MASTERCLADTM Medium Voltage

Metal-Clad Switch gear with

Type VR Vacuum Circuit Breakers

SQUARED

GROUPE SCHNElDER

Page 2: 6055 Br 9402
Page 3: 6055 Br 9402

The Reliability of a Quality Design

The quality of Square D MASTERCLADTM medium voltage

metal-clad switch gear stems from a design and manufac-

turing process that focuses on long-term switch gear

performance with the highest degree of reliability.

Reliable performance and safety is enhanced by the

rugged construction of MASTERCLAD switch gear. Each

switch gear assembly consists of individually grounded,

compartmentalized steel structures (with -gauge barriers

between vertical sections and major parts of each primary

circuit) to protect operating personnel.

Based on specific customer application needs, Square D

engineers and technicians select the appropriate standard

sections and bus configurations, with the ability to

customize where needed. After the specified circuit breakers,MASTERCLADswitch gearcomponents includeavailable state-of-the-art electronicslike POWERLOGIC

power monitoringand control systems,

digital microproces-sor-based protectiverelays and SY-MAXPLC-based automaticthrowover systems.

instrument and control power transformers, relays, meters

and other components are selected and approved, all are

factory-assembled, wired and tested as a complete

assembly. This testing is performed to insure reliability

by energizing the control circuits and verifying the specified

sequence of operation for each metal-clad switch gear

project along with the ANSI C37.20.2 Production Tests.

2

Page 4: 6055 Br 9402

ApplicationsMASTERCLAD mediumvoltage switch gear is usedin a wide variety of switch-ing, control and protective

applications includingelectric utility generationand distribution systems,industrial plants, commer-cial buildings, hospitals,municipal pumping stations,wastewater treatment

plants, transportationsystems, and pipelinestations. Transformers,

motors, generators,capacitors, distributionlines, and feeder circuitsare protected by thisclass of switch gear .Significantly, most of theMASTERCLAD switch gearspecified for theseapplications is relied uponto provide the criticalmain service entranceprotection and controls.

Standardization

Standardization of thedesign incorporates aseries of basic modularunits, control packages,and instrumentation. Formost switch gear ratings,circuit configurations andfunctions, one basic sizeunit is used. These features

provide applicationflexibility, versatility,efficiency and economy in

minimizing engineeringtime to plan and layoutthe switch gear .

Ratings:

.4.76-15 kV(to 13.8 kV nominal)

.1200-3000 Amperes

.250-1000 MVA

Interrupting Capacity

.60 and 95 kV BIL

.Indoor and OutdoorEnclosures

Standard Features:

Metal-Clad Switch gear asdefined by ANSI C37.20.2includes:

.Removable (Drawout)Circuit Breaker

.Fully CompartmentedConstruction

.Grounded Metal BarriersEnclose all Live Parts

.Automatic Shutters

.Insulated Bus

.Mechanical Interlocks

.Disconnect Type VoltageTransformers-CPTand VTs

.Grounded BreakerTruck in and betweenTest/Disconnected andConnected Positions

.Low Voltage Instrument/Control CompartmentIsolated from PrimaryVoltage areas

Square D Metal-Clad Switchgear is designed and manufacturedin a facility that is Quality Systems Registered by UnderwritersLaboratQries. Inc. to lSO 9001.

REGISTERED TO = _,CERnFK:ATE 00. A2211

3

Page 5: 6055 Br 9402

with the breaker rackingsystem. These protectivefeatures furnish integrityto the equipment andprovide safety foroperating personnel.

lower cell (indoorswitch gear) without useof any lifting device.A lifting truck is providedfor installation of abreaker into an uppercell. Typical breakerweight is 350480 lbs.Floor Space Economy and

Application FlexibilityThe two tier configurationpermits feeder breakersto be stacked two highto save valuable floorspace, or stacked one highcombined with auxiliaryunits for the ultimate inapplication flexibility.

Convenient Handling

The VR breaker is ahorizontal drawout typedesigned to provide longlife, reduced maintenanceand ease of handling. Thebreaker truck has wheelsfor easy movement into a

ComprehensiveTest Program

A comprehensive designtesting program has beenperformed by Square Ddevelopment engineers. Theswitch gear and breakersare designed and testedin accordance withallapplicable ANSI StandardsC37.04, C37.06, C37.09 andC37.20.2. The switch gearand breakers meet therequirements of ANSI,IEEE, NEMA, and generallyexceed IEC standards.

