26-1362-01 TWINFLEX ® SRP Fire Suppression System Remote Status Indicator (RSI) (Suitable for TWINFLEX ® SRP Control Panel from V01.000) Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER)

Transcript of 8 Zone Expansion PCB - Fike

Page 1: 8 Zone Expansion PCB - Fike

26-1362-01

TWINFLEX® SRP

Fire Suppression System Remote Status Indicator (RSI)

(Suitable for TWINFLEX® SRP Control Panel from V01.000)

Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER)

Page 2: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

2

Fike’s policy is one of continual improvement and the right to change a specification at any time without notice is reserved. Whilst every care has been taken to ensure that the contents of this document are correct at time of publication, Fike shall be under no liability whatsoever in respect of such contents.

Due to the complexity and inherent importance of a life risk type system, training on this equipment is essential and commissioning should only be carried out by competent persons. Fike cannot guarantee the operation of any equipment unless all documented instructions are complied with, without variation. E&OE.

TWINFLEX, Mulitpoint, Fike and Fike Corporation are registered trademarks of Fike Corporation and its subsidiaries. All other trademarks, trade names or company names referenced herein are the property of their respective owners.

Fike equipment is protected by one or more of the following patent numbers: GB2426367, GB2370670, EP1158472, PT1035528T, GB2346758, EP0917121, GB2329056, EP0980056, GB2325018, GB2305284, EP1174835, EP0856828, GB2327752, GB2313690

© 2016 Fike Safety Technology Ltd. All rights reserved. Document issued January 2016.

Page 3: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

3

Contents

Introduction ........................................................................................................................................................... 5

System Design ...................................................................................................................................................... 5

Equipment Guarantee .................................................................................................................................. 5 Anti-Static Handling Guidelines .................................................................................................................... 5 Warning ........................................................................................................................................................ 5 EMC .............................................................................................................................................................. 6

The TWINFLEX® SRP System ............................................................................................................................. 6

Remote Status Indicator (RSI) ............................................................................................................................. 6

Mounting the RSI .................................................................................................................................................. 7

Physical Dimensions .................................................................................................................................. 10

General Assembly .............................................................................................................................................. 10

Ribbon Cable Connection .......................................................................................................................... 11 Fixing Front Panel To Back Box ................................................................................................................. 11

Installation and Commissioning ....................................................................................................................... 12

Topology & Cabling .................................................................................................................................... 12 Maximum Cable Lengths ............................................................................................................................ 12 Power Supply & Connections ..................................................................................................................... 13

Power Connection Table .................................................................................................................. 13 Current Drawn by Single Remote Status Indicator @ 24.0V DC ..................................................... 13 Separate Power Supply Requirements ............................................................................................ 13 Remote Status Indicator Back Board Power Supply Connections .................................................. 13

Peripheral Bus Connections ....................................................................................................................... 14 SRP Control Panel Connector Board Peripheral Bus Connections ................................................. 14 Remote Status Indicator Back Board Peripheral Bus Connections ................................................. 14

Ext Switches SW1 and SW2 Connection Examples .................................................................................. 15 RSI With External Switch Connections ............................................................................................ 15 RSI Without External Switch Connections. EOL must be present. ................................................. 15

SRP Control Panel Peripheral Bus Settings .............................................................................................. 16 RSI Panel Settings ..................................................................................................................................... 16

Setting RSI Address/Number ........................................................................................................... 16 RSI Buzzer ....................................................................................................................................... 16

LCD Contrast .............................................................................................................................................. 17 Powering Up ............................................................................................................................................... 17 Commissioning ........................................................................................................................................... 18 Fault finding ................................................................................................................................................ 18

General Operation of Remote Status Indicator ............................................................................................... 19

RSI Front Panel .......................................................................................................................................... 19 LED Indication ............................................................................................................................................ 19 Fire Alarm Controls..................................................................................................................................... 20 System Controls ......................................................................................................................................... 20 Extinguishant Release Controls ................................................................................................................. 20 Access Levels ............................................................................................................................................. 21

Access Level 1 (Normal) .................................................................................................................. 22 Access Level 2 (User): ..................................................................................................................... 23

End User Training ............................................................................................................................................... 25

Maintenance ........................................................................................................................................................ 25

Technical Data .................................................................................................................................................... 25

Page 4: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

4

Remote Status Indicator Specification ....................................................................................................... 25

