Partial Discharge Diagnostics on
Switchgears
Dipl.-Ing. Falk-Rüdiger Werner
Doble Lemke, Germany

Partial Discharge Diagnostics on Power Transformers
Contents
2
1. Introduction
2. PD Detection Principles on Switchgears
3. PD Measurements on Switchgears
4. Summary of PD Solutions for Switchgears

Partial Discharge Diagnostics on Power Transformers
1. Introduction
3
Why online PD diagnostics on
switchgears?
• Risk assessment
• Health assessment under online conditions
• No downtimes
• Detection of problems at an early stage
• Planning of maintenance work
• To ensure safe operation and to prolong the asset‘s
liftetime
1.1 Why online PD diagnostics on switchgears?

Partial Discharge Diagnostics on Power Transformers
1. Introduction
4
Why online PD diagnostics on switchgears?
1.1 Why online PD diagnostics on switchgears?

Partial Discharge Diagnostics on Power Transformers
1. Introduction
Partial Discharges in Gases:
Corona discharge
Sharp edges
Conductors with too small
diameter
Sharp edged particles
Surface discharges
Generally faced problem
Countermeasures
• Capacitive potential grading at bushings
• Geometric field grading at terminations
• Prolongation of leakage distance and hydrophobic surfaces on
insulators
5
[Küchler, 1996]
Thin WireSharp Edge Particle
Glow discharges Streamer Discharges
Arrangements for Surface Discharges
1.2 PD Fault Scenarios

Partial Discharge Diagnostics on Power Transformers
1. Introduction
Defects in the dielectric causing PD:(solid insulation systems)
Voids, cavities
Cracks
Delaminations
6
Voids without (1) or
with (2) electrode contact
and delamination (3)
Cable with Termination
(1) Voids through treeing
(2) Voids at boundary surface
Cracks, Gaps and
uncompleted Layers
Delamination at staple
boundary surfaces
1.2 PD Fault Scenarios

Partial Discharge Diagnostics on Power Transformers
1. Introduction
7
Cause of Fault
• 20% Free particles and alien objects
• 18% Shielding and electrostatitic contacts
• 11% Poor contacts
• 7% Moisture
• 5% Protrusions, particles on HV
Fault Distribution (CIGRE JWG 33/23.12)• 41% Switching Compartements: Circuit breakers
• 17% VTs, Surge Arrestors , Bushings
• 42% others…
1.2 PD Fault Scenarios

Partial Discharge Diagnostics on Power Transformers
1. Introduction
8
1.2 PD Fault Scenarios

Partial Discharge Diagnostics on Power Transformers
2. PD Detection Principles on Switchgears
9
2.1 PD Detection Principles
PD Detection Principles
Acoustic
• Ultrasonic
transducers
UHF/VHF/RF
• UHF antenna
• UHF coupler
• TEV Sensor
IEC 60270
• Standard measurement
circuit

Partial Discharge Diagnostics on Power Transformers
2. PD Detection Principles on Switchgears
10
2.2 PD measurement according to IEC 60270
Impedance in Series to Ck
DUT
• Connection to conductor required (coupling capacitor, bushing)
• Mainly used for air insulated switchgears

Partial Discharge Diagnostics on Power Transformers
2. PD Detection Principles on Switchgears
11
Apparent Charge Information
2.2 PD measurement according to IEC 60270

Partial Discharge Diagnostics on Power Transformers
2. PD Detection Principles on Switchgears
12
2.3 Acoustic PD Detection
Acoustic Partial Discharge Detection Acoustic signal as a result of the pressure
build-up caused by the generated spark
in the insulation
Frequency spectrum 10 Hz up to 300 kHz
Different wave types
(longitudinal and transversal waves)
with different propagation velocities
Measurement Technique Microphones and ultrasonic directional
microphones
Sound sensors, accelerometers and piezo-electric converters

Partial Discharge Diagnostics on Power Transformers
2. PD Detection Principles on Switchgears
13
2.4 UHF PD Detection
Spacer
external sensor
ultra wide band
inductive coupler
external sensor
acoustic coupler
internal sensor
capacitive (sensor
external sensor
window sensor
standard coupling
capacitance

Partial Discharge Diagnostics on Power Transformers
2. PD Detection Principles on Switchgears
14
2.4 UHF PD Detection
Transient electromagnetic waves (TEM, TE and TM modes)
generated by partial discharges
Frequency range 300 MHz to 3 GHz
Measuring technique
Narrow band-bandwidth appr. 5 MHz
Wide band-frequency range 300 MHz to 1,5 GHz
In 420 kV plants – upper critical frequency 1 GHz
In 123 kV plants – upper critical frequency 1,5 GHz
UHF – Partial Discharge Detection

Partial Discharge Diagnostics on Power Transformers
3. PD Measurement on Switchgears
15
3.1 GIS Commissioning Test
(1) Resonance test set connected via bushings, (2) Sensors,
(3) PD Detector, (4) Sensitivity Check

Partial Discharge Diagnostics on Power Transformers
3. PD Measurement on Switchgears
16
3.1 GIS Commissioning Test, Noise Properties
Comparison of IEC60270 and UHF decoupling in terms of noise supression
UHF decouplong at 770 MHz,
background noise: 9mV (baseline)
No noise
IEC 60270 compliant measurement,
noise by testset (1) and external
noises (2)

Partial Discharge Diagnostics on Power Transformers
3. PD Measurement on Switchgears
17
No apparent charge information
- Detection and classification only
3.1 GIS Commissioning Test, Noise Properties

Partial Discharge Diagnostics on Power Transformers
3. PD Measurement on Switchgears
18
3.2 Acoustic PD Measurement
DFA100 acoustic PD measurement
device with piezo electric sensor

Partial Discharge Diagnostics on Power Transformers
3. PD Measurement on Switchgears
19
Acoustic PD measurements on GIS:1. Selection of one measurement point per chamber
2. At long chambers, one measurement point every
2-3 meters
3.2 Acoustic PD Measurement

Partial Discharge Diagnostics on Power Transformers
3. PD Measurement on Switchgears
20
3.2 Acoustic PD Measurement

Partial Discharge Diagnostics on Power Transformers
4. Summary of PD Solutions for Switchgears
21
PD Solutions
Acoustic UHF/VHF/RF
LDS-6/UHF, PD-Smart/UHF
• Sensitive PD detection
• PD Classification
PD-Guard/UHF
• Monitoring
IEC 60270
LDS-6, PD-Smart
• Factory tests
• Commissioning tests
DFA100
• PD location and
detection
• PD Classification

Partial Discharge Diagnostics on Power Transformers 22
Thank you for your attention