4 39.5 32.8 80.4 77.2 38.4 30.8 77.8 79.4 39.5 32.8 64.0 62.4 31.0 24.8

WSA 96.7 96.9 48.0 40.2 96.7 93.1 45.8 37.2 94.5 96.9 48.0 40.2 76.2 74.6 36.5 29.7MOP 100.0 100.0 50.0 40.0 100.0 100.0 50.0 40.0 100.0 100.0 50.0 40.0 90.0 90.0 45.0 35.0

62 kW (18 ton)FLA 97.7 94.5 47.1 37.7 97.7 94.5 47.1 37.7 86.5 88.1 43.9 36.3 81.3 79.7 39.7 31.7

WSA 125.7 122.1 62.2 49.1 125.7 122.1 62.2 49.1 110.6 113.0 57.1 46.8 105.2 103.6 52.9 41.6MOP 150.0 150.0 70.0 60.0 150.0 150.0 70.0 60.0 125.0 125.0 70.0 50.0 125.0 125.0 70.0 50.0

70 kW (20 ton)FLA 122.8 123.0 61.2 50.7 122.8 118.4 58.9 47.1 120.6 123.0 61.2 50.7 103.8 101.4 50.4 40.2

WSA 162.7 159.0 77.3 62.2 162.7 157.8 74.8 56.5 155.4 159.0 77.3 62.2 138.9 136.5 64.2 47.9MOP 175.0 175.0 90.0 70.0 175.0 175.0 90.0 90.0 175.0 175.0 90.0 70.0 175.0 175.0 80.0 60.0

90 kW (26 ton)FLA 136.9 126.6 54.2 52.3 136.9 125.4 53.6 50.0 127.7 126.6 54.2 52.3 117.9 108.4 45.1 43.1

WSA 174.1 169.2 77.8 64.7 174.1 169.2 75.7 61.0 161.8 165.4 77.8 64.7 150.4 148.0 65.1 52.4MOP 200.0 200.0 90.0 70.0 200.0 200.0 90.0 90.0 175.0 175.0 90.0 70.0 175.0 175.0 80.0 60.0

98 kW (28 ton)FLA 133.2 125.1 62.5 51.9 133.2 122.1 61.0 48.9 126.1 125.1 62.5 51.9 114.2 105.1 52.5 42.0

WSA 174.1 169.2 87.9 70.2 174.1 169.2 87.9 70.2 161.8 165.4 84.5 69.8 150.4 148.0 77.3 61.6MOP 200.0 200.0 100.0 80.0 200.0 200.0 100.0 100.0 175.0 175.0 100.0 80.0 175.0 175.0 100.0 80.0

FLA = Full Load AmpsWSA = Wire Size AmpsMOP = Maximum Overcurrent Protection

16 APC NetworkAIR™ AFX

Electrical Data

WATER COOLED - Optional 5HPREHEAT Electric Hot Gas,Steam, Hot Water

or None Electric Hot Gas,Steam, Hot Water or None

HUMIDIFIER Electrode Canister - Steam Electrode Canister - Steam Steam or None Steam or NoneVOLTAGE 208 230 480 600 208 230 480 600 208 230 480 600 208 230 480 600

20 kW (6 ton)FLA 46.1 46.1 23.0 18.9 46.1 43.7 21.8 17.4 45.3 46.1 23.0 18.9 29.7 28.9 14.4 11.4

WSA 61.2 61.4 30.3 25.2 61.2 58.4 28.8 23.4 60.2 61.4 30.3 25.2 40.7 39.9 19.5 15.9MOP 70.0 70.0 35.0 40.0 70.0 70.0 35.0 30.0 70.0 70.0 35.0 30.0 60.0 60.0 25.0 20.0

27 kW (8 ton)FLA 53.9 53.9 26.9 22.1 53.9 51.5 25.7 20.6 53.1 53.9 26.9 22.1 37.5 36.0 18.3 14.6

WSA 77.3 77.5 39.4 31.9 77.3 74.5 37.9 30.0 76.3 77.5 39.4 31.9 56.8 56.0 28.6 22.5MOP 100.0 100.0 50.0 50.0 100.0 100.0 50.0 40.0 100.0 100.0 50.0 40.0 90.0 80.0 45.0 35.0

34 kW (10 ton)FLA 76.5 76.5 37.9 31.5 68.5 65.3 32.3 25.9 71.7 73.3 36.3 30.2 52.1 50.5 24.9 19.9

WSA 93.5 95.1 48.0 39.8 93.5 89.9 45.8 36.4 92.7 95.1 48.0 39.8 73.0 71.4 36.5 28.9MOP 100.0 100.0 50.0 40.0 100.0 100.0 50.0 40.0 100.0 100.0 50.0 40.0 90.0 90.0 45.0 35.0

41 kW (12 ton)FLA 76.5 76.5 37.9 31.5 74.7 71.5 33.9 26.5 74.8 76.4 37.1 30.5 58.3 56.7 26.5 20.5

WSA 96.7 96.9 48.0 40.2 96.7 93.1 45.8 37.2 94.5 96.9 48.0 40.2 76.2 74.6 36.5 29.7MOP 100.0 100.0 50.0 40.0 100.0 100.0 50.0 40.0 100.0 100.0 50.0 40.0 90.0 90.0 45.0 35.0

48 kW (14 ton)FLA 76.8 77.1 38.4 31.8 75.8 72.6 36.2 28.8 75.5 77.1 38.4 31.8 59.4 57.8 28.8 22.8

WSA 96.7 96.9 48.0 40.2 96.7 93.1 45.8 37.2 94.5 96.9 48.0 40.2 76.2 74.6 36.5 29.7MOP 100.0 100.0 50.0 40.0 100.0 100.0 50.0 40.0 100.0 100.0 50.0 40.0 90.0 90.0 45.0 35.0

62 kW (18 ton)FLA 91.3 88.1 43.9 35.1 91.3 88.1 43.9 35.1 83.3 84.9 42.3 35.0 74.9 73.3 36.5 29.1

WSA 125.7 122.1 62.2 49.1 125.7 122.1 62.2 49.1 110.6 113.0 57.1 46.8 105.2 103.6 52.9 41.6MOP 150.0 150.0 70.0 60.0 150.0 150.0 70.0 60.0 125.0 125.0 70.0 50.0 125.0 125.0 70.0 50.0

70 kW (20 ton)FLA 116.6 119.0 59.2 49.1 114.8 110.4 54.9 43.9 116.6 119.0 59.2 49.1 95.8 93.4 46.4 37.0

WSA 162.7 159.0 77.3 62.2 162.7 157.8 74.8 56.5 155.4 159.0 77.3 62.2 138.9 136.5 64.2 47.9MOP 175.0 175.0 90.0 70.0 175.0 175.0 90.0 90.0 175.0 175.0 90.0 70.0 175.0 175.0 80.0 60.0

90 kW (26 ton)FLA 128.5 122.8 52.3 50.8 128.5 117.8 49.8 47.0 123.5 122.8 52.3 50.8 109.5 100.8 41.3 40.1

WSA 174.1 169.2 77.8 64.7 174.1 169.2 75.7 61.0 161.8 165.4 77.8 64.7 150.4 148.0 65.1 52.4MOP 200.0 200.0 90.0 70.0 200.0 200.0 90.0 90.0 175.0 175.0 90.0 70.0 175.0 175.0 80.0 60.0

98 kW (28 ton)FLA 125.7 121.7 60.8 50.5 125.7 115.3 57.6 46.2 122.3 121.7 60.8 50.5 106.7 98.3 49.1 39.3

