74-3679-1 - Light Commercial Building Solutions

92
SYSTEM ENGINEERING 74-36791 Light Commercial Building Solutions Introduction .................................................................................................................................. 5 Description ........................................................................................................... 5 Control Applications ............................................................................................. 5 Products Included ................................................................................................. 5 Organization of manual ........................................................................................ 5 Applicable Literature............................................................................................. 6 Agency Listings .................................................................................................... 7 Abbreviations and Definitions ............................................................................... 7 System Architectures .................................................................................................................................. 10 Overview .............................................................................................................. 10 XL15A Solution Architecture ................................................................................ 11 Networking Considerations.............................................................................. 12 Network constraints .................................................................................... 12 S7760A Command Display......................................................................... 12 Data sharing................................................................................................ 13 XL15B Solution Architecture ................................................................................ 14 Networking Considerations.............................................................................. 15 Network Constraints.................................................................................... 15 Alarm Handling ........................................................................................... 15 Configuration Considerations .......................................................................... 15 RapidZone Architecture........................................................................................ 17 Networking Considerations.............................................................................. 17 Configuration Considerations .......................................................................... 18 LonStat Solution Architecture ............................................................................... 18 Networking Considerations.............................................................................. 19 Configuration Considerations .......................................................................... 19 Unconfigured CVAHU Architecture....................................................................... 19 Networking Considerations.............................................................................. 20 Configuration Considerations .......................................................................... 20 LCBS Components ............................................................................................... 20 LonWorksfi Bus............................................................................................... 20 XL15 Network Management and General Purpose Controllers ...................... 20 XL15 W7760A Building Manager ................................................................ 20 XL15B W7760B Building Manager ............................................................. 20 XL15C W7760C Plant Manager ................................................................. 20 XL10 Application Specific Controllers .............................................................. 21 XL10 - W7750A,B,C Constant Volume Air Handling Unit Controllers ......... 21 XL10 W7751B,D,F Variable Air Volume Terminal Controller ...................... 21 XL10 W7751H,J Smart Actuator ................................................................. 21 XL10 W7752A Fan Coil Unit Controller ...................................................... 21 XL10 W7753A Unit Ventilator Controller ..................................................... 21 XL15 W7761A Remote Input/Output Device .............................................. 21 XL10 W7762B Hydronic Controller ............................................................. 22 XL10 W7763C Hydronic Controller ............................................................. 22 Other devices .................................................................................................. 22 S7600A Command Display Unit ................................................................. 22 T7300F/Q7300H Thermostat ...................................................................... 22 T7350 Communicating Subbase ................................................................ 22 CXS and CXL Variable Frequency Drives .................................................. 22 NX Variable Frequency Drive...................................................................... 22

Transcript of 74-3679-1 - Light Commercial Building Solutions

Page 1: 74-3679-1 - Light Commercial Building Solutions

SYSTEM ENGINEERING

74-3679�1

Light Commercial Building Solutions

Introduction .................................................................................................................................. 5Description ........................................................................................................... 5Control Applications ............................................................................................. 5Products Included................................................................................................. 5Organization of manual ........................................................................................ 5Applicable Literature............................................................................................. 6Agency Listings .................................................................................................... 7Abbreviations and Definitions............................................................................... 7

System Architectures .................................................................................................................................. 10Overview .............................................................................................................. 10XL15A Solution Architecture ................................................................................ 11

Networking Considerations.............................................................................. 12Network constraints .................................................................................... 12S7760A Command Display......................................................................... 12Data sharing................................................................................................ 13

XL15B Solution Architecture ................................................................................ 14Networking Considerations.............................................................................. 15

Network Constraints.................................................................................... 15Alarm Handling ........................................................................................... 15

Configuration Considerations .......................................................................... 15RapidZone Architecture........................................................................................ 17

Networking Considerations.............................................................................. 17Configuration Considerations .......................................................................... 18

LonStat Solution Architecture ............................................................................... 18Networking Considerations.............................................................................. 19Configuration Considerations .......................................................................... 19

Unconfigured CVAHU Architecture....................................................................... 19Networking Considerations.............................................................................. 20Configuration Considerations .......................................................................... 20

LCBS Components............................................................................................... 20LonWorks® Bus............................................................................................... 20XL15 Network Management and General Purpose Controllers ...................... 20

XL15 W7760A Building Manager................................................................ 20XL15B W7760B Building Manager ............................................................. 20XL15C W7760C Plant Manager ................................................................. 20

XL10 Application Specific Controllers.............................................................. 21XL10 - W7750A,B,C Constant Volume Air Handling Unit Controllers......... 21XL10 W7751B,D,F Variable Air Volume Terminal Controller ...................... 21XL10 W7751H,J Smart Actuator................................................................. 21XL10 W7752A Fan Coil Unit Controller ...................................................... 21XL10 W7753A Unit Ventilator Controller..................................................... 21XL15 W7761A Remote Input/Output Device .............................................. 21XL10 W7762B Hydronic Controller ............................................................. 22XL10 W7763C Hydronic Controller............................................................. 22

Other devices .................................................................................................. 22S7600A Command Display Unit ................................................................. 22T7300F/Q7300H Thermostat ...................................................................... 22T7350 Communicating Subbase ................................................................ 22CXS and CXL Variable Frequency Drives .................................................. 22NX Variable Frequency Drive...................................................................... 22

Page 2: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTIONS

74-3679�1 2

LonTalk® Adapters ..................................................................................... 23Configuration Tools .............................................................................................. 23

LONSPEC� (ZL7760A)................................................................................ 23RapidZone (ZL7751A) ................................................................................ 23LONSTAT� (zl7300A).................................................................................. 23

LCBS Architecture Comparison ........................................................................... 23

Application Steps .................................................................................................................................. 25Overview .............................................................................................................. 25Step 1. Plan the System....................................................................................... 25Step 2. LayOut Communications and Power Wiring ............................................ 26

Communications.............................................................................................. 26Power .............................................................................................................. 27

Power Budget Calculation Example ........................................................... 28Guidelines for power wiring are as follows: ................................................ 28

Line Loss ......................................................................................................... 29Step 3. Prepare Wiring Diagrams......................................................................... 30

Wiring Details .................................................................................................. 30Typical Wiring Diagrams.................................................................................. 30

General Considerations ....................................................................................... 32Attaching 2 or more wires to the same terminal ......................................... 32Field wiring types........................................................................................ 33

Step 4. Order Equipment...................................................................................... 33Step 5. Configure Controllers ............................................................................... 37Step 6. System Startup......................................................................................... 38

Check Installation and Wiring: ......................................................................... 38Verify Termination Module Placement ........................................................ 38

Power Up......................................................................................................... 38Assigning Neuron® ID..................................................................................... 38Alarms ............................................................................................................. 39Download the Configuration ............................................................................ 39Checkout ......................................................................................................... 39

LonSpec Data Sharing .................................................................................................................................. . 40Introduction to Data Sharing ................................................................................ 40Data Sharing for Control Devices......................................................................... 40

T7300F/Q7300H.............................................................................................. 41Excel 10 W7750 CVAHU................................................................................. 41XL10 VAV Terminal (W7751) ........................................................................... 41Excel 10 W7753 Unit Vent............................................................................... 41Excel 15 W7760A Building Manager............................................................... 41Excel 15 W7760C Plant Controller.................................................................. 42

Refer Points Applications ..................................................................................... 42Time of Day Scheduling .................................................................................. 42

Process:...................................................................................................... 43Outdoor Air Conditions .................................................................................... 43Bypass............................................................................................................. 44XL10 Free Points............................................................................................. 44Remote Point Selection................................................................................... 44

Appendix A - Refer Points Tables ..................................................................................................................................45

Appendix B � Remote Point Tables ..................................................................................................................................84

Appendix C � Enumerated Definitions ..................................................................................................................................93

Page 3: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

3 74-3679�1

List of TablesTable 1. Applicable Literature....................................................................................................................................................... 6Table 2. Physical Inputs and Outputs........................................................................................................................................... 21Table 3. LCBS Architecture Comparison. .................................................................................................................................... 23Table 4. Application Steps............................................................................................................................................................ 25Table 5. VA Ratings For Transformer Sizing................................................................................................................................ 28Table 6. Field Wiring Reference Table (Honeywell cable listed as AK#### or equivalent).......................................................... 33Table 7. Light Commercial Building Solution Ordering Information.............................................................................................. 33Table 8. Outdoor Air Conditions Network Variable Names. ......................................................................................................... 43Table 9. Refer points from W7750 XL10 Constant Volume Air Handling Unit (CVAHU) Controller to XL10. .............................. 45Table 10. Refer Points from W7750 XL10 CVAHU Controller to XL15, T7350 and Q7300. ........................................................ 46Table 11. Refer Points from W7753 XL10 Unit Ventilator (Unit Vent) Controller to XL10............................................................ 47Table 12. Refer Points from W7753 XL10 Unit Ventilator (Unit Vent) Controller to XL15, T7350 and Q7300............................. 48Table 13. Refer Points from W7751 XL10 VAV II Terminal Box Controller to XL10. ................................................................... 49Table 14. Refer Points from W7751 XL10 VAV II Terminal Box Controller to XL15, T7350 and Q7300H................................... 51Table 15. Refer Points from Fan Coil Unit Controller to XL10...................................................................................................... 52Table 16. Refer points from Fan Coil Unit Controller to XL15, T7350 and Q7300H. ................................................................... 53Table 17. Refer points from Chilled Ceiling Controller to XL10.................................................................................................... 54Table 18. Refer points from Chilled Ceiling Controller to XL15, T7350 and Q7300H. ................................................................. 55Table 19. Refer points from Hydronic controller to XL 10. ........................................................................................................... 56Table 20. Refer points from Hydronic Controller to XL15, T7350 and Q7300H. .......................................................................... 57Table 21. Refer Points from T/Q7300H XL10 Thermostat to XL10.............................................................................................. 57Table 22. Refer Points from T/Q7300H XL10 Thermostat to XL15, T7350 and Q7300............................................................... 58Table 23. Refer Points from W7760A XL15A Building Manager to XL10. ................................................................................... 59Table 24. Points from W7760A XL15A Building Manager to XL15, T7350 and Q7300H............................................................. 61Table 25. Refer Points from W7760C XL15C Plant Controller to XL10. ...................................................................................... 62Table 26. Refer Points from W7760C XL15C Plant Controller to XL15, T7350 and Q7300H...................................................... 63Table 27. Refer Points from W7761 Remote Input/Output Device to XL10. ................................................................................ 65Table 28. Refer Points from W7761 Remote Input/Output Device to XL15, T7350 and Q7300. ................................................. 66Table 29. Network Input Variable Description. ............................................................................................................................. 67Table 30. Network Output Variable Description. .......................................................................................................................... 74Table 31. Remote Point Functions. .............................................................................................................................................. 84Table 32. LonMark® HVAC Operating Mode Enumerated Definitions. ....................................................................................... 93

List of FiguresFig. 1 XL15A Solution Architecture. ............................................................................................................................................ 11Fig. 2 XL15B Solution Architecture. ............................................................................................................................................ 14Fig. 3 RapidZone Solution Architecture....................................................................................................................................... 17Fig. 4 LonStat Solution Architecture............................................................................................................................................ 18Fig. 5 Unconfigured CVAHU Architecture. .................................................................................................................................. 19Fig. 6 W7760 LonWorks wiring option 1...................................................................................................................................... 27Fig. 7 W7760 LonWorks wiring option 2...................................................................................................................................... 27Fig. 8 W7760 LonWorks wiring option 3...................................................................................................................................... 27Fig. 9 Power wiring details for multiple LCBS Devices................................................................................................................ 29Fig. 10 NEMA class 2 transformer voltage output limits.............................................................................................................. 29Fig. 11 Typical Temperature (Resistance) Actuator Wiring......................................................................................................... 30Fig. 12 Typical 2- Wire Voltage Output Sensor Wiring................................................................................................................ 30Fig. 13 Typical 3-Wire Voltage Output Sensor Wiring................................................................................................................. 30Fig. 14 Typical 4 - 20 mA Output Sensor Input Wiring. ............................................................................................................... 30Fig. 15 Typical Digital Input Wiring.............................................................................................................................................. 31Fig. 16 Typical Floating (Series 60) Actuator Wiring. .................................................................................................................. 31Fig. 17 Typical Pulse Width Modulating Actuator Wiring............................................................................................................. 31Fig. 18 Typical 4 - 20 mA Actuator Wiring................................................................................................................................... 31Fig. 19 Typical 0 - 10 or 2 - 10 Vdc Actuator Wiring.................................................................................................................... 31Fig. 20 Typical Relay (Digital) Output Wiring. ............................................................................................................................. 32Fig. 21 Wiring Triac Digital Outputs for Parallel Operation.......................................................................................................... 32Fig. 22 Attaching two or more wires to terminal blocks. .............................................................................................................. 33

Page 4: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 4

INTRODUCTION

DescriptionThe Light Commercial Building Solution (LCBS) is a family of control devices designed to meet the comfort control requirements of commercial buildings of small to medium size. Commercial buildings typical of this market include but are not limited to office buildings, retail stores, light manufacturing facilities, restaurants, schools, churches, theaters, super markets, grocery stores, and banks.

These buildings typically use some combination of single zone air handling units, heat-pumps, zoned air handling units, variable air volume systems, fan coil units, unit ventilators, and/or perimeter heating to maintain the building�s comfort levels. In addition, lighting control, equipment on-off scheduling, and data collection may be required of the control system.

Light Commercial Building Solution devices utilize the LonWorks® communication protocol for open systems network communications. The controllers may also be used for stand-alone control applications.

The Light Commercial Building Solution includes thermostats and a number of application specific controllers (Excel 10) to directly address typical mechanical systems. The advantage of application specific controllers is use of a sophisticated and efficient control strategy matched to the mechanical equipment functions, standardizing the control processes, and minimizing the effort required to configure and maintain the system insuring consistent performance.

LCBS also includes a selection of Building Manager and general purpose controllers (Excel 15) to address the need for custom applications and to handle alarm reporting, data collection and reporting, and operator interface communications.

Operator interface to a LCBS may be with an easy to use command display unit, LONSTATION� workstation software installed in a personal computer, or by internet access.

The system is configured using LONSPEC� software installed in a personal computer. LONSPEC� simplifies system configuration by letting the user select the desired control options while most networking functions are done �behind the scene�.

Specialized applications of LCBS are available as RapidZone� for zoning systems and LonStat� for thermostat only solutions.

Control ApplicationsTypical Light Commercial Building Applications:� Single zone air handling unit thermostat control for up to 3

stages of heat and 3 stages of cooling.� Single zone air handling unit control for up to 4 stages or

modulating heating and 4 stages or modulating cooling with integrated economizer control.

� Heat pump air handling unit control for up to 4 compressors (heating and cooling) and 4 stages of auxiliary/emergency heat and integrated economizer control.

� Unit ventilator control with ASHRAE cycle 1, 2, or 3 selection.

� Fan coil unit control� Fin tube radiation and convector control.� Variable air volume terminal unit control.

� Single and dual duct� Standard and fan powered (parallel and serial)� Reheat and/or peripheral heat� Air flow tracking

� Variable volume air handling units (plants) control� Custom air handling unit control

� Humidification and/or dehumidification� Preheat� Reheat� Make-up air� Tempering systems

� Lighting control� Equipment on-off scheduling� Custom applications

Products IncludedExcel 10 Application Specific Controllers:� W7750A, B, C Constant Volume Air Handling Unit

(CVAHU) Controllers� W7751B,D,F Variable Air Volume (VAV II) terminal unit

controllers.� W7751H,J Smart Actuators� W7752A Fan Coil Unit Controller� W7753A Unit Ventilator (UV) Controller� W7762B Hydronic Controller� W7763C Chilled Ceiling Controller� W7761A Remote Input/Output Device (RIO)� T7350 Communicating Subbase

Excel 15 Building Manager and Plant Manager Controllers:� W7760A Building Manager - includes network

management and general purpose control functions� W7760B Building Manager - Internet server, limited

network management, no control functions� W7760C Plant Manager - general purpose control - no

network management functions.

Wall Modules:� T7560A Digital Wall Module (connect to Excel 10 only)� T7770A,B,C,D,E,F Wall Modules� T7771A Wall Modules

Other Devices:� Vacon NX Variable Frequency Drive� CXS, CXL Variable Frequency Drives� Q7740A,B FTT-10 network repeater� Q7760 LonTalk® Adapter� S7760A Command Display - operator interface

Software:� ZL7760A LONSPEC� Configuration Tool with monitoring� ZL7751A RapidZone Configuration Tool with monitoring� ZL7300A LonStat Configuration Tool with monitoring� ZL7762A LONSTATION� Multi-site Monitoring Tool with

graphics

Organization of manualThis manual provides a system view of the Light Commercial Building Solution. As such it addresses the common networking and interface requirements of all the devices

Light Commer-cial Building Solution

Page 5: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

5 74-3679�1

included. It does not address directly any specific product. See the product specification data, user guides, and installation instructions for information, specific to each device.

This manual is divided into 4 sections:1. Introduction: Provides a brief description of the Light

Commercial Building Solution, lists the devices typically used in a system, lists additional literature, and provides a glossary of abbreviations and definitions.

2. System Architectures: Provides a system view of typical LCBS systems and discussion of the benefits and con-straints of the architectures.

3. LonWorks® for LCBS: Describes the layout and installa-tion requirements and practices for installing theLonWorks® FTT-10 Bus.

4. Data Sharing: Describes the processes used by the configuration tools to share data between controllers and provides tables of appropriate data sharing points.

This manual supplements the individual product application guides, providing the general information necessary to plan and layout a LCBS system. Individual specification data, application guide, and installation instruction manuals are required for each product included in the system.

Applicable LiteratureTable 1 lists the documents that contain information related to the Light Commercial Building Solution.

Table 1. Applicable Literature.

Model Number

Literature Form Numbersa

SpecificationData

ApplicationSelection

ApplicationGuide

InstallationInstructions

User�sGuide

E-PROMReplacement

XL15 Building Managers and ControllersW7760A Building Manager 74-2967 74-2969 95-7565 95-7631W7760B Building Manager 74-3472 95-7668 74-3471W7760C Plant Controller 74-3080 74-3079 95-7632 95-7632XL10 Application Specific ControllersW7750A,B,C CVAHU 74-2956 63-7046 74-2958 95-7521W7751B,D,F, VAVII 74-6942 63-7045 74-2949 95-7504W7751H Smart Actuator 74-2653 74-2949 95-7553W7751J Smart Actuator 74-3663 74-2949 95-7663W7752D,E,F,G Fan Coil Unit 74-2959 63-7043 74-2961 95-7519W7753A Unit Ventilator 74-2962 63-7044 74-2964 95-7520 95-7651W7761A Remote Input/Output 74-2698 74-2699 95-7539W7762B Hydronic 74-2934 63-7075 74-2935 95-7563W7763C Chilled Ceiling 74-2989 74-2990 95-7485T7350 Communicating Subbase 63-1299 63-9299 63-2605 62-0195 63-2604Other Network DevicesCXS, CXL Variable Frequency Drives

63-1285

Vacon NXS, NXP, and NXL Variable Frequency Drives

Refer to www.Vacon.com for information on the NX VFD device.

Q7300H Sub-baseT7300F Thermostat

63-1281 63-4365 62-045562-013463-9047b

62-0125c

Q7740A,B FTT Repeater 74-2858 95-7555Q7752B PCMCIA LONWORKS® Card

74-3067

a The from numbers shown do not include the revision number as these may change at any time. The revision number is indicated on the literature with a dash (-) after the form number followed by the revision number.

b Installer Setup and Test pocket guide.c Tradeline.d Product Data Sheet.

Page 6: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 6

Agency ListingsAgency listings for the devices listed in �Products Included� may vary. Refer to the Specification Data for each device for specific agency listings.

Abbreviations and DefinitionsAHU⎯Air Handling Unit; the central fan system that includes

the blower, heating equipment, cooling equipment, ventilation air equipment, and other related equipment.

Application⎯A specific Building Control function.

Binding⎯The process of logically connecting network variables in one node to network variable(s) in other node(s). Binding is performed by a network management node that writes the binding information into the EEPROM of each Neuron® involved. The binding information is saved in the network image of each Neuron.

Building Manager⎯A LONMARK® certified device that can be used to monitor and control HVAC equipment and other miscellaneous loads in a distributed network.

Bypass⎯Temporary override of the scheduled occupancy state to the occupied mode. At the end of the bypass time, the control returns to the scheduled occupancy state.

CHC⎯Chilled Ceiling Controller. (German acronym)

CO⎯Carbon Monoxide. Occasionally used as a measure of indoor air quality.

CO2⎯Carbon Dioxide. Often used as a measure of indoor air quality.

Command Display⎯A device used to monitor, override, and change parameters in a LONWORKS® HVAC application.

Continuous Trend⎯A type of log that starts accumulating data after configuration and continues to record data until re configured. After a specific number of configured samples are recorded, the data is replaced on a first-in-first out basis. This results in the most recent data being in the trend at the time of viewing or downloading.

Control Loop⎯A control function; A type of function in a node that includes processes, loops and programs. A node can contain one or more control loops. (In Excel 10 devices, the control loop occupies the entire node. In Excel 15 devices each start-stop loop, PID control loop, and Logic Loop is a control loop.)

Control Object�See Object.

COS⎯Change of state; COS conditions are used with schedule states such as occupied and unoccupied. Changing from the occupied mode to the unoccupied mode is COS.

CPU⎯Central Processing Unit; an EXCEL 5000® OPEN� SYSTEM controller module.

cUL⎯Underwriters Laboratories Canada.

CVAHU⎯Constant Volume AHU; Refers to a type of air handler with a single-speed fan that provides a constant amount of supply air to the space it serves.

CZS⎯Commercial Zoning System.

DDF⎯Delta Degrees Fahrenheit.

Q7760 Serial LONTALK® Adapter 74-2954 95-7511S7760A Command Display Unit 74-2972 95-7561 74-3450 95-7630Wall ModulesT7560A,B Digital Wall Module 74-3097 95-7620T7770A,B,C,D,E,F,GWall Modules

74-2679 95-7538

T7771A Wall Module 63-2617d

SoftwareZL7300A LonStatZL7751A RapidZone 74-3449ZL7760A LONSPEC� 74-2976 74-2937ZL7762A LONSTATION� 74-3069 74-3676

Table 1. Applicable Literature. (Continued)

Model Number

Literature Form Numbersa

SpecificationData

ApplicationSelection

ApplicationGuide

InstallationInstructions

User�sGuide

E-PROMReplacement

a The from numbers shown do not include the revision number as these may change at any time. The revision number is indicated on the literature with a dash (-) after the form number followed by the revision number.

b Installer Setup and Test pocket guide.c Tradeline.d Product Data Sheet.

Page 7: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

7 74-3679�1

D/X⎯Direct Expansion; Refers to a type of mechanical cooling where the refrigerant is expanded to its cold state in a heat exchanging coil that mounts in the air stream supplied to the conditioned space.

DLC⎯Demand Limit Control; A function that controls the maximum power demand made on the whole system by shedding some of the demand when power usage exceeds the predefined limit. Shedding requires turning off some digital output, or changing a setpoint to a more economical level.

Echelon⎯The company that developed the LONWORKS® Busand the Neuron® chips used to communicate on the LONWORKS® Bus.

Economizer⎯Refers to the mixed-air dampers that regulate the quantity of outdoor air that enters the building. In cool outdoor conditions, fresh air can be used to supplement the mechanical cooling equipment. Because this action saves energy, the dampers are often referred to as economizer dampers.

EEPROM⎯Electronically Erasable Programmable Read Only Memory; The variable storage area for saving user setpoint values and factory calibration information.

EMI⎯Electromagnetic Interference; Electrical noise that can cause problems with communications signals.

EMS⎯Energy Management System; Refers to the controllers and algorithms responsible for calculating optimum operational parameters for maximum energy savings in the building.

Enthalpy⎯The energy content of air measured in BTU�s per pound (KiloJoules per Kilogram).

EPID Control⎯An Enhanced Proportional Integral Derivative control algorithm that improves the PID control algorithm by compensating for system dynamics and allows faster control response rate reset. It also incorporates a sequencer, AI limit, deadband, start ramp and setpoint override.

EPROM⎯Erasable Programmable Read Only Memory; The firmware that contains the control algorithms for the Excel 15 and Excel 10 Controllers.

Excel 10s⎯A family of application specific HVAC Controllers such as the Excel 10 CVAHU, Excel 10 RIO, and the Excel 10 UV.

FCU⎯Fan Coil Unit.

Firmware⎯Software stored in a nonvolatile memory medium such as an EPROM.

Floating Control⎯Refers to Series 60 Modulating Control of a valve or damper. Floating Control utilizes one digital output to drive the actuator open, and another digital output to drive it closed.

FTT⎯Free Topology Transceiver.

HVAC⎯Heating Ventilation and Air Conditioning.

HYD⎯Hydronic Unit. (German acronym)

Hydronic - HVAC systems using water or steam and the heating or cooling medium.

IAQ⎯Indoor Air Quality. Refers to the quality of the air in the conditioned space, as it relates to occupant health and comfort.

I/O⎯Input/Output; the physical sensors and actuators connected to a controller.

I x R⎯I times R or current times resistance; refers to Ohms Law: V = I x R.

K⎯Degrees Kelvin.

LCBS - Light Commercial Building Solution

Level IV⎯Refers to a classification of digital communication wire. Formerly known as UL Level IV, but not equivalent to Category IV cable. If there is any question about wire compatibility, use Honeywell-approved cables (see Step 5 Order Equipment section).

LONWORKS® Bus⎯Echelons LONWORKS® network for communication among Excel 15 Controllers, Excel 10 Controllers and T7300F/Q7300H Commercial Thermostat/Communicating Subbases.

LONWORKS® Bus Segment⎯An LONWORKS® Bus network that contains no more than 120 total (Excel 15 W7760A,Cs, Excel10s and T7300F/Q7300H Commercial Thermostat/Communicating Subbases). A segment can have a repeater that allows the bus wire length to be doubled.

Mandatory Mechanisms/Objects/Network Variables⎯ Mandatory mechanisms, object and network variables that are implemented in all of the Excel 10 devices.

NamedObject⎯Objects that have names are called NamedObjects. These objects are visible on the network as functional independent entities and are accessed by name. Typical examples of NamedObjects are controllers, control loops and logic function blocks.

NEC⎯National Electrical Code; The body of standards for safe field-wiring practices.

NEMA⎯National Electrical Manufacturers Association; The standards developed by an organization of companies for safe field wiring practices.

Network Management Node⎯A LONWORKS® node that is responsible for configuring the network, installing the nodes, binding the network variables between nodes and general network diagnostics.

Network Object�See Object

Network Time Master⎯A network time master will be the only device sending out the time/date. All other network devices will use the time/date from the network time master (even if they have their own real-time clock). Network time master is chosen/configured from LONSPEC� and remains unchanged until re configured, even in the event of a failure on the network time master. (The Excel 15 W7760C can not be the network time master.)

Page 8: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 8

Network Time Scheduler⎯The network time scheduler sends out current and next state (occupied, unoccupied or standby) and time until the next change of state (TUNCOS) to all of its control loops based on the configured schedules.

Network Variables⎯A class of variables defined in Neuron C that allow communication over the LONWORKS® network to other nodes on the network. For example; An output network variable in one node can be bound to the corresponding input network variable(s) in other node(s). Changing the value of the output network variable in one node causes the new value to be automatically communicated to the bound input network variable(s) in other node(s). When an input network variable is updated, an nv_update_occurs event is posted at the receiving node(s) so that the application program can take action based on the change. A network management node that explicitly reads and/or writes the network variable can also poll network variables. Network variables can contain one data field (one or two bytes) or multiple data fields (a structure).

Node⎯A Communications Connection on a network; An Excel 15 or Excel 10 Controller is one node on the LONWORKS® Bus network.

NV⎯Network Variable; An Excel 15 or Excel 10 parameter that can be viewed or modified over the LONWORKS® Bus network.

Object�Also referred to as control object or network object. A single control algorithm with multiple input, output, setpoints, and/or configuration parameters. Each XL10 application specific controller is a single object. Each start/stop loop, control loop, and logic function in an XL15 controller is a unique object.

PC⎯An Personal Computer with Pentium processor capable of running Microsoft® Windows™.

Plant Controller⎯A device that can be used to monitor and control HVAC equipment and other miscellaneous loads in a distributed network.

Proportional Control⎯A control algorithm or method in which the final control element moves to a position proportional to the deviation of the value of the controlled variable from the setpoint.

Proportional Integral (PI) Control⎯A control algorithm that combines the proportional control and the integral reset control algorithms. Integral reset virtually eliminates offset by gradually shifting the controlled output in the direction that brings the controlled variable back to the setpoint.

Proportional Integral Derivative (PID) Control⎯A control algorithm that enhances the PI control algorithm by adding a component that is proportional to the rate of change (derivative) of the deviation of the controlled variable. PID compensates for system dynamics and allows faster control response rate reset.

PWM⎯Pulse Width Modulated output; Allows analog modulating control of equipment using a digital output on the controller.

RapidLink�RapidLink� is an RS232 and telephone line compatible serial device that allows any host (PC) with an RS 232 or Modem interface (and the necessary driver software) to communicate with a LonWorks® network.

RCD⎯Remote Communication Device; For the Building Management System, this is a piece of hardware that is functionally compatible to an SLTA and provides access directly to the LONWORKS® Bus.

Recovery Mode or Recovery Period⎯The time in unoccupied periods when the temperature control is adjusting the control setpoint so that the space temperature reaches the occupied setpoint when the schedule change occurs.

Reset⎯The reset of a control loop varies depending upon the type of control loop being reset. A reset for a thermostat loop or a control loop changes the setpoint and the algorithm in the energy saving direction. A reset for a start/stop loop causes the digital output to go to the inactive state before returning to its normal scheduled state.

RIO⎯Excel 10 Remote I/O Device; Additional inputs and outputs that can be configured for use by an Excel 15 W7760A or W7760C.

RTC⎯Real-time clock.

RTD⎯Resistance Temperature Detector; Refers to a type of temperature sensor whose resistance output changes according to the temperature change of the sensing element.

RTU - Roof Top Unit; typically refers to a CVAHU built as a single unit designed to be installed on a rooftop. Other types of AHU�s are also built for roof top mounting.

Schedule⎯The structure that defines the occupancy states, setpoints and the time of the changes between these states.

SLTA⎯Serial LONTALK® Adapter; A serial interface between the EIA-232 (serial port on a PC) and a LONWORKS® Bus used to adapt transformer-coupled Echelon messages.

SNVT⎯Standard Network Variable Type.

TOD⎯Time-Of-Day; The scheduling of Occupied and Unoccupied times of operation.

TUNCOS⎯Time Until Next Change Of State is a command that can be sent to other controllers.

UV⎯See Unit Vent below.

Unit Vent - Unit Ventilator (UV). A specialized AHU designed to control high rates of ventilation as defined by ASHRAE (Cycle I, II, or III).

VA⎯Volt Amperes; A measure of electrical power output or consumption as applies to an ac device.

Vac⎯Voltage alternating current; ac voltage rather than dc voltage.

Page 9: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

9 74-3679�1

VAV⎯Variable Air Volume; Refers to a type of air distribution system.

VAV II - An Excel 10 applications controller for VAV terminal units.

VFD�Variable Frequency Converter; an electronic device used for controlling speed and torque of three-phase AC motors.

VOC⎯Volatile Organic Compound; Refers to a class of common pollutants sometimes found in buildings. Sources include out-gassing of construction materials, production-line by-products, and general cleaning solvents. A VOC is occasionally used as a measure of indoor air quality.

W7750⎯The model number of the Excel 10 CVAHU Controllers (also see CVAHU).

W7751⎯The model number of the Excel 10 VAV Terminal Unit Controllers (also see VAV).

W7752 - The model number of the Excel 10 Fan Coil Unit Controller (also see FCU)

W7753⎯The model number of the Excel 10 UV Controller.

W7760⎯The model number of the Excel 15 Building Manager Controller and the Plant Controller (also see Building Manager and Plant Controller).

W7761⎯The model number of the Excel 10 RIO Device.

W7762 - The model number of the Excel 10 Hydronic controller without integral wall module (also see Hydronic).

W7763 - The model number of the Excel 10 Hydronic controller without integral wall module (also see Hydronic).

Wall Module⎯The Excel 10 Space Temperature Sensor and other optional controller inputs are contained in the T7770, T7771A, or T7560A,B Wall Modules. See Application Step 4. See �Light Commercial Building Solution Ordering Information.� on page 32. for details on the various models of Wall Modules.

SYSTEM ARCHITECTURES

OverviewThe Light Commercial Building Solution (LCBS) offers five distinctive solution architectures designed to address specific market requirements.

All five LCBS architectures utilize the Echelon® LONWORKS® Free Topology (FTT-10A) data communications bus for low cost and high performance open system communications.

The LCBS architectures use various combinations (sub-sets) of Excel 15, Excel 10, T7350, and T7300F/Q7300H control devices. The differentiation in the architectures is the application, configuration tool and/or user interface.

The five LCBS architectures are:� XL15A (LONSTATION�)� XL15B (Internet)� RapidZone� LonStat� Unconfigured CVAHU

In addition, the XL10 application specific controllers and T7300, and T7350 commercial programmable thermostats can be used as stand-alone controllers with no network connections.

Page 10: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 10

XL15A Solution Architecture

Fig. 1. XL15A Solution Architecture.

Back Select

FTT-10 LONTALK ADAPTER OPTIONS FOR DIRCT CONNECT: DESK TOP PC - Q7760A OR PCLTA (3RD PARTY)

T7560A DIGITAL WALL MODULE MAY BE USED IN LEU OF T7770.

Q7740 NETWORK REPEATER REQUIRED IF NETWORK WIRING EXCEEDS 4000 FT OR THE NUMBER OF CONTROL

DEVICES EXCEED 60.

1 4 8 12 16

17 23 30 31 37 44

EXCEL 15

W7760A

BUILDING

MANAGER

1 4 8 12 16

17 23 30 31 37 44

EXCEL 15

W7760A

PLANT

MANAGER

EXCEL 10

W7761A

REMOTE

INPUT/OUTPUT

DEVICE

EXCEL 10

W7751H

SMART

ACTUATOR

M20938A

LONWORKS FFT-10 BUS®

LONWORKS FTT-10 BUS®

LONSTATION

(PERSONAL COMPUTER)

LONSPEC

(PERSONAL COMPUTER)

T7770

WALL MODULE

1 2 3

1

2

2

2 2

3

3

1

LONSTATION / LONSPEC

(PERSONAL COMPUTER)

1

MODEM

MODEMQ7752A

SERIAL LONTALK

ADAPTER

S7760

COMMAND

DISPLAY

EXCEL 10

W7750A

CVAHU

EXCEL 10

W7751B, D, F

VAV II

T7770

WALL MODULE

EXCEL 10

W7753A

UNIT

VENTILATOR

EXCEL 10

W7752A

FAN COIL

UNIT

T7560A

DIGITAL

WALL

MODULE

T7300F/Q7300H

THERMOSTAT

EXCEL 10

W7762A, B

HYDRONIC

T7770

WALL

MODULE

VARIABLE

FREQUENCY

DRIVE

Q7740A

LONWORKS

FTT-10

REPEATER

T7560A

DIGITAL

WALL

MODULE

EXCEL 10

W7763C, D, E

CHILLED

CEILING

3RD PARTY LONMARK

COMPLIANT

DEVICES

NOTEBOOK PC WITH PCMCIA SLOT-Q7752A PCMCIA-LTA

T7350H

THERMOSTAT

Page 11: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

11 74-3679�1

Fig. 1 depicts the options available in the XL15A architecture.

The XL15A - LONSTATION� solution offers the most comprehensive LCBS solution. Network management functions including scheduling, alarm handling, and dial-out are performed by one or more Excel 15 W7760A Building Managers (XL15A). All Excel10 application specific controllers, T7350 and T7300F/Q7300H thermostats, Excel 15 W7760C Plant Manager, NX VFD, CXS AND CXL variable frequency drives are supported by the W7760A Building Manager. LONSTATION� provides a cost effective, user friendly operator interface.

See Table 3 for a complete list of devices supported and a comparison of architecture features.

The system is configured using ZL7760A LONSPEC� software configuration tool.

Local and remote system monitoring is performed using ZL7762A LONSTATION� Software Monitoring and Graphics software.

NOTE: The W7760B Building Manager is not supported in the XL15A architecture and should not be used with the W7760A Building Manager. While both the W7760A and W7760B may coexist on the same LONWORKS® bus, they do not support each other and network functions may conflict if implemented in both devices.

Networking ConsiderationsNETWORK CONSTRAINTSThe maximum number of devices on a LCBS LONWORKS® bus is 120. This does not include LONTALK® adapters. The maximum number of devices on a subnet segment is 60. If more than 60 devices are used on a network, a Q7740A or B repeater is required.

The recommended maximum LONWORKS® bus cable length of a network segment is 9,200 feet (2,800 meters) with a Q7740 repeater and 4,600 feet (1,400 meters) without a repeater. The cable wire gage network topology will also determine the maximum cable length that can be used.

The maximum number of W7760A Building Managers on a sub-network is 4.

The maximum number of W7761A RIO devices is 3 per W7760A and/or C.

In an XL15A solution further limitations on the number of devices on a bus may result from alarm handling and data sharing requirements.� Each W7760A will support a maximum of 20 nodes

(W7760C, XL10 controllers, T7350 and T7300F/Q7300H thermostats) for device internal alarms. Refer to Excel 15 W7760A Building Manager Application Guide 74-2969 for alarm data.

� The maximum number of devices with internal alarm reporting is 84 (4 W7760A plus 4 X 20 external = 84). Additional 120 devices can be used. However, only 84 devices can be configured to report internal alarms.

� Each W7760A supports a maximum of 20 analog and 20 digital user configured alarms. User configured alarms can be configured for any analog or digital point in the system. The maximum number of user configured alarms are 80 analog and 80 digital.

� Each W7760A will support a maximum of 16 Trend Logs. A trend log is a single analog or digital point. A tend log can be configured to use any point in the system. The maximum number of trend logs is 64.

� Each W7760A will support a maximum of 15 Run Time logs. A run time log may be configured for any single digital point in the system. The maximum number of run time logs is 60

� Each W7760A will support a maximum of 20 Bypass Logs. A bypass log may be configured for any control object bypass state. The maximum number of bypass logs is 80.

