7SD5xx_Manual_A1_V043003_en (1)
-
Upload
ngocanh2007 -
Category
Documents
-
view
215 -
download
0
Transcript of 7SD5xx_Manual_A1_V043003_en (1)
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
1/696
SIPROTEC
Line Differential Protection
with Distance Protection
7SD5
V 4.3
Manual
C53000-G1176-C169-1
Preface
Introduction
1Functions 2Mounting and Commissioning 3Technical Data 4
Appendix ALiterature
Glossary
Index
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
2/696
2 7SD5 ManualC53000-G1176-C169-1
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
3/696
7SD5 Manual
C53000-G1176-C169-1
Disclaimer of liability
We have checked the text of this manual against the hardwareand software described. However, deviations from the descrip-tion cannot be completely ruled out, so that no liability can be ac-cepted for any errors or omissions contained in the informationgiven.
The information in this manual is checked periodically, and nec-essary corrections will be included in future editions. We appreci-
ate any suggested improvements.We reserve the right to make technical improvements withoutnotice.
Copyright
Copyright Siemens AG 2004. All rights reserved.
Dissemination or reproduction of this document, or evaluationand communication of its contents, is not authorized exceptwhere expressly permitted. Violations are liable for damages. Allrights reserved, particularly for the purposes of patent applicationor trademark registration.
Registered Trademarks
SIPROTEC, SINAUT, SICAM and DIGSI are registered trade-marks of SIEMENS AG. Other designations in this manual maybe trademarks that if used by third parties for their own purposesmay violate the r ights of the owner.
4.30.03
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
4/696
4 7SD5 ManualC53000-G1176-C169-1
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
5/696
57SD5 ManualC53000-G1176-C169-1
Preface
Purpose of this
Manual
This manual describes the functions, operation, installation, and commissioning of the
device 7SD5. In particular, one will find:
Descriptions of device functions and settings Chapter 2;
Instructions for mounting and commissioning Chapter 3;
List of technical data Chapter 4;
As well as a compilation of the most significant data for experienced users Ap-pendix A.
General information about design, configuration, and operation of SIPROTEC 4
devices are laid down in the SIPROTECSystem Description /1/.
Target Audience Protection engineers, commissioning engineers, personnel concerned with adjust-
ment, checking, and service of selective protective equipment, automatic and control
facilities, and personnel of electrical facilities and power plants.
Applicability of this
Manual
This manual is valid for: SIPROTEC4 Line Differential Protection with Distance
Protection 7SD5; firmware version V 4.3.
Indication of
Conformity
This product is UL-certified according to the Technical Data:
Additional Support Should further information on the System SIPROTEC4 be desired or should partic-
ular problems arise which are not covered sufficiently for the purchaser's purpose, the
matter should be referred to the local Siemens representative.
This product complies with the directive of the Council of the European Communi-ties on the approximation of the laws of the Member States relating to electromag-
netic compatibility (EMC Council Directive 89/336/EEC) and concerning electrical
equipment for use within specified voltage limits (Low-voltage directive 73/23
EEC).
This conformity is proved by tests conducted by Siemens AG in accordance with
Article 10 of the Council Directive in agreement with the generic standards EN
50081 and EN 61000-6-2 for EMC directive, and with the standard EN 60255-6 for
the low-voltage directive.
The product conforms with the international standard of the series IEC 60255 and
the German standard VDE 0435.
Further Standards IEEE Std C37.90-*
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
6/696
Preface
6 7SD5 ManualC53000-G1176-C169-1
Training Courses Individual course offerings may be found in our Training Catalogue, or questions may
be directed to our training centre in Nuremberg.
WARNING!
Hazardous voltages are present in this electrical equipment during operation.
Failure to observe these precautions can result in death, personal injury, or serious
material damage.
Only qualified personnel shall work on and in the vicinity of this equipment. The per-
sonnel must be thoroughly familiar with all warnings and maintenance procedures of
this manual as well as the safety regulations.
Successful and safe operation of the device is dependent on proper transportation,
storage, mounting and assembly and the observance of the warnings and instructions
of the unit manual.
Of particular importance are the general installation and safety regulations for work in
a high-voltage environment (for example, VDE, IEC, EN, DIN, or other national and
international regulations). These regulations must be observed.
Instructions andWarnings The warnings and notes contained in this manual serve for your own safety and foran appropriate lifetime of the device. Please observe them!
The following indicators and standard definitions are used:
DANGER!
indicates that death, severe personal injury or substantial property damage can
result if proper precautions are not taken.
Warning
indicates that death, severe personal injury or substantial property damage can
result if proper precautions are not taken.
Caution
indicates that minor personal injury or property damage can result if proper precau-
tions are not taken. This particularly applies to damage on or in the device itself andconsequential damage thereof.
Note:
indicates information about the device or respective part of the instruction manual
which is essential to highlight.
Definition QUALIFIED PERSONNEL
Prerequisites to proper and safe operation of this product are proper transport,
proper storage, setup, installation, operation, and maintenance of the product, as
well as careful operation and servicing of the device within the scope of the warn-
ings and instructions of this manual. Qualifications are:
Training and Instruction to energize, de-energize, clear, ground and tag circuits
and equipment in accordance with established safety practices.
Training and instruction (or other qualification) for switching, earthing, and des-
ignating devices and systems.