WSA 174.1 169.2 87.9 70.2 174.1 169.2 87.9 70.2 161.8 165.4 84.5 69.8 150.4 148.0 77.3 61.6MOP 200.0 200.0 100.0 80.0 200.0 200.0 100.0 100.0 175.0 175.0 100.0 80.0 175.0 175.0 100.0 80.0

FLA = Full Load AmpsWSA = Wire Size AmpsMOP = Maximum Overcurrent Protection

APC NetworkAIR™ AFX 17

Electrical Data

GLYCOL COOLED - Optional 5HPREHEAT Electric Hot Gas,Steam, Hot Water

or None Electric Hot Gas,Steam, Hot Water or None

HUMIDIFIER Electrode Canister - Steam Electrode Canister - Steam Steam or None Steam or NoneVOLTAGE 208 230 480 600 208 230 480 600 208 230 480 600 208 230 480 600

20 kW (6 ton)FLA 49.9 49.9 24.9 20.5 49.9 47.5 23.7 19.0 49.1 49.9 24.9 20.5 33.5 32.7 16.3 13.0

WSA 61.2 61.4 30.3 25.2 61.2 58.4 28.8 23.4 60.2 61.4 30.3 25.2 40.7 39.9 19.5 15.9MOP 70.0 70.0 35.0 40.0 70.0 70.0 35.0 30.0 70.0 70.0 35.0 30.0 60.0 60.0 25.0 20.0

27 kW (8 ton)FLA 59.2 59.2 30.0 24.2 59.2 56.8 28.8 22.7 58.4 59.2 30.0 24.2 42.8 42.0 21.4 16.7

WSA 77.3 77.5 39.4 31.9 77.3 74.5 37.9 30.0 76.3 77.5 39.4 31.9 56.8 56.0 28.6 22.5MOP 100.0 100.0 50.0 50.0 100.0 100.0 50.0 40.0 100.0 100.0 50.0 40.0 90.0 80.0 45.0 35.0

34 kW (10 ton)FLA 76.5 77.1 38.2 31.7 76.1 72.9 36.1 28.9 75.5 77.1 38.2 31.7 59.7 58.1 28.7 22.9

WSA 93.5 95.1 48.0 39.8 93.5 89.9 45.8 36.4 92.7 95.1 48.0 39.8 73.0 71.4 36.5 28.9MOP 100.0 100.0 50.0 40.0 100.0 100.0 50.0 40.0 100.0 100.0 50.0 40.0 90.0 90.0 45.0 35.0

41 kW (12 ton)FLA 81.7 79.9 39.1 32.0 81.7 78.5 37.9 29.5 78.3 79.9 39.1 32.0 65.3 63.7 30.5 23.5

WSA 96.7 96.9 48.0 40.2 96.7 93.1 45.8 37.2 94.5 96.9 48.0 40.2 76.2 74.6 36.5 29.7MOP 100.0 100.0 50.0 40.0 100.0 100.0 50.0 40.0 100.0 100.0 50.0 40.0 90.0 90.0 45.0 35.0

48 kW (14 ton)FLA 83.4 80.9 40.3 33.4 83.4 80.2 40.0 32.0 79.3 80.9 40.3 33.4 67.0 65.4 32.6 26.0

WSA 96.7 96.9 48.0 40.2 96.7 93.1 45.8 37.2 94.5 96.9 48.0 40.2 76.2 74.6 36.5 29.7MOP 100.0 100.0 50.0 40.0 100.0 100.0 50.0 40.0 100.0 100.0 50.0 40.0 90.0 90.0 45.0 35.0

62 kW (18 ton)FLA 101.9 98.7 50.1 39.3 101.9 98.7 50.1 39.3 88.6 90.2 45.4 37.1 85.5 83.9 42.7 33.3

WSA 125.7 122.1 62.2 49.1 125.7 122.1 62.2 49.1 110.6 113.0 57.1 46.8 105.2 103.6 52.9 41.6MOP 150.0 150.0 70.0 60.0 150.0 150.0 70.0 60.0 125.0 125.0 70.0 50.0 125.0 125.0 70.0 50.0

70 kW (20 ton)FLA 128.0 125.6 62.5 51.7 128.0 123.6 61.5 49.1 123.2 125.6 62.5 51.7 109.0 106.6 53.0 42.2

WSA 162.7 159.0 77.3 62.2 162.7 157.8 74.8 56.5 155.4 159.0 77.3 62.2 138.9 136.5 64.2 47.9MOP 175.0 175.0 90.0 70.0 175.0 175.0 90.0 90.0 175.0 175.0 90.0 70.0 175.0 175.0 80.0 60.0

90 kW (26 ton)FLA 140.4 128.6 55.2 52.9 140.4 128.6 55.2 51.3 129.5 128.2 55.0 52.9 121.4 111.6 46.7 44.4

WSA 174.1 169.2 77.8 64.7 174.1 169.2 75.7 61.0 161.8 165.4 77.8 64.7 150.4 148.0 65.1 52.4MOP 200.0 200.0 90.0 70.0 200.0 200.0 90.0 90.0 175.0 175.0 90.0 70.0 175.0 175.0 80.0 60.0

98 kW (28 ton)FLA 135.9 126.3 63.1 52.3 135.9 124.5 62.2 49.9 127.4 126.3 63.1 52.3 116.9 107.5 53.7 43.0

WSA 174.1 169.2 87.9 70.2 174.1 169.2 87.9 70.2 161.8 165.4 84.5 69.8 150.4 148.0 77.3 61.6MOP 200.0 200.0 100.0 80.0 200.0 200.0 100.0 100.0 175.0 175.0 100.0 80.0 175.0 175.0 100.0 80.0

FLA = Full Load AmpsWSA = Wire Size AmpsMOP = Maximum Overcurrent Protection

18 APC NetworkAIR™ AFX

Dimensional DataDownflow - 20-27kW (6-8 ton)

* All dimensions are in inches (mm).

APC NetworkAIR™ AFX 19

Dimensional Data

Downflow - 34-62kW (10-18 ton)

* All dimensions are in inches (mm).

20 APC NetworkAIR™ AFX

Dimensional Data

Downflow - 70-98kW (20-28 ton)

* All dimensions are in inches (mm).

APC NetworkAIR™ AFX 21

Dimensional Data

Upflow front return - 20-27kW (6-8 ton)

* All dimensions are in inches (mm).

22 APC NetworkAIR™ AFX

Dimensional Data

Upflow front return - 34-62kW (10-18 ton)

* All dimensions are in inches (mm).

APC NetworkAIR™ AFX 23

Dimensional Data

Upflow front return- 70-98kW (20-28 ton)

* All dimensions are in inches (mm).

24 APC NetworkAIR™ AFX

Dimensional Data

Upflow rear return - 20-27kW (6-8 ton)

* All dimensions are in inches (mm).

APC NetworkAIR™ AFX 25

Dimensional Data

Upflow rear return - 34-62kW (10-18 ton)

* All dimensions are in inches (mm).

26 APC NetworkAIR™ AFX

Dimensional Data

Upflow rear return - 70-98kW (20-28 ton)

* All dimensions are in inches (mm).