The T7300F/Q7300H thermostats can schedule a maximum of 4 XL10 controllers, W7760C Plant Controller start-stop and control loops, and other T7300F/Q7300Hs whereas the T7350 can schedule all the 120 controllers on the network. T7350 can schedule only one Excel 15C object for every Excel 15C Plant controller.

NOTES:� The T7300F/Q7300H has only two Occupied and

two Unoccupied settings per day, no standby set-tings, uses a 7 day schedule with no temporary or holiday schedules, and does not support adaptive intelligent recovery in W7760C control loops and XL10 controllers.

� The T7350 has four settings (occupied, unoccu-pied, or standby) per day, uses a eight day sched-ule with a maximum of 10 holidays.

Alarm HandlingAll alarm reporting and logging is done by one or more W7760A Building Managers on the subnetwork. It requires that each device to be alarmed be mapped to a W7760A. Each W7760A will support a maximum of 20 other network devices for alarm reporting. Devices that are not mapped to a W7760A will not have alarms reported.

The W7760A Building Manager is configured to route alarms it processes. The alarms can be configured to be ignored (Do Nothing) or sent to any combination of dial-out to remote LONSTATION�, sent to local LONSTATION� and S7760A Command Display, and/or log to the W7760A alarm log. See Excel 15 W7760A Building Manager System Engineering (74-2969) for complete details on alarm handling.

S7760A COMMAND DISPLAYThe S7760A Command Display module can be configured to display data from a maximum of 270 network objects. Each LCBS network device is a network node object. In addition each individual start-stop loop, control loop, and logic loop configured in a W7760A or W7760C is a network object. Each W7760A can be configured for as many as 15 network objects (node + 8 start-stop + 6 control). Each W7760C can be configured for as many as 51 network objects (node + 8 start-stop + 10 control + 32 logic). The S7760A will support a maximum of 4 W7760A Building Manager node objects, a maximum of 10 W7760C Plant Controller node objects, and any combination of Excel10 application specific controller objects and Excel 15 control objects, not exceeding the limit of 270 network objects total.

Page 12: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 12

NOTE: Few control objects from a W7760A or C are config-ured for display in a S7760A Command Display.

The S7760A Command Display module can be configured to display alarm information from a W7760A Building Manager. To display the alarm data, the W7760A node object must be configured in the S7760A.

DATA SHARINGRefer to section �LonSpec Data Sharing� on page 38.

Configuring data sharing in LONSPEC� is primarily done as the individual controllers are already configured and requires no additional action by the user. However, the use of standard network shared points such as Outside Air Temperature and Economizer Enable must be configured using the �Refer Points� screen. See �Refer Points Applications� on page 40.

The LONSPEC�configuration screen �Refer Points� sorts the available destination points based on the source point. The sorting is based on the LonWorks® Standard Network

Variable Type (SNVT) which may include many controller variables that are very different in function. Refer to �Appendix A - Refer Points Tables� on page 43 for a complete listing of appropriate points for data sharing.

The W7760A Building Manager limit of scheduling a maximum of 20 network devices can be circumvented using �Refer Points� to share the schedule data to additional devices. See �Time of Day Scheduling� on page 40.

When using a single wall module with more than one Excel 10 controller, it is necessary to use �Refer Points� to share the wall module data from the source controller to the destination controller(s).

Data sharing for W7751 VAV terminal unit applications requires very specific attention to the application requirements. Refer to Excel 10 W7751B,D,D,F,H,J Variable Air Volume Controller Application Guide 74-2949 for specific application details and �XL10 VAV Terminal (W7751)� on page 39 for specific information on data sharing.

Page 13: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

13 74-3679�1

XL15B Solution Architecture

Fig. 2. XL15B Solution Architecture.

FTT-10 LONTALK ADAPTER OPTIONS FOR DIRCT CONNECT: DESK TOP PC - Q7760A OR PCLTA (3RD PARTY)

T7560A DIGITAL WALL MODULE CAN BE USED IN LEU OF T7770.

RAPIDLINK DEVICES CAN BE USED INSTEAD OF MODEMS.

LIMITED FUNCTIONALITY - DOES NOT SUPPORT SCHEDULING OR ALARM HANDLING.

Q7740 NETWORK REPEATER REQUIRED IF NETWORK WIRING EXCEEDS 4000 FT OR THE NUMBER OF CONTROL

DEVICES EXCEED 60.

EXCEL 15

W7760B

BUILDING

MANAGER

EXCEL 10

W7761A

REMOTE

INPUT/OUTPUT

DEVICE

M20939A

LONWORKS

FTT-10 BUS

®

LOCAL

PERSONAL

COMPUTER

MICROSOFT

INTERNET EXPLORER

LONSPEC

(PERSONAL

COMPUTER)

T7770

WALL

MODULE

EXCEL 10

W7751H, J

SMART

ACTUATOR

1 2 3

REMOTE

PERSONAL

COMPUTER

MICROSOFT

INTERNET EXPLORER

1

2

2

4

5

5

4

2

3

LONSPEC

(PERSONAL COMPUTER)

1

3

3 MODEM

MODEM

RS232

ETHERNET

Q7760A

SERIAL LONTALK

ADAPTER

EXCEL 10

W7750A

CVAHU

EXCEL 10

W7751B, D, F

VAV II

T7770

WALL

MODULE

2 T7770

WALL

MODULE

2T7770

WALL

MODULE

EXCEL 10

W7753A

UNIT

VENTILATOR

T7300F/Q7300H

THERMOSTAT

NOTEBOOK PC WITH PCMCIA SLOT-Q7752A PCMCIA-LTA

ISP

Back Select

S7760A

COMMAND

DISPLAY

T7350H

THERMOSTAT

Page 14: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 14

Fig. 2 depicts the options available in the XL15B Solution architecture.

The XL15B architecture utilizes the internet to access the LCBS system. The W7760B performs the network management functions and is a secure web server providing multi-user access to the system operating data, alarm and trend logs, and schedules using Microsoft® Internet Explorer (6.0 or higher) web browser.

The W7760B Building Manager supports:� W7760C&D Plant Controllers� W7750A,B,C CVAHU controller� W7751B,D,F,H,J VAV II controllers and Smart Actuators� W7753A Unit Ventilator controller� Q7300H Communicating sub-base for T7300 � T7350 Communicating sub-base� W7761A Remote Input Output Device� W7762A,B Hydronic Device� W7763C Cold Ceiling Device� W7752D,E,F,G,J Fan Coil Unit

CAUTIONThe S7760A Command Display will not support reading or changing schedules nor will it support alarm handling.The S7760A supports only W7760A Building Manager for scheduling and alarm handling. These functions are not available when using a W7760B Building Manager.

The S7760A can be used to read controller data and change setpoints and execute commands. The constraints are the same as those described for the XL15A solution, although, there will be no W7760A Building Manager in the mix of network objects.See page 11.

The W7760B will recognize and list other LONMARK® compliant devices including third party devices on the LONWORKS® bus but will not access them to read or write data. Following are the LCBS devices that are not supported:� ZL7762A LONSTATION�� W7760A Building Manager� S7760A (CD2) Command Display� Q7760A SLTA� RapidLink�� W7790A RF Gateway� XFL521 4-Digital Input Output Device

CAUTIONThe W7760A Building Manager is not supported in the XL15B architecture and must not be used with the W7760B Building Manager. While both the W7760A and W7760B may coexist on the same LONWORKS® bus, they do not support each other. It might result in conflicting of network functions if implemented in both devices. See Table 3 for a complete list of devices supported and a comparison of architecture features.

The W7760B Building Manager is configured using internal software tools. The remaining system devices are configured using ZL7760A LONSPEC� software configuration tool.

Networking ConsiderationsNETWORK CONSTRAINTSThe maximum number of devices on a LCBS LONWORKS® bus is 120 excluding LONTALK® adapters. The maximum number of devices on a subnet segment is 60. If more than 60 devices are used on a network, a Q7740 repeater is required.

The recommended maximum LONWORKS® bus cable length of a network segment is 9,200 feet (2,800 meters) with a Q7740 repeater and 4,600 feet (1,400 meters) without a repeater. The cable wire gage network topology will also determine the maximum cable length that can be used.

The maximum number of W7760B Building Managers on a sub-network is 1.

The maximum number of W7761A RIO devices is 3 per W7760C. You can use an RIO device on the network that is not associated with an W7760C strictly for monitoring the inputs. There will be no output control for that device.

The W7760B Building Manager is a web server. Precautions must be taken to insure appropriate LAN, WAN, and/or internet security to protect the server from unauthorized access.

WARNINGFailure to provide adequate internet security will result in unauthorized access to the W7760B Building Manager with severe consequences.

ALARM HANDLINGAll alarm handling is executed by the W7760B Building Manager.

Critical alarms are e-mailed to designated recipients.

The W7760B Building Manager supports multiuser access for operators.

The W7760B does not support the S7760A Command Display. Alarms cannot be routed to the W7760A.

Alarm data is accessible by internet if the user has access authorization.

Configuration ConsiderationsLONSPEC� (ZL7760A) is required to configure the supported controllers in XL15B solution. Since LONSPEC� is used to configure all LCBS control devices, the user must exercise care not to add devices that are not supported by the W7760B to the network.

In addition, Excel 15B can be a network interface when performing the following functions from LONSPEC�:

� Downloading all XL 10 and XL 15 devices' configurations.� Performing online functions like device diagnostics and

calibration.� Performing Device Discovery� Commission and configuration of Excel 15B from

LONSPEC�.� Upload or download Excel 15B configuration like alarms,

trends, schedules, and DLC loads from/to LONSPEC�.

Page 15: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

15 74-3679�1

Refer to LONSPEC� online help or LONSPEC� User�s Guide (form 74-2937).

Initial setup of the W7760B requires a PC running Windows® Hyper Terminal VT100 emulation that needs to be directly connected to the serial port of the W7760B.

The scheduling, alarm handling, DLC, and trend logging are configured using the W7760B Building Manager internal configuration capability and LAN, WAN, or internet access.

The W7760B Building Manager does scheduling for all supported devices on the LONWORKS® Network.� 20 Schedules� 20 alternate weekly schedules� 50 Holidays� 50 Temporary schedules

The W7760B Building Manager does Alarm Management for all supported devices on the LONWORKS® Network. All devices� internal alarms are automatically mapped.

Critical alarms can be configured to send e-mail annunciation to designated recipients.

A maximum of 500 user defined alarms can be configured.

The W7760B automatically creates a trend log for each supported XL10, XL15C plant controller, NXS/NXP/NXL VFD, T7350 and T7300F/Q7300H on the network.

The W7760B supports a maximum of 100 user created trend logs of 10 points each.

The W7760B does Building Management using DLC that monitors the building�s rate of energy consumption.

� Excel 15B supports a maximum of 50 load assignments across 120 objects.

� Each such load or a group of loads is further connected to an Excel 10 or Excel 15C output relay or an external load object.

� An XL 15C can be selected as the Pulse Meter input.

Page 16: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 16

RapidZone Architecture

Fig. 3. RapidZone Solution Architecture

Fig. 3 depicts the options available in the RapidZone architecture. Refer to the RapidZone Solution Application Guide (74-3449) for a detailed description.

RapidZone consists of the ZL7751A software configuration tool and is a subset of LCBS, designed specifically to meet the requirements of the zoned air handling systems market. The application uses the W7760C,D to control the air handling unit(s) and W7751J to control the individual zones.

RapidZone supports a maximum of 10 air handling units each with a maximum of 18 zones. The total number zones is limited by the network maximum of 120 devices.

The W7760A Building Manager is optional. It may be used to support scheduling and alarm handling. One W7760A may be used to schedule a maximum of 4 zoning units and associated zones. A single W7760A manages alarms for 1 W7760C RTU

Controller and 18 W7751J Zone Controllers. The number of W7760As required in a system is determined by the number of RTU�s that must have alarm reporting. A maximum of 10 W7760A�s can be used on a RapidZone LONWORKS® bus.

The term RTU used throughout the RapidZone documentation includes all the W7760C, CVAHU and Q7300 devices used in zoning applications.

See Table 3 for a complete list of devices supported and a comparison of architecture features.

Networking ConsiderationsThe ZL7751A RapidZone Configuration tool can be directly connected to the LonWorks® bus or connected via modem. Refer to LonWorks® for LCBS - Networking Considerations (form 74-2865).

Back Select

FTT-10 LONTALK ADAPTER OPTIONS FOR DIRCT CONNECT: DESKTOP PC - Q7760A OR PCLTA (3RD PARTY)

1 4 8 12 16

17 23 30 31 37 44

EXCEL 15

W7760A

BUILDING

MANAGER

1 4 8 12 16

17 23 30 31 37 44

EXCEL 15

W7760C

PLANT

MANAGER

(AHU CONTROLLER)

EXCEL 10

W7751J

SMART

ACTUATOR

M20940A

LONWORKS FTT-10 BUS®

Rapid Zone / LONSTATION

(PERSONAL COMPUTER)

T7770

WALL

MODULE

1 2 3

1

Rapid Zone / LONSTATION

(PERSONAL COMPUTER)

1

MODEM

MODEMQ7752A

SERIAL LONTALK

ADAPTER

S7760

COMMAND

DISPLAY

NOTEBOOK PC WITH PCMCIA SLOT-Q7752A PCMCIA-LTA

1 4 8 12 16

17 23 30 31 37 44

EXCEL 15

W7760A

BUILDING

MANAGER

1 4 8 12 16

17 23 30 31 37 44

EXCEL 15

W7760C

PLANT

MANAGER

(AHU CONTROLLER)

EXCEL 10

W7751J

SMART

ACTUATOR

T7770

WALL

MODULE

1 2 3

UP TO

10 RTU

2

EXCEL 10

W7750A

CVAHU

T7770

WALL MODULE

T7560A DIGITAL WALL MODULE MAY BE USED IN LEU OF T7770.2

T7300F/Q7300H

THERMOSTAT

Page 17: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

17 74-3679�1

The maximum number of devices on a LCBS LONWORKS® bus is 120 excluding LONTALK® adapters.

A RapidZone solution may have a maximum of 10 W7760A Building Managers, 10 W7760C Plant Managers (RTU controllers), and 18 W7751H,J Smart actuators for every W7760C. The maximum number of RTUs (any combination of W7760C, W7750, Q7300) on the network cannot exceed 50. Ensure that it does not exceed the total sub-network limit of 120 devices.

A Q7760A Repeater is required if the number of devices exceeds 60 or if the bus cable length exceeds the maximum allowable segment length.

ZL7762A LONSTATION� monitoring software can be used locally (direct connect) or remotely using a modem.

Configuration ConsiderationsIf a RapidZone configuration is to be imported into a LONSPEC� project that needs to be included in an XL15A architecture, the maximum number of XL15A�s in the RapidZone project is 10. However, when restored into LonSpec only the first four XL15A's can be modified. In order to be able to modify all W7760A's on the network through LONSPEC�, the total number of W7760A's configured in RapidZone must be limited to four.

If a RapidZone configuration is to be imported into a LONSPEC� project to be included in an XL15B architecture, no W7760A�s can be used. Scheduling and alarm handling must be configured with the W7760B Building Manager.

In both cases if S7760A Command Displays are to be used they should be configured in the LONSPEC� project and not in RapidZone.

Fig. 4 depicts the options available in the LonStat architecture.

LonStat Solution Architecture

Fig. 4. LonStat Solution Architecture.

A LonStat solution consist of T7300F commercial programmable thermostats with Q7300H communicating sub-base configured with ZL7300A LonStat configuration and monitoring software. A LonStat solution is used in the traditional commercial thermostat market when a communicating thermostat is required. LonStat does not support any other device. LONWORKS® compatible devices can reside on the same LONWORKS® bus but ZL7300A LonStat software will not recognize them.

T7300F/Q7300H thermostats do no support mechanical system alarms such as high or low limits, fan failure, or dirty filter. T7300F/Q7300H diagnostic alarms are reported when ZL7300 LonStat is used to monitor the specific thermostat in alarm.

Key advantages of using LonStat solution when compared to a traditional free standing commercial programmable thermostat installations are:� Current temperatures and setpoints can be checked

remotely with LonStat connected directly or remotely.� Setpoints, time, schedules, and bypass can be changed

with LonStat connected direct or remotely.

FTT-10 LONTALK ADAPTER OPTIONS FOR DIRCT CONNECT: DESK TOP PC - Q7760A OR PCLTA (3RD PARTY)

M20941A

LONWORKS FTT-10 BUS®

LONSTAT / LONSTATION

(PERSONAL COMPUTER)

1

LONSTAT / LONSTATION

(PERSONAL COMPUTER)

1

MODEM

MODEMQ7760

SERIAL LONTALK

ADAPTER

NOTEBOOK PC WITH PCMCIA SLOT-Q7752A PCMCIA-LTA

30

MAXIMUM

T7300F/Q7300H

COMMERCIAL

PROGRAMMABLE

THERMOSTAT

T7300F/Q7300H

COMMERCIAL

PROGRAMMABLE

THERMOSTAT

T7300F/Q7300H

COMMERCIAL

PROGRAMMABLE

THERMOSTAT

T7300F/Q7300H

COMMERCIAL

PROGRAMMABLE

THERMOSTAT

Page 18: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 18

� With master time keeping, all thermostats maintain the same time. Changing the master time keeper will update all other thermostats within one minute.

� With master scheduling, multiple thermostats can be �zoned� to maintain the same schedule. Changing the schedule of a single thermostat changes the schedule for all thermostats in the zone.With a discharge air sensor installed, mechanical system troubleshooting can be done remotely.

Networking ConsiderationsZL7300A LonStat will communicate with only one thermostat at a time.

See Table 3 for a complete list of devices supported and a comparison of architecture features.

Configuration ConsiderationsZL7300 LonStat does not create a database. It must be connected to the LONWORKS® bus directly or remotely by modem. LonStat reads all configuration and operating data directly from the thermostat. Changes made with LonStat are downloaded to the thermostat, no record of the configuration is retained on the PC. Since no LonStat database exists, a LonStat solution cannot be restored to LONSPEC�.

LonStat and LONSTATION� can be used to monitor a LonStat solution both locally and remotely.

The T7300F/Q7300H thermostat/sub-base has no configurable alarms. Internal diagnostic alarms are displayed in LonStat and LONSTATION� only when the thermostat is selected for monitoring.

Unconfigured CVAHU Architecture

Fig. 5. Unconfigured CVAHU Architecture

Fig. 5 depicts the options available in the Unconfigured CVAHU solution architecture.

The Unconfigured CVAHU Solution architecture provides a - no configuration XL10 constant volume air handling unit solution (use it directly out of the box). The W7750A,B,C controllers are the only control devices supported in this option. Monitoring is not supported as part of this solution.

Each unconfigured W7750 controller provides the control functions of a T7300 thermostat. The bypass and setpoint inputs if used, will work individually for the W7750 to which it is connected.

The Unconfigured CVAHU solution is a simple cost effective alternative to programmable thermostats especially when night setback is required for multiple air handling units running on the same schedule. This solution uses a simple wall module without the complexity of a programmable thermostat, simplifying operation for the user.

Since no configuration programming is required for the W7750�s the cost of installing the network is offset by lower labor cost.

The Unconfigured CVAHU solution does not require the installer to be knowledgeable of direct digital control system operation. Simply install the controllers, wire them, turn on the power, and the job is done.

The factory default configuration for all models of the W7750 controller sets digital input 1 as a time clock input and digital input 2 as Schedule Master. Placing a jumper across digital input 2 causes the Schedule Master controller to broadcast the occupancy mode. W7750 controllers that do not have the jumper will automatically follow the schedule of the one that does. Only one W7750 on the LONWORKS® bus can be designated as the Schedule Master.

WARNINGDownloading to a W7750 CVAHU controller from any configuration tool overwrites the factory default settings and the automatic binding capability is lost and cannot be restored. The W7750 controller factory default configuration settings must be accepted for all functions. Refer to Excel 10 W7750A,B,C Application Engineering manuals for complete details on factory default configuration.

See Table 3 for a complete list of devices supported and a comparison of architecture features.

Q7740AREPEATER

EXCEL 10W7750A CVAHU

T7770WALL

MODULE

EXCEL 10W7750A CVAHU

T7770WALL

MODULE

EXCEL 10W7750A CVAHU

T7770WALL

MODULE

EXCEL 10W7750A CVAHU

T7770WALL

MODULE

EXCEL 10W7750A CVAHU

M20942

EXCEL 10W7750A CVAHU

T7770WALL

MODULE

T7770WALL

MODULE

EXCEL 10W7750A CVAHU

T7770WALL

MODULE

EXCEL 10W7750A CVAHU

T7770WALL

MODULE

TIMECLOCK

Page 19: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

19 74-3679�1

Networking ConsiderationsAll devices must be connected to the LONWORKS® FTT-10 bus.

A maximum of 120 W770 CVAHU controllers can be connected to the network.

Zoning for multiple schedules can be created by adding multiple networks each with it�s own time clock and master scheduler jumper installed on one and only one W7750.

Configuration ConsiderationsNo configuration is required. The Unconfigured CVAHU solution uses the factory defaults.

The factor defaults for the Excel 10 W7750 CVAHU controllers includes an algorithm that binds all controllers without the Schedule Master input (digital input 2) to the one on the network that does have the input jumpered. A time clock is connected to the Time Clock input (digital input 1). The scheduled occupancy state of the Schedule Master W7750 is then shared to all others on the network.

LCBS Components

LONWORKS® BusFor more information, refer to LonWorks® Bus Wiring Guidelines (form 74-2865).

XL15 Network Management and General Purpose ControllersXL15 W7760A BUILDING MANAGERThe W7760A provides both network management functions and general purpose control functions. The network and control functions are configured with LONSPEC� or RapidZone configuration software.

For a complete description, refer to the documents listed for W7760A in �Applicable Literature� on page 5

� Physical Inputs and Outputs:� 8 analog inputs; configurable for resistance, voltage,

current, English or Systems International engineering units

� 8 digital inputs; dry contacts configurable for main-tained, momentary, counter (2), or totalizer operation (2)

� 2 analog outputs; 0 to 20 mA configurable for standard control signal ranges up to 10 Vdc

� 8 digital outputs; configurable as maintained on-off, momentary on-off, floating (modulating), and pulse width modulated (PWM).

� Supports up to 3 W7761A Remote Input - Output (RIO) devices for additional input and output capacity.

� Network management:� Eight 365 day schedules for a maximum of 20 network

objects plus internal control and start-stop functions.� Trend, Run Time, Bypass, and Alarm logs� Alarm annunciation management� Alarm dial-out to LONSTATION�� Demand Limit Control

� Control Functions:� 8 start-stop loops� 6 PID control loops� 8 logic functions

XL15B W7760B BUILDING MANAGERThe W7760B provides network management plus internet web server functions. The W7760B is configured with internal tools using Microsoft® Internet Explorer version 5.5 or higher.

For a complete description refer to the documents listed for W7760B in �Applicable Literature� on page 5.

� Physical Inputs and Outputs - None

� Network Management� Twenty 365 day schedules for a maximum of 120 net-

work controllers.� Trend Logs

- Automatically configured for each XL10, XL15C and/or T7300F/Q7300H.

- 100 user defined� Schedules

- 20 Schedules- 20 alternate weekly schedules- 50 Holidays- 50 Temporary schedules

� Alarm logs- 500 user defined alarms

� Alarm e-mail� Multi-user access� DLC

- Select XL15C as Pulse Meter input.- Assign 50 DLC loads to 120 objects across the

network.- Enable overriding a configured load.

� Control Functions: None.

XL15C W7760C PLANT MANAGERThe W7760C is a general purpose controller that can be configured to meet the control requirements of mechanical rooms and air handling units. The control functions are configured with LONSPEC� or RapidZone configuration software.

For a complete description refer to the documents listed for W7760C in �Applicable Literature� on page 5.

� Physical Inputs and Outputs:� 8 analog inputs; configurable for resistance, voltage,

current, English or Systems International engineering units

� 8 digital inputs; dry contacts configurable for main-tained, momentary, counter (2), or totalizer operation (2)

� 6 analog outputs; 0 to 20 mA configurable for standard control signal ranges up to 10 Vdc

� 8 digital outputs; configurable as maintained on-off, momentary on-off, floating (modulating), and pulse width modulated (PWM).

� Supports up to 3 W7761A Remote Input - Output (RIO) devices for additional input and output capacity

� Network management - none

Page 20: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 20

� Control functions� 8 start-stop loops� 10 enhanced PID control loops� 32 logic loops� 30 math functions

XL10 Application Specific ControllersXL10 - W7750A,B,C CONSTANT VOLUME AIR HANDLING UNIT CONTROLLERSThe W7750A,B,C controllers are application specific to single zone constant volume air handling units including roof top units, split systems, heat pumps meeting the LONMARK® HVAC profile 8030. The control algorithm is imbedded in the controller and can be configured to meet specific application requirements by changing default parameter settings using LONSPEC�. The controller can operate as a stand alone device or as part of a LONWORKS® network system.

For a complete description, refer to the documents listed for W7750A,B,C in �Applicable Literature� on page 5.

Table 2. W7750A,B,C Physical Inputs and Outputs.

XL10 W7751B,D,F VARIABLE AIR VOLUME TERMINAL CONTROLLERThe W7751B,D,F variable air volume terminal unit controller (VAV II) are application specific to variable volume terminal unit control that are as per the LonMark® HVAC profile 8010. The control algorithm is imbedded in the controller and can be configured to meet specific application requirements by changing default parameter settings using LONSPEC�. The controller can operate as a stand alone device or as part of a LONWORKS® network system.

For a complete description refer to the documents listed for W7751B,D,F in �Applicable Literature� on page 5

Physical Inputs and Outputs:� Analog Inputs - 5� Digital Inputs - 5� Analog Outputs - 0� Digital Outputs - 8 (may be configured as floating or pulse

width modulated for modulating applications)

XL10 W7751H,J SMART ACTUATORThe W7751H,J Smart Actuators are application specific to variable volume terminal unit control that is as per the LonMark® HVAC profile 8010. The control algorithm is

imbedded in the controller and can be configured to meet specific application requirements by changing default parameter settings using LONSPEC� or RapidZone. The controller can operate as a stand alone device or as part of a LONWORKS® network system.

For a complete description, refer to the documents listed for W7751H,J in �Applicable Literature� on page 5

Physical Inputs and Outputs:� Analog Inputs - W7751H - 4; W7751J - 3� Digital Inputs -1� Analog Outputs - 0� Digital Outputs - 4 (2 configured for floating)

XL10 W7752A FAN COIL UNIT CONTROLLERThe W7751H,J Smart Actuators are application specific to fan coil units that are as per the LONMARK® HVAC profile 8020. The control algorithm is imbedded in the controller and can be configured to meet specific application requirements by changing default parameter settings using LONSPEC�. The controller can operate as a stand alone device or as part of a LONWORKS® network system. For a complete description, refer to the documents listed for W7752A in �Applicable Literature� on page 5.

Physical Inputs and Outputs:� Analog inputs - 3� Digital inputs - 2� Analog outputs - 0� Digital outputs - 9 (may be configured as floating or pulse

width modulated for modulating applications)

XL10 W7753A UNIT VENTILATOR CONTROLLERThe W7753A Unit Ventilator Controllers are application specific to fan coil units that are as per the LONMARK® HVAC profile 8080. The control algorithm is imbedded in the controller and can be configured to meet specific application requirements by changing default parameter settings using LONSPEC�. The controller can operate as a stand alone device or as part of a LONWORKS® network system.

For a complete description, refer to the documents listed for W7753A in �Applicable Literature� on page 5.

Physical Inputs and Outputs:� Analog Inputs - 6� Digital Inputs - 5� Analog Outputs - 0� Digital Outputs - 9 (may be configured as floating or pulse

width modulated for modulating applications)

NOTE: One W7753A Digital output reserved for Bypass LED.

XL15 W7761A REMOTE INPUT/OUTPUT DEVICEThe W7761A Remote Input-Output Device provides additional physical inputs and outputs for the W7760A and W7760C Controllers. Up to 3 W7761A can be associated to each W7760A or C. The W77601A cannot be shared by 2 or more W7760A�s or C�s. The W7761A functions only on a LONWORKS® Bus and cannot be used as stand-alone. The W7761A is configured with LONSPEC�.

For a complete description, refer to the documents listed for W7761A in �Applicable Literature� on page 5.

W7750 A B CAnalog Inputs 3 6 6Digital Inputs 3 5 5Analog Outputs 0 0 31

1 4 to 20 mA. May be used with 2 to 10 Vdc devices by adding a dropping resister.

Digital Outputs2

2 One output reserved for Bypass LED

73

3 6 dry contacts, 2 may be configured for floating (modulating) control of the economizer dampers.

94

4 Traic outputs, may be configured as floating or pulse width modulating for control of economizer dampers, heating valve, and/or cooling valve.

64

Page 21: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

21 74-3679�1

Physical Inputs and Outputs:� Analog Inputs - 6� Digital Inputs - 4� Analog Outputs - 0� Digital Outputs - 8 (may be configured as floating or pulse

width modulated for modulating applications)

XL10 W7762B HYDRONIC CONTROLLERThe W7762B Hydronic controller is application specific to simple heating/cooling (thermostat and valve) applications that are as per the LONMARK® HVAC profile 8020. Applications include control of fin tube radiation, convectors, fan coil units with manual fan control, and pressure dependant VAV terminal units. The control algorithm is imbedded in the controller and can be configured to meet specific application requirements by changing default parameter settings using LONSPEC�. The controller can operate as a stand alone device or as part of a LONWORKS® network system. For a complete description, refer to the documents listed for W7762B in �Applicable Literature� on page 5.

Physical Inputs and Outputs:� Analog Inputs - 2� Digital Inputs - 1� Analog Outputs - 0� Digital Outputs - 4 (may be configured as floating or pulse

width modulated for modulating applications)

XL10 W7763C HYDRONIC CONTROLLERThe W7763C Hydronic controller with integrated wall module is application specific to simple heating/cooling (thermostat and valve) applications that are as per the LONMARK® HVAC profile 8020. Applications include control of chilled ceiling panels, fin tube radiation, convectors, fan coil units with manual fan control, and pressure dependant VAV terminal units. The control algorithm is imbedded in the controller and can be configured using LONSPEC� to meet specific application requirements by changing default parameter settings. The controller can operate as a stand alone device or as part of LONWORKS® underwork system.

NOTE: For a complete description, refer to documents listed for W7763C in �Applicable Literature� on page 5.

Physical Inputs and Outputs:� Analog Inputs - 2� Digital Inputs - 3� Analog Outputs - 0� Digital Outputs - 4 (may be configured as floating or pulse

width modulated for modulating applications)

Other devicesS7760A COMMAND DISPLAY UNITThe S7760A Command Display Unit is a user interface providing menu driven access to a Light Commercial Building Solution system. The S7760A is configured with LONSPEC� or RapidZone software configuration tools to display data, modify setpoints, and schedules for LCBS object on the LONWORKS® bus. Multiple S7760A�s may be used on a network.

For a complete description, refer to the documents listed for S7760A in �Applicable Literature� on page 5

T7300F/Q7300H THERMOSTATThe T7300F/Q7300H Thermostat/Sub-base is application specific to commercial programmable thermostat applications that are as per the LONMARK® HVAC profile 8060 object type 09. Applications include control of Single zone air handling units and heat pumps. The control algorithm is imbedded in the T7300F and can be configured to meet specific application requirements by changing default parameter settings using LONSPEC�, LonStat or the integral keypad. The T7300 can operate as a stand alone device or as part of a LONWORKS® network system.

For a complete description, refer to the documents listed for T7300 or Q7300 in �Applicable Literature� on page 5

T7350 COMMUNICATING SUBBASEThe T7350 Thermostat/Sub-base is application specific to commercial programmable thermostat. Different subbases are used for different applications including Three Heat or Three Cool, or Two Heat or Four Cool, Modulating Outputs, and Dehumidification High Limit Control. Each subbase is compatible with the common cover assembly. LONSPEC� supports configuration of the following two types of T7350:

� T7350H1009: Three Heat/Three Cool model; allows for conventional or heat pump operation. Total of 8 relays are available with the thermostat cover assembly and subbase. The auxiliary relay can be configured for an economizer, TOD, or dehumidification. The subbase can be configured for 3 Heat/3 Cool or 2 Heat/ 4 Cool by using the third stage of heat for an additional stage of cooling.

� T7350H1017: Modulating subbase. A total of 4 relays are available with the thermostat cover assembly and subbase. The auxiliary relay may be configured for an economizer, TOD, dehumidification or an additional stage of heating and cooling.

NOTE: For a complete description, refer to documents listed for T7350 in �Applicable Literature� on page 5

CXS AND CXL VARIABLE FREQUENCY DRIVESThe CXS and CXL Variable Frequency Drives (VFD) are used to control motor speeds for fans and pumps in commercial heating, ventilating, and air conditioning systems. The VFD application is configured using the built in operator interface. The LONWORKS® interface is configured using the LONSPEC� configuration tool.

NX VARIABLE FREQUENCY DRIVEThe VACON NX frequency converter (NXVFD) is an electronic device used for controlling speed and torque of three-phase AC motors. It converts the fixed frequency and voltage of the main supply (mains) to a variable frequency and voltage that can then be regulated to provide flexible motor operation and further reduce energy consumption.

The NX VFD application is configured using the built in operator interface. The LONWORKS® interface is configured using the LONSPEC� configuration tool.

NOTE: The NXL VFD utilizes single phase input power and provides three phase output.

Page 22: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 22

LONTALK® ADAPTERS� Q7760A2001 External Serial LONTALK® Adapter,

SLTA-10, FT-10) with standard RS 232 9 pin male to 9 pin female cable (refer to form, 95-7511-2).- external device to connect LONTALK® bus to RS-232 serial port of PC or modem.

� Q7752B PCC-10 FT-10 (O.S. Number Q7752B2009) LONTALK® CARD -Type II PCMCIA card (refer to form, 95-7613) - for use with notebook PC's equipped with Type II PCMCIA slots.

� PCLTA-10 FT-10 LONTALK® Adapter board (from Echelon) - half length ISA board for internal installation in a PC with an ISA slot available.

� PCLTA-20 FT-10 LONTALK® Adapter board (from Echelon) - half length PCI board for internal installation in a PC with a PCI slot available.

� RapidLink� Dialup Network Adapter with standard RS 232 9 pin male to 9 pin female cable.

� External Modem(s): 3COM U.S. Robotics 5686D,V.90/V.92 56K Standard compatible.

� Honeywell XM500-US TCP/IP modem for LAN/WAN connection (replacement for telephone line connection).

� Excel 15B (for accessing, give the appropriate IP address, User ID, and password details).

LONTALK® adapters are used to connect PCs� to the LONTALK® bus. The function of LONTALK® is to convert the data from the PC communication format to the LONWORKS® protocol.

Selection of the type of adapter depends on the computer and application. The Q7752B laptop and PCLTA-10/20 desktop are installed in the PC and can only be used for directly connecting the PC to the LONWORKS® bus. The external Q7760A LONTALK® Adapter or Q7770A RapidLink Dial-up Network Adapter is required for modem connection to the PC.

LONTALK® adapters connected directly to the bus are automatically configured. Only a Q7760A or Q7770A RapidLink Dial-up Network Adapter (Q7760A used with a modem) requires configuration with LONSPEC�, RapidZone or LONSTAT�.

The practical limit to the number of LONTALK® adapters connected to a single network is 3: one directly connected to a PC running LONSTATION�, another directly connected to a PC running LONSPEC�, and one more connected remotely by a modem to a PC running either LONSPEC�, or LONSTATION�. Multiple directly connected PCs� running either LONSPEC� or LONSTATION� can result in data collisions leading to communication failures.

Configuration ToolsThe following are the three software configuration tools that can be used to configure LCBS solutions:

LONSPEC� (ZL7760A)LONSPEC� is the general purpose configuration tool used to configure all LCBS network devices. LONSPEC� is required to configure XL15A and XL15B solutions. LONSPEC� can be used to monitor systems if no automatic dialing is required.

RAPIDZONE (ZL7751A)RapidZone is an application driven configuration tool used to configure W7760C Plant Manager, W7750A,B,C and T7300F/Q7300H single zone RTU, W7751J Smart Actuator, W7760A Building Manager, and S7760A Command Display for commercial zoning applications. Device configuration is automatic based on application data entered into the tool. RapidZone projects with 10 or less W7760A Plant Managers can be restored to LONSPEC�. RapidZone can be used to monitor RapidZone systems if support for automatic dialing is not required.

NOTE: LONSPEC� can only configure the first four W7760A Controllers on the network.

LONSTAT� (ZL7300A)LonStat� is an application driven configuration and monitoring tool used in projects that are comprised exclusively of T7300F/Q7300H commercial programmable thermostats. LonStat can be used only to configure the thermostats and monitor thermostat data. No alarm reporting is supported.

Page 23: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

23 74-3679�1

LCBS Architecture Comparison

a W7751 models supported by RapidZone are only W7751J,H (pressure-dependant).b Limited capability - does not support scheduling or alarm handlingc 3rd party devices must be configured with the manufacturer�s configuration tool and LonMark® compliant data can be read by

LONSTATION�.d 3rd party devices may coexist on the LonTalk® bus and will be identified in the W7760B Building Manager device list, but no

data can be read from or written to the device.

Table 3. LCBS Architecture Comparison.

Product/Feature XL15A XL15B RapidZone LonStatUnconfigured

CVAHUHardware

W7750A,B,C CVAHU Controller X X X XW7751B,D,F VAV II Controller X XW7751H,J Smart Actuator X X Xa

W7752A Fan Coil Unit Controller X XW7753A Unit Vent Controller X XW7760A Building Manager X XW7760B Building Manager XW7760C Plant Controller X X XW7760D Plant Controller X XW7761A Remote I/O Device X XW7762B Hydronic Controller X XW7763C Chilled Ceiling Controller X XS7760A Command Display Unit X Xb X

T7300F/Q7300H Thermostat X X X XT7350 Communicating Subbase X XRapidLink X X

3rd Party Devices c Xd

SoftwareZL7300A LONSTAT� XZL7751A RapidZone XZL7760A LONSPEC� X XZL7762A LONSTATION� and Graphics X X X

Features

LONWORKS® FTT-10 Bus X X X X X

Scheduling X X X XSelf Configuring XAlarm Handling X X XTrend Logs X X XRun Time Logs X XBypass Logs X XDemand Limit Control X XAlarm Dial-out XAlarm E-mail XInternet Access XMulti-user Access X

Page 24: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 24

APPLICATION STEPSOverviewThe application steps shown in Table 4 are planning considerations for engineering a Light Commercial Building Solution. These steps are guidelines intended to aid understanding: selection of appropriate control devices, selection of appropriate operator interface devices and software, LONWORKS® bus arrangement choices, power requirements, network device configuration options, and system startup and commissioning.

