4.Control Relays
Transcript of 4.Control Relays
control relays
control relays
3
Control relaysFunctions
• Phase control relays (series RF): three phaseelectronic relays to protect against phase failure,reverse sequence, voltage changes and phase unbalance.
• Level controllers (series HN): electronic level controllers for non inflammable conductive liquids.
• Alternating relays (series AR): electronic alterna-ting relays with 2 and 3 outputs by external inputsignal.
• Multi-voltage multi-function timers (series TM):functions selected by rotary switch or lateral DIPswitch.
According to standards
• EMC directive (89/336EEC)• IEC 60255-6 • IEC 61000-6-2• IEC 61000-6-3
General characteristics
• modular housing: 1, 2 and 4 modules width• DIN rail mounting• wide range of supplies
phase control relays
4
RF
RF011: Phase Failure and Phase Sequence Relay• Voltage monitoring relay for three phase supply.• Protects against Phase Failure (loss) and Phase Sequence.
• mounting on symmetrical DIN rail• connects when detecting: - 3 phases
- a correct phase sequence RST presence• trips when detecting: - a phase failure
- an incorrect phase sequence• phase failure is considered when nominal voltage is < 85% rated • output changeover relay 5A / 250V AC cos ϕ = 1• operating temperature: -10º to + 60ºC
RF01: Phase Failure and Phase Sequence Relay
Characteristics
• mounting on symmetrical DIN rail• connects when detecting: - 3 phases presence
- a correct phase sequence RST presence• trips when detecting: - a voltage drop < 25%
- an incorrect phase sequence• phase failure is considered when nominal voltage is < 75% rated• output changeover relay 8A / 250V AC cos ϕ = 1• operating temperature: -10º to + 60ºC
Characteristics
• Voltage monitoring relay for three phase supply.• Protects against Phase Failure (loss) and Phase Sequence.
output
output
Signalling• supply green LED on• incorrect phase sequence red LED on• phase failure all LED off
output
RF01-400
RF011
phase control relays
5
RF
Signalling• supply green LED on• incorrect phase sequence red LED on• phase failure all LED off
RF01A: Adjustable Phase Failure and PhaseSequence Relay• Electronic relay for three phase supply monitoring and protecting
against disturbances on the main supply.• Protection against Phase Failure (loss) and Phase Sequence.• Undervoltage adjustable.
• mounting on symmetrical DIN rail• adjustable phase failure tripping • connects when detecting: - 3 phases
- a correct phase sequence RST presence• trips when detecting: - a voltage drop under the preset voltage
- an incorrect phase sequence• detection of phase failure under preset value
RF01A-230: adjustable from 150V to 250VRF01A-400: adjustable from 300V to 440V
• output changeover relay 8A / 250V AC cos ϕ = 1• operating temperature: -10º to + 60ºC
Characteristics
description width (modules) reset time voltage reference17,5 mm (1) 0,1 sec. 208-480V AC RF01135 mm (2) 0,1 sec. 230V RF01-230
Phase failure andsequence
35 mm (2) 0,1 sec. 400V RF01-40035 mm (2) 0,1 sec. 230V RF01A-23035 mm (2) 0,1 sec. 400V RF01A-400
Phase failure andsequence adjustable
RF01A diagram
RF01A-400
phase control relays
6
RF
*A: immediate. (0,1 sec. approx.)*B: 3 minutes continuous input voltage within threshold.
RF03: Phase Failure, Sequence and Unbalance Relay• Electronic relay for three phase supply monitoring and protecting
against disturbances on the main supply.• Protection against Phase Failure (loss), Phase Sequence and Phase
unbalance.
• mounting on symmetrical DIN rail• connects when detecting: - 3 phases within the set voltage
- a correct phase sequence RST presence• trips when detecting: phase failure, incorrect phase sequence,
phase unbalance• tripping time delay adjustable against short time voltage variations • phase unbalance adjustable threshold (5 to 15%) • output changeover relay 8A / 250V AC cos ϕ = 1• operating temperature: -10º to + 60ºC
Characteristics
RF02: Phase Failure, Sequence and Voltage monitoring Relay• Electronic relay for three phase supply monitoring and protecting
against disturbances on the main supply.• Protection against Phase Failure (loss), Phase Sequence and Over/under
voltage.