APC NetworkAIR™ AFX 27

Air-Cooled Condensers

Air-cooled condenser—performance/electrical data

OHE SKU Voltage

Ambient Temperature Air Quantity # of

Circuits

Fan/Motor Connection Weight Electrical Data

95F 105F 115F CFM L/s Qty. HP RPM Hot Gas Liquid Lbs Kg FLA MCA MOP

ACCD75018 208-230/1/60 20kW 20kW N/A 6,450 3,044 1 1 1/2 1075 1-1/8 7/8 260 118 3.9 4.9 15.0ACCD75019 480/1/60 20kW 20kW N/A 6,450 3,044 1 1 1/2 1075 1-1/8 7/8 260 118 2.0 2.4 15.0ACCD75022 208-230/3/60 27kW 27kW 20kW 10,10 4,766 1 2 1/3 1140 1-1/8 7/8 450 204 5.2 5.9 15.0ACCD75023 480/3/60 27kW 27kW 20kW 10,10 4,766 1 2 1/3 1140 1-1/8 7/8 450 204 2.6 2.9 15.0ACCD75150 600/3/60 27kW 27kW 20kW 10,10 4,766 1 2 1/3 1140 1-1/8 7/8 450 204 2.1 2.4 15.0ACCD75026 208-230/3/60 N/A N/A 27kW 12,40 5,852 1 2 1/3 1140 1-1/8 7/8 470 213 5.2 5.9 15.0ACCD75027 480/3/60 N/A N/A 27kW 12,40 5,852 1 2 1/3 1140 1-1/8 7/8 470 213 2.6 2.9 15.0ACCD75152 600/3/60 N/A N/A 27kW 12,40 5,852 1 2 1/3 1140 1-1/8 7/8 470 213 2.1 2.4 15.0ACCD75076 208-230/3/60 34kW 34kW N/A 12,40 5,852 2 2 1/3 1140 1-1/8 7/8 470 213 5.2 5.9 15.0ACCD75077 480/3/60 34kW 34kW N/A 12,40 5,852 2 2 1/3 1140 1-1/8 7/8 470 213 2.6 2.9 15.0ACCD75153 600/3/60 34kW 34kW N/A 12,40 5,852 2 2 1/3 1140 1-1/8 7/8 470 213 2.1 2.4 15.0ACCD75080 208-230/3/60 41kW 41kW 34kW 13,70 6,465 2 2 1/3 1140 1-1/8 7/8 510 231 5.2 5.9 15.0ACCD75081 480/3/60 41kW 41kW 34kW 13,70 6,465 2 2 1/3 1140 1-1/8 7/8 510 231 2.6 2.9 15.0ACCD75155 600/3/60 41kW 41kW 34kW 13,70 6,465 2 2 1/3 1140 1-1/8 7/8 510 231 2.1 2.4 15.0ACCD75084 208-230/3/60 48kW 48kW 41kW 12,90 6,088 2 2 1/3 1140 1-3/8 1-1/8 530 240 5.2 5.9 15.0ACCD75085 480/3/60 48kW 48kW 41kW 12,90 6,088 2 2 1/3 1140 1-3/8 1-1/8 530 240 2.6 2.9 15.0ACCD75157 600/3/60 48kW 48kW 41kW 12,90 6,088 2 2 1/3 1140 1-3/8 1-1/8 530 240 2.1 2.4 15.0ACCD75088 208-230/3/60 62kW 62kW 48kW 20,50 9,674 2 3 1/3 1140 1-3/8 1-1/8 550 249 7.8 8.5 15.0ACCD75089 480/3/60 62kW 62kW 48kW 20,50 9,674 2 3 1/3 1140 1-3/8 1-1/8 550 249 3.9 4.2 15.0ACCD75159 600/3/60 62kW 62kW 48kW 20,50 9,674 2 3 1/3 1140 1-3/8 1-1/8 550 249 3.1 3.4 15.0ACCD75092 208-230/3/60 70kW 70kW 62kW 19,90 9,391 2 3 1/3 1140 1-3/8 1-1/8 580 263 7.8 8.5 20.0ACCD75093 480/3/60 70kW 70kW 62kW 19,90 9,391 2 3 1/3 1140 1-3/8 1-1/8 580 263 3.9 4.2 15.0ACCD75161 600/3/60 70kW 70kW 62kW 19,90 9,391 2 3 1/3 1140 1-3/8 1-1/8 580 263 3.1 3.4 15.0ACCD75096 208-230/3/60 90kW 90kW 70kW 20,70 9,768 2 3 1-1/2 1140 1-5/8 1-5/8 880 400 14.0 15.8 20.0ACCD75097 480/3/60 90kW 90kW 70kW 20,70 9,768 2 3 1-1/2 1140 1-5/8 1-5/8 880 400 7.0 7.9 15.0ACCD75163 600/3/60 90kW 90kW 70kW 20,70 9,768 2 3 1-1/2 1140 1-5/8 1-5/8 880 400 5.6 6.3 15.0ACCD75100 208-230/3/60 98kW 98kW 90kW 34,80 16,42 2 3 1-1/2 1140 2-1/8 2-1/8 1,190 540 21.0 22.8 25.0ACCD75101 480/3/60 98kW 98kW 90kW 34,80 16,42 2 3 1-1/2 1140 2-1/8 2-1/8 1,190 540 10.5 11.4 15.0ACCD75165 600/3/60 98kW 98kW 90kW 34,80 16,42 2 3 1-1/2 1140 2-1/8 2-1/8 1,190 540 8.4 9.1 15.0ACCD75104 208-230/3/60 N/A N/A 98kW 32,90 15,52 2 3 1-1/2 1140 2-1/8 2-1/8 1,210 550 21.0 22.8 25.0ACCD75105 480/3/60 N/A N/A 98kW 32,90 15,52 2 3 1-1/2 1140 2-1/8 2-1/8 1,210 550 10.5 11.4 15.0ACCD75167 600/3/60 N/A N/A 98kW 32,90 15,52 2 3 1-1/2 1140 2-1/8 2-1/8 1,210 550 8.4 9.1 15.0FLA = Full Load AmpsMCA = Minimum Circuit AmperesMOP = Maximum Overcurrent Protection

28 APC NetworkAIR™ AFX

Air-Cooled Condensers

1-fan air-cooled condenser

2-fan air-cooled condenser

APC PART CIRCUIT VOLTAGEACCD75018 single 208-230/1/60ACCD75019 single 480/1/60

APC PART CIRCUIT VOLTAGEACCD75022 single 208-230/3/60ACCD75023 single 480/3/60ACCD75150 single 600/3/60ACCD75026 single 208-230/3/60ACCD75027 single 480/3/60ACCD75152 single 600/3/60ACCD75076 dual 208-230/3/60ACCD75077 dual 480/3/60ACCD75153 dual 600/3/60

APC NetworkAIR™ AFX 29

Air-Cooled Condensers

2-fan air-cooled condenser

3-fan air-cooled condenser

APC PART CIRCUIT VOLTAGEACCD75080 dual 208-230/3/60ACCD75081 dual 480/3/60ACCD75155 dual 600/3/60ACCD75084 dual 208-230/3/60ACCD75085 dual 480/3/60ACCD75157 dual 600/3/60

APC PART CIRCUIT VOLTAGEACCD75088 dual 208-230/3/60ACCD75089 dual 480/3/60ACCD75159 dual 600/3/60ACCD75092 dual 208-230/3/60ACCD75093 dual 480/3/60ACCD75161 dual 600/3/60

30 APC NetworkAIR™ AFX

Air-Cooled Condensers

2-fan air-cooled condenser

3-fan air-cooled condenser

APC PART CIRCUIT VOLTAGEACCD75096 dual 208-230/3/60ACCD75097 dual 480/3/60ACCD75163 dual 600/3/60