Features and Benefits

Long Life/MinimumMaintenance

Reliability is the mainpriority. The VR vacuumcircuit breakers aredesigned for long life.The interrupter's copper-chromium contacts,hermetically sealed for lifein a vacuum, are protectedfrom external atmosphericinfluences. Dust, moisture,and all other possiblecontaminants are sealedout. This state-Qf-the-artvacuum interrupter designis capable of 20-100 fullfault interruptions (varies

by rating).

The high dielectric strengthof the vacuum environmentallows a very short clearingtime during fault interrup-tion to limit the energydissipated into the arc.Total fault clearing time isless than 3 cycles andcontact travel is only 3/8 to1/2 inch, depending on theratings of the circuit breaker .The short stroke producesless mechanical shock tothe operating mechanism.

For evaluation of wear onthe main contacts over thelife of the circuit breaker ,contact erosion indicationis provided on each

interrupter pole assembly.

Together with a totalcommitment to quality,these features provide longlife with high reliability.

Rear view/terminationcompartment withincoming line andload bus runbacks.

Safety Barriersand Interlocks

Full compartmentalizationis supplied with primaryfunctions separated bygrounded metal barriers.All bussing is insulated andlive parts are not exposed.Safety interlocks work

4

Page 6: 6055 Br 9402

Hinged Front Door

Relays and metering instru-ments are mounted on thedoors in standardizedarrangements to satisfycustomer requirements.Each breaker compartmentdoor provides a rackingaccess port to allow movingthe circuit breaker to orfrom the connected posi-tion with the door closed.(Option for single full-height door with "one-

high" construction.)

Horizontal DrawoutCircuit Breaker

VR vacuum circuit breakersutilize the horizontaldrawout design. Test/disconnected and connectedpositions are provided.

Control PowerTransfonners

Control power transformersrated up to 15 kV A aredrawer mounted and canbe completely withdrawnfrom the front of theswitch gear for ease ofmaintenance. A secondarycircuit breaker mechanicalinterlock is provided andmust be opened beforethe transformer can bewithdrawn for access toprimary fuses.

Racking System

The high quality gear.<\rivenracking mechanism iscenter-mounted on the cellfloor. providing balancedmovement of the breakerbetween cell positions.The racking system iscoordinated with safetyinterlocks to preventmovement of the breakerunless main contacts are inthe open position.

Voltage Transformers

Front accessible, drawermounted voltage trans-formers can be completelywithdrawn on extensionrails. For operator safety,the voltage transformersare disconnected andgrounded during movementto the withdrawn position.

port with front

door closed.

Square D Metat-Clad Switchgear is designed and manufacturedin a facility that is Quality Systems Registered by UnderwritersLaboratories, Inc. to JSO 9001.

5

Page 7: 6055 Br 9402

Automatic Shutters

When the breaker iswithdrawn from theconnected position, theracking mechanism linkagepositively rotates thegrounded metal shuttersinto a position whichcovers the energized

components.

Cable Space

Top or bottom power cableentry space is provided.The quantity of cabletermination devices andspace for surge arrestersvary with the ratings ofbreakers selected foreach vertical section.

Compartment Barriers

Grounded metal barriersseparate the main com-partments-breaker, main

bus, cable, instrument/relay(low voltage area), and

auxiliary (VT and/or CPT). Frame andHousing

Inter-bayControl Wire

Frame and Housing

Precision-formed steelframes and inner panels,painted by the superiorTGIC Polyester Powder

Coating Process, providea strong rust-resistantstructure with rigidalignment of components.

Cable Space

Main Bus and Insulation

Main bus and rullbacksare insulated with a track-resistant, flame retardantepoxy coating by thefluidized bed process. Bussupport standoff insulatorsare glass polyester at 5 kVand porcelain at 15 kV.Bus joints are insulated byvinyl boots. Access coversare provided for mainbus inspection from frontand rear .

Main Bus Barriers

Main bus barriers betweenbays are track-resistant,flame retardant glass

polyester. Optionalporcelain inserts areavailable with the glasspolyester barriers.

CompartmentBarriers

Insulated

Main Bus

Main BusBarriers

Side view with sidecover sheet removed.

AutomaticShutters

6

Page 8: 6055 Br 9402

.

