5.Energy Audit of CW System.ppt
Transcript of 5.Energy Audit of CW System.ppt
-
7/28/2019 5.Energy Audit of CW System.ppt
1/39
ENERGY AUDIT OF CONDENSER AND
CONDENSER COOLING WATER
SYSTEM
Presented ByM.V.Pande
Dy.Director
NPTI, Nagpur
-
7/28/2019 5.Energy Audit of CW System.ppt
2/39
Background
Condenser:The condenser is the most important component of the turbine cycle that
affects the turbine heat rate. The function of the condenser is to
condense exhaust steam from the steam turbine by rejecting the heat of
evaporation to the cooling water passing through the condenser.
Generally, twin shell- double pass- surface type condensers areemployed for higher capacity units
CW Pump
Hot Water
Condenser
Cooled
Water
Cooling
Tower AirAir
Make-up
Water
Hot
Water
-
7/28/2019 5.Energy Audit of CW System.ppt
3/39
Background
Cooling towers:
Different types of
cooling towers are
used in the power
plants depending upon
the location, size,
infrastructure andwater resources etc.
Close cycle wet
cooling systems:
-Induced draft
-Forced draft
- Natural draftcooling
towers
-
7/28/2019 5.Energy Audit of CW System.ppt
4/39
Background
Cooling water pumps:
Circulating water pumps supply cooling water at therequired flow rate and pressure to the power plant
condenser and the plant auxiliary cooling water heat
exchangers. These pumps are required to operate
economically and reliably over the life of the plant.
For once through systems, vertical wet pit pumps are in
common usage.
For re-circulating cooling systems, vertical wet pit and
horizontal dry pit are used about equally, with occasional
use of vertical dry pit pumps.
-
7/28/2019 5.Energy Audit of CW System.ppt
5/39
Specifications of Typical Cooling Water Pump
-
7/28/2019 5.Energy Audit of CW System.ppt
6/39
Steps Involved in Energy Audit
The major energy consuming equipments in the CW
systems are:
Cooling towers and fans
Cooling water pumps
Make up water pumps
Condensers
The steps involved in conducting energy audit of cooling
water and cooling tower are:
Data collection Observations and Analysis
Exploration for energy conservation measures
Report preparation
-
7/28/2019 5.Energy Audit of CW System.ppt
7/39
Data Collection
Specifications of cooling towers:
-
7/28/2019 5.Energy Audit of CW System.ppt
8/39
Data Collection
Specifications of cooling towers- contd:
-
7/28/2019 5.Energy Audit of CW System.ppt
9/39
Specification of water pumps and motors:
Specification of water pumps and motors
-
7/28/2019 5.Energy Audit of CW System.ppt
10/39
Specification of water pumps and motors- contd:
Data Collection
Rated kW of the pump
-
7/28/2019 5.Energy Audit of CW System.ppt
11/39
Data Collection- Other Information
Performance characteristics of all pumps and motors
Compile design, P. G. Test, previous best and last energy
audit value with respect to cooling tower and cooling water
system along with the condensers
If the pumps are operated in parallel then it is advised to
collect the performance curve for the parallel operation
Schematic diagram of Water pumping network (which
depict the source, pumps in operation & stand by, line sizes
and users)
Water and pressure equipments at the users as per the
design requirements
Brief description of the system with the key specifications in
which pumps are used (for example, if pumps are used for
supplying water to condenser, then add a brief write up
about the cooling water system)
-
7/28/2019 5.Energy Audit of CW System.ppt
12/39
Data Collection- Condenser Specifications
Heat load considered for design
Design inlet cooling water temperature/ Design TTD
Cleanliness factor/ Cooling water temperature raise
Condenser back pressure
Cooling water flow/ Cooling water side pressure drop
No of cooling water pass/ Total heat transfer area
No. of tubes - Condensing zone - Air cooling zone
Tube dimensions: - Tube OD x thickness - Length of
tube
Tube material: - Condensing zone - Air cooling zone
Water box design pressure
-
7/28/2019 5.Energy Audit of CW System.ppt
13/39
Instruments Required
Power Analyzer: Used for measuring electricalparameters of motors such as kW, kVA, pf, V, A andHz
Temperature Indicator & Probe
Pressure Gauge: To measure operating pressureand pressure drop in the system
Stroboscope: To measure the speed of the drivenequipment and motor
Ultra sonic flow meter or online flow meter
Sling hygrometer or digital hygrometer Anemometer
In addition to the above calibrated online instrumentscan be used
PH meter
-
7/28/2019 5.Energy Audit of CW System.ppt
14/39
Measurements & Observation Energy consumption pattern of pumps and cooling tower
fans
Motor electrical parameters (kW, kVA, Pf, A, V, Hz, THD)for pumps and cooling tower fans
Pump operating parameters to be measured/monitored foreach pump are: - Discharge, - Head (suction & discharge) -
Valve position Temperature - Load variation, Powerparameters of pumps - Pumps operating hours andoperating schedule
Pressure drop in the system (between discharge and userpoint)
Pressure drop and temperatures across the users (heatexchangers, condensers, etc)
Cooling water flow rate to users - Pump /Motor speed
Actual pressure at the user end
User area pressure of operation and requirement
-
7/28/2019 5.Energy Audit of CW System.ppt
15/39
Measurements & Observation
Cooling tower parameters to be monitored
Inlet temperature
Outlet temperature
Dry bulb temperature
Wet bulb temperature or relative humidity
Water flow to cooling towerAir flow rate of cooling tower
Range, oC
L/G ratio
Approach, oC
Fan speed, rpm
Fan power consumption (kW/cell)
-
7/28/2019 5.Energy Audit of CW System.ppt
16/39
Observations and Analysis