Fire Alarm System Notice .................................................................................................................................. 26

To Enable the Control Panel Keys ............................................................................................................. 26 To Manually Operate the Fire Alarm Sounders .......................................................................................... 26 Following a Fire Alarm Operation ............................................................................................................... 26 Following a Fault Condition ........................................................................................................................ 26

Important Notes .................................................................................................................................................. 27

Fire Alarm User Notice ....................................................................................................................................... 27

Engineers Notes ................................................................................................................................................. 29

Technical Support .............................................................................................................................................. 30

Page 5: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

5

Introduction

This Manual is intended as a guide to the engineering and commissioning principles of the TWINFLEX®

SRP Remote Status Indicator and covers the system hardware information only. Due to the complexity and inherent importance of a system covering a ‘Life Protection Risk’, training on this equipment is essential and commissioning should only be carried out by competent and approved persons. For further details of the availability of commissioning services, please contact your supplier.

System Design

This document does not cover Fire Alarm system design and a basic understanding is assumed. A knowledge of BS5839: Pt 1: 2002: Fire Detection and Alarm Systems for Buildings is essential. It is strongly recommended that a suitably qualified and competent person is consulted in connection with the Fire Alarm System design and that the entire system is commissioned in accordance with the current national standards and specifications.

Equipment Guarantee

The equipment carries no warranty unless the system is installed, commissioned and serviced in accordance with this manual and the relevant standards by a suitably qualified and competent person or organisation

Anti-Static Handling Guidelines

Immediately prior to handling any PCBs or other static sensitive devices, it is essential to ensure that a personal connection to earth is made with an anti-static wrist-strap or similar apparatus. Always handle PCBs by their sides and avoid touching any components. PCBs should also be stored in a clean dry place, which is free from vibration, dust and excessive heat and is protected from mechanical damage.

Warning

Do not attempt to install this equipment until you have fully read and understood this manual.

Failure to do so may result in damage to the equipment and could invalidate the warranty. For technical support please contact your distributor. Do not call the Fike Safety Technology support department unless your distributor has first given their advice and attempted to rectify the issue. Technical support will not be available if the instruction manual has not been read and understood. Please have this instruction manual available whenever you call for technical support.

!

!

!

!

Page 6: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

6

EMC

This equipment when installed is subject to the EMC directive 2004/108/EC. It is also subject to UK Statutory Instrument 2006 No. 3418.

To maintain EMC compliance, this system must be installed as defined within this manual. Any deviation from this renders the installer liable for any EMC problems that may occur either to the equipment or to any other equipment affected by the installation.

The TWINFLEX® SRP System

The TWINFLEX® SRP system is an intelligent ‘2-wire’ system utilising a conventional-type cabling

format. The system is classed as ‘Analogue non-addressable’ due to the architecture used within the design. All field devices including sounders can be connected to the zone via a common 2-core screened cable. The devices communicate with the Control Panel using the TWINFLEX

® data protocol.

Remote Status Indicator (RSI) The TWINFLEX

® Remote Status Indicator connects to a Control Panel and reports events that occur on

the system. It does not connect to any detection devices. The TWINFLEX

® RSI can also perform fire alarm system controls over the network (i.e. Silence Alarms,

Reset, Sound Alarms & Silence Buzzer). In addition, the RSI can put the system into the Manual Release ONLY operation mode and it can activate a Manual Extinguishant Release. A maximum of 8 RSI(s) can be connected to a single SRP Control Panel. The maximum cable length from the SRP Control Panel to an RSI is 500 metres. If 8 RSIs are used, they must all be within the maximum 500 metres cable length. All external connections are made on the back board. The Ext. Switches SW1 and SW2 are to be used for the external HOLD and RELEASE functions respectively. SW1 must be a momentary Normally Open switch. SW2 must be a Normally Open switch. If the Ext. Switches are not going to be implemented, then a 3.3KΩ EOL must be used for termination.

!