Table 4. Application Steps.

Step 1. Plan the SystemReview the plans and specifications, system requirements documentation, sales estimates, and/or any other documents defining control system operation, user interface functions, and data management requirements to determine the LCBS architecture best suited for the project.

The Light Commercial Building Solution (LCBS) was developed to address the HVAC control requirements typically found in small to medium sized commercial buildings. For large complex buildings, the EXCEL 5000 Open system provides an appropriate solution.

When planning the system layout, consider potential expansion possibilities to allow for future growth. Planning is very important to enable addition of HVAC systems and controllers in future projects.

The first consideration in selecting the architecture is what monitoring and data gathering requirements exist. This selection will determine the Building Manager that needs to be used, if any. LONSTATION� is used to monitor XL15A, RapidZone, and LonStat� solution architectures.

The XL15B solution is monitored with Microsoft® Internet Explorer and requires a local area network (LAN), wide area network (WAN), or internet connection.

WARNINGDo not install the W7760A and W7760B Building managers on the same network. Both devices may co-exist on the same network, but scheduling, alarm handling, and logging are configured with different tools (probability of data conflict is high).LONSPEC� supports both the W7760A and W7760B. LONSPEC� also uses W7760B as a network interface to connect online. W7760B has internal configuration settings and does not support the W7760A.

Refer to Table 3 LCBS Architecture Comparison for a brief comparison of W7760A and W7760B Building Manager capabilities.

Select the controllers that are supported by the application. Excel10 application specific controllers are available for HVAC equipment typically used in the target market. These include constant volume air handling units (CVAHU), variable air volume terminal units (VAV II), fan coil units (FCU), unit ventilators (UV), Hydronic units (HYD), Remote Input/Output unit (RIO), Chilled Ceiling Controller (CHC), thermostats and valve applications (fin tube radiation, convector, manual fan FCU, unit heater). T7350 and T7300F/Q7300H thermostats are available for applications requiring programmable thermostats. Refer to the respective Excel 10 controller, T7350 and/or T7300F/Q7300H Application Guide for specific information regarding input/output requirements, controller operation, and configuration. See Table 1 on page 5 to identify literature for a specific controller.

The XL15 controllers (W7760A,C) are used for custom applications such as mechanical room control, variable volume air handling units, specialized air handling systems, lighting control, and equipment scheduling.

Command Display (CD and CD2) allows viewing and modifying the parameters of other units over the LonWorks® network.

Refer to the respective Excel 15 controller Application Guide for specific information regarding input/output requirements, controller operation, and configuration. See Table 1 on page 5 to identify literature for a specific controller.

Other units are:� CXS/CXL Honeywell Variable Frequency Drive (VFD)

The Excel VRL CX/CXL/CXS frequency drive is used for controlling speed and torque of three-phase AC motors. Excel VRL CX/CXL/CXS frequency converters can be connected to LonWorks® network by using CX203OPT option board. They can then be controlled, monitored, and programmed from the LonWorks® network.

� Vacon NX Variable Frequency Drive (NXS/NXP/NXL VFD)Vacon NX frequency converter (NXVFD) is used to control speed and torque of three-phase AC motors. Refer to www.Vacon.com for more information on NX VFD. The NX VFD can be connected to LonWorks® network using NXOPTC4 option board. They can then be controlled, monitored, and programmed from the LONWORKS® network through LONSPEC�.

Determine the input and output device requirements for each controller used in the system. Select input and output devices compatible with the controller and the application. Consider the operating range, wiring requirements, and the environment conditions when selecting input/output devices. When selecting actuators for modulating applications consider using floating control. In direct digital control applications floating actuators will generally provide control action equal to or better than an analog input actuator for lower cost.

Determine the location of controllers, sensor, actuators and other input/output devices and create wiring diagrams. See �Step 3. Prepare Wiring Diagrams� on page 29.

Step No. Description1 Plan the System.2 Lay Out Communications and Power Wiring.3 Prepare Wiring Diagrams.4 Order Equipment.5 Configure Controllers.6 System Startup.

Light Commercial Building Solution

Page 25: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

25 74-3679�1

The application engineer must review the Direct Digital Control (DDC) job requirements. This includes the Sequences of Operation for the W7760A,C Controllers, and for the system as a whole. Usually there are variables that must be passed between the W7760A,C Controllers and other Excel 10 controller(s) that are required for optimum system wide operation. Typical examples are the TOD, Occ/Unocc signal, the outdoor air temperature, the demand limit control signal, and the smoke control mode signal.

It is important to understand these interrelationships early in the job engineering process to ensure implementation when configuring the controllers. Refer to the controller Application Guides (see Table 1 on page 5), the LONSPEC� ZL7760A software Help for configuring information for LCBS devices, and �LonSpec Data Sharing� on page 38.

The LONWORKS® Bus FTT-10A communication wiring between controllers is a free topology scheme that supports daisy chain, T-tap, star, and/or loop, wiring configurations. Refer to the LONWORKS® Bus Wiring Guidelines form,74-2865 for complete description of network topology rules. See Application Step 2. Lay Out Communications and Power Wiring for more information on bus wiring layout, and see Application Step 4. Prepare Wiring Diagrams, for wiring details.

The Light Commercial Building Solution implementation of LonWorks® supports 1 subnet per network while routers are not supported. Since there is only 1 sub-network per network in the LCBS, all capabilities and limitations of a sub-network apply to the network. The term network is often used in lieu of sub-network in LCBS discussions.

A sub-network supports a maximum of 127 nodes. Each LONWORKS® Bus device constitutes one node.

A maximum of 120 LCBS devices can be configured on a single LONWORKS® Bus sub-network. LONSPEC� and RapidZone reserves seven nodes for LONTALK® adapters for connecting software tools. The remaining 120 nodes are used for LCBS devices.

If the number of LCBS devices on the sub-network exceeds 60, a Q7740 repeater is required.

In an XL15A solution further limitations on the number of devices on a bus may result from alarm handling requirements.� The maximum number of W7760A Building Managers on a

sub-network is 4. � The maximum number of W7761A RIO devices is 3 per

W7760A and C.� The maximum number of external nodes that can be

mapped to a W7760A will support is 20.� The maximum number of nodes with alarm reporting is 84

(4 W7760A plus 4 X 20 external = 84). Additional devices may used up to the maximum of 120. However, only 84 devices will report alarms.

� Each W7760C control loop function� Each W7760A can support alarm handling for a maximum

of 20 network objects in addition to itself and the associated W7761A�s. Each control device on the network is 1 object effectively limiting the sub-network to 96 control devices In addition each W7760C Plant Manager control loop and logic loop is a network object.

� Each W7760A and C, Excel 15 controllers will support a maximum of 3 W7761A Remote Input/Output (RIO) devices. A W7761 must be associated with a W7760A or C and cannot be associated to more than 1 W7760A or C. Therefore, the maximum number of W7761A�s in a network is limited to 3 times the number of W7760A and C�s.

Refer to LonWorks® for LCBS (form number 74-2865_2) for complete description of network topology rules and the maximum wire length limitations. If a longer LONWORKS® Bus sub-network is required, a Q7740 Repeater can be added to extend its length. Each sub-network can have a maximum of one repeater.

All LONWORKS® Bus segments require a termination device. Doubly terminated daisy-chain requires 2 termination devices. For more details on LONWORKS® Bus termination, refer to LonWorks® for LCBS - Cable Termination (form number 74-2865_2) or see Application Step 3. Lay Out Communications and Power Wiring, and the LONWORKS® Bus Termination Module subsection in Application Step 4.

Step 2. LayOut Communications and Power Wiring

CommunicationsThe LONWORKS® Bus communications bus is a 78 kbps serial link that uses transformer isolation and differential Manchester encoding.

Installation of communications wiring requires special considerations that may vary from project to project. It is important that exact installation instructions be provided to the installer.

Guidelines for communications wiring are as follows:� All field wiring must conform to local codes and ordinances.� Approved cable types for LONWORKS® Bus communications

wiring is Level IV 22 AWG (0.34 mm2) plenum or non-plenum rated unshielded, twisted pair conductors. For non-plenum areas, Honeywell U.S. part AK3781 (one pair) or U.S. part AK3782 (two pair) can be used. In plenum areas, U.S. part AK3791 (one pair) or U.S. part AK3792 (two pair) can be used. Additionally, Echelon® approved cable can be used. Contact Echelon® Corp. Technical Support for the recommended vendors of Echelon® approved cables (refer to LonWorks® for LCBS - Network Cabling and Connections - Table 8 through 12, form 74-2865).

� Unswitched 24 Vac power wiring can be run in the same conduit as the LONWORKS® Bus cable.

� Do not bundle output wires with sensors, digital inputs, or communications LONWORKS® Bus wires.

� Do not use different wire types or gauges on the same LONWORKS® Bus segment. Using different wire types or gauges can result in line impedance changes that can cause unpredictable reflections on the LONWORKS® Bus.

� In noisy (high EMI) environments, avoid wires running parallel to noisy power cables, motor control centers, or lines containing lighting dimmer switches, and keep at least 3 in. (76 mm) of separation between noisy lines and the LONWORKS® Bus cable.

� Each LONWORKS® Bus segment containing up to 120 (see Table 18) Excel 15/10 Controllers, T7350s, T7300F/Q7300Hs, Command Displays, requires the installation of a 209541B Termination Module for a single terminated

Page 26: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 26

LONWORKS® Bus or two 209541B Termination Modules for a doubly terminated LONWORKS® Bus. For more details on LONWORKS® Bus termination, refer to LonWorks® for LCBS - Cable Termination (form number 74-2865_2).

� Make sure that neither of the LONWORKS® Bus wires is grounded.

� LONWORKS® Bus cable extended to T7770 Wall Modules to connect the LONWORKS® jack must be included in the total wire length.

NOTE: For specific wiring details, see Step 4. For wall module wiring, use U.S. part AK3782 (non-plenum) or U.S. part AK3792 (plenum). For an LONWORKS® Bus that is a doubly terminated daisy-chain, these cables contain two twisted pairs (one for the run to the wall module, and one for the run back to the controller) for ease of installation.

� If a longer LONWORKS® Bus segment is required, a Q7740 Repeater can be added to extend its length. Each sub-network can have a maximum of one repeater. If a Q7740 repeater is used, each sub-net segment must be terminated as described (refer to LonWorks® for LCBS - Cable Termination (form number 74-2865_2).

NOTE: Special consideration must be given to connecting the LONWORK®S Bus to the W7760A Building Manager and W7760C Plant Manager. Each is built with 2 pairs of terminals for connecting the bus. The jumper between the terminal pairs is on the controller printed circuit board. Removing the controller from the sub-base will interrupt the bus circuit. To maintain sub-net circuit continuity install jumpers between terminals or install the �in� and �out� bus cable on the same terminals. See W7760 LonWorks® Wiring Option Fig. 6 through 8.

Fig. 6. W7760 LonWorks wiring option 1.

Fig. 7. W7760 LonWorks wiring option 2.

Fig. 8. W7760 LonWorks wiring option 3.

PowerA power budget must be calculated for each device to determine the required transformer size for proper operation. A power budget is simply the summing of the maximum power draw ratings (in VA) of all the devices to be controlled. This includes the controller itself and any devices powered from the controller such as equipment actuators (ML6161, or other motors) and various contactors and transducers.

IMPORTANT� If a controller is used on Heating and Cooling

Equipment (UL 1995, U.S. only) and transformer primary power is more than 150 volts, connect the transformer secondary common to earth ground.

� When multiple controllers operate from a single transformer, you must connect the same side of the transformer secondary to the same power input terminal in each device. The earth ground terminal (W7760C Terminal 49) must be connected to a verified earth ground for each controller in the group.

41

LONWORKS LONWORKS

LONWORKS FTT-10

M19418

42

W7760A

W7760C

43 44

1

LO

NW

OR

KS

2

13

14

1

LO

NW

OR

KS

2

15

16

41

LONWORKS LONWORKS

LONWORKS FTT-10

M19419

42

W7760A

W7760C

43 44

1

LO

NW

OR

KS

2

13

14

1

LO

NW

OR

KS

2

15

16

41

LONWORKS LONWORKS

LONWORKS FTT-10M19420

42

W7760A

W7760C

43 44

1

LO

NW

OR

KS

2

13

14

1

LO

NW

OR

KS

2

15

16

Page 27: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

27 74-3679�1

POWER BUDGET CALCULATION EXAMPLEThe following is an example power budget calculation for a typical W7760C Excel 15 Plant Controller. While the example is shown for a W7760C the process is applicable for all LCBS controllers.

Assume a W7760C unit with a fan, two stages of D/X cooling, modulating steam valve for heating, and modulating economizer dampers. The power requirements are:

The W7760C System example requires 41.9 VA of peak power; therefore, a 75 VA AT88A Transformer could be used to power one controller of this type, or a 100 VA AT92A Transformer could be used to power two of these Plant Controllers and meet NEC Class 2 restrictions (no greater than 100 VA). See Fig. 44 and 45 for illustrations of power wiring details. See Table 5 for VA ratings of various devices.

Table 5. VA Ratings For Transformer Sizing.

For contactors and similar devices, the in-rush power ratings should be used as the worst case values when performing power budget calculations. Also, the application engineer must consider the possible combinations of simultaneously energized outputs and calculate the VA ratings accordingly. The worst case, that uses the largest possible VA load, should be determined when sizing the transformer.

Each W7760C requires 24 Vac power from an energy-limited Class II Power Source. To conform to Class II restrictions (U.S. only), transformers must not be larger than 100 VA. A single transformer can power more than one W7760C Controller. Fig. 9 shows a generic power wiring diagram for multiple devices using one transformer.

IMPORTANTUse the heaviest gauge wire available, up to 14 AWG (2.0 mm2) with a minimum of 18 AWG (1.0 mm2), for all power and earth ground wiring.

Screw type terminal blocks are designed to accept only one 14 AWG (2.0 mm2) conductor. Two or more wires that are 14 AWG (2.0 mm2) can be connected with a wire nut. Include a pigtail with this wire group and attach the pigtail to the terminal block.

GUIDELINES FOR POWER WIRING ARE AS FOLLOWS:� For multiple controllers operating from a single transformer,

the same side of the transformer secondary must be connected to the same power input terminal in each device. The earth ground terminal must be connected to a verified earth ground for each controller in the group. See Fig. 9. Controller configurations are not necessarily limited to two devices, but the total power draw including accessories cannot exceed 100 VA when powered by the same transformer (U.S. only).

� Many LCBS controllers require all loads to be powered by the same transformer that powers the controller.

� Keep the earth ground connection wire run as short as possible. Refer to Fig. 9.

� Do not connect earth ground to controller digital or analog ground terminals. Refer to Fig. 9.

� Unswitched 24 Vac power wiring can be run in the same conduit as the LONWORKS® Bus cable.

� Maintain at least a 3 in. (76 mm) separation between Triac outputs and LONWORKS® Bus wiring throughout the installation.

Device VA Information Obtained fromExcel 15 W7760C Plant Controller

18.0 W7760C Specification Data

ML6161 Damper Actuator

2.2 TRADELINE® Catalog

R8242A Contactor fan rating

21.0 TRADELINE® Catalog inrush rating

D/X Stages 0.0 NOTE: For example, assume the cooling stage outputs are wired into a compressor control circuit and has no impact on the budget.

M6410A Steam Heating Coil Valve

0.7 TRADELINE® Catalog, 0.32A at 24 Vac

TOTAL 41.9

Device Description VAW7760C Excel 15 W7760C Plant Controller 18.0ML6161A/B Damper Actuator, 35 lb-in. 2.2R8242A Contactor 21.0R6410A Valve Actuator 0.7ML684 Versadrive Valve Actuator 12.0ML6464 Damper Actuator, 66 lb-in. 3.0ML6474 Damper Actuator, 132 lb-in. 3.0ML6185 Damper Actuator SR 50 lb-in. 12.0

Page 28: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 28

Fig. 9. Power wiring details for multiple LCBS Devices.

Line LossLCBS Controllers must receive a minimum supply voltage of 20 Vac. If long power or output wire runs are required, a voltage drop due to Ohms Law (I x R) line loss must be considered. This line loss can result in a significant increase in total power required and thereby affect transformer sizing. The following example is an I x R line-loss calculation for a 200 ft. (61m) run from the transformer to a W7760C Controller drawing 37 VA using two 18 AWG (1.0 mm2) wires.

The formula is:Loss = [length of round-trip wire run (ft.)] x [resistance in

wire (ohms per ft.)] x [current in wire (amperes)]From specification data:

18 AWG twisted pair wire has 6.52 ohms per 1000 feet.Loss = [(400 ft.) x (6.52/1000 ohms per ft.)] x

[(37 VA)/(24V)] = 4.02 volts

This means that four volts are going to be lost between the transformer and the controller; therefore, to assure the controller receives at least 20 volts, the transformer must output more than 24 volts. Because all transformer output voltage levels depend on the size of the connected load, a larger transformer outputs a higher voltage than a smaller one for a given load. Fig. 10 shows this voltage load dependence.

In the preceding I x R loss example, even though the controller load is only 37 VA, a standard 40 VA transformer is not sufficient due to the line loss. From Fig. 10, a 40 VA

transformer is just under 100 percent loaded (for the 37 VA controller) and, therefore, has a secondary voltage of 22.9 volts. (Use the lower edge of the shaded zone in Fig. 10 that represents the worst case conditions.) When the I x R loss of four volts is subtracted, only 18.9 volts reaches the controller, which is not enough voltage for proper operation.

In this situation, the engineer basically has three alternatives:1. Use a larger transformer; for example, if an 80 VA

model is used an output of 24.4 volts minus the four volt line loss supplies 20.4V to the controller. See Fig. 10. Although acceptable, the four-volt line-loss in this example is higher than recommended. See the following IMPORTANT note.

2. Use heavier gauge wire for the power run. 14 AWG (2.0 mm2) wire has a resistance of 2.57 ohms per 1000 ft. which, using the preceding formula, gives a line-loss of only 1.58 volts (compared with 4.02 volts). This would allow a 40 VA transformer to be used. 14 AWG (2.0 mm2) wire is the recommended wire size for 24 Vac wiring.

3. Locate the transformer closer to the controller, thereby reducing the length of the wire run, and the line loss.

The issue of line-loss is also important in the case of the output wiring connected to the Triac digital outputs. The same formula and method are used. The rule to remember is to keep all power and output wire runs as short as practical. When necessary, use heavier gauge wire, a bigger transformer, or install the transformer closer to the controller.

IMPORTANTNo installation should be designed where the line loss is greater than two volts to allow for nominal operation if the primary voltage drops to 102 Vac (120 Vac minus 15 percent).

To meet the National Electrical Manufacturers Association (NEMA) standards, a transformer must stay within the NEMA limits. The chart in Fig. 10 shows the required limits at various loads.

With 100 percent load, the transformer secondary must supply between 23 and 25 volts to meet the NEMA standard. When a purchased transformer meets the NEMA standard DC20-1986, the transformer voltage regulating ability can be considered reliable. Compliance with the NEMA standard is voluntary.

Fig. 10. NEMA class 2 transformer voltage output limits.

L1 (HOT)

LCBSCONTROLLER

24

VA

C

24

V C

OM

EA

RT

HG

RO

UN

D

EARTHGROUND

EARTH GROUND

L2

1

4 4

33

52

1

2

3

4

5

LCBSCONTROLLER

24

VA

C

24

V C

OM

EA

RT

HG

RO

UN

D

EARTH GROUND

M22721

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

NEC CLASS 2 RESTRICTS THE MAXIMUM POWER TO 100VA.

TWO OR MORE LCBS DEVICES POWERED FROM THE SAME TRANSFORMERREQUIRES THAT THE 24 VAC POWER POLARITY BE OBSERVED. THE WIREUSED AS 24V COMMON MUST BE CONNECTED TO 24V COM ON ALL POWERED DEVICES. IF ONE POWER WIRE IS GROUNDED. IT MUST BE USED FOR 24V COMMON. THE POWER WIRE FOR 24 VAC MUST BE THE SAME ON ALL DEVICES.

EACH CONTROLLER EARTH GROUND TERMINAL MUST BE CONNECTED TO EARTH GROUND. KEEP THE EARTH GROUND WIRE LENGTH TO A MINIMUM. USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.2 SQ. mm) WITH A MINIMUM OF 18 AWG (1.0 SQ mm) FOR THE EARTH GROUND.

FOR CONTROLLERS USED IN HEATING/COOLING EQUIPMENT SUBJECT TO UL1995 AND PRIMARY POWER GREATER THAN 150V, ONE SIDE OF THE TRANSFORMER SECONDARY MUST BE GROUNDED.

27

26

25

24

23

22

21

20

19

18

17

16

15

14

0 50 100 150

% OF LOAD

SE

CO

ND

AR

Y V

OL

TA

GE

200

M993

Page 29: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

29 74-3679�1

The following Honeywell transformers meet this NEMA standard:

Transformer Type VA RatingAT20A 20AT40A 40AT72D 40AT87A 50

AK3310 Assembly 100

Step 3. Prepare Wiring Diagrams

Wiring DetailsThe Installation Instruction or each LCBS controller shows the device terminal arrangement and provides detailed wiring diagrams. Reference these diagrams to prepare site-specific job drawings. See �Applicable Literature� on page 5 to identify controller and Installation Instruction form number.

A portable PC equipped with a LONTALK® adapter can be connected to the miniature phone jack on any LCBS controller or to the miniature phone jack on a T7770A Wall Module if the LonWorks® Bus has been wired to the wall module.

Typical Wiring DiagramsThe following wiring diagrams are generic and not specific to any controller. They are general in nature and are intended only as a guide for planning only. For complete wiring details see the Installation Instructions manual for each product. For a list of all literature associated with LCBS see �Applicable Literature� on page 5.

Fig. 11. Typical Temperature (Resistance) Actuator Wiring

Fig. 12. Typical 2- Wire Voltage Output Sensor Wiring.

Fig. 13. Typical 3-Wire Voltage Output Sensor Wiring.

Fig. 14. Typical 4 - 20 mA Output Sensor Input Wiring

ANALOGCOM

E GROUND

AI

1

2

2

1

RESISTANCE SENSORS

20K NTC AND PT3000

LCBS CONTROLLER

M19402A

SHIELDED CABLE IS NOT GENERALLY REQUIRED. IF USED,

CONNECT THE SHIELD DRAIN WIRE TO EARTH GROUND AT

THE CONTROLLER.

SENSOR TYPE VARIES BY CONTROLLER AND APPLICATION

ANALOGCOM

AI

SENSORS• (0 TO 10 OR 2 TO 10 V)• HUMIDITY• STATIC PRESSURE• FLOW• VOLTAGE• CURRENT• POWER• CO• CO2

• VOC

XL10 APPLICATION SPECIFICCONTROLLERS REQUIRESPECIFIC ENGINEERING UNITSAND VOLTAGE RANGES.

XL15 GENERAL PURPOSECONTROLLER CAN BE CONFIGURED TO MATCH MOSTSENSORS.

LCBS CONTROLLER

M19403

SSIGNAL

COM –

ANALOGCOM

+22 VDC

AI

LCBS CONTROLLER

SSIGNAL

DC NEG

DC POS

+ +

SENSORS• (0 TO 10 OR 2 TO 10 V)

• HUMIDITY

• STATIC PRESSURE

• FLOW

• VOLTAGE

• CURRENT

• POWER

• CO

• CO2

• VOC

XL10 APPLICATION SPECIFIC

CONTROLLERS REQUIRE

SPECIFIC ENGINEERING UNITS

AND VOLTAGE RANGES.

XL15 GENERAL PURPOSE

CONTROLLER CAN BE

CONFIGURED TO MATCH MOST

SENSORS.

M19404A

ANALOGCOM

+22 VDC

AI

LCBS CONTROLLER

S499 OHM 1%

SIGNAL

DC NEG

DC POS

+ +

SENSORS

• HUMIDITY

• STATIC PRESSURE

• FLOW

• VOLTAGE

• CURRENT

• POWER

• VOC

• CO

• CO2

XL10 APPLICATION SPECIFIC

CONTROLLERS REQUIRE

SPECIFIC ENGINEERING UNITS

AND VOLTAGE RANGES.

XL15 GENERAL PURPOSE

CONTROLLER CAN BE

CONFIGURED TO MATCH

MOST SENSORS.

M19405A

1

1

SHIELDED CABLE IS NOT GENERALLY REQUIRED. IF USED,

CONNECT THE SHIELD DRAIN WIRE TO EARTH GROUND AT

THE CONTROLLER.

Page 30: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 30

Fig. 15. Typical Digital Input Wiring.

Fig. 16. Typical Floating (Series 60) Actuator Wiring.

Fig. 17. Typical Pulse Width Modulating Actuator Wiring

Fig. 18. Typical 4-20 mA Actuator Wiring

Fig. 19. Typical 0-10 or 2-10 Vdc Actuator Wiring

DIGITALCOM

DI

LCBS CONTROLLER

DIGITAL SENSOR(DRY CONTACT RATEDFOR ELECTRONIC DUTY)

M19406

OP

EN

CL

OS

ED

24

V C

OM

24

VA

C

DO DO

LCBS

CONTROLLER

FLOATING

(SERIES 60)

ACTUATOR

M19407A

OP

EN

24

V A

C

CL

OS

ED

120 VAC24 VAC

120V COM

1

2

2

1

2

POWER SUPPLY. PROVIDE DISCONNECT MEANS

AND OVERLOAD PROTECTION AS REQUIRED.

TERMINAL DESIGNATIONS VARY BY MODEL,

CONFIGRATION AND/OR APPLICATION.

M19408A

1

2

POWER SUPPLY. PROVIDE DISCONNECT MEANS

AND OVERLOAD PROTECTION AS REQUIRED.

TERMINAL DESIGNATIONS VARY BY MODEL,

CONFIGURATION AND/OR APPLICATION.

24

V C

OM

(TR

IAC

) DO

24

VA

C

DO

LCBS

CONTROLLER

PULSE WIDTH

MODULATING (PWM)

ACTUATOR

120 VAC24 VAC

120V COM

1

2

24

V C

OM

SIG

NA

L

24

VA

C

2

M19409A

1

2

POWER SUPPLY. PROVIDE DISCONNECT MEANS

AND OVERLOAD PROTECTION AS REQUIRED.

TERMINAL DESIGNATIONS VARY BY MODEL,

CONFIGRATION AND/OR APPLICATION.

24

V C

OM

4-2

0 m

A

24

VA

C

24 VAC

AO

LCBS

CONTROLLER

4-20 mA ACTUATOR

120 VAC

120V COM

1

2

24

V C

OM

SIG

NA

L

24

VA

C2

M19410A

1

2

POWER SUPPLY. PROVIDE DISCONNECT MEANS

AND OVERLOAD PROTECTION AS REQUIRED.

TERMINAL DESIGNATIONS VARY BY MODEL,

CONFIGURATION AND/OR APPLICATION.

24

V C

OM

0-2

0 O

R4

-20

mA

24

VA

C

AO

499 OHM

1%

LCBS

CONTROLLER

0-10V OR 2-10V

ACTUATOR

120 VAC24 VAC

120V COM

1

2

24

V C

OM

SIG

NA

L

24

VA

C

2

Page 31: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

31 74-3679�1

Fig. 20. Typical Relay (Digital) Output Wiring.

General ConsiderationsATTACHING 2 OR MORE WIRES TO THE SAME TERMINALFor field wiring, when attaching two or more wires, other than 14 AWG (2.0 mm2), to the same terminal, twist wires together. See Fig. 22. Deviation from this rule can result in improper electrical contact.

Wire to the terminal blocks as follows:1. Strip 1/2 in. (13 mm) insulation from the conductor.2. If using a single wire in the required terminal location,

cut the wire to 3/16 in. (5 mm) insert and tighten the screw to complete the termination.

3. If two or more wires are being inserted into one terminal location, twist the wires together a minimum of three turns before inserting them.

4. Cut the twisted end of the wires to 3/16 in. (5 mm) before inserting them into the terminal and tightening the screw.

NOTES:� Pull on each wire in all terminals to check for good

mechanical connection.� Consider adding Fig. 22 and the above notes to

the project wiring diagrams.

Fig. 21. Wiring Triac Digital Outputs for Parallel Operation.

M19411A

1

2

3

POWER SUPPLY. PROVIDE DISCONNECT MEANS

AND OVERLOAD PROTECTION AS REQUIRED.

TERMINAL DESIGNATIONS VARY BY MODEL,

CONFIGRATION AND/OR APPLICATION.

CONTROLLER SET FOR HIGH SIDE SWITCHING.

24

V C

OM

24

VA

C

DO

LCBS

CONTROLLER

120 VAC24 VAC

RELAY

24 VAC

0.5A MAXIMUM COIL CURRENT

CONTROL LOAD

120V COM

1

2

3

24

V C

OM

24

VA

C

DO DO

LCBS

CONTROLLER

M19412A

120 VAC24 VAC

RELAY

24 VAC

0.5 A MAXIMUM COIL CURRENT

CONTROL LOAD

CORRECT

120V COM

1

2

1

2

3

3

POWER SUPPLY. PROVIDE DISCONNECT MEANS

AND OVERLOAD PROTECTION AS REQUIRED.

TERMINAL DESIGNATIONS VARY BY MODEL,

CONFIGRATION AND/OR APPLICATION.

CONTROLLER SET FOR HIGH SIDE SWITCHING.

24

V C

OM

24

VA

C

DO DO

LCBS

CONTROLLER

120 VAC24 VAC

RELAY

24 VAC

0.5A MAXIMUM COIL CURRENT

CONTROL LOAD

INCORRECT

120V COM

1

2

3

3

Page 32: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 32

.

Fig. 22. Attaching two or more wires to terminal blocks.

FIELD WIRING TYPESTable 6 lists wiring types, sizes, and distances for Excel 15 products. The terminals on the W7760C, W7751, W7750, W7752, W7753, W7761, W7762, W7763, T7350, and T7770 accept 14 through 22 AWG (2.0 to 0.34 mm2) wire. The T7300F/Q7300H Commercial Thermostat/Communicating Subbase accept 18 through 22 AWG (1.0 to 0.34 mm2) wire.

Refer to LonWorks® for LCBS (form number 74-2865_2) Tables 8 through 12 for additional details.

Step 4. Order EquipmentAfter compiling a bill of materials through completion of the previous application steps, refer to Table 7 for ordering information. Contact Honeywell for information about Controllers and Wall Modules with no logo.

Table 6. Field Wiring Reference Table (Honeywell cable listed as AK#### or equivalent).

1/2(13)

STRIP 1/2 IN. (13 MM) FROM WIRES TO BE ATTACHED AT ONE TERMINAL.

1.

2. TWIST WIRES TOGETHER WITH PLIERS (A MINIMUM OF THREE TURNS).

3.CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) BEFORE INSERTING INTO TERMINAL AND TIGHTENING SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD MECHANICAL CONNECTION. M17207

Wire Function

Recommended Minimum Wire

Size AWG (mm2) Construction

Specification or

Requirement Vendor Wire Type Maximum Length

ft. (m)LONWORKS® Bus (Plenum)

22 AWG (0.34 mm2)

Twisted pair solid conductor, nonshielded or Echelon approved cable.

Level IV 140°F (60°C) rating

HoneywellAK3791 (one twisted pair) AK3792 (two twisted pairs)

Refer to LONWORKS Bus Wiring Guidelines for maximum length

LONWORKS® Bus (Non-Plenum)

22 AWG (0.34 mm2)

Twisted pair solid conductor, nonshielded or Echelon approved cable.

Level IV 140°F (60°C) rating

HoneywellAK3781 (one twisted pair) AK3782 (two twisted pairs)

Refer to LONWORKS® Bus Wiring Guidelines for maximum length

Input Wiring Sensors Contacts

18 to 22 AWG (1.0 to 0.34 mm2)

Multiconductor (usually five-wire cable bundle). For runs >200 ft. (61m) in noisy EMI areas, use shielded cable.

140°F (60°C) rating

Standard thermostat wire 1000 ft. (305m) for 18 AWG,200 ft. (61m) for 22 AWG

Output Wiring Actuators Relays

14 AWG (2.0 mm2) 18 AWG (1.0 mm2) acceptable for short runs)

Any pair nonshielded (use heavier wire for longer runs).

NEC Class 2 140°F (60°C) rating

HoneywellAK3702 (18 AWG) AK3712 (16 AWG) AK3754 (14 AWG)

Limited by line-loss effects on power consumption. (See Line Loss subsection.)

Power Wiring

14 AWG (2.0 mm2) Any pair nonshielded (use heavier wire for longer runs).

NEC Class 2 140°F (60°C) rating

HoneywellAK3754 (14 AWG) twisted pair AK3909 (14 AWG) single conductor

Limited by line-loss effects on power consumption. (See Line Loss subsection.)

Table 7. Light Commercial Building Solution Ordering Information.

Part Number Product Description CommentsW7750 CONTROLLERS (CVAHU)

W7750A Constant Volume AHU Controller Three Analog Inputs, Three Digital Inputs and Six 24 Vac Relay Outputs

W7750B Constant Volume AHU Controller Six Analog Inputs, Five Digital Inputs and Eight (High-side Low-side switchable) Triac Outputs

W7750C Constant Volume AHU Controller Six Analog Inputs, Five Digital Inputs, Five Triac Outputs and Three Analog Outputs

Page 33: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

33 74-3679�1

EXCEL 10 W7751 CONTROLLERSW7751B OEM Base Board (Only in bulk pack of 10) Order 207912 Snaptrack (See Accessories)W7751D Base Board, Mounting Enclosure With Internal WiringW7751F Base Board, Mounting Enclosure With External WiringW7751H Smart VAV II Actuator is a factory-combined VAV

Box Controller and a ML6161B1000 ActuatorPlenum Rated

W7751J Smart VAV II Actuator is a factory-combined pressure dependant VAV Box Controller and a ML6161B1000 Actuator

Plenum rated, no static pressure sensor.

Y7751F2001 W7751F2003 Base Board, Mounting Enclosure packed with ML6161B1000 Actuator

With External Wiring

W7751 SUBBASES AND ELECTRONICS ASSEMBLIES206167A Subbase for W7751F with External Wiring Available in bulk pack of 10 each (for use with

206168B VAV Controller Assembly).206168B Cover and Electronics for W7751D,F Contains Circuit Board for use with 206166A or

206167A Subbases (available only in bulk pack of 10).

W7752 CONTROLLERS (Fan Coil Units)W7752F Fan Coil Unit - 115/24 Vac With electric heat relayW7752G Fan Coil Unit - 115/24 Vac Standard unitW7752K Fan Coil Unit - 115/24 Vac Two DI, Two Triacs, Two Relays for lighting

EXCEL 10 W7753A CONTROLLERW7753A Unit Ventilator Controller (W7753A) Six Analog Inputs, Five Digital Inputs and Eight

Triac OutputsW7760 CONTROLLERS (Building and Plant Managers)

W7760A Building Manager with control functions Excel 15 - Alarm, dial-out, scheduling, logs, DLC, and controller functions

W7760B Building Manager with Internet access Excel 15 - Alarm, scheduling, DLC, Trends, and logs. Internet access.

W7760C Plant Controller Excel 15 - Eight Analog Inputs, Eight Digital Inputs, Eight Triac Outputs, Six Analog Outputs

EXCEL 10 W7761AW7761A Remote Input/Output Device RIO

EXCEL 10 W7762B, W7763C (Hydronic Controllers)W7762B Excel 10 W7762B Hydronic ControllerW7763C Excel 10 W7763C Hydronic Controller Includes built-in Wall Module (with °F scale)

EXCEL 10 T7350 COMMUNICATING SUBBASE

T7350H1009 (3H/3C communicating thermostat)

Communicating Thermostat with three heating and three cooling digital outputs.Humidity, Occupancy, Outdoor, Discharge Air Capability.

� Optional heat pump control.� Isolated auxiliary digital output.

T7350H1017 (modulating communicating thermostat)

Communicating Thermostat with two modulating outputs, one heating and one cooling digital output.Humidity, Occupancy, Outdoor, Discharge Air Capability.

� Isolated auxiliary digital output.� 4-20 mA output (2-10 Vdc with 500 ohm

resistor).

ECHELON-BASED COMPONENTS AND PARTSQ7740A Excel 10 2-Way Repeater Used to extend the length of the LONWORKS

Bus. Contains built in termination modules.Q7740B Excel 10 4-Way Repeater Used to extend the length of the LONWORKS

Bus. Contains built in termination modules.Q7751A Router FTT

Table 7. Light Commercial Building Solution Ordering Information. (Continued)

Part Number Product Description Comments

Page 34: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 34

ECHELON-BASED COMPONENTS AND PARTS (continued)Q7752A Serial Interface (PCMCIA card) PCC10 FTTQ7760A Serial Interface SLTA-10 FTTQ7770A1001 Honeywell RapidLink� Dialup Network Adapter

with standard RS 232 9 pin male to 9 pin female cable.

Built in Modem, power supply - 9V AC/DC to 24V AC/DC, 250mA, 50/60 Hz, NEC Class 2 wiring. Integral FT-3150® smart transceiver.

209541B Termination Module One/two required per LONWORKS Bus segment205979 Operator Terminal Cable for LONWORKS Bus Serial interface to wall module or controller

T7560 AND T7770 WALL MODULEST7560A1018 Digital Wall Module with Sensor, Setpoint and

Bypass/LCD, Honeywell Logo�

T7560A1042 Digital Wall Module with Sensor, Setpoint and Bypass/LCD, Honeywell Logo

All White

T7560B1016 Digital Wall Module with Sensor, Setpoint, Bypass/LCD and Humidity, Honeywell Logo

T7560B1032 Digital Wall Module with Sensor, Setpoint, Bypass/LCD and Humidity, Honeywell Logo

All White

T7770A1006 Sensor with Honeywell Logo Used with Excel 5000 and Excel 10 ControllersT7770A2004 Sensor, LONWORKS Jack and Honeywell Logo Used with Excel 5000 and Excel 10 ControllersT7770B1004 Sensor with Setpoint and LONWORKS Jack,

Honeywell LogoDegrees F Absolute

T7770B1020 Sensor with Setpoint and LONWORKS Jack, Honeywell Logo

Degrees C Absolute

T7770B1046 Sensor with Setpoint and LONWORKS Jack, Honeywell Logo

Relative Setpoint

T7770C1002 Sensor with Setpoint, Bypass/LED and LONWORKS Jack, Honeywell Logo

Degrees F Absolute

T7770C1010 Sensor with Setpoint, Bypass/LED and LONWORKS Jack, No Logo

Degrees F Absolute

T7770C1028 Sensor with Setpoint, Bypass/LED and LONWORKS Jack, Honeywell Logo

Degrees C Absolute

T7770C1044 Sensor with Setpoint, Bypass/LED and LONWORKS Jack, Honeywell Logo

Relative Setpoint

T7770C1051 Sensor with Setpoint, Bypass/LED and LONWORKS Jack, No Logo

Relative Setpoint

T7770D1000 Sensor with Bypass/LED and LONWORKS Jack, Honeywell Logo

Degrees F Absolute

TEMPERATURE SENSORS (VARIOUS APPLICATIONS)C7031G2014 Outdoor Air Temperature Sensor. PT3000 WeatherproofC7041B2005 Discharge/Return Air Temperature Sensor. 20K

ohm NTCElement length 6 in. (152 mm).