System familiarization and operational details
Energy consumption Pattern
The energy consumption of cooling water : kWh/day and
associated system
Total auxiliary power consumption : kWh/Day
O ti Effi i d P f
-
7/28/2019 5.Energy Audit of CW System.ppt
17/39
Operating Efficiency and Performance
Evaluation of the Pumps
Water flow rate and pressure of pumps / headers
Velocity in the main headers and pumps and major lines (to
verify adequacy of line sizes)
Power consumption of pumps (for estimating the operating
efficiency of the pumps) Monitor present flow control system and frequency of
control valve variation if any (for application of variable
speed drives)
Fill up the following data sheet for every pump forcomparison with the design / PG test values
Operating Efficiency and Performance
-
7/28/2019 5.Energy Audit of CW System.ppt
18/39
Operating Efficiency and Performance
Evaluation of the Pumps
Operating Efficiency and Performance
-
7/28/2019 5.Energy Audit of CW System.ppt
19/39
Operating Efficiency and Performance
Evaluation of the Pumps
-
7/28/2019 5.Energy Audit of CW System.ppt
20/39
Investigations & Recommendations Compare the actual values with the design / performance
test values if any deviation is found, investigate for the
contributing factors and arrive at appropriate suggestions The investigations for abnormality are to be carried out for
problems. Enlist scope of improvement with extensivephysical checks / observations.
Based on the actual operating parameters, enlistrecommendations for action to be taken for improvement, ifapplicable such as
Replacement of pumps/ Impeller replacement/ trimming
Variable speed drive application, etc
Compare the specific energy consumption with similar typeof pumps and latest energy efficient pumps
Cost analysis with savings potential for taking improvementmeasures.
-
7/28/2019 5.Energy Audit of CW System.ppt
21/39
Flow Distribution
Measure the flow at the individual pump discharge side,
main header, at the users (for the major and large users) along with the
pressure and
velocity. Depict these values in schematic diagram
Ensure Line adequacy by measuring the velocity in themajor pipe lines
Pressure drop in the distribution network
Specific water flow rate
-
7/28/2019 5.Energy Audit of CW System.ppt
22/39
CONDENSERS
-
7/28/2019 5.Energy Audit of CW System.ppt
23/39
Performance of Condensers
Parameters for condenser performance
-
7/28/2019 5.Energy Audit of CW System.ppt
24/39
Performance of Condensers
Parameters for condenser performance- contd
-
7/28/2019 5.Energy Audit of CW System.ppt
25/39
Performance of Condensers
The following needs to be computed:
1. Condenser heat load = Q x T x Cp
Parameter Details Unit
Q Water flow rate Kg/h
T Average CW temperature rise oC
Cp Specific heat kcal/kg oC
2. Calculated condenser vacuum =
Atmospheric pressure Condenser back-pressure
3. Deviation in condenser vacuum =Expected condenser vacuum - Measured condenser vacuum
4. Condenser TTD =Saturation temperature Cooling water outlet temperature
-
7/28/2019 5.Energy Audit of CW System.ppt
26/39
Performance of Condensers
5. Condenser Effectiveness =
Rise in cooling water temperature
Saturation temperature - Cooling water inlet temperature
6. Condenser heat duty in kcal/h =
Heat added by main steam + heat added by reheater + heat
added by SH attemperation + heat added by RHattemperation + heat added by BFP - 860 x (Pgen + Pgen
losses + heat loss due to radiation)
7. Condenser tube velocity (m/s) =
Cooling water flow rate (m3/h) x 106
3600 x tube area (mm2) x ( no. of tubes per pass - no. of
tubes plugged per pass )
-
7/28/2019 5.Energy Audit of CW System.ppt
27/39
Performance of Condensers
8. Determination of actual LMTD
Tsat - ToutLn
LMTD =
Tout - Tin
Tsat -Tin
9. LMTD expected = LMTD test x ft x fw x fq
(Saturation Temperature during test LMTD during test
Saturation Temperature design LMTD design)ft=
0.25
fw = Tube velocity during test Tube velocity design( )0.50
fq = Condenser design duty
Condenser duty during test( )
fw: correction forwater flow rate
fq: correction for
cooling water heat load
ft: Correction for cooling water inlet temperature
-
7/28/2019 5.Energy Audit of CW System.ppt
28/39
Observations During Condenser Energy Audit Tubes in operation Vs total installed
Cleaning system operation
Filtering system for cooling water Regular monitoring system for performance
Comparison of LMTD, TTD, heat load, condenser vacuum, flow,temperatures, pressures with design / PG test- arriving the factorscausing deviation
Modifications carried out in the recent past Cooling water flow
Pressure drop on water side and choking
Affect of present performance of cooling tower
Accurate metering of vacuum
Absolute back pressure deviation from expected value Sub cooling of air steam mixture and condensate
Circulation water temperature raise
Effectiveness of cleaning the tubes
Circulating water velocity in tubes
-
7/28/2019 5.Energy Audit of CW System.ppt
29/39
COOLING TOWERS
-
7/28/2019 5.Energy Audit of CW System.ppt
30/39
Performance of Cooling Towers
-
7/28/2019 5.Energy Audit of CW System.ppt
31/39
Performance of Cooling TowersWhile conducting the cooling tower, visual observations
need to be made with respect to:
Adequate water level in the trough Cross flow air from other cooling towers (which are under
maintenance)
Nozzle condition and operation
Fill condition Change of blade angles during change of seasons
The CT airflow shall be measured using an anemometerand compared with calculated airflow derived from fan
characteristic curves of CT fans with actual powermeasurements.