Control Wiring

Cell switch-T.O.C

Auxiliaryswitch-M.O-C

AuxiliarySwitchActuator

InsulatingBushing AroundStationary MainBus Contact

CurrentTransformers

RackingTrip/SpringDischargeInterlock

Ground Bus

BreakerRating Block

BreakerRemovalLatch Cam

ShutterLockingProvisions-Padlock/KeyInterlock

Breaker

Alignment

Rails

Breaker Compartment Floor Details

(Highlighted View)

BreakerPositionIndicator

-Secondarycontrol plug Control

operating Receptaclehandle usedfor test

position only.

~

SQUARE D COMPANYREGISTERED TO lSO ~1

CERT1FK:ATE NO A2211

"7

Square D Metal-Clad Switchgear is designed and manufacturedin a facility that is Quality Systems Registered by UnderwritersLaborotories, Inc. to /SO 9001.

Page 9: 6055 Br 9402

Control

Self-aligning receptacleautomatically engages thecontrol plug when circuitbreaker is racked to theconnected position.

Both opening and closingsprings are automaticallydischarged when circuitbreaker is removed fromthe compartment. Rackingarm operates linkage onbottom of breaker .

All secondary/controlwiring, including terminalblocks, CT shorting blocks,and other devices arelo<:ated in the instrumentcompartment at the frontof each breaker section,isolated from the primaryvoltage areas. Each sectionhas provisions for controlwiring entry from topor bottom.

Breaker Rating Block

Prevents insertion of abreaker with lower rating,either MVA or continuousarnpacity, than thecompartment is designedto accept.

Cell' T.O-C

(Optional) Stationary-mounted switch, 6 or 10

contacts, provideselectrical indication ofthe position of the circuitbreaker in the cell-connected position or

test/disconnected position.

The breaker cell has slottedalignment rails which cap-ture the breaker rail rollerson each side of the breakerto provide assurance ofbreaker alignment with thecell. Note that the rail rollersare side-mounted anddifferent from the wheelson the breaker truck.

Breaker PositionIndicator

The breaker position,either "connected" or"test/disconnected," isshown by the rotation ofa colored indicator wheeldriven by the rackingmechanism and clearlyvisible with the cell frontdoor either open or closed.

(Optional) Stationary-mounted switch, 6 or 10contacts, maintains thesame position as thebreaker-mounted auxiliaryswitch-indicating breakeropen or breaker closed. Prevents removal of circuit

breaker until handle at bot-tom front of circuit breakeris pulled by the operator .

Provisions ~

The safety shutters maybe locked closed bypadlocking (lor 2) or bykey interlock tu preventinstallation of a circuitbreaker when requiredby customer maintenance

procedures.

(Mounted behind shutters)

Bushing type currenttransformers are frontaccessible-located behindthe shutters (shown inopen position*, in photo atleft) and mounted on the

primary insulating bushings.Space will permit one ortwo current transformerson both sides of eachcircuit breaker-up to fourtotal with ANSI standardrelay accuracy class rating;two maximum with higher

relayaccuracies.

~~ck_ing- Trip

(Shown with currenttransformers)Standard glass polyester(or optional porcelain)insulating bushings are usedto support the primarystationary disconnectmain contacts. The samebushings provide insulatedmounting provisions forthe current transformers.

Maintains breaker trip

position during rackingbetween test and connectedpositions. Racking armoperates linkage on bottomof breaker.

'Note: Shown with shutter bamer removed and shutte13 in theopen position for illustrative purposes only. If access to currenttransforme13 is required, the switchgear must be de-energizedbefore the shutte13 are moved to the open position.

B

Page 10: 6055 Br 9402

The VR circuit breakerwith the Type RI advanced

design motor-<:hargedstored energy mechanismis a model of reliabilitywith simplicity-virtuallymaintenance free. With anoperating life exceedingthe ANSI test requirements,the RI mechanism withsynchronizing crossbaris electrically and

mechanically trip-free.An integral handle (non-removable) is providedfor manual charging and

slow-<:losing during testing.

The VR is

completelytested andcertified toall applicableANSI circuitbreaker

Square D Metal-Clad Switchgear is designed and manufacturedin a facility that is Quality Systems Registered by UnderwritersLaboratories, Inc. to /SO 9001.