C7041B2013 Discharge/Return Air Temperature Sensor. 20K ohm NTC

Element length 12 in. (305 mm).

C7041C2003 Duct Discharge/Return Air Sensor. 20K ohm 18 in. (457mm) insertion length.C7041D2001 Hot or chilled Water Temperature Sensor. 20K ohm

NTCUse 50001774-001 Immersion Well

C7041F2006 Outside Air Temperature Sensor. 20K ohm NTC W7750B,C onlyC7041J2007 Averaging Discharge/Return Air Temperature

Sensor. 20K ohm NTCDuct element cord length 12 ft. (3.7m).

C7041K2005 Hot or chilled Water Temperature Sensor. 20K ohm NTC

Strap-on

Table 7. Light Commercial Building Solution Ordering Information. (Continued)

Part Number Product Description Comments

Page 35: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

35 74-3679�1

TEMPERATURE SENSORS (VARIOUS APPLICATIONS) [continued]C7100A1015 Averaging Discharge/Return Air Temperature

Sensor. PT300013 in. (330mm) insertion length.

C7170A1002 Outdoor Air Temperature Sensor. PT3000 �C7770A1006 Air Temperature Sensor. 20K ohm NTC

nonlinearizedDuct-mounted sensor that functions as a primary and/or secondary sensor.

SENSORS (CO2, Humidity, Enthalpy, and Pressure)C7232A1008 CO2 Wall Mount Sensor/Monitor with display Use to measure the levels of carbon dioxide

C7232A1016 CO2 Wall Mount Sensor/Monitor without display Use to measure the levels of carbon dioxide

C7232B1006 CO2 Duct Mount Sensor/Monitor with display Use to measure the levels of carbon dioxide

C7232B1014 CO2 Duct Mount Sensor/Monitor without display Use to measure the levels of carbon dioxide

C7400A1004 Solid State Enthalpy Sensor (4 to 20 mA) For outdoor and return air enthalpyC7600B2008 Solid State Humidity Sensor (2 to 10 Vdc) For wall mount air humidityC7600C1008 Solid State Humidity Sensor (4 to 20 mA) For outdoor and return air humidityC7632A1004 Solid State Humidity Sensor without display For wall mount air humidityC7632B1002 Solid State Humidity Sensor without display For duct mount air humidityH7625A, H7635A Solid State Humidity Sensor, wall mount Includes a 20K ohm temperature sensorH7625B, H7635B, H7655B

Solid State Humidity Sensor, duct mount Includes a 20K ohm temperature sensor

H7635C Solid State Humidity Sensor, outdoor mount Includes a 20K ohm temperature sensorP7640A,B Pressure Sensor (4 to 20 mA) Use to measure the levels of carbon dioxide

ACCESSORIES� Two DIN rail adapters Obtain locally: Part number TKAD, from Thomas

and Betts, two for each controller.AT72D, AT88A, AK3310, etc.

Transformers �

EN 50 022 DIN rail 35 mm by 7.5 mm (1-3/8 in. by 5/16 in.) Obtain locally: Each controller requires 5 in.ML6161B1000 Damper Actuator Series 60 �M6410A Valve Actuator Series 60 Use with V5852/V5853/V5862/V5863 ValvesML684A1025 Versadrive Valve Actuator with linkage, Series 60 Use with V5011 and V5013 ValvesML6464A1009 Direct Coupled Actuator, 66 lb-in. torque, Series 60 �ML6474A1008 Direct Coupled Actuator, 132 lb-in. torque, Series 60 �ML6185A1000 Direct Coupled Actuator, 50 lb-in. spring return Series 60ML7984B3000 Valve Actuator Pulse Width Modulation (PWM) Use with V5011 or V5013 F and G ValvesR8242A Contactor, 24 Vac coil, DPDT �V5852A/V5862A Two-way terminal unit water valve; 0.19, 0.29, 0.47,

0.74, 1.2, and 1.9 Cv 1/2 in. npt (13 mm) or 2.9 and 4.9 Cv 3/4 in. npt (19 mm)

Use with M6410 Valve Actuator. Close-off rating for 0.19 to 1.9 Cv is 65 psi; for 2.9 and 4.9, Cv is 45 psi. (Coefficient of volume or capacity index Cv = gallons per minute divided by the square root of the pressure drop across the valve.)

V5853A/V5863A Three-way mixing terminal unit hot water valve; 0.19, 0.29, 0.47, 0.74, 1.2, and 1.9 Cv 1/2 in. npt (13 mm) or 2.9 and 4.9 Cv 3/4 in. npt (19 mm)

Use with M6410 Valve Actuator. Close-off rating for 0.19 to 0.74 Cv is 55 psi; 1.2 and 1.9 Cv is 22 psi; 2.9 and 4.9 Cv is 26 psi.

CABLING� Serial Interface Cable, male DB-9 to

female DB-9 or female DB-25.Obtain locally from any computer hardware vendor.

Honeywell AK3702 (typical or equivalent)

18 AWG (1.0 mm2) twisted pair Non-plenum

Table 7. Light Commercial Building Solution Ordering Information. (Continued)

Part Number Product Description Comments

Page 36: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 36

Step 5. Configure ControllersControllers are configured using ZL7760A LONSPEC�, ZL7751A RapidZone, or ZL7300A LonStat� configuration software tools. Refer to the individual LCBS controller Application Guide for complete information on configuring the controller. For a list of controllers and literature see �Applicable Literature� on page 5.

The following identifies the tools used for each of the 5 solution architectures:� XL15A Solution - ZL7760A LONSPEC�.� XL15B Solution - ZL7760A LONSPEC� (The W7760B

Building Manager has an internal setup function).� RapidZone Solution - XL7751A RapidZone software.� LonStat� - ZL7300A LonStat software. (LONSPEC� can

be used but LonStat� is simpler for the user.)� Unconfigured CVAHU - None, the controllers use factory

default parameters. Any software download will delete the factory default parameters.

Projects configured with RapidZone can be saved as a LONSPEC� backup database and restored to LONSPEC� to include the RapidZone Solution in an XL15A or XL15B Solution. While it is possible to manually configure a RapidZone application using LONSPEC�, the task is extremely complex and tedious.

LonStat� does not create a database. It must be connected to one or more T7300F/Q7300H communicating commercial programmable thermostats to be used.

A LONSPEC� database backup including one created in RapidZone can be associated to ZL7762A LONSTATION� monitoring software to significantly reduce the time required to commission LONSTATION�.

LONSTATION� can be used to monitor the XL15A Solution, the RapidZone Solution, and the LonStat� Solution. It cannot be used to monitor the XL15B Solution or Unconfigured CVAHU Solution.

Step 6. System StartupSystem startup assumes that the controller has been configured in a software tool and that some, if not all network devices have been installed. It is preferred that all devices be operational, but recognized that projects may be brought on line over time.

The major concern for projects being started over time is that the data sharing may not be complete to meet application needs. There is also a risk of electrical damage to one or more network devices if a device is connected to the network while the network is operational.

Check Installation and Wiring:Inspect all wiring connections at the controller terminals, and verify compliance with job drawings. If any wiring changes are required, first be sure to remove power from the device before starting work. Pay particular attention to:� 24 Vac power connections. Verify that multiple devices

powered by the same transformer are wired with the transformer secondary connected to the same input terminal identification on each controller. See Fig. 9. Controller configurations are not necessarily limited to two devices, but the total power draw including accessories cannot exceed 100 VA when powered by the same transformer (U.S. only).

� Device wiring. Be sure that each device is wired to a verified earth ground using a wire run as short as possible with the heaviest gauge wire available, up to 14 AWG (2.0 mm2) with a minimum of 18 AWG (1.0 mm2) for each controller in the group. See Fig. 9.

� Verify Triac wiring to external devices uses the proper load power/24 Vac hot terminals. Check for 24 Vac with a meter.

NOTE: All wiring must comply with applicable electrical codes and ordinances or as specified on installation wiring diagrams.

CABLING (continued)Honeywell AK3712 (typical or equivalent)

16 AWG (1.3 mm2) twisted pair Non-plenum

Honeywell AK3725 Inputs: 18 AWG (1.0 mm2) five wire cable bundle Standard thermostat wireHoneywell AK3752 (typical or equivalent)

Outputs/Power: 14 to 18 AWG (2.0 to 1.0 mm2) NEC Class 2 140°F (60°C) rating

Honeywell AK3754 (typical or equivalent)

14 AWG (2.0 mm2) two conductor Non-plenum

Honeywell AK3781 (one twisted pair) AK3782 (two twisted pairs)

LONWORKS Bus (nonplenum): 22 AWG (0.34 mm2) twisted pair solid conductor, nonshielded or Echelon approved cable.

Level IV 140°F (60°C) rating

Honeywell AK3791 (one twisted pair) AK3792 (two twisted pairs)

LONWORKS Bus (plenum): 22 AWG (0.34 mm2) twisted pair solid conductor, nonshielded or Echelon approved cable.

Level IV 140°F (60°C) rating

Table 7. Light Commercial Building Solution Ordering Information. (Continued)

Part Number Product Description Comments

Page 37: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

37 74-3679�1

VERIFY TERMINATION MODULE PLACEMENTThe installation wiring diagrams should indicate the locations for placement of 209541B Termination Module(s). Refer to LONWORKS® Bus Wiring Guidelines (form number 74-2865_2) and the Excel 10 FTT Termination Module Installation Instructions form, 95-7554. Correct placement of the termination module(s) is required for proper LONWORKS® Bus operation.

Power UpApply power to the controller(s). Observe for any physical signs of malfunctions.

Observe the LED on the controller. The LED provides a visual indication of the status of the device. When the controller receives power, the LED should appear in one of the following allowable states:

1. Off - no power to the processor.2. Continuous On - processor is in initialized state.3. Slow Blink - controlling, normal state.4. Fast Blink - when the controller has an alarm condition.

See below for additional information on alarms.

Assigning Neuron® IDEach LCBS device communicating on the network has a neuron number assigned to the transceiver by the chip manufacturer. This number is printed on a 3 part identification label attached to each device. One part of the label is permanently affixed to the device and the other 2 parts are removable gummed labels that can be affixed to job documentation.

Assigning a Neuron® ID allows a device on the LONWORKS® Bus to be positively identified. The controller Neuron® ID number can be used to confirm the physical location of a particular Excel 15, Excel 10, T7350, T7300F/Q7300H, VFD, and NX VFD.

There are two methods of assigning a Neuron ID for an LCBS controller. One uses a hardware service pin button on the controller and manually entering the Neuron ID is the second.

When an Assign ID command (use the service pin button is issued from LONSPEC�, RapidZone, or LonStat�, the configuration tool goes into the SERVICE_MESSAGE mode for five minutes. In the SERVICE_MESSAGE mode, pressing

the hardware service pin button on a controller causes the Service Message to be broadcast on the network. All other functions are normal in the SERVICE_MESSAGE mode. Use of the Service Pin assures that the correct device is being selected for configuration download from the tool.

When manually entering the Neuron® ID and issuing the Assign ID command, LONSPEC�, RapidZone, or LonStat� locates and communicates directly with the controller (the controller does not go into the SERVICE_MESSAGE mode in this case). Refer to the LONSPEC� ZL7760A software Help for more information on the ID assignment process.

AlarmsIn addition to the following information, refer to the Installation Instructions and Checkout and Test manual for each product. See the �Applicable Literature� on page 5 for form numbers.

When an LCBS controller has an alarm condition, it reports it to the central node on the LONWORKS® Bus (typically, a W7760A or W7760B Building Manager). Information contained in an alarm message is:� Subnet Number:

LONWORKS® Bus segment that contains the node that has the alarm condition.

� Node Number:Node that has the alarm condition.

� Alarm Type: Specific alarm being issued.

Download the ConfigurationOnce the tool has the neuron® ID it can download the controller configuration to the controller. The download may take several minutes for each controller. The files being downloaded are shown in the download screen of the tool.

CheckoutOnce the configuration has been downloaded to the controller, the controller operation can be checked. Refer to the controller documentation to determine what procedures should be followed for checkout. The configuration tool can be used to monitor the controller to check the operation. Some controllers permit the configuration tool to manually override the outputs, others do not.

Page 38: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 38

LONSPEC DATA SHARING

Introduction to Data SharingData sharing for the Light Commercial Building Solution (LCBS) is configured using one of the LCBS configuration tools; LONSPEC� ZL7760A, RapidZone, or LonStat. The LCBS configuration tools configure the data sharing as part of the configuration process and automatically selects the communication mechanisms as appropriate. A brief overview of the mechanisms used is helpful in planning a system configuration.

The LONWORKS® communications protocol uses a number of mechanisms to transfer data from one network device to another. This discussion is limited to 2 mechanisms used to share data between 2 or more devices on a LONWORKS® network in the Light Commercial Building Solution and is a brief and simplified summary of the function of these 2 communications mechanisms. For complete and detailed information on LonWorks® operation, refer to published documentation available from Echelon® Corp.

Data sharing or the exchange of data between 2 or more devices on a LONWORKS® network in the light commercial building solution uses one of two communication mechanisms, polling or binding.

Polling is a process in which one device on the network request data from another device on the network. The originating device sends a message requesting the data from a specific device and that device responds with the specific data requested. If the originating device needs data from multiple controllers it must send an individual request to each controller from which it needs data. In this case the polling device is configured to request data from a single or multiple network devices. The most common use of polling is, supervisory devices such as LONSTATION�, W7760A or B Building Manager, W7760C Plant Controller, S7760A Command Display Module, and LONSPEC� monitoring system. Another example is configuring a controller to use a �remote� point as an input. In LONSPEC�, RapidZone, and LonStat all polling is configured automatically as the network devices are configured.

Binding is the process where one device is configured to read data being transmitted by another device. The device originating the data is not sending the data to any specific device on the network, but any and all devices configured to read the data will do so. In this case the device receiving the data is configured to read the data from an originating controller. An example of binding is configuring an outdoor air temperature sensor on one controller and referring all other devices on the network to it.

The data shared between various network devices is transmitted and received as network variables (NV). Within a device the network variable is identified as being an output (nvo) or input (nvi). A nvo transmits specific data from the device. A nvi receives specific data from the network for use by the device. In data sharing the source is a nvo and the destination is a nvi.

The LONMARK® Association defines Standard Network Variable Types (SNVT) for each registered profile. Manufacturers define additional network variables that are

specific to a given device. SNVTs are used to provide open communication between multiple manufacturers� devices. A manufacturer�s proprietary network variables are used to implement functionality beyond the profiles and to enhance device or system operation. LONSPEC�, RapidZone, and LonStat make no distinction between SNVTs and proprietary network variables. LonMark® SNVTs for each controller are shown in the Specification Data sheets for each controller. See Table 1 Applicable Literature for specific literature numbers.

In RapidZone and LonStat the applications are defined in the software tool and binding is done automatically and no user activity is required. While LONSPEC� also does much of the binding automatically, it is a more flexible tool supporting custom applications that may require the user to configure the binding in a configuration screen called �Refer Points�.

Each controller point available as a data source or destination is given a point name. The point name used in LONSPEC� �Refer Points� is not the user defined point name. The point names are consistent for all controllers of the same model but unique for each controller model. The point names are as shown in Tables 9 through 28.

The LONSPEC� configuration screen �Refer Points� sorts the available destination points based on the source point type. The sorting is based on the LonWorks® Standard Network Variable Type (SNVT) which may include many controller variables that are very different in function and not appropriate to share. In LONSPEC� each specific variable is identified by a unique name. For example the LonWorks® variable �SNVT_Temp_p� is used for outdoor air temperature, space temperature, discharge air temperature, effective setpoint, setpoint, and setpoint offset. In LONSPEC� each of these variable is given a unique name. However, in �Refer Points� when any one of the these variables is selected as the source point all of the variables of this type will be shown in the destination points list. It would be inappropriate to bind the outside air temperature to the setpoint. The user must ensure the binding meets the application requirements. Tables 9 through 28 show the relationship of the source and destination points.

In LCBS all network variables (points) exist for each controller even if not configured. Configuring the input tells the controller to expect data on the input and in Excel 10 controllers may enable specific control functions. It is possible to configure data sharing using points that are not configured. If an unconfigured point is used as a source point (nvo), no data will be sent and all receiving controllers will report it as an alarm. If the unconfigured point is a destination point, the data will be ignored by the controller. LONSPEC� does not check to determine if the points used have been configured.

Data Sharing for Control DevicesData sharing occurs in the configuration of the control devices (controllers) listed below. Supervisory devices such as Command Display, LONSTATION�, and LONSPEC� are not included in this discussion.

NOTE: Notation Convention: >> indicates a menu or field selection in a LONSPEC� configuration screen.

Light Commercial Building Solution

Page 39: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

39 74-3679�1

Depending on the data sharing function, LONSPEC� will do the complete data sharing configuration as part of the controller configuration or will set inputs and outputs to be used as NV�s when configuring the function >> Network >> Refer Points. In cases where NV�s are set, the data sharing is not complete until >> Network >> Refer Points is configured for the points involved.

The following discussion identifies where data sharing is configured for each control device including where it is necessary to use >> Network >> Refer Points.

NOTE: For all LCBS control devices, If a network variable is data shared (bound) to an algorithm input, the con-troller will always use the network variable even if a physical input is connected to the controller for that algorithm function.

T7300F/Q7300HTab: System Configuration - Space Temp Sensor Mode

>> NETWORK SENSOR � Sets the controller to use the sensor data from another controller. Use Menu >> Network >> Refer Points to bind source temperature point to destination temperature point(s).

Tab: Schedule Assign � Unscheduled Controllers

Used to bind the T7300 schedule to as many as 4 objects (controllers or XL15 control loops).

Menu >> Network >> Refer Points may be used to extend the number of objects using the T7300 schedule.

Excel 10 W7750 CVAHU Tab: Outputs - Optional Points

>> Free[#] - Sets the controller to use network data to control the configured output. A source point must be bound to the Free Output by configuring the free point as a remote point in an XL15A or C, or by using Menu >> Network >> Refer Points.

Tab: Inputs - Space Temp:

>> NetworkOnly - Sets the controller to use a sensor from another device but does not select the sensor. A source point must be bound to the destination point (SpaceTempIn) using Menu >> Network >> Refer Points.

Tab: Economizer - Enable Type

>> [Select the desired control algorithm]. If the controller nvi(s) are bound using >> Network >> Refer Points, the controller will use the network points, otherwise it will use the physical input point(s).

XL10 VAV Terminal (W7751)While it is possible to share the space temperature to VAV controllers, it is not recommended. Refer to Excel 10 VAV W7751 System Engineering Guide (74-2949-1) pages 40 and 82.

Tab: Configuration - Output Setting - Flow Type:

>> Share Wall Module � Sets the controller to use the temperature PID result from another controller as the input to the volume control algorithm. Use Menu >> Network >> Refer Points to bind nvoShare from the originating controller to nviShare in the receiving controller(s).

Other networked points such as morning warm-up (nviApplicMode), unoccupied bypass (nviBypass), must be bound using Refer Points.

Tab: Configuration - Optional Output - Free

>> Free - Sets the controller to use network data to control the configured output. A source point must be bound to the free by configuring the free point as a remote point in an XL15A or C, or by using Menu >> Network >> Refer Points.

Excel 10 W7753 Unit VentTab: Outputs - Optional Points

>> Free[#] - Sets the controller to use network data to control the configured output. A source point must be bound to the Free Output by configuring the free point as a remote point in an XL15A or C, or by using Menu >> Network >> Refer Points.

Tab: Inputs - Space Temp:

>> NetworkOnly - Sets the controller to use a sensor from another device but does not select the sensor. A source point must be bound to the destination point (DestRmTemp) using Menu >> Network >> Refer Points.

Tab: Economizer - Enable Type

>> [Select the desired control algorithm]. If the controller nvi(�s) are bound using >> Network >> Refer Points, the controller will use the network points, otherwise it will use the physical input point(s).

Excel 15 W7760A Building ManagerTab: Analog Inputs

Network variables ODTemp and ODHum can be created by selecting the appropriate �Sensor shared across network for:� function when configuring the Analog Input. Only 1 sensor can be configured for ODTemp and only 1 sensor can be configured for ODHum

Tab: Digital Inputs

Network variable Occ Sensor can be created by selecting the DI Type �Occupancy Sensor�. Only 1 digital input can be configured as �Occupancy Sensor�

Tab: Math Function, Start/Stop Loop, Control Loop, or Logic Loop - Input

>> Remote is used to select the points from other network devices to be used as inputs. The selections are limited to analog or digital point types based on the selection function. The inputs are polled. Network variables cannot be bound to the W7760A as source points.

Tab: Start/Stop Loop or Control Loop - Output

Page 40: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 40

>> Remote is used to bind the output to an output in a remote network device. Start/Stop Loops and Control Loops cannot be used to control network variables.

Tab: Schedule Assign �

Up to 20 objects may be assigned for the controller, each object can be assigned to any of the 8 schedules. LONSPEC� binds the controller output point TOD Event [#] (nvoTodEventCmd_[#-1]) to the network object. This function can be extended beyond 20 objects by using Refer Points.

Tab: Run Times � Select Point Name

>> Remote � Polls selected data point.

Tab: Trend

>> Trend Point � Remote � Polls selected data points.

Tab: Bypass Log

>> Select Bypass Object � Polls selected data points.

Tab: Alarms >> Analog, Digital, or General

>> Remote � Polls selected data points.

Tab: Alarms >> XL10 Alarm Mapping

>> Binds nvoStatus and nvoAlarm from an XL10, T7350H, T7300F/Q7300H, or XL15C controller to the XL15A nviStatus[#] and nviAlarm[#]

Tab: DLC - Override If

>> Remote � Polls selected data points.

Tab: DLC >> External Load Assignment �

Binds nvoDLCLoadStatus from XL15A to nviDlcShed in XL10, T7350H, T7300F/Q7300H, and/or XL15C controllers.

Excel 15 W7760C Plant ControllerTab: Analog Inputs

Network variables ODTemp, ODHum, and Discharge Temp can be created by selecting the appropriate �Input Type:� function when configuring the Analog Input. Only 1 sensor of each function can be configured in a controller.

Tab: Digital Inputs

2 of the digital inputs can be configured as OccSensor by selecting Sensor Occupancy.

Tab: Math Function, Start/Stop Loop, Control Loop, or Logic Loop - Inputs

>> Remote is used to select the points from other network devices to be used as inputs. The selections are limited only to analog or digital point types based on the selection function. The inputs are polled.

>> Remote >> Network - Network points are a subset of remote points. Network points require the source point be bound to the destination points within the XL15C using Menu >> Network >> Refer Points. The network variables for outdoor air temperature (nvoOdTemp), outdoor air humidity (nvoOdHum), or discharge air temperature (nvoDATemp) are set to the value of the corresponding nvi.

Tab: Start/Stop Loop, Control Loop, or Logic Loop - Outputs

>> Remote is used to bind the output to an output in a remote network device. >> Remote >> Network - Network points are a subset of remote points. Selecting a network will control the network variable output (nvo�) for the controller. It is necessary to bind this output as the source to the corresponding network variable input (nvi�) in any and all desired destination devices using >> Network >> Refer Points.

Tab: Control Loop � Setpoint Override � Digital Input

>> Remote is used to select the points from other network devices to be used as inputs. The selections are limited to digital point types based on the selection function. The inputs are polled.

>> Remote >> Network � Sets the input to nviEconEnable. Network points require the source point be bound to the destination points (nvi�) within the XL15C using Menu >> Network >> Refer Points.

Refer Points ApplicationsIn general, data sharing with refer points is a simple process. In the Refer Points screen select the desired source controller and point and then select the desired destination controller(s) and point and add them to the Bound Points list. Appendix A provides tables listing all available source and destination points by controller type. The tables identify the appropriate pairings.

Time of Day SchedulingTime keeping and Time of Day (TOD) scheduling is done in the W7760A Building Manager and T7350H or T7300F/Q7300H Commercial Thermostat with communicating sub-base.

The W7760A has 7 schedules that can be assigned to the 6 Control Loops, 8 Start/Stop Loops, and 20 network objectsa

using the LONSPEC� Schedule Assign functionb. The T7350H has a single schedule that can be assigned to an unlimited number of objects. The T7300F/Q7300H has a single schedule that can be assigned to 4 network objects.

Each of the network objects assigned to a W7760A, T7350H, or T7300 schedule uses a network variable output (nvo) to send the Current State, Next, and Time Until Next Change of State (TUNCOS) across the LonWorks® bus to a corresponding network variable input (nvi). There are 20 nvo�s available from a W7760A, one from a T7350H, and 4 from a T7300. LONSPEC� binds the nvi to the respective nvo with no additional intervention by the user.

Using the LONSPEC� Schedule Assign function is the optimum method for scheduling XL10 controllers and W7760C Control Loops and Start/Stop Loops. However if the

Page 41: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

41 74-3679�1

number of Schedule Assign(ments) are insufficient for an application, it is possible to bind additional objects to a W7760A, T7350H, or T7300F/ Q7300H using the LONSPEC� >>Network>>Refer Points function.

NOTE: This method extends the number of objects that can be scheduled from a controller but it does not expand the number of schedules available.

PROCESS:5. Determine the number of schedules required for the

objects to be scheduled. The total cannot exceed the number of schedules available from the source control-ler (8 for W7760A and one for T7350H and T7300A).

6. The source controller (W7760A and T7300F/Q7300H) and the destination controllers (objects) must beavailable in the LONSPEC� project. Best practicesdictates that the controllers be configured, especially the source controller schedules.

7. Use LONSPEC� Schedule Assign to assign eachschedule to be used to at least 1 object. It is necessary to review the T7350, T7300F/Q7300H, or W7760A Building Manager configuration for schedule assign-ment and manually record the schedule information for the object assigned and the number sequentially of the assignment (1 through 4 for T7300F/Q7300H and 1 through 20 for W7760A).

8. In the LONSPEC� Refer Points screen, select the desired schedule (T7350 Time of Day Out (TOD) [1], T7300F/Q7300H TOD Out [1-4], or W7760A TOD Event [1-20]) as the source point and refer it to the time of day input for the control device.

Outdoor Air ConditionsThe light commercial building system uses LonMark® standard network variable types (SNVT) to share the outdoor air temperature, humidity, enthalpy, and air quality from a

source controller to multiple controller requiring the data. It is necessary to use the LONSPEC� >> Network >> Refer Points to bind the source point (network variable output � nvo) to the destination points (network variable input � nvi).

To perform the Refer Points function, it is necessary that the controllers be available in the LONSPEC� project. Good engineering practice would dictate that the controllers be configured prior to referring points

The controller to which the outdoor air sensor is physically connected is the source controller and the input must be configured for the function. Configuring an Excel10 input automatically sets the appropriate network variable output for the controller. When configuring an W7760A Building Manager or W7760C Plant Manager, it is necessary to set the network variable type when configuring the analog input.

It is possible to have multiple source controllers for the same outside measurement (network variable). This can be desirable with a building or campus situated such that significant differences can exist for various measurements. For such configurations, the user must ensure the correct source controller is selected for the destination controller.

CAUTIONWhen using Refer Points, LONSPEC� does not check to verify that the source has been configured.The user must ensure the correct source and destination controllers and points are selected in the configuration process.

The following table provides by controller and outdoor air measurement the names of the network variables used in Refer Points.

Table 8. Outdoor Air Conditions Network Variable Names.

a While the nvi�s can be bound to the W7760A, they cannot be selected as an input for any control functions. For the W7760A it is necessary to select the source point as a remote (polled) point.

b The nvi�s are selectable as Input >> Remote >> Network >> nvoOdTemp or nvoOdHum.

Outdoor Measurement

W7750A CVAHU

W7753A Unit Vent

W7760A Building Manager

W7760C Plant Controller

T7350H Thermostat

SourceTemperature OdTempOut Outside Temperature Outdoor Air

Temperature OutOd Temp Output Outdoor Tempearture

OutHumidity OdHumOut Outside Relative

HumditiyOutdoor Air Humidity Out

Od Hum Output N/A

Enthalpy OD Enthalpy Out SrcOaEnth N/A N/A N/ACO2 N/A SrcOaQuality N/A N/A N/A

DestinationTemperature OdTempIn DestOaTemp Outdoor Air

Temperature InaOd Temp Inb Outdoor Temperature

In

Humidity OdHumIn DestOaHum Outdoor Air Humidity Ina

Od Hum Inb N/A

Enthalpy Outdoor Enthalpy In DestOaEnth N/A N/A N/ACO2 N/A DestOaQuality N/A N/A N/A

Page 42: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 42

BypassSharing the Bypass operation from one control device to another is done in the Refer Points screen. It is important to note that it is the bypass operation of the control device and not the wall module push button being shared. A number of factors determine the actual bypass status for a control device. Refer to the Application Guide for the specific controller for detailed information on the sequence of operation.

When the network bypass input is active, the bypass timer of the destination is not used and the destination controller will execute the bypass function as long as the source object is in bypass. When the source bypass goes inactive the destination bypass function will continue for 300 seconds. This permits multiple source objects to be referred (bound) to the same destination object and be read so that any one of the source objects being in bypass will cause the destination object to be in bypass.

To refer bypass in the Refer Points screen, select the source control device bypass output and the destination object bypass input and add to the Bound Points list. See the Refer Points tables in Appendix A for a complete list of source and destination points by controller type.

XL10 Free PointsThe Excel10 W7750A,B,C CVAHU, W7751B,D,F,H,J VAV II, and W7753 Unit Ventilator controllers may all be configured with network commandable digital output points called Free points. Generally these points are configured as remote points when configuring Excel 15 start-stop, control loops, or logic loops. However, they can also be controlled by binding them to an appropriate output from another Excel10 controller. For example, a switch might be wired to a digital input on a W7750 CVAHU controller configured as Monitor (source). This could then be referred to the Free 1 output on another controller (destination) wired to control lights. When the switch is activated on the source controller, the output on the destination controller would be activated turning on the lights. Any input of network output of NV type 95 can be used as the source for activating a Free point in Excel 10. It is the user�s responsibility to ensure the source is appropriate for the application.

Remote Point SelectionWhen configuring XL15A and XL15C control loops, start-stop loops, logic loops, and math functions, it is possible to select remote points (points from another control device on the network). The available points are automatically displayed when the remote function is selected in the configuration process. Appendix C provides a complete listing of the available points with a description of their function.

Page 43: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

43 74-3679�1

APPENDIX A - REFER POINTS TABLESThe following tables identify the appropriate data sharing source and destination points for each controller combination. There are 2 tables for each source controller type. The first table details the combinations available for the source controller to Excel10 W7750 CVAHU, W7753 Unit Vent, W7751 VAV II, W7752 FCU, W7763 Chilled Ceiling Controller

(CHC), and W7762 Hydronic (HYD) destination controllers, and the second table details the combinations available from the source controller to Excel15 W7760A Building Manager, W7760C Plant Manager, T7350, and T7300/Q7300 Commercial Thermostat.

Table 9. Refer points from W7750 XL10 Constant Volume Air Handling Unit (CVAHU) Controller to XL10.

SourceW7750 CVAHU

DestinationW7750 CVAHU

DestinationW7753 Unit Vent

DestinationW7752 VAV II

DestinationW7763 CHC

DestinationW7752 FCU and

W7762 HYDNV

TypeBypass Out Bypass In DestBypass nviBypass N/A N/A 95Econ Out Econ In DestEconEnable N/A N/A N/A 95EffectSetPtOut SetPointIn DestRmTempSpt nviSetPoint DestRmTemp

SptRoom temperature setpoint

105

EmergOut EmergIn DestEmerg nviEmergCmd DestEmerg Emergency command

103

IAQ Override Out IAQ Override In DestIaqOvrd N/A N/A N/A 95Monitor SW Out Note 1 Note 1 Note 1 N/A N/A 95OccSensorOut OccSensorIn DestOccSensor nviOccCmd DestOccSensor SensorOcc 109OD Enthalpy Out Outdoor Enthalpy

InDestOaEnth N/A N/A N/A 0

OdHumOut OdHumIn DestOaHum N/A DestRmRelHum

N/A 81

OdTempOut OdTempIn DestOaTemp N/A DestRmTempDestRmTempSpt

Room Temperature SetpointSpace Temperature Input

105

SpaceTempOut SpaceTempIn DestRmTemp nviSpaceTemp DestCoolTempDestRmTempDestRmTempSpt

Space Temperature input

105

Time Clock Out Time Clock In N/A N/A N/A N/A 95Window Contact Out

Window Contact In

N/A nviEnergyHold Off DestWindow Window sensor sharing

95

Note 1: Monitor SW Out may be referred to any input with a NV type of 95 if appropriate for the application.The following destination inputs can be shared from CVAHU outputs of the same NV typeFree1 In Free1 In Free1 In Window sensor

sharing95

The following listed destination inputs have no applicable source point from CVAHUDLC Shed In DestDlcShed nviDlcShed Load shed control 0Manual Mode In nviManualMode nviManualMode Manual mode 0ManualValue In nviManValue nviManValue 0

nviShare 0nviFlowOffset 0nviFlowTrack 15

DestOaQuality 29WSHP Enable Out

95

FanSpeedIn Fan speed command

95

DestHtSource nviHeaterOverid 95

Page 44: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 44

DestSourceTemp 105nviDuctInTemp 105

SetPtOffsetIn CmdSetPtOffst nviSetPtOffset Setpoint offset 105ApplModeIn CmdHvacMode nviApplicMode Application mode 108ManOccIn CmdManualOcc nviManOcc Manual network

occupancy 109

Time Of Day In SchedOcc nviTodEvent Time Of Day In 128Auxiliary reheat output

95

External cool output control

81

External heat output control

81

Table 10. Refer Points from W7750 XL10 CVAHU Controller to XL15, T7350 and Q7300.

SourceW7750 CVAHU

DestinationW7760A Bldg Mgr

DestinationW7760C Plant Mgr

DestinationT7300F / Q7300H

DestinationT7350

NV Type

Bypass Out CLoop[1-6] Bypass InStartStop[1-8] Bypass In

Bypass_[1-18] In Bypass In Bypass In 95

Econ Out N/A Econ Enable In N/A N/A 95EffectSetPtOut N/A N/A Setpoint In Outdoor Temperature

InSetpoint InSpace Temperature In

105

EmergOut N/A Emergency Override In N/A N/A 103IAQ Override Out N/A N/A N/A N/A 95Monitor SW Out Note 1 Note 1 Note 1 Note 1 95OccSensorOut CLoop[1-6] Occupancy

InStartStop[1-8] Occupancy In

Occupancy InSensor Occupancy_[1-18] In

Occupancy Cmd In Occupancy Sensor In 109

OD Enthalpy Out N/A N/A N/A N/A 0OdHumOut Outdoor Air Humidity In Od Hum In N/A Space Humidity In 81OdTempOut Outdoor Air

Temperature InOd Temp In N/A Outdoor Temperature

In105

SpaceTempOut N/A N/A Space Temperature In Setpoint InSpace Temperature In

105

Time Clock Out N/A N/A N/A N/A 95Window Contact Out N/A N/A N/A N/A 95Note 1: Monitor SW Out may be referred to any input with a NV type of 95 if appropriate for the application.

The following destinations inputs have no applicable source point from W7750 CVAHUDlc Shed_[-18]1 In DLC Shed In 0

Counter Enable/Disable [1-2]

Counter Enable_[1-2] In 0

Runtime Enable/Disable [1-15]

0

RIO Analog Inpust_[1-3]

RIO Analog Input_[1-3] In

0

Table 9. Refer points from W7750 XL10 Constant Volume Air Handling Unit (CVAHU) Controller to XL10.

SourceW7750 CVAHU

DestinationW7750 CVAHU

DestinationW7753 Unit Vent

DestinationW7752 VAV II

DestinationW7763 CHC

DestinationW7752 FCU and

W7762 HYDNV

Type

Page 45: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

45 74-3679�1

Runtime Value Preset [1-15]

0

Counter Preset Value [1-2]

Counter Preset_[1-2] In 8

KW Cascade In KW Cascade In 28Total KW In 28

RA Relative Humidity In 81Remote Digital In [1-12]

Remote Sensor_[1-12] In

95

FanOnAuto In 95DA Temp In 105RA Temp In 105

Setpoint In 105Setpoint Offset In 105

Appl Mode In Application Mode In 108CLoop[1-6] ManOcc In Manual Occupancy_[1-

18] In 109

Bldg Static Pressure In 113Duct Static Pressure In 113Time of Day Event_[1-18] In

Occupancy Schedule In

128

Table 11. Refer Points from W7753 XL10 Unit Ventilator (Unit Vent) Controller to XL10.

SourceW7753 Unit Vent

DestinationW7753 Unit Vent

DestinationW7750 CVAHU

DestinationW7751 VAV II

DestinationW7763 CHC

DestinationW7752 FCU and

W7762 HYDNV

Type Effective Stpt Out DestRmTempSpt SetPointIn nviSetPoint DestRmTemp

DestRmTemp SptRoom temperature setpoint

105

Outside Relative Humidity

DestOaHum OdHumIn N/A N/A N/A 81

Outside Temperature

DestOaTemp OdTempIn N/A DestRmTempDestRmTempSpt

N/A 105

Space Temperature Out

DestRmTemp SpaceTempIn nviSpaceTemp DestRmTempDestRmTempSpt

Space temperature input

105

SrcBypass DestBypass Bypass In nviBypass N/A N/A 95SrcEconEnable DestEconEnable Econ In N/A N/A N/A 95SrcEmerg DestEmerg EmergIn nviEmergCmd DestEmerg Emergency

command103

SrcIaqOvr DestIaqOvrd IAQ Override In N/A N/A N/A 95SrcMonSw Note 1 Note 1 Note 1 N/A N/A 95SrcOaEnth DestOaEnth Outdoor Enthalpy

InN/A N/A N/A 0

SrcOaQuality DestOaQuality N/A N/A N/A N/A 29SrcOccSensor DestOccSensor OccSensorIn nviOccCmd DestOccSensor SensorOcc 29Note 1: SrcMonSw may be referred to any input with a NV type of 95 if appropriate for the application.