Calculate range, approach, L/G (Liquid to gas) ratio andeffectiveness for design and operating conditions for eachtower
-
7/28/2019 5.Energy Audit of CW System.ppt
32/39
Performance of Cooling Towers
1. C.T. Range = Water inlet temperature Water outlet temp.
2. C.T. Approach = Water outlet temperature Wet bulb temp.
3. Effectiveness % = Range x 100( range + approach )
Fan actual airflow (Nm3) / cell =
Fan rated airflow (Nm3) / h x ( Fan input kW actual )
( Fan input rated )
1/3
1/3
4.
5. Air mass flow / cell = flow x density of air
-
7/28/2019 5.Energy Audit of CW System.ppt
33/39
Performance of Cooling Towers
5. Evaporation losses =CW flow (m3/ h) x CT range in 0C
675
6. Makeup water consumption = Evaporation losses(COC 1)
The above readings may be taken on daily basis for three
days on different atmospheric conditions say during mid
summer, winter & monsoon period. Once in the mid day and
once in the mid night time and a record duly maintained.
Collect unit load (MW), frequency, and condenser vacuum
condition while taking the cooling tower measurement
-
7/28/2019 5.Energy Audit of CW System.ppt
34/39
Performance of Cooling Towers
Power consumption of CT fans
Exploration of Energy Conservation Possibilities:
Condenser Possibility of Improvement in condenser vacuum
Turbine heat rate Reduction possibilities
Improving the effectiveness of condenser and TTD Cooling water flow adequacy and flow optimization
Air ingress
Increasing the TTD of the condenser
-
7/28/2019 5.Energy Audit of CW System.ppt
35/39
Exploration of Energy Conservation Possibilities
Water pumping and cooling tower
Improvement of systems and drives Use of energy efficient pumps Correcting inaccuracies of the Pump sizing / Trimming of impellers Use of high efficiency motors
Integration of variable speed drives into pumps: The integration ofadjustable speed drives (VFD) into compressors could lead toenergy efficiency improvements, depending on load characteristics
High Performance Lubricants: The low temperature fluidity and hightemperature stability of high performance lubricants can increaseenergy efficiency by reducing frictional losses
Improvements in condenser performance Improvement in cooling tower performance Application potential for energy efficient fans for cooling tower fans Measuring and tracking system performance
-
7/28/2019 5.Energy Audit of CW System.ppt
36/39
Exploration of Energy Conservation Possibilities
Measuring water use and energy consumption is essentialin determining whether changes in maintenance practices
or investment in equipment could be cost effective
In this case it is advised to monitor the water flow rate andcondenser parameters, cooling tower parameters
periodically i.e. at least once in a three months and energyconsumption on daily basis. This will help in identifying the -
- Deviations in water flow rates
- Heat duty of condenser and cooling towers
- Measures to up keep the performance
-
7/28/2019 5.Energy Audit of CW System.ppt
37/39
Exploration of Energy Conservation Possibilities
System Effect Factors
Equipment cannot perform at its optimum capacity if fans,
pumps, and blowers have poor inlet and outlet conditions
Correction of system effect factors (SEFs) can have asignificant effect on performance and energy savings
Elimination of cavitation: Flow, pressure, and efficiency arereduced in pumps operating under cavitation. Performance
can be restored to manufacturers specifications through
modifications. This usually involves inlet alterations and
may involve elevation of a supply tank
f C
-
7/28/2019 5.Energy Audit of CW System.ppt
38/39
Exploration of Energy Conservation Possibilities
Internal Running Clearances: The internal runningclearances between rotating and non-rotating elements
strongly influence the turbo machine's ability to meet ratedperformance. Proper set-up reduces the amount of leakage
(re-circulation) from the discharge to the suction side of the
impeller
Reducing work load of pumping: Reducing of obstructionsin the suction / delivery pipes thereby reduction in frictional
losses. This includes removal of unnecessary valves of the
system due to changes. Even system and layout changes
may help in this including increased pipe diameter.Replacement of components deteriorated due to wear and
tear during operation, modifications in piping system
-
7/28/2019 5.Energy Audit of CW System.ppt
39/39