Training in rendering first aid.
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
7/696
Preface
77SD5 ManualC53000-G1176-C169-1
Deviations may be permitted in drawings and tables when the type of designator can
be obviously derived from the illustration.
The following symbols are used in drawings:
Besides these, graphical symbols are used according to IEC 60617-12 and IEC
60617-13 or symbols derived from these standards. Some of the most frequently used
are listed below:
Typographic and
Graphical Conven-
tions
To designate terms which refer in the text to information of the device or for the
device, the following fonts are used:
Parameter names
Designators of configuration or function parameters which may appear word-for-word in the display of the device or on the screen of a personal computer (with op-
eration software DIGSI), are marked in bold letters of a monospace type style. This
also applies to header bars for selection menus.
1234A
Parameter addresses have the same character style as parameter names. Param-
eter addresses contain the suffixAin the overview tables if the parameter can onlybe set in DIGSI via the option Display additional settings.
Parameter Conditions
Possible settings of text parameters, which may appear word-for-word in the
display of the device or on the screen of a personal computer (with operation soft-
ware DIGSI), are additionally written in italics. This also applies to header bars for
selection menus.
Annunciations
Designators for information, which may be output by the relay or required from other
devices or from the switch gear, are marked in a monospace type style in quotation
marks.
Device-internal logical input signal
Device-internal (logical) output signal
Internal input signal of an analog quantity
External binary input signal with number (binary input, input
indication)
External binary output signal with number (device indication)
External binary output signal with number (device indication)
used as input signal
Example of a parameter switch designated FUNCTION with
the address 1234 and the possible settings ON and OFF
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
8/696
Preface
8 7SD5 ManualC53000-G1176-C169-1
Input signal of an analog quantity
AND gate
OR gate
ExclusiveOR gate (antivalence): output is active, if only
oneof the inputs is active
Equivalence: output is active, if bothinputs are active or in-
active at the same time
Dynamic inputs (edgetriggered) above with positive, below
with negative edge
Formation of one analog output signal from a number of
analog input signals
Limit stage with setting address and parameter designator
(name)
Timer (pickup delay T, example adjustable) with setting
address and parameter designator (name)
Timer (dropout delay T, example non-adjustable)
Dynamic triggered pulse timer T (monoflop)
Static memory (RS-flipflop) with setting input (S), resetting
input (R), output (Q) and inverted output (Q)
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
9/696
97SD5 ManualC53000-G1176-C169-1
Contents
1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
1.1 Overall Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
1.2 Application Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
1.3 Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
2 Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
2.1.1 Functional Scope. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
2.1.1.1 Configuration of the Scope of Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
2.1.1.2 Control of the Main Protection Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
2.1.1.3 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
2.1.1.4 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
2.1.2 General Power System Data (Power System Data 1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
2.1.2.1 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
2.1.2.2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
2.1.3 Change Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
2.1.3.1 Purpose of the Setting Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 552.1.3.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
2.1.3.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
2.1.3.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
2.1.4 General Protection Data (Power System Data 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
2.1.4.1 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
2.1.4.2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
2.1.4.3 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
2.2 Protection Data Interfaces and Protection Data Topology. . . . . . . . . . . . . . . . . . . . . . . . . . 74
2.2.1 Functional Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
2.2.1.1 Protection Data Topology / Protection Data Communication. . . . . . . . . . . . . . . . . . . . . . . . 74
2.2.2 Protection Data Interfaces. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 812.2.2.1 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
2.2.2.2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
2.2.2.3 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
2.2.3 Differential Protection Topology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
2.2.3.1 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
2.2.3.2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
2.2.3.3 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
10/696
Contents
10 7SD5 ManualC53000-G1176-C169-1
2.3 Differential Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
2.3.1 Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
2.3.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
2.3.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
2.3.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
2.4 Breaker Intertrip and Remote Tripping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
2.4.1 Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
2.4.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
2.4.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
2.4.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
2.5 Distance Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
2.5.1 Distance Protection, General Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
2.5.1.1 Earth Fault Detection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
2.5.1.2 Fault Detection (optional). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
2.5.1.3 Calculation of the Impedances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
2.5.1.4 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
2.5.1.5 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
2.5.1.6 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
2.5.2 Distance Protection with Quadrilateral Characteristic (optional) . . . . . . . . . . . . . . . . . . . . 137
2.5.2.1 Method of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
2.5.2.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
2.5.2.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
2.5.3 Distance Protection with MHO Characteristic (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . 150
2.5.3.1 Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
2.5.3.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
2.5.3.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
2.5.4 Tripping Logic of the Distance Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
2.5.4.1 Method of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
2.5.4.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
2.6 Power Swing Detection (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
2.6.1 Method of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
2.6.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
2.6.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
2.6.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
11/696
Contents
117SD5 ManualC53000-G1176-C169-1
2.7 Teleprotection for Distance Protection (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
2.7.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
2.7.2 Method of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
2.7.3 PUTT (Pickup) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
2.7.4 Permissive Underreach Transfer Trip with Zone Acceleration Z1B (PUTT) . . . . . . . . . . 1792.7.5 Direct Underreach Transfer Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
2.7.6 Permissive Overreach Transfer Trip (POTT). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
2.7.7 Directional Comparison Pickup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
2.7.8 Directional Unblocking Scheme. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
2.7.9 Directional Blocking Scheme. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
2.7.10 Pilot Wire Comparison. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
2.7.11 Reverse Interlocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
2.7.12 Transient Blocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
2.7.13 Measures for Weak and Zero Infeed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
2.7.14 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
2.7.15 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
2.7.16 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
2.8 Earth Fault Protection in Earthed Systems (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207
2.8.1 Method of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207
2.8.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
2.8.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
2.8.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
2.9 Teleprotection for Earth Fault Protection (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
2.9.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2322.9.2 Directional Comparison Pickup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
2.9.3 Directional Unblocking Scheme. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
2.9.4 Directional Blocking Scheme . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
2.9.5 Transient Blocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242
2.9.6 Measures for Weak or Zero Infeed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
2.9.7 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
2.9.8 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