The following destination inputs can be shared from W7753 Unit Vent outputs of the same NV typeFree1 InDestIaqOvrd

Free1 In Free1 In 95

Table 10. Refer Points from W7750 XL10 CVAHU Controller to XL15, T7350 and Q7300.

SourceW7750 CVAHU

DestinationW7760A Bldg Mgr

DestinationW7760C Plant Mgr

DestinationT7300F / Q7300H

DestinationT7350

NV Type

Page 46: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 46

DestRmTempSpt Room temperature setpoint

105

The following listed inputs have no applicable source point from W7753 Unit VentDestDlcShed DLC Shed In nviDlcShed Load shed control 0

nviFlowOffset 0nviShare 0

nviManValue ManualValue In nviManValue 0nviManualMode Manual Mode In nviManualMode Manual mode 0

nviFlowTrack 15DestHtSource nviHeaterOverid 95FanSpeedIn Fan speed

command95

Time Clock In 95Window Contact In nviEnergyHold Off Window sensor

sharing 95

WSHP Enable Out 95DestSourceTemp 105

nviDuctInTemp 105CmdSetPtOffst SetPtOffsetIn nviSetPtOffset Setpoint offset 105CmdHvacMode ApplModeIn nviApplicMode Application mode 108CmdManualOcc ManOccIn nviManOcc Manual network

occupancy109

SchedOcc Time Of Day In nviTodEvent Time Of Day In 128External cool output control

81

External heat output control

81

Auxiliary reheat output

95

Table 12. Refer Points from W7753 XL10 Unit Ventilator (Unit Vent) Controller to XL15, T7350 and Q7300.

SourceW7753 Unit Vent

DestinationW7760A Bldg Mgr

DestinationW7760C Plant Mgr

DestinationT7300F / Q7300H Destination T7350

NV Type

Effective Stpt Out Setpoint In Setpoint InSpace Temperature In

105

Outside Relative Humidity

Outdoor Air Humidity In Od Hum In Space Humidity In 81

Outside Temperature

Outdoor Air Temperature In

Od Temp In Outdoor Temperature InSetpoint InSpace Temperature In

105

Space Temperature Out

Space Temperature In Setpoint InSpace Temperature In

105

SrcBypass Cloop[1-6] Bypass InStartStop [1-8] Bypass In

Bypass_[1-18] In Bypass In Bypass In 95

SrcEconEnable Econ Enable In N/A 95SrcEmerg Emergency Override In N/A 103SrcIaqOvr N/A 95

Table 11. Refer Points from W7753 XL10 Unit Ventilator (Unit Vent) Controller to XL10. (Continued)

SourceW7753 Unit Vent

DestinationW7753 Unit Vent

DestinationW7750 CVAHU

DestinationW7751 VAV II

DestinationW7763 CHC

DestinationW7752 FCU and

W7762 HYDNV

Type

Page 47: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

47 74-3679�1

SrcMonSw Note 1 Note 1 Note 1 Note 1 95SrcOaEnth N/A 0SrcOaQuality N/A 29SrcOccSensor Cloop[1-6] Occupancy

InStartStop [1-8] Occupancy In

Occupancy InSensor Occupancy_[1-18] In

Occupancy Cmd In Occupancy Sensor In 109

Note 1: SrcMonSw may be referred to any input with a NV type of 95 if appropriate for the application. The following listed inputs have no applicable source point from W7753 Unit Vent

Dlc Shed_[1-18] In DLC Shed In 0Counter Enable/Disable [1-2]

Counter Enable_[1-2] In 0

Runtime Enable/Disable [1-15]

0

RIO Analog Inputs_[1-3]

RIO Analog Input_[1-3] In

0

Runtime Value Preset [1-15]

0

Counter Preset Value [1-2]

Counter Preset_[1-2] In 8

KW Cascade In KW Cascade In 28Total KW In 28

RA Relative Humidity In 81FanOnAuto In 95

Remote Digital In [1-12] Remote Sensor_[1-12] In

95

DA Temp In 105RA Temp In 105

Setpoint Offset In 105Control Loop[1-6] Mode Appl Mode In Application Mode In 108Cloop[1-6] ManOcc In Manual Occupancy_[1-

18] In 109

Bldg Static Pressure In 113Duct Static Pressure In 113Time of Day Event_[1-18] In

Occupancy Schedule In 128

Table 13. Refer Points from W7751 XL10 VAV II Terminal Box Controller to XL10.

SourceW7751 VAV II

DestinationW7751 VAV II

DestinationW7750 CVAHU

DestinationW7753 Unit Vent

Destination W7763 CHC

DestinationW7752 FCU and

W7762 HYDNV

TypeEffectSetPtOut nviSetPoint SetPointIn DestRmTempSpt DestRmTemp

SptRoom temperature setpoint

105

nvoBoxFlow nviFlowTrack N/A N/A N/A N/A 15nvoBypass nviBypass Bypass In DestBypass N/A N/A 95nvoEnergyHoldOff

nviEnergyHoldOff Window Contact In N/A DestWindow Window sensor sharing

95

nvoFlowControlPt

N/A N/A N/A N/A N/A 15

nvoFlowTrack nviFlowTrack N/A N/A N/A N/A 15

Table 12. Refer Points from W7753 XL10 Unit Ventilator (Unit Vent) Controller to XL15, T7350 and Q7300. (Continued)

SourceW7753 Unit Vent

DestinationW7760A Bldg Mgr

DestinationW7760C Plant Mgr

DestinationT7300F / Q7300H Destination T7350

NV Type

Page 48: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 48

nvoMonSw Note 1 Note 1 Note 1 N/A N/A 95nvoSensorOcc nviOccCmd OccSensorIn DestOccSensor DestOccSensor SensorOcc 109nvoShare nviShare N/A N/A N/A N/A 0nvoStatus N/A N/A N/A N/A N/A 93SpaceTempOut

nviSpaceTemp SpaceTempIn DestRmTemp DestRmTemp Space temperature input

105

TerminalLoad N/A N/A N/A N/A N/A 81Note 1: nvoMonSw may be referred to any input with a NV type of 95 if appropriate for the application.

The following destination inputs can be shared from VAVII outputs of the same NV typeFree1 In Free1 In Free1 In 95

Free2 In 95The following listed inputs have no applicable source point from W7751 VAV IInviDlcShed DLC Shed In DestDlcShed Load shed control 0nviFlowOffset 0nviManValue ManualValue In nviManValue 0nviManualMode Manual Mode In nviManualMode Manual mode 0

Outdoor Enthalpy In

DestOaEnth 0

DestOaQuality 29OdHumIn DestOaHum 81

nviHeaterOverid 95Econ In DestEconEnable 95IAQ Override In DestIaqOvrd 95Time Clock In 95WSHP Enable Out 95

FanSpeedIn Fan speed command

95

DestHtSource 95nviEmergCmd EmergIn DestEmerg Emergency

command103

nviDuctInTemp 105nviSetPtOffset SetPtOffsetIn CmdSetPtOffst Setpoint offset 105

DestSourceTemp 105OdTempIn DestOaTemp 105

nviApplicMode ApplModeIn CmdHvacMode Application mode 108nviManOcc ManOccIn CmdManualOcc Manual network

occupancy109

nviTodEvent Time Of Day In SchedOcc Time Of Day In 128External cool output control

81

External heat output control

81

Table 13. Refer Points from W7751 XL10 VAV II Terminal Box Controller to XL10. (Continued)

SourceW7751 VAV II

DestinationW7751 VAV II

DestinationW7750 CVAHU

DestinationW7753 Unit Vent

Destination W7763 CHC

DestinationW7752 FCU and

W7762 HYDNV

Type

Page 49: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

49 74-3679�1

Table 14. Refer Points from W7751 XL10 VAV II Terminal Box Controller to XL15, T7350 and Q7300H.

SourceVAVII

DestinationW7760A Bldg Mgr

DestinationW7760C Plant Mgr

DestinationT7300F / Q7300H Destination T7350

NV Type

EffectSetPtOut N/A N/A Setpoint In Setpoint In 105nvoBoxFlow N/A N/A N/A N/A 15nvoBypass Cloop[1-6] Bypass In

StartStop [1-8] Bypass In

Bypass_[1-18] In Bypass In Bypass In 95

nvoEnergyHoldOff N/A N/A N/A N/A 95nvoFlowControlPt N/A N/A N/A N/A 15nvoFlowTrack N/A N/A N/A N/A 15nvoMonSw Note 1 Note 1 Note 1 Note 1 95nvoSensorOcc Cloop[1-6] Occupancy

InStartStop [1-8] Occupancy In

Occupancy InSensor Occupancy_[1-18] In

Occupancy Cmd InN/A

Occupancy Sensor In 109

nvoShare N/A N/A N/A N/A 0SpaceTempOut N/A N/A Space Temperature In Space Temperature In 105nvoStatus N/A N/A N/A N/A 93TerminalLoad N/A N/A N/A N/A 81Note 1: nvoMonSw may be referred to any input with a NV type of 95 if appropriate for the application.

The following listed inputs have no applicable source point from W7751 VAV IICounter Enable/Disable [1-2]

Counter Enable_[1-2] In 0

Runtime Enable/Disable [1-15]

0

Runtime Value Preset [1-15]

0

RIO Analog Inputs_[1-3]

RIO Analog Input_[1-3] In

0

Dlc Shed_[-18]1 In DLC Shed In DLC Shed In 0Counter Preset Value [1-2]

Counter Preset_[1-2] In 8

KW Cascade In KW Cascade In 28Total KW In 28Outdoor Air Humidity In Od Hum In 81

RA Relative Humidity In 81Econ Enable In 95

Remote Digital In [1-12] Remote Sensor_[1-12] In

95

FanOnAuto In FanOnAuto In 95Emergency Override In 103

Outdoor Air Temperature In

DA Temp In 105

Od Temp In 105RA Temp In 105

Setpoint Offset In Setpoint Offset In 105Control Loop[1-6] Mode Appl Mode In Application Mode In Application Mode In 108

Page 50: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 50

Cloop[1-6] ManOcc In Manual Occupancy_[1-18] In

109

Bldg Static Pressure In 113Duct Static Pressure In 113Time of Day Event_[1-18] In

Occupancy Schedule In Occupancy Schedule In

128

Table 15. Refer Points from Fan Coil Unit Controller to XL10.

SourceW7752 FCU

DestinationW7752 FCU and

W7762 HYDDestination

W7750 CVAHUDestination

W7753 Unit VentDestination

VAV2Destination W7763 CHC

NV Type

Active Setpoint Room temperature setpoint

SetPointIn DestRmTempSpt nviSetPoint DestRmTempSpt

105

Application mode Output

Application mode ApplModeIn CmdHvacMode nviApplicMode DestHvacMode 108

Cool Control Output

External cool output control

N/A N/A N/A DestManCool 81

Digital Input State N/A Note 1 Note 1 Note 1 N/A 95Effective Occupancy State

Manual network occupancy

ManOccIn CmdManualOcc nviManOcc DestManOcc 109

Fan Speed Output Fan speed command

HYD: N/A

N/A FanSpeedIn N/A DestFanSpeed 95

Fan Speed Switch Fan speed switch

HYD: N/A

N/A FanSpeedIn N/A DestFanSpeed 95

Heat Control Output

External heat output control

N/A N/A N/A DestManHeat 81

Polled Fcu status N/A N/A N/A N/A N/A 0Reheat output Auxiliary reheat

output

HYD: N/A

N/A N/A nviHeater Overide DestReheat 95

SensorOccOut SensorOcc OccSensorIn DestOccSensor nviOccCmd DestOccSensor 109Space Temperature Output

Space temperature Input

SpaceTempIn DestRmTemp nviSpaceTemp DestRmTempDestRmTempSpt

105

Terminal Load N/A N/A N/A N/A N/A 81Window Output Window sensor

sharingWindow Contact In N/A nviEnergyHoldOff DestWindow 95

Note 1: Digital input state may be referred to any input with a NV type of 95 if appropriate for the application.The following listed inputs can be shared from W7752 FCU outputs of the same NV type

Free1 In Free1 In Free1 In 95Free2 In 95

The following points have no applicable source points in the W7752 FCU ControllerLoad shed control DLC Shed In DestDlcShed nviDlcShed 0

ManualValue In nviManValue nviManValue 0Manual mode Manual Mode In nviManualMode nviManualMode 0Setpoint offset SetPtOffsetIn CmdSetPtOffst nviSetPtOffset 105

Table 14. Refer Points from W7751 XL10 VAV II Terminal Box Controller to XL15, T7350 and Q7300H. (Continued)

SourceVAVII

DestinationW7760A Bldg Mgr

DestinationW7760C Plant Mgr

DestinationT7300F / Q7300H Destination T7350

NV Type

Page 51: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

51 74-3679�1

NOTE: Refer to the controller engineering guide for the specific sequence of operation for each controller and the use of network variables.

Outdoor Enthalpy In

DestOaEnth 0

Bypass In DestBypass nviBypass 95Econ In DestEconEnable 95IAQ Override In DestIaqOvrd 95Time Clock In 95WSHP Enable Out 95OdHumIn DestOaHum 81OdTempIn DestOaTemp 105

DestHtSource 95nviShare 0nviFlowOffset 0nviDuctInTemp 105

8195105

Table 16. Refer points from Fan Coil Unit Controller to XL15, T7350 and Q7300H.

Source W7752 FCU

Destination W7760A Bldg Mgr

DestinationW7760C Plant Mgr

DestinationT7300F / Q7300H Destination T7350

NV Type

Active Setpoint N/A N/A Setpoint In Setpoint In 105Application mode Output

ControlLoop[1-6] Mode Appl Mode In Application Mode in Application Mode in 108

Cool Control Output N/A N/A N/A N/A 81Digital input state Note 1 Note 1 Note 1 Note 1 95Effective occupancy state

CLoop[1-6] ManOcc InStartStop[1-8] ManOccIn

Manual Occupancy_[1-18]Occupancy In

Occupancy Cmd In Occupancy Sensor In 109

Fan speed output N/A N/A N/A N/A 95Fan speed switch N/A N/A FanOnAuto In FanOnAuto In 95Heat Control Output N/A N/A N/A N/A 81Polled Fcu status N/A N/A N/A N/A 0Reheat output Remote Digital In [1-12] Remote Sensor_[1-12]]

InN/A N/A 95

SensorOccOut CLoop[1-6] Occupancy In

Sensor Occupancy_[1-18] In

Occupancy Cmd In Occupancy Sensor In 109

Space temperature output

N/A N/A Space Temperature In Space Temperature In 105

Terminal Load N/A N/A N/A N/A 81Window Output Remote Digital In [1-12] Remote Sensor_[1-12]

InN/A N/A 95

Note 1: Digital input state may be referred to any input with a NV type of 95 if appropriate for the application.Counter Enable/Disable [1-2]

Counter Enable_[1-2] In 0

Runtime Enable/Disable [1-15]

0

Table 15. Refer Points from Fan Coil Unit Controller to XL10. (Continued)

SourceW7752 FCU

DestinationW7752 FCU and

W7762 HYDDestination

W7750 CVAHUDestination

W7753 Unit VentDestination

VAV2Destination W7763 CHC

NV Type

Page 52: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 52

Runtime Value Preset [1-15]

0

RIO Analog Inputs_[1-3]

RIO Analog Input_[1-3] In

0

Dlc Shed_[1-18]1 In DLC Shed In DLC Shed In 0Counter Preset Value [1-2]

Counter Preset_[1-2] In 8

KW Cascade In KW Cascade In 28Total KW In 28Outdoor Air Humidity In Od Hum In 81

RA Relative Humidity In 81Econ Enable In 95

Remote Digital In [1-12] Remote Sensor_[1-12] In

95

Emergency Override In 103Outdoor Air Temperature In

Od Temp In 105

DA Temp In 105RA Temp In 105

Setpoint Offset In Setpoint Offset In 105

Table 17. Refer points from Chilled Ceiling Controller to XL10.

SourceW7763 CHC

DestinationW7763 CHC

DestinationW7750 CVAHU

DestinationW7753 Unit Vent

DestinationVAV2

DestinationW7752 FCU and

W7762 HYDNV

TypeSrcCoolPos DestManCool N/A N/A N/A External cool

output control81

SrcFanSpeed DestFanSpeed N/A FanSpeedIn N/A Fan speed command

HYD: N/A

95

SrcFanSpeedSw DestFanSpeed N/A FanSpeedIn N/A Fan speed command

HYD: N/A

95

SrcHeatPos DestManHeat N/A N/A N/A External heat output control

81

SrcHvacMode DestHvacMode ApplModeIn CmdHvacMode nviApplicMode Application mode 108SrcOccEff DestManOcc ManOccIn CmdManualOcc nviManOcc Manual network

occupancy109

SrcOccSensor DestOccSensor OccSensorIn DestOccSensor nviOccCmd SensorOcc 109SrcReheatPos DestReheat N/A N/A nviHeater Overid Auxiliary reheat

output

HYD: N/A

95

SrcRmDewPt N/A N/A N/A N/A Space Temperature Input

105

SrcRmTempEff DestRmTemp SpaceTempIn DestRmTemp nviSpaceTemp Space Temperature Input

105

SrcRmTempSpt Eff DestRmTempSpt SetPointIn DestRmTempSpt nviSetPoint Room Temperature setpoint

105

Table 16. Refer points from Fan Coil Unit Controller to XL15, T7350 and Q7300H. (Continued)

Source W7752 FCU

Destination W7760A Bldg Mgr

DestinationW7760C Plant Mgr

DestinationT7300F / Q7300H Destination T7350

NV Type

Page 53: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

53 74-3679�1

SrcStateDI1 N/A Note 1 Note 1 Note 1 N/A 95SrcTermLoad N/A N/A N/A N/A N/A 81SrcWindow DestWindow Window Contact In N/A nviEnergyHold

OffWindow sensor sharing

95

Note 1: SrcStateDI1 may be referred to any input with a NV type of 95 if appropriate for the application.The following listed inputs can be shared from W7762 Hyd outputs of the same NV type

Free1 In Free1 In Free1 In 95Free2 In 95

The following points have no applicable source points in the W7762 Hyd ControllerDestManMode Manual Mode In nviManualMode nviManualMode Manual mode 0

ManualValue In nviManValue nviManValue 0DestSptOffset SetPtOffsetIn DestSetPtOffst nviSetPtOffset Setpoint offset 105DestCoolTemp 105DestRmRelHum 81DestCondSensor 95DestEmerg EmergIn DestEmerg nviEmergCmd Emergency

command103

OdHumin DestOaHum 81Bypass In DestBypass nviBypass 95Econ In DestEconEnable 95

DestHtSource 95IAQ Override In DestIaqOvrd 95OdTempIn DestOaTemp 105

DestSourceTemp 105nviDuctInTemp 105

Table 18. Refer points from Chilled Ceiling Controller to XL15, T7350 and Q7300H.

SourceW7763 CHC

DestinationW7760A Bldg Mgr

DestinationW7760C Plant Mgr

Destination T7300F / Q7300H Destination T7350

NV Type

SrcCoolPos N/A N/A N/A N/A 81SrcFanSpeed Remote Digital In [1-12] Remote Sensor_[1-12]

InFanOnAuto In FanOnAuto In 95

SrcFanSpeedSw Remote Digital In [1-12] Remote Sensor_[1-12] In

FanOnAuto In FanOnAuto In 95

SrcHeatPos N/A N/A N/A N/A 81SrcHvacMode Control Loop[1-6] Mode Appl Mode In Application Mode In Application Mode In 108SrcOccEff CLoop[1-6] ManOcc In Manual Occupancy_[1-

18] InOccupancy Cmd In Occupancy Sensor

In109

StartStop[1-8] ManOcc In

109

SrcOccSensor CLoop [1-6] Occupancy In

Occupancy In Occupancy Cmd In Occupancy Sensor In

109

StartStop[1-8] Occupancy In

Sensor Occupancy_[1-18] In

109

SrcReheatPos Remote Digital In [1-12] Remote Sensor_[1-12] in

N/A N/A 95

Table 17. Refer points from Chilled Ceiling Controller to XL10. (Continued)

SourceW7763 CHC

DestinationW7763 CHC

DestinationW7750 CVAHU

DestinationW7753 Unit Vent

DestinationVAV2

DestinationW7752 FCU and

W7762 HYDNV

Type

Page 54: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 54

SrcRmDewPt N/A N/A N/A Setpoint InSpace Temperature In

105

SrcRmTempEff N/A N/A Space Temperature In Space Temperature In

105

SrcRmTempSpt Eff N/A N/A Setpoint In Setpoint In 105SrcStateDI1 Remote Digital In [1-12] Remote Sensor_[1-12]

InN/A N/A 95

SrcTermLoad N/A N/A N/A N/A 81SrcWindow Remote Digital In [1-12] Remote Sensor_[1-12]

InN/A N/A 95

The following points have no applicable source points in the W7762 Hyd.CLoop[1-6] Bypass In Bypass_[1-18] In Bypass In Bypass In 95StartStop [1-8] Bypass In

95

Outdoor Air Temperature In

Od Temp In 105

DA Temp In 105RA Temp In 105Od Hum In 81RA Relative Humidity In 81Econ Enable In 95

Setpoint Offset In Setpoint Offset In 105

Table 19. Refer points from Hydronic controller to XL 10.

SourceW7762 HYD

Destination W7752 FCU and

W7762 HYD Destination

W7750 CVAHUDestination

W7753 Unit VentDestination

VAV2Destination W7763 CHC

NV Type

Active Setpoint Room temperature setpoint

SetPointIn DestRmTemp Spt nviSetPoint DestRmTempSpt 105

Application Mode Output

Application Mode ApplModeIn N/A nviApplicMode N/A 108

Cool Control Output

External Cool Output Control

N/A N/A N/A DestManCool 81

Digital Input State N/A Window Contact In N/A nviEnergyHoldOff DestWindow 95Effective Occupancy State

Manual Network Occupancy

ManOccIn CmdManual Occ nviManOcc DestManOcc 109

Heat Control Output

External Heat Output Control

N/A N/A N/A DestManHeat 81

Polled Hyd Status N/A N/A N/A N/A N/A 0SensorOccOut SensorOcc OccSensorIn DestOccSensor nviOccCmd DestOcc Sensor 109Space Temperature Output

Space Temperature Input

SpaceTempIn DestRmTemp nviSpaceTemp DestRmTemp 105

Window Output Window Sensor Sharing

Window Contact In N/A nviEnergyHoldOff DestWindow 95

Table 18. Refer points from Chilled Ceiling Controller to XL15, T7350 and Q7300H. (Continued)

SourceW7763 CHC

DestinationW7760A Bldg Mgr

DestinationW7760C Plant Mgr

Destination T7300F / Q7300H Destination T7350

NV Type

Page 55: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

55 74-3679�1

Table 20. Refer points from Hydronic Controller to XL15, T7350 and Q7300H.

SourceW7762 HYD

Destination W7760A Bldg Mgr

DestinationW7760C Plant Mgr

Destination T7300F / Q7300H Destination T7350

NV Type

Active Setpoint N/A N/A Setpoint InSpace Temperature In

Setpoint InSpace Temperature In

105

Application Mode Output

Control Loop[1-6] Mode Appl Mode In Application Mode In Application Mode In 108

Cool Control Output N/A N/A N/A N/A 81Digital Input State N/A Remote Sensor_[1-12]

InN/A N/A 95

Effective Occupancy State

CLoop[1-6] ManOcc InStartStop[1-8] ManOcc In

Manual Occupancy_[1-18] In

Occupancy Cmd In Occupancy Sensor In 109

Heat Control Output N/A N/A N/A N/A 81Polled Hyd Status N/A N/A N/A N/A 0SensorOccOut CLoop [1-6] Occupancy

InStartStop[1-8] Occupancy InCLoop[1-6] ManOcc InStartStop[1-8] ManOccIn

Sensor Occupancy_[1-18] InOccupancy In

Occupancy Cmd In Occupancy Sensor In 109

Space Temperature Output

N/A N/A Setpoint InSpace Temperature In

Setpoint InSpace Temperature In

105

Window Output Remote Digital In [1-12] Remote Sensor_[1-12] In

N/A N/A 95

Table 21. Refer Points from T/Q7300H XL10 Thermostat to XL10.

SourceT / Q7300

DestinationW7750 CVAHU

DestinationW7753 Unit Vent

DestinationW7751 VAV II

DestinationW7752 FCU and

W7762 HYDDestination W7763 CHC

NVType

Application Mode out

ApplModeIn CmdHvacMode nviApplicMode Application mode DestHvacMode 108

Bypass Out Bypass In DestBypass nviBypass N/A N/A 95Cool Output N/A N/A N/A External cool

output controlDestManCool 81

EffectiveOcc Out OccSensorIn DestOccSensor nviOccCmd SensorOcc DestOcc Sensor 109Effective Stpt Out SetPointIn DestRmTemp Spt nviSetPoint Room temperature

setpointDestRmTempDestRmTempSpt

105

Fan Out N/A FanSpeedInDestBypass

N/A Fan speed command

HYD: N/A

DestFan Speed 95

Heat Output N/A N/A N/A External heat output control

DestManHeat 81

Setpoint Out SetPointIn DestRmTemp Spt nviSetPoint Room temperature setpoint

DestRmTempDestRmTempSpt

105

Space Temperature Out

SpaceTempIn DestRmTemp nviSpaceTemp Space Temperature Input

DestRmTempDestRmTempSpt

105

Time Of Day Out [1-4]

Time Of Day In SchedOcc nviTodEvent Time Of Day In N/A 128

The following listed inputs have no applicable source point from T7300F/Q7300H.DLC Shed In DestDlcShed nviDlcShed Load shed control 0Outdoor Enthalpy In

DestOaEnth 0

Page 56: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 56

Manual Mode In nviManualMode nviManualMode Manual mode 0ManualValue In nviManValue nviManValue 0

nviFlowOffset 0nviShare 0nviFlowTrack 15

DestOaQuality 29OdHumIn DestOaHum 81Free1 In Free1 In Free1 In 95Free2 In 95Econ In DestEconEnable 95IAQ Override In DestIaqOvrd 95Time Clock In 95Window Contact In nviEnergyHoldOff Window sensor

sharing95

WSHP Enable Out 95DestHtSource Auxiliary reheat

output95

EmergIn DestEmerg nviEmergCmd Emergency command

103

OdTempIn DestOaTemp 105DestSource Temp nviDuctInTemp 105

SetPtOffsetIn CmdSetPtOffst nviSetPtOffset Setpoint offset 105ManOccIn CmdManualOcc nviManOcc Manual network

occupancy109

8195

Table 22. Refer Points from T/Q7300H XL10 Thermostat to XL15, T7350 and Q7300.

SourceT/Q7300

DestinationT7300F / Q7300H

DestinationW7760A Bldg Mgr

DestinationW7760C Plant Mgr

DestinationT7350

NVType

Application Mode out Application Mode In Control Loop[1-6] Mode Appl Mode In Application Mode In 108Bypass Out Bypass In Cloop[1-6] Bypass In

StartStop [1-8] Bypass InBypass_[1-18] In Bypass In 95

Cool Output N/A N/A N/A N/A 81Effective Occ Out Occupancy Cmd In Cloop[1-6] Occupancy In Occupancy In Occupancy Sensor

In109

StartStop [1-8] Occupancy In

Sensor Occupancy_[1-18] In

109

Effective Stpt Out Setpoint In N/A N/A Setpoint InSpace Temperature In

105

Fan Out N/A N/A N/A FanOnAuto In 95Heat Output N/A N/A N/A N/A 81Setpoint Out Setpoint In N/A N/A Setpoint In 105Space Temperature Out

Space Temperature In N/A N/A Space Temperature In

105

Time Of Day Out[1-4] Occupancy Schedule In

N/A Time of Day Event_[1-18] In

Occupancy Schedule In

128

Table 21. Refer Points from T/Q7300H XL10 Thermostat to XL10. (Continued)

SourceT / Q7300

DestinationW7750 CVAHU

DestinationW7753 Unit Vent

DestinationW7751 VAV II

DestinationW7752 FCU and

W7762 HYDDestination W7763 CHC

NVType

Page 57: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

57 74-3679�1

The following listed inputs have no applicable source point from T/Q7300.DLC Shed In Dlc Shed_[-18]1 In Dlc Shed_[-18]1 In 0

Counter Enable/Disable [1-2]

Counter Enable_[1-2] In Counter Enable_[1-2] In

0

Runtime Enable/Disable [1-15]

0

Runtime Value Preset [1-15]

0

RIO Analog Inputs_[1-3] RIO Analog Input_[1-3] In

RIO Analog Input_[1-3] In

0

Counter Preset Value [1-2]

Counter Preset_[1-2] In Counter Preset_[1-2] In

8

KW Cascade In KW Cascade In KW Cascade In 28Total KW In 28Outdoor Air Humidity In Od Hum In Od Hum In 81

RA Relative Humidity In RA Relative Humidity In

81

FanOnAuto In 95Econ Enable In Econ Enable In 95

Remote Digital In [1-12] Remote Sensor_[1-12] In

Remote Sensor_[1-12] In

95

Emergency Override In Emergency Override In

103

DA Temp In DA Temp In 105Outdoor Air Temperature In

Od Temp In Od Temp In 105

RA Temp In RA Temp In 105Cloop[1-6] ManOcc In Manual Occupancy_[1-

18] InManual Occupancy_[1-18] In

109

Bldg Static Pressure In Bldg Static Pressure In

113

Duct Static Pressure In Duct Static Pressure In

113

Table 23. Refer Points from W7760A XL15A Building Manager to XL10.

SourceW7760ABldg Mgr

DestinationW7750 CVAHU

DestinationW7753 Unit Vent

DestinationW7751 VAV II

DestinationW7752 FCU and

W7762 HYDDestination W7763 CHC

NV Type

CLoop[1-6] Bypass Out

Bypass In DestBypass nviBypass N/A N/A 95

Counter Value [1-2]

N/A N/A N/A N/A N/A 8

Table 22. Refer Points from T/Q7300H XL10 Thermostat to XL15, T7350 and Q7300. (Continued)

SourceT/Q7300

DestinationT7300F / Q7300H

DestinationW7760A Bldg Mgr

DestinationW7760C Plant Mgr

DestinationT7350

NVType

Page 58: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 58

Dig Cmd Free_[0-23]

Free1 In Free1 In Free1 In Auxiliary reheat output

95

Free 2 In FanSpeedIn nviHeaterOverid Fan speed command

DestFan Speed 95

WSHP Enable Out DestHtSource nviEnergyHold Off Window sensor sharing

HYD: Window Sensor Sharing

DestWindow 95

Econ In DestEcon Enable 95IAQ Override In DestIaqOvrd 95Time Clock In 95Window Contact In 95

DLC Output Load [1-20]

DLC Shed In DestDlcShed nviDlcShed Load shed control N/A 0

KW Cascade Out N/A N/A N/A N/A N/A 28Occupancy Sensor [1-2] Out

OccSensorIn DestOccSensor nviOccCmd SensorOcc DestOcc Sensor 109

Outdoor Air Humidity Out

OdHumIn DestOaHum N/A DestRmRel Hum

81

Outdoor Air Temperature Out

OdTempIn DestOaTemp N/A N/A 105

Remote Output [0-23]

OdHumIn N/A N/A External Cool Output Control

N/A 81

Runtime Value [1-15]

N/A N/A 0

StartStop [1-8] Bypass Out

Bypass In DestBypass nviBypass N/A N/A 95

TOD Event [1-20] Time Of Day In SchedOcc nviTodEvent Time Of Day In N/A 128Total KW N/A N/A 28

The following listed inputs have no applicable source point from W7760A Bldg Mgr.Outdoor Enthalpy In

DestOaEnth 0

Manual Mode In nviManualMode nviManualMode Manual mode 0ManualValue In nviManValue nviManValue 0

nviFlowOffset 0nviShare 0nviFlowTrack 15

DestOaQuality 29EmergIn DestEmerg nviEmergCmd Emergency

command103

SetPointIn DestRmTempSpt nviSetPoint Room temperature setpoint

105

SpaceTempIn DestRmTemp nviSpace Temp Space temperature input

105

SetPtOffsetIn CmdSetPt Offst nviSetPtOffset Setpoint offset 105

Table 23. Refer Points from W7760A XL15A Building Manager to XL10. (Continued)

SourceW7760ABldg Mgr

DestinationW7750 CVAHU

DestinationW7753 Unit Vent

DestinationW7751 VAV II

DestinationW7752 FCU and

W7762 HYDDestination W7763 CHC

NV Type

Page 59: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

59 74-3679�1

DestSource Temp 105nviDuctIn Temp 105

ApplModeIn CmdHvacMode nviApplicMode Manual mode 108ManOccIn CmdManualOcc nviManOcc Manual network

occupancy109

Table 24. Points from W7760A XL15A Building Manager to XL15, T7350 and Q7300H.

SourceW7760A Bldg Mgr

DestinationW7760A Bldg Mgr

DestinationW7760C Plant Mgr

Destination T7300F / Q7300H Destination T7350

NVType

Cloop[1-6] Bypass Out Cloop[1-6] Bypass In Bypass_[1-18] In Bypass In Bypass In 95StartStop [1-8] Bypass In

95

Counter Value [1-2] Counter Preset Value [1-2]

Counter Preset_[1-2] In N/A N/A 8

Dig Cmd Free_[0-23] Econ Enable In FanOnAuto In FanOnAuto In 95DLC Output Load [1-20]

Dlc Shed_[-18]1 In DLC Shed In DLC Shed In 0

KW Cascade Out KW Cascade In KW Cascade In N/A 28Occupancy Sensor [1-2] Out

Cloop[1-6] Occupancy In

Occupancy In Occupancy Cmd In Occupancy Sensor In

109

StartStop [1-8] Occupancy In

Sensor Occupancy_[1-18] In

109

Outdoor Air Humidity Out

Outdoor Air Humidity In Od Hum In Space Humidity In 81

Outdoor Air Temperature Out

Outdoor Air Temperature In

Od Temp In Outdoor Air Temperature InSetpoint InSpace Temperature In

105

Remote Output [0-23] N/A 81Runtime Value [1-15] N/A 0StartStop [1-8] Bypass Out

Bypass In 95

TOD Event [1-20] Time of Day Event_[1-18] In

Occupancy Schedule In Occupancy Schedule In

128

Total KW Total KW In N/A 28The following listed inputs have no applicable source point from W7760A Bldg MgrCounter Enable/Disable [1-2]

Counter Enable_[1-2] In 0

Runtime Enable/Disable [1-15]

0

Runtime Value Preset [1-15]

0

RIO Analog Inpust_[1-3] RIO Analog Input_[1-3] In

0

Counter Preset Value [1-2]

Counter Preset_[1-2] In 8

RA Relative Humidity In 81Remote Digital In [1-12] Remote Sensor_[1-12]

In95

Table 23. Refer Points from W7760A XL15A Building Manager to XL10. (Continued)

SourceW7760ABldg Mgr

DestinationW7750 CVAHU

DestinationW7753 Unit Vent

DestinationW7751 VAV II

DestinationW7752 FCU and

W7762 HYDDestination W7763 CHC

NV Type

Page 60: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 60

Emergency Override In 103DA Temp In 105RA Temp In 105

105105

Control Loop[1-6] Mode Appl Mode In 108Cloop[1-6] ManOcc In Manual Occupancy_[1-

18] In109

Bldg Static Pressure In 113Duct Static Pressure In 113

Table 25. Refer Points from W7760C XL15C Plant Controller to XL10.

SourceW7760C

Plant MgrDestination

W7750 CVAHUDestination

W7753 Unit VentDestination

W7751 VAV II

DestinationW7752 FCU and

W7762 HYDDestination W7763 CHC

NVType

AI [1-8] Sensor N/A N/A 0Appl Mode Out ApplModeIn CmdHvacMode nviApplicMode Application mode DestHvacMode 108Bypass_[1-18] Out Bypass In DestBypass nviBypass N/A N/A 95Cool UTML Out N/A N/A N/A N/A N/A 95Counter_[1-2] Out N/A N/A N/A N/A N/A 8DA Temp Out N/A N/A N/A N/A DestCool

TempDestRmTempDestRmTempSptDestSptOffset

105

Digital Cmd Free_[1-24] Out

Free1 In Free1 In Free1 In Auxiliary reheat output

DestReheat 95

Free2 In FanSpeedIn Fan speed command

DestFanSpeed 95

Window Contact In DestHtSource nviEnergyHold Off Window sensor sharing

HYD: Window Sensor Sharing

DestWindow 95

WSHP Enable Out DestEcon Enable 95Time Clock In DestIaqOvrd 95IAQ Override In nviHeater Overid 95

Econ Enable Out Econ In N/A DestWindow 95Heat UTML Out N/A N/A 95KW Cascade Out N/A N/A 28Occupancy Out OccSensorIn DestOccSensor nviOccCmd SensorOcc DestManOcc

DestOccSensor109

Od Hum Output OdHumIn DestOaHum N/A N/A DestRmRelHum

81

Od Temp Output OdTempIn DestOaTemp N/A N/A DestCoolTempDestRmTempDestRmTempSpt

105

Table 24. Points from W7760A XL15A Building Manager to XL15, T7350 and Q7300H. (Continued)

SourceW7760A Bldg Mgr

DestinationW7760A Bldg Mgr

DestinationW7760C Plant Mgr

Destination T7300F / Q7300H Destination T7350

NVType

Page 61: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

61 74-3679�1

Remote Cmd_[1-24] Out

N/A N/A N/A External cool output control

DestManCool 81

External heat output control

DestManHeat 81

Sensor Occupancy_[1-2] Out

OccSensorIn DestOccSensor nviOccCmd SensorOcc DestManOccDestOccSensor

109

The following listed inputs have no applicable source point from W7760C Plant MgrDLC Shed In DestDlcShed nviDlcShed Load shed control 0Outdoor Enthalpy In

DestOaEnth 0

Manual Mode In nviManualMode nviManualMode Manual mode 0ManualValue In nviManValue nviManValue 0

nviFlowOffset 0nviShare 0nviFlowTrack 15

DestOaQuality 29EmergIn DestEmerg nviEmergCmd Emergency

command103

SpaceTempIn DestRmTemp nviSpaceTemp Space temperature input

105

DestRmTemp Spt nviSetPoint Room temperature setpoint

105

SetPtOffsetIn CmdSetPtOffst nviSetPtOffset Setpoint offset 105DestSource Temp 105

nviDuctInTemp 105ManOccIn CmdManualOcc nviManOcc Manual network

occupancy109

Time Of Day In SchedOcc nviTodEvent Time Of Day In 12881

Table 26. Refer Points from W7760C XL15C Plant Controller to XL15, T7350 and Q7300H.

