575 Series - Motor Reversing Contactor 2X 3PST, 30 Amp Section_Motor_2020.pdfMar 05, 2020  · 575...

2
575 Series - Motor Reversing Contactor 2X 3PST, 30 Amp GENERAL SPECIFICATIONS (@ 25° C) Contacts: Contact Configuration Contact Material Contact Rating 120 / 240VAC Resistive Motor 120VAC 1 Phase Motor 240VAC 1 Phase Motor 240VAC 2-3 Phase Motor 480 / 600VAC 2-3 Phase Contact Resistance, Initial Coil: Coils Available Nominal Coil Power Input Voltage Tolerance - AC Input Voltage Tolerance - DC Drop-out voltge Duty Timing: Operate Time (max) Release Time (max) Dielectric Strength: Across Open Contacts Between Mutally Insulated Points Insulation Resistance Temperature: Operating Storage Life Expectancy: Electrical (full load operations) Mechanical (no load operations) Miscellaneous: Mounting Position Enclosure Weight 3PST-NO Double Make per side Silver alloy 30 Amp 1.5Hp 3Hp 5Hp 7.5Hp 100milliohms max @ 6VDC AC and DC 22VA 10W 85% to 110% of nominal 80% to 110% of nominal 10% of nominal Continuous 60mS 30mS 2500 VRMS 2500 VRMS 1000 Megohms @ 500 VDC -34 to 74°C (-30 to 165°F) -40 to 105°C (-40 to 221°F) 100,000 1,000,000 Vertical, Contacts Up Semi-Enclosed 42.0oz (1.1 Kg) The 575 series relay is rated to 7.5HP. Two sets of 3 pole, double-make, N.O. contacts are mechanically interlocked to prevent simultaneous closure. Front mounted auxiliary contacts are available for electrical lockup. The 575 motor revering contactor is widely used for control of overhead doors, elevators, hoists, machine tools, and others similar devices that requires frequent jogging. E13224 1/2 www.struthers-dunn.com (843) 346-4427 575 Wire Diagram 6 2 3 1 4 5 7 8 9 252808 3/5/2020

Transcript of 575 Series - Motor Reversing Contactor 2X 3PST, 30 Amp Section_Motor_2020.pdfMar 05, 2020  · 575...

Page 1: 575 Series - Motor Reversing Contactor 2X 3PST, 30 Amp Section_Motor_2020.pdfMar 05, 2020  · 575 Series - Motor Reversing Contactor 2X 3PST, 30 Amp Ordering Code 575 KXX 90 -24VAC

575 Series - Motor Reversing Contactor 2X 3PST, 30 Amp

GENERAL SPECIFICATIONS (@ 25° C)Contacts:Contact ConfigurationContact MaterialContact Rating 120 / 240VAC Resistive Motor 120VAC 1 Phase Motor 240VAC 1 Phase Motor 240VAC 2-3 Phase Motor 480 / 600VAC 2-3 PhaseContact Resistance, Initial

Coil:Coils AvailableNominal Coil PowerInput Voltage Tolerance - ACInput Voltage Tolerance - DCDrop-out voltgeDuty

Timing:Operate Time (max)Release Time (max)

Dielectric Strength:Across Open ContactsBetween Mutally Insulated PointsInsulation Resistance

Temperature:OperatingStorage

Life Expectancy:Electrical (full load operations)Mechanical (no load operations)

Miscellaneous:Mounting PositionEnclosureWeight

3PST-NO Double Make per sideSilver alloy

30 Amp1.5Hp3Hp5Hp

7.5Hp100milliohms max @ 6VDC

AC and DC22VA 10W

85% to 110% of nominal80% to 110% of nominal

10% of nominalContinuous

60mS30mS

2500 VRMS2500 VRMS

1000 Megohms @ 500 VDC

-34 to 74°C (-30 to 165°F)-40 to 105°C (-40 to 221°F)

100,0001,000,000

Vertical, Contacts UpSemi-Enclosed42.0oz (1.1 Kg)

The 575 series relay is rated to 7.5HP. Two sets of 3 pole, double-make, N.O. contacts are mechanically interlocked to prevent simultaneous closure. Front mounted auxiliary contacts are available for electrical lockup. The 575 motor revering contactor is widely used for control of overhead doors, elevators, hoists, machine tools, and others similar devices that requires frequent jogging.

E13224

1/2 www.struthers-dunn.com (843) 346-4427

575 Wire Diagram

6

2 31

4 5

7 8 9

252808

3/5/2020

Page 2: 575 Series - Motor Reversing Contactor 2X 3PST, 30 Amp Section_Motor_2020.pdfMar 05, 2020  · 575 Series - Motor Reversing Contactor 2X 3PST, 30 Amp Ordering Code 575 KXX 90 -24VAC

Sec

tion

3

575 Series - Motor Reversing Contactor 2X 3PST, 30 Amp

Ordering Code 575 KXX 90 -24VAC

Series 575

Contact Arrangement KXX (2X 3PST – N.O. – double make) Optional Features 1 Auxiliary contacts each SPDT - CODE 90

Coil Voltage AC: 12, 24, 120, 240, 550 (Add VAC)DC: 12, 24,48,115-125, 240 (Add VDC)

Max Outline DimensionsDimensions Shown in inches & (millimeters)

AC Coil, 50/60HZ DC CoilNominal Resistance Nominal Nominal Resistance Nominalvoltage ohms current voltage ohms current ±10% (Amp) ±10 (Amp) 12 1 1.833 12 16.5 0.72724 5.3 0.917 24 58.2 0.412*120 92 0.183 **120 1450 0.083240 420 0.920 240 4,200 0.055440 2100 0.050 - - -550 3100 0.040 - - -

Note: *AC coil is 120, 50/60HZ**DC coils 115VDC

Coil Specifications

3.46(87.8)

1.64(42.9)

2.5(63.5)

4.75(120.4)

5.3(134.62)

Motor Relays 15 - 75 Amp

2/2www.struthers-dunn.com (843) 346-4427

4.43(112.5)

UP

RecommendedMounting Position .88

(22.4)