2.9.9 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
2.10 Weak-infeed Tripping (optional). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
2.10.1 Classical Tripping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
2.10.1.1 Method of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
2.10.1.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
2.10.2 Tripping According to Specification RTE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
2.10.2.1 Functional Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
2.10.2.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
2.10.3 Weak Infeed Tripping (optional). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
2.10.3.1 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
2.10.3.2 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
12/696
Contents
12 7SD5 ManualC53000-G1176-C169-1
2.11 Direct Local Trip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260
2.11.1 Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260
2.11.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
2.11.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
2.11.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
2.12 Direct Remote Trip and Transmission of Binary Information . . . . . . . . . . . . . . . . . . . . . . . 262
2.12.1 Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262
2.12.2 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
2.13 Instantaneous High-Current Switch-onto-Fault Protection (SOTF) . . . . . . . . . . . . . . . . . . 265
2.13.1 Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265
2.13.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 266
2.13.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
2.13.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268
2.14 Backup Time Overcurrent Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269
2.14.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269
2.14.2 Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269
2.14.3 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275
2.14.4 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281
2.14.5 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 282
2.15 Automatic Reclosure Function (optional). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 284
2.15.1 Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285
2.15.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 301
2.15.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3092.15.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
2.16 Synchronism and Voltage Check (optional). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314
2.16.1 Method of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314
2.16.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 318
2.16.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 322
2.16.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 323
2.17 Undervoltage and Overvoltage Protection (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325
2.17.1 Overvoltage Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325
2.17.2 Undervoltage Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3302.17.3 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
2.17.4 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338
2.17.5 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 340
2.18 Frequency Protection (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 342
2.18.1 Method of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 342
2.18.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 344
2.18.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346
2.18.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 347
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
13/696
Contents
137SD5 ManualC53000-G1176-C169-1
2.19 Fault Locator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 348
2.19.1 Functional Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 348
2.19.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 352
2.19.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356
2.19.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356
2.20 Circuit Breaker Failure Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 358
2.20.1 Functional Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 358
2.20.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 368
2.20.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 371
2.20.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 372
2.21 Thermal Overload Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373
2.21.1 Method of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373
2.21.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 374
2.21.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3762.21.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376
2.22 Monitoring Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 378
2.22.1 Measurement Supervision. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 378
2.22.1.1 Hardware Monitoring Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 378
2.22.1.2 Software Monitoring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 380
2.22.1.3 Measuring Circuit Monitoring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 381
2.22.1.4 Malfunction Responses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 386
2.22.1.5 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 388
2.22.1.6 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 390
2.22.1.7 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 391
2.22.2 Trip Circuit Supervision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3912.22.2.1 Functional Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 392
2.22.2.2 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395
2.22.2.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395
2.22.2.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395
2.23 Function Control and Circuit Breaker Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 396
2.23.1 Function Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 396
2.23.1.1 Line Energization Recognition. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 396
2.23.1.2 Detection of the Circuit Breaker Position. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 399
2.23.1.3 Open Pole Detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 402
2.23.1.4 Pickup Logic for the Entire Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 403
2.23.1.5 Tripping Logic of the Entire Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4042.23.2 Circuit Breaker Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 409
2.23.2.1 Functional Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 409
2.23.2.2 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 410
2.23.3 Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .411
2.23.3.1 Trip-dependent Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .411
2.23.3.2 Spontaneous Indications on the Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .411
2.23.3.3 Switching Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .411
2.23.3.4 Setting Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 412
2.23.3.5 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 412
2.23.3.6 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 412
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
14/696
Contents
14 7SD5 ManualC53000-G1176-C169-1
2.24 Ancillary Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 414
2.24.1 Commissioning Tools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 414
2.24.1.1 Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 414
2.24.1.2 Setting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 415
2.24.1.3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 416
2.24.2 Processing of Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 416
2.24.2.1 Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 416
2.24.3 Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 421
2.24.3.1 Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 421
2.24.3.2 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 421
2.24.4 Measurement During Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 423
2.24.4.1 Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 423
2.24.4.2 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 425
2.24.5 Differential Protection Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 427
2.24.5.1 Measured Values of the Differential Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 427
2.24.5.2 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 427
2.24.6 Remote Measured Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4282.24.6.1 Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 428
2.24.7 Measured Values Constellation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 429
2.24.7.1 Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 429
2.24.8 Oscillographic Fault Records. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 429
2.24.8.1 Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 429
2.24.8.2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 430
2.24.8.3 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 430
2.24.9 Demand Measurement Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 431
2.24.9.1 Long-term Average Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 431
2.24.9.2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 431
2.24.9.3 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 431
2.24.10 Min/Max Measurement Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 432
2.24.10.1 Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 432
2.24.10.2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 432
2.24.10.3 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 432
2.24.11 Set Points (Measured Values) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 434
2.24.11.1 Limit Value Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 434
2.24.11.2 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 434
2.24.12 Energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 435
2.24.12.1 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 435
2.25 Command Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 436
2.25.1 Control Authorization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4362.25.1.1 Command Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 436