Page 7: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

7

Mounting the RSI

First identify the proposed location for the RSI. Ensure that it will be easily accessible and that account is taken of any subsequent work that may affect access. The RSI should be located at an access point to a building which is not covered by the SRP Control Panel. RSIs can also be located in other buildings which are connected to the SRP Control Panel. It should be mounted on a flat, vertical wall at a height where the indicators may be seen without difficulty. Do not locate the RSI at high level where stepladders or other access equipment may be required, in spaces with restricted access, or in a position that may require access panels to be removed. Do not locate the RSI where extremes of temperature or humidity may occur i.e. close to a heat source, or where there is any possibility of condensation or water ingress. Like all electronic equipment, the RSI may be affected by extreme environmental conditions. The position selected for its installation should therefore be clean and dry, not subjected to high levels of vibration or shock and at least 2 metres away from any pager or radio transmitting equipment. Ambient temperatures should be within the range given within the “Technical Data” section, e.g. not directly over a radiator or heater. In common with all microprocessor-controlled panels, the RSI may operate erratically or may be damaged if subjected to lightning-induced transients. Proper earth/ground connections will greatly reduce susceptibility to this problem.

Page 8: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

8

Page 9: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

9

Page 10: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

10

Physical Dimensions

Page 11: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

11

General Assembly

Ribbon Cable Connection

Fixing Front Panel To Back Box

Page 12: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

12

Installation and Commissioning

Topology & Cabling

All system wiring should be installed to comply with BS 5839: Pt 1: 2002 and BS 7671 (wiring regulations) and any other standards relevant to the area or type of installation. A cable complying with BS 5839: Pt 1: 2002 Category 1 (cable required to operate for prolonged periods during fire conditions) is required. This must be a 2-core 1.5mm

2 screened fire resistant cable (i.e. MICC, FP200, Firetuff,

Firecell, Lifeline or equivalent). In order to protect against possible data corruption it is important to ensure the following points are adhered to:

1. The cable screen must be connected to the SCRN terminal for each circuit at the RSI.

2. The cable screen must not be connected to earth/ground at any point other than the Control Panel (at the SCRN terminal provided). Do not connect the screen to a metal back box.

3. The cable screen continuity must be maintained at every point of the circuit, using the terminals provided or a suitable connection block.

4. Do not use a 4-core cable for 24V supply and communications, due to the possibility of data corruption. It is essential that two 2-core screened cables are used, one for the 24V DC supply and the other for communications.

Maximum Cable Lengths

The maximum total cable length from the Control Panel to an RSI is 500 metres for power and

communication. Up to 8 RSIs can be used but they must all be within the maximum 500 metres cable length. The maximum cable length from the RSI to the HOLD and RELEASE switches is 100 metres. Refer to the “Power Supply & Connections” and “Peripheral Bus Connections” sections below for further details.

Page 13: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

13

Power Supply & Connections

24V DC Power is provided to the RSI from the Control Panel via the AUX PWR 1 or AUX PWR 2 connectors on the SRP Control Panel connector board. The preferred cable to carry the 24V from the Control Panel to the RSI is 2-core 1.5mm

2 screened fire resistant cable (i.e. MICC, FP200, Firetuff,

Firecell, Lifeline or equivalent).

The maximum total cable length from the SRP Control Panel to an RSI is 500 metres. Up to 8 RSIs can be connected but they must all be within the maximum 500 metres cable length and must be wired +24V to +24V, 0V to 0V, Screen to Screen and so on.

Power Connection Table

SRP Control Panel First RSI Second RSI

AUX PWR + +24V +24V

AUX PWR - 0V 0V

SCRN Screen Screen

When powering an RSI from the panel, the extra current will reduce the battery backup run time and has to be allowed for in the battery calculations. NOTE: A jumper wire MUST be installed between the Screen of the Power and the Screen of the Peripheral Bus if power is provided by the SRP Control Panel.

Current Drawn by Single Remote Status Indicator @ 24.0V DC

Quiescent (default screen, back light off) 15.0mA

Controls enabled (back light on) 35.0mA

Separate Power Supply Requirements

The RSI can be powered by a separate 24V power supply if required. The RSI working voltage range is between 21V DC to 32V DC with a maximum current of 50.0mA. NOTE: If an RSI is powered from something other than the SRP Control Panel, the screen of the cable MUST be connected to the Screen of the back board but no jumper from Power Screen MUST be connected to the Screen of the Peripheral Bus.

Remote Status Indicator Back Board Power Supply Connections

Page 14: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

14

Peripheral Bus Connections

Communication between the SRP Control Panel and RSI is established via a multi-drop RS-485 Peripheral Bus using 2-core 1.5mm

2 screened fire resistant cable (i.e. MICC, FP200, Firetuff, Firecell,

Lifeline or equivalent).