APC PART CIRCUIT VOLTAGEACCD75100 dual 208-230/3/60ACCD75101 dual 480/3/60ACCD75165 dual 600/3/60ACCD75104 dual 208-230/3/60ACCD75105 dual 480/3/60ACCD75167 dual 600/3/60

APC NetworkAIR™ AFX 31

G

O

AAAAAAAAA

A

A

A

AAAAAAAAAAAAAAAA

A

A

A

A

A

FMM* g

Fluid Coolers

lycol-cooled fluid cooler—performance/electrical data

HE SKU VoltageAmbient

Temperature

40% Ethylene Glycol@

130FAir Quantity Feeds Fan/Motor Connect

-ionsWeight Glycol

Volume Electrical Data

95F 105F PD(ft) CFM L/s Qty HP RPM Lbs Kg Gal L FLA MCA MOPCFC75116 208-230/3/60 20kW 20kW 25.7@20 10,100 4,766 12 2 1/3 1140 (2) 1-3/8 450 204 4.9 18.1 5.2 5.9 15.0CFC75117 480/3/60 20kW 20kW 25.7@20 10,100 4,766 12 2 1/3 1140 (2) 1-3/8 450 204 4.9 18.1 2.6 2.9 15.0CFC75242 600/3/60 20kW 20kW 25.7@20 10,100 4,766 12 2 1/3 1140 (2) 1-3/8 450 204 4.9 18.1 2.1 2.4 15.0CFC75120 208-230/3/60 27kW N/A 14.7@20 13,700 6,465 16 2 1/3 1140 (2) 1-3/8 420 191 9.1 34.4 5.2 5.9 15.0CFC75121 480/3/60 27kW N/A 14.7@20 13,700 6,465 16 2 1/3 1140 (2) 1-3/8 420 191 9.1 34.4 2.6 2.9 15.0CFC7543 600/3/60 27kW N/A 14.7@20 13,700 6,465 16 2 1/3 1140 (2) 1-3/8 420 191 9.1 34.4 2.1 2.4 15.0CFC75130 208-230/3/60 N/A 27kW 10.2@25 19,900 9,391 24 3 1/3 1140 (2) 1-3/8 580 263 10.2 38.6 7.8 8.5 15.0CFC75131 480/3/60 N/A 27kW 10.2@25 19,900 9,391 24 3 1/3 1140 (2) 1-3/8 580 263 10.2 38.6 3.9 4.2 15.0CFC75246 600/3/60 N/A 27kW 10.2@25 19,900 9,391 24 3 1/3 1140 (2) 1-3/8 580 263 10.2 38.6 3.1 3.4 15.0

CFC75127 208-230/3/6034kW41kW 48kW

34kW 14.0@30 20,500 9,674 24 3 1/3 1140 (2) 1-3/8 550 249 10.2 38.6 7.8 8.5 15.0

CFC75128 480/3/60 34kW41kW 34kW 14.0@30 20,500 9,674 24 3 1/3 1140 (2) 1-3/8 550 249 10.2 38.6 3.9 4.2 15.0

CFC75245 600/3/6034kW41kW 48kW

34kW 14.0@30 20,500 9,674 24 3 1/3 1140 (2) 1-3/8 550 249 10.2 38.6 3.1 3.4 15.0

CFC75137 208-230/3/60 N/A 48kW 6.6@30 20,700 9,768 18 2 1-1/2 1140 (2) 2-5/8 880 399 11.8 44.7 14.0 15.8 20.0CFC75138 480/3/60 N/A 48kW 6.6@30 20,700 9,768 18 2 1-1/2 1140 (2) 2-5/8 880 399 11.8 44.7 7.0 7.9 15.0CFC75248 600/3/60 N/A 48kW 6.6@30 20,700 9,768 18 2 1-1/2 1140 (2) 2-5/8 880 399 11.8 44.7 5.6 6.3 15.0CFC75139 208-230/3/60 62kW 41kW 4.7@50 20,700 9,768 28 2 1-1/2 1140 (2) 2-5/8 1600 726 11.8 44.7 14.0 15.8 20.0CFC75140 480/3/60 62kW 41kW 4.7@50 20,700 9,768 28 2 1-1/2 1140 (2) 2-5/8 1600 726 11.8 44.7 7.0 7.9 15.0CFC75249 600/3/60 62kW 41kW 4.7@50 20,700 9,768 28 2 1-1/2 1140 (2) 2-5/8 1600 726 11.8 44.7 5.6 6.3 15.0CFC75148 208-230/3/60 98kW N/A 6.9@50 31,800 15,006 28 3 1-1/2 1140 (2) 2-5/8 1240 562 16.7 63.2 21.0 22.8 25.0CFC75149 480/3/60 98kW N/A 6.9@50 31,800 15,006 28 3 1-1/2 1140 (2) 2-5/8 1240 562 16.7 63.2 10.5 11.4 15.0CFC75252 600/3/60 98kW N/A 6.9@50 31,800 15,006 28 3 1-1/2 1140 (2) 2-5/8 1240 562 16.7 63.2 8.4 9.1 15.0CFC75141 208-230/3/60 70kW N/A 15.8@60 34,800 16,422 21 3 1-1/2 1140 (2) 2-5/8 1190 540 13.0 49.2 21.0 22.8 25.0CFC75142 480/3/60 70kW N/A 15.8@60 34,800 16,422 21 3 1-1/2 1140 (2) 2-5/8 1190 540 13.0 49.2 10.5 11.4 15.0CFC75250 600/3/60 70kW N/A 15.8@60 34,800 16,422 21 3 1-1/2 1140 (2) 2-5/8 1190 540 13.0 49.2 8.4 9.1 15.0CFC75151 208-230/3/60 N/A 70kW 20.7@60 46,400 21,896 21 4 1-1/2 1140 (2) 2-5/8 1580 717 16.7 63.2 28.0 29.8 35.0CFC75152 480/3/60 N/A 70kW 20.7@60 46,400 21,896 21 4 1-1/2 1140 (2) 2-5/8 1580 717 16.7 63.2 14.0 14.9 15.0CFC75253 600/3/60 N/A 70kW 20.7@60 46,400 21,896 21 4 1-1/2 1140 (2) 2-5/8 1580 717 16.7 63.2 11.2 11.9 15.0CFC75144 208-230/3/60 90kW 62kW 20.7@70 32,900 15,526 21 3 1-1/2 1140 (2) 2-5/8 2360 1070 13.0 49.2 21.0 22.8 25.0CFC75145 480/3/60 90kW 62kW 20.7@70 32,900 15,526 21 3 1-1/2 1140 (2) 2-5/8 2360 1070 13.0 49.2 10.5 11.4 15.0CFC75251 600/3/60 90kW 62kW 20.7@70 32,900 15,526 21 3 1-1/2 1140 (2) 2-5/8 2360 1070 13.0 49.2 8.4 9.1 15.0

CFC75153 208-230/3/60 N/A 90kW98kW 16.3@70 43,900 20,716 21 4 1-1/2 1140 (2) 2-5/8 1620 735 16.7 63.2 28.0 29.8 35.0

CFC75154 480/3/60 N/A 90kW98kW 16.3@70 43,900 20,716 21 4 1-1/2 1140 (2) 2-5/8 1620 735 16.7 63.2 14.0 14.9 15.0

CFC75254 600/3/60 N/A 90kW98kW 16.3@70 43,900 20,716 21 4 1-1/2 1140 (2) 2-5/8 1620 735 16.7 63.2 11.2 11.9 15.0

LA = Full Load AmpsCA = Minimum Circuit AmperesOP = Maximum Overcurrent Protection

Fluid coolers can be selected for multiple indoor air conditioning units from the factory. Consult factory for help configuring many-to-one or one-to-manylycol loops.