2.25.1.2 Sequence in the Command Path . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 437
2.25.1.3 Switchgear Interlocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 438
2.25.1.4 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 441
2.25.2 Control Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 441
2.25.2.1 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 441
2.25.3 Process Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 442
2.25.3.1 Method of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 442
2.25.3.2 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 442
2.25.4 Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 443
2.25.4.1 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 443
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
15/696
Contents
157SD5 ManualC53000-G1176-C169-1
3 Mounting and Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 445
3.1 Mounting and Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 446
3.1.1 Configuration Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 446
3.1.2 Hardware Modifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 451
3.1.2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4513.1.2.2 Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 453
3.1.2.3 Switching Elements on Printed Circuit Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455
3.1.2.4 Interface Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 462
3.1.2.5 Reassembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 466
3.1.3 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 466
3.1.3.1 Panel Flush Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 466
3.1.3.2 Rack Mounting and Cubicle Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 468
3.1.3.3 Panel Surface Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 470
3.2 Checking Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 471
3.2.1 Checking Data Connections of Serial Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 471
3.2.2 Checking the Protection Data Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 473
3.2.3 Power Plant Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 474
3.3 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 477
3.3.1 Test Mode / Transmission Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 478
3.3.2 Checking the Time Synchronization Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 478
3.3.3 Checking the System Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 479
3.3.4 Checking the States of the Binary Inputs/Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 481
3.3.5 Checking the Protection Data Topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 484
3.3.6 Tests for the Circuit Breaker Failure Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 490
3.3.7 Checking the Instrument Transformer Connections of One Line End . . . . . . . . . . . . . . . . 4923.3.8 Checking the Instrument Transformer Connections of Two Line Ends . . . . . . . . . . . . . . . 494
3.3.9 Checking the Instrument Transformer Connections for More than Two Ends. . . . . . . . . . 506
3.3.10 Measuring the Operating Time of the Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . 507
3.3.11 Checking the Teleprotection System with Distance Protection . . . . . . . . . . . . . . . . . . . . . 508
3.3.12 Testing the Signal Transmission with Earth Fault Protection. . . . . . . . . . . . . . . . . . . . . . . .511
3.3.13 Checking the Signal Transmission for Breaker Failure Protection and/or
Stub Fault Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 513
3.3.14 Checking the Signal Transmission for Internal and External Remote Tripping . . . . . . . . . 513
3.3.15 Testing User-Defined Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 513
3.3.16 Trip and Close Test with the Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5143.3.17 Trip/Close Tests for the Configured Operating Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . 514
3.3.18 Triggering Oscillographic Recordings for Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 515
3.4 Final Preparation of the Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 516
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
16/696
Contents
16 7SD5 ManualC53000-G1176-C169-1
4 Technical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 517
4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 519
4.1.1 Analog Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 519
4.1.2 Auxiliary voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 520
4.1.3 Binary Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 520
4.1.4 Communications Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 522
4.1.5 Electrical Tests. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 526
4.1.6 Mechanical Stress Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 528
4.1.7 Climatic Stress Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 529
4.1.8 Service Conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 529
4.1.9 Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 530
4.1.10 Mechanical Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 530
4.2 Protection Data Interfaces and Differential Protection Topology . . . . . . . . . . . . . . . . . . . . 531
4.3 Differential Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 533
4.4 Breaker Intertrip and Remote Tripping -Direct Local Trip . . . . . . . . . . . . . . . . . . . . . . . . . 535
4.5 Distance Protection (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 536
4.6 System Power Swing (with impedance) (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 539
4.7 Teleprotection for Distance Protection (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 540
4.8 Earth Fault Protection in Earthed Systems (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 541
4.9 Teleprotection for Earth Fault Protection (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 550
4.10 Weak-infeed Tripping (classic/optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 551
4.11 Weak-infeed Tripping (French specif./optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 552
4.12 Direct Remote Trip and Transmission of Binary Information . . . . . . . . . . . . . . . . . . . . . . . 553
4.13 Instantaneous High-Current Switch-onto-Fault Protection (SOTF) . . . . . . . . . . . . . . . . . . 554
4.14 Time Overcurrent Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 555
4.15 Automatic Reclosure Function (optional). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 558
4.16 Synchronism and Voltage Check (optional). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 559
4.17 Undervoltage and Overvoltage Protection (optional). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 561
4.18 Frequency Protection (optional). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 564
4.19 Fault Locator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 565
4.20 Circuit Breaker Failure Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 566
4.21 Thermal Overload Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 567
4.22 Monitoring Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 569
4.23 User Defined Functions (CFC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 571
4.24 Additional Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 574
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
17/696
Contents
177SD5 ManualC53000-G1176-C169-1
4.25 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 577
4.25.1 Panel Flush and Cubicle Mounting (Housing Size 1/2) . . . . . . . . . . . . . . . . . . . . . . . . . . . 577
4.25.2 Panel Flush and Cubicle Mounting (Housing Size 1/1)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 578
4.25.3 Panel Surface Mounting (Housing Size1
/2). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5794.25.4 Panel Surface Mounting (Housing Size 1/1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 579
A Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 581
A.1 Ordering Information and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 582
A.1.1 Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 582
A.1.1.1 Ordering Code (MLFB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 582
A.1.2 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 586
A.2 Terminal Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 590
A.2.1 Panel Flush Mounting or Cubicle Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 590A.2.2 Panel Surface Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 595
A.3 Connection Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 602
A.3.1 Current Transformer Connection Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 602
A.3.2 Voltage Transformer Connection Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 606
A.4 Default Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 609
A.4.1 LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 609
A.4.2 Binary Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 610
A.4.3 Binary Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .611
A.4.4 Function Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 612A.4.5 Default Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 612
A.4.6 Pre-defined CFC Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 615
A.5 Protocol-dependent Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 616
A.6 Functional Scope. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 617
A.7 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 619
A.8 Information List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 638
A.9 Group Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 673
A.10 Measured Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 674
Literature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 681
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 683
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 691
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
18/696
Contents
18 7SD5 ManualC53000-G1176-C169-1
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
19/696
197SD5 ManualC53000-G1176-C169-1
Introduction 1The SIPROTECLine Differential Protection with Distance Protection 7SD5 is intro-
duced in this chapter. The 7SD5 is presented in its application, characteristics, and
functional scope.