The maximum total cable length from the Control Panel to an RSI is 500 metres. Up to 8 RSIs can be

used but they must all be within the maximum 500 metres cable length. The RSIs must be wired A to A, B to B, Screen to Screen and so on. The peripheral bus must be run from the SRP Control Panel to the first RSI, then to the second RSI and so on. The peripheral bus must not be spurred from one central point.

SRP Control Panel Connector Board Peripheral Bus Connections

There are two sets of peripheral bus connections on the SRP Control Panel Connector Board. These are connections A1/B1 and A2/B2. These are linked on the SRP Control Panel so either set can be used for the Field Connections. A 120Ω termination resistor must also be fitted across either A1/B1 or A2/B2 on the last RSI as indicated in the diagram below.

Remote Status Indicator Back Board Peripheral Bus Connections

The last RSI on the network must have a 120Ω End of Line (EOL) resistor fitted across A and B of the RSI PERIPHERAL BUS terminal NOTE: A jumper wire MUST be installed between the Screen of the Power and the Screen of the Peripheral Bus if power is provided by the SRP Control Panel.

Page 15: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

15

Ext Switches SW1 and SW2 Connection Examples

EXT SWITCHES SW1 must only be used for the HOLD operation. EXT SWITCHES SW2 must only be used for the RELEASE operation. The maximum cable length from the EXT SWITCHES connector on the RSI Back Board to the SW1-HOLD and SW2-RELEASE switches is 100 metres. The Activation Resistor may be either 680Ω or 470Ω. NOTE: A jumper wire MUST be installed between the Screen of the Switch Connection and the Screen of the Peripheral Bus.

RSI With External Switch Connections

RSI Without External Switch Connections. EOL must be present.

Page 16: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

16

SRP Control Panel Peripheral Bus Settings

To set up the SRP Control Panel to supervise the RSI(s) installed in the system, set the Write Enable switch to ON position, login with Engineer level access, and select “13 RSI SUPERVISION” from the MAIN MENU. Then using the UP/DOWN and LEFT/RIGHT arrow keys, navigate to each relevant RSI address and set the MODE to On. When this is done press ESC to return to the SRP Control Panel’s MAIN MENU. The SRP Control Panel will now be set up to supervise the selected RSI(s) and will report them as missing if there is a cable break or loss of communications. Set the Write Enable switch back to OFF position. NOTES:

If an RSI address MODE is turned ON and the RSI is not connected to the Peripheral Bus, the panel reports an “RSI Missing” fault.

The RSI must be supervised to be fully functional. The Home Screen on the RSI indicates that it is supervised by displaying a check mark next in the upper right corner of the display.

RSI Panel Settings

Setting RSI Address/Number

Each RSI has to be set with a unique address in the range 1 – 8, the default address is 1. This is done using DIL switches A0 to A2. NOTES:

The RSI must be reset or power cycled for changes to take effect.

The RSI address is indicated on the Home Screen in the upper right corner of the RSI display. Address Settings

A0 (1) A1 (2) A2 (3) RSI Address

Off Off Off 1

On Off Off 2

Off On Off 3

On On Off 4

Off Off On 5

On Off On 6

Off On On 7

On On On 8

RSI Buzzer

The local RSI internal buzzer can be switched off using DIL switch SP1 (4). Buzzer Setting

SP1 (4) Buzzer State

On Buzzer on

Off Buzzer off

This setting only affects the local buzzer state and has no effect on the panel buzzer or other RSIs on the system. NOTE: The RSI must be reset or power cycled for changes to take effect.

Page 17: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

17

LCD Contrast

LCD Contrast

The LCD contrast can be adjusted by rotating the screw on the variable resistor, located in the upper right of the main RSI PCB.

Powering Up

Turn on the SRP Control Panel to initialize the RSI. The RSI briefly displays the start-up message: When communication between the RSI and SRP Control Panel is established, the HOME screen shows the same date and time as displayed on the SRP Control Panel: NOTES:

The Time/Date format on the RSI is same as the SRP Control Panel.

The RSI displays the same Home Screen message as the SRP Control Panel (lines 2 and 3). If the Home Screen is modified on the SRP Control Panel, the Home Screen on the RSI gets updated automatically.

