7. Brayton Cycle and Combined Cycle - Engsoft · 2018-01-13 · Thermodynamics 7. Brayton Cycle 4 /...
Transcript of 7. Brayton Cycle and Combined Cycle - Engsoft · 2018-01-13 · Thermodynamics 7. Brayton Cycle 4 /...
Thermodynamics 7. Brayton Cycle 1 / 126
7. Brayton Cycle and Combined Cycle
Thermodynamics 7. Brayton Cycle 2 / 126
Starter &
Gear Box
Air Inlet CompressorCombustor
Turbine Exhaust
VIGV
Air Extraction
PortsDiffuser
Transition
Piece
Cold Section Hot Section
7FA Gas Turbine for Power Generation
Thermodynamics 7. Brayton Cycle 3 / 126
Idealized Brayton Cycle [1/3]
Thermodynamics 7. Brayton Cycle 4 / 126
The entering air is compressed to higher pressure.
No heat is added. However, compression raises the air temperature so that the discharged air has
higher temperature and pressure.
The mechanical energy transmitted from the turbine is used to compress the air.
Compression Process (1 2)
Compressed air enters the combustor, where fuel is injected and combustion occurs.
Combustion occurs at constant pressure. However, pressure decreases slightly in the practical process.
Although high local temperatures are reached within the primary combustion zone (approaching
stoichiometric conditions), the combustion system is designed to provide mixing, burning, dilution,
cooling.
Combustion mixture leaves with mixed average temperature.
The chemical energy contained in the fuel is converted into thermal energy.
Combustion of fuel is irreversible process, and entropy is produced during the combustion of the fuel.
Combustion Process (2 3)
Idealized Brayton Cycle [2/3]
Thermodynamics 7. Brayton Cycle 5 / 126
The thermal energy contained in the hot gases is converted into mechanical work in the turbine.
This conversion actually takes place in two steps:
• Nozzle: the hot gases are expanded and accelerated, and a portion of the pressure energy is
converted into kinetic energy.
• Bucket: a portion of the kinetic energy is transferred to the rotating buckets and converted into
mechanical work.
Some of the work produced by the turbine is used to drive the compressor, and the remainder is used to
drive load equipment, such as generator, ship propeller, and pump, etc.
Typically, more than 50% of the work produced by the turbine section is used to power the compressor.
Expansion Process (3 4)
Exhaust Process (4 1)
This is a constant-pressure cooling process.
This cooling is done by the atmosphere, which provides fresh, cool air as well.
The actual cycle is an “open” rather than “closed”.
Idealized Brayton Cycle [3/3]
Thermodynamics 7. Brayton Cycle 6 / 126
Simple Cycle
The term simple cycle is used to distinguish this configuration from the complex cycles, which utilizes
additional components, such as heat exchanger for regeneration, intercooler, reheating system, or steam
boilers.
This cycle is suitable for a fixed speed and fixed load operation, such as power generation.
In order to analyze gas turbine system in a convenient form, the assumptions listed below are frequently
used.
1) The working fluid is treated as the air. The air is an ideal gas and has a constant specific heat. (In
practice, there is a change in the composition of the working fluid because of the combustion process)
2) The combustion process is replaced by a heat transfer process from an external source. In other words,
the mass flow rate remains constant throughout the system.
3) The inlet and exhaust processes are replaced by a constant pressure process that will in turn complete
the gas turbine cycle.
4) All processes are internally reversible.
The combination of these assumption is called the air-standard cycle approach.
General Notes
Thermodynamics 7. Brayton Cycle 7 / 126
Heat and Work
754 MJ/s
(100%)
205 MW
(27.2%)
203 160 119 MW = 482 MW (63.9%)
277 MW (Net Output)
(36.7%)
272 MJ/s
(36.1%)
Simple Cycle
Thermodynamics 7. Brayton Cycle 8 / 126
Cycle Arrangement
Simple Cycle
Compressor
Fuel Combustor
Turbine
Air
Power
Exhaust gas1
243
p
2
1
T
(h)
s
qin
3
41
2
3
4
qout
winwout
win
wout
qin
qout
Thermodynamics 7. Brayton Cycle 9 / 126
Compressor Work (|CW|) = Turbine Work (|TW|)
Coo hhCW /1,2,
Coop TTc /1,2,
11
1
1,
2,1,
1,
2,1,
o
o
C
op
o
o
C
op
p
pTc
T
TTc
1
1
1,
CPR
Tc
C
op
4,3, ooT hhTW
4,3, oopT TTc
1
3,
4,
3,
3,
4,
3, 11o
o
opT
o
o
opTp
pTc
T
TTc
1
3, 1 TPRTc opT
11
1
3,
1,
1
CPR
T
TTPR
oTC
o
h
s
1
2
3
4
3
4
2
Compressor – Turbine Matching
Compressor
Fuel Combustor
Turbine
Air
Power
Exhaust gas1
24
3
Thermodynamics 7. Brayton Cycle 10 / 126
Process Component Heat Work Process
12 Compressor q12 = qC = 0 w12 = wC = (h2h1) Power in (adiabatic compression)
23 Combustor q23 = qB = h3h2 w23 = wB = 0 Heat addition at constant pressure
34 Turbine q34 = qT = 0 w34 = wT = h3h4 Power out (adiabatic expansion)
41 Exhaust q41 = qE = (h4h1) w41 = wE = 0 Heat release at constant pressure
Simple Cycle Analysis [1/13]
121212 whhq
p
2
1
T
(h)
s
qin
3
41
2
3
4
qout
winwout
win
wout
qin
qout
Thermodynamics 7. Brayton Cycle 11 / 126
0 5 10 15 20Pressure Ratio [r]
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Th
erm
alE
ffic
ien
cy
Thermal efficiency in a simple cycle gas
turbine increases with pressure ratio
and specific heat ratio.
The increasing rate of the thermal
efficiency is getting smaller as the
pressure ratio increases.
4
3
1
2
p
p
p
pr
crth
111
/1
1
rc
Thermal Efficiency
Simple Cycle Analysis [2/13]
2
1
23
14
23
1423
23
4123
23
3412 11T
T
TT
TT
hh
hhhh
q
q
ww
q
w
inputheat
ouputworknet
in
sys
th
Thermodynamics 7. Brayton Cycle 12 / 126
Specific Work Output
Simple Cycle Analysis [3/13]
1
3
T
Tt
Specific work output:
124341342312 TTcTTcwwwww ppsys
1
111
11 /1
/1
1
c
ctr
rt
Tc
w
p
sys
The specific work output, which is the output per unit mass flow rate of working fluid, is a function of
pressure ratio and maximum cycle temperature.
The specific work output increases with the pressure ratio when the maximum cycle temperature is greater
than a certain value.
There is a pressure ratio having a maximum specific work out in a constant t-curve.
4
3
1
2
p
p
p
pr
1
rc
0 5 10 15 20Pressure Ratio [r]
0.0
0.5
1.0
1.5
2.0
Sp
ecific
Wo
rkO
utp
ut[w
/CT
]sys
1p
t = 2
t = 3
t = 4
t = 5
Thermodynamics 7. Brayton Cycle 13 / 126
Simple Cycle Analysis [4/13]
Optimum Pressure Ratio for a Given TIT [1/3]
There are different optimum pressure ratios in
terms of thermal efficiency and specific work
output for a given maximum cycle temperature.
The thermal efficiency increases with the
pressure ratio, and it has a maximum value
when the air temperature at the compressor
outlet is equal to TIT.
In this limiting case, the cycle net work tends
toward zero, and the thermal efficiency
approaches the Carnot efficiency. In terms of
available work output (= turbine work –
compressor work), it increases with pressure
ratio and reaches a maximum at a certain
pressure ratio, then it becomes smaller, and
finally reaches zero when the air temperature at
the compressor outlet is equal to TIT.
Therefore, it is clear that there are different optimum pressure ratios in terms of thermal efficiency and
specific work output for a given maximum cycle temperature.
This means that the maximum net specific work and the maximum thermal efficiency do not occur at the
same pressure ratio. Therefore, in designing gas turbines, the design pressure ratio must be a compromise
between the maximum thermal efficiency and the maximum specific work.
T
(h)
s
1
2
3
4
4
3
2
2
4
3
Tmax
Thermodynamics 7. Brayton Cycle 14 / 126
Simple Cycle Analysis [5/13]
This can be understand more easily with the
investigation of the diagram shown relationship among
thermal efficiency, specific output, and pressure ratio.
In a real (non-ideal) gas turbine, the specific work
produced by the turbine increases more rapidly than
the specific work that the compressor consumes, as
the pressure ratio increases (from 5 to 8).
As a result, both shaft specific work output and
efficiency increase with pressure ratio.
As the pressure ratio increases, the compressor outlet
temperature also increases. This in turn reduces the
combustor temperature rise necessary to achieve a
given TIT. As a result, the combustor heat input
decreases and cycle efficiency increases.
Optimum Pressure Ratio for a Given TIT [2/3]
Specific output, MW/lb/s
Th
erm
al e
ffic
ien
cy
Maximum thermal efficiency
Maximum shaft output
Pressure ratio = 5
1015
20
TIT = 1,800F (982C)
Thermodynamics 7. Brayton Cycle 15 / 126
Simple Cycle Analysis [6/13]
At the point corresponding to the maximum shaft specific work output (turbine specific work produced
minus compressor specific work consumed), the turbine specific work produced and the compressor
specific work consumed increase at the same rate.
As pressure ratio increases further (beyond the maximum shaft output), the compressor specific work
consumed increases as a greater rate than the turbine specific work produced and, as a result, the shaft
work output actually decreases.
However, because the combustor heat input continues to decrease, the efficiency continue to increase as
pressure increases (from 8 to 16). The reason for this is that the shaft specific work output decreases
because compressor specific work consumed is increasing faster than turbine specific work output, as the
pressure ratio increases. Therefore, shaft specific work output decreases.
However, fuel consumption is reduced and overall thermal efficiency increases because of higher
compressor outlet temperatures due to higher pressure ratios.
As the pressure ratio increases further (greater than 16), the increase in compressor specific work
consumed offsets the advantage of higher compressor outlet temperature and overall efficiency begins to
decrease.
The actual pressure ratio at which this occurs depend on the specific gas turbine considered.