~GISTEAEDK TO 190 _,CERTJFK:ATE I«). A2211

9

Page 11: 6055 Br 9402

The vacuum interruptersof the VR circuitbreaker are mounted inhigh-strength, molded

glass-reinforced polyesterinsulation/supporthousings. The moldedhousings position the busrunbacks for precisealignment. The completedpole units are bolteddirectly to the breakertruck. The inherent rigidityand mechanical strength ofthis circuit breaker designcomplement the operatingmechanism, resulting in highendurance and reliability.

10

Page 12: 6055 Br 9402

36"w Sections with Standard Dimensions

Two high feeder section arrangement-1200/1200Aor 1200/2000A. Top or bottom cable entry.

One high (main or feeder) arrangement with auxiliarydrawout units behind the relay/meter door .

Note: For 3000A applications, the compartment abovethe 3000A breaker is blank except for relays, controlswitches, and other instruments.

"

Auxiliary section with up to four drawout units-VTs, CPT (to 15 kV A), primary fuse truck for(rear) fixed-mtd. CPT to 50 kVA-10; 45 kVA-30.

Weights

Section, (less bkr): 2000 Ibs

1200A Breaker: 360 Ibs

2000A Breaker: 410 Ibs

3000A Breaker: 480 Ibs "'Do Not Use for Construction. Dimensions are in Inches.Square D Metal-Clad Switchgear is designed and manufactured

in a facility that is Quality Systems Registered by UndennritersLaboratories, Inc. to ISO .9001.

Page 13: 6055 Br 9402

Insulation LevelRated Withstand

Interrupting Ratings'

Amps. -SymmetricalShort

Time

Rating

3 Sec.

Amps.-

rms

Rated VoltagesNominal Rating Rated

Cont. --

Current Max. Min. Low Impulse Max.

Three Voltage 60 Hertz Voltage Range Voltage Freq. 1.2x50IJ5 kV

Phase kV- Amps.- kV- Factor kV- kV- kV- Amps.-

MVA rms rms rms K rms rms Crest"' rms(j)

Nom.kVAmps.-rms

Min.kVAmps.-rms

Close &

Latch

Rating

Amps.-nns"'Type 01 Breaker

250 I 4.16 I 1200 I 4.76 I 1.24 I 3.85 I 19

19

19

19

19

19

36

36

36

36

36

36

36

36

36

36

36

36

60

60

60

60

60

60

95

95

95

95

95

95

95

95

95

95

95

95

29,000 I 33,200 I 36,000 I 1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

36,000

36,000

48,000

48,000

58,000

77,000

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

VR-O5025-12

VR-Q5025-20

VR-Q5025-30*

VR-Q5035-12

VR-Q5035-20

VR-Q5035-3Q*

VR-Q8050-12

VR-08050-20

VR-08050-30*

VR-15050-12

VR-15050-20

VR-15050-3Q*

VR-15075-12

VR-15075-20

VR-15075-3Q*

VR-15100-12

VR-15100-20

VR-15100-3Q*

29,000 I 33,200 I 36,000 I250 I 4.16 I 2000 I 4.76 I 1.24 I 3.85 I

250 I 4.16 I 3000 I 4.76 I 1.24 I 3.85 I 29,000 I 33,200 I 36,000 I

41,000 I 46,900 I 49,000 I350 I 4.16 I 1200 I 4.76 I 1.19 I 4.0

350 I 4.16 I 2000 I 4.76 I 1.19 I 4.0 41,000 I 46,900 I 49,000 I

41 ,000 I 46,900 I 49,000 II 350 I 4.16 I 3000 I 4.76 I 1.19 I 4.0500 I 7.20 I 1200 I 8.25 I 1.25 I 6.6 33,000 I 37,800 I 41,000 I

500 I 7.20 I 2000 I 8.25 I 1.25 I 6.6 33,000 I 37,800 I 41,000 I

3000 I 8.25 I 1.25 I 6.6 33,000 I 37,800 I 41,000 I500 I 7.20

500 113.8 1200 I 15.0 1.30 111.5 18.000 I 19.500 I 23.000 I

18,000 I 19,500 I 23,000 I500 I 13.8 I 2000 I 15.0 1.30 I 11.5

18,000 I 19,500 I 23,000 I500 113.8 I 3000 I 15.0 1.30 I 11.5

28,000 I 30,400 I 36,000 I750 I 13.8 I 1200 I 15.0 1.30 I 11.5

28,000 I 30,400 I 36,000 1750 113.8 I 2000 I 15.0 1.30 I 11.5

750 113.8 I 3000 I 15.0 1.30 I 11.5 28,000 I 30,400 I 36,000 I

37,000 I 40,200 I 48,000 I1000 113.8 I 1200 I 15.0 1.30 I 11.5

1000 113.8 I 2000 I 15.0 1.30 111.5 37,000 I 40,200 I 48,000 I

37,000 I 40,200 I 48,000 I1000 113.8 I 3000 I 15.0 1.30 111.5

* Availability to be announc,

Rating

(i) These values apply with circuitbreaker in or out of enclosure.