The RSI Access Level and Address is displayed in the upper right corner of the RSI display. “NM” is NORMAL access and “US” is USER access, depending on the Enable Key Switch position. The “x” represents the RSI address with a value between 1 and 8.

A check mark appears next to the Access Level to indicate that the RSI is being supervised.

RSI INITIALIZED WAITING FOR PANEL...

01/23/2016 04:56 √NMx TWINFLEX RELEASING FIKE(UK) Turn Key/Press Enter

Rotate anticlockwise to reduce the contrast

(lighten text)

Rotate clockwise to increase the contrast

(darken text)

Page 18: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

18

Commissioning

Ensure that the RSI has been correctly and securely mounted to the wall.

For each RSI, verify that the Date and Time match the date and time on the SRP Control Panel.

For each RSI, verify that a check mark appears in the upper right corner of the RSI Home Screen.

For each RSI, carry out all 5 tests from the “2. TEST MODES” option in the MAIN MENU.

Verify that the Current Events on the RSI are displayed correctly and match the Current Events on the SRP Control Panel.

If SW1 HOLD operation and SW2 RELEASE operation are being used, verify that they function correctly.

Ensure the system users and responsible persons have been trained properly. See the “End User Training” section below.

Fault finding

If the Date and Time do not update on the RSI and are not in sync with the SRP Control Panel, check the wiring between the SRP Control Panel and the RSI. If the supervision check mark is not present in the upper right corner of the RSI’s display, check the RSI supervision setting on the SRP Control Panel. Also, verify the address setting on the RSI. The SRP Control Panel reports an “RSI Missing” fault and the RSI reports an “SRP Communication Timeout . . .” message if the communication is lost between them. Check the wiring and the RSI supervision setting. The RSI reports a “NON-Supervised RSI Function Disabled” message when trying to view Current Events and the RSI is not being supervised by the SRP Control Panel. Fix the supervision setting on the SRP Control Panel.

Page 19: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

19

General Operation of Remote Status Indicator

RSI Front Panel

LED Indication

The LED operation of the RSI is described below. The LED indication can also be confirmed by checking the message displayed in the RSI information window or by accessing the relevant Current Event from the RSI menu. The SRP Control Panel logs may also be checked.

Description Colour State Reason

FIRE – 1 LED (left) Red Flashing The Control Panel is in the Fire 1 state. Other indicators will show the origin.

Continuous The Control Panel is in the fire state and sounders have been silenced.

FIRE – 2 LED (right) Red Flashing The Control Panel is in the Fire 2 state. Other indicators will show the origin.

Continuous The Control Panel is in the Fire 2 state and sounders have been silenced.

RELEASE IMMINENT Yellow Flashing The Control Panel has reached a pre-release state and the counter is counting down to release.

Continuous The Control Panel has reached a pre-release state and the counter is counting down to release and sounders have been silenced.

RELEASED Yellow Flashing The Control Panel has reached the release state and release outputs have been activated.

Continuous The Control Panel has reached the release state and release outputs have been activated and sounders have been silenced.

HOLD ACTIVE Yellow Flashing A hold activation has been received and the panel is currently in a hold mode. System operation will continue once the hold condition is cleared.

Continuous This LED goes continuous on a silence.

SYSTEM

POWER Green Continuous This indicates that power is being supplied to the RSI panel.

FAULT Yellow Flashing The Control Panel is in the fault state. Display will show details.

Continuous A Fault condition exists and the Silence Buzzer button has been activated

DISABLED Yellow Flashing An input, output or zone has been disabled on the Control Panel.

Continuous This LED goes continuous on a silence.

CONTROLS

ENABLE (fire alarm controls)

Yellow Continuous Fire Alarm Controls and Access Level 2 are enabled through the Enable Key Switch.

MANUAL (auto/manual)

Yellow

Continuous Manual mode operation has been enabled from this RSI panel.

Flashing Manual mode operation has been enabled from the Control Panel or other remote RSI panel.

General Indication LEDs System Indication LEDs

System

Controls

Auto/Manual

Key Switch

Extinguishant

Release

RSI Information

Window

Fire Alarm

Controls

Enable Key Switch

Page 20: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

20

Fire Alarm Controls

The Silence Alarms button will silence any fire alarm sounders that are currently sounding. The Reset System button will reset the SRP Control Panel and place the system into a non-alarm state. The Sound Alarms button will activate all fire alarm sounders. The Silence Buzzer button will silence the buzzer on the SRP Control Panel and all RSI panels.