• mounting on symmetrical DIN rail• connects when detecting: - 3 phases within the set voltage
- a correct phase sequence RST presence• trips when detecting: phase failure, incorrect phase sequence,
voltage variations• adjustable threshold (5 to 20%) for voltage variations (from 0,1 to 10 seconds)• output changeover relay 8A / 250V AC cos ϕ = 1• operating temperature: -10º to + 60ºC
Characteristics
DiagramsRF02 diagram RF03 diagram
35 mm (2) B 230V RF02-23035 mm (2) B 400V RF02-400
Phase failure, sequenceand voltage monitoring
35 mm (2) A 230V RF02I-23035 mm (2) A 400V RF02I-400
35 mm (2) B 400V RF03-400Phase failure, sequenceand phase unbalance
description width (modules) reset time* voltage reference
35 mm (2) A 400V RF03I-400
t1 = tripping time voltage variations = 0,1-10s. t2 = reset time voltage failure = 3 min.
t1 = tripping time phase unbalance = 0,1-10s. t2 = reset time phase unbalance = 3 min.
RF03
RF02
alternating relays
7
AR
AR01: Alternating Relay • Electronic relay designed to alternate 2 different outputs (pumps,
compressors...) controlled by an external signal.• Alternates cyclically between 2 outputs.
Characteristics• real changeover relay to alternate cyclically and to avoid short-cycling• when the device is receiving no external signal, both changeover contacts will
remain open• mounting on symmetrical DIN rail• output changeover relay 8A / 250V AC cos ϕ = 1 • output contacts (1,3,4,6) voltage free• operating temperature: -10º to + 60ºC
AR02: Simultaneous Alternating Relay • Electronic relay designed to alternate 2 different outputs (pumps,
compressors...) controlled by an external signal.• Alternates cyclically between 2 outputs.• Possible operation of both outputs at the same time (simultaneous).
Characteristics• real changeover relay to alternate cyclically and to avoid short-cycling• when the device is receiving no external signal, both changeover contacts will
remain open• mounting on symmetrical DIN rail• output changeover relay 8A / 250V AC cos ϕ = 1 • output contacts (1,3,4,6) voltage free• operating temperature: -10º to + 60ºC
signal lev. cont. / press. sw.
outputpump 1
outputpump 2
signal lev. cont. / press. sw. 1
outputpump 1
signal lev. cont. / press. sw. 2
Diagrams
AR01 diagram
AR02 diagram
level control relay / AR01 diagram connection
level control relay / AR02 diagram connection
outputpump 2
AR01
AR02
alternating relays
8
AR
35 mm (2) 24V AC AR03-24ACSimultaneous alternatingrelay (3 outputs)
description width (modules) voltage supply reference35 mm (2) 220-240V/380-415V AC AR0135 mm (2) 24V AC AR01-24AC
Alternating relay
35 mm (2) 220-240V/380-415V AC AR0235 mm (2) 24V AC AR02-24AC35 mm (2) 220-240V/380-415V AC AR03
Simultaneous alternatingrelay (2 outputs)
AR03: Simultaneous Alternating Relay - 3 outputs• Electronic relay designed to alternate 3 different outputs (pumps,
compressors...) controlled by an external signal.• Alternates cyclically between 3 outputs.• Possible operation of all 3 outputs at the same time (simultaneous).
Characteristics
Signalling• relay on red LED on
• real changeover relay to alternate cyclically and to avoid short-cycling• when the device is receiving no external signal, all changeover contacts will
remain open• mounting on symmetrical DIN rail• output changeover relay 8A / 250V AC cos ϕ = 1• output contacts (1 to 6) voltage free• operating temperature: -10º to + 60ºC
AR03 diagram
level control relay / AR03 diagram connection
AR03
level control relays
9
HN
Characterisitics• mounting on symmetrical DIN rail• output changeover relay 2A / 240V AC cos ϕ = 1• protection up to 5000V peak (1,2-50 µs) in voltage supply and
probes against lightning disturbances on the supply• operating temperature: -10º to + 60ºC
HN12: Single Level Control Relay• Electronic modular relay for the automatic control of conductive liquids
in a single tank. • Adjustable sensitivity, either well or tank.• Monitoring of filling (up) or empting (down).
