9.1_DPFCCS_PFC

download 9.1_DPFCCS_PFC

of 2

Transcript of 9.1_DPFCCS_PFC

  • 8/17/2019 9.1_DPFCCS_PFC

    1/2

    PFC EngineeringStation Road

    Great ChesterfordEssex CB10 1NY

    t: 01799 530728

    f: 01799 530235

    e: [email protected]

    w: pfc-engineering.com

     The Energy

    Solution

    Specialists.

    Detuned Power Factor Correction

    Case Study – Plastics Factory

    We were asked to attend site to carry

    out a power factor correction survey on a

    plastics factory who, due to their impending

    increase in load, had a requirement for

    more power factor correction. As a normal

    part of our power factor correction survey

    our survey engineer measured the voltage

    harmonics to determine whether any powerfactor correction recommend would have

    to incorporate detuning reactors to avoid

    harmonic overloading of the capacitors.

    During this survey the voltage harmonics

    were recorded as being in excess of 8%.

    Such a level of harmonic voltage distortion

    is beyond even the IEC compatibility limits,

    meaning that any equipment connected

    to such a distorted supply cannot be

    guaranteed to function correctly.

    BY INSTALLING OUR DETUNED

    POWER FACTOR CORRECTION

    SYSTEM WE MANAGED TO NOT

    ONLY PREVENT A DAMAGING

    HARMONIC RESONANCE, BUT

     ACTUALLY REDUCE THE LOAD

    HARMONICS, POTENTIALLY

    INCREASING THE LIFE OF THE

    CLIENTS PLANT.

     The installation at the time of the survey

    included a 400 kVAr power factor correction

    bank arranged in four steps of 100kVAr, all

    of which was in circuit at the time of the test.

     The immediate suspicion was that the power

    factor correction capacitors were forming a

    resonant or at least partial resonant circuit

    with the supply transformer leading to a

    magnification of the loads natural harmonic

    levels. In order to test this theory the

    capacitor banks were all switched out of

    circuit and the harmonic voltage measured

    once again. Upon doing this the voltage

    distortion was found to be in the region of

    3.5% to 4.0%, clearly supporting the theory

    that the capacitors were exacerbating a

    previously moderate harmonic issue. Upon

    closer analysis of the specific harmonics

    contributing to the overall harmonic

    distortion it was discovered that the 5th

    harmonic was the dominant harmonic.

    In order to determine the true extent of the

    problem a period of harmonic logging was

    commissioned with the original power factor

    correction operating. Figure 1 shows the

    profile of the voltage total harmonic voltage

    distortion captured with the original power

    factor correction running. The first couple of

    days of the analysis were during the weekend

    and consequently no plant was operating.

    Once the plant started operating on the

    Sunday night there was an immediate jump

    in the voltage THD, with the distortion levelpeaking at more than 8%. Figure 2 shows

    the profile of the 5th harmonic voltage taken

    during the same period. It can be seen that

    this profile is almost identical to the THD

    profile, indicating that the 5th harmonic is by

    far the dominant harmonic.

    From the predicted increase in loading it

    was calculated that the total future power

    factor correction requirement was 600

    kVAr. Clearly this amount of power factorcould not be connected without detuning

    reactors as it would result in harmonics

    levels even higher than the elevated values

    existing at the time. In cases such as this

    the most common solution would be to

    install capacitors with 189 Hz detuning

    reactors, which prevent the magnification

    of harmonics for all of the harmonics from

    the 5th order upwards. Normally the total

    harmonic distortion of a supply consists of

    contributions from a number of harmonics

    whose magnitude decreases as the

    harmonic order increases. As has already

    been mentioned, the harmonic distortion at

    this site is overwhelmingly dominated by the

  • 8/17/2019 9.1_DPFCCS_PFC

    2/2

    PFC EngineeringStation Road

    Great ChesterfordEssex CB10 1NY

    t: 01799 530728

    f: 01799 530235

    e: [email protected]

    w: pfc-engineering.com

     The Energy

    Solution

    Specialists.

    5th harmonic and as such any reduction in

    this harmonic would have a profound impact

    on the total harmonic distortion. With this in

    mind it was recommended that a 210 Hz

    detuned power factor correction system

    was installed at this site. The effect of tuning

    the power factor correction to 210 Hz is that

    as well as preventing magnification of all of

    the major harmonics it actually provides

    filtration of the 5th harmonic.

     The larger the capacitor bank, the greaterthe filtration effect is and bearing in mind the

    recommended capacitor bank size for this

    site was 600 kVAr the potential filtration was

    significant.

    Based upon the commercial and technical

    arguments presented for this project, the

    installation of a 600 kVAr, 210 Hz detuned

    power factor correction system was

    commissioned. Figure 3 and Figure 4

    show, respectively, a profile of the voltage

    total harmonic distortion and 5th harmonic

    distortion with all of the replacement

    detuned power factor correction in circuit.