System Controls

SELECTION ARROW

Press the ESC key to exit to the previous menu.

Extinguishant Release Controls

Auto/Manual operation When in ‘manual’ mode, the following will occur during a detection and release process: i. If a zone is enabled and it detects a fire, the panel will log the detection and operate like

normal. All appropriate outputs will activate, sounders will sound, the piezo will activate, etc. ii. If a SECOND zone activates, the panel will log the detection but will remain in Fire 1 and will

not advance to Pre-Release or Release. iii. If the system is placed back into ‘automatic’ mode, it will then advance to Pre-Release or

Release and proceed like normal.

VIEW CURRENT EVENTS 5. ALL EVENTS 1. FIRE EVENTS 2. FAULT EVENTS

The main Fire Alarm Controls may be enabled by turning the key switch to the controls enabled position to go from access level 1 to access level 2.

The menus may be navigated by using the UP / DOWN keys to move the required selection to the line with the SELECTION ARROW. Pressing enter will then select the chosen option. The top line shows the current menu name. In the example below, pressing enter will select the VIEW CURRENT FIRE EVENTS option.

The extinguishant release switch allows the user to manually release the extinguishing agent from the RSI. To operate the switch, the user must pull down the protective cover and then push the release button. The auto/manual key switch allows the user to place the fire alarm system in ‘automatic’ or ‘manual’ operation modes. When set to the default ‘automatic’ mode, the SRP Control Panel will operate in a normal fashion and will advance to release through automatic detection methods. The ‘manual’ LED will blink if the ‘manual’ mode has been set from the SRP Control Panel or by another RSI, and will be continuous if the adjacent key switch has been turned. When set to ‘manual’, the SRP Control Panel’s zone circuits will not advance the system into release. In this mode, the only way to release the extinguishant is to manually activate it.

Page 21: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

21

Access Levels

The menu system is divided into two access levels in order to restrict access to only those who require it. The Access Level status is indicated in two ways. The first way is by displaying an “NMx” for Normal Access or a “USx” for User Access, in the upper right corner of the HOME screen. The “x” indicates the address of the RSI and will have a value between 1 and 8. The second way the access level status is indicated is by the Controls Enabled light which shows the level selected as follows:

RSI Access Level Summary

Access Level

ACCESS Description

Home Screen Display

(upper right) (x = RSI Address)

Controls Enabled

LED

Key Operation

Normal View Current Events 1 – NMx OFF N/A

User Fire Alarm Controls

View Current Events

Test Modes

Status/Version

2 – USx ON YES

Access to the Fire Alarm Controls requires the operation of the Enable Key Switch to enter Access Level 2 (USx - User).

HOME SCREEN NORMAL ACCESS LEVEL 1 (NORMAL) – EXAMPLE RSI Address = 3

HOME SCREEN NORMAL ACCESS LEVEL 2 (USER) – EXAMPLE RSI Address = 3

01/23/2016 04:56 √NM3 TWINFLEX RELEASING FIKE(UK) Turn Key/Press Enter

01/23/2016 04:56 √US3 TWINFLEX RELEASING

FIKE(UK) Turn Key/Press Enter

Page 22: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

22

Access Level 1 (Normal)

At Access Level 1 (NMx - Normal), the main Fire Alarm Controls are disabled and only the View Current Events Menu can be accessed. The Fire Alarm Controls will only be accessible if the key switch is turned to “enabled”. The Fire Alarm Controls Enabled LED will be OFF in this mode.

NOTE: When in the Normal mode, the HOME screen will automatically change to display any fires or faults or other events from the SRP Control Panel. The latest event with the highest priority will be the event that the SRP Control Panel displays on the RSI.

SYSTEM EVENT DISPLAY FORMAT (FIRE, FAULTS, DISABLES, PANEL)

EVENT TYPE and Number of Events

EVENT SOURCE

EVENT DESCRIPTION

EVENT TIME AND DATE Pressing the enter or ESC button when in Access Level 1 will show the VIEW CURRENT EVENTS Menu with an arrow pointing to the events to be selected for viewing (Fire, Fault, Disable, Panel, or All events). The menu may be scrolled through by pressing the UP and DOWN arrow keys. Press the ESC key to exit the menu. Current Events are displayed in the format shown below and may be scrolled through by pressing the LEFT and RIGHT arrow keys.