Optimum Pressure Ratio for a Given TIT [3/3]
Thermodynamics 7. Brayton Cycle 16 / 126
The Performance Map of a Simple-Cycle Gas Turbine
Simple Cycle Analysis [7/13]
Thermodynamics 7. Brayton Cycle 17 / 126
Practical Brayton Cycle
h1 = enthalpy at compressor inlet
h2s = enthalpy at constant entropy and
compressor discharge pressure
h2 = actual enthalpy at compressor discharge
pressure
h3 = enthalpy at turbine inlet
h4s = enthalpy at constant entropy and turbine
exit pressure
h4 = actual enthalpy at turbine exit pressure
p
2
1
T
(h)
s
qin
3
4 1
2s
3
4
qout
win
wout
2
4s
12
12
hh
hh sC
s
Thh
hh
43
43
Simple Cycle Analysis [8/13]
Thermodynamics 7. Brayton Cycle 18 / 126
General Expression of the Simple Cycle Net Work and Efficiency [1/4]
1
1
1
21
12T
TTcTTcw s
C
p
sp
C
C
crp
p
T
T s
1
1
1
2
1
2
where, r is a pressure ratio. Therefore, compressor
work is
11 c
Tcw
C
p
C
Similarly, the turbine work is given by
cTcTTcw pTspTT
11343
Simple Cycle Analysis [9/13]
T
(h)
s
1
2s
3
4
4s
2
Thermodynamics 7. Brayton Cycle 19 / 126
General Expression of the Simple Cycle Net Work and Efficiency [2/4]
CTnet www
11
1
c
tc
Tcw TC
C
p
net
1
2
1
3123
T
T
T
TTcTTcq ppin
12
12
TT
TT sC
1
11
1
2 cT
T
C
where, t is a maximum temperature ratio. Therefore, heat input is expressed by
111
23 ctTc
TTcq C
C
p
pin
11
1
ctc
ctc
q
w
C
TC
in
netcy
Four major parameters affecting the cycle efficiency of a simple gas turbine are pressure ratio (c), TIT
(t), compressor efficiency, and turbine efficiency.
1
3
T
Tt
Simple Cycle Analysis [10/13]
Thermodynamics 7. Brayton Cycle 20 / 126
General Expression of the Simple Cycle Net Work and Efficiency [3/4]
Pressure Ratio
t = 3.25
t = 4.73
t = 5.69
Reversible
0.7
0.1
Th
erm
al E
ffic
ien
cy
1
3
T
Tt
2 4 6 80 10 12 14 16 18 20 22 24 26 28 30
0.6
0.5
0.4
0.3
0.2
0
T = 0.90
C = 0.85
Simple Cycle Analysis [11/13]
Thermodynamics 7. Brayton Cycle 21 / 126
General Expression of the Simple Cycle Net Work and Efficiency [4/4]
In general, the cycle efficiency is relatively low, because of the high EGT, and because a significant portion
of the turbine output is used for compressor operation.
For a given turbine and compressor efficiency, the cycle performance is determined by the TIT and pressure
ratio.
The TIT is usually fixed by the metallurgical temperature limit of the first row of turbine blade.
As the TIT increases, the cycle efficiency is greatly improved.
The impact of the pressure ratio on the cycle efficiency is quite different.
There is an optimum pressure ratio that produces the maximum cycle efficiency.
The optimum pressure ratio increases with the TIT.
Simple Cycle Analysis [12/13]
Thermodynamics 7. Brayton Cycle 22 / 126
Simple Cycle Efficiency
Shaft power application
Simple Cycle Analysis [13/13]
Thermodynamics 7. Brayton Cycle 23 / 126
Simple Cycle
[Exercise 4.1]
Calculate the cycle efficiency and net work per pound of air. A gas turbine is operated under the
following conditions.
• Compressor inlet pressure and temperature 14.7 psia, 60F
• Pressure ratio 12
• Compressor efficiency 0.88
• Turbine inlet temperature 2000F
• Turbine efficiency 0.90
• Average constant pressure specific heat 0.25 Btu/lb-R
• Specific heat ratio 1.4
The pressure drops in the combustor, compressor inlet, and turbine outlet are assumed to be negligible.
T
(h)
s
1
2s
3
4
4s
2
Thermodynamics 7. Brayton Cycle 24 / 126
[Solution]
Process 12s is an isentropic process. Thus,
T2s = T1 2.03394 = 1057.6 R
T2 = 1130.9 R
Similarly, process 34s is an isentropic process. Thus,
T4s = 1209.5 R
T4 = 1334.6 R
03394.212 4.1
4.01
1
2
1
2
p
p
T
T s
12
12
TT
TT sC
1
4
3
4
3
ss p
p
T
T
s
TTT
TT
43
43
Simple Cycle
Thermodynamics 7. Brayton Cycle 25 / 126
[Solution]
Heat input in the combustor is
Compressor work and turbine work are
Cycle efficiency is
cy = 0.387 or 38.7%
Cycle network is
128.6 Btu/lb
23 TTcq pin
12 TTcw pC
43 TTcw pT
23
141TT
TT
q
ww
in
CTcy
CTnet www
11
1
ctc
ctc
q
w
C
TC
in
netcy
Simple Cycle
Thermodynamics 7. Brayton Cycle 26 / 126
Compressor
Fuel
Combustor
Turbine
Air
Power
Exhaust gas
Heat exchanger
1
2
5
34
6
Regenerative Cycle
Cycle Arrangement
p
2
1
T
s
3
41
2
3
46
5
5
6
A B C D
Thermodynamics 7. Brayton Cycle 27 / 126
General Notes
Regenerative Cycle
Normally, gas turbine exhaust gas temperature is higher than that of air discharging from a compressor.
In order to increase the gas turbine efficiency, the gas turbine exhaust gas can be used to heat the air leaving
the compressor, thus reducing the amount of fuel required to reach the firing temperature.
This is achieved by the use of regenerators or recuperators, which heat the compressor exit air by the
exhaust gases from the turbine exit.
Regenerators or recuperators are usually used in small- to intermediate-sized gas turbines having output less
than 10 MW.
Regenerative cycle is also called as heat exchange cycle.
Thermodynamics 7. Brayton Cycle 28 / 126
A Typical Regenerative Cycle Gas Turbine
Air flow path – Mercury 50 gas turbine (Solar)
Power = 4.6 MW
PR = 9.9:1
TIT = 2200F (1204C)
th = 38.5%
Regenerative Cycle
Thermodynamics 7. Brayton Cycle 29 / 126
Regenerative Cycle Analysis [1/5]
Cycle Analysis
Process Component Heat Work Process
12 Compressor q12 = qC = 0 w12 = wC = (h2h1) Power in (adiabatic compression)
25 Heat Ex. q52 = qin = h5h2 w52 = wHE = 0 Heat addition through heat exchanger
53 Combustor q53 = qB = h5h3 w53 = wB = 0 Heat addition in a burner
34 Turbine q34 = qT = 0 w34 = wT = h3h4 Power out (adiabatic expansion)
46 Heat Ex. q46 = qout = (h6h4) w46 = wHE = 0Heat transfer to compressor discharged air
(h4h6 = h5h2)
61 Exhaust q61 = qE = (h6h1) w61 = wE = 0 Heat release to atmosphere
121212 whhq
p
2
1
T
s
3
41
2
3
46
5
5
6
A B C D
Thermodynamics 7. Brayton Cycle 30 / 126
0 5 10 15 20Pressure Ratio [r]
0.0
0.5
1.0
1.5
2.0S
pecific
Wo
rkO
utp
ut[w
/CT
]sys
1p
t = 2
t = 3
t = 4
t = 5
압력비 vs 비출력
The regenerative cycle has
the exactly same specific
work out with a simple cycle.
11
11
c
ct
Tc
w
p
sys
1
3
T
Tt
1
rc
1
2
p
pr
Regenerative Cycle Analysis [2/5]
Thermodynamics 7. Brayton Cycle 31 / 126
압력비 vs 열효율
t
cth 1
1
3
T
Tt
1
rc1
2
p
pr
4
1
3
2 11T
T
T
Tth
Regenerative Cycle Analysis [3/5]
0 5 10 15 20Pressure Ratio [r]
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
Th
erm
alE
ffic
ien
cy
Simple cycle efficiency
t = 2
t = 3
t = 4
t = 5t = 6
t
cth 1
사이클 최고온도가 일정한 상태에서압력비가 작아질수록 재생사이클 가스터빈 열효율 향상.
압력비가 일정한 상태에서 최고온도가 증가할수록 열효율이 향상된다.
4
1
3
2 11T
T
T
Tth
재생사이클 가스터빈은 TIT가 증가할수록, 그리고 EGT가 증가할수록 열효율 향상.
Thermodynamics 7. Brayton Cycle 32 / 126
The cycle efficiency decreases as the pressure ratio increases, which is opposite to that of a simple cycle.
This is due to the fact that, as the pressure ratio increases the air temperature exiting the compressor
increases and ultimately will exceed that of the turbine exhaust gas temperature. Then heat in the heat
exchanger (regenerator) will be lost from the air to the exhaust gases instead of desired gain.
The efficiency with lower temperatures, say at t=2, is seen to become negative soon after the pressure
ratio 11.3 is exceeded. The reason is that the temperature at compressor outlet actually exceeds the
assumed combustion temperature in this case.
In many cases, regeneration is not desirable. This is because the efficiency increases with pressure ratio, if
regenerative cycle is not employed.
Efficiency, with regenerative cycle rises very rapidly with increase in maximum temperature of the cycle.
Lower pressure ratios and high cycle temperatures are favorable for the regenerative cycle, since a large
heat recovery is then possible.
After the efficiency becomes equal to that of simple cycle, any further increase of pressure ratio will yield an
efficiency which is lower than that of simple cycle and that is of no interest.
Power output may be reduced by 10% for a given size of plant because of the pressure losses occurred in
the heat exchanger.
Normally, micro gas turbines having lower thermal efficiency adopts this kind of arrangement to improve
thermal efficiency.