    It can be seen that as opposed to the

    original level of 8%, the voltage THD with

    the detuned capacitors in circuit was barely

    2%. In addition to this the 5th harmonic

    voltage no longer dominates the voltage

     THD to the same degree as before, this time

    only constituting approximately 1.6% of the

    2.2% distortion.

    Conclusion

    From the preceding results it is apparent

    that the old power factor correction was

    producing a serious harmonic resonantcondition. The additional harmonics

    imposed upon the supply transformer would

    have produced significant additional stress

    upon the supply transformer, potentially

    reducing the lifespan of the transformer and

    compromising the integrity of the supply.

    By installing 210 Hz detuned power factor

    correction, a solution to the poor load

    power factor has been implemented that

    provides both an economical and technical

    advantage, resulting in a supply that

    operates efficiently with little potential for

    mal-operation of connected equipment due

    to excessive voltage harmonic distortion.

    Figure 1: Profile of voltage total harmonic distortion captured during

    initial harmonic analysis period.

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

       1   1  :   3   4  :   0   0 

       1   3  :   1   0  :   0   0 

       1   4  :   4   6  :   0   0 

       1   6  :   2   2  :   0   0 

       1   7  :   5   8  :   0   0 

       1   9  :   3   4  :   0   0 

       2   1  :   1   0  :   0   0 

       2   2  :   4   6  :   0   0 

       0   0  :   2   2  :   0   0 

       0   1  :   5   8  :   0   0 

       0   3  :   3   4  :   0   0 

       0   5  :   1   0  :   0   0 

       0   6  :   4   6  :   0   0 

       0   8  :   2   2  :   0   0 

       0   9  :   5   8  :   0   0 

       1   1  :   3   4  :   0   0 

       1   3  :   1   0  :   0   0 

       1   4  :   4   6  :   0   0 

       1   6  :   2   2  :   0   0 

       1   7  :   5   8  :   0   0 

       1   9  :   3   4  :   0   0 

       2   1  :   1   0  :   0   0 

       2   2  :   4   6  :   0   0 

       0   0  :   2   2  :   0   0 

       0   1  :   5   8  :   0   0 

       0   3  :   3   4  :   0   0 

       0   5  :   1   0  :   0   0 

       0   6  :   4   6  :   0   0 

       0   8  :   2   2  :   0   0 

       0   9  :   5   8  :   0   0 

       1   1  :   3   4  :   0   0 

       1   3  :   1   0  :   0   0 

       1   4  :   4   6  :   0   0 

       1   6  :   2   2  :   0   0 

       1   7  :   5   8  :   0   0 

       1   9  :   3   4  :   0   0 

       2   1  :   1   0  :   0   0 

       2   2  :   4   6  :   0   0 

       0   0  :   2   2  :   0   0 

       0   1  :   5   8  :   0   0 

       0   3  :   3   4  :   0   0 

       0   5  :   1   0  :   0   0 

       0   6  :   4   6  :   0   0 

       V   o    l   t   a   g   e    d   i   s   t   o   r   t   i   o   n    (   %

        )

    Voltage total harmonic distortion with original PFC

    Vthd L1 Vthd L2 Vthd L3

    Figure 2: Profile of voltage 5th harmonic distortion captured during initial

    harmonic analysis period.

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

       1   1  :   3   4  :   0   0 

       1   3  :   1   0  :   0   0 

       1   4  :   4   6  :   0   0 

       1   6  :   2   2  :   0   0 

       1   7  :   5   8  :   0   0 

       1   9  :   3   4  :   0   0 

       2   1  :   1   0  :   0   0 

       2   2  :   4   6  :   0   0 

       0   0  :   2   2  :   0   0 

       0   1  :   5   8  :   0   0 

       0   3  :   3   4  :   0   0 

       0   5  :   1   0  :   0   0 

       0   6  :   4   6  :   0   0 

       0   8  :   2   2  :   0   0 

       0   9  :   5   8  :   0   0 

       1   1  :   3   4  :   0   0 

       1   3  :   1   0  :   0   0 

       1   4  :   4   6  :   0   0 

       1   6  :   2   2  :   0   0 

       1   7  :   5   8  :   0   0 

       1   9  :   3   4  :   0   0 

       2   1  :   1   0  :   0   0 

       2   2  :   4   6  :   0   0 

       0   0  :   2   2  :   0   0 

       0   1  :   5   8  :   0   0 

       0   3  :   3   4  :   0   0 

       0   5  :   1   0  :   0   0 

       0   6  :   4   6  :   0   0 

       0   8  :   2   2  :   0   0 

       0   9  :   5   8  :   0   0 

       1   1  :   3   4  :   0   0 

       1   3  :   1   0  :   0   0 

       1   4  :   4   6  :   0   0 

       1   6  :   2   2  :   0   0 

       1   7  :   5   8  :   0   0 

       1   9  :   3   4  :   0   0 

       2   1  :   1   0  :   0   0 

       2   2  :   4   6  :   0   0 

       0   0  :   2   2  :   0   0 

       0   1  :   5   8  :   0   0 

       0   3  :   3   4  :   0   0 

       0   5  :   1   0  :   0   0 

       0   6  :   4   6  :   0   0 

       V   o    l   t   a   g   e    d   i   s   t   o   r   t   i   o

       n    (   %    )

    Voltage 5th harmonic distortion with original PFC

    Vthd L1 Vthd L2 Vthd L3

    Figure 3: Profile of voltage total harmonic distortion captured after the

    installation of the detuned power factor correction.