The top line contains the event type and number of current events of that type.

The second line contains the time and date of the event.

The third line contains the event description. Note that these events are only the events that are currently active in the system.

CURRENT EVENT FORMAT (Showing Event 1 of 3)

EVENT TYPE and Number

EVENT TIME AND DATE (See NOTE)

EVENT DESCRIPTION

Press the ESC key to exit the menu once viewing is complete.

PANEL 01/03 08:56:06 05-MAR-2016 PANEL RESET Press //ESC

FAULT EVENT NO.3 PANEL EARTH FAULT 12:24:59 05-MAR-2016

Page 23: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

23

Access Level 2 (User):

At Access Level 2 (user), the main Fire Alarm Controls are enabled and the following menus are accessible. Pressing the enter button when in level 2 shows the MAIN MENU. The available options are shown below and may be scrolled through by pressing the UP and DOWN arrow keys. Press the ESC key to exit the menu. The Fire Alarm Controls Enabled LED will be ON in this mode.

MAIN MENU 1. VIEW EVENTS 2. TEST MODES 3. STATUS/VERSION

VIEW CURRENT EVENTS 1. FIRE EVENTS 2. FAULT EVENTS 3. DISABLE EVENTS 4. PANEL EVENTS 5. ALL EVENTS

TEST MODES 1. TEST LEDS 2. TEST KEYPAD 3. TEST BUZZER 4. TEST LCD 5. TEST BACKLIGHT The TEST LEDS option causes the panel LEDs to toggle on/off and will illuminate to ensure correct operation. The test will count down and return to the TEST MODES menu screen. The TEST KEYPAD option enables the user to test all buttons and key switches to ensure proper function. The display will give feedback as each button is operated. Press the ESC key twice in a row to exit the test. The TEST BUZZER option turns the buzzer on (regardless of the DIL switch SP1 (4) position) to ensure buzzer operation. The test will count down and return to the TEST MODES menu screen.

VIEW CURRENT EVENTS 5. ALL EVENTS 1. FIRE EVENTS 2. FAULT EVENTS

TEST MODES: 5. TEST BACKLIGHT 1. TEST LEDS 2. TEST KEYPAD

LED TEST In Progress 10 Press ESC to EXIT

KEYPAD TEST In Progress RIGHT arrow-Press ESC&ESC to End Test

BUZZER TEST In Progress 10 Press ESC to EXIT

MAIN MENU: 3. STATUS/VERSION 1. VIEW EVENTS 2. TEST MODES

Page 24: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

24

The TEST LCD option causes the LCD to black out each character in succession to ensure correct operation. The test will count down and return to the TEST MODES menu screen. The TEST BACKLIGHT option causes the panel backlight to blink to ensure correct operation. The test will count down and return to the TEST MODES menu screen.

STATUS/VERSION 1. ADDRESS STATUS 2. BUZZER STATUS 3. SOFTWARE VERSION The ADDRESS STATUS option displays the current RSI address that is set by the DIL switches A0 to A2 located next to the buzzer. The display will time out and return to the STATUS/VERSION screen. The BUZZER STATUS option displays the current RSI buzzer state set by the DIL switch SP1. The display will time out and return to the STATUS/VERSION screen. The SOFTWARE VERSION option displays the current RSI Software Version. The display will time out and return to the STATUS/VERSION screen.

STATUS/VERSION: 3. SOFTWARE VERSION 1. ADDRESS STATUS 2. BUZZER STATUS

BACKLIGHT TEST In Progress 10 Press ESC to EXIT

RSI Address: 8 Press ESC to EXIT

Buzzer: Disabled

Press ESC to EXIT

RSI SW Ver: 01.000

Press ESC to EXIT

Page 25: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

25

End User Training

A Fire Alarm System is of little use if the end user and/or the responsible persons who will be present in the building do not know how to operate and respond to the system. It is therefore essential that commissioning includes training for the users of the system and responsible persons.

User instructions and a Zone Chart should be left adjacent to the SRP Control Panel. As access to the system must be controlled by responsible persons, it would be unusual to display the access codes on this notice. These codes must however be available for the responsible persons, so ensure that they know and record them in a secure place.

The TWINFLEX® SRP User Guide should be explained and left with the responsible person on site, for

storage in an accessible and known location, in order that the responsible person and the service engineer may keep information records up to date.