Regenerative Cycle Analysis [4/5]
Thermodynamics 7. Brayton Cycle 33 / 126
Cycle Efficiency of Practical Regenerative Cycles
Regenerative Cycle Analysis [5/5]
24
25
24
25
TT
TT
hh
hhreg
53
1243
TT
TTTT
q
ww
in
CTcy
2423
1243
TTTT
TTTT
reg
cy
1
2
1
3
3
4
1
2
1
3
1
2
1
3
3
4
1
3 1
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
reg
cy
11
1
2
C
c
T
T
cT
TT
111
3
4
It can be seen that the irreversibility of the system significantly lower the cycle efficiency.
Compared with the simple gas turbine system, the optimum pressure ratio is smaller for the regenerative
cycle.
The small pressure ratio means a small cycle net output.
Therefore, the cost associated with this output reduction must be weighted against the saving that can be
affected by the cycle efficiency improvement.
Pressure Ratio
t = 4.73
t = 5.69
Reversible0.7
0.1
Therm
al E
ffic
iency
2 4 6 80 10 12 14 16 18 20 22 24 26 28 30
0.6
0.5
0.4
0.3
0.2
0
1
3
T
Tt
T = 0.90
C = 0.85
reg = 0.80
0.8
0.9
1.0
Practicalt = 5.69
t = 4.73
Thermodynamics 7. Brayton Cycle 34 / 126
Regenerative Cycle
This modified form is more suitable for fuels those combustion products contain constituents which may
corrode or erode the turbine blades.
It is much less efficient than the simple cycle power plant because of the efficiency of the heat exchanger.
Such a cycle may be considered only if low grade fuels are to be used.
Gas turbines of a more complicated design (i.e., with intermediate cooling in the compressor or
recuperator) are less suitable for combined cycle plants. They normally have a high simple cycle
efficiency combined with a low exhaust gas temperature, so that the efficiency of the water/steam cycle
is accordingly lower.
An Alternative Regenerative Cycle
Compressor
FuelCombustor
Turbine
Air
Power
Exhaust gasHeat exchanger
1
2 34
Thermodynamics 7. Brayton Cycle 35 / 126
Reheat Cycle
Cycle Arrangement
FuelReheat combustor
LP turbine
Power
Exhaust gas5
4 6
Compressor
Fuel
Combustor
Air
1
2
3
HP turbine
p
2
1
T
s
3
61
2
5
6
4 54
3
4
4
Thermodynamics 7. Brayton Cycle 36 / 126
A Typical Reheat Cycle Gas Turbine for Power Generation - GT26 Gas Turbine
Reheat Cycle
Thermodynamics 7. Brayton Cycle 37 / 126
Reheat Cycle
F-14
Reheat Cycle Gas Turbine for Military Aviation
F100-PW-229 (F-15, F-16)Reheat Cycle Gas Turbine for Civil Aviation
Olympus 593
Thermodynamics 7. Brayton Cycle 38 / 126
Cycle Analysis
Reheat Cycle Analysis [1/3]
Process Component Heat Work Process
12 Compressor q12 = qC = 0 w12 = wC = (h2h1) Power in (adiabatic compression)
23 Combustor q23 = qB = h3h2 w23 = wB = 0 Heat addition in a burner
34 Turbine q34 = qHPT = 0 w34 = wHPT = h3h4 Power out (adiabatic expansion)
45 Reheat q45 = qin,R = h5h4 w45 = wR = 0 Heat addition in a reheat combustor
61 Exhaust q61 = qE = (h6h1) w61 = wE = 0 Heat release to atmosphere
121212 whhq
p
2
1
T
s
3
61
2
5
6
4 54
3
4
4
Thermodynamics 7. Brayton Cycle 39 / 126
Reheat Cycle Analysis [2/3]
11
121
max
c
ct
TC
w
p 1
3
T
Tt
1
rc1
2
p
pr
0 5 10 15 20Pressure Ratio [r]
0.0
0.5
1.0
1.5
2.0
2.5
Sp
ecific
Wo
rkO
utp
ut[w
/CT
]
t = 2
t = 3
t = 4
t = 5
Reheat cycle
Simple cycle
sys
p1
0 5 10 15 20Pressure Ratio [r]
0.0
0.1
0.2
0.3
0.4
0.5
0.6
Th
erm
alE
ffic
ien
cy
Simple cycleefficiency
t = 2
t = 3
t = 4
t = 5
ctct
cctth
/2
1/112
Thermodynamics 7. Brayton Cycle 40 / 126
An increase of specific work output can be obtained by splitting the expansion and reheating the gas
between the high pressure and low pressure turbines.
The increase of specific work output can be seen in p- diagram.
The turbine work increase is obvious from the fact that the vertical distance between any pair of constant
pressure lines increases as the entropy increases. Thus,
(T3T4) + (T5 T6) (T3 T4’)
The shaft length becomes longer and the control of shaft vibration becomes difficult.
The maximum temperature in low pressure turbine is the same as in high pressure turbine.
Thermal efficiency of the reheat cycle is lower than that of the simple cycle. This is because the reheat
cycle is made by the combination of a simple cycle and a less efficient cycle which is operated over a lower
temperature range.
Reheat Cycle Analysis [3/3]
Thermodynamics 7. Brayton Cycle 41 / 126
Intercooled Cycle
Cycle Arrangement
HP compressor
Fuel
Combustor
Power turbine
Air
Power
Intercooler
Coolant in Coolant out
HPT
LP compressor
LPT
1 2 3 4 5
6
p
2
1
T
s
3
6 1
2
5
6
4 5
4
3
2
2
Thermodynamics 7. Brayton Cycle 42 / 126
Typical Intercooled Cycle Gas Turbines
Air-to-Water Heat Exchanger Air-to-Air Heat Exchanger
Intercooler
LMS 100 (GE)
Thermodynamics 7. Brayton Cycle 43 / 126
The specific work output of a gas turbine may be improved substantially by reducing the work of
compression.
If, therefore, the compression process is carried out with intercooling, the work of compression will be
reduced, as can be seen in p- diagram.
The compressor work decrease is obvious from the fact that the vertical distance between any pair of
constant pressure lines decreases as the entropy decreases. Thus,
(T2T1) + (T4 T3) < (T2′ T1)
Heat is extracted by an intercooler between the first and second compressors.
Rejecting heat worsens SFC, since more fuel should be burnt to raise cooler compressor delivery air to any
given TIT.
Therefore, the thermal efficiency of the intercooled cycle will be less than that for a simple cycle.
Intercooling is useful when the pressure ratios are high and the efficiency of the compressor is low.
Intercooled Cycle
Thermodynamics 7. Brayton Cycle 44 / 126
Intercooled Cycle Analysis [1/5]
Cycle Analysis
Process Component Heat Work Process
12 LP compressor q12 = qC = 0 w12 = wLPC = (h2h1) Power supply in a LP compressor
23 Intercooler q23 = qIC = (h3h2) w23 = wIC = 0 Heat rejection in an intercooler
34 HP compressor q34 = qC = 0 w34 = wHPC = (h4h3) Power supply in a HP compressor
45 Combustor q45 = qB = h5h4 w45 = wB = 0 Heat addition in a burner
56 Turbine q56 = qT = 0 w56 = wT = h5h6 Power out (adiabatic expansion)
61 Exhaust q61 = qE = (h6h1) w61 = wE = 0 Heat release to atmosphere
121212 whhq
p
2
1
T
s
3
61
2
5
6
4 5
4
3
2
2
Thermodynamics 7. Brayton Cycle 45 / 126
압력비 vs 비출력
Simple CycleIntercooled Cycle
0 5 10 15 20Pressure Ratio [r]
0.0
0.5
1.0
1.5
2.0
Sp
ecific
Wo
rkO
utp
ut[w
/CT
]
t = 2
t = 3
t = 4
t = 5
max
p1
0 5 10 15 20Pressure Ratio [r]
0.0
0.5
1.0
1.5
2.0
Sp
ecific
Wo
rkO
utp
ut[w
/CT
]sys
1p
t = 2
t = 3
t = 4
t = 5
121
max cc
tt
Tc
w
p 1
3
T
Tt
1
rc
Intercooled Cycle Analysis [2/5]
Thermodynamics 7. Brayton Cycle 46 / 126
압력비 vs 효율
0 5 10 15 20Pressure Ratio [r]
0.0
0.1
0.2
0.3
0.4
0.5
0.6
Th
erm
alE
ffic
ien
cy
Simple cycleefficiency
t = 2
t = 3
t = 4
t = 5
0 5 10 15 20Pressure Ratio [r]
0.0
0.1
0.2
0.3
0.4
0.5
0.6
Th
erm
alE
ffic
ien
cy
t = 2
t = 3
t = 4
t = 5
Intercooled Cycle Reheat Cycle
1
3
T
Tt
1
rcct
cctth
2/1
Intercooled Cycle Analysis [3/5]
Thermodynamics 7. Brayton Cycle 47 / 126
A Typical Spray Intercooling Gas Turbine
LM6000-SPRINT Gas Turbine
LM6000 (GE)
Intercooled Cycle Analysis [4/5]
Thermodynamics 7. Brayton Cycle 48 / 126
Spray Intercooling
Intercooling can also be accomplished by fog spraying atomized water between the HP and LP
compressors.
GE LM6000-SPRINT is one example of such a system.
Water in injected through 24 spray nozzles.
Water is atomized to a droplet diameter of less than 20 microns using high-pressure air taken from the
eighth-stage of HP compressor.
Injecting water significantly reduces the compressor outlet temperature.
The result is higher output and better efficiency.
Output increases of more than 20% and efficiency increases of 3.9% are possible on 90F(32C) day.
Intercooled Cycle Analysis [5/5]
Thermodynamics 7. Brayton Cycle 49 / 126
[ A simple schematic diagram of a combined cycle system ]
Compressor
Fuel Combustor
Turbine
Air
Steam Turbine
Exhaust gas1
2
4
3
G G
HR
SG
5
6
7
8
9Condenser
Pump
Combined Cycle
Cycle Arrangement
Thermodynamics 7. Brayton Cycle 50 / 126
Combined cycle power plants have a higher
thermal efficiency because of the application of
two complementary thermodynamic cycles
Combined Cycle
Condenser
(heat out)
T
s
Topping cycle
Bottoming cycle
Combustion
(heat In)
Stack
(heat
out)
Thermodynamics 7. Brayton Cycle 51 / 126
Condenser
G
G
Fuel
Air
Gas Turbine
Heat Recovery
Steam Generator
IP Steam LP
SteamCold Reheat
Steam
Hot Reheat
Steam
Main
Steam
Steam Turbine
Condensate Pump
Steam
Water
Fuel
Air
Three Pressure
Reheat Cycle
Combined Cycle
Thermodynamics 7. Brayton Cycle 52 / 126
The first power generation gas turbine was introduced by ABB in 1937.