1.1 Overall Operation 20
1.2 Application Scope 23
1.3 Characteristics 27
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
20/696
1 Introduction
20 7SD5 ManualC53000-G1176-C169-1
1.1 Overall Operation
The SIPROTECline protection 7SD5 is equipped with a powerful microcomputer
system. This provides fully numerical processing of all functions in the device, from the
acquisition of the measured values up to the output of commands to the circuit break-ers, as well as the exchange of measured data with the other ends of the protected
area. Figure 1-1shows the basic structure of the device.
Analog Inputs The measuring inputs (MI) convert the currents and voltages coming from the instru-
ment transformers and adapt them to the level appropriate for the internal processing
of the device. The device has 4 current and 4 voltage inputs. Three current inputs are
provided for measurement of the phase currents, a further measuring input (I4) may
be configured to measure the earth current (residual current from the current trans-
former star-point or separate earth current transformer), the earth current of a parallel
line (for parallel line compensation) or the star-point current of a power transformer (for
earth fault direction determination).
Figure 1-1 Hardware structure of the line differential protection 7SD5
A voltage input is provided for each phase-earth voltage. The connection of voltage
transformers is not required for differential protection, but for using distance protection
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
21/696
1.1 Overall Operation
217SD5 ManualC53000-G1176-C169-1
and other ancillary functions. A further voltage input (U4) may optionally be used to
measure either the displacement voltage, for a busbar voltage (for synchronism and
voltage check) or any other voltage UX(for overvoltage protection). The analog signals
are then routed to the input amplifier group IA.
The input amplification IA stage provides high-resistance terminations for the analog
input quantities. It contains filters that are optimized with regard to bandwidth and pro-
cessing speed.
The AD analog digital converter group contains analog/digital converters and memory
chips for data transfer to the microcomputer system.
Microcomputer
System
Apart from processing the measured values, the microcomputer system also executes
the actual protection and control functions. In particular, the following are included:
Decisions for trip and close commands,
Continuous supervision of measured signals.
Monitoring of the pickup conditions of the individual protection functions.
Formation of the local differential protection values (phasor analysis and chargecurrent computation) and creation of the transmission protocol.
Decoding of the received transmission protocol, synchronization of differential pro-
tection values and summing up of the differential currents and charge currents,
Monitoring of the communication with the other devices part of the line protection
system
Interrogation of threshold values and time sequences.
Processing of signals for the logic functions.
Decisions for trip and close commands
Storage of messages, fault annunciations as well as fault records for system fault
analysis
Operating system and related function management such as, e.g., data recording,
real-time clock, communication, interfaces, etc.
The information is provided via output amplifier OA.
Binary Inputs and
Outputs
The microcomputer system obtains external information through binary inputs such as
remote resetting or blocking commands for protection functions. The computer system
obtains the information from the system (e.g remote resetting) or the external equip-
ment (e.g. blocking commands). These outputs include, in particular, trip commands
to circuit breakers and signals for remote annunciation of important events and condi-
tions.
Front Elements Light emitting diodes (LEDs) and a display screen (LCD) on the front panel provide
information such as measured values, messages related to events or faults, status,
and functional status of the device.
Integrated control and numeric keys in conjunction with the LCD facilitate local inter-
action with the device. All information of the device can be accessed using the inte-
grated control and numeric keys. The information includes protective and control set-
tings, operating and fault messages, and measured values (see also Chapter 2 and
SIPROTEC4 System Description /1/).
Using integrated switchgear control functions, the control of circuit breakers and other
equipment is possible from the device front panel.
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
22/696
1 Introduction
22 7SD5 ManualC53000-G1176-C169-1
Serial Interfaces Via the serial operator interface in the front panel the communication with a personal
computer using the operating program DIGSIis possible. This permits convenient
operation of all functions of the device.
The service interface can also be used for communication with a personal computer
using DIGSI. This port is especially well suited for dedicated connection of the
devices to the PC or for operation via a modem.