@ Rated Short Circuit Current(at rated Max kV).

@ Rating factor is based onbreaker speed from initiation oftrip signal to contact parting,allowing for 1/2 cycle relay time.To obtain the asymmetricalcurrent interrupting capacityof the breaker, multiply thesymmetrical current by 1.2.

@ Close and Latch Rating(Momentary) Amps rms = (1.6K)

(Rated Short Circuit Current).Additional Close and Latch Ratingin kA Crest = (2.7K) (Rated Short

Circuit Current).

12

Asym-

metrical

Rating

Factor"

Inter-

rupting

Time

Cycles

Page 14: 6055 Br 9402

The (indoor) (outdoornon-walk-in) (outdoorwalk-in) Metal-CladSwitch gear described inthis specification isintended for use on a(2400) (4160) (4800) (6900)(13800) volt 3-phase (3)( 4) wire (grounded)(ungrounded) 60 Hertzsystem. The switch gearshall be rated (4160) (7200)(13800) nominal voltsand have VR horizontaldrawout circuit breakers.

The switch gear and circuitbreakers, individually andas a unit, shall have a BIL(impulse) rating of (60)(95) kV. The momentaryrating of the switch gearbus shall be equal to theclose and latch rating ofthe circuit breakers. Theentire switch gear assemblyincluding circuit breakers,meters, relays, etc., shallbe completely factorytested and the circuitbreakers of like ratingsshall be interchangeable.

(Clamp type cable lugs)

(potheads) (Cableterminators) shall befurnished as shown onplans. The copper groundbus shall extend throughthis compartment for thefull length of the switch gear .

The switch gear shallconsist of -sectionsincluding -breakercompartments and -auxiliary compartmentsassembled to form a rigid,self-supporting, completelyenclosed structure provid-ing steel barriers betweensections. The sections aredivided by metal barriersinto the following separatecompartments: circuitbreaker, instrument, mainbus, auxiliary device, andcable. Each section mayhave up to two breakercompartments.

The main bus is to be rated(1200) (2000) (3000) amperesand be fully insulated forits entire length with anepoxy coating by thefluidized bed process.The conductors are to be(aluminum with tin-platedjoints) (copper withsilver-plated joints) and beof a bolted (not welded)design. Access to thiscompartment is gainedfrom the front or rear ofthe structure by removinga steel barrier. Bus supportstandoff insulators shall beglass polyester at SkV andporcelain at lSkV. Busjoints shall be insulatedwith vinyl boots.

Each circuit breaker cellcompartment shall bedesigned to house a VRhorizontal drawout (4160)(7200) (13800) volt vacuumcircuit breaker. Thestationary primarydisconnecting contacts areto be silver-plated copperand mounted within glasspolyester support bushings.The movable contacts andsprings shall be mountedon the circuit breakerelement for ease ofins pection/maintenance.

Entrance to the stationaryprimary disconnecting con-tacts shall be automaticallycovered by metal shutterswhen the circuit breaker iswithdrawn to the test ordisconnected positions orremoved from the circuitbreaker compartment.

The metal shutters shallbe operated by directmechanical linkage tothe floor-mounted rackingmechanism. Extend aground bus into the circuitbreaker compartment toautomatically ground thebreaker frame when inthe test and connectedpositions with high-currentspring type groundingcontacts located on thebreaker chassis. Slottedguide rails for positioningthe circuit breaker and allother necessary hardwareare to be an integral partof the circuit breakercompartment. The circuitbreaker rail rollers shall beheld captive on both topand bottom by the slottedguide rails to provideassurance of breakeralignment with the cell,while preventing verticalmovement of the breakertruck during normaloperation and under shortcircuit conditions. Abreaker position indicatorC"connected" or "test/disconnected") shall bedriven by the rackingmechanism and be visiblewith the front door eitheropen or closed. Blockingdevices shall interlockbreaker frame sizes toprevent installation of alower ampere rating orinterrupting capacity ele-ment into a compartmentdesigned for one of ahigher rating. It shall bepossible with indoor oroutdoor walk-in switch gearto install a circuit breakerinto a bottom compartmentwithout use of a transporttruck or lift device.