SourceW7760C Plant Mgr

DestinationW7760C Plant Mgr

DestinationW7760A Bldg Mgr

DestinationT7300F / Q7300H Destination T7350

NVType

AI [1-8] Sensor N/A 0Appl Mode Out Appl Mode In Control Loop[1-6] Mode Application Mode In Application Mode In 108Bypass_[1-18] Out Bypass_[1-18] In Cloop[1-6] Bypass In Bypass In Bypass In 95

StartStop [1-8] Bypass In StartStop [1-8] Bypass In

95

Cool UTML Out N/A 95Counter_[1-2] Out N/A 8DA Temp Out DA Temp In Space Temperature

InSetpoint In

105

Digital Cmd Free_[1-24] Out

FanOnAuto In FanOnAuto In 95

Econ Enable Out Econ Enable In N/A 95Heat UTML Out N/A 95

Table 25. Refer Points from W7760C XL15C Plant Controller to XL10. (Continued)

SourceW7760C

Plant MgrDestination

W7750 CVAHUDestination

W7753 Unit VentDestination

W7751 VAV II

DestinationW7752 FCU and

W7762 HYDDestination W7763 CHC

NVType

Page 62: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 62

KW Cascade Out KW Cascade In KW Cascade In N/A 28Occupancy Out Occupancy In Cloop[1-6] Occupancy In Occupancy Cmd In Occupancy Sensor

In109

Sensor Occupancy_[1-18] In

StartStop [1-8] Occupancy In

109

Od Hum Output Od Hum In Outdoor Air Humidity In Space Humidity In 81Od Temp Output Od Temp In Outdoor Air Temperature

InOutdoor Temperature InSpace Temperature InSetpoint In

105

Remote Cmd_[1-24] Out

Outdoor Air Humidity In

81

Sensor Occupancy_[1-2]Out

Sensor Occupancy_[1-18] In

Cloop[1-6] Occupancy In Occupancy Cmd In Occupancy Sensor In

109

Occupancy In StartStop [1-8] Occupancy In

109

The following listed inputs have no applicable source point from W7760C Plant MgrDlc Shed_[-18]1 In DLC Shed In 0Counter Enable_[1-2] In

Counter Enable/Disable [1-2]

Counter Enable/Disable [1-2]

0

RIO Analog Input_[1-3] In

RIO Analog Inputs_[1-3] RIO Analog Inputs_[1-3]

0

Runtime Enable/Disable[1-15]

Runtime Enable/Disable[1-15]

0

Runtime Value Preset [1-15]

Runtime Value Preset [1-15]

0

Counter Preset_[1-2] In

Counter Preset Value [1-2]

Counter Preset Value [1-2]

8

Total KW In Total KW In 28Total KW In Total KW In 28

RA Relative Humidity In

81

Remote Sensor_[1-12] In

Remote Digital In [1-12] Remote Digital In [1-12]

95

Emergency Override In 103RA Temp In 105

Space Temperature In 105Setpoint In 105

Manual Occupancy_[1-18]In

Cloop[1-6] ManOcc In Occupancy Cmd In Cloop[1-6] ManOcc In

109

Bldg Static Pressure In 113Duct Static Pressure In 113Time of Day Event_[1-18] In

Occupancy Schedule In 128

An RIO must be associated to an XL15. All network variables are automatically assigned to the associated XL15. The following points may be referred to additional devices as indicated.

Table 26. Refer Points from W7760C XL15C Plant Controller to XL15, T7350 and Q7300H. (Continued)

SourceW7760C Plant Mgr

DestinationW7760C Plant Mgr

DestinationW7760A Bldg Mgr

DestinationT7300F / Q7300H Destination T7350

NVType

Page 63: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

63 74-3679�1

Table 27. Refer Points from W7761 Remote Input/Output Device to XL10.

SourceRIO

DestinationW7750 CVAHU

DestinationUnit Vent

DestinationW7751 VAV II

Destination W7763 CHC

DestinationW7752 FCU and

W7762 HYDNV

TypeCO2 Sensor N/A DestOaQuality N/A N/A N/A 29Current Sensor N/A N/A N/A N/A N/A 2Humidity Sensor [1-2]

OdHumIn DestOaHum N/A DestRmRelHum

N/A 81

Pressure Sensor [1-2]

N/A N/A N/A N/A N/A 113

Remote Analog Input N/A N/A N/A N/A N/A 0Remote Input [1-4] Econ In DestEcon Enable DestReheat Auxiliary reheat

output95

Free1 In Free1 In Free1 In 95Free2 In DestHtSource nviEnergyHold Off 95IAQ Override In DestIaqOvrd 95Time Clock In 95Window Contact In Window sensor

sharing

HYD: Window Sensor Sharing

95

WSHP Enable Out 95Temperature Sensor [1-4]

OdTempIn DestOaTemp nviDuctInTemp DestCoolTemp 105SpaceTempIn DestRmTemp nviSpaceTemp DestRmTemp Space

temperature input105

DestSource Temp DestRmTempSpt 105Voltage Sensor N/A N/A N/A N/A N/A 44

The following listed inputs have no applicable source point from RIODLC Shed In DestDlcShed nviDlcShed Load shed control 0Outdoor Enthalpy In

DestOaEnth 0

Manual Mode In nviManualMode nviManualMode Manual mode 0ManualValue In nviManValue nviManValue 0

nviFlowOffset 0nviShare 0nviFlowTrack 15

Bypass In DestBypass nviBypass 95FanSpeedIn Fan speed

command95

nviHeaterOverid Auxiliary reheat output

95

EmergIn DestEmerg nviEmergCmd Emergency command

103

SetPtOffsetIn CmdSetPtOffst nviSetPtOffset Setpoint offset 105DestRmTemp Spt nviSetPoint Room

temperature setpoint

105

ApplModeIn CmdHvacMode nviApplicMode Application mode 108ManOccIn CmdManual Occ nviManOcc Manual network

occupancy109

OccSensorIn DestOcc Sensor nviOccCmd SensorOcc 109

Page 64: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 64

Time Of Day In SchedOcc nviTodEvent Time Of Day In 128External cool output control

81

External heat output control

81

An RIO must be associated to an XL15. All network variables are automatically assigned to the associated XL15. The following points may be referred to additional devices as indicated.

Table 28. Refer Points from W7761 Remote Input/Output Device to XL15, T7350 and Q7300.

SourceRIO

DestinationW7760A Bldg Mgr

DestinationW7760C Plant Mgr

DestinationT7300F / Q7300H Destination T7350

NV Type

CO2 Sensor N/A 0Current Sensor N/A 2Humidity Sensor [1-2] Outdoor Air Humidity In Od Hum In N/A Space Humidity In 29

RA Relative Humidity In 29Pressure Sensor [1-2]

N/A Bldg Static Pressure InDuct Static Pressure In

N/A N/A 44

Remote Analog Input N/A 81Remote Input [1-4] Econ Enable In N/A 95Temperature Sensor [1-4]

Outdoor Air Temperature In

Od Temp In Space Temperature In Outdoor Temperature In

105

DA Temp In Setpoint In 105RA Temp In Space Temperature

In105

Voltage Sensor N/A 113The following listed inputs have no applicable source point from RIOCounter Enable/Disable [1-2]

Counter Enable_[1-2] In Counter Enable_[1-2] In

0

Dlc Shed_[-18]1 In DLC Shed In Dlc Shed_[-18]1 In 0RIO Analog Inpust_[1-3] RIO Analog Input_[1-3]

InRIO Analog Input_[1-3] In

0

Runtime Enable/Disable [1-15]

0

Runtime Value Preset [1-15]

0

Counter Preset Value [1-2]

Counter Preset_[1-2] In Counter Preset_[1-2] In

8

KW Cascade In KW Cascade In KW Cascade In 28Total KW In 28Cloop[1-6] Bypass In Bypass_[1-18] In Bypass In Bypass_[1-18] In 95StartStop [1-8] Bypass In

95

FanOnAuto In 95Remote Digital In [1-12] Remote Sensor_[1-12] In Remote Sensor_[1-

12] In95

Emergency Override In Emergency Override In

103

Setpoint In 105

Table 27. Refer Points from W7761 Remote Input/Output Device to XL10. (Continued)

SourceRIO

DestinationW7750 CVAHU

DestinationUnit Vent

DestinationW7751 VAV II

Destination W7763 CHC

DestinationW7752 FCU and

W7762 HYDNV

Type

Page 65: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

65 74-3679�1

Control Loop[1-6] Mode Appl Mode In Application Mode In Appl Mode In 108Cloop[1-6] ManOcc In Manual Occupancy_[1-

18] InOccupancy Cmd In Manual

Occupancy_[1-18] In109

StartStop [1-8] Occupancy In

Occupancy In Occupancy In 109

Sensor Occupancy_[1-18] In

Sensor Occupancy_[1-18] In

109

Bldg Static Pressure In Bldg Static Pressure In

113

Duct Static Pressure In Duct Static Pressure In

113

Time of Day Event_[1-18] In

Occupancy Schedule In Time of Day Event_[1-18] In

128

Table 29. Network Input Variable Description.

NV Input Address Comment ControllerNV

TypeNV

IndexAppl Mode In HVAC operating mode network input. (Off, Auto, Heat, Emergency Heat, Fan Only, Morning Warmup,

Night Purge) XL15C 108 361

Application mode HVAC operating mode network input. (Off, Auto, Heat, Emergency Heat, Fan Only, Morning Warmup, Night Purge, Pre-Cool, Cool, Test)

FCUHYD

108 10

Application Mode In HVAC operating mode network input. (Off, Auto, Heat, Emergency Heat, Fan Only) Q7300H 108 13Application Mode In HVAC operating mode network input. Sets the current state of the system mode switch. (�0�-

�HVAC_AUTO�, �1�- �HVAC_HEAT�, �3� - �HVAC_COOL�, �6� - �HVAC_OFF� (power up value), and �8�- �HVAC_EMERG_HEAT�). The value is saved in a non-volatile memory and set to �HVAC_AUTO� upon power up.

T7350 108 27

ApplModeIn HVAC operating mode network input. (Off, Auto, Heat, Emergency Heat, Fan Only, Cool) CVAHU 108 3Auxiliary Reheat Output Used for manually controlling the reheat relay output. It requires that the reheat be configured to be

external, which makes this point essentially a �Free� point.FCU 95 50

Bldg Static Pressure In Cannot be referred. No source point available. XL15C 113 370Bypass In Bypass network input. It shares the Bypass operation from the source controller to the destination

controller. The destination controller's bypass timer is not activated. The destination controller follows the bypass operation of the source controller based on the bypass arbitration status.

CVAHU, Q7300H,T7350

95 341930

Bypass_[1-18] In Bypass network input. It shares the Bypass operation from the source controller to the destination controller. The destination controller's bypass timer is not activated. The destination controller follows the bypass operation of the source controller based on the bypass arbitration status. [1-10] represent Control loops 1-10 and [11-18] represent StartStop Loops 1-8.

XL15C 95 126

CLoop[1-6] Bypass In Bypass network input. It shares the Bypass operation from the source controller to the destination controller. The destination controller's bypass timer is not activated. The destination controller follows the bypass operation of the source controller based on the bypass arbitration status.

XL15A 95 127

CLoop[1-6] ManOcc In Manual occupancy command network input. This network input is primarily intended for use with the command display unit and/or LONSTATION�. A network command to place the control device in manual occupancy mode of Occupied, Standby, or Unoccupied will cause the control device to remain in that mode until a command of Occ_Null is received.CAUTION: Extreme care must be exercised in using this input.

XL15A 109 155

CmdHvacMode HVAC operating mode network input. (Off, Auto, Heat, Emergency Heat, Fan Only) Unit Vent 108 9CmdManualOcc Manual occupancy command network input. This network input is primarily intended for use with the

command display unit and/or LONSTATION�. A network command to place the control device in manual occupancy mode of Occupied, Standby, or Unoccupied will cause the control device to remain in that mode until a command of Occ_Null is received.CAUTION: Extreme care must be exercised in using this input.

Unit Vent 109 7

CmdSetPtOffst Cannot be referred. It is reserved for network operator interface devices. Unit Vent 105 5Control Loop[1-6] Mode HVAC operating mode network input. (Off, Auto, Heat, Emergency Heat, Fan Only) XL15A 108 51

Table 28. Refer Points from W7761 Remote Input/Output Device to XL15, T7350 and Q7300. (Continued)

SourceRIO

DestinationW7760A Bldg Mgr

DestinationW7760C Plant Mgr

DestinationT7300F / Q7300H Destination T7350

NV Type

Page 66: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 66

Counter Enable/Disable [1-2]

Cannot be referred. No source point available. XL15A 0 214

Counter Enable_[1-2] In Cannot be referred. No source point available. XL15C 0 180Counter Preset Value [1-2]

Cannot be referred. No source point available. XL15A 8 216

Counter Preset_[1-2] In Cannot be referred. No source point available. XL15C 8 182DA Temp In Discharge Air Temperature network input. It can be used for any network temperature to be referred

to XL15C. However, most network temperature inputs are configured through remote point selection.XL15C 105 363

DestBypass Bypass network input. It shares the Bypass operation from the source controller to the destination controller. The destination controller's bypass timer is not activated. The destination controller follows the bypass operation of the source controller based on the bypass arbitration status.

Unit Vent 95 35

DestDlcShed Demand load control network input. Unit Vent 0 36DestCondSensor LonWorks® condensation switch contact network input. CHC 95 54DestCoolTemp Binds any remote chilled ceiling temperature sensor to the source CHC controller. The chilled ceiling

temperature is used for controlling the temperature below dew point while controlling the space temperature. If the chilled water temperature exceeds the actual dew point limit (excluding safety band) for more than 5 minutes, then the controller will close down operation of cooling valve and report ALARM_H2O_TOO_COLD. In this condition, the heat outputs will operate normally.

CHC 105 52

DestEconEnable Economizer enable network input. When active, the economizer is enabled. If bound in Refer Points, a economizer enable digital input sensor wired to the local input will be ignored.

Unit Vent 95 11

DestEmerg Emergency network input. It initiates the smoke detector mode as programmed. Unit Vent, CHC

103 1232

DestFanSpeed Allows a fan speed switch of the master controller to be used for all slaves assigned to the same room. Includes switch (Off, On, Auto) and present value (0-100%) to determine number of stages on. In order to work, the Override Priority in slave controllers must be set to �Network wins�.

CHC 95 8

DestHtSource Cannot be referred. No source point available. Unit Vent 95 41DestHvacMode HVAC operating mode network input. (Off, Auto, Heat, Emergency Heat, Fan Only, Morning Warmup,

Night Purge, Pre-Cool, Cool, Test)CHC 108 10

DestIaqOvrd Indoor air quality network input. When active, the economizer is set to the programed IAQ override position. If bound in Refer Points, a economizer enable digital input sensor wired to the local input will be ignored.

Unit Vent 95 38

DestManCooll Network control of cool output (Range: -164% to 164%) CHC 81 43DestManHeat Network control of heat output (Range: -164% to 164%) CHC 81 42DestManOcc Manual occupancy command network input. This network input is primarily intended for use with the

command display unit and/or LONSTATION�. A network command to place the control device in manual occupancy mode of Occupied, Standby, or Unoccupied will cause the control device to remain in that mode until a command of Occ_Null is received.CAUTION: Extreme care must be exercised in using this input.

CHC 109 9

DestOaEnth Outside air enthalpy network input. If bound in Refer Points, an Enthalpy sensor wired to the local input will be ignored.

Unit Vent 0 39

DestOaHum Outside air humidity network input. If bound in Refer Points, an Air Quality sensor wired to the local input will be ignored.

Unit Vent 81 15

DestOaQuality Outside air quality (CO2 or CO) network input. If bound in Refer Points, an Air Quality sensor wired to the local input will be ignored.

Unit Vent 29 40

DestOaTemp Outside air temperature network input. If bound in Refer Points, a temperature sensor wired to the local input configured as outside air temperature will be ignored.

Unit Vent 105 14

DestOccSensor Occupancy sensor network input. If bound in Refer Points, an Occupancy sensor wired to the local input will be �OR'ed� with the network signal. Occupancy signal must be unoccupied for 300 seconds before the controller returns to unoccupied operation. This permits multiple Occupancy Sensors to be bound to the input and �OR'ed� together.

Unit Vent, CHC

109 835

DestReheat It is used for manually controlling the reheat relay output. It requires that the reheat be configured to be external, which makes this point essentially a �Free� point.

CHC 95 49

Table 29. Network Input Variable Description. (Continued)

NV Input Address Comment ControllerNV

TypeNV

Index

Page 67: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

67 74-3679�1

DestRmTemp Space temperature network input. If bound in Refer Points, a temperature sensor wired to the local input configured as space temperature will be ignored.

Unit Vent, CHC

105 3

DestRmRelHum It provides CHC controller with an external humidity sensor value and if valid, the input network value will have priority over locally wired humidity sensor values.DestRmRelHum value is �INVALID� after power up or application reset until it receives an update within the specified heartbeat time.

CHC 81 53

DestRmTempSpt Space temperature setpoint network input. If bound in Refer Points, a setpoint device wired to the local input will be ignored. The controller setpoints are calculated from the input value received. OccHeatSetpoint = DestRmTempSpt - 1/2 DeadBand. OccCoolSetpoint = DestRmTempSpt + 1/2 DeadBand. DeadBand = ProgrammedOccCoolSetpoint - ProgrammedOccHeatSetpoint.NOTE: There might be slight discrepancy between the source and destination controllers if Effec-

tive Setpoint is the source. DestRmTempSpt not effective in unoccupied mode.

Unit Vent, CHC

105 4

DestSourceTemp Supply water temperature network input. If the water temperature is lower than the programmed setpoint the unit is supplied with heating energy. If the water temperature is greater than the programmed setpoint the unit is supplied with cooling energy.

Unit Vent 105 13

DestSptOffset Cannot be referred. Reserved for network operator interfaces. CHC 105 11DestWindow Window network input. Same as EnergyHoldOff input. If bound, the input must remain active for 300

seconds to change the controller to the frost protection mode. This permits multiple source controllers to be bound to the input and "OR'ed" together.

CHC 95 17

Digital Input [1-8] Input network variables directly sent to the application. Default value is 0;0.NOTE: For more information, refer to Chapter 6.5 Process Data in ud887a.pdf (NX VFD user

manual).

NX VFD 95 13-20

DLC Shed In Demand load control network input. (�0� or �1 or other values�). �0� implies that there is no request for load shedding (mains power up or failure detect value) and �1 or other values� implies that there is a request for load shedding.

CVAHU, Q7300HT7350

0 302133

Dlc Shed_[1-18] In Demand load control network input. [1-10] represent Control loops 1-10 and [11-18] represent StartStop Loops 1-8.

XL15C 0 54

Drive Speed Setpt Scaling

Input network variable that provides scaling for Drive Speed Setpoint. Negative values indicate a reverse motor direction. For example, if Drive Speed Setpoint value is �50%� and Drive Speed Setpt Scaling value is �-150%�, then the actual speed setpoint is �-75%�, or �0.75� times the nominal speed in reverse direction. The valid range is �-163,840%� to �163,830�.

NX VFD 81 10

Drive Start Stop Setpoint

Input network variable that provides control and a low resolution speed setpoint. The following are the states, values received, and commands executed:� �0� (state) -�NA� (value), �Stop�(command)� �1� (state), �0� (value), �0%� (command)� �1� (state), �1 to 200� (value), �0.5 to 100%� (command)� �1� (state), �201 to 255� (value), �100.0%� (command)� �0xFF (state), �NA� (value), �Auto� (command)

NX VFD 95 1

Duct Static Pressure In Cannot be referred. No source point available. XL15C 113 371Econ Enable In Economizer enable network input. When active, the economizer is enabled. If bound in Refer Points,

a economizer enable digital input sensor wired to the local input will be ignored.XL15C 95 365

Econ In Economizer enable network input. When active, the economizer is enabled. If bound in Refer Points, a economizer enable digital input sensor wired to the local input will be ignored.

CVAHU 95 41

Emergency Command Emergency network input. It initiates the smoke detector mode as programmed. (Normal, Pressurize, Depressurize, Purge, Shutdown, Null)

FCU 103 33

Emergency Override In Emergency network input. It initiates the smoke detector mode as programmed. XL15C 103 369EmergIn Emergency network input. It initiates the smoke detector mode as programmed. CVAHU 103 14External cool output control

Network control of cool output (-164% to 164%) FCUHYD

81 44

External heat output control

Network control of heat output (-164% to 164%) FCUHYD

81 43

Factory Test In Indicates the command or test that is requested by the controller. CD 0 12File Request In One of the Echelon® file transfer input network variables, the operations of which are governed by

LonMark® and E-Bus mechanisms.CD 0 7

Table 29. Network Input Variable Description. (Continued)

NV Input Address Comment ControllerNV

TypeNV

Index

Page 68: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 68

File Position In One of the Echelon® file transfer input network variables, the operations of which are governed by LonMark® and E-Bus mechanisms.

CD 0 6

File Position Out One of the Echelon® file transfer input network variables, the operations of which are governed by LonMark® and E-Bus mechanisms.

CD 0 9

File Status In One of the Echelon® file transfer input network variables, the operations of which are governed by LonMark® and E-Bus mechanisms.

CD 0 8

File Status Out One of the Echelon® file transfer network input variables, the operations of which are governed by LonMark® and E-Bus mechanisms.

CD 0 5

Fan speed command Allows a fan speed switch of the master controller to be used for all slaves assigned to the same room. Includes switch (Off, On, Auto) and present value (0-100%) to determine number of stages on. In order to work, Override Priority in slave controllers must be set to �Network wins�.

FCU 95 8

FanOnAuto In Input network variable that reflects the current state of the thermostat fan switch mode when polled by a LonWorks® tool. It is automatically updated whenever the fan switch mode is changed by either the PDA or the thermostat keyboard; the fan switch mode is also automatically updated when the FanOnAuto In is updated across the network. (�ON� (AUTO), and �OFF� (fan continuously on).

Q7300HT7350

95 2231

FanSpeedIn Cannot be referred. No source point available. Unit Vent 95 10Free1 In Digital output network commandable point. Source controller network output must be of the NV type

95CVAHU, Unit Vent, VAV II

95 439537

Free2 In Digital output network commandable point. Source controller network output must be of the NV type 96

CVAHU 95 44

IAQ Override In Indoor air quality input network variable. When active, the economizer is set to the programed IAQ override position. If bound in Refer Points, a economizer enable digital input sensor wired to the local input will be ignored.

CVAHU 95 42

KW Cascade In If bound the input value is summed with local pulse meter value if available to set KW Cascade Out. XL15A, XL15C

28 288289

Load shed control Demand load control input network variable. FCUHYD

0 35

ManOccIn Manual occupancy command input network variable. This network input is primarily intended for use with the command display unit and/or LONSTATION�. A network command to place the control device in manual occupancy mode of Occupied, Standby, or Unoccupied will cause the control device to remain in that mode until a command of Occ_Null is received.CAUTION: Extreme care must be exercised in using this input.

CVAHU 109 4

Manual mode Cannot be referred. No source point directly available. FCUHYD

0 32

Manual network occupancy

Manual occupancy command input network variable. This network input is primarily intended for use with the command display unit and/or LONSTATION�. A network command to place the control device in manual occupancy mode of Occupied, Standby, or Unoccupied will cause the control device to remain in that mode until a command of Occ_Null is received. CAUTION: Extreme care must be exercised in using this input.

FCUHYD

109 9

Manual Occupancy_[1-18] In

Manual occupancy command input network variable. This network input is primarily intended for use with the command display unit and/or LONSTATION�. A network command to place the control device in manual occupancy mode of Occupied, Standby, or Unoccupied will cause the control device to remain in that mode until a command of Occ_Null is received. [1-10] represent Control loops 1-10 respectively and [11-18] represent StartStop Loops 1-8 respectively.CAUTION: Extreme care must be exercised in using this input.

XL15C 109 162

nviApplicMode HVAC operating mode input network variable. (Off, Auto, Heat, Emergency Heat, Fan Only) VAV II 108 7nviBypass Bypass network input network variable. It shares the Bypass operation from the source controller to

the destination controller. The destination controller's bypass timer is not activated. The destination controller follows the bypass operation of the source controller based on the bypass arbitration status.

VAV II 95 27

nviDlcShed Demand load control input network variable. VAV II 0 25nviDuctInTemp No source point directly available. Source must be configured in XL15 VAV II 105 14nviEmergCmd Emergency input network variable. Initiates the smoke detector mode as programmed. VAV II 103 11

Table 29. Network Input Variable Description. (Continued)

NV Input Address Comment ControllerNV

TypeNV

Index

Page 69: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

69 74-3679�1

nviEnergyHoldOff EnergyHoldOff input network variable. Same as Window input. If bound the input must remain active for 300 seconds to change the controller to the frost protection mode. This permits multiple source controllers to be bound to the input and �OR'ed� together.

VAV II 95 12

nviFlowOffset Cannot be referred. No source point directly available. VAV II 0 36nviFlowTrack Shares flow tracking data from the source VAV II controller to the destination VAV II controller. VAV II 15 35nviHeaterOverid Input network variable that is used for manual control of reheat and peripheral reheat values. (Null or

Off - don�t care, On - 0 and On - Greater than 0).VAV II 95 13

nviManOcc Manual occupancy command input network variable. This network input is primarily intended for use with the command display unit and/or LONSTATION�. A network command to place the control device in manual occupancy mode of Occupied, Standby, or Unoccupied will cause the control device to remain in that mode until a command of Occ_Null is received.CAUTION: Extreme care must be exercised in using this input.

VAV II 109 10

nviManValue Cannot be referred. No source point directly available. Unit Vent 0 27nviOccCmd Occupancy sensor input network variable. If bound in Refer Points, an Occupancy sensor wired to the

local input will be �OR'ed� with the network signal. Occupancy signal must be unoccupied for 300 seconds before the controller will return to unoccupied operation.

VAV II 109 28

nviSetPoint Space temperature setpoint input network variable. If bound in Refer Points, a setpoint device wired to the local input will be ignored. Notes - 1) The controller setpoints are calculated from the input value. OccHeatSetpoint = nviSetPoint - 1/2 DeadBand. OccCoolSetpoint = nviSetPoint + 1/2 DeadBand. DeadBand = ProgrammedOccCoolSetpoint - ProgrammedOccHeatSetpoint. 2) nviSetPoint not effective in unoccupied mode. 3) If Effective Setpoint is the source there is likely to be slight discrepancy between the source and destination controllers due to the above calculation.

VAV II 105 4

nviSetPtOffset Cannot be referred. Reserved for network operator interfaces. VAV II 105 9nviShare Shares the temperature control output from the source VAV II controller to the air flow control of the

destination VAV II controller.VAV II 0 38

nviSpaceTemp Space temperature input network variable. If bound in Refer Points, a temperature sensor wired to the local input configured as space temperature will be ignored.

VAV II 105 3

nviTodEvent Network time of day scheduling. VAV II 128 26OccSensorIn Occupancy sensor input network variable. If bound in Refer Points, an Occupancy sensor wired to the

local input will be �OR'ed� with the network signal. Occupancy signal must be unoccupied for 300 seconds before the controller will return to unoccupied operation.

CVAHU 109 26

Occupancy Cmd In Occupancy sensor input network variable. If bound in Refer Points, an Occupancy sensor wired to the local input will be �OR'ed� with the network signal. Occupancy signal must be unoccupied for 300 seconds before the controller will return to unoccupied operation.

Q7300H 109 12

Occupancy In Occupancy sensor or manual occupancy command input network variable. Intended for use with Logic Loops to decode the Occupancy status.

XL15C 109 367

Occupancy Schedule In Time of Day Scheduling network input. Q7300HT7350

128 2024

Occupancy Sensor In Occupancy sensor input from a device or node on the network. (�0� - �OC_OCCUPIED�, �1� - �OC_UNOCCUPIED�, and �-1� - �OC_NUL not connected� (mains power up and fail detect value), and �Others� - �same as OC_NUL�).NOTE: If occupancy sensor input value is valid, it is used as the occupancy sensor even if there is

no sensor currently configured.

T7350 109 26

Od Hum In Outside air humidity input network variable. If bound in Refer Points, a humidity sensor wired to the local input will be ignored.

XL15C 81 42

Od Temp In Outside air temperature input network variable. If bound in Refer Points, a temperature sensor wired to the local input configured as outside air temperature will be ignored.

XL15C 105 40

OdHumIn Outside air humidity input network variable. If bound in Refer Points, a humidity sensor wired to the local input will be ignored.

CVAHU 81 12

OdTempIn Outside air temperature input network variable. If bound in Refer Points, a temperature sensor wired to the local input configured as outside air temperature will be ignored.

CVAHU 105 10

Outdoor Air Humidity In Outside air humidity input network variable. If bound in Refer Points, a humidity sensor wired to the local input will be ignored.

XL15A 81 23

Table 29. Network Input Variable Description. (Continued)

NV Input Address Comment ControllerNV

TypeNV

Index

Page 70: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 70

Outdoor Air Temperature In

Outside air temperature input network variable. If bound in Refer Points, a temperature sensor wired to the local input configured as outside air temperature will be ignored.

XL15A 105 21

Outdoor Enthalpy In Outside air enthalpy network input. If bound in Refer Points, an Enthalpy sensor wired to the local input will be ignored.

CVAHU 0 40

Outdoor Temperature In Outside temperature network input. If bound, a temperature sensor wired to the local input configured as outside temperature will be ignored.

T7350 105 28

Process Data Input [1-8] Input network variables. They are directly sent to NX VFD and used with all-in-one applications. Valid range is �0� to �65535� (-163,840 to 163,835). For the following Basic, Standard, Local/Remote, and Multi-step applications, the PD1-PD8 values are not used. For all Multipurpose Control Applications, the following are the data and values used: � �Process Data IN1� - �Torque Reference�� �Process Data IN2� - �Free Analog Input�� �Process Data IN3� - �Adjust Input�� �PD3-PD8� - �Not Used�. NOTE: For more information, refer to Chapter 6.5 Process Data in ud887a.pdf (NX VFD user

manual).

NX VFD 81 2-9

RA Relative Humidity In Return air humidity network input. If bound in Refer Points, a humidity sensor wired to the local input will be ignored.

XL15C 81 373

RA Temp In No source point available. Cannot be referred. XL15C 105 372Remote Digital In [1-12] Cannot be referred. Reserved for RIO. XL15A 95 101Remote Output [1-8] Cannot be referred. Automatically bound to XL15C when associated in XL15 configuration. RIO 81 3Remote Sensor_[1-12] In

Cannot be referred. Reserved for RIO. XL15C 95 114

RIO Analog Inputs_[1-3] Cannot be referred. These points are automatically bound by LONSPEC� when the RIO is associated to the XL15 controller during the XL15 configuration.

XL15A, XL15C

0 286

Room Temperature Setpoint

Space temperature setpoint network input. If bound in Refer Points, a setpoint device wired to the local input will be ignored. Notes - 1) The controller setpoints are calculated from the input value. OccHeatSetpoint = Room Temperature Setpoint - 1/2 DeadBand. OccCoolSetpoint = Room Temperature Setpoint + 1/2 DeadBand. DeadBand = ProgrammedOccCoolSetpoint - ProgrammedOccHeatSetpoint. 2) Room Temperature Setpoint not effective in unoccupied mode. 3) If Effective Setpoint is the source there is likely to be slight discrepancy between the source and destination controllers because of the above calculation.

Unit VentHYDFCU

105 4

Runtime Enable/Disable [1-15]

Cannot be referred. No source point available. XL15A 0 169

Runtime Value Preset [1-15]

Cannot be referred. No source point available. XL15A 0 184

SchedOcc Time of day scheduling network input. Unit Vent 128 6Sensor Occupancy_[1-18] In

Occupancy sensor network input. If bound in Refer Points, an Occupancy sensor wired to the local input will be �OR'ed� with the network signal. Occupancy signal must be unoccupied for 300 seconds before the controller will return to unoccupied operation. [1-10] represent Control loops 1-10 respectively and [11-18] represent StartStop Loops 1-8 respectively.

XL15C 109 291

SensorOcc Occupancy sensor network input. If bound in Refer Points, an Occupancy sensor wired to the local input will be �OR'ed� with the network signal. Occupancy signal must be unoccupied for 300 seconds before the controller will return to unoccupied operation.

FCUHYD

109 36

SetpointIn Space temperature setpoint network input. If bound in Refer Points, a setpoint device wired to the local input will be ignored. Notes - 1) The controller setpoints are calculated from the input value. OccHeatSetpoint = Setpoint In - 1/2 DeadBand. OccCoolSetpoint = Setpoint In + 1/2 DeadBand. DeadBand = ProgrammedOccCoolSetpoint - ProgrammedOccHeatSetpoint. 2) Setpoint In effective only in occupied mode. 3) If Effective Setpoint is the source there is likely to be slight discrepancy between the source and destination controllers because of the above calculation.

CVAHU, Q7300H

105 56

Table 29. Network Input Variable Description. (Continued)

NV Input Address Comment ControllerNV

TypeNV

Index

Page 71: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

71 74-3679�1

Setpoint In Space temperature setpoint input network variable. Following validations are considered for calculating the controller setpoints from the input value:� Deadband_occupied = occupied_cool - occupied_heat� Deadband_standby = standby_cool - standby_heat� Effective_occupied_cool = nviSetpoint + 0.5 (deadband_ occupied)� Effective_occupied_heat = nviSetpoint - 0.5 (deadband_ occupied)� Effective_standby_cool = nviSetpoint + 0.5 (deadband_standby)� Effective_standby_heat = nviSetpoint - 0.5 (deadband_ standby)

T7350 105 23

Setpoint Offset Cannot be referred. Reserved for network operator interfaces. FCUHYD

105 11

Setpoint Offset In Cannot be referred. Reserved for network operator interfaces. Q7300H 105 14SetPtOffsetIn Cannot be referred. Reserved for network operator interfaces. CVAHU 105 6Space Humidity In Space humidity input network variable. If bound in Refere Points, the humidity sensor wired or the

local input configured as humidity sensor will be ignored. NOTE: If Space Humidity In value is not invalid (163.83), then it is used as the space relative

humidity even if another sensor or no sensor is configured.

T7350 81 29

Space Temperature In Space Temperature Network Input. If bound in Refer Points, a temperature sensor wired to the local input configured as space temperature will be ignored.

Q7300HT7350

105 1122

Space Temperature Input

Space Temperature Network Input. If bound in Refer Points, a temperature sensor wired to the local input configured as space temperature will be ignored.

FCUHYD

105 3

SpaceTempIn Space Temperature network input. If bound in Refer Points, a temperature sensor wired to the local input configured as space temperature will be ignored.

CVAHU 105 8

StartStop [1-8] Bypass In

Bypass network input. Shares the Bypass operation from the source controller to the destination controller. The destination controller's bypass timer is not activated. The destination controller follows the bypass operation of the source controller based on the bypass arbitration status. [1-10] represent Control loops 1-10 respectively and [11-18] represent StartStop Loops 1-8 respectively.

XL15A 95 133

StartStop [1-8] ManOcc In

Manual Occupancy Command network input. This network input is primarily intended for use with the command display unit and/or LONSTATION�. A network command to place the control device in manual occupancy mode of Occupied, Standby, or Unoccupied will cause the control device to remain in that mode until a command of Occ_Null is received.CAUTION: Extreme care must be exercised in using this input.

XL15A 109 161

StartStop [1-8] Occupancy In

Occupancy Sensor network input. If bound in Refer Points, an Occupancy sensor wired to the local input will be �OR'ed� with the network signal. Occupancy signal must be unoccupied for 300 seconds before the controller will return to unoccupied operation.

XL15A 109 298

Time Clock In Time Clock network input. If bound in Refer Points, a time clock wired to the local input will be ignored.

CVAHU 95 58

Time In Input network variable that gets the current date and time (current year, month, day, hour, minutes, and seconds). The following are the input values:� Year: �0� - �Not specified� (power up value), �Valid Range� - �2000 through 2175�, and �-1� - �Invalid

Value�.� Month: �0� - �Invalid Month� (not programmed) (power up value) and �1� - �12� (�January� -

�December�). � Day: �0� - �Not specified� (power up value) and �1-31� - �Valid range�.� Current time: Hour of day: �0� - Midnight� (power up value), �12� - �noon�, and �23� - �11 PM�. Minute

of hour: �0� - �First minute of hour� (power up value) and �59� - �last minute of hour�. Second of minute: �0� - �First second of minute� (power up value) and �59� - �last second of hour�.

As long as the Time In network variable is bound and the values are received every 300 seconds, the automatic daylight savings time feature in the thermostat is turned off.

T7350 84 3

Time of Day Event_[1-18] In

Time of day scheduling input network variable. [1-10] represent Control loops 1-10 respectively and [11-18] represent StartStop Loops 1-8 respectively.

XL15C 128 72

Time Of Day In Time of day scheduling input network variable. CVAHU FCUCHC

128 313433

Total KW In If the Total KW In is bound then the Total KW Out value is equal to the Total KW In otherwise it is equal to KW Cascade Out.

XL15A 28 290

Table 29. Network Input Variable Description. (Continued)

NV Input Address Comment ControllerNV

TypeNV

Index

Page 72: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 72

UnitStatus Supports LonMark® communication requirements for 3rd party integration. Unit Vent 112 18Window Contact In Window contact input network variable. Same as EnergyHoldOff input in VAV II. If bound the input

must remain active for 300 seconds to change the controller to the frost protection mode. This permits multiple source controllers to be bound to the input and �OR'ed� together.

CVAHU 95 28

Window Sensor Sharing Window contact input network variable. Same as EnergyHoldOff input in VAV II. If bound the input must remain active for 300 seconds to change the controller to the frost protection mode. This permits multiple source controllers to be bound to the input and �OR'ed� together.

FCUHYD

95 17

WSHP Enable Out Cannot be referred. No source point available. CVAHU 95 57Table 30. Network Output Variable Description.

NV Output Address Comments ControllerNV

TypeNV

IndexActive Fault Code Output network variable is EXCEL VRL CX's active fault code. It that shares the drive active fault

code with other nodes or devices on the network (�0� - frequency converter is fault free). NOTE: Refer to the Fault Code list in Vacon NX Frequency Converter user�s manual for details

on fault identification.