32 APC NetworkAIR™ AFX

Fluid Coolers

2-fan fluid cooler3-fan fluid cooler

2-fan fluid cooler

APC PART VOLTAGEACFC75116 208-230/3/60ACFC75117 480/3/60ACFC75242 600/3/60

APC PART VOLTAGEACFC75120 208-230/3/60ACFC75121 480/3/60ACFC75243 600/3/60

APC NetworkAIR™ AFX 33

Fluid Coolers

3-fan fluid cooler3-fan 2luid cooler

2-fan fluid cooler

APC PART VOLTAGEACFC75130 208-230/3/60ACFC75131 480/3/60ACFC75246 600/3/60ACFC75127 208-230/3/60ACFC75128 480/3/60ACFC75245 600/3/60

APC PART VOLTAGEACFC75137 208-230/3/60ACFC75138 480/3/60ACFC75248 600/3/60ACFC75139 208-230/3/60ACFC75140 480/3/60ACFC75249 600/3/60

34 APC NetworkAIR™ AFX

Fluid Coolers

3-fan fluid cooler

4-fan fluid cooler

APC PART VOLTAGEACFC75148 208-230/3/60ACFC75149 480/3/60ACFC75252 600/3/60ACFC75144 208-230/3/60ACFC75145 480/3/60ACFC75251 600/3/60ACFC75141 208-230/3/60ACFC75142 480/3/60ACFC75250 600/3/60

APC PART VOLTAGEACFC75151 208-230/3/60ACFC75152 480/3/60ACFC75253 600/3/60ACFC75153 208-230/3/60ACFC75154 480/3/60ACFC75254 600/3/60

APC NetworkAIR™ AFX 35

Pump Specifications

Pump performance

Pump connection sizes

Pump electrical data

HP (kW) 3/4 (.56) 1 (.75) 1.5 (1.1) 2 (1.5) 3 (2.2)

LINE Suction Discharge Suction Discharge Suction Discharge Suction Discharge Suction Discharge

Size (inches) 1-1/4 1 1-1/4 1 1-1/4 1 1-1/2 1-1/4 2 1-1/2

HP (kW) 3/4 (.56) 1 (.75) 1.5 (1.1) 2 (1.5) 3 (2.2)

VOLTAGE FLA MCA FLA MCA FLA MCA FLA MCA FLA MCA

208-230/3/60 3.5 4.4 4.6 5.8 6.6 8.3 7.5 9.4 8.2 10.3

480/3/60 1.6 2.0 2.1 2.6 3.0 3.8 3.4 4.3 3.8 4.8

*Values are calculated based on 3-phase power.FLA = Full Load AmperesMCA = Minimum Circuit Amperes

20

30

50

60

10

70

80

90

100

110

120

40

0

25

30

35

40

5

10

15

20

TOTA

L D

YNA

MIC

HEA

D IN

MET

ERS

TOTA

L D

YNA

MIC

HEA

D IN

FEE

T

BH

P A

BSO

RBED

20 30 50 6010 70 80 90 10040

CAPACITY IN U.S. GALLONS PER MINUTE

0 1.0 2.0 3.0 4.0 5.0 7.0

20

30

50

60

10

70

80

90

100

40

PERCEN

T EFFICIEN

CY

CAPACITY IN LITERS PER SECOND

3600 R.P.M.

6.0 8.0 9.0 10

110 120 130

130

2 HP

1.5 HP3 HP

1 HP

0.75 HP

36 APC NetworkAIR™ AFX

Pump Specifications

Single Pump Package

* All dimensions are in inches (mm).

Dual Pump Package

* All dimensions are in inches (mm).

APC NetworkAIR™ AFX 37

38 APC NetworkAIR™ AFX

Guide Specifications

PART 1 — PART 1 GENERAL

1.01 SUMMARY

A. The environmental control system shall be designed specifically for precision temperature and humidity control applications. It will automatically monitor and control heating, cooling, humidifying, dehumidifying, and filtering functions for the conditioned space. The system shall be built to the highest quality engineering and manufacturing standards, and shall be floor mounted and configured for ________(up/down) discharge of conditioned airflow, with draw-through air pattern, to provide uniform air distribution over the entire face of the coil.

1.02 DESIGN REQUIREMENTS

A. The system shall be as described in the following specification as manufactured by APC.

1 . Model: ____________________________.2 . Total cooling capacity: _______________ MBH (kW).3 . Sensible cooling capacity: ____________ MBH (kW).4 . Return air temperature: _______________ º F (º C) DB.5 . Return air temperature: _______________ º F (º C) WB.6 . Humidity: __________________________% RH.7 . Air quantity: _______________________ CFM (L/s).8 . External Static Pressure _______________inches (Pa).9 . Humidifier capacity: _________________ lbs/hr (kg/hr).

10 . Electrical supply: ________ V, _________ ph, 60 Hz.

1.03 SUBMITTALS

A. Submittals shall be provided with the proposal and shall include: capacity data, electrical data, physical data, electrical connection drawing, and piping connection drawing.

1.04 QUALITY ASSURANCE

A. The system shall be completely factory-tested prior to shipment. Testing shall include, but not be limited to: complete pressure and leak testing to ensure system integrity, “Hi-Pot” test, and controls calibration and settings. Each system shall ship with a completed test report to verify completion of factory testing procedure. The system shall be NTRL listed, MCA, and electrical system shall be UL Listed to UL 1995 and CSA 22.2 No. 236.

1.05 WARRANTY

A. System parts shall be warranted for a period of 12months from date of shipment from factory.

APC NetworkAIR™ AFX 39

Guide Specifications

PART 2 — PART 2 PRODUCT

2.01 STANDARD COMPONENTS

A. MICROPROCESSOR

1. The microprocessor controller shall provide total environmental control. The system, based on the main controller, shall offer up to eight analog inputs, two analog outputs, twelve digital inputs and thirteen digital outputs. The operator interface shall provide a 4-line, 80-character backlit LCD display. User-friendly menu structure along with clearly defined prompts shall allow the operator to easily move about the program and monitor the following functions and alarm conditions.a. Status: Complete status monitoring shall be provided within the status menu of the

microprocessor controller, and shall include the following information: current temperature, current humidity, temperature setpoint, humidity setpoint, cooling status, heating status, humidification status and dehumidification status.

b. Alarms: Quick access to any alarm condition shall be facilitated through the menu structure. Presence of a new alarm shall sound an audible alarm. A red alarm LED on the display panel shall remain illuminated until such time that all alarms have been cleared. Alarm annunciation shall include: loss of airflow, clogged filter, high head pressure, low suction pressure, high temperature, low temperature, high humidity, and low humidity. The temperature and humidity alarm setpoints are user adjustable.

c. Setpoint: The microprocessor controller shall provide independent setpoints for heating, cooling, humidification, and dehumidification. Automatic setpoint cross-over protection shall prevent the setting of the heat setpoint above the cool setpoint and the humidify setpoint above the dehumidify setpoint. Setpoint adjustment shall be capable of being protected via security code.

d. Configuration: Flexibility shall be offered through the use of the configuration menu. It shall closely match the operating requirements by changing the configuration settings. The site configuration shall be stored in the EEPROM and be protected from unauthorized tampering by the user selectable 4-digit security password in the security menu. Configuration options shall include: Fahrenheit or Celsius display, compressor minimum off-time, power-loss restart time-delay, primary-secondary transfer functions, alarm input polarity, alarm enable, temperature deadbands, humidity deadbands, and small room delay.

e. Run time: The major components within the unit shall have independent run-timers that monitor and store the accumulated run-hours on the components. The run timers shall be provided with operator-adjustable run-time alarms for proper component maintenance.

f. Security: The microprocessor shall have multiple security levels to prevent unauthorized adjustment of the important system parameters. A user-selectable 4-digit password shall allow setpoint and configuration changes.