It was a standby unit with a thermal efficiency of 17%.
Today the gas turbine is a major player in the huge power generation market, with orders of around 30GW
per year.
This success is due partly to large reserves of natural gas which provide a cheap fuel which is rich in
hydrogen, and therefore produces less carbon dioxide than liquid fuels.
The other factor is thermal efficiency, which for combined cycle power plants have 60%
A final advantage is the variety of gas turbines in a very wide range of power levels, up to 300MW per simple
cycle, and 500MW per combined cycle.
Power Generation Applications
Thermodynamics 7. Brayton Cycle 53 / 126
Unit Steam CycleNet Plant
Output (MW)
Heat Rate (LHV) Thermal
EfficiencyBtu/kWhr kJ/kWhr
S106B Non-Re, 3-P 59.8 7005 7390 48.7
S106FA Re, 3-P 107.1 6440 6795 53.0
S107EA Non-Re, 3-P 130.2 6800 7175 50.2
S107FA Re, 3-P 258.8 6090 6425 56.1
S107G Re, 3-P 350.0 5885 6210 58.0
S107H Re, 3-P 400.0 5690 6000 60.0
The three-pressure reheat cycle that is applied with gas turbines with exhaust gas
temperature higher than 1000F/538C.
= ---------------3412.14
Heat Rate3412.14 = constant for the number of BTU’s in a kilowatt
(1 kWh = 3412.14 Btu)
GE’s Single-Shaft STAG Ratings
Thermodynamics 7. Brayton Cycle 54 / 126
Simple cycle
Combined cycle
Thermodynamics of a Combined Cycle [1/2]
Thermodynamics 7. Brayton Cycle 55 / 126
In simple cycle application, thermal efficiency increases with the pressure ratio at a given firing
temperature.
For a given pressure ratio, thermal efficiency decrease as the TIT increases. This is because the lager
amount of cooling air for turbine blade is required as the TIT increases.
The pressure ratio resulting in maximum output and maximum efficiency change with firing temperature.
The higher the pressure ratio, the greater benefits from the increased firing temperature.
The power increases with the firing temperature at a given pressure ratio. However, efficiency decrease
because the flow of the cooling air extracted increase with the firing temperature.
Simple cycle
Combined cycle
In combined cycle applications, pressure ratio have a less pronounced effect on efficiency.
As pressure ratio increases, specific power decreases.
Thermal efficiency increases with firing temperature.
The optimum cycle parameters for combined cycle are different from simple cycle.
Simple cycle efficiency is achieved with high pressure ratios. However, combined cycle efficiency is
obtained with more modest pressure ratios and greater firing temperatures.
Thermodynamics of a Combined Cycle [2/2]
Thermodynamics 7. Brayton Cycle 56 / 126
Efficiency of Combined Cycle [1/3]
Thermodynamics 7. Brayton Cycle 57 / 126
SFGT
STGTCC
ww
CC: gross efficiency of the combined cycle
wGT: output of gas turbine
wST: output of steam turbine
qGT: heat input in the gas turbine
qSF: heat input through supplementary firing in the HRSG
SFGT
AuxSTGTnetCC
www
,
CC,net: net efficiency of the combined cycle
wAux: auxiliary consumption (=station service power consumption + electrical
losses)
Efficiency of Combined Cycle [2/3]
Thermodynamics 7. Brayton Cycle 58 / 126
The efficiency of the simple cycle gas turbine,
GT
GTGT
q
w
The efficiency of the simple cycle steam turbine,
SFExhGT
STST
w
,
GTGTExhGT qq 1,
SFGTGT
STST
w
1
The efficiency of the combined cycle without supplementary firing,
GT
GTGTSTGTGTCC
q
1
GTSTGTCC 1
Efficiency of Combined Cycle [3/3]
Thermodynamics 7. Brayton Cycle 59 / 126
[Exercise 4.2]
Calculate the combined cycle efficiency. The efficiencies are 26 and 33% for a gas turbine cycle and a steam
turbine cycle, respectively.
[Solution]
The efficiency of the combined cycle is
[Note]
This calculation is based on the assumption of no pressure drops at the various cycle locations. Therefore,
this cycle efficiency represents an optimistic estimate. When the pressure drops are taken into account, the
efficiency of the combined cycle is greatly reduced. When detailed design of a combined cycle plant is made,
it usually shows the plant efficiency in the range of 38 to 42%.
GTSTGTCC 1
504.0CC
Efficiency of Combined Cycle
Thermodynamics 7. Brayton Cycle 60 / 126
When the operation flexibility is important, such as marine applications, a mechanically independent power
turbine is used.
Compressor and high pressure turbine combination acts as a gas generator for the low pressure turbine.
Fuel flow to the combustor is controlled to achieve variation of power. This will cause a decrease in cycle
pressure ratio and maximum temperature.
At off-design conditions the power output reduces with the result that the thermal efficiency deteriorates
considerably at part loads.
Compressor
Fuel Combustor
LP Turbine
Air
Power
Exhaust gas
HP Turbine
Two-Shaft GT
Thermodynamics 7. Brayton Cycle 61 / 126
Closed Cycle
Thermodynamics 7. Brayton Cycle 62 / 126
Closed Cycle
In a closed cycle, the working fluid is continuously recirculated. It may be air or another gas such as helium.
Usually, the gas turbine is of intercooled recuperated configuration.
However, the combustor is replaced by a heat exchanger as fuel can not be burnt directly.
The heat source for the cycle may be a separate combustor burning normally unsuitable fuels, such as coal,
a nuclear energy, etc.
On leaving the recuperator, the working fluid must pass through a pre-cooler where heat is rejected to an
external medium, such as sea water, to return it to the fixed inlet temperature, usually between 15C and
30C.
The pressure at inlet to the gas turbine is maintained against leakage from the system by an auxiliary
compressor supplying a large storage tank called an accumulator.
The high density of the working fluid at engine inlet enables very high power output, which is the main
benefit of the closed cycle.
Thermodynamics 7. Brayton Cycle 63 / 126
Factors Affecting Gas Turbine Performance
Thermodynamics 7. Brayton Cycle 64 / 126
Generals
The gas turbine is a standardized machine, and can be used under widely different ambient conditions.
Manufacturers quote gas turbine performances at ISO ambient conditions of 15C(59F), 1.013 bar (14.7
psia), and 60% relative humidity.
Gas turbine performance is mainly governed by pressure ratio, turbine inlet temperature, and efficiency of
each parts.
The performance of gas turbine is affected by its inlet and exit conditions. The most important items are
pressure and temperature. Ambient weather conditions are the most obvious changes.
Since the gas turbine is an air-breathing machine, its performance is changed by anything that affects the
density and/or mass flow rate of air intake to the compressor.
A smaller weight of air requires a smaller weight of fuel to mix with, and the mixture then produces less
power when burned.
Most peak power enhancement opportunities exists in the topping cycle.
In general, however, performance enhancements to the gas turbines will carry with them an increase in
bottoming cycle performance due to an associated increase in gas turbine exhaust energy.
Duct firing within HRSG is an exceptional performance enhancement occurred in the bottoming cycle.
Thermodynamics 7. Brayton Cycle 65 / 126
Factors Affecting GT Performance
Factors to be considered individually
Is there a need for peak power production with
premium paid for the resulting power?
Does peak power demand occur on hot days
(summer peaking) only?
Is there a need to compensate the power
reduction continuously during summer period?
Is frequency support required?
Solutions for power augmentation
Supplementary firing in HRSG
Steam / water injection
GT peak load firing
GT inlet air cooling
Thermodynamics 7. Brayton Cycle 66 / 126
Options for power enhancementsTypical performance impact
Output Heat Rate
Base configuration Base Base
Evaporative cooling GT inlet air (85% effective cooler) +5.2 % -
Chill GT inlet air to 45F +10.7 % +1.6 %
GT peak load operation +5.2 % 1.0 %
GT steam injection (5% of GT airflow) +3.4 % +4.2 %
GT water injection (2.9% of GT airflow) +5.9 % +4.8 %
HRSG supplementary firing +28 % +9 %
Note: 1. Site conditions = 90F, 30% RH(Relative Humidity)
2. Fuel = NG
3. 3-pressure, reheat steam cycle
4. At sites where large power enhancement is possible, the owner must verify that the
added power is within the capabilities of the generator and transformer
Output = m h•
Various Options for Power Enhancement
Thermodynamics 7. Brayton Cycle 67 / 126
1. Ambient Temperature [1/7]
Pe
rce
nt
de
sig
n
130
120
110
100
90
80
700 20 40 60 80 100 120 F
-18 -7 4 16 27 38 49 C
Compressor inlet temperature
The output and thermal efficiency of
the gas turbines decrease as air
temperature increases. This is because
an air density decreases as the
ambient air temperature increases,
thus the mass flow rate of air
decreases because industrial gas
turbines running at constant speed are
constant volume flow machines.
The thermal efficiency decreases as
the air temperature increases. This is
because compressor driving power
increases as the air temperature
increase. In addition, heat transfer
efficiency of the blade cooling system
decreases as the air temperature
increases.
Thermodynamics 7. Brayton Cycle 68 / 126
1. Ambient Temperature [2/7]
The specific power consumed by the compressor increases
proportional to the inlet air temperature (in K) without a
corresponding increase in the turbine output.
The exhaust gas temperature increases as the inlet air
temperature increases because the turbine pressure ratio is
reduced, although the gas turbine inlet temperature remains
constant. This is the main reason for that the gas turbine
output and efficiency decrease while the ambient air
temperature increases.
However, the effect on the performance of the combined cycle
is somewhat less because a higher exhaust gas temperature
improves the performance of the steam cycle.
