6839-00-16-50-sp--43_Ind. light_

download 6839-00-16-50-sp--43_Ind. light_

of 5

Transcript of 6839-00-16-50-sp--43_Ind. light_

  • 7/27/2019 6839-00-16-50-sp--43_Ind. light_

    1/5

    DOCUMENT No.

    6839-00-16-50-SP-43 Rev.0

    SPECIFICATION FOR NON-HAZARDOUS AREA LIGHTINGFIXTURES & JUNCTION BOXES

    Page 1 of 5

    0 28.03.07 ISSUED WITH BID PACKAGE

    Rev.No

    Date PurposePrepared

    byChecked

    byApproved

    by

    Format No. 1641-1924 Rev. 1 Copyright EIL All rights reserved

    SPECIFICATION

    FOR

    NON-HAZARDOUS AREA

    LIGHTING FIXTURES

    &

    JUNCTION BOXES

    B-22 FIELD DEVELOPMENT PROJECT

    OIL AND NATURAL GAS CORPORATION LTD.

  • 7/27/2019 6839-00-16-50-sp--43_Ind. light_

    2/5

    DOCUMENT No.

    6839-00-16-50-SP-43Rev.0

    SPECIFICATION FOR NON-HAZARDOUS AREA LIGHTINGFIXTURES & JUNCTION BOXES Page 2 of 5

    Format No. 1641-1924 Rev. 1 Copyright EIL All rights reserved

    CONTENTS

    SECTION TITLE

    1.0 SCOPE

    2.0 CODES AND STANDARDS

    3.0 SITE CONDITIONS

    4.0 SCOPE OF SUPPLY

    5.0 TECHNICAL REQUIREMENTS

    6.0 TESTING AND INSPECTION

    7.0 VENDOR DATA REQUIREMENT

    8.0 CERTIFICATION

    9.0 PACKING AND TRANSPORTATION

  • 7/27/2019 6839-00-16-50-sp--43_Ind. light_

    3/5

    DOCUMENT No.

    6839-00-16-50-SP-43Rev.0

    SPECIFICATION FOR NON-HAZARDOUS AREA LIGHTINGFIXTURES & JUNCTION BOXES Page 3 of 5

    Format No. 1641-1924 Rev. 1 Copyright EIL All rights reserved

    1.0 SCOPE

    This specification provides the minimum requirements for the design, manufacture,testing and supply of lighting fixtures and junction boxes suitable for installation innon-hazardous areas on offshore platforms.

    2.0 CODES & STANDARDS

    2.1 The equipment supplied shall comply with the requirements of the latest revision ofthe relevant standards of:

    NEC - National Electrical Code

    NEMA - National Electrical Manufacturers Association

    BSI - British Standards Institution.

    ANSI - American National Standards Institute

    BIS - Bureau of Indian Standards

    2.2 Any other recognized international standard or code may be used in lieu of above,subject to approval of the Company.

    3.0 SITE CONDITIONS

    All the equipment shall be suitable for use in extreme, harsh marine environments. Theequipment shall be tropicalised and treated to protect the same against the siteconditions as specified in Specification-Site Conditions and Climate and traces of H2Sfound in the atmosphere, if specified in equipment data sheet.

    All painting shall be in accordance with SpecificationProtective Coating.

    4.0 SCOPE OF SUPPLY

    The scope of supply through this specification includes:

    4.1 Lighting Fixtures.

    4.2 Junction Boxes

    4.3 Cable glands, lugs, plugs etc.

    4.4 Clamps, Brackets etc. for fixture supports.

    5.0 TECHNICAL REQUIREMENTS

    5.1 GENERAL

    5.1.1. All outdoor equipment shall be industrial type and shall have enclosure protection toIP-55 or equivalent.

    5.1.2 All indoor equipment (located in enclosed rooms) shall be industrial/decorative typewith enclosure protection to IP-20, as minimum. They shall be provided withshrouding type terminals/live parts to make them shockproof, while cleaning,relamping, replacement purpose etc.

    5.1.3 The body of the equipment shall be cast metal and shall be free from frictionalsparking hazard. Copper or copper alloy shall not be used for manufacturing of any

    exposed parts.

  • 7/27/2019 6839-00-16-50-sp--43_Ind. light_

    4/5

  • 7/27/2019 6839-00-16-50-sp--43_Ind. light_

    5/5

    DOCUMENT No.

    6839-00-16-50-SP-43Rev.0

    SPECIFICATION FOR NON-HAZARDOUS AREA LIGHTINGFIXTURES & JUNCTION BOXES Page 5 of 5

    Format No. 1641-1924 Rev. 1 Copyright EIL All rights reserved

    5.3 JUNCTION BOXES

    5.3.1 Junction boxes shall be provided with cable termination accessories for connecting

    PVC insulated and sheathed, armoured, copper conductor, FRLS Cables. Minimumnumber of side entries shall be three. Spare plugs shall be provided to block theunused entries.

    5.3.2 Adequate no. of the terminals shall be provided to terminate three cables. Sufficientspace for accommodating specified number of cables and easy access to theirterminals for termination purposes, shall be provided.

    5.3.4 Four lugs shall be provided for mounting of junction box on wall/steel structure withthe help of bolts.

    6.0 TESTING AND INSPECTION

    Testing and inspection of lighting fixtures and junction boxes shall include but notnecessarily be limited to the following:

    A visual inspection shall be made to ensure that the finishing and workmanship areupto the mark.

    Company reserves the right to witness the final testing and inspection. Priorintimation of atleast 20 days shall be given to enable the Company to depute itsrepresentative to witness the test.

    7.0 VENDOR DATA REQUIREMENTS

    7.1 Catalogue, technical literature, drawings giving details of make, catalogue no.,overall dimensions, weight, material of construction and mounting details.

    7.2 Copies of type test certificates.

    8.0 CERTIFICATION

    All offered equipment or equipment of similar design and construction featuresmanufactured by the same vendor:

    - Shall have been type tested by an authority approved by the Company.

    - Shall have been in continuous satisfactory service in offshore for aminimum period two years.

    Shall be having current certification/approval/listing by an agency approvedby Company or UL or FM.

    9.0 PACKING AND TRANSPORTATION

    The offered equipment alongwith their accessories shall be shipped to site packedin wooden crates. They shall be wrapped with polythene sheets, before beingplaced in the crates to prevent damage to finish. Crates shall have skid bottom forhandling.