40 APC NetworkAIR™ AFX

Guide Specifications

B. CABINET CONSTRUCTION

1. The cabinet and frame shall be constructed from welded structural steel. Access panels shall be flush with the frame and insulated with fiberglass 1 in. (25 mm) in thickness, 1.5 lb/ft3 (24.0 kg/m3) in density. The panels shall be powder coated and lift off for access to the unit. A piping and electrical access plate shall be provided in the bottom of the unit. All units shall require front service access, 24 in (610 mm) minimum.

C. FAN/MOTOR SECTION

1. The unit shall be configured for draw-through air pattern, to provide uniform air-flow over the entire face of the coil. The blower shall be double-inlet centrifugal type, with forward-curving blades, dynamically and statically balanced. Each blower shall be independently driven by a high-efficiency motor. The drive package shall be designed for 200% of the fan motor horsepower. Minimum bearing life shall be 200,000 L10 hrs. The motor and blower shall be mounted on a common frame.

D. REFRIGERATION SYSTEM AND COMPRESSOR

1. Each refrigeration system shall consist of a fully protected scroll compressor, evaporator coil mounted over an insulated stainless steel condensate pan, adjustable expansion valve, filter-drier, liquid line solenoid valve, sight glass, receiver, liquid line isolation valve, low pressure switch and manual reset high pressure switch.

E. MAIN POWER DISCONNECT

1. A non-automatic main power circuit breaker shall disconnect all high voltage power to the unit if necessary. The disconnect switch shall be accessible without removing the electric box cover.

F. ELECTRICAL PANEL

1. The electrical system shall conform to National Electrical Code (NEC) requirements. The control voltage shall be 24 VAC, wired in accordance with NEC Class 1 requirements. The wire for the control circuit shall not be smaller than 18-gauge AWG. Each wire shall end with a service loop and be securely fastened by an approved method. Control wires more than 6 in. (150 mm) shall be color-coded or numbered every 3 in. (80 mm) for ease of service tracing. All electrically-actuated components shall be easily accessible from the front of the unit. Each high voltage unit shall be individually protected on all three phases. Main power shall be connected to a circuit breaker mounted on the electrical panel. The compressor and motor shall have overload and short circuit protection. The electrical box shall include all components and controls required for system operation. An emergency cool override manual switch shall be provided with provision for control using a field supplied thermostat. Incoming power is _________ V, _________ phase, 60 Hz.

APC NetworkAIR™ AFX 41

Guide Specifications

G. EVAPORATOR COIL/DRAIN PAN

1. The evaporator coil shall use the latest heat-transfer technology, raised lanced-aluminum fins and rifle-bored copper tubes. Coil end-supports shall be galvanized steel. To enhance dehumidification, the coil shall be split into two circuits by a microprocessor-controlled solenoid valve. An insulated stainless steel drain pan for condensate shall be included.

2.02 OPTIONAL COMPONENTS

A. AIR FILTER

1. The air filters shall be 30% efficient per ASHRAE Standard 52.1-92, UL Class 2. The full 4” (102 mm) deep, pleated filters shall be replaceable from the front on upflow units and from the top on downflow units.

B. HUMIDIFIER

1. Humidifier shall be self-contained steam-generating type, factory piped and wired, with disposable cylinder and automatic solid-state control circuit. Capacity: ______ lb/h (g/s).

C. ELECTRIC REHEAT

1. Reheat elements shall be low watt density, wired for three-phase, loaded equally on all three phases and shall be electrically and thermally protected by both automatic and manual reset thermal cutouts. Reheat capacity shall be ___________ MBH, ___________ kW, controlled in ________ (#) steps.

D. CONDENSER

1. Water and glycol cooled systems shall employ a brazed plate condenser that uses the latest heat transfer technology. Type 316L stainless plates shall be brazed together in a vacuum furnace and shall comply with ASME pressure vessel code. Pressure rating shall be 450 psi (3100 kPa).

E. WATER-REGULATING VALVES

1. Water and glycol cooled systems shall utilize two-way or three-way valves to regulate the amount of water or glycol supplied to the condenser in response to refrigerant discharge pressure. The standard valve pressure rating shall be 150 psi (1030 kPa).

F. DISCHARGE DUCT COLLAR

1. A 1” (25 mm) duct flange shall be provided for field installation on a unit to provide convenient connection to external ductwork.

42 APC NetworkAIR™ AFX

Guide Specifications

G. SECONDARY DRAIN PAN

1. Systems shall be provided with two drain pans. The primary stainless steel condensate pan shall lie directly under the cooling coil. The secondary, emergency drain pan shall provide additional protection by catching any water before it reaches the subfloor.

H. SPOT WATER DETECTOR

1. A water detector shall be factory-wired and shipped in the bottom of the unit to sense water and send a signal to the master control giving the operator possible alarm indications options for shutdown. The water detector shall be provided with 15 ft (5 m) of wire.

I. CABLE WATER DETECTOR

1. A leak detection sensing cable shall be shipped loose with the unit. If water or other conductive liquids contact the cable anywhere along its length, the main controller visually and audibly annunciates the leak.

2 . The detector shall be provided with 35ft (10.6 m) of cable. Cable may be cascaded up to 1000ft (305 m).

J. FIRESTAT

1. A firestat shall be factory-installed in the return air to sense heat and send a signal to the main controller shutting down the unit and activating a visual and audible alarm.

K. SMOKE DETECTOR

1. A smoke detector shall be factory-installed in the return air to sense concentrations of smoke and send a signal to the main controller shutting down the unit and activating a visual and audible alarm.

L. CONDENSATE PUMP

1. The Condensate Pump shall be factory installed and wired and shall pump 36 gal/h (0.06 L/s) at 15 ft. (4.6m) head.

M. REMOTE RELAY SHUTDOWN

1. Remote shutdown of the system can be done by a factory installed relay with a 24V, 120V, or 240V coil. The relay must be powered by others to disable the cooling system.

N. COMPRESSOR LOCKOUT

1. This lockout shall prevent compressor operation in emergency situations where limited back-up power is available.

APC NetworkAIR™ AFX 43

Guide Specifications

O. REHEAT/HUMIDITY LOCKOUT

1. When facilities have limited backup power capacity, this lockout shall prevent the operation of electrical loads that are not essential for continued site operation.

P. REDUNDANT GROUP CONTROL

1. Up to six units shall have the ability to communicate with each other to automatically switch upon alarm condition, or time rotation.

Q. REMOTE DISPLAY PANEL

1. Facility and building-maintenance personnel shall have the ability to evaluate and control the unit from up to 50ft. from the unit.

R. REMOTE SENSOR(S)

1 . Environmental sensor(s) shall be strategically placed, up to 50ft from the unit to better meet the site’s cooling needs. The sensor shall be positioned to permit air movement across the sensor.

S. HOT GAS REHEAT

1. The water- or glycol-cooled unit shall be supplied with a factory-installed copper tube and aluminum fin hot gas reheat coil. The coil shall be controlled by the main controller through a factory piped and wired three-way heat reclaim regulator and check valve.