NX VFDVFD

8 375

Actual Motor Power Output network variable is EXCEL VRL CX's output power in percent of its nominal power. Its transmission across the network is controlled by the corresponding configuration variable.

VFD 81 2

Active Setpoint Output network variable that shares the control algorithm�s active setpoint. The value is based on the occupancy setpoints and recovery ramping. It is transmitted immediately when its value changes (> 0.5 delta°C). NOTE: nvoActiveSetPt is limited to the range +10°C to +35°C.

FCUHYD

105 15

AI Sensor [0-7] Out Engineering unit sensor image that represents all the onboard physical analog input sensors on EXCEL 15C/D nodes. It is a polled network variable that is sent only when requested and is initially set to zero on power up.

XL15C 0 18-25

Alarm Out Output network variable that uses the acknowledged service to report a detected alarm condition to a supervisory node via the LonWorks® network. Each such output variable has a domain subnet and node address; these belong to the domain to which the output variable is bound. The domain index is �0� if the output variable is not bound to the domain. Each alarm condition is issued only once. Only one unacknowledged alarm condition is remembered for each alarm type. Alarm reporting can be enabled or disabled.

T7350 0 13

Appl Mode Out HVAC operating mode output network variable whose value can be driven by any of the XL15C algorithm�s analog output. It is initialized to HVAC_NUL on power up. NOTE: Please ensure that the analog output assumes only the values desired for the

application.

XL15C 108 362

Application Mode Out HVAC operating mode output network variable. Reports the current system mode of the thermostat and co-ordinates the operating mode with other nodes. The mode is determined either in Q7300H or in the thermostat, whichever was changed last. It reflects the following operating modes: Auto, Heat, Cool, FanOnly, EmergencyHeat, and Off.

Q7300HT7350

108 2438

Application Mode Output HVAC operating mode output network variable. It co-ordinates between the respective master and slave controllers and reflects the current heat/cool modes depending on the supplied energy levels. The value is refreshed immediately when the mode changes. The default value is HVAC_OFF. The value remains unchanged until unless updated by the control algorithm.

FCUHYD

108 52

Bypass Out Bypass output network variable. Indicates to other nodes that a timed bypass function has occurred. It depends on the effective occupancy state of the current device.

CVAHUQ7300HT7350

95 353143

Bypass [1-18] Out The effective occupancy state of one object is shared with another object using Bypass In and Bypass Out network variables. Every flexible and start-stop loop has these variables (index 0 is flexible loop 1, index 9 is flexible loop 10, index 10 is start stop loop 1 and index 17 is start stop loop 8).

XL15C 95 144-161

Cloop [1-6] Bypass Out Bypass output network variable. Gives the bypass operation information to the destination controller. The destination controller's bypass timer is not activated and the controller in turn follows the bypass operation of the source controller based on the bypass arbitration status.

XL15A 95 141-146

Table 29. Network Input Variable Description. (Continued)

NV Input Address Comment ControllerNV

TypeNV

Index

Page 73: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

73 74-3679�1

Counter Value [1-2] It tracks the number of times a digital input transitions from �OFF� state to �ON� state when nviCounterEnable is TRUE. The value must be within �0� to �65535� counts with a resolution of one count. When the count exceeds �65535�, the counter is reset to zero counts.

XL15A 8 218 &219

CO2 Sensor There are six output network variables corresponding to the analog input channels, of which four are resistive type (AI1 - AI4) and the remaining two (AI5 - AI6) are voltage or current. CO2 sensor is one of the sensors that can be associated with AI5 and AI6 channels. This output variable reports the AI5 or AI6 value on which the CO2 sensor is configured.

RIO 29 23

Cool Control Output Output network variable for a cool actuator node or a slave FCU/HYD controller. The output value is limited to a range of 0% to 100%. It is transmitted immediately when its value changes (>= 1%) and is periodically transmitted based on the Send Heartbeat output. It can also be used as a heartbeat at the receiving node.

FCUHYD

81 6

Cool Output Reports the current percentage of cooling stages turned on in the Cool mode. Cool Output is considered invalid if there is no cooling configured.

Q7300H 81 8

Cool UTML Out(*UTML-Uable to Meet Load)

SNVT output variable and is initialized to 0, SW_OFF on power up. It is intended that Cool UTML Out be assigned to digital output(s) such as a logic loop. The logic loop(s) would determine the state of the output variable. The EXCEL 15C/D converts the digital value to SNVT_switch.

XL15C 95 374

Counter [1-2] Out It tracks the number of times a local digital input transitions from OFF state to ON state when nviCounterEnable is Enabled (True).

XL15C 8 184&185

Current Sensor There are six output network variables corresponding to the analog input channels, of which four are resistive type (AI1 - AI4) and the remaining two (AI5 and AI6) are voltage or current. Current Sensor is one of the sensors that is associated with A15 and A16 channels.

RIO 2 25

DA Temp Out Discharge air temperature output network variable. Shares the local discharge temperature sensor value with the corresponding input network variable on another node. If bound, it is periodically sent on the network.

XL15C 105 364

Dig Cmd Free [0-23] It provides a command output that allows control loops onboard the controller to command outputs of type SNVT_switch that do not physically reside on the XL 15A controller.

XL15A 95 360-383

Digital Cmd Free [1-24] Out

It provides a command output that allows control loops onboard the controller to command outputs of type SNVT_switch that do not physically reside on the XL15C controller.

XL15C 95 329-352

Digital Input State Indicates the binary states of the XL10 FCU controller's digital input, which can be configured to support a window contact, an occupancy sensor, an air flow contact, or a heat/cool changeover contact. It is usually bound to the digital network input variable of a third party node.Following are the supported SNVT modes: Contact Closed, Contact Open, and Contact not Assigned.

FCU 95 49

Digital Output [1-8] Output network variables directly sent from NX VFD to the appropriate input network variables on other nodes or devices on the network.

NOTE: For more information, refer to Chapter 6.5 Process data in ud887a.pdf (NX VFD user manual).

NX VFD 95 38-45

Discharge Temperature Out

Output network variable that displays the current discharge air temperature value. T7350 105 39

DLC Output Load [1-20] Load Shed Command

Demand Load Control Network Output. It is the output from the energy management system. There can be up to 20 external individually energy managed loads/nodes. At any point of time, DLC Output Load can either be true/shed or false/noshed.

XL15A 0 31-50

Drive Current Output network variable that provides the drive output current in amperes. NX VFD 1 32Drive Power Output network variable that provides the drive output power in kW. NX VFD 28 33Drive Run Hours Output network variable that provides the drive resettable operation time counter for the motor in

running hours. The maximum value is �65535� h. If the value goes beyond �65535� h, the network variable stays at its maximum. In such cases the real value can be seen on Vacon NX�s operating keypad.

NX VFD 124 34

Drive Speed Feedback Output network variable that provides the speed of the drive as a percentage of the nominal speed. NX VFD 81 23Drive Speed Feedback It provides the speed of the drive as a percentage of the nominal speed. VFD 81 0Econ Out Economizer enable output network variable that shares the outdoor air sensor value with other

nodes on the network. The air sensor validates if the outdoor air can be used for free cooling of the space. It has the following valid states: ON (0), OFF (100), and NUL (0).

CVAHU 95 54

Table 30. Network Output Variable Description. (Continued)

NV Output Address Comments ControllerNV

TypeNV

Index

Page 74: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 74

Econ Enable Out Economizer enable output network variable whose value can be assigned to any algorithm's (logic loops, control loops) digital output. It is initialized to 0, SW_OFF on power up. The loop can be configured to decide EconEnable value.

XL15C 95 366

Effective Occ Out Output network variable that reflects the effective occupancy mode of the controller. In a remote schedule mode, its value is derived from DestManOcc, DestBypass, StatusLocalOvrRide, and DestSchedOcc and in a local mode, its value is derived from SrcSchedOcc0. The following are the valid enumerated points: Occ, UnOcc, and Bypass.

Q7300H 109 30

Effective Occ Out Output network variable that reflects the scheduled occupancy mode of the device. (�0� -�OC_OCCUPIED� (power up value), �1� - �OC_UNOCCUPIED�, �2� - �OC_BYPASS�, �3� - �OC_STANDBY�, and �-1� - �OC_NUL�).

T7350 109 37

Effective Occupancy State

Output network variable that reflects the effective occupancy mode of the controller. The value is derived from nviTodEvent, occupancy sensor, override button, and nviManOccCmd.

FCUHYD

109 16

EffectSetPtOut Output network variable that provides the current actual space temperature that the controller is trying to maintain in the conditioned space. The current setpoint is derived from various setpoints, operating modes, and network variable inputs. The network variable is updated periodically and on significant change in the value, which is plus or minus 0.07 degrees C.

VAVIICVAHU

105 157

Effective Stpt Out Output network variable that provides the current space temperature setpoint that the controller is trying to maintain in the conditioned space. The current setpoint is derived from various setpoints, operating modes, and network variable inputs. The network variable is updated periodically and on significant change in the value, which is �+/- 0.07� degrees C. (Different states: Heat, Cool, and Not Heat or Cool).NOTE: If the sub-base fails to receive information from the thermostat cover assembly

periodically, the Effective Stpt Out is set to its power up default values.Generally the default values indicate device that the source of information has failed.

Q7300HUnit VentT7350

105 1736

EmergOut Emergency output network variable that reflects the state of the locally wired smoke detector. The two valid enumerated values are: Emerg_Purge and Emerg_Normal.

CVAHU 103 32

Factory Test Out Output network variable that gives a status update on the progress and the outcome of a particular factory test.

CD 0 13

Fan Output Output network variable that indicates if a fan is on/off. Usually used for controlling a remote fan actuator.

Q7300H 95 16

Fan Speed Output Output network variable that is typically bound to an external fan node and is transmitted immediately when its value changes from one fan speed to another. It gives the current fan speed output of the FCU.

FCU 95 7

Fan Speed Switch Output network variable that allows the master FCU controller�s fan speed switch to be used for all slave XL10 FCUs assigned to the same room. The following are the different fan speed switch positions used: OFF, Fan Speed1, Fan Speed2, Fan Speed3, and Fan AUTO.

FCU 95 46

File Request Out One of the Echelon file transfer output network variables, the operations of which are governed by LonMark® and E-Bus mechanisms.

CD 0 10

Heat Control Output Output network variable for a heat actuator node or a slave FCU controller. The output value is limited to a range of 0% to 100%. It is transmitted immediately when its value changes (>= 1%) and transmitted periodically based on the Send Heartbeat output. It can also be used as heartbeat at the receiving node.

FCUHYD

81 5

Heat Output Output network variable that reports the current percentage of heating stages turned on in the Heat mode. The Heat Output is considered invalid if there is no heating configured.

Q7300H 81 7

Heat UTML Output(*UTML-Unable to Meet Load)

SNVT output variable that is initialized to �0�, �SW_OFF� on power up. It is intended that Heat UTML Output be assigned to digital output(s) such as a logic loop or control loop. The logic loop(s) would determine the state of the output variable. The EXCEL 15C/D converts the digital value to SNVT_switch.

XL15C 95 375

Humidity Sensor [1-2] There are six output network variables corresponding to the analog input channels, of which four are resistive type (AI1 thru AI4) and the remaining two (AI5 and AI6) are voltage or current. Humidity sensor is one of the sensors that is associated with A15 and A16 channels.

RIO 81 19 & 20

IAQ Override Out Indoor air quality override output network variable that allows an indoor air quality sensor to be shared with other nodes and is typically bound to the corresponding input variable on other nodes. This variable will be ON if the local CO2 Sensor value exceeds the setpoint or if the local IAQ Override digital input is ON.

CVAHU 95 55

Table 30. Network Output Variable Description. (Continued)

NV Output Address Comments ControllerNV

TypeNV

Index

Page 75: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

75 74-3679�1

In Use Out The value is used by Command Display controller while modifying configuration files on other nodes. The controller executes a process by which this output variable is bound to the corresponding input variable.

CD 0 14

KW Cascade Out It is of type SNVT_power_kilo. If nviCascadeIn is bound then it is summed with any configured onboard physical pulsemeter inputs and the resultant is output on nvoCascadeOut. If nviCascadeIn is NOT bound then any configured onboard physical pulsemeter inputs are summed without nviCascadeIn and that resultant is output on nvoCascadeOut. The reset value is zero.

XL 15A XL15C

28 289290

KWH Counter Output network variable that provides the drive resettable energy consumption counter. The maximum value is �65535� kWh. If it goes beyond �65535� kwh, then the output network variable stays at its maximum. In such cases the real value can be seen on Vacon NX�s operating keypad.

NX VFD 13 36

Monitor SW Out Allows the controller�s monitor switch to be shared with another node on the network. Following are the output values: SW_OFF, SW_On, and SW_NULL.

CVAHU 95 56

nvoAlarm Reports the latest changed low battery alarm condition, which is detected in a sensor node to the supervisory node over the LonWorks® network. There are 24 types of alarms for every node and nvoAlarm can hold only one unacknowledged alarm condition for each alarm type.

Q7790A 0 59

nvoBoxFlow Reports the air flow measured at the node. It reports zero if the actual air flow velocity is less than 50 ft/sec. It is set to invalid status if a flow sensor error is detected.

VAVII 15 17

nvoBypass Bypass output network variable that indicates the current occupancy state of the node for bypassing the schedule. It allows a wall module at one node to override the scheduled occupancy of another node. The following are the bypass states and their corresponding values: �ON (0%)� and �OFF(100%)�.

VAVII 95 33

nvoEnergyHoldOff EnergyHoldOff output network variable that allows the hard wired window sensor to be used by other nodes on the network. Values can be �OFF (0%)� when window is closed, �ON (100%)� when window is open, or �NULL� when window sensor is not configured.

VAVII 95 19

nvoFlowControlPt SGPU output network variable that reports the current air flow setpoint with a 5L/second significant update difference.

VAVII 15 16

nvoFlowTrack FlowTrackOut (nvoFlowTrack) reports the air flow measured at the node plus the value received from the corresponding input variable (FlowTrackIn) on another node. The FlowTrackOut is set to invalid if a flow sensor error is detected or the Pressure Dependent is True or the value received is invalid.

VAVII 15 40

nvoMonSW Output network variable that allows the controller�s monitor switch to be shared with another node on the network. Following are the output values: SW_OFF, SW_On, and SW_NULL.

VAVII 95 45

nvoOccManCmd[0-13] SNVT_occupancy type output network variable with a default value �OCC_NULL�. It transmits the BYPASS value when the override button is pressed on the RF wall module node and transmits the NULL value when the Wink button is pressed.

Q7790A 109 3,6,9,12...42

nvoOccup[0-13] SNVT_occupancy type output variable on a RF Occupancy node. It reflects the last received state of the occupancy sensor on the RF Occupancy node. If the device receives the previously transmitted value again from the RF node, then the device waits for the periodic transmission timer to expire before transmitting the received value. If the value is different from what was last transmitted, then device will transmit the new value immediately and reset the periodic transmission timer for that variable. NOTE: Occupancy sensors will be filtered by Honeywell's vendor code (0x101) for traffic rea-

sons. The default value will be OCC_NULL until a transmission is received from RF node or an application reset is generated.

Q7790A 109 45-58

nvoSensorOcc Output network variable that reflects the current state of the hard wired occupancy sensor. (Valid enumerated states: �Occ�, �UnOcc�, and �Null�).

VAVII 109 32

nvoSetpoint[0-13] Output network variable that reflects the last received state of the setpoint knob on the RF Wall Module node. The default value will be INVALID_VALUE until a transmission is received from a RF node or an application reset is generated. The value stored in nvoSetpoint is adjusted and sent out on the network only when the incoming value from the setpoint knob on the RF Wall Module node is different from the previously transmitted value by 0.125 C or greater.

Q7790A 105 5,8,11...44

nvoShare A sending node with a wall module can be used to control the damper and ReHeat of one or more other receiving nodes that do not have a wall module. The sending nodes must have the nvoShare bound to the nviShare of a receiving node. In other cases, the master node (controlling the damper for cool air) controls the satellite node via nvoShare. The nvoShare of the master node must be connected to the nviShare of the satellite node.

VAVII 0 39

Table 30. Network Output Variable Description. (Continued)

NV Output Address Comments ControllerNV

TypeNV

Index

Page 76: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 76

nvoSpaceTemp[0-13] Wall Module SNVT_temp_p type output network variable that reflects the last received state of the space temperature sensor on the RF Wall Module node.

Q7790A 105 4,7,10...43

nvoStatus Output network variable that sends the current status of the controller when requested by another node on the network.

VAVII 93 1

Occupancy Out Occupancy sensor or manual occupancy command output network variable. Intended for use with Logic Loops to decide the Occupancy status. It will be in Occupancy NULL state on power up. The logic loop must be configured to report proper values for occupancy.

XL15C 109 368

Occupancy Sensor [1-2] Output network variable that provides the current state of a local hard-wired occupancy sensor. (Valid enumerated states: �OC_OCCUPIED�, �OC_UNOCCUPIED�, and �OC_NULL�). A local digital input must be configured on Occ Sensor to use the value.

XL15A 109 306&307

OccSensorOut Occupancy sensor output network variable that provides the current state of the hard wired occupancy sensor. (Valid enumerated states: �OC_OCCUPIED�, �OC_UNOCCUPIED�, and �OC_NULL�).

CVAHU 109 27

Occupancy Sensor Out Occupancy sensor output network variable that provides the current state of the hard wired occupancy sensor. (Valid enumerated states: �0� - �OC_OCCUPIED�, �1� - �OC_UNOCCUPIED�, and �-1� - �OC_NUL�).If the sub-base fails to receive information from the thermostat cover assembly periodically, then the Occupancy Sensor Out is set to its power up default value. Generally the default value indicates the device that the information source has failed.

T7350 109 45

OD Enthalpy Out Outside air enthalpy output network variable that allows the local outdoor enthalpy sensor to be shared with other nodes and is always bound to the corresponding input variable on other nodes. OD Enthalpy Out is periodically sent on the network if the local sensor is configured otherwise the value is Sl_INVALID.

CVAHU 0 53

OdHumOut Outside air humidity output network variable that allows the sharing of the local outdoor humidity sensor with other nodes and is always bound to the corresponding input variable on other nodes. OdHumOut is periodically sent on the network if the local sensor is configured otherwise the value is taken as �Sl_INVALID�.

CVAHU 81 13

Od Hum Output Outside air humidity output network variable that allows the sharing of the local outdoor humidity sensor with other nodes and is always bound to the corresponding input variable on other nodes. OdHumOut is periodically sent on the network if the local sensor is configured otherwise the value is taken as �Sl_INVALID�.

XL15C 81 43

OdTempOut Outside air temperature output network variable that allows the sharing of the local outdoor temperature sensor with other nodes and is always bound to the corresponding input variable on other nodes. OdTempOut is periodically sent on the network if the local sensor is configured otherwise the value is taken as �Sl_INVALID�.

CVAHU 105 11

Od Temp Output Outside air temperature output network variable that allows the sharing of the local outdoor temperature sensor with other nodes and is always bound to the corresponding input variable on other nodes. OdTempOut is periodically sent on the network if the local sensor is configured otherwise the value is taken as �Sl_INVALID�.

XL15C 105 41

Outdoor Air Humidity Out Output network variable that allows the local outdoor humidity sensor to be shared with other nodes on the network. It is always bound to the Outdoor Air Humidity In on other nodes and if bound is periodically sent on the network. NOTE: If the local sensor is unconfigured the value is �SI_INVALID�, except when a valid

nviODHum is received.

XL15A 81 24

Outdoor Air Temperature Out

Output network variable that allows the local outdoor temperature sensor to be shared with other nodes on the network. It is always bound to the Outdoor Air Temperature In on other nodes and if bound is periodically sent on the network. NOTE: If the local sensor is unconfigured the value is �SI_INVALID�, except when a valid

nviOdTemp is received.

XL15A 105 22

Outdoor Temperature Out

Output network variable that shares the current outdoor temperature value with other nodes or devices on the network. If the value shared is �327.67�, then it means that the sensor is not functioning correctly or is out of range. If the sub-base fails to receive information from the thermostat cover assembly periodically, then the Outdoor Temperature Out is set to its power up default value. Generally the default value indicates the device that the information source has failed.

T7350 105 42

Table 30. Network Output Variable Description. (Continued)

NV Output Address Comments ControllerNV

TypeNV

Index

Page 77: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

77 74-3679�1

Outside Relative Humidity

Output network variable that shares the outside air humidity sensor values with other nodes or devices on the network.

Unit Vent 81 19

Outside Temperature Output network variable that shares the outside temperature sensor values with other nodes or devices on the network.

Unit Vent 105 20

Polled FCU Status Output network variable whose value signifies the FCU status and is similar to nvoFcuStatus except that the actual values are retained. It is a polled request output and is typically used by a supervisory device.

FCU 0 51

Polled HYD Status Output network variable whose value signifies the HYD status and is similar to nvoHydStatus except that the actual values are retained. It is a polled request output and is typically used by a supervisory device.

HYD 0 51

Pressure Sensor [1-2] There are six output network variables corresponding to the analog input channels, of which four are resistive type (AI1 thru AI4) and the remaining two (AI5 and AI6) are voltage or current. Pressure sensor is one of the sensors that is associated with AI5 and AI6 channels.

RIO 113 21 & 22

Process Data Out [1-8] Output network variables that provide the converters actual values to appropriate input network variables on other nodes or devices on the network. (Valid range is �0 to 65535� (-163,840 to 163,835)). The following are the applications that use these variables: Basic, Standard, Local/Remote, Multi-Step, PID control, and Pump and fan control. The variables and the values that they represent are as follows: � Process Data Out 1 - Output Frequency� Process Data Out 2 - Motor Speed� Process Data Out 3 - Motor Current� Process Data Out 4 - Motor Torque� Process Data Out 5 - Motor Power� Process Data Out 6 - Motor Voltage� Process Data Out 7 - DC Link Voltage� Process Data Out 8 - Active Fault Code.In case of Multipurpose Control Application, it has a selector parameter for every Process Data where the monitoring values and drive parameters are selected using the ID number. NOTE:

� For more information, refer to Chapter 6.5 Process Data in ud887a.pdf (NX VFD user manual).

� For more information on using selector parameter for process data, refer to see NX All in One Application Manual, Tables for monitoring values and parameters.

NX VFD 81 24-31

Read Parameter Output network variable used for reading the value of any EXCEL VRL CX parameter or variable. The value read (parameter or variable address) is defined by the network configuration variable, nciParOutPt.

VFD 8

Reheat Output Output network variable that is typically bound to an electric heat actuator node and reflects the current state of an �ON/OFF� reheat output. It is transmitted immediately when its value changes. The value can either be �OFF� (0%) or �ON� (100%).

FCU 95 13

Remote Analog Input Remote analog input network variable that can store six analog sensor values whose units are of type SNVT.

RIO 0 26

Remote Cmd [1-24] Out Remote output network variable that allows controller objects on EXCEL 15C/D to command analog and digital outputs that do not physically reside on the EXCEL 15C/D. Its range is from 0.00% to 100.00% with increments of .005%. In addition to RIO, it can also be bound to other devices. It is set to zero on power up. It can be used for commanding a smart valve or damper motor, communicate percent Outdoor Air Flow, fan capacity, condenser capacity, or send information to another EXCEL 15C/D.

XL15C 81 90-113

Remote Input [1-4] Remote Input0 is the network output variable for Digital Input channel1 and Remote Inputs from 1-3 are the network output variables for digital input channels 2 - 4.

RIO 95 11

Remote Output [0-23] It allows control loops onboard the EXCEL 15A to command outputs that do not physically reside on EXCEL 15A. Its purpose is to expand the possible hardware outputs available to EXCEL 15A. Its valid range is between -163.84% and +163.83% with a resolution of 0.005%. If the receiving output is not of modulating type but instead is of boolean type, then it is expected that the receiving device will interpret that zero percent as OFF / FALSE and any non-zero percent as ON / TRUE.

XL15A 81 77-100

Table 30. Network Output Variable Description. (Continued)

NV Output Address Comments ControllerNV

TypeNV

Index

Page 78: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 78

Runtime Value [1-15] nvoRuntime accumulates the amount of time a digital point is in the ON state when nviRuntimeEnable is TRUE. The value accumulated is between 0 to 65535 hours with a resolution of 1 hour. When nvoRuntime exceeds 65535 hours, the runtime accumulator resets to 0 hours.NOTE: The preset value in nviRuntimeInput is written to nvoRuntime once and is not retained

over a power outage. nviRuntimeInput resets nvoRuntime.

XL15A 0 199-213

Request LonMark® node object status reporting output network variable that provides the mechanism to request the status report of a particular object in the current node, using the Status network output variable.

CD 0 0

Sensor Occupancy [1-2] Out

Output network variable that displays the current state of the hard-wired occupancy sensors. It is initialized to NULL occupancy state on power up. Two digital inputs are assigned to these network variable outputs. The lowest index digital input configured to be an occupancy sensor goes on nvoSensorOcc[0] and the next highest on nvoSensorOcc[1]. The following are the valid enumerated states: OC_OCCUPIED (DI = On) and OC_UNOCCUPIED (DI = OFF).NOTE: They are not used by XL 15C/D algorithms as each Flexible and Start-Stop Loop has

their own occupancy DI sensor input that are already selected in the configuration file.

XL15C 109 309 & 310

Setpoint Out Space temperature setpoint output network variable that is calculated from the heating and cooling set points and is also based on the occupancy status. This output, if bound to the corresponding input variable on another node can change the temperature set point of that particular connected node.

Q7300H 105 29

Space Humidity Out Output network variable that shares the device�s current space humidity with other devices or nodes on the network. The sensor being used is specified by nciConfig.humiditySensor (room humidity sensor value). NOTE: If the values given out is �163.84�, then it means that the sensor is not functioning cor-

rectly or is out of range. If the sub-base fails to receive information from the thermostat cover assembly periodically, then the Space Humidity Out is set to its power up default value. Generally the default value indicates the device that the information source has failed.

T7350 81 41

SpaceTempOut Space temperature output network variable that is used by the control process and is read from another node on the network or from a local sensor. The network input takes priority over the local sensor if it is a valid value. SpaceTempOut is typically bound to the corresponding input variable of another node, which may not have it's own space temperature sensor but still controls the same space.

CVAHUVAVII

105 95

Space Temperature Out Space temperature output network variable that is used for controlling the space temperature. This in turn depends on the value received from the corresponding input variable on another node or from the local sensor.

Unit VentQ7300H

105 169

Status LonMark® node object status reporting output network variable that provides the status report of a particular object in the current node.

CD 0 1

Sensor OccOut Occupancy sensor output network variable that typically displays the state of the hard wired occupancy sensor. (Valid states: �OC_OCCUPIED�, �OC_UNOCCUPIED�, and �OC_NUL�).

FCUHYD

109 37

Space Temperature Output

It is the sensed space temperature at the node taken from the locally wired sensor. It is also used for monitoring purposes and displays the current space temperature used for the control algorithm. It reports an accurate space temperature between 0°C - 40°C and is transmitted immediately when its value changes (> 0.5 delta°C).

FCUHYD

105 14

Space Temperature Out Output network variable that shares the current space temperature with the other nodes or devices on the network. The value �327.67� means the sensor is not functioning correctly or is out of range.NOTE: If the sub-base fails to receive information from the thermostat cover assembly periodi-

cally, then the Space Temperature Out is set to its power up default value. Generally the default values indicate the device that the information source has failed.

T7350 105 34

SrcBypass Bypass output network variable. It is the current occupancy state of the node for bypassing the schedule. It is a combination of the bypass state and the bypass value. The following are the bypass states and their corresponding values: ON (0%) and OFF (100%).

Unit Vent 95 42

SrcCoolPos Output network variable that is used for controlling a cool actuator node or a slave CHC controller. The output value is limited to a range of 0% to 100%. It is transmitted immediately when its value changes (>= 1%).

CHC 81 6

Table 30. Network Output Variable Description. (Continued)

NV Output Address Comments ControllerNV

TypeNV

Index

Page 79: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

79 74-3679�1

SrcEconEnable Economizer output network variable that allows the value from a outdoor air sensor to be shared with the other nodes on the network. The air sensor validates if the outdoor air can be used for free cooling of the available space. It is bound to the corresponding network input on other nodes and has the following valid states: �ON� (0), �OFF� (100), and �NUL� (0).

Unit Vent 95 43

SrcEmerg Output network variable that shares the smoke detector values with other nodes on the network. Unit Vent 103 44SrcFanSpeed Output network variable that is typically bound to the external fan node and the value is transmitted

immediately as and when the fan speed changes. CHC 95 7

SrcFanSpeedSW Output network variable that allows the master CHC controller�s fan speed switch to be used for controlling all the slave CHCs assigned to the same room. The following are the different fan speed switch positions used: OFF, Fan Speed1, Fan Speed2, Fan Speed3, and Fan AUTO.

CHC 95 45

SrcHeatPos Output network variable used for controlling a heat actuator node or a slave CHC controller. The output value is limited to a range of 0% to 100%. It is transmitted immediately when its value changes (>= 1%).

CHC 81 5

SrcHVACMode HVAC operating mode output network variable. The master controller uses this value to control the fan coil unit controller slave devices. It reflects the current heat/cool mode based on the available energy excluding electrical reheat. This is required for configurations with heat/cool changeover. (Valid enumerated values are: �HVAC_COOL�, �HVAC_HEAT�, and �HVAC_OFF�. The initial value is set to �HVAC_OFF�, which changes when updated by the control algorithm. The value is refreshed as and when the mode changes.

CHC 108 51

SrcIaqOvr Output network variable that shares the indoor air quality override with other nodes on the network. Unit Vent 95 47SrcMonSw Output network variable that shares the monitor switch sensor values with other nodes across the

network. Unit Vent 95 48

SrcOaEnth Output network variable that shares the outside air enthalpy sensor value with or from other nodes on the network.

Unit Vent 0 49

SrcOaQuality Output network variable that shares the outside air quality (CO/CO2 levels) with other nodes on the network.

Unit Vent 29 50

SrcOccEff Output network variable that reflects the effective occupancy mode of the controller. The value is derived from schedule states (nviTodEvent), occupancy sensor, override button, and nviManOccCmd.

CHC 109 16

SrcOccSensor Occupancy sensor sharing output network variable that shares the state of a hard wired occupancy sensor. (Valid enumerated states: �OC_OCCUPIED�, �OC-UNOCCUPIED�, AND �OC_NULL�).

CHCUnit Vent

109 3651

SrcReheatPos It is typically bound to an electric heat actuator node and reflects the current state of an �ON/OFF� reheat output. It is transmitted immediately when its value changes. It can either be in �OFF� (0%) or �ON� (100%) states.

CHC 95 13

SrcRmDewPt CHC calculates the space dew point temperature using space temperature and relative space humidity values and uses this variable to transmit the value across the network. The output variable is updated immediately as and when the value changes. The value 0x7FFF = +327.67°C will be handled as an invalid value in case the CHC controller cannot calculate the dewpoint if there is a sensor break or NV failure detect and if there is no valid dewpoint setpoint configured.

CHC 105 55

SrcRmTempEff It is the sensed space temperature at the node taken from the locally wired sensor. It is also used for monitoring purposes and displays the current space temperature used for the control algorithm. It reports an accurate space temperature between 0°C - 40°C and is transmitted immediately when its value changes (> 0.5 delta°C).

CHC 105 14

SrcRmTempSptEff Gives the control algorithm�s active setpoint and is transmitted immediately when its value changes. It is based on occupancy setpoints recovery ramping.NOTE: nvoActiveSetPt is limited to the range +10°C to +35°C.

CHC 105 15

SrcStateDl1 Output network variable that is usually bound to the digital network input variable of a third party node. Indicates the binary states of the CHC controller's digital input which can be configured to support a window contact, an occupancy sensor, an air flow contact, or a heat/cool changeover contact. Following are the supported SNVT modes: Contact Closed, Contact Open, and Contact not Assigned.

CHC 95 48

Table 30. Network Output Variable Description. (Continued)

NV Output Address Comments ControllerNV

TypeNV

Index

Page 80: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 80

SrcTermLoad The output in percentage shows the terminal load, which is between -160% and +160% based on the control output level. Negative values indicate heating load and positive values indicate cooling load. 100% is the full terminal capacity. An absolute terminal load value of more than 100% indicate that the terminal is not able to supply the required heating or cooling energy which at the zone controller should cause a demand for more supply energy. The terminal load is computed from the output of the PID control algorithm. It is transmitted immediately when its value changes (> 1%).

CHC 81 12

SrcWindow Window output network variable that allows a hard wired sensor to be used by other nodes. The following are the SrcWindow values and the corresponding valid window states: WINDOW_CLOSED (0%), WINDOW_OPEN (100%), and WINDOW_NOT_ASSIGNED (0%).

CHC 95 18

Start-Stop [1-8] Bypass Out

Bypass output network variable that shares the Bypass operation from the source controller to the destination controller. The destination controller's bypass timer is not activated. The destination controller follows the bypass operation of the source controller based on the bypass arbitration status. [1-8] represent StartStop Loops 1-8 respectively.

XL 15A 95 147-154

Temperature Sensor [1-4]

There are six output network variables corresponding to the analog input channels, of which four are resistive type (AI1 thru AI4) and the remaining two (AI5 and AI6) are voltage or current. Temperature sensor is one of the sensors that is associated with AI1-AI4 channels.

RIO 105 15-18

Terminal Load The output in percentage shows the terminal load, which is between -160% and +160%. It is further based on the control output level. Negative values indicate heating load and positive values indicate cooling load. The full terminal capacity is 100%. An absolute terminal load value of more than 100% indicates that the terminal is not able to supply the required heating or cooling energy. This in turn causes a demand for more supply energy at the zone controller level. The terminal load is computed from the output of the PID control algorithm and is transmitted immediately when its value changes (> 1%).

FCU 81 12

TerminalLoad TerminalLoadOut reports the demand for supply energy. 100% indicates full capacity of the terminal capacity. Positive numbers are cooling demand and negative numbers are heating demand. Terminal loads greater than 100 percent indicate that the terminal is not able to supply the required heating or cooling energy. TerminalLoad (TerminalLoadOut) is used for co-ordination within the HVAC subsystem and energy management decisions by the supply equipment.

VAVII 81 18

Terminal Load Out Reports the demand for supply energy. Positive numbers indicate cooling demand and negative numbers indicate heating demand. Terminal loads greater or less than 100% indicate that the equipment is not able to supply the required heating or cooling energy. (Valid range is between �+/-163%� and �163.84� is the power up condition).NOTE: If the sub-base fails to receive information from the thermostat cover assembly periodi-

cally, then the Terminal Load Out is set to its power up default value. Generally the default values indicate the device that the information source has failed.

T7350 81 40

Time Clock Out Time Clock output network variable that reports the current state of the digital input configured on the physical time clock input. The following are the output values: SW_On, SW_OFF, and SW_NULL.

CVAHU 95 59

Time of Day Out [0-3] Time of day scheduling output network variable. A node when in local schedule mode shares its scheduled occupancy with up to four other nodes using the network variables: nvoOccSchedule0, nvoOccSchedule1, nvoOccSchedule2, and nvoOccSchedule3. In local schedule mode, all four of these network variables are controlled by the thermostat's schedule. SrcSchedOcc0 is the current scheduled occupancy state that is followed by the SrcTodEventNext0 (next scheduled occupancy state), and the later one will occur in SrcTuncos0 minutes. The supported occupancy states are: Occ, UnOcc, and Null.

Q7300H 128 25

Table 30. Network Output Variable Description. (Continued)

NV Output Address Comments ControllerNV

TypeNV

Index

Page 81: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

81 74-3679�1

Time of Day Out Output network variable that shares the current scheduled occupancy state with other devices or nodes on the network. The current scheduled occupancy is a combination of the current state (status1.currentState), next state (status1.nextState), and time to next state (status1.tuncos) values as it is either the local programmed schedule or a network schedule. It allows the destination node to make its own decision on override and occupancy sensor. � Valid Current Occupancy states: �0� - �OC_OCCUPIED�, �1� - �OC_UNOCCUPIED�, �2� - Bypass,

�3� - �OC_STANDBY�, and �-1� - �OC_NUL� (power up value).� Valid Next scheduled occupancy states: �0� - �OC_OCCUPIED� (power up value), �1� -

�OC_UNOCCUPIED�, �2� - �Bypass�, �3� - �OC_STANDBY�, and �-1� - �OC_NUL� (power up value)� Time until next scheduled change of occupancy state: �2880�, means there is not a next change

of occupancy state or it is longer than 2 days from now. NOTE: If the sub-base fails to receive information from the thermostat cover assembly periodi-

cally, then the Time of Day Out is set to its power up default value. Generally the default values indicate the device that the information source has failed.

T7350 128 44

Time Out Output network variable that provides the current date (month, year, and day) and current time (hours, minutes, and seconds). The significant event update occurs every time the minutes is updated. Following are the valid date and time range.� Current date (Year): �0� - means not specified. (power up value), valid range: �2000 through

2175�, and �-1� - �Invalid Value�.� Current date (Month): �0� - �Invalid Month� (not programmed) (power up value) and �1-12�

(January-December). � Current date (Day): �0� - �Not specified� (power up value) and �1-31� - �Valid range�.� Current time (hour of the day): �0� - �Midnight� (power up value), �12� - �noon�, and �23� - �11� PM.� Current time (minute of the hour): �0� - �First minute of hour� (power up value) and �59� - �last

minute of hour�. � Current time (Second of the minute): �0� - �First second of minute� (power up value) and �59� - �last

second of hour�.

T7350 84 12

TOD Event [1-20] Time of day scheduling output network variable. It is the command output from the Time Of Day Scheduler and specifies the current scheduled occupancy state, the next scheduled occupancy state, and the time until the next occupancy state begins. Schedule assignment configuration determines the XL15A schedule (out of the 8 XL15A schedules) that will drive these nv values.

XL15A 128 57-76

Total KW nviKWTotalIn and nvoKWTotalOut are of type SNVT_power_kilo. If nviKWTotalIn is bound then it is output on the network variable nvoKWTotalOut. If nviKWTotalIn is NOT bound then nvoKWTotalOut is a copy of nvoCascadeOut. The reset value for nviKWTotalIn and nvoKWTotalOut is zero.

XL15A 28 291

Voltage Sensor There are six output network variables corresponding to the analog input channels, of which four are resistive type (AI1 thru AI4) and the remaining two (AI5 and AI6) are voltage or current. Voltage sensor is one of the sensors that is associated with A15 and A16 channels.