HN22: Double Level Control Relay • Electronic modular relay for the automatic control of conductive liquids
in two different tanks. • Two independent adjustable sensitivities, for well and tank.• Monitoring of filling (up) or empting (down).
Both functions combined for monitoring the pumping out of a well and filling of a tank.
Characterisitics• mounting on symmetrical DIN rail• output changeover relay 2A / 240V AC cos ϕ = 1• protection up to 5000V peak (1,2-50 µs) in voltage supply and
probes against lightning disturbances on the supply• operating temperature: -10º to + 60ºC
HN12
HN22
level control relays
10
HN
HN12A: Single Level Control Relay with 3 intermediate levels• Electronic modular relay for the automatic control of conductive liquids
in a single tank. • Adjustable sensitivity, either well or tank.• Monitoring of filling (up) or empting (down).
Characterisitics• mounting on symmetrical DIN rail• output changeover relay 2A / 240V AC cos ϕ = 1• protection up to 5000V peak (1,2-50 µs) in voltage supply and
probes against lightning disturbances on the supply• operating temperature: -10º to + 60ºC
Characterisitics• plug-in base mounting (11 pin)• mounting options: on symmetrical DIN rail
panel mounting with one screw DIN 963, M4panel mounting with two screws and two nuts, M3
• protection up to 5000V peak (1,2-50 µs) in voltage supply and probes against lightning disturbances on the supply
• output changeover relay 2A / 240V AC cos ϕ = 1• operating temperature: -10º to + 60ºC
HN1P: Single Level Control Relay• Electronic modular relay for the automatic control of conductive liquids
in a single tank. • Adjustable sensitivity, either well or tank.• Monitoring of filling (up) or empting (down).
HN12A
HN1P
level control relays
11
HN
* higher sensitivity long distances.
Double level controlrelay
description voltage supply reference230V-400V AC well or tank HN1P230V-400V AC well or tank HN1PLD*
Single level controlrelay
230V-400V AC well and tank HN2P
24V AC well and tank HN22-24ACDouble level controlrelay
description voltage supply reference230V-400V AC well or tank HN12230V-400V AC well or tank HN12A
Single level controlrelay
24V AC well or tank HN12-24AC12V DC well or tank HN12-12DC
230V-400V AC well and tank HN22
Signalling• supply green LED on• output relay connected red LED on• HN12A: yellow level LED on
4 modules width
2 modules width
HN2P: Double Level Control Relay• Electronic relay for the automatic control of conductive liquids in two
different tanks. • Two independent adjustable sensitivities, for well and tank.• Monitoring of filling (up) or empting (down).
Both functions combined for monitoring the pumping out of a well and filling of a tank.
Characterisitics• plug-in base mounting (11 pin)• mounting options: on symmetrical DIN rail
panel mounting with one screw DIN 963, M4panel mounting with two screws and two nuts, M3
• protection up to 5000V peak (1,2-50 µs) in voltage supply and probes against lightning disturbances on the supply
• output changeover relay 2A / 240V AC cos ϕ = 1• operating temperature: -10º to + 60ºC
HN2P
control relays
12
Dimensions
• 1 module width17,5 mmDIN rail mounting
• 2 modules width35 mmDIN rail mounting
• 4 modules width70 mmplug-in on 11 pin baseDIN rail or panel mounting
TM
13
multi-voltage multi-function timer
Equal cycling, ON cycle firstSupply voltage is on. When making “Start” the output relay will energize duringthe set timing period. A cyclic mode does continue with de-energizing and ener-giznig periods according to the set timing. Timer will reset to zero when supplyis removed.
On delaySupply voltage is on. Set delay time starts when “Start” signal is on. Outputrelay energizes after the timing period. Reset to zero occurs when disconnec-ting supply or after a new “Start” connection when the time cycle is finished.
Interval timerSupply voltage is on. When connecting “Start” the output relay energizes, afterthe timing period output relay de-energizes. Reset to zero occurs when discon-necting supply or after a new “Start” connection when the time cycle is finished.
Interval on Make/BreakSupply voltage is on. When making or breaking “Start” output relay energisesuntil set time is reached. Any signal change in “Start” will reset timing to zero.
Off DelaySupply voltage is on. When connecting “Start” output relay energises. When“Start” breaks timing period will start. At the end of timing period output relaywill de-energize. When “Start” breaking occurs during timing period timer illreset timing to zero.