The switch gear covered bythis specification shall bedesigned, tested, andassembled in accordancewith the applicablestandards of ANSI/IEEEand NEMA.

Square D Metal-Clad Switchgear is designed and manufacturedin a facility that is Quality Systems Registered by Underwrite~Laboratories, Inc. to /SO 9001.

13

Page 15: 6055 Br 9402

Finish

After pretreatment to forma primer coating of zincphosphate on the metal,finish coating shall be an

electrostatically appliedTGIC polyester powderpaint. The process shall bedesigned to withstand atleast 2500 hours of saltspray as tested per ASTMB-117 and ASTM 0-1654.Switch gear finish to belight gray ANSI #61.

InstrumentTransformers

Current transformers: eachbreaker compartment shallhave provision for front-accessible mounting of upto four current transformersper phase, two on bus sideand two on cable side ofcircuit breaker. The currenttransformer assemblyshall be insulated for thefull voltage rating of theswitch gear. Relaying andmetering accuracy shallconform to ANSI standards.

Voltage transformers aredrawout mounted with

primary current-Iimitingfuses and shall haveratio as indicated. Thetransformers shall havemechanical rating equal tothe momentary rating ofthe circuit breakers andshall have metering accuracyper ANSI standards.

Doors and Panels -Indoor and Outdoor

Relays, meters, controlswitches, etc., shall bemounted on a formedfront-hinged panel foreach circuit breakercompartment. In addition,outdoor sections, NEMA 3Rnon-walk-in, have full-heightweatherproof front doorwith 3-point latch. Indoorsections to be furnishedwith two screw-removablerear panels. Outdoorsections to be furnishedwith full-height rear-

hinged panels.

Accessories

Standard accessoriesshall be furnished withthe switch gear, including:

Manual charging/slowclose handle (on frontof each breaker.)

Manual racking crankhandle (one per lineup.)

Optional Accessories:Test cabinet, test cablewith jack and plug, Sthwheel, breaker lift truck* ,manual ground and testunit (MGTU), automatic/el ectri cally-o peratedground and test unit (AGTU),and remote racking motor .

Control Wiring

The switch gear shall bewired with Type 515 #14AWG, except #12 AWG forcurrent transformerswiring. The switch gearshall be provided withterminal blocks for out-going control connections.

Circuit Breakers

The VR circuit breakersshall be rated (4160) (7200)(13800) nominal volts, 60

Hertz, (1200) (2000) (3000)amperes and an interruptingclass rating of (250) (350)(500) (750) (1000) MV A withone vacuum interrupterper phase. Breakers ofequal rating shall be

completely interchangeable.The circuit breaker shallbe operated by means of astored energy mechanismwhich is normally charged

by a universal motor, butcan also be charged by theintegral handle for manualemergency closing ortesting. The closing speedof the moving contacts isto be independent of boththe control voltage and theoperator. Provide a fullfront shield on the breaker .Positive contact secondarydisconnect shall bethrough automaticself-aligning, self-engagingtype plug and contactarrangement. Provisionshall be made for controlpower plug to be manuallyconnected in test position.A minimum of 4 auxiliarycontacts (2a, 2b) shall beprovided for external use.Provisions shall be madefor (6) (10) additionalcell-mounted auxiliarycontacts (M-a-C type) ( and)cr -a-C type) for external use.

An interlocking systemshall be provided to makeit impossible to rack aclosed circuit breaker toor from any position. Anadditional interlock shallautomatically dischargethe stored-energy operatingmechanism springs uponremoval of the breakerfrom the compartment.

The circuit breaker controlvoltage shall be:

(48) (125) (250) volts DC

(120) (230) volts AC

For further informationabout Square DMASTERCLAD Switch gearwith Vacuum or SFGCircuit Breakers, contactyour nearby Square Dsales office. They areconveniently located inover 200 cities throughoutthe world to serve you.

'The lift InIck is provided for indoor and outdoor walk-inswitchgear with upper compartment breaker cells. The liftInIck is a/so provided for all outdoor non-walk-in switchgear toinstall breakers over the base channels.