T
s
1
2
3
4
1
2
3
4
1
1
1,
CPR
Tcw
C
op
C
Thermodynamics 7. Brayton Cycle 69 / 126
Effect on Combined Cycle Efficiency
1. Ambient Temperature [3/7]
Rela
tive e
ffic
iency,
%
Gas turbine
100
0
Air temperature, C
105
95
10 20 30 40-10
Based on constant
condenser pressure
Steam turbine
Combined cycle
An increase in the inlet air temperature has a
slightly positive effect on the efficiency of the
combined cycle plant, while other ambient
conditions as well as condenser pressure
remain constant.
Because the increased gas turbine exhaust gas
temperature improves the efficiency of the
steam process, it more than compensates for
the reduced efficiency of the gas turbine unit.
According to the open literature, with each one-
degree temperature increase above 30°C, power
output of the gas turbines drops by 0.50%–
1.02% while efficiency drops by approximately
0.24%. Steam turbine power output and
efficiency are not significantly changed by
changing air temperature, while net CCGT power
output drops by 0.3%–0.6% and net efficiency
drops by approximately 0.01% per degree above
30°C.
Source: Kehlhofer et al., 2009
Thermodynamics 7. Brayton Cycle 70 / 126
Effect on Combined Cycle Efficiency
1. Ambient Temperature [4/7]
Com
bin
ed c
ycle
effic
iency,
%
Ambient air temperature, K
Thermodynamics 7. Brayton Cycle 71 / 126
Net efficiency of a combined cycle power plant as a function of river water temperature.
1. Ambient Temperature [5/7]
Thermodynamics 7. Brayton Cycle 72 / 126
Effect on Combined Cycle Output
The power output of the combined cycle
decreases as the inlet air temperature
increases.
In a combined cycle plant, gas turbines
contribute approximately two-thirds of the
power production, while the steam turbine
contributes the remaining one-third.
The combined cycle power output curve is
dominated by the gas turbine output curve, and
it is expected that changes in air temperature
will have more significant impact on plant
power output than changes in water
temperature.
The power output of the combined cycle is
affected differently from the efficiency because
change in mass flow of inlet air and exhaust
gases are more dominant than the exhaust gas
temperature.
Source: Kehlhofer et al., 2009
1. Ambient Temperature [6/7]
Rela
tive p
ow
er
outp
ut, %
Gas turbine
100
0
Air temperature, C
120
90
10 20 30 40-10
Based on constant
condenser pressure
110
Thermodynamics 7. Brayton Cycle 73 / 126
1. Ambient Temperature [7/7]
When the ambient temperature is low, gas turbine output and HRSG steam production are increased above
plant rating point.
Condenser (exhaust) pressure directly influenced by ambient air or cooling water temperature.
Condenser pressure is expected to be lowest at low ambient air / cooling water temperature, and exhaust
annulus velocity will be the highest.
Thermodynamics 7. Brayton Cycle 74 / 126
2. Ambient Air Pressure
Gas turbine performance is quoted at an air
pressure of 1.013 bar – ISO conditions, which
corresponds to the average pressure
prevailing at sea level.
A different site elevation and daily weather
variations result in a different pressure.
The air density reduces as the site elevation
increases. Therefore, airflow and output
decrease as the site elevation increases.
However, the air pressure has no effect on the
efficiency if the ambient temperature is
constant, even though the output decreases
as the pressure decreases. This is because
the backpressure of the gas turbine is
correspondingly lower at a lower ambient
pressure.
GT ModelCC Configu-
ration
Ambient
Temp.,CSite
Site
Elevation, m
CC Thermal
Effcy., %
CC Net
Power, MW
GT Net
Power, MW
ST Net
Power, MW
PG7221FA 2-on-128.1
(82.5F)
Las Vegas 664 53.4 437.0 285.3 151.7
Miami Sea side 53.2 475.5 312.9 162.6
Altitude x 103 feet
20 4 6 80.5
0.6
0.7
0.8
0.9
1.0
Correction
factor
Atmospheric
pressure
11.0
12.0
13.0
14.0
15.0
Co
rrection f
acto
r
Atm
osph
eric p
ressure
, p
sia
Thermodynamics 7. Brayton Cycle 75 / 126
3. Humidity
Humid air is less dense than dry air.
In the past, this effect was thought to be too small to
be considered.
However, as the size of gas turbine increases, this
effect become important.
Steam or water injection for NOx control makes this
effect more significance.
Specific humidity (kg water vapor/kg dry air)
ISO specific humidity
0.0064
60% RH
1.008
0.996
Co
rre
ctio
n f
acto
r
0.010 0.02 0.03
1.006
1.004
1.002
1
0.998
0.994
1.010
Thermodynamics 7. Brayton Cycle 76 / 126
4. Inlet & Exhaust Pressure Drop [1/5]
Inlet filter
Evaporative cooler or chiller
Anti-icing system
Silencer (The large frontal areas of the
compressors reduce the inlet velocities, thus
reducing air noise)
Thermodynamics 7. Brayton Cycle 77 / 126
Hot-end drive Cold-end drive
• In the hot-end drive configuration, the output shaft
extends out the rear of the turbine.
• The designer is faced with many constraints, such
as output shaft length, high EGT, exhaust duct
turbulence, pressure drop, and maintenance
accessibility.
• Insufficient attention to any of these details, in the
design process, often results in power loss,
vibration, shaft or coupling failures, and increased
down-time for maintenance.
• This configuration is difficult to service as the
assembly must be fitted through the exhaust duct.
• In the cold-end drive configuration, the output shaft
extends out the front of the compressor.
• The single disadvantage is that the compressor
inlet must be configured to accommodate output
shaft.
• The inlet duct must be turbulent free and provide
uniform, vortex free, flow over the all operating
range.
• Inlet turbulence may induce surge in the
compressor resulting in complete destruction of the
unit.
MS7001E, GE MS7001F, GE
4. Inlet & Exhaust Pressure Drop [2/5]
Thermodynamics 7. Brayton Cycle 78 / 126
Inlet Pressure Drop
The improved operating performance associated with a
lower inlet air velocity design must be evaluated against the
associated higher capital cost.
A similar cost evaluation determines the optimum point that
dirty air filters, which have higher pressure losses, should
be changed out.
Inlet pressure drop is a function of the inlet air system design and cleanliness of the inlet air filters.
Lower inlet air pressure losses can be achieved by designing for lower inlet air velocities through the filter,
silencer, and duct.
4. Inlet & Exhaust Pressure Drop [3/5]
Inlet pressure prop, inH2O
Co
rre
ctio
n f
acto
r
0 1 2 3 4 5 6 7 8 9 100.96
0.97
0.98
0.99
1.00
1.01
1.02
Thermodynamics 7. Brayton Cycle 79 / 126
Exhaust Pressure Drop
Higher exhaust pressure loss is primarily a function of
the exhaust system design.
For a simple cycle applications, the exhaust system
typically consists of an exhaust duct, silencers, and a
stack.
Exhaust pressure losses of 4.0 to 5.0 inH2O are typical
for simple cycle gas turbines.
For combined cycle or cogeneration applications, the
exhaust gases pass through an HRSG with the
associated additional.
Exhaust pressure losses of 10 to 17 inH2O are typical
for combined cycle and cogeneration applications
depending on the complexity of the cycle arrangement,
exhaust emission control, or noise-abatement.
4. Inlet & Exhaust Pressure Drop [4/5]
Exhaust pressure drop, inH2O
Co
rre
ctio
n f
acto
r1
1.020
1.015
1.010
1.005
0.995
0.990
0.985
0.980
2 3 4 5 6 7 8 9 10 11 12 13 140 15
1.025
1.000
0.975
Thermodynamics 7. Brayton Cycle 80 / 126
MS7001EA 기준
4.0 inH2O (10mbar) inlet pressure drop produces:
1.42% Power output loss
0.45% Heat rate increase
1.1C Exhaust temperature increase
4.0 inH2O (10mbar) Exhaust pressure drop produces:
0.42% Power output loss
0.42% Heat rate increase
1.1C Exhaust temperature increase
Inserting air filter, silencer, evaporative coolers or chillers into the inlet or heat recovery devices in the
exhaust causes pressure losses in the system.
The effects of these pressure losses are unique to each gas turbine models. This is because the amount of
pressure drop at the exit of compressor is pressure drop at the inlet times pressure ratio.
Hot-end drive has not been used since the cold-end drive type gas turbines have developed.
HRSG flue gas draft losses: approximately 25 mbar, 35 mbar if catalysts are required.
4. Inlet & Exhaust Pressure Drop [5/5]
Hot-end drive (“E” technology)
Thermodynamics 7. Brayton Cycle 81 / 126
5. Fuel [1/7]
Fuel affects combined cycle performance in a variety of ways.
Output of the gas turbine can be defined as the product of mass flow, specific heat, and temperature
differential across the turbine. Here, specific heat (cp) means that the heat energy in the combustion
products.
The mass flow in this equation is the sum of compressor air flow and fuel flow.
Natural gas (methane) produces nearly 2% higher output than does distillate oil. This is because of the
higher specific heat in the combustion products of natural gas, resulting from the higher water vapor content
produced by the higher hydrogen/carbon ratio of methane. This effect is noted even though the mass flow of
natural gas is lower than that of distillate oil. Here the effects of specific heat were greater than and in
opposition to the effects of mass flow rate.
4343 TTcmhhmW pT
Model FuelISO base rati
ng, kW
Heat rate,
Btu/kWh
Exhaust flow,
kg/hr x10-3
EGT,
℃Pressure
ratio
PG7251FB
N.G. 184,400 9,245 1613 623 18.4
D.O. 177,700 9,975 1677 569 18.7
Thermodynamics 7. Brayton Cycle 82 / 126
C + O2 = CO2 + 33.9 MJ/kg
H2 + 1/2O2 = H2O(water) + 143.0 MJ/kg (HHV)
H2 + 1/2O2 = H2O(vapor) + 120.6 MJ/kg (LHV)
S + O2 = SO2 + 9.28 MJ/kg
5. Fuel [2/7]
Thermodynamics 7. Brayton Cycle 83 / 126
The Composition of Natural Gases
The composition on a molar basis of natural gases is as follows:
The average heat content of natural gas is 1,030 Btu/ft3 on an HHV basis and 930 Btu/ft3 on
an LHV basis – about a 10% difference.