T. HOT WATER REHEAT (MODULATING)

1. The unit shall be supplied with factory-installed copper tube, aluminum fin, and hot water reheat coil in place of electrical heater elements. Capacity shall be ________ MBH (kW), with ________ GPM (L/s) of ________ º F (º C) entering hot water temperature. Hot water shall be controlled with a modulating control valve.

U. STEAM/HOT WATER REHEAT (2-WAY ON/OFF)

1 . The unit shall be supplied with a factory-installed copper tube, aluminum fin, reheats steam-coil in place of electrical heat elements. Capacity shall be ________ MBH (kW) with 5 psi (35 kPa) of saturated steam. Steam shall be controlled with an on/off solenoid valve.

V. OPTIONAL BLOWER/MOTOR HP

1. An optional 5HP motor shall be used for increased CFM or to accommodate special air filters, high external static pressure, etc. while maintaining the standard CFM rating.

44 APC NetworkAIR™ AFX

Guide Specifications

W. HIGH EFFICIENCY FILTER(S)

1 . Pleated final filter(s) with an efficiency of 45% and 65% per ASHRAE Standard 52.2. The full 4” (102 mm) deep, pleated filters shall be replaceable from the front or top of the unit.

X. PREFILTER(S)

1 . Replaceable 1” (50 mm) deep, 30% efficient filters shall be installed upstream of the final filters to lengthen main filter life.

Y. HOT GAS BYPASS

1. Activation of the hot gas bypass circuit shall maintain the evaporator coil temperature during low load conditions.

Z. 3-WAY VALVE FLOW SWITCH

1. A Single-Pole, Double-Throw flow switch shall be wired to energize one device and de-energize another device powered from the same source when fluid flow either exceeds or drops below the set flow rate.

AA.FLOORSTAND

1. The heavy gauge floorstand shall raise the unit above the subfloor to match the height of the raised floor. Heights shall be available from 6” (152mm) to 36” (915mm) on upflow units and 12" (305mm) to 36" (915mm) for downflow units, in 3" (76mm) increments and shall be adjustable +/- 1.5". Threaded pedestals shall provide adjustment. Vibration absorbing pads shall be included. Pedestals and vibration pads shall be included. Seismic floorstands shall be available in 12” (305mm), 18” (457mm), and 24” (610mm) heights.

AB.AIR DEFLECTOR

1. A ninety degree air deflector shall ship loose and shall be ________ in. (mm) high.

AC.PLENUM

1. A discharge plenum shall mount on top of an upflow unit to direct and distribute conditioned air. a. The plenum shall be manually adjustable with double deflecting grilles provided on 3

or 4 sides. Plenum height shall be 20”.b. The plenum shall be provided with a duct collar and no grilles. Plenum height shall be

24” (610mm).

AD.CASTERS

1. A set of 6” (152mm) plated rolling casters shall be provided for handling of equipment.

APC NetworkAIR™ AFX 45

Guide Specifications

AE.ENVIRONMENTAL MONITORING AND MANAGEMENT

1. Environmental Monitoring Unit: A stand-alone unit shall perform continuous temperature and humidity sensing through two available proves and contact monitoring. Unit shall be controlled by available web, control console, or SNMP interface with network connection. In the event of an environmental anomaly, notification shall be sent to the customer via e-mail or SNMP. The unit shall be 18.25”x9”x2.75”(464mm x 229mm x 70mm).

2 . Environmental Management System: A browser-accessible, 1U, rackmountable appliance shall allow monitoring of environmental conditions. Monitoring of one temperature, one humidity, and one vibration sensor shall ship standard. When conditions change, notifications shall be sent via email to the appropriate personnel. The EMS shall provide eight input contacts, 2 output relays, and controllable power outlets for defining actions remotely should conditions warrant it.

AF. OHE DISCONNECT

1. A non-fused disconnect switch shall be wired to an outdoor heat exchanger to disconnect high voltage power if necessary.

AG.CUSTOM ALARM DRY CONTACT CLOSURES

1. Each unit shall be equipped with any or all or the listed dry contact closures. Upon activation of the associated alarm, a discreet Normally Open or Normally Closed contact is available for remote monitoring of that discreet alarm.a. High Temperature Alarmb. Low Temperature Alarmc. High Humidity Alarmd. Low Humidity Alarme. Compressor High Head Pressure Alarmf. Clogged Filter Alarmg. Fire Alarm (with Firestat)h. Smoke Alarm (with Smoke Detector)i. Humidifier Change Canister Alarmj. Water Underfloor Alarm (with Water Detector)k. Condensate Pump Overflow Alarm (with Condensate Pump)l. Loss of Flow (with Flow Switch)

AH.MODBUS/JBUS GATEWAY

1. The Gateway shall translate transmission protocol from the system’s network into ModBus/JBus communication protocol. One gateway shall support up to 16 units.

AI. DOWNFLOW RETURN DUCT

1. A return duct the length and width of the unit shall be provided for field installation on a downflow unit to provide convenient connection to external ductwork.

46 APC NetworkAIR™ AFX

Guide Specifications

PART 3 — PART 3 INDIVIDUAL SYSTEMS

3.01 AIR-COOLED

A. The indoor unit shall consist of an evaporator section including evaporator coil, blower package, controls, electrical section, and compressor.

B. CONDENSER

1. Outdoor Propeller Fan Condenser: The outdoor condenser casing shall be made of aluminum, and all structural supports, coil frame, motor drive supports, and mounting legs shall be made of galvanized steel. The condenser shall have copper tubes expanded into aluminum fins. Headers and connections shall be copper. The coil shall be pressure tested and sealed for shipment. The condenser motors shall have permanently lubricated, sealed, ball bearings, and internal overload protection, and operate on ________ V, ________ ph, 60 Hz power. Motors shall be 1140 RPM and mounted inside the condenser casing for weather protection, and shall be wired to a terminal strip in a weatherproof panel on the unit. The direct drive, aluminum fan blade and painted steel hub assembly, shall be protected by a heavy-gauge, vinyl-coated, steel-wire fan guard. On multiple units, each fan section shall be separated by full-width baffles to prevent bypass air. The condenser shall be sized for ________ º F (ºC) ambient, and condensing temperature controls shall be fan speed for -20º F (-29º C) winter ambient. A ship loose pressure relief valve shall ship with the condenser.

2 . Flooded Controls: Flooded controls shall maintain head pressure to -30º F (-34.4ºC) by regulating the effective condensing area within the condenser coil. Controls shall ship loose and be mounted to the side of the condenser. A ship loose pressure relief valve shall ship with the condenser.

3.02 WATER-COOLED

A. The water-cooled system shall consist of an evaporator section including evaporator coil, blower package, controls, electrical section, compressor, and water-cooled condenser. The condenser shall be stainless steel brazed plate design and shall be controlled by 2-way (3-way optional) head pressure-regulated valve. Maximum water pressure shall be 400 psi (2758 kPa).

3.03 GLYCOL-COOLED

A. The glycol-cooled system shall consist of an evaporator section including evaporator coil, blower package, controls, electrical section, compressor, and glycol-cooled condenser. The condenser shall be stainless steel brazed plate design and shall be controlled by 2-way (3-way optional) head pressure-regulated valve. Maximum water pressure shall be 400 psi (2758 kPa).