A single page user instruction sheet is included at the end of this manual. A copy of this should be mounted adjacent to the Control Panel.

Maintenance

The RSI does not require user maintenance, however periodic functional checks should be carried out by an engineer or responsible persons.

Technical Data

Remote Status Indicator Specification

Dimensions (mm) 250 x 140 x 85

Weight 650 grams

Construction UL94-V0 rated ABS

Cable Entry 6 x 20mm knockouts, 4 x double 20mm knockouts

Cable type 2 core 1.5mm2 screened fire rated cable

Operating voltage Nominal 24V DC (Range 21 - 32V DC)

Operating current Quiescent @ 24V DC 15 mA (back light off)

Operating current Max @ 24V DC 35 mA (controls enabled, back light on)

Communications Multi-drop RS-485

Total peripheral bus length 500m (max)

IP rating 30

Maximum number of RSI per Control Panel 8

Operating temperature -5OC to 40

OC, Class A

Page 26: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

26

Fire Alarm System Notice

To Enable the Control Panel Keys

To prevent unauthorised operation, the controls should be kept disabled and the key kept secure under the control of the responsible person.

To Manually Operate the Fire Alarm Sounders

.

Following a Fire Alarm Operation

Following a Fault Condition

Enable the controls and then press ‘SOUND ALARMS’.

To silence the alarm sounders press ‘SILENCE ALARMS’.

You may gain access to the fire alarm controls by inserting the key turning ¼ turn. The ‘Controls Enabled’ LED should then be illuminated. To disable the Control Panel keys, turn the key switch off. When disabled, the ‘Enabled’ LED should then be extinguished.

The red ‘FIRE’ LED will illuminate. The fire alarms and the internal buzzer will operate as programmed. Take appropriate action as defined by the emergency plan for the premises. To silence the alarm press ‘SILENCE ALARMS’, then establish the cause of the alarm and enter the details in the log book. Reset any Manual Call Points which may have been operated, or if a detector has been operated be sure that the cause of the alarm has been removed, before resetting the system by pressing ‘RESET SYSTEM’.

The fault LED will illuminate. The internal buzzer will sound. To mute the internal buzzer press ‘SILENCE BUZZER’. Investigate and rectify the appropriate fault (competent persons). Once the fault has been rectified the fault indication will clear automatically.

Page 27: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

27

Important Notes

FIRE ALARM COMPANY: ________________________________________________________________________________ ADDRESS: ______________________________________________________________________ For Service Phone: _________________(During Working Hours) ________________(Out of Working Hours)

FIRE ALARM COMPANY:

ADDRESS:

FOR SERVICE CALL: (Working hours) (Call Out)

Page 28: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

28

Fire Alarm User Notice

Note

The Fire alarm system installed in this building has ‘Alarm Confirmation’ technology to help eliminate false alarms.

Please read and understand the following information in order to make the most use of the system.

Action Required

If you think that you may have accidentally set off the fire alarms, then check the following: If the fire alarm within your area only is sounding, then check your own area for the cause of the alarm. If this proves to be a false alarm due to dust, cooking fumes, steam, cigarette smoke, etc. then clear the smoke from the area and press reset on the Control Panel. If the alarm state does not re-annunciate then no further action is required. If the fire alarms in the communal areas are also sounding, then follow the building’s fire procedures for evacuation. If you discover a genuine fire, then follow the building’s fire procedures for evacuation, activating the nearest Fire Alarm manual call point on the way out if the alarms are not already sounding.

Do not attempt to put out the fire unless it is safe to do so.

Further Information

Further information will be located adjacent to the Main Fire Alarm Control Panel, or may be obtained from either the person responsible for building maintenance or from the Fire Alarm Company responsible for maintaining the Fire Alarm System.

Page 29: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

29

Engineers Notes

Page 30: 8 Zone Expansion PCB - Fike

TWINFLEX® SRP Remote Status Indicator Engineering and Commissioning Manual

30

15

0834

Fike Safety Technology Ltd,

31 Springvale Ind Est, Cwmbran, UK. NP44 5BD

15 DoP-100-0002

100 - 0002

Intended for use in the fire detection and

fire alarm - Fixed fire fighting and gas

extinguishing systems in and around

buildings

Technical Support Contact your distributor for technical support on this product.