Composition, mol% A B C D E F
Methane
Ethane
Propane
Isobutane
Normal butane
Isopentane
Normal pentane
Hexane
Nitrogen
Carbon dioxide
Hydrogen sulphide
Heating value, Btu/ft3
95.0
1.9
0.5
0.5
0.1
0.1
0.1
0.1
1.5
0.2
0.0
?
94.3
2.1
0.4
0.0
0.2
0.0
0.0
0.0
0.0
0.0
2.8
1010
72.3
5.9
2.7
0.2
0.3
0.0
0.2
0.0
0.0
17.8
0.1
934
88.9
6.3
1.8
0.1
0.2
0.0
0.0
0.0
0.0
2.2
0.1
1071
75.4
6.4
3.6
0.6
1.0
0.2
0.1
0.0
0.0
12.0
0.1
1044
85.6
7.8
1.4
0.1
0.0
0.1
0.0
0.0
0.0
4.7
0.2
1051
5. Fuel [3/7]
Thermodynamics 7. Brayton Cycle 84 / 126
Plant output and efficiency can be reduced when the fuels containing higher sulfur content are used. This is
because higher stack gas temperature is required to prevent condensation of corrosive sulfuric acid.
Plant output and efficiency can be reduced when the ash bearing fuels (crude oil, residual oil, blends, or
heavy distillate) are used because of fouling occurred in gas turbine and HRSG.
Heavy fuels normally cannot be ignited for gas turbine startup; therefore a startup and shutdown fuel, usually
light distillate, is needed with its own storage, forwarding system, and fuel changeover equipment.
The LHV of the fuel is important because it defines the mass flow of fuel supplied to the gas turbine.
The lower the LHV, the higher the mass flow of fuel required to provide a certain chemical heat input,
normally resulting in a higher power output and efficiency. However, there is no clear relationship between
fuel lower heating value and output.
This is why low BTU gases can result in high power outputs if they are supplied at the pressure required by
the gas turbine.
This effect is noted even though the mass flow of methane is lower than the mass flow of distillate fuel.
Here the effects of specific heat were greater than that of mass flow.
5. Fuel [4/7]
Thermodynamics 7. Brayton Cycle 85 / 126
Ash deposition
on turbine
vanes
5. Fuel [5/7]
Degradation in CCPP after 8,000 hours of operation
Clean fuel Heavy or crude oil
Plant output, % 0.8~1.5 4.0~5.5
Plant efficiency, % 0.5~0.8 1.5~1.9
Thermodynamics 7. Brayton Cycle 86 / 126
Hot corrosion of blades Burned turbine blades
In the past, corrosion is one of the major causes of gas turbine failures.
Corrosion problems have been eliminated by the use of advanced materials and coating.
Whenever heavy fuels are used, particularly those containing vanadium or sodium, it is necessary to use
additives or treat the fuel to prevent high-temperature corrosion.
The additives commonly used are based on magnesium, chromium, or silicon.
5. Fuel [6/7]
Thermodynamics 7. Brayton Cycle 87 / 126
Effects of Fuel Heat Value on Output
As the amount of inert gas is increased, the decrease in
LHV will provide an increase in output.
This is the major impact of IGCC type fuels that have
large amounts of inert gas in the fuel.
This mass flow addition, which is not compressed by the
gas turbine’s compressor, increase the turbine output.
5. Fuel [7/7]
Thermodynamics 7. Brayton Cycle 88 / 126
6. Fuel Heating [1/2]
One way of improving the cycle efficiency is to
raise the apparent LHV (LHV + sensible heat) of
the fuel by preheating it with hot water from the
IP economizer of the HRSG.
Heated fuel gas gives higher turbine efficiency
because of the reduced fuel flow required to
raise the total gas temperature to firing
temperature.
Fuel heating will result in slightly lower gas
turbine output (almost negligible) because of the
incremental volume flow decrease.
The reduction in combined cycle output is
typically greater than simple cycle output
because energy that would otherwise be used to
make steam.
Actual combined cycle output and efficiency
changes are dependent on fuel temperature rise
and cycle design.
G
Fuel gas
ST
Condenser
G
Air
Stack gas
HRSG
Thermodynamics 7. Brayton Cycle 89 / 126
For combined cycle applications, fuel temperatures on the order of 150 to 230°C (300~450°F) are generally
economically optimal.
Provided the fuel constituents are acceptable, fuel temperatures can potentially be increased up to
approximately 370°C(700°F) before carbon deposits begin to form on heat transfer surfaces.
Typical F-class three-pressure reheat systems use water from the intermediate pressure economizer to
heat the fuel to approximately 185°C (365°F). Under this conditions, efficiency gains of approximately 0.3
points can be expected for units with no stack temperature limitations.
Another factor is the gas supply pressure, depended on the combustor design and the gas turbine pressure
ratio.
If the gas turbine pressure ratio is high, a gas compressor may be required to increase fuel pressure. In this
case, the temperature of the fuel is increased in proportion to the pressure ratio and the benefit of gas
preheater will be reduced.
It is important to ensure that the fuel does not enter the steam system because maximum steam
temperatures are typically above the auto ignition temperature for gas fuels.
For a system utilizing a direct water-to-fuel heat exchangers, the water pressure is maintained above the
fuel pressure so that any leakage takes place in the fuel system.
Additional system design and operation requirements ensure that the fuel does not enter the steam system
during periods when the water system is not pressurized.
6. Fuel Heating [2/2]
Thermodynamics 7. Brayton Cycle 90 / 126
7. Steam Injection [1/6]
Effects of Steam Injection on Output and Heat Rate [MS7001EA]
Compressor Inlet Temperature
Options for Power
Enhancements
Performance Impact
Output Heat
Rate
Base configuration Base Base
Evaporative cooling GT inlet air
(85% effective cooler)+5.2 % -
Chill GT inlet air to 45F +10.7 % +1.6 %
GT peak load operation +5.2 % 1.0 %
GT steam injection (5% of GT
airflow)+3.4 % +4.2 %
GT water injection (2.9% of GT
airflow)+5.9 % +4.8 %
HRSG supplementary firing +28 % +9 %
Note: 1. Site conditions = 90F, 30% RH(Relative Humidity)
2. Fuel = NG
3. 3-pressure, reheat steam cycle
Thermodynamics 7. Brayton Cycle 91 / 126
7. Steam Injection [2/6]
Re
lative
po
we
r o
utp
ut, %
Water or steam/fuel ratio,
114
Rela
tive
effic
iency,
%112
110
108
106
104
102
100
98
96
940.5 1.0 1.5
Hot water injection (150C)
0.0
Thermodynamics 7. Brayton Cycle 92 / 126
Diluent injection is accomplished by admitting water or steam in the cap area or head-end of the
combustion liner to reduce the peak flame temperature.
Actually, this has been used for NOx control to meet environmental regulation.
The mass flow passing through the gas turbine increase with the amount of water or steam injection.
Increased mass flow produces higher power output.
Generally, the amount of water is limited to the amount required to meet the NOx abatement in order to
minimize operating cost and impact on inspection intervals.
When steam is injected for power augmentation, it can be introduced into the compressor discharge casing
of the gas turbine as well as combustor.
Normally, gas turbines are designed to allow up to 5% of the compressor airflow for steam injection.
Steam must contain 50F(28C) superheat and be at pressures comparable to fuel gas pressures (at least
40 bar above the compressor discharge).
The way steam is injected must be done very carefully so as to avoid compressor surge.
Gas turbine output and heat rate increase 3.4% and 4.2% respectively, by the steam injection of 5% of the
compressor airflow.
Water or steam injection for emission control or power augmentation can impact parts lives and
maintenance intervals.
7. Steam Injection [3/6]
Thermodynamics 7. Brayton Cycle 93 / 126
The control system on most base load
applications reduces firing temperature as
water or steam is injected. This is known as
dry control curve operation.
The dry control curve operation counters
the effect of higher heat transfer on the gas
side, and results in no net impact on bucket
life.
This is the standard configuration for all gas
turbines, both with and without water or
steam injection.
Dry Control
On some installations, however, the control system is
designed to maintain firing temperature constant with
water or steam injection level. This is known as wet
control curve operation.
The wet control curve operation results in additional unit
output, but decreases parts life.
Units controlled in this way are generally in peaking
applications where annual operating hours are low or
where operators have determined that reduced parts
lives are justified by the power advantage.
Wet Control
An additional factor associated with water or steam injection relates to the higher aerodynamic loading on
the turbine components that results for the injected water increasing cycle pressure ratio.
This additional loading can increase the downstream deflection rate of the second- and third-stage nozzles,
which would reduce repair interval for those components.
7. Steam Injection [4/6]
Thermodynamics 7. Brayton Cycle 94 / 126
EGT Control Curve – MS7001EA
[ Steam Injection for 25 ppm NOx ]
GER-3620K
7. Steam Injection [5/6]
Wet control 3% steam injection
TF = 2020F(1104C)
Load ratio = 1.10
3% steam injection
TF = 1994F(1090C)
Load ratio = 1.08
0% steam injection
TF = 2020F(1104C)
Load ratio = 1.0
EG
T, F
Compressor discharge pressure, psig
Dry control
The wet control maintains
constant TF
Thermodynamics 7. Brayton Cycle 95 / 126
Steam/water injection increases metal temperature of hot-gas-path components in the case
of constant firing temperature operation.
• Water affects gas transport properties:
k – thermal conductivity
cp – specific heat
– viscosity
• This increases heat transfer coefficient, which increases metal temperature and
decreases bucket life
Example (MS7001EA 1st stage bucket):
• 3% steam injection (25 ppm NOx)
• h = +4% (heat transfer coefficient)
• Tmetal = +15F (8C)
• Life = – 33%
7. Steam Injection [6/6]
Thermodynamics 7. Brayton Cycle 96 / 126
8. Air Extraction
Effects of Air Extraction on Output and Heat Rate
In some gas turbine applications, it may be desirable to
extract air from the compressor.
In general, up to 5% of the compressor airflow can be
extracted from the compressor discharge casing without
modification to casings or on-base piping.
Air extraction between 6% and 20% may be possible,
depending on the machine and combustor, with some
modification to the casings, piping and controls.
Air extractions above 20% will require extensive
modification to the turbine casing and unit configuration.