    0

    0.5

    1

    1.5

    2

    2.5

       1   2  :   5   3  :   0   0 

       1   4  :   3   4  :   0   0 

       1   6  :   1   5  :   0   0 

       1   7  :   5   6  :   0   0 

       1   9  :   3   7  :   0   0 

       2   1  :   1   8  :   0   0 

       2   2  :   5   9  :   0   0 

       0   0  :   4   0  :   0   0 

       0   2  :   2   1  :   0   0 

       0   4  :   0   2  :   0   0 

       0   5  :   4   3  :   0   0 

       0   7  :   2   4  :   0   0 

       0   9  :   0   5  :   0   0 

       1   0  :   4   6  :   0   0 

       1   2  :   2   7  :   0   0 

       1   4  :   0   8  :   0   0 

       1   5  :   4   9  :   0   0 

       1   7  :   3   0  :   0   0 

       1   9  :   1   1  :   0   0 

       2   0  :   5   2  :   0   0 

       2   2  :   3   3  :   0   0 

       0   0  :   1   4  :   0   0 

       0   1  :   5   5  :   0   0 

       0   3  :   3   6  :   0   0 

       0   5  :   1   7  :   0   0 

       0   6  :   5   8  :   0   0 

       0   8  :   3   9  :   0   0 

       1   0  :   2   0  :   0   0 

       1   2  :   0   1  :   0   0 

       1   3  :   4   2  :   0   0 

       1   5  :   2   3  :   0   0 

       1   7  :   0   4  :   0   0 

       1   8  :   4   5  :   0   0 

       2   0  :   2   6  :   0   0 

       2   2  :   0   7  :   0   0 

       2   3  :   4   8  :   0   0 

       0   1  :   2   9  :   0   0 

       0   3  :   1   0  :   0   0 

       0   4  :   5   1  :   0   0 

       0   6  :   3   2  :   0   0 

       0   8  :   1   3  :   0   0 

       0   9  :   5   4  :   0   0 

       1   1  :   3   5  :   0   0 

       V   o    l   t   a   g   e    d   i   s   t   o   r   t   i   o   n    (   %    )

    Voltage total harmonic distortion with detuned PFC

    Vthd L1 Vthd L2 Vthd L3

    Figure 4: Profile of voltage 5th harmonic distortion captured after the

    installation of the detuned power factor correction

    0

    0.2

    0.4

    0.6

    0.8

    1

    1.2

    1.4

    1.6

    1.8

       1   2  :   5   6  :   0   0 

       1   4  :   3   7  :   0   0 

       1   6  :   1   8  :   0   0 

       1   7  :   5   9  :   0   0 

       1   9  :   4   0  :   0   0 

       2   1  :   2   1  :   0   0 

       2   3  :   0   2  :   0   0 

       0   0  :   4   3  :   0   0 

       0   2  :   2   4  :   0   0 

       0   4  :   0   5  :   0   0 

       0   5  :   4   6  :   0   0 

       0   7  :   2   7  :   0   0 

       0   9  :   0   8  :   0   0 

       1   0  :   4   9  :   0   0 

       1   2  :   3   0  :   0   0 

       1   4  :   1   1  :   0   0 

       1   5  :   5   2  :   0   0 

       1   7  :   3   3  :   0   0 

       1   9  :   1   4  :   0   0 

       2   0  :   5   5  :   0   0 

       2   2  :   3   6  :   0   0 

       0   0  :   1   7  :   0   0 

       0   1  :   5   8  :   0   0 

       0   3  :   3   9  :   0   0 

       0   5  :   2   0  :   0   0 

       0   7  :   0   1  :   0   0 

       0   8  :   4   2  :   0   0 

       1   0  :   2   3  :   0   0 

       1   2  :   0   4  :   0   0 

       1   3  :   4   5  :   0   0 

       1   5  :   2   6  :   0   0 

       1   7  :   0   7  :   0   0 

       1   8  :   4   8  :   0   0 

       2   0  :   2   9  :   0   0 

       2   2  :   1   0  :   0   0 

       2   3  :   5   1  :   0   0 

       0   1  :   3   2  :   0   0 

       0   3  :   1   3  :   0   0 

       0   4  :   5   4  :   0   0 

       0   6  :   3   5  :   0   0 

       0   8  :   1   6  :   0   0 

       0   9  :   5   7  :   0   0 

       1   1  :   3   8  :   0   0 

       V   o    l   t   a   g   e    d   i   s   t   o   r   t   i   o   n    (   %

        )

    Voltage 5th harmonic distortion with detuned PFC

    Vthd L1 Vthd L2 Vthd L3