APC NetworkAIR™ AFX 47

aclark
Highlight

Guide Specifications

B. FLUID COOLER

1. Outdoor Fluid Cooler: The fluid cooler casing shall be of aluminum, and all structural supports, coil frame, motor-drive supports, and mounting legs shall be made of galvanized steel. The fluid cooler coil shall have copper tubes expanded into aluminum fins. Headers and connections shall be copper. The coil shall be pressure-tested and sealed for shipment. The fluid cooler motors shall have permanently lubricated, sealed, ball bearings, and internal overload protection. Motors shall be mounted inside the fluid cooler casing for weather protection and wired to a terminal strip in a weatherproof panel on the unit. The direct-drive, aluminum fin blade and painted steel hub assembly shall be protected by a heavy-gauge, vinyl-coated, steel-wire fan guard. On multiple fan units, each fan section shall be separated by full-width baffles to prevent bypass air. The Fluid Cooler shall be sized for 95º F (35º C) ambient, and operate on ________ V, ________ ph, 60 Hz power.

C. PUMP PACKAGE

1. Single Pump Package: The pump package shall be comprised of a centrifugal pump in a vented enclosure with pump starter, separate Fluid Cooler fan and pump circuit breakers, Aquastat, and fan cycling contractors to control the fluid temperature. The controls shall be mounted in a weather-tight box. A _______ gal (L) expansion tank and Airtrol fitting shall be supplied for field installation. The pump size shall be sized for ________ GPM (L/s) at ________ ft (m) external head, and operate on ________ V, ________ ph, 60 Hz power.

2 . Dual Pump Package: The dual pump package shall consist of two centrifugal pumps in an enclosure. Pump starters, automatic pump switch-over controls, lead-lag pump selector switch, separate Fluid Cooler fan and pump circuit breakers, Aquastat, and fan cycling contractor to control the fluid temperature shall be mounted in a separate weather-tight box. A _______ gal (L) expansion tank and Airtrol fitting shall be supplied for field installation. Each pump shall be sized for ________ GPM (L/s) at _________ ft (m) external head, and operate on ________ V, ________ ph, 60 Hz power.

48 APC NetworkAIR™ AFX

Guidelines for Installation

The AFX provides reliable, accurate temperature and humidity control of computer rooms, laboratories, and other environments that require close tolerance control. The unit incorporates the latest system design innovations to provide you with optimum efficiency, reliability, and accuracy of control.

The AFX system will provide years of trouble-free service, when installed and maintained by technically qualified personnel.

Room preparation During the design of the room, consideration should be given to the following factors: ease of entry for the system, floor-loading factors, and accessibility of piping and wiring.

The room must be sealed with a vapor barrier to minimize migration of moisture. Polyethylene film (plastic sheeting) is a good vapor barrier for ceiling and wall applications. Rubber- or plastic-based paints should be applied to concrete floors and walls. The room should be thoroughly insulated to minimize thermal loads and make-up air (if required) should be preconditioned to reduce additional temperature, filtration, and moisture loads.

A room using a raised-floor plenum for air distribution should have at least 9" (300 mm) of clear space between the false floor and sub-floor for a finished floor height of 12" (380 mm). Pay special attention to the location of pipe chases, electrical conduits and other obstructions under the floor. These objects can block air circulation and cause loss of air pressure, thus reducing system efficiency and causing hot spots in your room.

Minimum clear space of 18" (460 mm) is to be provided for units over 15 tons (53 kW).

APC should be notified before installation if the unit is incorrect for the application.

Unit location The location of the unit is important for efficient and balanced environmental control in your room. The air conditioner should be located as close as possible to the largest heat load. In rooms having a high aspect ratio, mount the unit along the longest wall to ensure even air distribution. If improperly installed, erratic control or mechanical failure can and will result.

APC NetworkAIR™ AFX 49

Guidelines for Installation

Service access At least 24" (610 mm) of clear space must be left in front of the unit for routine service (filters, humidifier). We strongly recommend approximately 32" (813 mm) clearance in front of the unit.

Receiving the unit Your AFX unit has been completely tested and inspected prior to shipment. To ensure that you have received the unit in excellent condition, perform a careful inspection of the crating and the unit immediately upon receipt. Verify that all parts ordered were received as specified and that the unit is the correct size and voltage necessary to fulfill your environmental control needs. Report any damage discovered to the freight carrier. If necessary, contact the APC field service department for help in repairing or replacing damaged parts. While APC is not responsible for damage incurred in transit, we want to make sure that you have no undue delays in your system start-up.

Rigging The unit is manufactured with a formed steel frame for maximum strength and unit integrity. However, as with all electrical and mechanical equipment, you must take care with proper rigging of your unit.

When using a forklift to move the unit, use the shipping skid to protect the bottom of the unit. When using chains, cables or rope to lift the unit, use spreader bars to prevent damage to the finished panel.

Floorstand Install a threaded pedestal into each leg of the floorstand. Use the washer and nut on each panel to tighten against the floorstand leg.

Utility connections All connections are made through the bottom left of the unit (the left side of upflow discharge units) for ease of service connections. Refer to the installation manual for pipe sizes and specific locations for your unit.

Power unit The AFX unit uses 3-phase power for operation. Power connections are landed to a receptacle on either floorstand or sub base. Bring the service cable through the bottom left of the unit and through the bulkhead hole into the electrical box to the circuit breaker provided on the left side of the electrical box. The ground lug is located near the 3-phase high-voltage connector. THE UNIT MUST BE UTILITY GROUNDED OR THE WARRANTY IS VOID.

Humidifier connections The humidifier inlet connection point is provided with the equipment. A 1/4" (6.4mm) compression connection is supplied with the unit.

Condensate drain Condensate from the evaporator pan is collected and discharged by the condensate pump to a 7/8" (22.2mm) fitting for field connection.

50 APC NetworkAIR™ AFX

Guidelines for Installation

Water supply to humidifier 1. The humidifier fill valve orifice is sized for supply water pressure from 15 PSIG (103.4 kPa) to 150 PSIG (1034 kPa).

2. For cases above 150 PSIG (1034 kPa), install a pressure-reducing valve in the water feed line to the unit.

3. With extremely dirty or muddy water sources, proper filtration is required on the unit’s incoming water line.

4. DO NOT use softened water with the humidifier. Softened water is too conductive.

5. DO NOT use completely demineralized water with the humidifier. The minerals allow the electrode principle to work.

6. DO NOT use a hot water source. Doing so will cause deposits that will eventually block the fill valve orifices.

7. Water supplies with high conductivity (above 800 mW) must be preconditioned for proper operation and longevity of the humidi-fier.

Water supply A 16- to 20-mesh strainer must be installed in the water supply to the water units to prevent clogging of brazed plate condenser. This is a field item.Also recommended on glycol units.

Note: Because of an ongoing program dedicated to product improvement, specifications are subject to revisions without notice. APC assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.

APC NetworkAIR™ AFX 51

52 APC NetworkAIR™ AFX

APC Worldwide Customer Support

Customer support for this or any other APC product is available at no charge in any of the following ways:• Visit the APC Web site to find answers to frequently asked questions (FAQs), to access documents

in the APC Knowledge Base, and to submit customer support requests.– www.apc.com (Corporate Headquarters)

Connect to localized APC Web sites for specific countries, each of which provides customer support information.

– www.apc.com/support/Global support with FAQs, knowledge base, and e-support.

• Contact an APC Customer Support center by telephone or e-mail.– Regional centers:

– Local, country-specific centers: go to www.apc.com/support/contact for contact information.

Contact the APC representative or other distributor from whom you purchased your APC product for information on how to obtain local customer support.

APC headquarters U.S.,Canada (1)(800)800-4272 (toll free)

Latin America (1)(401)789-5735 (USA)

Europe, Middle East, Africa (353)(91)702020 (Ireland)

Asia Pacific (61) 2 9955 9366 (Australia)