As a rule of thumb, every 1% in air extraction results in a
2% loss in power. Ambient temperature%
Effect
on o
utp
ut
C
F1200 20 40 60 80 100
0 -7 4 16 27 38 49
100
80
60
40
20
0
-20
-40
-60
% E
ffect
on h
eat
rate
20%
15%
10%
5%
5%
10%
15%
20%
Thermodynamics 7. Brayton Cycle 97 / 126
9. Inlet Air Cooling [1/24]
Roughly, 1C temperature decrease corresponds to a combined cycle power increase of about +0.4 to
0.5% and overall efficiency remains more or less same.
Compressor
Fuel gas
pre-heater
Turbine
Fuel oil
Fuel gas
compressor
Fuel oil
treatment
Fuel gas
Water
Evaporative
cooler
or
chiller
Wet compression
(Overspray)
Compressor
washing
Fuel additives
Water
(NOx reduction,
power augmentation)
Cooling air
cooler
Air
Air filter
Drain
Water
Steam
Water
Inlet Fogger
(spray cooler)
Thermodynamics 7. Brayton Cycle 98 / 126
건구온도 vs. 습구온도
상대습도(relative humidity): 공기중에 있는 수증기의 양과 그때의 온도에서 공기중에 최대로 포함할 수 있는 수증기의 양을백분율로 표현한 값.
건구온도(dry bulb temperature): 일반 온도계 측정한 온도.
습구온도(wet bulb temperature): 온도계 아래 부분 동그란 구면을 거즈로 감싸고 거즈의 한쪽 끝을 물이 담긴 그릇에 넣어그릇에서 빨아올린 물이 끊임없이 온도계의 구면에서 증발하도록 한 상태에서 측정한 온도. 물이 증발하면서 기화열을 빼앗아 가기 때문에 건구온도보다 더 낮은 온도를 나타냄.
공기중의 습도가 낮으면 물이 더 많이 증발할 수 있어서 열을더 많이 빼앗아 가기 때문에 건구와 습구온도 차이가 더 커짐.
일반적으로 건구온도와 습구온도 차이에 의해서 습도를 계산.
습도 계산표가 있어서 건구온도와 습구온도를 알면 그 때의 습도를 찾을 수 있음. 대부분 습도 계산표를 이용하여 습도 확인.
[ 습구온도계 ]
9. Inlet Air Cooling [2/24]
Thermodynamics 7. Brayton Cycle 99 / 126
For applications where significant power demand and highest electricity prices occur during the hot summer,
a gas turbine air inlet cooling system is a useful option for increasing power output.
Inlet air cooling increases output because the mass flow rate of air passing through the compressor
increases as air temperature decreases.
A decrease in the inlet dry-bulb temperature by 10F(5.6C) will normally result in around 2.7% power
increase of a combined cycle using heavy-duty gas turbines.
The output of the simple-cycle gas turbines is also increased by the same amount.
There are three basic systems currently available for inlet air cooling.
• The first and perhaps the most widely used system is evaporative cooler. Evaporative coolers use the
high efficiency evaporative media for the evaporation of water to decrease the gas turbine inlet air
temperature.
• The second one is a fogger system, also called as spray cooler. This is classified as evaporative cooling.
• The third system employs various ways to chill the inlet air. In this system, the coolant (usually chilled
water) flows through a heat exchanger located in the inlet duct to remove heat from the inlet air.
Evaporative cooling is limited by the wet-bulb temperature.
Chilling, however, can cool the inlet air to temperature that are lower than the wet-bulb temperature, thus
providing additional output, although chilling is much more expensive.
Depending on the combustion and control system, evaporative cooling may reduce NOx emissions; however,
this is very little because of current dry low NOx technology.
9. Inlet Air Cooling [3/24]
Thermodynamics 7. Brayton Cycle 100 / 126
High efficiency evaporative media
Evaporative Cooler (Wetted Honeycomb Evaporative Coolers)
9. Inlet Air Cooling [4/24]
Thermodynamics 7. Brayton Cycle 101 / 126
Evaporative Cooler (Wetted Honeycomb Evaporative Coolers)
Conventional evaporative coolers use a wetted honeycomb type medium to maximize evaporative surface
area and the cooling effectiveness.
The medium for gas turbines is typically 12 inches thick and covers the entire cross-section of the filter
house or the inlet air duct.
The pressure drop caused by evaporative media and droplet eliminator is 1 inH2O.
9. Inlet Air Cooling [5/24]
Thermodynamics 7. Brayton Cycle 102 / 126
The plant output and efficiency decrease due to this pressure drop.
The reduction in gas turbine and combined cycle output is 0.35% and 0.3%, respectively.
A controller is provided to prevent operation of the evaporative cooler system below 60F(15.6C).
Icing could form if the system is allowed to operate below this temperature.
The whole system must be deactivated and drained to avoid damage to the water tank and piping if the
ambient temperature is expected to fall below freezing.
Evaporative cooling is a cost-effective method to recover capacity during periods of high temperature and
low or moderate relative humidity.
Evaporative cooling works on the principle of reducing the temperature of an air stream through water
evaporation.
The process of converting the water into a vapor state requires energy.
This energy is drawn from the air stream. The result is cooler, denser air.
There are limitations that must be considered for each site condition. The key design parameters are the wet
and dry bulb temperature and the allowable load limits for the generator and the transformer.
At sites where large reductions in the compressor inlet temperature are possible, the owner must verify that
the added power is within the capabilities of the generator and transformer.
Evaporative Cooler (Wetted Honeycomb Evaporative Coolers)
9. Inlet Air Cooling [6/24]
Thermodynamics 7. Brayton Cycle 103 / 126
Evaporative Cooling - Theory
Theoretically, the lowest temperature that can be achieved by adding water to the air is equal to the ambient
wet-bulb temperature.
Practically, however, this level of cooling is difficult to achieve.
The actual temperature drop realized is a function of both the equipment design and atmospheric conditions.
Other factors being constant, the effectiveness of an evaporative cooling system depends on the surface
area of water exposed to the air stream and the residence time.
T means air temperature. Subscripts 1 and 2 refer to inlet and exit of the cooler, respectively. Subscripts DB
and WB refer to ‘dry bulb’ and ‘wet bulb’, respectively.
Temperature drop of the compressor inlet air is proportional to the difference between wet and dry bulb
temperature. If the effectiveness is 85%, the temperature drop is
The effectiveness of evaporative cooler is typically 85% and of foggers somewhat higher at 90 to 95%.
WBDB
DBDB
TT
TTessEffectivenCooler
,2,1
,2,1
WBDB TTdropeTemperatur ,2,185.0
9. Inlet Air Cooling [7/24]
Thermodynamics 7. Brayton Cycle 104 / 126
Psychrometric Chart [습도 선도]
Water
Evaporated
Degrees Cooled
Dry Bulb Temperature
[Solution]
The corresponding wet-bulb
temperature is 70F.
T = 0.85(100-70) = 25F (14C)
[Example 9.1]
Ambient temperature is 100F (37.8C)
and relative humidity is 20%. Calculate
the temperature drop through the cooler.
The effectiveness of the evaporation
system is 85%.
9. Inlet Air Cooling [8/24]
Thermodynamics 7. Brayton Cycle 105 / 126
Evaporative Cooling
Roughly, 1C temperature decrease corresponds to a
combined cycle power increase of about 0.4 to 0.5% and
overall efficiency remains more or less same.
The exact increase in power available from a particular gas
turbine as a result of evaporative cooling depends on the
machine model and site altitude, as well as on the ambient
temperature and humidity.
However, the chart given in the figure can be used to get the
power increase from evaporative cooling.
As would be anticipated, power increase is greatest in hot, dry
weather.
Evaporative cooling is limited to ambient temperatures (15C)
and above (compressor inlet temperature >7.2C) because of
the potential for icing the compressor.
An evaporative cooling does only make sense at locations
with humidity below 70 to 80%.
9. Inlet Air Cooling [9/24]
Thermodynamics 7. Brayton Cycle 106 / 126
Gas turbines have been used foggers, also called as spray coolers, since mid-1980s.
These systems atomize the supply of water into billions of tiny droplets.
The droplets require a certain amount of residence time in the air stream to evaporate. The size of droplet
plays an important role in determining the surface area of water exposed to the airstream and, therefore, to
the speed of evaporation.
The water droplets should be atomized to less than 20 m in foggers.
Fogger
Demineralized water is used
to reduce compressor fouling
or nozzle plugging. However,
it necessitates the use of a
high grade stainless steel for
all wetted parts.
9. Inlet Air Cooling [10/24]
Thermodynamics 7. Brayton Cycle 107 / 126
Fogger - EPRI Spray Nozzle Array
A typical spray-impingement
fog nozzle
Nozzle fog spray pattern
9. Inlet Air Cooling [11/24]
Thermodynamics 7. Brayton Cycle 108 / 126
Two methods are used for water atomization.
The first relies on compressor air in the nozzles to atomize the water.
The second uses a high pressure pump to force the water through a small orifice.
Air-atomized nozzles require less water pressure.
However, they result in low power output due to the air extraction from the gas turbine. An air-atomized
system using compressor discharge air would reduce the power output 1.3% (EPRI, TR-104612).
The typical air-to-water mass ratio is 0.6 (volume ratio is 500).
Some high-pressure pumps use swirlers to break the water into small droplets.
Other force the water on an impingement pin to generate the same effect.
A typical high-pressure pumped fog system has an operating pressure of between 1000 and 3000 psi (6.8
and 20.4 MPa).
Fogger
9. Inlet Air Cooling [12/24]
Thermodynamics 7. Brayton Cycle 109 / 126
Careful application of these systems is
essential, because condensation or
carryover of water can be causes of severe
compressor fouling and performance
degradation.
These systems generally are followed by
moisture separators or coalescing pads to
reduce the possibility of moisture carryover.
More spray flow was removed (~70%) by the
Large Droplet Eliminator than was originally
anticipated (~58%) in the EPRI test (TR-
108057).
Normally, water droplets are agglomerated
by turbulent fluctuations and become large
droplets.
Analysis of the drain water gives some
beneficial air scrubbing effects when the
spray cooler is operating.
Fogger - Large Droplet Eliminator
A large droplet eliminator (LDE) is installed in the in the inlet
housing downstream of the spray nozzle array to remove
large water droplets from the air stream. The modules are
manufactured using polypropylene with sine curve shaped
vanes.