RIO 44 24

Window Contact Out Window contact output network variable that allows the hard wired window sensor to be used by other nodes on the network. The following are the output values: SW_On, SW_OFF, and SW_NULL.

CVAHU 95 29

Window Output Window output network variable that allows a hard wired sensor to be used by other nodes. The following are the SrcWindow values and the corresponding valid window states: WINDOW_CLOSED (0%), WINDOW_OPEN (100%), and WINDOW_NOT_ASSIGNED (0%).

FCUHYD

95 18

Table 30. Network Output Variable Description. (Continued)

NV Output Address Comments ControllerNV

TypeNV

Index

Page 82: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 82

APPENDIX B � REMOTE POINT TABLESThe following table describes the function of all remote point names. Names are listed alphabetically.

Table 31. Remote Point Functions.

Remote Point Name FunctionActiveDLCDeadband DLC deadband currently in use. Peak or Off-Peak programmed value.ActiveDLCSetpt DLC setpoint currently in use. Peak or Off-Peak programmed value.ADCalError Controller diagnostic error message.AI[1-4]FLInput Temperature input value.AI[5-6]FLInput Voltage/Current input value as configured.AISensor[1-8] Analog input [1-8] value with engineering unit for configured sensors.AnalogHiAlarm[1-20] The high alarm status of analog alarm assignment [1-20]. It is necessary to review the XL15A configuration to

determine the analog alarm assignment for any given analog point.AnalogHiWarning[1-20] The high warning status of analog alarm assignment [1-20]. It is necessary to review the XL15A configuration to

determine the analog alarm assignment for any given analog point.AnalogInput[1-8] Analog input value with engineering unit for configured sensors.AnalogLoAlarm[1-20] The low alarm status of analog alarm assignment [1-20]. It is necessary to review the XL15A configuration to

determine the analog alarm assignment for any given analog point.AnalogLoWarning[1-20] The low warning status of analog alarm assignment [1-20]. It is necessary to review the XL15A configuration to

determine the analog alarm assignment for any given analog point.AuxEconOutOn During MANUAL mode, AuxEconOutOn turns the AUX_ECON_OUT on(1) or off(0).AuxOn The state of the Auxiliary digital output or the state of the latching relay attached to the AuxiliaryPulseOn or

AuxiliaryPulseOff digital outputs. The physical outputs must be mapped (configured) to the logical outputs to actually work.

BoxFlow Reports the air flow measured at the controller calculated from differential pressure sensor. When the actual flow velocity is less than 50 feet per second, then BoxFlow reports zero. If a flow sensor error has been detected, then BoxFlow is set to Invalid. If FlowSensor is Invalid, then BoxFlow and BoxFlowOut is also Invalid

BoxFlowControlPt The current air flow calculated set point value. BoxHeatFlow When the controller configuration ReHeatType specifies DualDuctReHeat, BoxHeatFlow reports the air flow of

the associated satellite controller that is controlling the hot air flow from the hot air duct. The satellite controller reports its box flow to the master controller by binding the satellite�s BoxFlowOut to the master�s FlowTrackIn. The master�s BoxHeatFlow then reports FlowTrackIn.

Bypass In Controller network bypass input. When scheduled for unoccupied or standby mode the controller will operate in the bypass (occupied) mode as long as the input remains active(ON, 1). The internal bypass timer is not used. Normally the local wall module bypass input is not used.

Bypass_[1-10] In The network bypass input to the control loop [1-10]. The control loop will remain in bypass as long as this input remains active and the control loop is not scheduled occupied.

Bypass_[11-18] In The network bypass input to the start-stop loop [1-8]. The start-stop loop will remain in bypass as long as this input remains active and the control loop is not scheduled occupied.

ByPassStateOut Indicates the current bypass state of the controller. Off = no bypass; On = Bypass active.BypassTimer The time left in the bypass timer is BypassTimer minutes. If BypassTimer is zero, then the bypass timer is not

running.ByPassValueOut Controller bypass analog output. Value of 0% = controller is not in bypass; value of 100% = controller is in

bypass. No intermediate values are valid. Output remains active (100%) if the scheduled occupancy mode is unoccupied or standby and the bypass timer value is greater than 1.

BypTimer The time left in the bypass timer is BypassTimer minutes. If BypassTimer is zero, then the bypass timer is not running.

CalcOdEnthalpy CalcODEnthalpy is the calculated outdoor air enthalpy in btu / lb calculated from the OutdoorTemp and OutdoorHumidity.

CalcRtnEnthalpy CalcRAEnthalpy is the calculated return air enthalpy in btu / lb calculated from the ReturnTemp and ReturnHumidity.

Cloop[1-10] FlexMan_AO_Stage[1-4] The state of control loop [1-10] PID staged outputs [1-4] when manually commanded.Cloop[1-10] FlexManPerCmdAO The value in percent of control loop [1-10] sequence [1-3] output when it is manually commanded.

Page 83: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

83 74-3679�1

Cloop[1-10] FlexManPerCmdSeq1 The value in percent of control loop [1-10] PID output when it is manually commanded.Cloop[1-6] Bypass In The network input to the control loop [1-6]. The control loop will remain in bypass as long as this input remains

active and the control loop is not scheduled occupied.Cloop[1-6]_ManualIn_Aux The state of the control loop [1-6] Aux output when manually commanded.Cloop[1-6]_ManualIn_Percent The value in percent of control loop logical output when it is manually commanded.Cloop[1-10] FlexMan_Seq[1-3]_Stage[1-4] The state of control loop [1-10] Sequence [1-3] staged outputs [1-4] when manually commanded.Cloop[1-10] FlexManAuxDO The state of control loop [1-10] Aux output when manually commanded.Cloop[1-6]_EffectiveSetpoint The actual setpoint the control loop is using. Calculated based on mode, occupancy, recovery, reset, and DLC. Cloop[1-6]_ManualIn_Stage[1-4]On The state of the control loop [1-6] staged output [1-4] when manually commanded.Cloop[1-6]_StagesActive The number of control loop [1-6] output stages turned on.CO2Sens The indoor air CO2 content used by the control process read by the local sensor. If the local sensor has failed or

is not configured, SpaceCo2 is SI_INVALID.CoilFreezeStat State of the digital input wired to a general purpose monitor switch. 1 means that the switch is closed and 0

means that the switch is open.CommFail Controller diagnostic error message.ControlLoop[1-10] BypassState The bypass state of the control loop [1-10]ControlLoop[1-10] ControlSensor Main sensor input value for control loop [1-10] ControlLoop[1-10] CurrentState Current scheduled occupancy state for control loop [1-10]ControlLoop[1-10] EffectiveOccupancy Occupancy state currently in effect for control loop [1-10] ControlLoop[1-10] EffectiveSetpt Setpoint currently in effect for control loop [1-10] ControlLoop[1-10] NextState Occupancy state scheduled next for control loop [1-10] ControlLoop[1-10] PriStgActive Number of stages turned on in control loop [1-10] PID output.ControlLoop[1-10] SensorOccupancy Current status of occupancy sensor input for control loop [1-10] ControlLoop[1-10] Seq[1-3]StgActive Number of stages turned on in control loop [1-10] sequence [1-3] output.ControlLoop[1-10] TUNCOS Time remaining until next change of occupancy state for control loop [1-10]ControlLoop[1-6]_BypassOutstate The bypass state of the control loop [1-6]ControlPointTemp The current temperature control point (i.e., the current actual space temperature set point which the controller is

using) calculated from the various Set Points, operating modes, network variable inputs, and start-up parameters.

CoolPos If the controller is configured for modulating cooling, CoolPosition indicates the current position of the cooling modulating output.

CoolPosition If the controller is configured for modulating cooling, CoolPosition indicates the current position of the cooling modulating output.

CoolStagesOn Indicates number of compressor stages on. If the node is controlling a heat pump, compressor stages are turned on for both heating or cooling.

CoolStgsOn Indicates the number of compressor stages turned on.Counter_Out[1-2] The number of counts currently in the counter.CounterEnable_In[1-2] The state of the counter [1-2] enable input.DamperPos The current output value (0-100% of full rotation) to the flow control damper.DaSetpt The calculated discharge air temperature setpoint when cascade control is being used.DaTemp The discharge air temperature used by the control process is read from the local sensor. If the sensor has failed

or is not configured, DischargeTemp is SI_INVALID.DestBypass Controller network bypass input. When scheduled for unoccupied or standby mode the controller will operate in

the bypass (occupied) mode as long as the input remains active (ON, 1). The internal bypass timer is not used. Normally the local wall module bypass input is not used. Note: nviBypass value must be greater than zero.

DestEconEnable Controller network input used for enabling the economizer. Off = Outdoor air not suitable for cooling. On = Outdoor air is suitable for cooling.

DestHtSource Controller network input used for determining if energy source is for heating or cooling. Off = cooling; On = heating. If not used the controller assumes both are available.

Table 31. Remote Point Functions. (Continued)

Remote Point Name Function

Page 84: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 84

DestIaqOvrd Controller network input used for disabling the economizer from indoor air quality. Off = indoor air quality is acceptable, enable economizer; On = indoor air quality is not acceptable, disable economizer.

DigitalIn[1-4] Status of digital input as configured.DigitalOut[1-8] The commanded state of all the digital outputs 1 through 8. Assumes the triacs or relays and hardware external

to the controller are following the microprocessor.DigitalOutput[1-8] RIO digital output corresponds to the physical output. RIO outputs configured as Discrete (digital) will appear in

remote point selection list for staged (digital) outputs. RIO outputs configured for Float or Modulate (PWM) will appear in remote point selection list for analog outputs.

DirtlyFilterAlrm Indicates the current filter alarm state. Alarm is generated by DirtyFilter state. Either FilterPressure voltage input or DirtyFilter digital input can generate the alarm.

DirtyFilter Indicates the current filter input state. DirtyFilter can be generated by either FilterPressure voltage input or DirtyFilter digital input.

DirtyFilterAlrm Indicates the current filter alarm state. Alarm is generated by DirtyFilter state. Either FilterPressure voltage input or DirtyFilter digital input can generate the alarm.

DischargeSetPt Calculated desired discharge air temperature when cascade control is being used.DischargeTemp The discharge air temperature used by the control process is read from the local sensor. If the sensor has failed

or is not configured, DischargeTemp is SI_INVALID.DischgTempError Controller diagnostic error message.DISwitch1_LogicalState The state of the digital input [1-8].DLCShed Indicates the Demand Limit Control state of the controller. Note: The DLC state is used with occupancy state and

other factors to determine the effective setpoint.DlcShed Indicates the Demand Limit Control state of the controller. Note: The DLC state is used with occupancy state and

other factors to determine the effective setpoint.DualDuctError Controller diagnostic error message.EconEnable Indicates the current suitability of outdoor air for use in cooling used by the control process. ST_OFF means

outdoor air is not suitable to augment cooling. ST_ON means the outdoor air is suitable to augment cooling. ST_NUL means no local sensor is selected, or the selected local sensor has failed or has not been configured as an input point, and the network point Econ In is SW_NUL. The outdoor air is considered unsuitable for cooling.

Econ Enable In Network input for economizer enable.Econ In Controller network input used for enabling the economizer. Off = Outdoor air not suitable for cooling. On =

Outdoor air is suitable for cooling.EconFloatingSynch Indicates that the economizer damper motor is being synchronized with the reported economizer position by

driving the damper for a period longer than it takes to fully close the damper. The reported economizer position is �synchronized� whenever an endpoint is reached (full open or full close) and when the elapsed time since the last synchronization is 24 hours.

EconPos If the controller is configured for modulating economizer, EconPos shows the current position of the economizer modulating output.

EconPosition If the controller is configured for modulating economizer, EconPosition shows the current position of the economizer modulating output.

EffectiveOcc The effective occupancy arbitrated from SchedOcc, SenOcc, and OverRide. EffectiveOcc is used for selecting the current temperature set point. Occ; Unocc; Bypass; and Standby.

EffectOcc The effective occupancy arbitrated from SchedOcc, SenOcc, and OverRide. EffectOcc is used for selecting the current temperature set point. Occ; Unocc; Bypass; and Standby.

EffectSetPtOut The current temperature control point (i.e., the current actual space temperature set point which the controller is using) calculated from the various Set Points, operating modes, network variable inputs, and start-up parameters.

FanOn Indicates the state of the fan digital output. 1 means on, and 0 means off.FanSpeed Indicates fan speed if controller output Fan Type is configured for Parallel PWM Control.FanSwitch The commanded fan speed by the wall module fan switch and / or the network. 1stage fan will show On / Off; 2

Stage fan will show Off / Low / High; and 3 stage fan will show Off / Low / Med / High. All three will show Null, or automatic speed selection, if switch is set to Auto and no command is given to the network point, DestFanSpeed.

Table 31. Remote Point Functions. (Continued)

Remote Point Name Function

Page 85: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

85 74-3679�1

FieldNo[1-2] Indicates which other data field has changed since the last time data was sent on the network. If FieldNo is UPDATE_ALL_FIELDS, then all fields have been updated. If FieldNo is UPDATE_NO_FIELDS, then no fields have been updated recently.

FilterPress The differential air pressure (in. w.c.) across the air filter used by the control process read from the local sensor. If the local sensor has failed or is not configured, FilterPress is SI_INVALID.

FilterPressure The differential air pressure (in. w.c.) across the air filter used by the control process read from the local sensor. If the local sensor has failed or is not configured, FilterPressure is SI_INVALID.

FlowError Controller diagnostic error message.FlowTrackingError Controller diagnostic error message.Free1 Controller network input used for controlling a digital output configured as Free1. 0 = OFF, 1 = On.Free1 In Controller network input used for controlling a digital output configured as Free1. 0 = OFF, 1 = On.Free1On Reports the current state of the digital output configured as Free1. 0 = OFF, 1 = On. Free1Stat The status of the digital output configured as Free1.Free2 In Controller network input used for controlling a digital output configured as Free2. 0 = OFF, 1 = On.Free2On Reports the current state of the digital output configured as Free2. 0 = OFF, 1 = OnFreshAirRatio FreshAirRatio is FreshAirRequired divided by BoxFlow. When FreshAirRatio is Large (greater than 100 percent),

there is insufficient fresh air being supplied to the zone even if the supply air is 100 percent fresh air. When FreshAirRatio is small, there is sufficient fresh air being supplied to the zone. FreshAirRatio is used for coordination within the HVAC subsystem and energy management decisions by the supply equipment. If the actual FreshAirRatio is greater than 150 percent, FreshAirRatio reports 150 percent. If BoxFlow is zero, then FreshAirRatio is Invalid. If the calculated ratio is greater than the range that can be handled by a two byte number, then FreshAirRatio is set to the biggest number possible before Invalid is indicated.

FrostProtect If the controller is not disabled and the space temperature falls below 42.8 degrees, a FrostProtect is issued. When the space temperature rises above 46.4 degrees F, the FrostProtect returns to normal.

FrostProtectAlrm If the controller is not disabled and the space temperature falls below 42.8 degrees, a FrostProtectAlrm is issued. When the space temperature rises above 46.4 degrees F, the FrostProtectAlrm returns to normal.

HeatCoolSwitch The state of the digital input configured and wired to a Heat / Cool change over switch. Cool = False (Off, 0)); Heat = True (ON, 1)

HeatPos If the controller is configured for modulating heat, HeatPos shows the current position of the heating modulating output.

HeatPosition If the controller is configured for modulating heat, HeatPosition shows the current position of the heating modulating output.

HeatSource In a two pipe system, the HeatSource indicates whether hot or cold water is being supplied to the equipment being controlled. HeatSource is calculated from DestHtSource, DestSourceTemp, HtSrcTemp, and either the AqstatMakeTmpRise or AqstatBrkTmpRise physical input.

HeatStages When the ReHeat is staged, HeatStages reports the number of ReHeat stages currently turned on. When the fan is off, or air flow in the duct is less than half the FlowControlPt, then the HeatStages is 0 to prevent ReHeat coils from over heating.

HeatStagesOn Indicates the number of heating stages turned on. If the node is controlling a heat pump, HeatStagesOn indicates the number of auxiliary heating stages turned on.

HeatStgsOn Indicates the number of heating stages turned on.HwConfigError Controller diagnostic error message.IAQ Override In Controller network input used for disabling the economizer from indoor air quality. Off = indoor air quality is

acceptable, enable economizer; On = indoor air quality is not acceptable, disable economizer.IaqOverRideAlrm Indicates the current state of the indoor air quality alarm. 1 means poor indoor air quality, and 0 means indoor air

quality is OK. IaqOverRideOn When an economizer is configured, IaqOverRideOn indicates the current state of the indoor air quality, and is

used by the control process to open the economizer damper to let in more outside air. 1 means poor indoor air quality, and 0 means indoor air quality is OK. When IaqOverRide is 1, the IAQ_OVERRIDE alarm is initiated.

InputNVFaiLAlrm One or more NV inputs have failed in receiving an update within their specified FAILURE_DETECT_TIME.InvalidConfig Configuration Error - Correct the controller configuration for selected application.InvalidSetPoint One of the space temperature points in nciSetPts is not in the valid range.InvalidSetPtAlrm One of the setpoints is not in the valid range.

Table 31. Remote Point Functions. (Continued)

Remote Point Name Function

Page 86: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 86

KW_Demand The current demand the DLC program is using.LogicFunction [1-8] The output value (analog) or state (digital) of the logic loop.LogicLoop[1-32] AO Analog output value for logic loop [1-32].LogicLoop[1-32] DigitalOut The digital output state for logic loop [1-32].LossAirFlowAlrm The air flow switch indicates that there is no air flow when the node is commanding the fan to run. The control is

shut down and disabled until power is cycled or the node is reset. LowFlowAlarm Low air flow alarm. False = The duct pressure is sufficient to allow the desired air flow; True = The duct pressure

is not sufficient to meet the desired air flow at a fully open damper.MixAirTemp The temperature of the mixed air read from the local sensor. If the local sensor has failed or is not configured,

MixAirTemp is SI_INVALID.Mode Mode indicates the current Mode of the node determined by many inputs and arbitrated by control logic. See

Table 11 for mode values.MonitorSens The voltage (0-10 Vdc) applied at the analog input terminals configured as monitor. If the sensor is not

configured or has failed, the value is SI_INVALID.MonitorSw The state of the digital input configured and wired to a general purpose monitor switch. 1 (input shorted) means

that switch is closed, and 0 (input open) means that the switch is open.MonitorSwitch The state of the digital input configured and wired to a general purpose monitor switch. 1 (input shorted) means

that switch is closed, and 0 (input open) means that the switch is open.MonitorVolts The voltage (0-10 Vdc) applied at the analog input terminals configured as monitor. If the sensor is not

configured or has failed, the value is SI_INVALID.MonSwitch The state of the digital input configured as Monitor Switch. Open contact = False; Closed contact = True.NetManOcc The network manual occupancy state of the controller. The valid enumerated states are: Occ; Unocc, Standby;

Null or other unspecified value.NodeDisabled The control algorithm has stopped because the controller is in Disabled, Manual, IOTest, or FactoryTest mode.

No more alarms are reported when the controller is Disabled and the last alarm issued is NodeDisabled.nvApplicModeError Controller diagnostic error message.nvBypassError Controller diagnostic error message.nvDlcShedError Controller diagnostic error message.nvDuctInTempError Controller diagnostic error message.nvEnergyHoldOffError Controller diagnostic error message.nvFlowOffsetError Controller diagnostic error message.nvFlowTrackError Controller diagnostic error message.nvFree1Error Controller diagnostic error message.nvHeaterOveridError Controller diagnostic error message.nviBypass Controller network bypass input. When scheduled for unoccupied or standby mode the controller will operate in

the bypass (occupied) mode as long as the input remains active(ON, 1). The internal bypass timer is not used. Normally the local wall module bypass input is not used.

nviEnergyHoldOff Controller network Energy Hold Off input. If either the network input or the local sensor is active, the Energy Hold Off algorithm will be in effect. Off = window closed; On = window open. This is the same as the Window Open function in other XL10 controllers.

nviHeaterOverid Normally the ReHeat is controlled automatically. However the ReHeat and peripheral ReHeat can be controlled manually by nviHeaterOverid. OFF = ReHeat and peripheral ReHeat is automatically controlled; ON = ReHeat and peripheral ReHeat is turned OFF.

nvSensorOccError Controller diagnostic error message.nvSetPtOffsetError Controller diagnostic error message.nvShareError Controller diagnostic error message.nvSpaceTempError Controller diagnostic error message.nvTodEventError Controller diagnostic error message.OaEnthalpy Measured outdoor air enthalpy.OaEnthCalc The calculated outdoor air enthalpy in btu / lb calculated from the OutdoorTemp and OutdoorHumidity.

Table 31. Remote Point Functions. (Continued)

Remote Point Name Function

Page 87: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

87 74-3679�1

OaHum The outdoor air humidity used by the control process read from another controller via the network or the local sensor.

OaQuality The outdoor air quality measurement read from the local sensor. If the sensor is not configured or has failed, the value is SI_INVALID.

OaTemp The outdoor air temperature used by the control process read from another controller via the network or the local sensor.

OccSensorOut Indicates the state of the hard wired occupancy sensor. (Occ = space is Occupied, UnOcc = space is Unoccupied, Null = occupancy sensor is not configured).

OccStatusOut Indicates the state of the AuxEcon digital output. 1 means on (not OC_UNOCCUPIED), and 0 means off (OC_UNOCCUPIED).

OccStatusOutOn Indicates the state of the AuxEcon digital output. 1 means on (not OC_UNOCCUPIED), and 0 means off (OC_UNOCCUPIED).

OdEnthalpy The outdoor air enthalpy in btu / lb calculated from outdoor air temperature and outdoor air humidity.OdHumidity The outdoor air humidity used by the control process read from another controller via the network or the local

sensor. OdTemp The outdoor air temperature used by the control process read from another controller via the network or the local

sensor.OverRide The effective manual over ride state arbitrated from NetManOcc, ByPassStateIn, the wall module over ride

button and, BypassTimer. Enumerated states are: Occ; Unocc; Standby; and Null.PeriphHeatOn When the peripheral Heat is staged, PeriphHeatOn reports whether the peripheral heating stage is currently

turned on (True) or turned off (False).PeriphHeatPos When the peripheral ReHeat is modulating, PeriphHeatPos reports the current peripheral ReHeat motor

Position.PowerOut The KW value of KW Cascade In and any pulse meter inputs configured.PowerTotalOut If the network input Total KW In is bound the output is equal to the input. If Total KW In is not bound it is set to the

value of KW Cascade Out.RaEnthalpy The return air enthalpy in btu / lb calculated from the return air temperature and return air humidity.RaEnthCalc CalcRAEnthalpy is the calculated return air enthalpy in btu / lb calculated from the ReturnTemp and

ReturnHumidity.RaHum The return air enthalpy in btu / lb calculated from the return air temperature and return air humidity.RaTemp The return air temperature used by the control process read from the local sensor. If the sensor has failed or is

not configured, ReturnTemp is INVALID.ReheatPos When the ReHeat is modulating ReHeat, ReheatPos reports the current ReHeat motor Position. When the

DualDuctDischSensor or DualDuctDischSenCV is properly configured, then ReheatPos reports the Position of the hot duct damper.

Remote Digital In [1-12] Do not use. Reserved for RIO digital inputsRemote Sensor_[1-12] In Do not use. Reserved for RIO digital inputsRemoteCmd[1-24]_Out Status of command to associated RIO output. [1-8] are assigned to the outputs of the 1st RIO associated, [9-16]

are assigned to the 2nd RIO associated, and [17-24] are assigned to the 3rd RIO associated.ReturnEnthalpy The return air enthalpy in btu / lb calculated from the return air temperature and return air humidity.ReturnHumidity The return air humidity used by the control process read from the local sensor. If the sensor has failed or is not

configured ReturnHumidity is INVALID.ReturnTemp The return air temperature used by the control process read from the local sensor. If the sensor has failed or is

not configured, ReturnTemp is INVALID.RmTemp The measured space temperature. If the sensor is not configured or has failed, the value is SI_INVALID.RoomTempActSpt The current temperature control point (i.e., the current actual space temperature set point which the controller is

using) calculated from the various Set Points, operating modes, network variable inputs, and start-up parameters.

RmTempActSpt The current temperature control point (i.e., the current actual space temperature set point which the controller is using) calculated from the various Set Points, operating modes, network variable inputs, and start-up parameters.

Runtime_Out[1-15] Current runtime of assigned. Point. It is necessary to review the XL15A configuration to determine the Runtime assignment number for the desired point.

Table 31. Remote Point Functions. (Continued)

Remote Point Name Function

Page 88: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 88

SaFanSpd Wired in Fan Switch determines fan speed if it is configured, or the control process controls it if no Fan Switch is present. Enumerated Values will be On / Off for 1 stage Fan; Off / Low / High for 2 stage; Off / Low / Med / High for 3 speed.

SaFanStatus Each time the fan is energized, the controller waits for FanFailTime to sample the ProofAirFlow input. If input shows fan is not running, controller will shut down the fan for the minimum off time, and try 2 more times. If it fails 3 times, a LossAirFlowAlrm is issued and the control stays in the Disable Mode. On = Air flow is not detected. Turn off control. Try to start three times before LossAirFlowAlrm and setting the Mode to Disable. Off = Air flow is detected or no ProofAirFlow switch is configured.

SchedOcc The controller's scheduled occupancy state as determined by the time program except if the controller is configured as Single Duct - Share Wall Module, or Dual Duct - DD Satel No Flow Mix, DD Satel Flow Mix, or DD Satel Constant Volume in which case the SchedOcc will equal the EffectOcc of the source controller.

SenOcc SenOcc indicates the current state of the sensed occupancy as calculated from the network occupancy sensor input and the local occupancy sensor. If either the local sensor or network input shows occupancy, then SenOcc shows occupancy. The valid enumerated values are: Occ, Unocc, and Null.

SensorFail Space temperature sensor failure. Temperature control is turned off and the damper is set to either a minimum Position or closed depending on the EffectOcc, Mode, and FlowControlType. Fan operation is not affected.

SensorFailAlrm One or more sensors have failed.SensorOcc SensorOcc indicates the current state of the sensed occupancy as calculated from the network occupancy

sensor input and the local occupancy sensor. If either the local sensor or network input shows occupancy, then SensorOcc shows occupancy. The valid enumerated values are: Occ, Unocc, and Null.

SetPtError Controller diagnostic error message.ShareError Controller diagnostic error message.ShutDown Indicates the state of the ShutDown digital. 1 means a ShutDown is being commanded and 0 means normal

operation.SmokeAlrm The smoke detector has detected smoke and the controller has entered an emergency state.SmokeDetected Indicates the current state of the SmokeMonitor input used by the control process and is read from another

controller via the network and/or the local sensor. If either is 1, then SmokeDetector is 1 meaning that smoke is detected. Otherwise SmokeDetector is 0, meaning smoke is not detected. When smoke monitor is 1, the algorithm controls as per the settings found in controller configuration.

SmokeEmergency When the controller enters the Pressurize or DePressurize mode, then the node issues the SmokeAlarm.SpaceCO2 The indoor air CO2 content used by the control process read by the local sensor. If the local sensor has failed or

is not configured, SpaceCo2 is SI_INVALID.SpaceTemp The space temperature used by the control process read from the local sensor or another controller. If

SpaceTempIn is not Invalid, then SpaceTempIn has priority. SpaceTempError Controller diagnostic error message.SrcBypass Indicates the current bypass state of the controller.SrcBypassV Controller bypass analog output. Value of 0% = controller is not in bypass; value of 100% = controller is in

bypass. No intermediate values are valid. Output remains active (100%) if the scheduled occupancy mode is unoccupied or standby and the bypass timer value is greater than 1.

SrcCoolOutput Percentage of the cooling stages on. (Stages On / Configured Stages X 100%)SrcEffectOcc Occupancy state being called for by the thermostat including the local schedule or activation of Temporary

Occupied or Continuous Occupied buttons: Occ, UnOcc SrcEmerg Source point used for sharing Smoke Detector with other nodes. False = No smoke detected or no smoke

detector present; True = Smoke detected. Take action depending on controller configuration. Generate a SmokeAlrm.

SrcHeatOutput Percentage of the heating stages on. (Stages On / Configured Stages X 100%)SrcHvacMode An output that may be used for coordinating system operating mode with other nodes. The current system mode

of the thermostat is reported in SrcHvacMode. This mode is determined either in the Q7300 (from network inputs) or in the thermostat (from front panel entries), whichever was changed last. Some thermostat models do not allow the system mode to be changed from the front panel. Not all operating modes are allowed in every thermostat model (i.e., a particular T7300 model may be heat-only, with no cooling allowed, etc.), and SrcHvacMode reflects the operating modes allowed in the thermostat model. See table 11 for enumerated values.

SrcOaTemp Source point used for sharing outside air temperature to other nodes.

Table 31. Remote Point Functions. (Continued)

Remote Point Name Function

Page 89: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

89 74-3679�1

SrcRmTemp The space temperature used by the control process read from the local sensor or another controller. If SpaceTempIn is not Invalid, then SpaceTempIn has priority.

SrcRmTempActSpt The current temperature control point (i.e., the current actual space temperature set point which the controller is using) calculated from the various Set Points, operating modes, network variable inputs, and start-up parameters.

SrcRmTempSpt The average of the scheduled heating and cooling setpoints - a single value representing center of the heating and cooling setpoints.

sSrcBypass Indicates the current bypass state of the controller. Off = no bypass; On = Bypass active.StartStop 1 Bypass In The network input to the start-stop loop [1-8]. The control loop will remain in bypass as long as this input remains

active and the control loop is not scheduled occupied.StartStop[1-8]_Out The state of the start-stop loop [1-8] output when manually comanded.StartStopLoop[1-8] CurrentState Current scheduled occupancy state for start-stop loop [1-8].StartStopLoop[1-8] EffOcc Occupancy state currently in effect for start-stop loop [1-8].StartStopLoop[1-8] NextState Occupancy state scheduled next for start-stop loop [1-8] StartStopLoop[1-8] SenOcc Current status of occupancy sensor input for start-stop loop [1-8] StartStopLoop[1-8] TUNCOS Time remaining until next change of occupancy state for start-stop loop [1-8]StartStopLoop[1-8]_BypassOutstate The bypass state of the start-stop loop [1-8]StartStopLoop1 BypassState The bypass state of the control loop [1-6]StartStopLoop1 Out The state of the start-stop loop [1-8] output when manually comanded.StatDripPanFull Indicates the drip pan is full if a local digital input is configured on the controller. The fan runs but cooling is

disabled.StatFreezeStat Indicates current state of the freeze stat. False = the coil is not about to freeze or there is no freeze stat

configured. True = the heating and / or cooling coil is about to freeze and the controller should take appropriate action. The FreezeStatAlrm is generated.

StatusEconEn Current state of economizer. Off = Outdoor air is not suitable to augment cooling. On = Outdoor air is suitable to augment cooling.

StatusEconOn The status of the Aux outputStatusEconOut During MANUAL mode, AuxEconOutOn turns the AUX_ECON_OUT on(1) or off(0).StatusFilter Indicates the current filter input state. DirtyFilter can be generated by either FilterPressure voltage input or

DirtyFilter digital input. StatusIaqOvr When an economizer is configured, IaqOverRideOn indicates the current state of the indoor air quality, and is

used by the control process to open the economizer damper to let in more outside air. 1 means poor indoor air quality, and 0 means indoor air quality is OK. When IaqOverRide is 1, the IAQ_OVERRIDE alarm is initiated.

StatusManOcc Reports the network manual occupancy state from network point CmdManualOcc. The valid enumerated states are: Occ = space is occupied; UnOcc = space is not occupied; Bypass = the space is occupied for the BypTime after CmdManualOcc first becomes Bypass. If CmdManualOcc changes to another value, the timer is stopped; Standby = space is on �Standby�. Null = No manual occupancy control is requested.

StatusMode Indicates the current StatusMode of the controller determined by many inputs and arbitrated by control logic. The valid enumerated values are: StartUpWait = after application restart or power up. Prevent multiple controllers from starting major electrical loads simultaneously when power is restored to a building; Heat = Heat energy is being supplied to the controlled space; Cool = Cooling energy is being supplied to the controlled space; Off = All temperature control and Free1 is off. Frost protection & smoke control is still sensed. NodeDisableAlrm initiated.; Disabled = All temperature control is off. Frost protection is no longer sensed. NodeDisableAlrm initiated.; SmokeEmerg = Controller is in smoke emergency. SmokeAlrm is initiated. FreezeProtect = Window is open and heating or cooling is turned off.

StatusOcc Occupancy state being called for by the thermostat including the local schedule or activation of Temporary Occupied or Continuous Occupied buttons: Occ, UnOcc

StatusOcySen Current state of the Occupancy sensor. Occ, UnOcc, Null = no occupancy sensor or failed network occupancy sensor.

StatusOvrd Effective manual over ride state by various inputs. The valid enumerated values are: Occ = Occupied; UnOcc = Unoccupied; Bypass = Bypass timer is running in either this node or another node and the effective manual override is occupied; Standby = Standby mode; Null = no manual override of the scheduled occupancy.

Table 31. Remote Point Functions. (Continued)

Remote Point Name Function

Page 90: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

74-3679�1 90

StatusSched Calculated from TimeClckOcc and Sched Occ. Note: If Time clock is configured, it has higher priority than Time of Day network input. (Occ, UnOcc, Standby)

StatusSmoke Indicates the current state of the SmokeMonitor input used by the control process and is read from another controller via the network and/or the local sensor. If either is 1, then SmokeDetector is 1 meaning that smoke is detected. Otherwise SmokeDetector is 0, meaning smoke is not detected. When smoke monitor is 1, the algorithm controls as per the settings found in controller congiuration.

StatusWndw The state of the digital input configured and wired to a window open sensor switch. 1 (input open circuit) means that the window is open, and 0 (input shorted) means that the window is closed.

SupplyTemp The temperature of the air being supplied to the variable air volume control box.SupplyTempError Controller diagnostic error message.tCool1 The status of cool 1 outputtCool2 The status of cool 2 outputtCool3 The status of cool 3 outputtEmHeat1 The status of emergency heat 1 outputtEmHeat2 The status of emergency heat 2 outputTempControlPt The current temperature control point (i.e., the current actual space temperature set point which the controller is

using) calculated from the various Set Points, operating modes, network variable inputs, and start-up parameters.

TerminalLoadOut The demand for supply energy. Positive numbers are cooling demand and negative numbers are heating demand. 100 percent is full capacity of the terminal capacity (valves/dampers at 100 percent setting). Terminal loads greater than 100 percent indicate that the terminal is not able to supply the required heating or cooling energy. TerminalLoadOut is used for coordination within the HVAC subsystem and energy management decisions by the supply equipment.

tFanOn The status of the fan outputtHeat1 The status of heat 1 outputtHeat2 The status of heat 2 outputtHeat3 The status of heat 3 outputTimeClockOcc Shows the state of the physical time clock input �ORed� with the network input. The valid enumerated values

are: ST_OFF means OC_UNOCCUPIED; ST_ON means OC_OCCUPIED when either the physical input or the netowrk input state is ON; ST_NUL means the time clock input is not configured and the network point state is SW_NUL.

Time Clock In Controller network input used for time clock. Off = Unoccupied; On - Occupied. Note: This is not the same as time of day programming. Standby operation and Intelligent Adaptive Recovery are not available.

UnitAlarm When there is an alarm reported, then UnitAlarm is set to 1, else it is set to 0. If alarms reporting is suppressed via Manual Mode, then UnitAlarm is set to AlarmNotifyDisabled.

UnitInAlarm When there is an alarm reported, then UnitInAlarm is set to 1, else it is set to 0. If alarms reporting is suppressed via Manual Mode, then UnitInAlarm is set to ALARM_NOTIFY_DISABLED.

UnitSecHeat If the controller is configured heat pump, reports the current percentage of auxiliary heating stages turned on when the controller is in the HVAC_HEAT or HVAC_EMERG_HEAT mode. If the controller is not configured as heat pump, it is set to zero.

WaterSHPEnable Indicates if the heat pump is enabled. 0 = disabled; 1 = enabled.Window Contact In Controller network window open input. If either the network input or the local sensor is active, the window open

algorithm will be in effect. Off = window closed; On = window open.WindowOpen The state of the digital input configured and wired to a window open sensor switch. 1 (input open circuit) means

that the window is open, and 0 (input shorted) means that the window is closed.WSHP Enable Out Controller network input used for enabling the compressor stages in heat pump applications. Typically

nviWSHPEnable is bound to a water flow sensor that detects heating/cooling water supplied to the heat pump. If there is no water flowing the compressor is disabled.

Table 31. Remote Point Functions. (Continued)

Remote Point Name Function

Page 91: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

91 74-3679�1

APPENDIX C � ENUMERATED DEFINITIONSTable 32. LonMark® HVAC Operating Mode Enumerated Definitions.

a If a code is received that is not applicable the default value of AUTO is assumed.b Emergency Heat is only applicable for objects configured as heat pump.c Applicable only to control loops configured as thermostat.d No control objects in XL15C support HVAC Operating Mode. The logic loops can be used to encode the network output and

decode the network input for use in central plant functions.

HVAC Operating

Mode Value Definition

Applicable Toa

Q7300H CVAHU Unit Vent VAV II FCU CHC XL15Ac XL15Cd T7350HAuto 0 Controller automatically

changes modeX X X X X X X X X

Heat 1 Heating only X X X X X X X X XMorning Warmup

2 Application specific morning warmup

X X X X

Cool 3 Cooling only X X X X X X X X XNight Purge

4 Application specific night purge X X X X

Pre-Cool 5 Application specific pre-cool X XOff 6 Controller not controlling

outputsX X X X X X X X

Test 7 Equipment being tested X XEmergency Heat b

8 Emergency heat mode for heat pumps

X X X X X X X

Fan Only 9 Air not conditioned, fan turned on

X X X X X X

Page 92: 74-3679-1 - Light Commercial Building Solutions

LIGHT COMMERCIAL BUILDING SOLUTION

Automation and Control SolutionsHoneywell International Inc. Honeywell Limited-Honeywell Limitée1985 Douglas Drive North 35 Dynamic DriveGolden Valley, MN 55422 Scarborough, Ontario M1V 4Z9customer.honeywell.com

® U.S. Registered Trademark© 2005 Honeywell International Inc.74-3679�1 B.B. Rev. 04-05

Neuron®, LONWORKS®, LONMARK®, and LONTALK® are registered trademarks of Echelon® Corporation.

LONSPEC� and LONSTATION� are trademarks of Echelon® Corporation.

By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.