All device data can be transferred to a central master or main control system through
the serial system (SCADA) interface. This interface may be provided with various pro-
tocols and physical transmission modes to suit the particular application.
Another interface is provided for the time synchronization of the internal clock via ex-
ternal synchronization sources.
The operator and service interface allow the communication from one PC with the
devices at all ends of the protected object during commissioning, checking and also
during operation of the device, using a standard browser. A software program named
WEB-Monitor) supports this function which has been optimized with regard to the
line protection system.
Protection Data
Interfaces
The protection data interfaces are a particular case. Depending on the model there are
one or two protection data interfaces. Via these interfaces the measured value data of
each end of the protected object is transmitted to the other ends; during this procedure
measured values from the other ends may also be added. Further information such as
closing the local circuit breaker, pickup of the inrush restraint as well as other external
trip commands coupled via binary inputs or binary information can be transmitted to
other ends via the protection data interfaces.
Power Supply These described functional units are supplied by a current supply PS with the neces-
sary power in the different voltage levels. Brief supply voltage dips which may occur
on short circuits in the auxiliary voltage supply of the devices are usually bridged by acapacitor (see also Technical Data, Chapter 4.1).
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
23/696
1.2 Application Scope
237SD5 ManualC53000-G1176-C169-1
1.2 Application Scope
The SIPROTECline protection 7SD5 is a protection relay that combines differential
and distance protection. A multi-end fault locator allows to precisely locate faults in
two-ended lines, even with unfavourable operating or fault conditions.The combined line protection is a selective short-circuit protection for overhead lines
and cables with single- and multi-ended infeeds in radial, ring or any type of meshed
systems of any transmission level. Measuring data are compared separately for each
phase. The network neutral can be earthed, compensated or isolated.
The device incorporates the functions which are normally required for the protection
of an overhead line feeder and is therefore capable of universal application. It may
also be applied as time graded back-up protection to all types of comparison protec-
tion schemes used on lines, transformers, generators, motors and busbars of all
voltage levels.
The inrush current restraint allows for the application of the 7SD5 even if a power
transformer is situated within the protected zone (ordering option) whose starpoint(s)might also be isolated, earthed or provided with a Petersen coil.
A major advantage of the differential protection principle is the instantaneous tripping
in the event of a short-circuit at any point within the entire protected zone. The current
transformers limit the protected zone at the ends towards the remaining system. This
rigid limit is the reason why the differential protection scheme shows such an ideal se-
lectivity.
The line protection system requires a 7SD5 device as well as a set of current trans-
formers at either end of the protected zone.
If the 7SD5 line protection is to be operated with distance protection as the main or
backup protection function, voltage transformers are required. They are also needed
for the acquisition and display of measured values (voltages, power, power factor).
The devices located at the ends of the protected zone exchange measuring informa-
tion via protection data interfaces using dedicated communication links (usually fibre
optic cables) or a communication network, provided that they operate with differential
protection. The distance protection can exchange measuring information via telepro-
tection functions with conventional connections (contacts), or transmit it through fast
command channels provided on the protection data interfaces (can be configured with
DIGSI). Two type 7SD5 devices can be used for an object with two ends to be protect-
ed: cables, overhead line or both, with or without unit-connected power transformer
(option). Employing type 7SD5*3, objects having 3 (three-terminal lines) or more ends
can be protected, besides two-terminal lines, also with or without unit-connected
transformers (option). Up to 6 ends can be covered, which means that smaller busbar
arrangements can also be protected. For each end a 7SD5*3 is used. Building up acommunication chain between 3 or more devices the outermost ends of the chain can
be equipped with the 7SD5*2 model. For more information refer to Section 2.2.1.
With two and more devices (= ends of the protected object) the communication can be
built up as a ring. This enables a redundant operation in case one communication l ine
fails. The devices will automatically find the remaining healthy communication lines.
But even with two ends, communication lines can be doubled to create redundancies.
Since fault-free data transmission is the prerequisite for the proper operation of the dif-
ferential protection system, it is continuously monitored internally.
In the event of a communication failure, if there is no backup channel available, the
devices can automatically be switched to the second main protection function, i.e. dis-
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
24/696
1 Introduction
24 7SD5 ManualC53000-G1176-C169-1
tance protection, or to emergency operation using an integrated time overcurrent pro-
tection, until communication is restored again.
The communication link can be used for transmitting further information. Besides mea-
sured values, binary commands or other information can be transmitted.
As an alternative, distance protection can be used as backup protection, just as timeovercurrent protection is used for emergency protection; both protection functions
operate in this case independently and in parallel to differential protection at each end.
Protection
Functions
Generally speaking, two basic functions are available in the 7SD5 line protection relay,
namely differential and distance protection. One of the protection functions can be
configured at a time as the main protection function (Main1). As an alternative, differ-
ential protection can be selected as the main protection function, and distance protec-
tion as backup protection (Main2).
Recognition of short-circuits in the protection zone only with the measured currents is
the basic function of the differential protection. Also high resistive faults with small cur-
rents can be recognized. Even complex multiphase faults are precisely detected, asthe measured values are evaluated phase segregated. The protection system is re-
straint against inrush currents of power transformers in the protection zone. When
switching onto a fault at any point of a line, an undelayed trip signal can be emitted.