9. Inlet Air Cooling [13/24]
Thermodynamics 7. Brayton Cycle 110 / 126
The power increase from evaporative cooling is about 3.5% for every 10F (5.6C) of cooling.
Evaporative cooling is limited by the difference between the dry bulb and wet bulb temperatures.
If sufficient water can be introduced into the air such that the air becomes fully saturated, the air
temperature will be reduced to the wet bulb temperature.
The amount of cooling is limited by the potential for icing as the air flow speeds up in the bellmouth and the
static air temperature drops.
The icing limit is engine dependent but typically varies from 40F to 50F.
Fogger - Summary of ERPI Test Results
9. Inlet Air Cooling [14/24]
Thermodynamics 7. Brayton Cycle 111 / 126
Evaporative Cooling
Evaporative Cooler Fogger (Spray cooler)
Advantages
• Water quality requirements are less
severe than fogger system.
• Simple and reliable.
• More operating experience.
• Gas turbine inlet pressure drop is lower
than that of evaporative cooler and
provides increased output.
• Higher effectiveness.
• Potential for lower uprate costs and faster
installation time due to reduced duct
modifications compared to evaporative
cooler.
Disadvantages
• Uprates frequently require substantial
duct modifications.
• Higher gas turbine inlet pressure drop
than fogger system degrades output and
efficiency when not in use.
• Lower cooling effectiveness.
• Requires demineralized water.
• Higher parasitic load than evaporative
cooler for high-pressure pumped systems.
• Lower power increase for air-atomized
systems.
• Controls are more complex.
9. Inlet Air Cooling [15/24]
Thermodynamics 7. Brayton Cycle 112 / 126
Compressor Turbine
Overspray (Wet compression)
Water
Evaporative
cooler
or
chiller
Overspray
(wet compression)
Compressor
washing
Cooling air
cooler
Air
Air filter
Drain
Water
Steam
Water
Inlet Fogger
(spray cooler)
• Overspray is defined as the excess spray beyond that
which is required to completely saturate the air.
• As an extension of the fogger system, water droplets
are allowed to enter the compressor and evaporation
takes place within the compressor.
• Droplets are evaporated inside the compressor to give
evaporative intercooling effect.
Overspray
9. Inlet Air Cooling [16/24]
Thermodynamics 7. Brayton Cycle 113 / 126
LM6000 Sprint
Overspray
GER-3620K
Overspray (Wet compression)
• The power increase resulting from overspray is about
5% for every 1% overspray (overspray water mass is
expressed as a percentage of inlet air mass).
• The amount of overspray will depend on ambient
conditions.
9. Inlet Air Cooling [17/24]
Thermodynamics 7. Brayton Cycle 114 / 126
Overspray
GER-3620K
9. Inlet Air Cooling [18/24]
Thermodynamics 7. Brayton Cycle 115 / 126
There are two types of inlet chilling systems, direct chillers and thermal storage.
Liquefied natural gas (LNG) systems use the cooling generated by the vaporization of liquefied gas in the
fuel supply.
Thermal storage systems use off-peak power to store thermal energy in the form of ice.
During peak power periods, the ice is used to perform inlet chilling.
Direct chilling systems use mechanical or absorption chillers.
All these options can be installed in new plants or retrofitted in older plants.
The chilling achieved by using cooling coils depends on the design of the equipment and ambient
conditions.
Unlike evaporative coolers, cooling coils are capable of lowering the temperature below the wet-bulb
temperature.
The capacity of the inlet chilling device, the compressor’s acceptable temperature and humidity limits, and
the effectiveness of the coils limit actual reduction in temperature.
Figure illustrates a typical cooling process from an ambient dry-bulb temperature of 100F(37.8C) and 20%
relative humidity.
The initial cooling process follows a line of constant specific humidity.
Chiller
9. Inlet Air Cooling [19/24]
Thermodynamics 7. Brayton Cycle 116 / 126
As the air approaches saturation,
condensation starts to occur.
Additional cooling results in further
condensation.
Mist eliminator should be installed
downstream of coils to prevent
condensed water from entering the
gas turbine.
The air can be cooled below the
ambient wet-bulb temperature.
However, the compressor inlet
temperature should be higher than
45F(7.2C) with a relative humidity of
95%.
Icing will form at lower temperature,
resulting in possible equipment
damage.
Water
Evaporated
Degrees Cooled
Dry Bulb Temperature
Chiller
9. Inlet Air Cooling [20/24]
Thermodynamics 7. Brayton Cycle 117 / 126
Chiller
9. Inlet Air Cooling [21/24]
Thermodynamics 7. Brayton Cycle 118 / 126
Chiller
F-Class gas turbine inlet filter house, showing
installation of chiller coils. Coil manifolds are the
vertical pipes along side the filter house. This filter
house is “passively balanced” with a third “reverse
return manifold”.
Filter houses for chilling applications are much
larger than standard models. A larger “face area”
keeps pressure drop across the coils low. This filter
house also has a symmetrical transition duct that
improves the airflow across the coils.
The fogger systems react to the ambient weather conditions, being limited to the spread between DB and
WB. However, chiller systems break through the WB and dew-point barriers that would limit fogger systems.
The power output enhancement associated with chiller systems can be nearly twice that of the fogger
systems. In addition, temperature of the inlet air can be as constant as possible using chiller systems.
9. Inlet Air Cooling [22/24]
Thermodynamics 7. Brayton Cycle 119 / 126
CaseInlet Air
Cooling
GT Output,
kW (each)
ST Output,
kW (gross)
Auxiliary
Power, kW
Net Plant
Output,
kW
Each GT
Fuel Input,
MMBtu/hr
(LHV)
Total Duct
Burner Fuel
Input,
MMBtu/hr
(LHV)
Net Plant
Heat Rate,
Btu/kWh
(LHV)
1 None 14207 169942 12173 452183 1440.373 0.000 6371
2 Fogger 159850 174642 12489 481853 1531.400 0.000 6356
3 Chiller 173833 178055 19799 505922 1632.324 0.000 6453
4 None 147185 252408 16575 530203 1440.300 654.636 6668
5 Fogger 159831 254283 16839 557106 1531.337 635.466 6638
6 Chiller 173813 255761 24071 579316 1632.256 619.586 6705
7 Chiller 164800 175366 15918 489048 1565.722 0.000 6403
• Model: STAG207FA
• Simulation software: GTPro & GTMaster
• Ambient conditions: 95F (35C), 40% RH
• Effectiveness of fogging system: 95%
• The chiller cools the inlet air temperature down to 50F (10C)
Summary for Performance Simulation Results
9. Inlet Air Cooling [23/24]
Thermodynamics 7. Brayton Cycle 120 / 126
CaseInlet Air
Cooling
Duct
Firing
Net Plant
Output, kW
Incremental Output,
kW
Reference
Cost, M$
Incremental
Cost (to Case 1),
M$
Unit Cost,
S/kW
1 None No 452183 212.4 470
2 Fogger No 481853 29670 6.6% 215.1 2.7 446
3 Chiller No 505922 53739 11.9% 225.3 12.9 445
4 None Yes 530203 78020 17.3% 229.5 17.1 433
5 Fogger Yes 557106 104923 23.2% 231.5 19.0 416
6 Chiller Yes 579316 127133 28.1% 239.9 27.5 414
• All cost figures are provided by Thermoflow’s PEACE costing module.
• This software uses the plant configuration as provided by GTPro.
Summary for Capital Cost Simulation Results
9. Inlet Air Cooling [24/24]
Thermodynamics 7. Brayton Cycle 121 / 126
Some gas turbine models can be operated at a higher firing temperature than their base rating.
This is called peak firing. During the peak firing operation, both simple-cycle and combined-cycle output will
increase.
Peak firing is available to get 3~10% higher output than the output at base load.
Normally, thermal efficiency of the plant is increased during peak firing of gas turbine because of higher
firing temperatures.
This mode of operation results in a shorter inspection interval and increased maintenance.
Despite this penalty, operating at elevated peak firing temperatures for short periods is cost-effective way
for power gain without any additional peripheral equipment.
“Peaking” at 110% rating will increase maintenance costs by a factor of 3 relative to base-load operation at
rated capacity, for any given period.
For an MS7001EA turbine, each hour of operation at peak load firing temperature (+100F/56C) is the
same, from a bucket parts life standpoint, as six hours of operation at base load.
10. Peak Firing [1/2]
Thermodynamics 7. Brayton Cycle 122 / 126
Maintenance Factor
E Class
F ClassE Class
Peak Rating
Life Factor 6x
0 50 100 150
Firing Temperature, F
Ma
inte
na
nce
Fa
cto
r
100
10
6
0
10. Peak Firing [2/2]
Thermodynamics 7. Brayton Cycle 123 / 126
11. Part Load Operation
Load, %30 40 50 60 70 80 90 100
65
60
75
70
85
80
95
90
100
Thermodynamics 7. Brayton Cycle 124 / 126
12. Supplementary Firing in HRSG
It can be used to increase steam turbine capacity by
as much as 100%.
This will increase plant capacity by about 25%.
Cogeneration of power and process steam is usually
the incentive for HRSG supplementary firing.
There is a small performance penalty when operating unfired compared to operating a unit designed without
supplementary firing, and the magnitude of this performance penalty is directly proportional to the amount of
supplementary firing built into the combined-cycle plant.
The performance penalty is due to two factors: unfired operation results in lower steam flows and pressures
and, thus, lower steam turbine efficiency; also, the pumps, auxiliary equipment and generator are sized for
higher loads.
Operating unfired results in comparatively higher parasitic loads compared to a unit designed solely for
unfired operation.
Normally, thermal
efficiency of the plant is
decreased during HRSG
supplementary firing.
Thermodynamics 7. Brayton Cycle 125 / 126
13. Cooling Water Temperature
T
s
2
P4’
1
1
2
3
a b
4
P4
a
4
The end pressure of steam expansion in the turbine is determined by the steam saturation
temperature depending on the cooling water temperature and heat transfer conditions on the
condenser tubes.
Thermodynamics 7. Brayton Cycle 126 / 126
질의 및 응답
작성자: 이 병 은 (공학박사)작성일: 2015.02.11 (Ver.5)연락처: [email protected]
Mobile: 010-3122-2262저서: 실무 발전설비 열역학/증기터빈 열유체기술