Equal cycling, OFF cycle firstSupply voltage is on. When making “Start” the output remains de-energizedduring the set timing period. A cyclic mode does continue with energizing andde-energizing periods according to the set time. Timer will reset to zero whensupply is removed.
supply
output
timing
supply
output
timing
supply
output
timing
supply
output
timing
supply
output
timing
supply
output
timing
Multifunctional Timer TM01• Multi-voltage and multi-function timer with four basic operational
functions and six selectable time ranges by frontal rotary selector.
• working temperature: -10º + 55ºC• supply: 24-230V AC, 50/60Hz - 24V DC• power consumption: 1,7W / 3VA• output changeover relay AC1: 5A, 250V
DC1: 5A, 24VAC15: 3A, 250VDC13: 2A, 24V
Characteristics
• 1S (from 0,1 sec. to 1 sec.) • 10M (from 1 min. to 10 min.)• 10S (from 1 sec. to 10 sec.) • 1HOUR (from 10 min. to 1 hour)• 1M (from 0,1 min. to 1 min.) • 10HOURS (from 1 hour to 10 hours)
Time ranges
• mounting on symmetrical DIN rail• connection with protected wire clamps
Assembly
• 2 indicating LED for ouput relay and operation status• elapsed time indication by blinking LED
Signalling
Operational Functions
description width (modules) voltage supply reference17,5 mm (1) 24-230V AC TM0117,5 mm (1) 12V DC TM01-12DC
Multifunctional timer
TM01
17,5 mm (1) 127V DC + 20% TM01
TM
14
multi-voltage multi-function timer
Cycling Timer TM02• Multi-voltage and multi-function timer with three operating modes
by lateral DIP and six time ranges by frontal rotary selector.
• working temperature: -10º + 55ºC• supply: 24-230V AC, 50/60Hz - 24V DC• power consumption: 1,7W / 3VA• output changeover relay AC1: 5A, 250V
DC1: 5A, 24VAC15: 3A, 250VDC13: 2A, 24V
Characteristics
Time ranges
• mounting on symmetrical DIN rail• connection with protected wire clamps
Assembly
Signalling
Function C: Asymmetrical cycling, OFF/ONWhen supply voltage is on the 1st timing period (T1) starts. After finishing the first periodoutput relay energizes and the 2nd timing period (T2) starts. After finishing the secondperiod output relay de-energizes until the supply is removed.
supply
output
timing 1
timing 2
Function ModesFunction A: Asymmetrical re-cycling, OFF cycle first
Function B: Asymmetrical re-cycling, ON cycle first
Function C: Asymmetrical re-cycling, OFF/ON
supply
output
timing 1
timing 2
supply
output
timing 1
timing 2
Function A: Asymmetrical re-cycling, OFF cycle firstWhen supply voltage is on, set delay time (T1) starts. Output relay energizes whenreaches T1 then starts the 2nd timing. Output relay (T2) de-energizes after the timingperiod the cycle re-starts. T1 and T2 are regulated independently. Timer will reset to zerowhen supply is removed.
Function B: Asymmetrical re-cycling, ON cycle firstWhen supply voltage is on set delay time starts the 1st timing preiod, otuput is energized.When the time cycle (T1) is finished output relay T2 energizes and starts the 2nd timingperiod. When the time cycle (T2) is finished the cycle re-starts. T1 and T2 areregulated independently. Timer will reset to zero when supply is removed.
Operational Functions
• 1S (from 0,1 sec. to 1 sec.) • 10M (from 1 min. to 10 min.)• 10S (from 1 sec. to 10 sec.) • 1HOUR (from 10 min. to 1 hour)• 1M (from 0,1 min. to 1 min.) • 10HOURS (from 1 hour to 10 hours)
• 2 indicating LED for ouput relay and operation status• elapsed time indication by blinking LED
description width (modules) voltage supply reference17,5 mm (1) 24-230V AC TM0217,5 mm (1) 12V DC TM02-12DC
Cycling timer
TM02
gave electro, s.a.paratge Coll-Blanc, s/n08430 La Roca del VallèsBarcelona - Spain
phone. +34 93 842 48 87fax. + 34 93 842 27 [email protected]://www.gave.com
11/2
005