The basic function of the distance protection is the recognition of the distance to the
fault with distance protection measurement. In particular for complex multiphase
faults, the distance protection has a non-switched 6-impedance-loops design (full
scheme). Different pickup schemes enable a good adaption to system conditions and
the user philosophy. The network neutral can be isolated, compensated or earthed
(with or without earth current limiting). The use on long, high-loaded lines is possible
with or without serial compensation. The distance protection may be supplemented by
teleprotection using various signal transmission schemes (for fast tripping on 100 %
of the line length). In addition, an earth fault protection for high resistance earth faults(ordering option) is available, which may be directional, non-directional and may also
be incorporated in signal transmission. On lines with weak or no infeed at one line end,
it is possible to achieve fast tripping at both line ends by means of the signal transmis-
sion schemes. When switching onto a fault at any point of a line, an undelayed trip
signal can be emitted.
The integrated time overcurrent protection function can be configured as a permanent
backup protection at all line ends, or as a protection function for emergency operation.
Emergency operation is a state in which the differential protection cannot operate, for
example because of a communication failure, and in which no distance protection op-
erating in parallel is available (e.g. because of a measuring voltage failure). The time
overcurrent protection function has three definite time overcurrent stages and one
inverse time (IDMT) stage; a series of characteristics according to various standardsis available for the inverse time stage.
Depending on the version ordered, the short-circuit protection functions may also trip
single-pole. They may operate in co-operation with an integrated automatic reclosure
(available as an option) with which single-pole, three-pole or single- and three-pole
rapid automatic reclosure as well as multi-shot automatic reclosure are possible on
overhead lines. Before reclosure after three-pole tripping, the validity of the reclosure
can be checked by voltage and/or synchronism check by the device (can be ordered
optionally). It is possible to connect an external automatic reclosure and/or synchro-
nism check, as well as double protection with one or two automatic reclosure func-
tions.
Other protection functions are possible in addition to the short-circuit protection func-
tions described above. A thermal overload protection has been integrated which pro-
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
25/696
1.2 Application Scope
257SD5 ManualC53000-G1176-C169-1
tects in particular cables and power transformers from illegal heating through over-
load. Other possible functions are multi-stage overvoltage, undervoltage and
frequency protection, circuit breaker failure protection and protection against effects of
power swings (simultaneously active as power swing blocking for the distance protec-
tion). For rapid location of the damage to the line after a short-circuit, a multi-end fault
locator is integrated which also may compensate the influence of parallel lines, and ofthe fault resistances when power is flowing in the line.
Control Functions Depending on the ordered variant the device provides control functions which can be
accomplished for activating and deactivating switchgears via the integrated operator
panel, the system interface, binary inputs and a personal computer with the operating
software DIGSI. The status of the primary equipment can be transmitted to the device
via auxiliary contacts connected to binary inputs. The current status (or position) of the
primary equipment can be read out at the device, and used for interlocking or plausi-
bility monitoring. The number of the operating equipment to be switched is limited by
the binary inputs and outputs available in the device or the binary inputs and outputs
allocated for the switch position indications. Depending on the equipment used one
(single point indication) or two (double point indication) binary inputs may be used. Thecapability of switching primary equipment can be restricted by a setting associated
with the switching authority (remote or local), and by the operating mode (inter-
locked/non-interlocked, with or without password request). Processing of interlocking
conditions for switching (e.g. switching error protection) can be established with the
aid of integrated, user-configurable logic functions.
Messages and Mea-
sured Values; Fault
Recording
The operating messages provide information about conditions in the power system
and the device. Measurement quantities and values that are calculated can be dis-
played locally and communicated via the serial interfaces.
Device messages can be assigned to a number of LEDs on the front panel (allocat-
able), can be externally processed via output contacts (allocatable), linked with user-definable logic functions and/or issued via serial interfaces (see Communication
below).
During a fault (system fault) important events and changes in conditions are saved in
fault logs (Event Log or Trip Log). Instantaneous fault values are also saved in the
device and may be analysed subsequently.
As a special feature the values are synchronized between the line terminals via the
communication link.
Communication Serial interfaces are available for the communication with operating, control and
memory systems.
A 9-pin DSUB socket on the front panel is used for local communication with a person-
al computer. By means of the SIPROTEC4 operating software DIGSI, all operation-
al and evaluation tasks can be executed via this operator interface, such as specifying
and modifying configuration parameters and settings, configuring user-specific logic
functions, retrieving operational messages and measured values, inquiring device
conditions and measured values, issuing control commands.
To establish an extensive communication with other digital operating, control and
memory components the device may be provided with further interfaces depending on
the order variant
The service interface can be operated through data lines. Also, a modem can be con-
nected to this interface. For this reason, remote operation is possible via personal
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
26/696
1 Introduction
26 7SD5 ManualC53000-G1176-C169-1
computer and the DIGSIoperating software, e.g. to operate several devices via a
central PC.
The system interface is used for central communication between the device and a
control centre. The service interface can be operated through data cables or optical
fibres. For data transmission there are several standardized protocols available.
Another interface is provided for the time synchronization of the internal clock via ex-
ternal synchronization sources (IRIG-B or DCF77).
Other interfaces provide for communication between the devices at the ends of the
protected object. These protection data interfaces have been mentioned above in the
protection functions.
The operator and service interface allow to operate the device remotely or locally,
using a standard browser. This is possible during commissioning, checking and also
during operation of the devices at all ends of the protected object, using a communi-
cation network. For this special commissioning tool, the WEB-Monitor, is provided,
which has been optimized for the differential protection system, but upgraded for the
needs of the distance protection.
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
27/696
1.3 Characteristics
277SD5 ManualC53000-G1176-C169-1
1.3 Characteristics
General Features Powerful 32-bit microprocessor system
Complete digital processing of measured values and control, from the sampling of
the analog input values, the processing and organization of the communication
between devices up to the closing and tripping commands to the circuit breakers
Complete galvanic and reliable separation between internal processing circuits
from the measurement, control, and power supply circuits by analog input transduc-
ers, binary inputs and outputs and the DC/DC or AC/DC converters
Suited for lines with up to 6 ends, even with transformers in the protected zone
(order option)
Simple device operation using the integrated operator panel or a connected person-
al computer with operator guidance
Storage of fault indications as well as instantaneous values for fault recording
Differential
Protection
Differential protection system for up to 6 ends with digital protection data transmis-
sion
Protection for all types of short-circuits in systems with any starpoint conditioning
Reliable distinction between load and short-circuit conditions, also on high resistant
faults with small fault currents;
High sensitivity in the case of a weakly loaded system, extreme stability against
load jumps and power swings
Due to phase segregated measurement the pickup sensitivity is independent of the
type of fault
Suited for transformers in the protected area (order option)
Detection of high-resistant, weak-current faults due to high sensitivity;
Insensitive against in-rush and charge currents also for transformers in the pro-
tected area and against higher-frequency switching transients;
Charging current compensation; therefore increased pickup sensitivity
High stability also for different current transformer saturation
Adaptive restraint that is automatically derived from the measured values and the
configured current transformer data
Fast phase segregated tripping also on weak or zero infeed ends (breaker intertrip)
Low dependence on frequency due to frequency tracking
Digital transmission of protection data; communication between devices via dedi-
cated communication connections (in general optical fibre) or a communication
system
Communication possible via ISDN networks or pilot wire connections (up to 30 km,
depends on the type of pilot wire);
Permanent supervision of the protection data transmission concerning disturbance,
failure, and transfer time deviation in the transmission network, with automatic
transfer time correction
Automatic changeover of communication paths in case of transmission failure or
transmission disturbance is provided (for ring topology with 7SD5*3)
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
28/696
1 Introduction
28 7SD5 ManualC53000-G1176-C169-1
Phase segregated tripping (in conjunction with single-pole or single- and three-pole
auto-reclosure) is possible (order option)
Distance Protection
(optional)
Can be used either to operate in parallel to differential protection, or as the main
protection function
Protection for all types of faults in systems with earthed, compensated or isolated
starpoint
Selectable polygonal tripping characteristic or MHO characteristic
Possibility to choose between Z pickup, I>, U/Ior U/I/pickup, enabling the adap-tion to different system conditions and the user philosophy
Reliable differentiation between load and fault conditions also on long, high-loaded
lines
High sensitivity in the case of a weakly loaded system, extreme stability against
load jumps and power swings
Optimum adaption to the line parameters by means of the tripping characteristicwith diverse configuration parameters and load trapezoid (elimination of the pos-
sible load impedances)
Six measuring systems for each distance zone
Six distance zones, selectable as forward, reverse or non-directional reaching, one
may be used as an overreach zone
Nine time stages for the distance zones
Direction determination (with polygon) or polarization (with MHO characteristic) is
done with unfaulted loop (quadrature) voltages and voltage memory, thereby
achieving unlimited directional sensitivity, and not affected by capacitive voltage
transformer transients Suitable for lines with serial compensation
Insensitive to current transformer saturation
Compensation against the influence of a parallel line
Shortest command time significantly less than one cycle
Phase segregated tripping (in conjunction with single-pole or single- and three-pole
auto-reclosure)
Non delayed tripping following switch on to fault is possible
Two sets of earth impedance compensation
Power Swing
Supplement
(optional)
Power swing detection with dZ/dt measurement with three measuring systems
Power swing detection up to a maximum of 7 Hz swing frequency;
In service also during single-pole dead times
Settable power swing programs
Prevention of undesired tripping by the distance protection during power swings
Tripping for out-of-step conditions can also be configured
-
8/12/2019 7SD5xx_Manual_A1_V043003_en (1)
29/696
1.3 Characteristics
297SD5 ManualC53000-G1176-C169-1
Teleprotection
Supplement
(optional)
Different procedures settable
Permissive Underreach Transfer Trip = PUTT (via a separately settable overreach
zone)
Comparison schemes (Permissive Overreach Transfer Trip = POTT or blocking
schemes, with separate overreach zone)
Pilot wire comparison/reverse interlocking (with DC voltage for local connections or
extremely short lines)
Suitable for lines with two or three ends
Phase segregated transmission possible in lines with two ends
Signal exchange between devices via binary outputs and binary inputs, either di-
rectly via device contacts or through the protection data interface(s)
Earth Fault
Protection
(optional)
Time overcurrent protection with maximally three definite time stages (DT) and one
inverse time stage (IDMT) for high resistance earth faults in earthed systems
For inverse-time overcurrent protection a selection from various characteristics
based on several standards is possible
The inverse time s